Single Location, Multi-Location, or Multi-Zone SIMPLY5 Wall Station Catalog No. S5W INSTALLATION INSTRUCTIONS WARNINGS AND CAUTIONS: • • • • • Disconnect power at circuit breaker or fuse when servicing, installing, or removing fixture. To be installed and/or used in accordance with electrical codes and regulations. If you are unsure about any part of these instructions, consult an electrician. Wall stations must be used in conjunction with SIMPLY5 Intelligent Junction Box (S5JB) and/or Light Energy Manager (S5LEM). SIMPLY5 wall stations are not compatible with standard 3-way or 4-way switches. For multi-location control, use multiple SIMPLY5 wall stations as shown. Tools needed to install your wall station Slotted/Phillips Screwdriver Pliers Cutters Electrical Tape Pencil Ruler The Simply5 wallstation can function as a dimming or switching only station. Frames are included for dimming and switching. To change frame for color, switching or dimming: √ NOTE: Use check boxes when Steps are completed. Step 1 WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring! Push in side at tab to release OFF ON ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Pull off pre-cut insulation from wall station leads. Make sure that the ends of the wires from the wall box are straight (cut if necessary). Remove insulation from each wire in the wall box as shown. Installing wall station by itself or with other devices If installing wall station in a single device application, proceed with the INSTALLING YOUR WALL STATION section. If installing wall station in a multi-device application, proceed as follows: MULTI-DEVICE APPLICATION In multi-device installations or to convert to ON/OFF only station, there is no derating necessary. Breaking off fins is not required on this device. Cut (if necessary) Use only with other SIMPLY5 system components and fixtures. Wall station is a low voltage device; warranty void if connected to line voltage. Only use lamps listed on ballast label. Linear fluorescent lamps must be used with rapid start sockets. Lamps must be burned in at full intensity for 24 hours prior to dimming for proper dimming performance. Recommended minimum wall box depth is 2-1/2”. Use this device with COPPER OR COPPER CLAD WIRE ONLY. In the standard SIMPLY5 configuration (no “HW” option), all components are shipped with Reloc modular wiring connectors. All power and signal connections for each component are made in a single plug-in connector. The connectors are color-coded: Blue connectors are used for all connections in a room, like the lights, wall stations and any sensors. The S5W wall station connector can be connected at any light fixture on the zone that it is controlling or at the Intelligent Junction Box blue connector. For 3-way and 4-way applications, simply connect all stations to the wiring for the zone that they are to control. Connected stations will Female connector be automatically configured to work together. T-connector supplied Preparing and connecting wires: Step 2 Line up tabs and press in side to attach ON OFF • • • • • • Step 3a Installation with Reloc connectors INSTALLING YOUR WALL STATION OFF DI-400-VP50C-02A WARNINGS AND CAUTIONS: 5/8” (1.6 cm) Stations that are to function as master stations for multiple zones may be connected to any of the zones that they are to control. Strip Gage (measure bare wire here) CAUTION: BEFORE INSTALLING YOUR WALL STATION, CHECK NEW INSTALLATION WIRING FOR ANY SHORTS IN THE CIRCUIT. with wall station Male connector From other rooms this circuit SIMPLY5 Light Fixture S5JB Intelligent Junction Box SIMPLY5 Light Fixture WIRING SW5 WALL STATION If your installation is using Reloc SIMPLY5 modular wiring connectors, go to Step 3a. If your installation is hard wired (no Reloc connectors), then go to Step 3b. VP50C Wall Station For additional information, please call 1-800-533-2719 To other lights this zone USER OPERATION Step 3a cont’d To install the wall station to the Reloc connector, simply connect the two Purple wires at the end of the supplied connector to the purple screw terminals on the wall station. PURPLE PURPLE PURPLE Terminals GREEN Terminal Step 3b Installation with hard wiring Connect the S5W leads as shown in the diagram below. The station may be connected at any point in the room after the Intelligent Junction Box. The signal wiring for the room may be run as either Class 1 or Class 2 wiring, so long as all national and local electrical codes are followed for the wiring method selected. For 3-way and 4-way applications, simply connect all stations to the signal wires for the zone that they are to control. Connected stations will be automatically configured to work