Installation guide - Schneider Electric

advertisement
Layout advice
Run optimisation
Installation guide
Canalis KTA
CanBrass software
PD202428
CanBrass software can be used to design the busbar trunking line.
The easy-to-use program creates a graphic model of the line, determines the
length and draws up the list of Canalis KT parts to order.
The Canalis KT line is easy to specify simply by indicating the required dimensions.
However, it is strongly advised to use the shortest and simplest path possible
between the transformer and the switchboard.
It is important to carefully plan the layout of the transformer and switchboard in
order to use:
b the maximum number of standard components rather than made-to-measure
components,
b the minimum number of components for changing direction,
b straight made-to-measure components rather than made-to-measure
components for changing direction.
Advice
Before defining your busbar trunking run, it is recommended you pay particular
attention to the various parameters which could be detrimental to the installation.
DD210900
DD210895
Obstacles that obstruct the busbar trunking such as beams,
pipes, etc.
Design and
installation guide
DD210903
DD210902
Badly positioned places for going through walls and floors.
2
DD210896
DD210897
Joint positions in the middle of a partition wall.
Schneider Electric
K9AE41000
Layout advice
Run optimisation
Installation guide
Canalis KTA
Insufficient ceiling height.
DD210898
DD210899
If the busbar trunking must be installed edgewise between a transformer and
switchboard, ensure the ceiling height is sufficient for fitting the joint blocks from
the top.
Reserve a space between the busbar trunking and the ceiling equal to 2 times the
busbar trunking height (variable depending on the rating, see “Catalogue numbers
and dimensions”).
DD210903
DD210904
Going through a floor to bottom feed a switchboard on the
next floor.
DD210905
Difference in floor levels of 2 rooms.
Design and
installation guide
Also make sure that as the work progresses other tradesmen do not carry out
installations that could hinder your initial layout.
K9AE41000
Schneider Electric
3
Layout advice
Run optimisation
Installation guide
Canalis KTA
Examples of link optimisation
DD210910
Example 1
Reducing the number of changes of direction by modifying the switchboard or
transformer layout.
DD210911
Example 2
Use of 2 standard elbows in place of a made to measure zed by increasing
dimension “L”.
DD210912
Modification of the busbar trunking height
By slightly increasing dimension “Z”, replace a made to measure elbow feed
connector with a standard feed connector and standard elbow section.
When choosing the layout of the electrical installation, it is important care is taken
when positioning the neutral between the transformer and the switchboard.
If the neutral position is different to that planned, it is recommended the transformer
is moved, if possible, to align the neutral with respect to the switchboard’s neutral.
When it is not possible to move the transformer, it is recommended the phase order
in the switchboard is inversed.
If this cannot be done, use the phase and neutral transposition section.
DD210780
Design and
installation guide
Neutral position
KTAppppTNp10
KTAppppTPp10
4
Schneider Electric
K9AE41000
Layout advice
Positioning and supports
Installation guide
DD210935
Canalis KTA
Edgewise passage through
partition wall
DD210933
DD210932
Flat passage through partition wall
Rating (A)
Height H (mm)
Re-filling recommendation
800
74
1000
104
1250
124
1600
164
2000
204
2500
244
3200
324
4000
404
DD210934
We recommend re-filling is carried out as follows.
K9AE41000
Schneider Electric
Design and
installation guide
Rock wool
Promatect 100
Plaster finishing
5
Layout advice
Positioning and supports
Installation guide
Canalis KTA
A support point as close as possible to the connections is needed because
transformers, generator sets and switchboards must not support the weight of the
busbar trunking.
In some industries, for service continuity reasons, transformers may be replaced
quickly. The busbar trunking must be able to support itself.
Edgewise horizontal installation
DD210930
The maximum recommended distance between supports is 3 metres.
In all cases, provide for 2 supports for 4 metre sections.
For clamping busbar trunking to support brackets, see page K9AE41000/16.
Flat horizontal installation
DD210931
The recommended distance between supports is 2 metres. In addition, a support
must be placed at 300 or 400 mm from the joint block axis.
For clamping busbar trunking to support brackets, see page K9AE41000/16.
Example of spreading out supports
Design and
installation guide
DD210929
Plan for a maximum distance between supports of 3 metres.
