CIGRE INDIA Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 1 • Transmission lines constitute more than 60% of asset of power transmission. • They traverse an incredible range of kilometer in harsh environments, climates and terrains. Transmissio n lines • In India many of the Transmission lines currently in service were built in the 1960s and 70s and are subject to many problems including ageing. • With growing demands, there is huge expectations from transmission companies to keep the transmission line uptime near to 100%. • Hence accurate fault location, health check / monitoring the same is very much essential. Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 2 Type of common faults in overhead Transmission lines All Types of Open & Short Category faults Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 3 Overhead Transmission line fault locator & Analyzer • Pre-Commissioning Check of EHV Lines –Continuity, Phase Sequence, line length verification. • Ascertaining line healthiness before re-Charging. • For Preventive & Predictive Maintenance of existing EHV Lines. • Restore the EHV lines ASAP to maintain UP TIME. Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 4 Fault Locator and types of fault locator OVER HEADTRANSMISSIONLINE FAULT LOCATOR (OHFL) • Online • Offline Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 5 OHFL Basic Principals of working • ONLINE-Systems works on the principal of power system Parameters & Data is taken during stressed breakdown condition and this data is in percentage accuracy depending on the residual impedance of the line. • OFFLINE-Systems works on the principal of Multiple pulse Eco Co-relation technique & doesn't require any input parameters for accurate fault finding. Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 6 Online method some of it’s limitations • Each Line require one dedicated equipment. • It is not helpful for spur lines. • Open Circuit faults can’t locate through online systems. • Fault locating accuracy may vary in percentage. (+/_ 10% or more) • Pre-Commissioning tests are not possible. Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 7 • Advanced high frequency multiple pulse co-relation technique Offline method • How it works: - High frequency Coded pulse sent in to the powerline - picks up different types of disturbance and location - Information Decoded - Generates User Friendly Report and gives complete vision of the line end to end Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 8 Offline methods and it’s advantages • • • • • It’ is accurate up to +/- 100Mtr. One equipment is enough for whole sub station. It can be used for Spur line fault locating. Pre –Commissioning tests are possible. Offline system can identify the secondary faults before re charging the line. • It can find out Open Circuit faults. • Does not require any complimentary system at other end of the sub station. • It can Locate faults up to 2500KM. Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 9 Offline OHFL Diagnostic outputs • Fault Locator(Breakdown): For finding the faults at accurate distance. • Line Signature Analysis: for understanding the healthiness of the line. Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 10 Overhead transmission line fault locator benefits • Apart from finding dead faults , useful for predictive and preventive maintenancei) It can detect developing faults . ii) It can detect nature of the fault(Open/Short) iii) It can indicate severity of the fault (Level of the Faults). • Less time to find faults and its location. • Healthiness check up for the entire line . Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 11 Case Studies • • • • • • Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 12 CASE STUDIES SHORT CIRCUIT FAULT at 112 KM Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 13 CASE STUDIES Decapping Fault at 69 Km in B Phase Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com Decapping Fault 14 CASE STUDIES ALL JUMPERS NOT THROUGH AT 55 KM Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 15 CASE STUDIES Corona due to loose jumper Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 16 CASE STUDIES SIGNATURE AFTER THROUGH JUMPER Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 17 CASE STUDIES Flashover insulator at 5.8 and 5.3 KM Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 18 CASE STUDIES Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 19 CASE STUDIES Trees very close to Transmission Line in B-phase Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 20 CASE STUDIES After Removal of trees Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 21 CASE STUDIES • Line Signature Analyser could identify the stress of the line caused by high frequency noise flowing on the surface of insulators and flashover. • Line Signature Analyser printout with and without filters reveal the presence of several kV’s of high frequency noise and really a cause for flash over of insulators Short circuit Fault De-capping All jumpers not through in • The noise was later found due to parallel HVDC lines and Quad line thyristor switching action Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 22 CASE STUDIES Annexure –A without filter Padghe – BBLR – gain 1 without filter-Lots of noise Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 23 CASE STUDIES Annexure – B with HVDC filter Padghe – BBLR– Gain1 No noise observed Short circuit Fault De-capping All jumpers not through in Quad line Leaky Insulators Clearance related problems High frequency effects on transmission lines Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 24 CASE STUDIES OFFLINE OVERHEAD LINE FAULT LOCATOR Case Studies of 25 lines taken in a Transmission ZONE during 2011-2012 . Statistics are based on the OnM internal record maintained for 365 days With Ideally Time Without OHFL No. Of Time taken Average with taken to Tota OHFL time time Lines in Total to find Line No. of OHFL OHFL find OHFL l EXTRA taken to taken to the Zone Trippi fault in Lengths in Tripping time used fault not time HOUR rectify the rectify (Total ngs in HRS KMs in a would at with used take S fault in a fault in a Sample 25 a Year without Year/Line have OHFL in n line (Hrs) line lines) OHFL (Hrs) taken ( Hrs) (Hrs) 0 to 150 KMs 15 3 19 3 57 171 hrs 30 places 90 hrs 27 places 405 hrs 495 324 hrs hrs 150 to 250 Kms 19 4 4 2 8 32 hrs 5 Places 20 hrs 3 Places 95 hrs 115 hrs 83 hrs 250 to 350 Kms 23 4 2 2 4 16 hrs 1 places 4 hrs 1 place 23 hrs 27 hrs 11 hrs Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 25 Case Studies Case Studies of 73 new lines in a Utility Transmission company in India No. of lines No.of Lines signature successfully charged test was done after Signature Analyzer KV of the line No.of Lines No of Tripping Without Line Signature test OFFLINE OHFL 132KV 5 3 3 3 Line Signature 220KV 20 11 9 9 400KV 40 16 14 14 765KV 8 3 3 3 Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 26 Important parameterswhile choosing an overheadtransmis sion line fault • Equipment should be Portable & Battery operated. • Induction Voltage Suppression capability. • Auto Impedance matching facility for the kit to be used in any EHV Lines. • Instrument should be EMI/EMC Compliance. locator Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 27 PAPER Presented by POWERGRID IN CBIP – INTERNATIONAL CONFERENCE Using Offline Fault Locator TO DIAGNOSE THE TRANSMISSION LINE Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 28 29 Thank you for your attendan ce For more information Write to : PRASHANT DAS prashant.das@tauruspowertronics.com +91 9766355355 Prashant Das Tauruspowertronics Pvt. Ltd prashant.das@tauruspowertronics.com www.tauruspowertronics.com 30