Single Location, Multi-Location, or Multi-Zone
SIMPLY5 Wall Station
Catalog No. S5W
INSTALLATION INSTRUCTIONS
WARNINGS AND CAUTIONS:
•
•
•
•
•
Disconnect power at circuit breaker or fuse when servicing, installing, or removing fixture.
To be installed and/or used in accordance with electrical codes and regulations.
If you are unsure about any part of these instructions, consult an electrician.
Wall stations must be used in conjunction with SIMPLY5 Intelligent Junction Box (S5JB) and/or Light Energy Manager (S5LEM).
SIMPLY5 wall stations are not compatible with standard 3-way or 4-way switches. For multi-location control, use multiple SIMPLY5 wall
stations as shown.
Tools needed to install your wall station
Slotted/Phillips Screwdriver
Pliers
Cutters
Electrical Tape
Pencil
Ruler
The Simply5 wallstation can function as a dimming or switching only
station. Frames are included for dimming and switching.
To change frame for color, switching or dimming:
√
NOTE: Use check boxes when
Steps are completed.
Step 1 WARNING: TO AVOID FIRE, SHOCK, OR DEATH;
TURN OFF POWER at circuit breaker or fuse and test that
power is off before wiring!
Push in side at
tab to release
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Pull off pre-cut insulation from wall station leads. Make sure that the
ends of the wires from the wall box are straight (cut if necessary).
Remove insulation from each wire in the wall box as shown.
Installing wall station by itself or with other devices
If installing wall station in a single device application, proceed with the
INSTALLING YOUR WALL STATION section. If installing wall station in
a multi-device application, proceed as follows:
MULTI-DEVICE APPLICATION
In multi-device installations or to convert to ON/OFF only station, there is
no derating necessary. Breaking off fins is not required on this device.
Cut
(if necessary)
Use only with other SIMPLY5 system components and fixtures.
Wall station is a low voltage device; warranty void if connected to line voltage.
Only use lamps listed on ballast label. Linear fluorescent lamps must be used with rapid start sockets.
Lamps must be burned in at full intensity for 24 hours prior to dimming for proper dimming performance.
Recommended minimum wall box depth is 2-1/2”.
Use this device with COPPER OR COPPER CLAD WIRE ONLY.
In the standard SIMPLY5 configuration (no “HW” option), all components
are shipped with Reloc modular wiring connectors. All power and signal
connections for each component are made in a single plug-in connector.
The connectors are color-coded: Blue connectors are used for all
connections in a room, like the lights, wall stations and any sensors.
The S5W wall station connector can be connected at any light fixture on the
zone that it is controlling or at the Intelligent Junction Box blue connector.
For 3-way and 4-way applications, simply connect all stations to the wiring
for the zone that they are to
control. Connected stations will
Female connector
be automatically configured to
work together.
T-connector supplied
Preparing and connecting wires:
Step 2
Line up tabs
and press in
side to attach
ON
OFF
•
•
•
•
•
•
Step 3a Installation with Reloc connectors
INSTALLING YOUR WALL STATION
OFF
DI-400-VP50C-02A
WARNINGS AND CAUTIONS:
5/8”
(1.6 cm)
Stations that are to function as
master stations for multiple zones
may be connected to any of the
zones that they are to control.
Strip Gage
(measure bare
wire here)
CAUTION:
BEFORE INSTALLING YOUR WALL STATION, CHECK NEW
INSTALLATION WIRING FOR ANY SHORTS IN THE CIRCUIT.
with wall station
Male connector
From other
rooms this
circuit
SIMPLY5
Light Fixture
S5JB
Intelligent
Junction
Box
SIMPLY5
Light Fixture
WIRING SW5 WALL STATION
If your installation is using Reloc SIMPLY5 modular wiring connectors, go to
Step 3a.
If your installation is hard wired (no Reloc connectors), then go to Step 3b.
VP50C
Wall Station
For additional information, please call 1-800-533-2719
To other lights this zone
USER OPERATION
Step 3a cont’d
To install the wall station to the Reloc connector, simply connect the two
Purple wires at the end of the supplied connector to the purple screw
terminals on the wall station.
PURPLE
PURPLE
PURPLE
Terminals
GREEN
Terminal
Step 3b Installation with hard wiring
Connect the S5W leads as shown in the diagram below. The station may
be connected at any point in the room after the Intelligent Junction Box.
The signal wiring for the room may be run as either Class 1 or Class 2
wiring, so long as all national and local electrical codes are followed for
the wiring method selected.