6
Schneider Electric
K9AE41000
Layout advice
Positioning and supports
Installation guide
Canalis KTA
Defining the layout, dimensions to be
provided
DD210924
The position of the joint block with respect to the transformer axes and switchboard
edges (defined in the “Installation guide”).
Edgewise installation
DD210928
Rating (A)
Height H (mm)
800
74
1000
104
1250
124
1600
164
2000
204
2500
244
3200
324
4000
404
Edgewise installation
Design and
installation guide
DD210925
Distance between busbar trunking
(without tap-off units)
Flat installation
DD210927
Distance of the busbar trunking from
the wall
(1) Provide 2 times the height if the joint block must be fitted from the top.
Direction of fitting joint blocks.
DD210926
Flat installation
Direction of fitting joint blocks.
K9AE41000
Schneider Electric
7
Layout advice
Anticipate unexpected worksite
problems
Installation guide
Canalis KTA
In order to cope with dimensional differences between the drawings and actual
dimensions, it is desirable to provide an adjustable section or to leave a section
undecided for each partial run.
Adjustable section
DD202483
It has an initial length of 1300 mm and can be reduced or extended by the
installation contractor at the worksite (± 200 mm).
By planning the use of an adjustable section when producing the drawings, it can
be ordered with the rest of the material, without needing to wait until the job is
finished. It therefore allows the overall project completion time to be reduced.
DD210908
Allow a nominal dimension of 1300 mm on the drawing to guarantee an adjustment
of ± 200 mm on-site.
This section will be ordered after the gap to be filled has been measured at the end
of the job. To optimise its delivery to site, prefer a straight section with a length of
less than 2 metres rather than made to measure elbows.
1: Standard straight
section.
2: Made to measure
elbow.
DD210906
DD202390
Undecided section
DD210907
3: Made to measure
straight section.
4: Standard elbow.
Layout recommendations for adjustable
or undecided sections
In order to provide for the place needed for an adjustable or undecided section,
install the elbows and the sections attached to the elbows in each angle (support
each assembly using 2 supports on each straight section).
DD210994
Design and
installation guide
DD210908
On the drawing, provide a minimum dimension of 700 mm to guarantee an
adjustment of ± 200 mm on-site. The minimum length of straight sections being
equal to 500 mm.
And then complete the layout with standard and made to measure straight
sections.
8
Schneider Electric
K9AE41000
Layout advice
Tips for determining dimensions at
the worksite
Installation guide
Canalis KTA
Straight section
DD210913
The nominal length “L” of a straight section is measured from the axis of the
joint block to the other axis of the joint block, in millimetres (the joint block axis is
located 20 mm from the end of the bars).
Dimension L of the standard or made to measure section = x - 40 mm.
(1) : For the different busbar trunking heights, see page K9AE41000/7.
(2) : See “Run sections” in “Catalogue numbers and Dimensions”.
x : measured dimension.
Example: x = 1860 mm hence L = 1860 - 40 = 1820 mm.
Flat elbows
Change-of-directions
DD210918
DD210916
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
Design and
installation guide
A and B: See “Changes of direction” in “Catalogue numbers
and Dimensions”.
“Flat” elbow, external positioning
A = A1 + A2 + (140 / 2) - 20
“Flat” elbow, internal positioning
A = A1 - A2 - (140 / 2) - 20
(1) See “Changes of direction” in “Catalogue numbers and Dimensions”.
K9AE41000
Schneider Electric
9
Layout advice
Tips for determining dimensions at
the worksite
Installation guide
Canalis KTA
DD210917
Edgewise elbows
DD210919
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
A and B: See “Changes of direction” in “Catalogue numbers
and Dimensions”.
“Edgewise” elbow, external
positioning
A = A1 + A2 + (H / 2) - 20
“Edgewise” elbow, internal
positioning
A = A1 - A2 - (H / 2) - 20
(1) See “Changes of direction” in “Catalogue numbers and Dimensions”.
DD210921
Flat Zed
Design and
installation guide
DD210922
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
The nominal length of the intermediary branch(es) is measured from the axis of
one branch to the axis of another.
A, B and C: See “Changes of direction” in “Catalogue
numbers and Dimensions”.
