FM 55-509-1 CHAPTER 12 ELECTRICAL CONDUCTORS INTRODUCTION Many factors determine the type of electrical conductor to be used to connect components. Some of these factors are the physical size of the conductor, the type of material used for the conductor, and the electrical characteristics of the insulation. Other factors that can determine the choice of a conductor are the weight, the cost, and the environment where the conductor is to be used. CONDUCTOR SIZES To compare the resistance and size of one conductor with that of another, a standard or unit must be established. A convenient unit of measurement for the diameter of a conductor is the mil (0.001 or one-thousandth of an inch). A convenient unit of conductor length is the foot. The standard unit of size in most cases is the mil-foot. A wire will have a unit size if it has a diameter of 1 mil and a length of 1 foot. Square Mil The square mil is a unit of measurement used to determine the cross-sectional area of a square or rectangular conductor (Figure 12-1 views A and B). A square mil is the area of a square whose sides are each 1 mil. To obtain the cross-sectional area of any square conductor, multiply the dimensions of any side of the conductor by itself. For example, with a square conductor with a side dimension of 3 mils, multiply 3 mils by itself (3 mils x 3 mils). This gives a cross-sectional area of 9 square mils. To determine the cross-sectional area of a rectangular conductor, multiply the length times the width of the end face of the conductor (in mils). For example, if one side of the rectangular crosssectional area is 6 mils and the other side is 3 mils, nultiply 6 mils x 3 mils. The cross-sectional area is 18 square mils. The following is another example of how to determine the cross-sectional area of a rectangular conductor. Assume a bus bar is 3/8 inch thick and 4 inches wide. The 3/8 inch expressed in decimal form is .375 inch. Since 1 mil equals .001 inch, the thickness of the conductor is 375 mils. The width is 4 inches. Since there are 1,000 mils per inch, the width is 4,000 mils. To determine the cross-sectional area, multiply the length by the width, or 375 mils x 4,000 mils. The area (A) equals 1,500,00 square mils. 12-1 FM 55-509-1 Circular Mil Solution: The circular mil is the standard unit of measure of the cross-sectional area of a wire. This unit of measurement is found in American and English wire tables. The diameter of a round conductor used to conduct electricity may be only a fraction of an inch. Therefore, it is convenient to express this fraction in mils to avoid using decimals. For example, the diameter of a wire is expressed as 25 mils instead of 0.025 inch, A circular mil is the area of a circle whose diameter is 1 mil, as shown in Figure 12-2 view B. The area in circular mils of a round conductor is obtained by squaring the diameter, which is measured in mils. Thus 2a wire having a diameter of 25 mils has an area of 25 or 625 circular mils. a. A = D = (80.81) = 6,530 circular mils. To determine the number of square mils in the same conductor, apply the conventional formula for determining the area o2 a circle (area [A] = pi x radius squared = pi x r . In this formula, A is the unknown. It equals the cross-sectional area in square mils. Pi is the constant 3.1416. Letter r is the radius of the circle, or half the2 diameter. Through substitution A = 3.1416 (12.5) . Therefore, 3.1416 x 156.25 = 490.625 square mils. The cross-sectional area of the wire has been shown to have 625 circular mils, while it has only 490.625 square mils. Therefore, a circular mil represents a smaller unit of area than the square mil. If a wire has a cross-sectional diameter of 1 mil,2 by definition he circular mil area (CMA) is 2 A = D ,or A = 1 , or A = 1 circular mil. To determine thes2 are mil area of the same wire, the form2 a A = pir is applied. Therefore, A = 3.1416 x (.5) . When the formula is carried forward, A = 3.1416 x .25, or A = .7854 square mils. From this, it can be concluded that 1 circular mil equals .7854 square mil. This becomes important when square conductors (Figure 12-2 view A) and round conductors (view B) are compared. View C shows the comparison. When the square mil area is given, divide the area by 0.7854 to determine the circular mil area. When the circular mil area is given, multiply the area by 0.7854 to determine the square mil area. Example: The American wire gauge (AWG) No. 12 wire has a diameter of 80.81 mils: a. What is the area in circular mils? b. What is the area in square mils? 12-2 2 2 b. A = 0.7854 x 6,530 = 5,128.7 square mils. A wire in its usual form is a slender rod or filament of drawn metal. In larger sizes, wire is difficult to handle. To increase flexibility, it is stranded. Strands are usually single wires twisted together in sufficient numbers to make up the necessary crosssectional area of the cable. The total area in circular mils is determined by multiplying the area in circular mils of one strand by the number of strands in the cable. FM 55-509-1 Circular Mil-Foot A circular mil-foot is a unit of volume (Figure 12-3). It is a unit conductor 1 foot in length with across-sectional area of 1 circular mil. Because it is considered a unit conductor, the circular mil-foot is useful in making comparisons between wires that are made of different metals. For example, a basis of comparison of the resistivity (to be discussed later) of various substances may be made by determining the resistance of a circular mil-foot of each of the substances. In working with square or rectangular conductors, such as ammeter shunts and bus bars, it is sometimes more convenient to use a different unit volume. Bus bars are to be used when a large current capacity is required. Accordingly, unit volume may also be measured as the centimeter cube. Specific resistance, therefore, becomes the resistance offered by a cube-shaped conductor 1 centimeter in length and 1 square centimeter in cross-sectional area. The unit volume to be used