For 3-way and 4-way applications, simply connect all stations to the signal
wires for the zone that they are to control. Connected stations will be
automatically configured to work together.
Stations that are to function as master stations for multiple zones may be
connected to the signal wires for any of the zones they control.
PUSH PAD:
• Lights are currently OFF: Tap to turn ON the lights to their last state.
• Lights are currently ON: Tap to turn OFF the lights.
• Lights are currently ON and the system has warned of an
impending automatic OFF (amber locator LED is blinking): Tap to
override the automatic OFF for 2 hours. The system will warn again at
the end of the two hours prior to turning the lights OFF.
• Lights are currently ON: Press and hold the push pad to enter Quiet
Time Mode. The Brightness Display LED will blink after 3 seconds
confirming that Quiet Time Mode has been entered. If an occupancy
sensor is being used in this room, Quiet Time Mode disables the sensor
for one hour. If an occupancy sensor is not being used, entering Quiet
Time Mode will not affect the operation of the system. This mode is
typically used in classrooms to keep the lights ON during periods of
inactivity, such as during a test or nap time.
RAISE/LOWER BAR:
• While lights are ON: Use the right half of the bar (^) to raise the light
level. Press and release the right half of the bar (^) to raise the lights by
one step, press and hold to ramp up the lights. Use the left half of the bar
(v) to lower the light level. Press and release the left half of the bar (v) to
lower the lights by one step, press and hold to ramp down the lights. The
Raise/Lower bar will only adjust the current level of the lights.
• While the lights are OFF: Tap either the right or left to display the level
to which the lights will turn ON when the Push Pad is pressed (LEDs
remain lit for 3 seconds after last button press). While the LEDs are lit,
the Raise/Lower Bar may be used to change this level without turning
ON the lights.
AMBER LOCATOR LED:
The amber locator LED has three modes:
1. Continuous ON: normal operation.
FIGURE 1
2. Blinking: the system has warned
before an impending automatic OFF;
LED Brightness
Raise/Lower
Display
Bar
the lights in the room will turn OFF
automatically sometime in the next 5
minutes. The user can tap the Push
Pad during this period to override the
OFF for 2 hours.
3. Continuous OFF: the station has
lost communication with the rest of
the system for some reason.
WIRING DIAGRAM
HOT
NEUTRAL
SIGNAL FROM
S5LEM LIGHT
ENERGY
MANAGER
HOT TO ZONE
FIXTURES
S5JB
INTELLIGENT
JUNCTION
BOX
NEUTRAL TO
ZONE FIXTURES
SIGNAL TO ZONE
FIXTURES &
WALL STATIONS
PURPLE
HOT
NEUTRAL
SIMPLY-5
LIGHT
FIXTURES
Locator
Light
Push Pad
FIGURE 2
PURPLE
PURPLE
PURPLE
GREEN GROUND
1 2 3 4 5 6 7
LED Brightness
Display
DAYLIGHT HARVESTING SETUP MODE
ADVANCED PROGRAMMING FEATURES
PROGRAMMING MODE
Step Function
Range
Default
1
Set Configuration
Group # for Room
0 - 7 indicated by LED display.
0 is no LED lit,1 is LED 1 ON, 2 is
LED 2 ON, etc…
Zone 0
2
Master / Zone Switch
Enable / Disable Warn
OFF
Master Switch is LED 7 ON
Zone Switch is LED 7 OFF
Warn OFF enabled – LED 1 ON
Warn OFF disabled – LED 1 OFF.
Zone
Switch
Warn OFF
enabled
3
Motion Sensor Manual
ON or Automatic ON
operation
Manual ON is all LEDs OFF
Automatic ON is all LEDs ON
Manual ON
1. Press and hold the Push Pad and the right half of the Raise/Lower Bar
(^) for 5 seconds until the Locator LED begins to blink green.
2. Upon releasing the push pad, the locator LED will blink one green pulse
per second indicating programming step number 1.
3. Set Configuration Group number for this room by using the Raise/Lower
Bar to light the LED for the corresponding Configuration Group. No LEDs
for Configuration Group 0, LED # 1 for Configuration Group 1 …, LED # 7
for Configuration Group 7, as shown in figure 2.
4. Tap the push pad to change to step 2. The locator LED will blink 2 short
green pulses per second.
5. The system normally warns the occupants of an impending automatic
OFF by blinking the lights 5 minutes before it turns them OFF. This
warning blink can be disabled by pressing the left half of the Raise/Lower
Bar (v). LED 1 ON = enable warn, LED 1 OFF = disable warn.