B = B1 - B2
(1) See “Changes of direction” in “Catalogue numbers and Dimensions”.
10
Schneider Electric
K9AE41000
Layout advice
Tips for determining dimensions at
the worksite
Installation guide
Canalis KTA
DD210920
Edgewise Zed
DD210923
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
The nominal length of the intermediary branch(es) is measured from the axis of
one branch to the axis of another.
A, B and C: See “Changes of direction” in “Catalogue
numbers and Dimensions”.
B = B1 - B2
(1) See “Changes of direction” in “Catalogue numbers and Dimensions”.
Definition of final section parameters
Reminder: the final section should preferably be a straight section.
Take into account the neutral position when choosing the section.
DD210914
Tools
Tape
measure
Spirit level
Lead line
Stick
Ruler
Laser or infra-red reader
Design and
installation guide
DD210915
Their use
K9AE41000
Schneider Electric
11
Horizontal distribution
Positioning the tap-off units
Installation guide
Canalis KTA
PD202398
It is possible to combine the following in the same installation:
b straight transport sections with straight sections containing fixed or plug-on tapoff points,
b straight sections of different lengths,
b straight sections with different numbers of fixed or plug-on tap-off points,
b …
Positioning the tap-off units on the
busbar trunking
DD210938
Several configurations are possible.
Some examples:
b on a 2000 mm straight section with plug-on tap-off points (KTAppppEDp20):
v 3 x 160 A circuit breaker tap-off units:
DD210936
v 1 x 400 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit,
DD210939
v 3 x 160 A fuse tap-off units:
DD210996
v 1 x 400 A fuse tap-off unit, 1 x 250 A fuse tap-off unit and 1 x160 A fuse tap-off
unit:
b on a 4000 mm straight section with fixed tap-off points (KTAppppEBp40):
v 1 x 400 to 630 A fixed tap-off unit and 1 x 800 to 1000 A fixed tap-off unit:
DD210937
Design and
installation guide
DD210995
b on a 4000 mm straight section with plug-on tap-off points (KTAppppEDp40):
v 1 x 400 A circuit breaker tap-off unit, 1 x 250 A circuit breaker tap-off unit and 1 x
160 A circuit breaker tap-off unit:
Cable exit.
12
Schneider Electric
K9AE41000
Horizontal distribution
Tap-off units
Installation guide
Canalis KTA
DD210997
When the tap-off units have to be distributed along the length of the busbar
trunking, use 2 metre sections and alternate the tap-off point positions.
Recommendations for installing
2 parallel busbar trunking runs
For an installation with tap-off units, provide for a between centres distance that
takes into account the minimum dimension of 100 mm and the dimensions A and B
of the tap-off units.
DD210940
Type
Circuit
breaker
tap-off units
Tap-off unit door opening
Cat. no.
Dimensions
(mm)
A
B
KSB160DCp 160 150
KSB250DCp 240 160
KSB400DCp 240
KTB0630CBp 175
160
KTB1000CBp 275
Fuse tap-off KSB160SEp 150
units
KSB250SEp 250
275
KSB400SEp 440
160
175
150
160
DD210941
Provide for a minimum distance of 1000 mm between the busbar trunking and the
ceiling to allow for the opening of tap-off unit doors.
Type
Circuit
breaker
tap-off units
Cat. no.
Dimensions
(mm)
X
E(1)
KSB160DCp 625.5 246
KSB250DCp 726.5 300
KSB400DCp 976,5
Fuse tap-off KSB160SEp 577,5
units
KSB250SEp 777
KSB400SEp 855
350
207
258
316
Design and
installation guide
Installing an isolator or run protective
device
DD210942
(1) With the handle.
Rating (A)
1000
1250
1600
2000
2500
3200
K9AE41000
Schneider Electric
Dimensions (mm)
A
B
159
529
149
539
129
559
109
579
89
599
98
662
13
Horizontal distribution
Checking and compensating for
expansion
Installation guide
Canalis KTA
DD202446
Expansion poses a problem when:
b the runs are made up of long straight sections,
b when the busbar trunking passes through an expansion joint between two
buildings.
Long part runs
Electrical busbar trunking can be subjected to a multitude of load variations during
its service life (e.g. day / night, summer / winter) which cause temperature rise
differences and thus variable expansions.