is given in tables of specific resistances. SPECIFIC RESISTANCE OR RESISTIVITY Specific resistance, or resistivity, is the resistance in ohms offered by a unit volume (the circular mil-foot or the centimeter cube) of a substance to the flow of electric current. Resistivity is the reciprocal of conductivity. A substance that has a high resistivity will have a low conductivity and vice versa. Thus, the specific resistance of a substance is the resistance of a unit volume of that substance. Many tables of specific resistance are based on the resistance in ohms of a volume of a substance 1 foot in length and 1 circular mil in cross-sectional area. If the kind of metal of which a conductor is made is known, the specific resistance of the metal may be obtained from one of these tables. These tables also specific the temperature at which the resistance measurement is made. Table 12-1 gives the specific resistance of some common substances. The resistance of a conductor of a uniform cross section varies directly as the product of the length and the specific resistance of the conductor and inversely as the cross-sectional area of the conductor. Therefore, the resistance of a conductor may be calculated if the length, cross-sectional 12-3 FM 55-509-1 area, and specific resistance of the substance is known. Expressed as an equation, the resistance (R) in ohms of a conductor is — R=pL A Where: p (Greek rho) = the specific resistance in ohms per circular mil-foot (refer to Table 12-1) L = the length in feet A = the cross-sectional area in circular mils Example: What is the resistance of 1,000 feet of copper wire having a cross-sectional area of 10,400 circular mils (No. 10 AWG wire) at a temperature of 20C? Given p = 10.37 ohms/circular mil-foot L = 1,000 feet A = 10,400 circular mils Solution: R = p L = 10.37 (1,000) = 1 ohm (approximately) 10,400 A RELATIONSHIP BETWEEN WIRE SIZES Wires are manufactured in sizes numbered according to a table known as the American wire gauge (AWG). The National Bureau of Standards publishes tables for various conductors either solid or stranded and the material they are made from, such as copper or aluminum. Table 12-2 is one example of such a table. The wire diameters become smaller as the gauge numbers become larger. (Numbers are rounded off for convenience but are accurate for practical application.) The largest wire in Table 12-2 is 0000, and the smallest is number 22. Larger and smaller sizes are manufactured but are not commonly used by the Army. The tables show the diameter, circular mil area, and area in square inches of the different AWG wire sizes. It also shows the resistance per thousand feet of the various wire sizes at 25C. 12-4 STRANDED WIRES AND CABLES A wire is a slender rod or filament of drawn metal. The definition restricts the term to what would ordinarily be understood as solid wire. The word “slender” is used because the length of a wire is usually’ large in comparison with the diameter. If a wire is covered by insulation, it is called an insulated wire. Although wire properly refers to the metal, it is generally understood to include the insulation. A conductor is a wire suitable for carrying an electric current. A stranded conductor is composed of a group of wires or of any combination of groups of wires. The wires in a stranded conductor are usually twisted together and not insulated from each other. A cable is either a stranded conductor (a single conductor cable) or a combination of conductors insulated from one another (multiple conductor cable). The term “cable” is a general one, and in practice, it usually applies only to larger sizes of conductors. A small cable is more often called a stranded wire. The insulated cables may be sheathed (covered) with lead or protective armor. Figure 12-4 shows some of the different types of wire and cable used in the military. Conductors are stranded mainly to increase their flexibility. The wire strands in cables are arranged in the following order. The first layer of strands around the center conductor are made of 6 conductors. The second layer is made up of 12 conductors. The third layer is made up of 18 conductors, and so on. Thus, standard cables are composed of 7, 19, and 37 strands, in continuing fixed increments. The overall flexibility may be increased by further stranding of the individual strands. All Army marine electrical wires and cables will be of the stranded type. The excessive vibration of a vessel prohibits solid conductor wires. Figure 12-5 shows a typical cross section of a 37-strand cable. It also shows how the total circular mil cross-sectional area of a stranded cable is determined. FM 55-509-1 SELECTION OF WIRE SIZE Several factors must be considered in selecting the size wire to be used for transmitting and distributing electric power. There are military specifications that cover the installation of wiring of ships and electrical/electronic equipment. These specifications describe the technical requirements for material which is to be purchased from manufacturers by the Department of Defense. One important reason for these specifications is to reduce the danger of fires caused by the improper selection of wire sizes. Wires can carry only a limited amount of current safely. If the current flowing through a wire exceeds the current-carrying capacity of the wire, excess heat is generated. This heat may be great enough to burn off the insulation around the wire and continue to do much greater damage by starting a fire. 12-5 FM 55-509-1 Some of these factors affect the resistance of a wire carrying current. An increase in the diameter or cross section of a conductor decreases its resistance and increases its capability to carry current. An increase in the specific resistance of a conductor increases its resistance and decreases its capacity to carry current. FACTORS AFFECTING THE CURRENT RATING The current rating of a cable or wire indicates the current capacity that the wire or cable can safely carry continuously. If this limit, or current rating, is exceeded for a length of time, the heat generated may bum the insulation. The current rating of a wire is used to determine what size is needed for a given electrical load. The following factors determine the current rating of a wire: The conductor size. The material of which the conductor is made. The location of the wire. The type of insulation used. Ambient temperature. 