together. Stations that are to function as master stations for multiple zones may be connected to the signal wires for any of the zones they control. PUSH PAD: • Lights are currently OFF: Tap to turn ON the lights to their last state. • Lights are currently ON: Tap to turn OFF the lights. • Lights are currently ON and the system has warned of an impending automatic OFF (amber locator LED is blinking): Tap to override the automatic OFF for 2 hours. The system will warn again at the end of the two hours prior to turning the lights OFF. • Lights are currently ON: Press and hold the push pad to enter Quiet Time Mode. The Brightness Display LED will blink after 3 seconds confirming that Quiet Time Mode has been entered. If an occupancy sensor is being used in this room, Quiet Time Mode disables the sensor for one hour. If an occupancy sensor is not being used, entering Quiet Time Mode will not affect the operation of the system. This mode is typically used in classrooms to keep the lights ON during periods of inactivity, such as during a test or nap time. RAISE/LOWER BAR: • While lights are ON: Use the right half of the bar (^) to raise the light level. Press and release the right half of the bar (^) to raise the lights by one step, press and hold to ramp up the lights. Use the left half of the bar (v) to lower the light level. Press and release the left half of the bar (v) to lower the lights by one step, press and hold to ramp down the lights. The Raise/Lower bar will only adjust the current level of the lights. • While the lights are OFF: Tap either the right or left to display the level to which the lights will turn ON when the Push Pad is pressed (LEDs remain lit for 3 seconds after last button press). While the LEDs are lit, the Raise/Lower Bar may be used to change this level without turning ON the lights. AMBER LOCATOR LED: The amber locator LED has three modes: 1. Continuous ON: normal operation. FIGURE 1 2. Blinking: the system has warned before an impending automatic OFF; LED Brightness Raise/Lower Display Bar the lights in the room will turn OFF automatically sometime in the next 5 minutes. The user can tap the Push Pad during this period to override the OFF for 2 hours. 3. Continuous OFF: the station has lost communication with the rest of the system for some reason. WIRING DIAGRAM HOT NEUTRAL SIGNAL FROM S5LEM LIGHT ENERGY MANAGER HOT TO ZONE FIXTURES S5JB INTELLIGENT JUNCTION BOX NEUTRAL TO ZONE FIXTURES SIGNAL TO ZONE FIXTURES & WALL STATIONS PURPLE HOT NEUTRAL SIMPLY-5 LIGHT FIXTURES Locator Light Push Pad FIGURE 2 PURPLE PURPLE PURPLE GREEN GROUND 1 2 3 4 5 6 7 LED Brightness Display DAYLIGHT HARVESTING SETUP MODE ADVANCED PROGRAMMING FEATURES PROGRAMMING MODE Step Function Range Default 1 Set Configuration Group # for Room 0 - 7 indicated by LED display. 0 is no LED lit,1 is LED 1 ON, 2 is LED 2 ON, etc… Zone 0 2 Master / Zone Switch Enable / Disable Warn OFF Master Switch is LED 7 ON Zone Switch is LED 7 OFF Warn OFF enabled – LED 1 ON Warn OFF disabled – LED 1 OFF. Zone Switch Warn OFF enabled 3 Motion Sensor Manual ON or Automatic ON operation Manual ON is all LEDs OFF Automatic ON is all LEDs ON Manual ON 1. Press and hold the Push Pad and the right half of the Raise/Lower Bar (^) for 5 seconds until the Locator LED begins to blink green. 2. Upon releasing the push pad, the locator LED will blink one green pulse per second indicating programming step number 1. 3. Set Configuration Group number for this room by using the Raise/Lower Bar to light the LED for the corresponding Configuration Group. No LEDs for Configuration Group 0, LED # 1 for Configuration Group 1 …, LED # 7 for Configuration Group 7, as shown in figure 2. 4. Tap the push pad to change to step 2. The locator LED will blink 2 short green pulses per second. 5. The system normally warns the occupants of an impending automatic OFF by blinking the lights 5 minutes before it turns them OFF. This warning blink can be disabled by pressing the left half of the Raise/Lower Bar (v). LED 1 ON = enable warn, LED 1 OFF = disable warn. 6. If multiple control zones are being used in this room, the wall station may be configured to either control only the zone to which it is connected (normal function), or to control all of the zones in the room as a ’master’ switch. Set this switch as master or zone switch by using the right half of the Raise / Lower Bar (^). LED 7 ON = master switch, LED 7 OFF = zone switch. 