To absorb expansion in a Canalis KT busbar trunking, a specific section must be
used: the expansion section.
Horizontal runs without tap-off units
If the busbar trunking length is greater than 30 metres, provide for expansion
sections and appropriate blocking means. The ends and, in some cases, the
centre of part runs must be blocked in order to direct the extensions towards the
expansion sections.
DD210998
Layout of expansion sections and blocking means for the following busbar
trunking lengths:
b 0 to 30 metres:
DD210999
b 31 to 60 metres:
DD211000
b 61 to 90 metres:
DD211001
91 to 120 metres:
Design and
installation guide
Blocked fixing supports,
Expansion section,
Direction of expansion.
14
Schneider Electric
K9AE41000
Horizontal distribution
Checking and compensating for
expansion
Installation guide
Canalis KTA
Horizontal runs with tap-off units
DD211002
Layout of expansion sections and blocking means for the following busbar trunking
lengths:
b 0 to 30 metres:
DD211003
b 31 to 60 metres:
DD211004
b 61 to 120 metres:
Blocked fixing supports,
Expansion section,
Direction of expansion,
Tap-off unit.
DD2111005
Transformer / switchboard links
Design and
installation guide
Blocked fixing supports,
Expansion section,
Direction of expansion.
K9AE41000
Schneider Electric
15
Horizontal distribution
Checking and compensating for
expansion
Installation guide
Canalis KTA
Rules for fixing busbar trunking to the supports
DD211006
For correct system operation, the expansion of the part run in question must be
directed towards the expansion section.
This implies:
b the busbar trunking must be free from all longitudinal movement on its supports,
b the expansion section must be blocked on the opposite side to that by which it is
pushed.
1
2
Free fixings.
Blocked fixings.
Direction of expansion.
Installation of free fixings
Flat assembly
DD211008
DD211007
Edgewise assembly
Installation of blocked fixings
DD211010
Flat assembly
Design and
installation guide
DD211009
Edgewise assembly
16
Schneider Electric
K9AE41000
Horizontal distribution
Checking and compensating for
expansion
Installation guide
Canalis KTA
Passing through a joint between
2 buildings
DD211012
Here, the expansion section allows the busbar trunking to absorb the forces due to
the relative movement between the 2 buildings.
Building A
Building B
DD211011
Blocked fixing supports.
1 Blocked fixings.
Installation of blocked fixings
Flat assembly
Design and
installation guide
DD211010
DD211009
Edgewise assembly
K9AE41000
Schneider Electric
17
Installation guide
Rising mains
General
Canalis KTA
PD202319
Canalis KT enables power distribution to each floor of multi-storey buildings (office
buildings, hotels, hospitals, etc).
In this application, Canalis KT retains all its construction principles:
Vertically mounted, the protection degree of the KT busbar trunking is IP55 as
standard.
Installing a rising main
1 Installation principle
Installation at each floor of:
b a 2 metre distribution section,
b a made to measure transport section to go through the floor slab,
b a busbar trunking support,
b up to 3 x 160 A tap-off units or a 250 or 400 A tap-off unit and a 160 A tap-off unit.
2 Installation feed
The installation feed is achieved using either a cable box or by direct connection to
an electrical distribution switchboard.
3 Busbar trunking supports
The supports fix the vertical run section to the building structure. a floor slab
support. It can be fixed to either the wall, to a wall bracket or directly to the floor,
This type of fixing support has the following advantages:
b fitting to either the wall, to a wall bracket or directly to the floor,
b height adjustment to make up for positioning errors,
b depth adjustment from 50 to100 mm,
b spring adjustment to ensure distribution of the load at each floor,
b absorption of building stresses with respect to the busbar trunking (expansion,
vibration, etc) thanks to the springs.
4 Tap-off units
Design and
installation guide
All Canalis KS tap-off units can be mounted vertically on the Canalis KT without the
risk of interference with the supports.
2
Schneider Electric
K9AE45000
Rising mains
Positioning the busbar trunking
Installation guide
Canalis KTA
DD210960
Positioning the neutral
The busbar trunking must be positioned with the neutral on the right.
Positioning the joint block
It is important the joint block is not positioned in the floor slab.