12-6 The location of a conductor determines the temperature under which it operates. A cable may be located in a row of other cables (banked) or placed alongside other cables in one of two rows (doublebanked). Therefore, it operates at a higher temperature than if it is open to the free air. The higher the temperature under which a wire is operating, the greater its resistance. Its capacity to carry current is also lowered. In each case, the resistance of a wire determines its current-carrying capacity. The greater the resistance, the more power it dissipates in the form of heat energy. Electrical conductors may also be installed in locations where the ambient temperature is relatively high. When this is the case, the heat generated by external sources constitutes an appreciable part of the total conductor heating. This will be explained further under Temperature Coefficient. Due allowances must be made for the influence of external heating on the allowable conductor current. Each case has its own specific limitations. Table 12-3 gives the maximum currentcarrying capacity for distribution cable. Table 12-4 shows control cable ampacities. Table 12-5 specifies the maximum allowable operating temperature of insulated conductors. It varies with the type of conductor insulation being used. The insulation of a wire does not affect its resistance. It does, however, determine how much heat is needed to burn the insulation. The limit of current that an insulated conductor can withstand depends on how hot the conductor can get before it burns the insulation. Different types of insulation will burn at different temperatures. Therefore, the type of insulation used is a factor that determines the current rating of a conductor. Polyvinyl chloride (PVC) insulation will begin to deteriorate at relatively low temperatures. Silicon rubber retains its insulating properties at much higher temperatures. FM 55-509-1 12-7 FM 55-509-1 Copper has high conductivity. It is more ductile (can be drawn out). It has relatively high tensile strength (the greatest stress a substance can bear along its length without tearing apart). It can also be easily soldered. US Army vessels use only soft annealed copper wire. The copper conductor is tinned or alloy-coated to ensure compatibility with insulation. TEMPERATURE COEFFICIENT COPPER VERSUS ALUMINUM CONDUCTORS Although silver is the best conductor, its cost limits its use to special circuits. It is used where a substance with high conductivity or low resistivity is needed. 12-8 The resistance of pure metals, such as silver, copper, and aluminum, increases as the temperature increases. The resistance of some alloys, such as constantan and manganin, changes very little as the temperature changes. Measuring instruments use these alloys because the resistance of the circuits must remain constant to achieve accurate measurements. The amount of increase in the resistance of a l-ohm sample of the conductor per degree rise in temperature above 0C is called the temperature coefficient of resistance. For copper, the value is about 0.00427 ohm. This and more is taken into account when designing the electrical distribution system of the vessel. A wire is not just any wire. There is a reason and a purpose for the entire electrical system. The only changes in the electrical system should be for expedient repairs and approved modifications. Do not modify electrical systems without proper authority. FM 55-509-1 CONDUCTOR INSULATION To be useful and safe, electric current must be forced to flow only where it is needed. It must be channeled from the power source to a useful load. In general, current-carrying conductors must not be allowed to come in contact with one another, their supporting hardware, or personnel working near them. To accomplish this, conductors are coated or wrapped with various materials. These materials have such a high resistance that they are, for all purposes, nonconductors. They are generally referred to as insulators or insulating material. Only the necessary minimum of insulation is applied to any particular type of conductor designed to do a particular job. This is done because of several factors. The expense, stiffening effect, and variety of physical and electrical conditions under which the conductors are operated must be considered. Therefore, a wide variety of insulated conductors is available to meet the requirements of any job. Two fundamental properties of insulating materials, such as rubber, glass, asbestos, and plastic, are insulation resistance and dielectric strength. These are two entirely different and distinct properties. Insulation resistance is the resistance to current leakage through the insulation materials. Insulation resistance can be measured by means of a megger without damaging the insulation. Information so obtained serves as a useful guide in appraising the general condition of the insulation. Clean, dry insulation having cracks or other faults may show a high resistance but would not be suitable for use. Megger testing does not damage the cable. This is one form of nondestructive testing. Dielectric strength is the ability of the insulation to withstand potential difference. It is usually expressed in terms of the voltage at which the insulation fails because of the electrostatic stress. Maximum dielectric strength values can be measured only by raising the voltage of a test sample until the insulation breaks down. When the dielectric strength is tested, the cable insulation is damaged. This is an example of destructive testing. Figure 12-6 shows two types