6. If multiple control zones are being used in this room, the wall station may
be configured to either control only the zone to which it is connected
(normal function), or to control all of the zones in the room as a ’master’
switch. Set this switch as master or zone switch by using the right half of
the Raise / Lower Bar (^). LED 7 ON = master switch, LED 7 OFF = zone
switch.
7. Tap the push pad to change to step 3. The locator LED will blink 3 short
green pulses per second if in step 3.
Note that if a S5LEM is installed, the Configuration Group for this room
must be set so that motion sensors are Configured Locally under the
Advanced Setup menu for this step to be accessible. If any other setting
has been programmed for motion sensor function at the S5LEM, step 3
will be skipped and the station will exit setup mode and save the settings.
If step 3 is skipped, the locator LED will flash 4 short red pulses.
8. If a motion sensor is being used in this room, the system will normally
function so that the lights must be turned on manually but will turn off
automatically. This can be changed to automatic on / automatic off by
using the Raise / Lower Bar: press the right half of the bar (^) for auto on
/ auto off operation; press the left half of the bar (v) for manual on / auto
off operation.
9. Tap the push pad to exit the programming mode and save the settings.
The station will also exit out of programming mode automatically after 3
minutes of inactivity.
Manual setup is typically NOT required for proper photocell operation.
However, for situations where greater control over daylight harvesting
operation is desired, a Scale Factor feature and manual photocell
calibration process are available if a wall station is installed on the
daylight harvesting zone. Note that the Daylight Harvesting Setup mode
can be disabled at the S5LEM, through the Advanced Setup menu. If
the Daylight Harvesting Setup has been disabled, the station will blink
the locator LED with 4 short red flashes and return to normal operation
when someone attempts to enter the setup mode.
The Scale Factor allows the installer to adjust the systemsʼ response to
sensed ambient light. This feature is typically used for rooms in which
the light level on the ceiling does not accurately represent the light level
on the working surfaces in the room (for example, when a large amount
of sunlight is being reflected off of a white concrete pad outside the
room). As the Scale Factor setting is lowered, changes in the sensed
ambient light in the space will have less effect on the electric light level;
as it is raised, changes in the sensed ambient light in the space will
have more effect on the electric light level.
Scale Factor Setup:
1. Press and hold the Push Pad and the left half of the Raise/Lower
Bar (v) for 5 seconds until the Locator LED begins to blink. If the
setup mode is disabled, the locator LED will flash red 4 times and the
station will return to normal operation.
2. The zone lights will flash 3 times indicating Daylight Harvesting Setup
Mode is active. The bargraph will indicate the current Scale Value.
3. Use the Raise/Lower bar to set the Scale Factor from 1 to 7.
4. Press & release the paddle switch once more to exit the Daylight
Harvesting Setup Mode and save the settings. The zone lights will
flash 3 times indicating the system has exited.
The system will typically calibrate the photocell input automatically over
the course of a normal day of operation. The system will begin dimming
the lights in response to daylight once the photocell has calibrated. If
the furnishings in the room have changed siginificantly since the system
was installed (for example, if carpet has been installed) or if the photcell
needs to be calibrated more quickly for testing purposes, a manual
calibration procedure is available.
Manual Photocell Calibration:
Note: the photocell calibration procedure should only be performed
after the controlled lights have been on at 100% for at least 20
minutes, allowing the lamps to fully warm up.
1. Press and hold the Push Pad and the left half of the Raise/Lower
Bar (v) for 5 seconds until the Locator LED begins to blink. If the
setup mode is disabled, the locator LED will flash red 4 times and the
station will return to normal operation.
2. The zone lights will flash 3 times indicating Daylight Harvesting Setup
Mode is active.
3. To begin the Photocell Calibration procedure, press and hold the
paddle switch until the bargraph LED begins to flash, approximately
3 seconds. The zone lights will flash off and then back on once to
indicate calibration mode is active, then they will be set to 100% for
approximately 30 seconds. While at full, the LED brightness display
will blink sequentially from left to right. After this time interval ends,
the zone lights will then turn off for 5 seconds. While off, the LED
brightness display will blink sequentially from right to left.
4. Once the Photocell Calibration procedure is complete, the zone lights
will blink off and then back on once more to indicate the end of the
procedure.
5. Press & release the paddle switch once more to exit the Daylight
Harvesting Setup Mode and save the settings. The zone lights will
flash 3 times indicating the system has exited.
For additional information, please call 1-800-533-2719