DD210961
We recommend you provide for a distance of:
b 400 mm between the floor slab and the joint block axis to be able to install a
support to the wall or wall bracket to facilitate the re-filling of the hole and to cope
with possible building faults (e.g. screed not indicated on the drawings). Provide
500 mm for a floor fixing.
b 200 mm between the upper joint block and the ceiling to allow the busbar
trunking to be boxed-in when filling-in the hole with plaster or concrete.
Positioning the tap-offs
Design and
installation guide
The run sections are fitted with 3 tap-off points. Spaced at 500 mm intervals, they
provide a high density of tap-offs per floor.
K9AE45000
Schneider Electric
3
Rising mains
Positioning the tap-off units
Installation guide
Canalis KTA
DD210962
Positioning the tap-off units on the busbar trunking
Several configurations are possible.
Some examples:
1 - 3 x 160 A circuit breaker tap-off units,
2 - 1 x 400 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit,
3 - 3 x 160 A fuse tap-off units,
4 - 1 x 800 to 1000 A bolted tap-off unit.
Cable exit
DD210964
R = 12 x Ø of cable
Recommendations for installing 2 rising mains in parallel
Cable exit.
DD210954
For an installation with tap-off units, provide for a between centres distance that
takes into account the minimum dimension of 100 mm and the dimensions A and B
of the tap-off units.
Type
Circuit
breaker
tap-off units
Cat. no
Dimensions
(mm)
A
B
KSB160DCp 160 150
KSB250DCp 240 160
KSB400DCp 240 160
KTB0630CBp 175 175
Design and
installation guide
KTB1000CBp 275
Fuse tap-off KSB160SEp 150
units
KSB250SEp 250
KSB400SEp 440
275
150
160
160
Tap-off unit door opening
DD210963
If installed in a technical room, provide for a minimum distance of 1000 mm
between the busbar trunking and the wall in order to be able to open the doors of
the tap-off units.
4
Schneider Electric
K9AE45000
Rising mains
Positioning of supports
Installation guide
Canalis KTA
DD210968
2 fixing systems are available:
b a rear wall fixing system for 800 A to 1600 A busbar trunking,
b a side wall fixing system for 2000 A to 4000 A busbar trunking.
DD210967
Wall support
Wall drilling drawing to fix
the support.
800 to 1600 A
2000 to 4000 A
(1) Dimensions with free springs.
Y : 50 mm minimum to 100 mm maximum
DD210966
Wall bracket support (if Y > 100 mm)
X u 400.
2000 to 4000 A
Design and
installation guide
800 to 1600 A
DD210965
Floor support
800 to 1600 A
K9AE45000
Schneider Electric
2000 to 4000 A
5
Rising mains
Going through the floor
Installation guide
Canalis KTA
DD210977
Going through the floor
2000
2500
3200
Design and
installation guide
4000
DD210969
DD210970
DD210971
DD210972
DD210973
1600
DD210974
1250
DD210975
1000
Height H (mm)
DD210976
Rating (A)
800
Re-filling recommendation
DD210934
We recommend re-filling is carried out as follows.
Rock wool
Promatec 100
Plaster finishing
6
Schneider Electric
K9AE45000
Rising mains
Installation with feed via a cable box
or direct onto the switchboard
Installation guide
Canalis KTA
Design and
installation guide
Installation with feed via a cable box.
DD210979
2 possibilities:
b installation with feed direct to the switchboard,
b installation with feed via a cable box.
K9AE45000
Schneider Electric
7
Rising mains
Installation with feed via a cable box
or direct onto the switchboard
Installation guide
Design and
installation guide
Installation with feed direct to the
switchboard
DD211013
Canalis KTA
8
Schneider Electric
K9AE45000
Installation guide
Panorama of
connection solutions
Canalis KTA
The Schneider Electric system
The comprehensive Schneider Electric system makes it simple to design a
complete transformer / Canalis KT/ switchboard installation.
Using dedicated interfaces, the trunking connects directly to the dry-type
transformer and the switchboard for:
b tested and standardised connections,
b fast and flexible installation,
b shorter lead times.