of insulated wire. One is a single, solid conductor. The other is a two-conductor cable with each stranded conductor covered with a rubber-type insulation. In each case, the rubber serves the same purpose: to confide the current to its conductor. Materials Marine cable insulation should be one of the following materials: Polyvinyl chloride (designated T). This is the most common type of insulation currently used on modern vessels. It is a form of polymerized vinyl compound, resin, or plastic. The maximum conductor temperature that the insulation can handle is 75C. The voltage range is a maximum of 600 volts. The maximum allowable ambient temperature is 50C. It is of thermoplastic construction. This means it becomes soft when heated and rigid when cooled and cured. Polyvinyl chlorideprotected cable provides a nonmetallic rigid sheathed cable. It is commonly called PVC. WARNING This product produces extremely toxic vapors when ignited. When selecting this type of cable, a designation of “LS” (low smoke) indicates insulation modifications have been made to reduce these toxic gases. Ethylene propylene rubber (designated E). This insulation is thermosetting (not reshapeable). The maximum conductor temperature that the insulation can handle is 90C. The maximum allowable ambient temperature is 60C. It is normally used for up to 2,000 volts. For special applications, a maximum of 5,000 volts may be used. Cross-linked polyethylene (designated X). This insulation is thermosetting. The maximum conductor temperature it can handle is 90C. The maximum allowable ambient temperature is 60C. It is used from 2,001 to 5,000 volts. 12-9 FM 55-509-1 Mineral (MI) (designated M). This is a refactory material made of magnesium oxide that is highly compressed to provide the properties needed for insulation. The maximum conductor temperature that the insulation can handle is 85C. The ambient temperature is specified by distinct design only. Some special applications allow a maximum conductor temperature of 250C. Care must be taken when considering cable end fittings. See IEEE Standard 45, Table A-21, for ampacity. Silicon rubber (designated S). The maximum conductor temperature that the insulation can handle is 100C. The maximum allowable ambient temperature is 70C. It may be used in specific applications up to 5,000 volts. Impregnated glass, varnished cloth (designated GTV). The outside covering consists of a composite wall of glass or varnished cloth layers. Figure 12-7 shows the insulation helically wound around the cable. The maximum conductor temperature that the insulation can handle is 100C. The maximum allowable ambient temperature is 70C. 12-10 Moisture-Resistant Jackets An additional cable identification designation of I will be displayed on all cables with a moistureresistant jacket. The jacket will be composed of one of the following: Thermoplastic type T. Thermoplastic type T covered with a nylon coating, which changes the designator to type N. Thermosetting chlorosulfonated polyethylene (type CP). Separators and Fillers Separators may be provided inside the insulation to allow free stripping of cable conductors. Fillers eliminate air spaces in the cable (Figure 12-8). Marine cables will not permit the passage of water along the inside of a cable, nor will they support conductor oxidation. Additional insulating coding and specifications may be found in the Recommended Practice for Electrical Installations on Shipboard, the FM 55-509-1 Institute of Electrical and Electronics Engineers, Inc. (IEEE Standard 45). Enamel Coating The wire used on the coils of meters, relays, small transformers, motor windings, and so forth is called magnetic wire. It is insulated with an enamel coating. The enamel is a synthetic compound of cellulose acetate (wood pulp and magnesium). In the manufacturing process, the bare wire is passed through a solution of hot enamel and then cooled. This process is repeated until the wire acquires from 6 to 10 coatings. Enamel has a higher dielectric strength than rubber, thickness for thickness. It is not practical for large wires because of the expense and because the insulation is readily fractured when large wires are bent. Do not handle any enamel-covered conductors in a rough manner. Never set a disassembled component down on its enamel-coated wires. Figure 12-9 shows an enamel-coated wire. Enamel is the thinnest insulating coating that can be applied to wires. Hence, enamel-insulated magnetic wire makes smaller coils. Enameled wire is sometimes covered with one or more layers of cotton to protect the enamel from nicks, cuts, or abrasions. CONDUCTOR PROTECTION Wires and cables are generally subject to abuse. The type and amount of abuse depends on how and where they are installed and the manner in which they are used. Generally, except for overhead transmission lines, wires or cables are protected by some form of covering. The covering may be some type of insulator like rubber or plastic. Over this, an outer covering of fibrous braid may be applied. If conditions require, a metallic outer covering may be used. The type of outer covering used depends on how and where the wire or cable is to be used. Metallic armor provides a tough protective covering for wires or cables. The type, thickness, and kind of metal used to make armor depends on three factors: The use of the conductors. The circumstances under which the conductors are to be used. The amount of rough treatment that is expected. 