x architecture inc.

advertisement
MARK
1
AHU
MAKE
Engineered Air
MODEL
LM4/K
SUPPLY
AIRFLOW
(cfm)
(L/s)
4300
2029
ZONE SERVED
Building
SUPPLY FAN
E.S.P.
(" w.c.)
(Pa)
0.75
187
AIR HANDLING UNIT SCHEDULE
SUPPLY FAN
POWER
MINIMUM O/A
(hp)
(kW)
(cfm)
(L/s)
(%)
3.00
2.24
0
0
0.0
HEAT INPUT
(Btu/h)
(kW)
205000.0
60
FILTERS
MERV 8
(Btu/h)
0.0
COOLING CAPACITY
(kW) (tons) (Btu/h)
0
0
0.0
(kW)
0
ELECTRICAL
240V/1ph
NOTES
1
1. Refer to plans for dimensions of unit and location and sizes of return and supply connection.
MARK
1
HRV
MODEL
Venmar CES
HRV1200i
ZONE SERVED
AHU-1
SUPPLY
AIRFLOW
(cfm)
(L/s)
925
437
EXHAUST AIRFLOW
(cfm)
(L/s)
925
437
HEAT/ENERGY RECOVERY VENTILATION UNIT SCHEDULE
SUPPLY FAN
SUPPLY FAN
E.S.P.
POWER
EXHAUST FAN E.S.P.
(" w.c.)
(Pa)
(hp)
(kW)
("w.c.)
(Pa)
0.40
100
0.25
0.19
0.40
100
EXHAUST FAN POWER
(hp)
(kW)
0.25 hp
0.19
HEATING COIL
CAPACITY
(Btu/h)
(kW)
0.0
0
FILTERS
MERV-8
ELECTRICAL
120/1/60
NOTES
1
Certificate of Authorization
Epp Siepman Engineering Inc.
1. E.S.P. does not include unit filters.
MARK
1
DH
MAKE
Thermolec
13-05-10
No. 4035 Date:_______________
MODEL
FC
ELECTRIC REHEAT COIL SCHEDULE
AIR FlOW (CFM)
AIR FLOW (L/s)
MAX
MIN
MAX
MIN
925
925
437
437
ZONE SERVED
HRV-1
SIZE
18.5 kW
DUCT SIZE
500x200
ELECTRICAL
240V/1ph
CONTROL
SCR
NOTES
1
1. All units complete with air proving switch, disconnect switch
2. Provide duct temperature sensor with 0-10 vdc signal output with dial temperature control.
HWT
MARK
1
MAKE
A. O. Smith
MODEL
DEN-40
ZONE SERVED
Building
HOT WATER TANK SCHEDULE
RECOVERY
HEAT INPUT
(GPH)
(LPH)
4500 W
18
72
LOUVER SCHEDULE
L
L
Mark
1
2
Manufacturer
Ruskin
Ruskin
Model
PHB
PHB
WIDTH x HEIGHT
mm
mm
350
350
350
350
Notes
1,2
1,2
TEMP RISE
(°F)
100
(°C)
38
ELECTRICAL
240V/1ph
NOTES
1
SYSTEM
S
S
S
S
R
R
R
MARK
1
2
3
4
1
2
3
DIFFUSER & GRILLES SCHEDULE
MODEL
600X125/520/N/L/B12
SDGE/400/500X150/DD/A/B66
SDGE/500/500X150/DD/A/B66
SDGE/600/500X150/DD/A/B66
150X150/80/F/A/B12
250x250/80/F/A/B12
3168X448/530/N/L/B66
SIZE
600X125
600X125
500X150
500X150
150X150
250X250
3156X435
1. Refer to architectural reflected ceiling plan for mounting conditions and exact location.
2. Complete with steel opposed blade damper at grille.
3. Outside dimensions of grille face including boarder to be 3200mm X 480mm, outside edge to
outside edge.
4. Set horizontal deflection to 22.5 degrees.
NOTES
1,2,4
1,4
1,2,4
1,2,4
1
1,2
1,3
1
13-05-10
ISSUED FOR CONSTRUCTION
No.
DATE
ISSUANCE
Seal
1. All exterior louvers pre-finished and colour matched as per architects direction.
2. Width and depth are same dimension.
13-05-10
Architect
x
architecture inc.
120 Fort Street, Suite 103 Winnipeg, Manitoba R3C 1C7
204 318 2010
Engineer
epp siepman engineering inc.
mechanical engineers
303-100 Osborne St. South
Winnipeg, MB
R3L 1Y5
Project
p 204.453.1080
f 204.453.1335
ese@eppsiepman.com
BID OPPORTUNITY NO. 317-2013
St. Vital Park Pavillion
190 River Road
Sheet Title
SCHEDULES
Project No .
Sheet
1309
Date
2013-05-10
M3.1