Heronhill - for all your Airking requirements Installation Instruction 40101102-09 Page 1 of 6. CWD FAN COIL UNIT INSTALLATION CWD fan coil units are designed to be installed within a ceiling void. Air discharge should be via insulated ducting, connected to 200mm diameter spigots (250mm diameter spigots also available) and to appropriately sized discharge plenums/grilles. Ducting and discharge facilities are supplied by others and are not included with the fan coil units. Similarly, return air arrangements, via ducting or to the ceiling void, must also be provided. The installer must ensure that the mounting suspension points are capable of supporting the operating weight of the unit, (refer to the table below). UNIT FIXING If a condensate pump kit is used it should be fitted prior to hanging the unit and connecting the pipework. 1. Before lifting the unit into position, mark out the four outer fixing points as shown below, and fit suspension rods of appropriate length and diameter, (minimum recommended thread size M8). Two inner, central fixing points are available for installer convenience. DO NOT lift the unit by its spigots, drain tray or electrics box when raising it into position. MODEL 25 A 463 B 785 G H J K OPERATING WEIGHT (kg) PIPE CONNECTIONS ( mm OD) No. OF OUTLETS MINIMUM No. OF OUTLETS TO BE USED C CRS D CRS E CRS F 427 344 688 260 332 130 195 195 22 15 15 15 15 15 3 (A,C,E) 1 W X Y Z DRAIN TRAY 45 733 785 697 344 688 260 342 130 195 195 33 15 15 15 15 15 4 (A,B,D,E) 2 65 1103 785 1067 344 688 260 352 130 195 195 44 22 22 15 15 15 4 (A,B,D,E) 2 95 1383 785 1347 344 688 260 392 120 205 205 56 22 22 15 15 15 5 3 105 1383 785 1347 344 688 260 392 120 205 205 58 22 22 15 15 15 5 3 115 1383 785 1347 344 688 260 392 120 205 205 59 22 22 15 15 15 5 3 165 1383 835 1347 394 738 315 392 130 205 195 86 22 22 15 15 15 5 3 175 1383 835 1347 394 738 315 392 130 205 195 86 22 22 15 15 15 5 3 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807 Heronhill - for all your Airking requirements Installation Instruction 40101102-09 Page 2 of 6. 2. Lift the unit into position and secure with appropriate fixings (as shown). The use of lock nuts will stabilize the unit. NOTE: The drain tray is designed with a natural fall to ensure complete drainage. It is essential, for the correct operation of the condensate removal system, that the unit is square and level. RETURN AIR PLENUM When installing a unit fitted with a return air plenum, there are eight fixing points as shown below. The centre fixings must always be used to support the weight of the unit correctly, (refer to the table below). MODEL A B C D E CRS CRS CRS F G H J K OPERATING WEIGHT (kg) PIPE CONNECTIONS ( mm OD) W X Y Z DRAIN TRAY No. OF OUTLETS MINIMUM No. OF OUTLETS TO BE USED 25 463 1076 427 344 981 260 332 421 486 486 26 15 15 15 15 15 3 (A,C,E) 1 45 733 1076 697 344 981 260 342 421 486 486 39 15 15 15 15 15 4 (A,B,D,E) 2 65 1103 1076 1067 344 981 260 352 421 486 486 52 22 22 15 15 15 4 (A,B,D,E) 2 3 95 1383 1076 1347 344 981 260 392 411 496 496 66 22 22 15 15 15 5 105 1383 1076 1347 344 98 260 392 411 496 496 68 22 22 15 15 15 5 3 115 1383 1076 1347 344 981 260 392 411 496 496 69 22 22 15 15 15 5 3 165 1383 1126 1347 394 1031 315 392 421 496 486 96 22 22 15 15 15 5 3 175 1383 1126 1347 394 1031 315 392 421 496 486 96 22 22 15 15 15 5 3 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807 Heronhill - for all your Airking requirements Installation Instruction 40101102-09 Page 3 of 6. PIPE CONNECTIONS A. Connect the flow and return pipework as indicated in the diagrams and tables on the two previous pages. It is recommended that compression fittings are used for ease of installation B. If using compression fittings, two spanners should be used when tightening to prevent twisting and damage to the coil terminals. C. Coil pipe connections are:Chilled water: Models 25 and 45: 15mm OD: Models 65 to 175: 22mm OD LPHW: All models: 15mm OD D. When making the condensate drain connection, use a flexible or compression connector to allow removal of the drain tray for cleaning and maintenance. The condensate outlet connection is 15mm OD. ELECTRICAL CONNECTIONS, CONTROLS and DATA Mains, control and interconnecting cables must be supplied and fitted by the installer. Installer wiring must be carried out in accordance with local and national codes. Cables must be size compatible with the recommended fuse for a given system. An isolator switch should be positioned within easy reach of the unit. If slave units are connected to a standard unit, isolation of any slave MUST also isolate the standard unit. The equipment MUST be earthed. Cable glands suitable for stranded cables are supplied and should be used to secure all cables. Installers must supply a method of securing any solid sheathed cable. CWD UNIT WIRING Remove the electrics box cover (2 screws) and connect a suitably fused and isolated mains supply. Site fitted controls should be connected as specified on the wiring diagram found on the inside face of the electric box cover: typical wiring diagrams are shown on pages 5 and 6, but these are for reference only as many CWD units have a unique congiguration CWD Maximum Running Current in Amps (At 230 V, 50 Hz). Model 25 45 65 95 105 115 165 175 Standard 0.4 0.6 0.7 0.8 0.8 0.8 1.9 2.1 With Electric Htg 4.4 8.6 10.7 16.8 16.8 16.8 18.2 18.8 RECOMMENDED FUSE SIZES (Amps) Model 25 45 65 95 105 115 165 175Stand With Electric Htg 10 10 16 20 20 20 25 25 DUCTWORK Connect discharge ductwork to the spigots provided. Spigot positions are shown below. Spigots are designed to accept 200mm diameter ducting (250mm diameter spigots are available as an option). The installation engineer must ensure that insulated ducting is used and that the complete spigot exterior is insulated up to the unit casing to prevent condensation forming. Tel: 01823 665660 B C MAXIMUM No. OF SPIGOTS MINIMUM NUMBER OF SPIGOTS REQUIRED FRONT SIDES CWD A 25 195 --- --- 1 2 1 45 184 476 --- 2 2 2 65 322 708 --- 2 2 2 95 270 655 1040 3 2 3 105 270 655 1040 3 2 3 115 270 655 1040 3 2 3 165 270 655 1040 3 2 3 175 270 655 1040 3 2 3 www.heronhill.co.uk Fax: 01823 665807 Heronhill - for all your Airking requirements Installation Instruction 40101102-09 Page 4 of 6. Installation of a Remote Controller Select a position to mount the thermostat taking into account the following comments: a. The thermostat must be mounted on a flat surface within the area conditioned by the unit to which it is connected. b. Avoid draughts, heat from radiators, temperature variations from hot/cold water pipes and direct sunlight. c. Avoid corners of the room where air is likely to stagnate. d. Avoid direct air discharge from the unit onto the thermostat. e. Avoid positions where the thermostat may be covered or obscured. f. If the room contains pillars, mount on the side of the pillar furthest away from the unit. If thermostat 97200211 (RCC 30) is used:The thermostat should be wired with 7 core double insulated cable, 0.5mm2 minimum, preferably in plastic conduit for good appearance. Using a flat-bladed screwdriver in the slot at the bottom of the casing, lever off the cover. Mount the backpanel directly to a wall or onto a plinth, using the fasteners supplied. Wire between the remote controller and the unit as shown on the unit wiring diagram: the table below is typical only: OPERATION RETURN AIR MAX MED MIN RCC 30 B1, M NEUTRAL LIVE N L HEAT COOL Y11 Y21 Q3 Q2 Q1 Typical CWD 25 *97200212 N L 9 7 5 3 1 Typical CWD 45-115 *97200212 N L 9 7 5 3 1 Typical CWD 165 *97200212 N L 9 7 5 3 1 Typical CWD 175 *97200212 N L 9 7 6 4 2 *Optional return air sensor 97200212 can detect return air temperature at the unit rather than the controller. DIP switches at the bottom rear of the controller can be set on site to suit the application. DIP switch Function ON position OFF position 1 Fan control Fan control is temperature dependent in all Fan control in normal operation is operating modes temperature independent 2 Operating mode changeover via external switch Changeover between normal operation and energy saving mode Changeover between normal operation and standby 3 Action of switch for externally operated mode changeover Changeover activated when contact of switch is closed Changeover activated when contact of switch is open 4 Standby Frost protection disabled Frost protection enabled 5 Switching differential 1K in heating mode, 0.5K in cooling mode 4K in heating mode, 2K in cooling mode 6 Dead zone in normal operation 2K 5K = factory settings Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807 Heronhill - for all your Airking requirements Installation Instruction 40101102-09 Page 5 of 6. WHEN INSTALLATION HAS BEEN COMPLETED - CHECK:1. All pipework and joints for leaks 2. That all pipes and fittings are insulated 3. That terminals are tight and that no wire cores are exposed 4. That duct connections are air tight and insulated where necessary. 5. Filters are clean and undamaged MAINTENANCE A. Every 2 months Inspect the filters and clean or replace as necessary B. Every 6 months Inspect and clean the fan rotors. C. Every 12 months 1. Check the unit fixing 2. Ensure that the fan motor and fan deck fixings are tight. 3. Check the unit wiring for damage and ensure that all terminals are tight. WIRING DIAGRAMS CWD 25/95/105/115 CWD 45/65 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807 Heronhill - for all your Airking requirements Installation Instruction 40101102-09 Page 6 of 6. CWD 165 CWD 175 TEV Ltd. Armytage Road, Brighouse, West Yorkshire. HD6 1QF, UK. Tel: +44 (0) 1484 405630. Fax: +44 (0) 1484 405620. Email: sales@quartz.co.uk Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807