12-11 FM 55-509-1 For additional information and specifications, refer to IEEE Standard 45-1983, Section 20.2, and Code of Federal Regulations, Title 46, Subpart 111.05-7. Cables should not be painted. Only when cables carry a potential of 5,000 volts or greater is yellow color-coding permissible. For general use, polyvinyl chloride-protected cable is replacing armor cable. WIRING TECHNIQUES Figure 12-10 shows an armored cable. Basketweave wire-braid armor is used wherever a light and flexible protection is needed. In the past, this type of armor covering has been used almost exclusively onboard ships. Wire braid is still used for special purposes in the engineering spaces. The individual wires that are woven together to form the braid are made out of aluminum or bronze. Besides mechanical protection, the wire braid also provides a static shield. This is important in radio work aboard ship to prevent interference from stray magnetic fields. Wire connections should be made inside the electrical component or inside watertight feeder, branch, or connection boxes. These boxes are generally brass or bronze. Watertight integrity is maintained by using stuffing tubes and gaskets. All the wire ends should be provided with lugs for connecting to bus terminals or for bolting and insulating individual wires together. During the course of normal electrical servicing, splicing wires is not authorized. Electrical cables must be continuous between the terminals except as outlined below: Component subassemblies may be spliced together. Splices may not be made to the subassembly power supply cables or branch circuits. Cables may be spliced to extend a circuit when a vessel is receiving authorized alterations. An extremely long cable may be spliced to allow its proper and efficient installation as explained above. CAUTION The armor braid must be grounded directly or indirectly to the hull In this situation, grounding does not mean that current will be carried through the armor braid under normal conditions. Rather, it means that an electrical path will be provided to the hull should an abnormal electrical fault cause current to flow in the armor. 12-12 Splicing is authorized for repair of damaged cables if the remainder of the cable is in good mechanical and electrical condition. The cable must be replaced in its entirety at the most opportune time. When electrical casualty requires expedient repairs, it is absolutely necessary that the repairs be made properly. A poor repair can prevent the operation of emergency equipment or develop into a tire. Any electric circuit is only as good as its weakest link. The basic requirement of any splice or connection is that it is both mechanically and electrically sound. FM 55-509-1 Quality workmanship and materials must be used to ensure lasting electrical contact, physical strength, and proper insulation. The most common methods of making splices and connections in electrical cables are explained below. Splicing Splices should be located in an area that is easily accessible and inspect able. The splice should consist of the following components: A conductor connector (terminal lugs, splice bolts, or splices) (Figure 12-11). A replacement jacket for the insulation. A shunt or suitable conductor to maintain the electrical continuity between two severed pieces of the armor braid. WARNING Continuity must be maintained between the armor covering and the vessel’s hull at all times. Removing Insulation The preferred method of removing insulation is with the use of a wire-stripping tool. The calibrated hand wire stripper in Figure 12-12 is excellent for even the most intricate electrical wire work. Hand Wire Stripper. The procedure for stripping wire with the hand wire stripper is as follows: Confirm the stripper’s operation. Use a spare wire to ensure the conductor is not marred by the cutting blades of the wire stripper. If the wire strippers have been used or abused, consult the manufacturer’s instructions to adjust the depth of the insulation cut. Insert the wire into the exact center of the correct cutting slot for the wire size to be stripped (Figure 12-13). Keep the wire perpendicular to the stripper. Close the handles together until the wire is held firmly by the jaws of the wire stripper. Continue to close the handles only until the insulation starts to separate. Do not use the stripper to pull the insulation from the conductor. Remove the wire from the wire stripper. Gently unwind the insulation so that the natural lay of the conductors is not disturbed. 12-13 FM 55-509-1 emergencies, the following procedure will keep conductor damage to a minimum. A sharp knife can be used to strip the insulation from a conductor. The procedure is much the same as sharpening a pencil. The knife should be held at a 60-degree angle to the conductor. Use extreme care to avoid cutting into the conductor. This procedure produces a taper on the cut insulation (Figure 12-14). Should the connection require solder, the tapered insulation will fuse more readily to the conductor. This fusion increases mechanical strength at the weak point and prevents the entrance of moisture. WIRE STRIPPING CAUTIONS The following minimum precautions are necessary when preparing conductors for repair: Ensure power is off before connecting or removing wires. NOTE: If you are going to solder the conductor, do not touch the conductor with your hands. The contamination from your hands will start to oxidize the conductor, and proper tinning and soldering will become more difficult. Knife Stripping. This is not recommended because it cuts into the conductor and effectively reduces the circular mil area at the fault. Nicks and cuts also reduce the mechanical strength of the conductor at a point that is naturally weaker then the section of cable where it is protected by insulation. However, the very nature of a vessel requires it to be placed in situations that must be satisfactorily managed until a more advantageous time arrives. In 12-14 Do not touch any conductor you intend to solder. Ensure the wire strippers are held perpendicular to the wire. Make sure the insulation is clean-cut with no frayed or ragged edges. Trim if necessary. This is particularly important when stripping armored cable. If the frayed armor insulation is allowed to chafe the replacement insulation at the spliced area, current may accidentally energize the exterior armor of the cable. This can be deadly. Ensure all insulation is removed from the conductor. Some wires are provided with a transparent