7. Tap the push pad to change to step 3. The locator LED will blink 3 short green pulses per second if in step 3. Note that if a S5LEM is installed, the Configuration Group for this room must be set so that motion sensors are Configured Locally under the Advanced Setup menu for this step to be accessible. If any other setting has been programmed for motion sensor function at the S5LEM, step 3 will be skipped and the station will exit setup mode and save the settings. If step 3 is skipped, the locator LED will flash 4 short red pulses. 8. If a motion sensor is being used in this room, the system will normally function so that the lights must be turned on manually but will turn off automatically. This can be changed to automatic on / automatic off by using the Raise / Lower Bar: press the right half of the bar (^) for auto on / auto off operation; press the left half of the bar (v) for manual on / auto off operation. 9. Tap the push pad to exit the programming mode and save the settings. The station will also exit out of programming mode automatically after 3 minutes of inactivity. Manual setup is typically NOT required for proper photocell operation. However, for situations where greater control over daylight harvesting operation is desired, a Scale Factor feature and manual photocell calibration process are available if a wall station is installed on the daylight harvesting zone. Note that the Daylight Harvesting Setup mode can be disabled at the S5LEM, through the Advanced Setup menu. If the Daylight Harvesting Setup has been disabled, the station will blink the locator LED with 4 short red flashes and return to normal operation when someone attempts to enter the setup mode. The Scale Factor allows the installer to adjust the systemsʼ response to sensed ambient light. This feature is typically used for rooms in which the light level on the ceiling does not accurately represent the light level on the working surfaces in the room (for example, when a large amount of sunlight is being reflected off of a white concrete pad outside the room). As the Scale Factor setting is lowered, changes in the sensed ambient light in the space will have less effect on the electric light level; as it is raised, changes in the sensed ambient light in the space will have more effect on the electric light level. Scale Factor Setup: 1. Press and hold the Push Pad and the left half of the Raise/Lower Bar (v) for 5 seconds until the Locator LED begins to blink. If the setup mode is disabled, the locator LED will flash red 4 times and the station will return to normal operation. 2. The zone lights will flash 3 times indicating Daylight Harvesting Setup Mode is active. The bargraph will indicate the current Scale Value. 3. Use the Raise/Lower bar to set the Scale Factor from 1 to 7. 4. Press & release the paddle switch once more to exit the Daylight Harvesting Setup Mode and save the settings. The zone lights will flash 3 times indicating the system has exited. The system will typically calibrate the photocell input automatically over the course of a normal day of operation. The system will begin dimming the lights in response to daylight once the photocell has calibrated. If the furnishings in the room have changed siginificantly since the system was installed (for example, if carpet has been installed) or if the photcell needs to be calibrated more quickly for testing purposes, a manual calibration procedure is available. Manual Photocell Calibration: Note: the photocell calibration procedure should only be performed after the controlled lights have been on at 100% for at least 20 minutes, allowing the lamps to fully warm up. 1. Press and hold the Push Pad and the left half of the Raise/Lower Bar (v) for 5 seconds until the Locator LED begins to blink. If the setup mode is disabled, the locator LED will flash red 4 times and the station will return to normal operation. 2. The zone lights will flash 3 times indicating Daylight Harvesting Setup Mode is active. 3. To begin the Photocell Calibration procedure, press and hold the paddle switch until the bargraph LED begins to flash, approximately 3 seconds. The zone lights will flash off and then back on once to indicate calibration mode is active, then they will be set to 100% for approximately 30 seconds. While at full, the LED brightness display will blink sequentially from left to right. After this time interval ends, the zone lights will then turn off for 5 seconds. While off, the LED brightness display will blink sequentially from right to left. 4. Once the Photocell Calibration procedure is complete, the zone lights will blink off and then back on once more to indicate the end of the procedure. 5. Press & release the paddle switch once more to exit the Daylight Harvesting Setup Mode and save the settings. The zone lights will flash 3 times indicating the system has exited. For additional information, please call 1-800-533-2719 DI-400-VP50C-02A