Advantages
b No design work for the connections.
b Simplified layout design:
v pre-defined position of the jointing unit,
v simplified routing (only three dimensions required),
v smaller size (no additional covers required).
b Transformer and switchboard supplied with connections already mounted.
b Short lead times and fewer catalogue numbers for connections.
b Adaptable on the worksite:
v transformer end: ± 15 mm adjustments along all three axes,
v switchboard end: phases can be inverted.
b Continuity of service:
v transformer can be replaced in less than one hour,
v transformer, trunking and switchboard designed to be used together.
b Safety:
v trunking fully tested in compliance with IEC 60439-1 and 2,
v compliance with standards and installation rules,
v excellent fire-withstand capability.
b Comfort:
v low level of electromagnetic radiation,
v no noise.
Connection to an
LV switchboard
using a dedicated
interface, see page
K9AE42000/6.
Design and
installation guide
PD202432
Connection to a
dry-type transformer
using a dedicated
interface, see page
K9AE43000/4.
2
Schneider Electric
K9AE42000
Installation guide
Panorama of
connection solutions
Canalis KTA
Connection to an
LV switchboard
using a dedicated
interface, see page
K9AE42000/6.
PD202301
Universal
connection to a
dry-type transformer,
see page
K9AE43000/7.
Universal
connection
to an oil-filled
transformer,
see page
K9AE44000/4.
Design and
installation guide
PD202302
Universal
connection to an
LV switchboard,
see page
K9AE42000/12.
K9AE42000
Schneider Electric
3
Installation guide
Connection to LV switchboards
Selection guide
Canalis KTA
This guide may be used to:
v select the connection best suited to your installation (incoming direction, trunking
installed flat or edgewise, different phase order),
v check the total height of the connection with respect to the ceiling, i.e.
dimension Z0 + Z2 (100 mm minimum clearance required between top of
connection and ceiling),
v optimise the connection by ensuring that (Z0 + Z1)switchboard = (Z0 + Z1)transformer to
avoid having to use elbows and zed units,
v position the fixing devices used to support the trunking.
Connection with an interface
DD210755
SB2
DD210754
SB1
Direct connection
Without protective covers
SB3
DD21v0753
Design and
installation guide
PD202304
Type of connection
see page K9AE42000/6
see page K9AE42000/6
As per manufacturing drawing
minimum
74
82
138
maximum
-
-
472
Z2
Z1 + 140
Z1 + H
Z1 + H
Phase order can be changed
b
b
Mounting in workshop
b
b
Exit through front or rear
b
Z0
Z1
b
Exit through left or right side
b
Edgewise installation
b
Flat installation
4
b
b
Schneider Electric
K9AE42000
Canalis KTA
Trunking cross-section
Rating (A)
800(1)
1000
1250
1600
2000
2500
3200
4000
With protective covers
SB7
DD210759
SB6
DD210758
SB5
DD210757
SB4
As per manufacturing drawings
As per manufacturing drawings
As per manufacturing drawings
As per manufacturing drawings
473
130
465
H = 74 to 124 mm
195 - H / 2
H = 164 to 244 mm
255 - H / 2
H = 324 to 404 mm
355 - H / 2
-
464
-
-
Z1 + H
Z1 + 140
Z1 + 140
H = 74 or 104 or 124 mm
H = 164 or 204 or 244 mm
H = 324 or 404 mm
b
Design and
installation guide
DD210867
DD202180
Height H (mm)
Width W (mm)
DD210756
gs
Connection to LV switchboards
Selection guide
Installation guide
Z1 + H / 2 + 115
Z1 + H / 2 + 175
Z1 + H / 2 + 255
b
b
b
b
b
b
b
b
K9AE42000
b
Schneider Electric
5
Connection to Okken and
Prisma Plus LV switchboards
By Canalis interface
Installation guide
Canalis KTA
PD202328
Switchboards can be equipped with connections for Canalis KT. Jointing with the
switchboard is via a standard run component (straight length, elbow, etc.) and a
jointing unit (identical to those used between line components). The trunking enters
the switchboard via the top (roof).
Switchboard connections are available from 800 to 4000 A.
Type of
switchboard
Rating of trunking Type of circuit
(A)
breaker
Type of connection
Prisma Plus
800 to 1600
Compact NS
Top direct and rear
Masterpact NT
Top direct and rear
Okken
800 to 3200
Masterpact NW
Top direct and rear
4000
Masterpact NW
Rear
800 to 4000
Masterpact NW
Top direct and rear
Connections are tested and qualified under normal operating conditions in
terms of temperature rise (∆θ) and short-circuit currents (Isc).