layer between the conductor and the insulation. This must be removed. FM 55-509-1 Figure 12-16 shows how a two-conductor cable is joined to a similar size cable by means of staggering the splices. Take care to ensure that a short wire from one side of the cable is connected to a long wire from the other side of the cable being spliced. Then clamp the sharp ends firmly down on the conductor. Figure 12-16 shows a Western Union splice being staggered. Each conductor is insulated separately. WESTERN UNION SPLICE Figure 12-15 shows the steps to make a Western Union splice. First, prepare the wires for splicing. Remove enough insulation to make the splice and then clean the conductor. Next, bring the wires to a crossed position and make a long twist or bend in each wire. Then wrap one of the wire ends four or five times around the straight portion of the wire. Wrap the other end of the wire in a similar manner. Finally, press the ends of the wire down as close as possible to the straight portion of the wire. This prevents the sharp ends from puncturing the tape covering that is wrapped over the splice. SPLICE INSULATION The splices discussed above are those usually insulated with tape. The tape used to insulate a splice should be centered over the splice and should overlap the existing insulation by at least 2 inches on each side. The characteristics of rubber, friction, and plastic electrical tape are described below. Rubber Tape Latex (rubber) tape is a splicing compound. It is used where the original insulation was of a rubber compound. The tape is applied to the splice with a light tension so that each layer presses tightly against the one beneath it. This pressure causes the rubber tape to blend into a solid mass. Care must be taken to keep the spliced area watertight. Upon completion, insulation similar to the original is restored. WARNING STAGGERED SPLICES Joining small, multiconductor cables together presents somewhat of a problem. Each conductor must be spliced and taped. If the splices are contiguous to each other, the size of the joint becomes large and bulky. A smoother and less bulky joint may be made by staggering the splices. Some rubber tapes are made for special applications. These types are semiconducting and will pass current that presents a shock hazard. These types of tape are packaged similar to the latex rubber tape. Take care to insulate splices only with latex rubber insulation tape. 12-15 FM 55-509-1 In roll form, a layer of paper or treated cloth is between each layer of rubber tape. This layer prevents the latex from fusing while still on the roll. The paper or cloth is peeled off and discarded before the tape is applied to the splice. furnished by friction tape. Plastic electrical tape usually has a certain amount of stretch so that it easily conforms to the contour of the splice. Apply the rubber splicing tape smoothly and under tension so that no air exists between the layers. Start the first layer near the middle of the joint instead of the end. The diameter of the completed insulated joint should be somewhat greater than the overall diameter of the original wire, including the insulation. Since marine cables are stranded, it is necessary to use terminal lugs to hold the stranded wires together to help fasten the wires to terminal studs (Figure 12-17). This is the preferred method for connecting wires to terminals or to other wire ends. Generally, distribution system cable connectors will not use solder. The terminals used in electrical wiring are either of the soldered or crimped type. Terminals used in repair work must be of the size and type specified on the electrical wiring diagram for the particular equipment. Friction Tape Putting rubber over the splice means that the insulation has been restored to a great degree. It is also necessary to restore the protective covering. Friction tape is used for this purpose. WARNING Some friction tapes may conduct electrical current. Friction tape is a cotton cloth that has been treated with a sticky rubber compound. It comes in rolls similar to rubber tape, except that no paper or cloth separator is used. Friction tape is applied to rubber; however, it does not stretch. Start the friction tape slightly back on the original insulation. Wind the tape so each turn overlaps the one before it. Extend the tape over onto the insulation at the other end of the splice. From this point, wind a second layer back along the splice until the original starting point is reached. To complete the job, cut the tape and firmly press down the end. Plastic Electrical Tape Plastic electric tape has come into wide use in recent years. It has certain advantages over rubber and friction tape. For example, it withstands higher voltages for a given thickness. Single layers of certain plastic tapes will withstand several thousand volts without breaking down. In practice, however, several layers of tape are used to equal or slightly exceed the original thickness of the insulation. Additional layers of plastic electrical tape add the protection normally 12-16 TERMINAL LUGS FM 55-509-1 The increased use of crimp on terminals is a result of the limitations of soldered terminals. The quality of soldered connections depends mostly on the operator’s skill. Other factors, such as temperature, flux, cleanliness, oxides, and insulation damage due to heat, also add to defective connections. An advantage of crimp on solderless terminal lugs is that they require relatively little operator skill to use. Another advantage is that the only tool needed is the crimping tool. This allows terminal lugs to be applied with a minimum of time and effort. The connections are made more rapidly and are cleaner and more uniform in construction. Because of the pressures exerted and the material used, the crimped connection or splice, properly made, is both mechanically and electrically sound. Figure 12-17 shows some of the basic types of terminals. There are several variations of these basic types, such as the use of a slot instead of a terminal hole, three- and fourway splice type connectors, and insulation covering. Figure 12-18 shows how to determine the amount of insulation to remove from the wire. Solderless terminals may be of the insulated type. The barrel of the terminal or splice is enclosed in an insulating material. The insulation is compressed along with the terminal barrel when it is crimped, but it is not damaged in the process (Figure 12-19). Aluminum Terminals and Splices Do not use aluminum terminals, connectors, or wires interchangeably with copper wires and connectors. Copper and aluminum expand at different rates and will become loose over a period of time. Electrolysis also takes place. The two dissimilar metals and the salt air will create a chemical reaction that will eat away the materials. Also, never use an aluminum crimping tool for compressing copper hardware. Preinsulated Terminal Lugs The use of preinsulated terminal lugs and splices has become the most common method for copper wire termination and splicing in recent years. It is by far the best and easiest method. Many tools are used for crimping terminal lugs and splices. Small diameter copper wires are terminated with solderless, preinsulated copper terminal lugs. As Figure 12-20 shows, the insulation is part of the terminal lug. It extends beyond the barrel so that it covers a portion of the wire insulation. This makes the use of spaghetti or heat shrink tubing unnecessary. Preinsulated terminal lugs also have an insulation support (a metal reinforced sleeve) beneath the insulation for extra supporting strength of the wire insulation. Some preinsulated terminals fit more than one size of wire. The insulation is color-coded, and the range of wire sizes is marked on the tongue. This identifies the wire sizes that can be terminated with each of the terminal lug sizes (Table 12-6). For crimping small copper terminal lugs, the MS90413 hand crimping tool is used for wire sizes 12-17 FM 55-509-1 AWG 26 to 14. The MS3316 tool is used for wire sizes 12 and 10. Figure 12-21 shows these tools. These hand crimping tools have a self-locking ratchet that prevents the tool from opening until the crimp is completed. These and other one-cycle compression tools (as outlined in ANSI/UL 4S6-1975[25]) are the preferred method of compression. After completing the compression, visually inspect the terminal or splice. Check for the following conditions: Soldering Tools Many types of soldering tools are in use today. Some of the more common types are the soldering iron, soldering gun, resistance soldering set, and pencil iron. The main concern when selecting a soldering tool is the selection of the wattage. Table 12-7 provides a guide for determining the correct wattage for the size wire. Indent centered on the terminal barrel. Indent in line with the barrel. Terminal lug not cracked. Terminal lug insulation not cracked. Insulation grip crimped. SOLDERING The following discussion on basic soldering skills provides information needed when soldering wires to electrical connectors, splices, and terminals. 12-18 Soldering Iron. Figure 12-22 shows some types of common soldering irons. All high-quality soldering irons operate in the temperature range of 500 to 600F. Even the little 25-watt midget irons produce this temperature. The important difference in iron sizes is not the temperature, but the wattage. The wattage, or thermal inertia, is the capacity of the iron to generate and maintain a satisfactory temperature while giving up heat to the joint to be soldered. Although it is not practical to solder large conductors with a 25-watt iron, this iron is suitable for replacing a half-watt resistor in an electronic circuit or soldering a miniature connector. One advantage of using a small iron for small work is that it is light and easy to handle and has a small tip which is easily used in close places. Even though its temperature is high enough, it does not have the thermal energy to solder a large conductor. FM 55-509-1 A well-designed iron is self-regulating. The resistance of its element increases with rising temperature, thus limiting the flow of current. Figure 12-23 shows some tip shapes of the soldering irons in common use in the Army. An iron is always tinned prior to soldering a component in a circuit. After extended use, the tip tends to become pitted due to oxidation. Pitting indicates the need for retinning, as shown in Figure 12-24. Melt a piece of clean solder dipped in rosin flux over the soldering iron tip until all cavities are gone and the tip is completely shiny and silver-coated Figure 12-25). Use a lint-free paper towel to wipe the solder away. Do not shake the solder off. The larger soldering irons used exclusively for large conductors may require the tip to be filed first. The tip must then be tinned. Never clean the tip of an iron by dipping it into the flux container. All this does is contaminate the flux and add impurities to the next soldering project. Soldering Gun. The soldering gun (Figure 12-26) has gained popularity in recent years 12-19 FM 55-509-1 because it heats and cools rapidly. It is especially well-adapted to maintenance and troubleshooting work where only a small part of the technician’s time is spent soldering. damage the soldering gun. The gun is operated by a finger switch. The gun heats only while the switch is depressed. For most jobs, depress the trigger for no more than 10 seconds. Regulate the tip temperature by pulsating the gun on and off with the trigger. A transformer in the soldering gun supplies about a volt at high current to a loop of copper, which acts as the soldering tip. It heats to soldering temperature in 3 to 5 seconds. However, it may overheat to the point of incandescence if left on more than 30 seconds. This should be avoided because excess heat will burn the insulation of the wiring and The gun or iron should always be kept tinned to permit proper heat transfer to the connection to be soldered. Tinning also provides adequate control of the heat to prevent solder from building up on the tip. This reduces the chance of the solder spilling over to nearby components and causing short circuits. 