The panel builder receives and connects the Canalis KT interface in the workshop.
The phase order at the interface output can be adapted if necessary (this
information must be forwarded to the panel builder).
The switchboard is then delivered to the site and the trunking can be rapidly
connected using a simple jointing unit with torque nuts to ensure the correct
tightening torque.
Compatibility between Canalis KT and the interface in the switchboard(1)
Canalis KT
Cat. no.
Rating
(A)
Height
(mm)
Sealing kit
KTA0800
KTA1000
KTA1250
KTA1600
KTA2000
KTA2500
KTA3200
KTA4000
800
1000
1250
1600
2000
2500
3200
4000
74
104
124
164
204
244
324
404
KTB0074TT01
KTB0104TT01
KTB0124TT01
KTB0164TT01
KTB0204TT01
KTB0244TT01
KTB0324TT01
KTB0404TT01
Circuit breakers in Okken et Prisma Plus switchboards
NS / NT / NW
NS / NW
800 and 1000 A 1250 A
1600 A
2000 A
2500 A
Interface 08 / 16
Interface 20 / 25
H164(2)
H244(2)
NW
3200 A
4000 A
Interface 32 Interface 40
H404(2)
H404(2)
(1) Coordination with a dry-type transformer, see the “Transformer” section, see page
K9AE43000/4.
(2) Height of the jointing unit in millimetres.
Phase order
Using the dedicated interface, it is possible to change the phase order if it is
different between the trunking and the switchboard.
DD210772
Design and
installation guide
The prefabricated connections installed in the switchboard are designed to operate
without derating and can therefore operate at the rated circuit breaker current.
6
Schneider Electric
K9AE42000
Connection to Okken
switchboards
By Canalis interface
Installation guide
Canalis KTA
Top direct connection (TDC)
DD202310
To 800 to 4000 A Masterpact NW circuit breakers
b Enclosure 600 or 1000 mm deep, access through the front.
Position of the jointing unit
Circuit breaker
Drawout, 3P/ 4P(1)
NW08 / 16
NW20 / 25
NW32
NW40
Dimensions (mm)
A
B
175
325
175
325
175
325
175
325
DD210761
(1) To order, see “Catalogue numbers”, page K9AE23000/4.
C
156
156
156
156
Design and
installation guide
Reference point
K9AE42000
Schneider Electric
7
Connection to Okken
switchboards
By Canalis interface
Installation guide
Canalis KTA
Rear connection (RC)
DD202311
To 800 to 4000 A Masterpact NW circuit breakers
b Enclosure 1000, 1200 or 1400 mm deep, access through the rear.
Position of the jointing unit
Circuit breaker
Drawout, 3P/ 4P(1) ,
top position
Drawout, 3P/ 4P(1) ,
medium position
Drawout, 3P/ 4P(1) ,
bottom position
Dimensions (mm)
A
Depth (mm)
1000 1200 1400
NW08 / 16
NW20 / 25
NW32
NW40
NW08 / 16
NW20 / 25
NW32
NW40
NW08 / 16
NW20 / 25
NW32
825
825
825
825
825
825
-
953
953
-
1225
1225
1225
B
C
363
363
363
363
363
363
363
363
363
363
363
317
317
317
156
942
942
942
881
1417
1417
1417
DD210763
(1) To order, see “Catalogue numbers”, page K9AE23000/4.
Depth: 1200 mm
Depth: 1400 mm
Design and
installation guide
DD202384
Top views
Depth: 1000 mm
Reference point
Bottom connection
8
For installations with connections through the bottom, please consult us.
Schneider Electric
K9AE42000
Connection to Prisma Plus
LV switchboards
By Canalis interface
Installation guide
Canalis KTA
Top direct connection (TDC)
DD202306
To a Compact NS 1250 or Masterpact NT 1200 circuit breaker
b Enclosure 400 mm deep, access through the front.