12-20 FM 55-509-1 or acid flux cleans and prevents oxidation of the materials to be soldered. Never use acid core solder in soldering electronic components. Acid core flux causes corrosion and leads to shorts or open conditions. Avoid acid core solder whenever possible when soldering electrical components. Rosin is the only acceptable electrical soldering flux. Soldering Process When the soldering gun or iron is used, heating and cooling cycles tend to loosen the nuts or screws that hold the replaceable tips. When the nut on the gun becomes loose, the resistance of the tip increases. The temperature of the connection is increased and reduces the heat at the tip. Continued loosening may even cause an open circuit. Therefore, the tip should be tightened before and during operations as needed. CAUTION Never use soldering guns to solder solid state electronic components, such as resistors, capacitors, and transistors, because the heat generated can destroy the components. Cleanliness is necessary for efficient, effective soldering. Solder will not adhere to dirty, greasy, or oxidized surfaces. Heated metals tend to oxidize rapidly, so the oxide must be removed before soldering. Remove oxides, scale, and dirt by mechanical means, such as scraping and cutting with an abrasive cloth, or by chemical means. Remove grease or oil films with a suitable solvent (alcohol). Clean the connections to be soldered just before the actual soldering operation. Items to be soldered should normally be tinned before making a mechanical connection. Tinning is coating the material to be soldered with a light coat of solder (Figure 12-27). When the surface has been properly cleaned, place a thin, even coating of flux over the surface to be tinned. This will prevent oxidation while the part is being heated to soldering temperature. Rosin core solder is usually preferred in electrical work. However, a separate rosin flux may be used instead. Separate rosin flux is often used when wires in cable fabrication are tinned. Solder Ordinary soft solder is a fusible alloy consisting chiefly of tin and lead. It is used to join together two or more metals at temperatures below their melting point, A good general solder for electrical work is 60/40 solder; 60/40 represents the tin-to-lead ratio (percentage) of the solder. Eutectic solder (63/37) is an ideal solder combination. Eutectic solder goes from a solid to a liquid state without entering a mushy condition. The eutectic solder is used in electrical and electronic soldering processes. Solder comes on rolls. Many times the solder is hollow and contains a rosin or acid core. The rosin Placing a very thin coating of solder on the copper conductor is called tinning the wire. This is done before soldering the conductor to a terminal or other component. First, strip the insulation from the wire. Do not touch the copper conductor with your 12-21 FM 55-509-1 hands or any other oily objects. Apply heat from the soldering iron under the copper conductor. Then apply the solder to the top of the copper conductor. Starting at either the insulation end of the conductor or at the bitter end of the conductor, move the soldering iron as the solder melts and coat the entire length of the conductor. There is to be a complete, yet very fine solder coating. Every layer of the conductor should be easily defined underneath the bright solder coating. If the tinned lead is to be connected to a shaped device, such as a turret or post, then form the tinned portion to exactly match the shape. Ensure no open space is between the tinned wire and the point of connection. Figure 12-28 shows the exact relationship the stripped conductor maintains with the terminal post. The insulation is stripped back far enough to be one conductor diameter from the post. The bitter end of the conductor never goes farther around the post terminal than its widest point. This is the only way to ensure the best current flow. In earlier years, tinning was not extended to the insulation because the wire was thought to provide better performance when it was allowed to flex at the insulation. However, actual performance is improved when this weakened portion is not allowed to flex. Proper strength is maintained when there is a slight fusing between the soldier and the insulation. This gives more protection from vibration and maintains the conductor more steadily in application. Tinning to the insulation eliminates the 12-22 small movement that causes the conductor to break near the insulation. Do not tin wires that are to be crimped to solderless terminals or splices. Once the conductor has been tinned, start to prepare the terminal for soldering. Clean all oils and foreign material from the terminal. Remove all remaining solder and any leftover broken conductors. Use a soldering wick to remove old solder expeditiously. Place the wick on the old solder and the soldering tool on top of the wick (Figure 12-29). Capillary action draws the old solder off the terminals and into the wick. Clean the area with denatured alcohol and a white pencil-type typist eraser. Connect the tinned conductor to the terminal without placing your hands on either prepared surface. Apply heat and solder. Never apply the solder to the tip of the soldering iron. Always apply solder to the opposite side of the component lead. There should be just enough solder to penetrate and surround the terminal and conductor connection. There should not be so much solder that there is a bulge at the connection. If the conductor or terminal is moved while the solder is solidifying, a cold solder joint will result. This poor joint has a dull, grainy appearance. If there is any bridging, dimples, or holes, then the joint has been improperly made and must be remade. A properly soldered joint will be bright and shiny.