Position of the jointing unit
Circuit breaker
Fixed, 3P/ 4P(2)
Drawout, 3P/ 4P(2)
Dimensions(1) (mm)
A
B
C
NS800 / 1250
NT08 / 12
NS800 / 1250
or 08 / NT16
236
260
260
325
325
325
160
160
170
DD210765
(1) Dimensions measured from switchboard framework.
(2) To order, see “Catalogue numbers”, page K9AE23000/2.
Reference point
DD202304
To 800 to 3200 A Masterpact NW circuit breakers
b Enclosure 600 mm deep, access through the front.
Position of the jointing unit
Circuit breaker
Fixed, 3P/ 4P(2)
Drawout, 3P/ 4P(2)
Dimensions(1) (mm)
A
B
C
NW08 / 16
NW20 / 25
NW32
NW08 / 16
NW20 / 25
NW32
185
185
185
185
185
185
325
325
325
344
344
344
264
289
264
164
214
214
DD210767
Design and
installation guide
(1) Dimensions measured from switchboard framework.
(2) To order, see “Catalogue numbers”, page K9AE23000/2.
Reference point
K9AE42000
Schneider Electric
9
Connection to Prisma Plus
LV switchboards
By Canalis interface
Installation guide
Canalis KTA
Rear connection (RC)
DD202307
To a Compact NS 1600 or Masterpact NT 1600 circuit breaker
b Two enclosures combined:
v 1 enclosure, 400 mm deep, for the circuit breaker,
v 1 enclosure, 400 mm deep, for the Canalis KT/switchboard interface.
Position of the jointing unit
Circuit breaker
Fixed, 3P/ 4P(2)
Drawout, 3P/ 4P(2)
Dimensions(1) (mm)
A
B
C
NS800 / 1600
or NT08 / 16
NS800 / 1600
or NT08 / 16
638
325
160
638
325
170
DD210769
(1) Dimensions measured from switchboard framework.
(2) To order, see “Catalogue numbers”, page K9AE23000/2.
Reference point
DD202305
To 800 to 4000 A Masterpact NW circuit breakers
b Two enclosures combined:
v 1 enclosure, 600 mm deep, for the circuit breaker,
v 1 enclosure, 400 mm deep, for the Canalis KT/switchboard interface.
Position of the jointing unit
Disjoncteur
Fixed, 3P/ 4P(2)
Design and
installation guide
Drawout, 3P/ 4P(2)
Dimensions(1) (en mm)
A
B
C
NW08 / 16
NW20 / 25
NW32
NW40
NW08 / 16
NW20 / 25
NW32
NW40
815
757
774
790
815
815
815
790
325
325
325
325
317
342
317
325
264
414
414
750
414
414
339
700
DD210771
(1) Dimensions measured from switchboard framework.
(2) To order, see “Catalogue numbers”, page K9AE23000/2.
Reference point
10
Schneider Electric
K9AE42000
Connection to Okken and
Prisma Plus LV switchboards
By Canalis interface
Installation guide
Canalis KTA
Sealing kit
DD210775
DD202314
The sealing kit must be ordered with the KT trunking. The size of the trunking
determines that of the sealing kit. For the different types of kit, see the “Catalogue
numbers and dimensions” pages.
The kit includes a drilling and cut-out drawing for the switchboard roof.
DD210774
KTB0ppppTT01
It is advised to cut out the switchboard roof in the workshop.
Important. The dimensions are measured from switchboard framework.
Design and
installation guide
DD210776
Cut-out drawing (for all the ratings)
Centre lines.
K9AE42000
Schneider Electric
11
Connection to LV switchboards
By universal feed unit
Installation guide
Canalis KTA
PD202329
Canalis KT can be connected to switchboards via a universal connector. To simplify
the work, it is advised to fit the switchboard busbars with a distance between
centres of 115 mm.
Jointing with the switchboard is via a straight or elbow universal feed unit with a
straight or flat outlet.
Connections are made using torque nuts offering both ease of use and the
possibility of a visual check before energising.
Enclosure depth depending on the rating of the trunking
Rating of trunking (A)
If the order of the
phases in the trunking
and the switchboard is
different, it is advised to
invert the phases in the
switchboard. If that is not
possible, use the phase
and neutral crossover
components.
For more information,
see the “Description”
section, page
K9AE12000/4 and
“Catalogue numbers and
dimensions” section,
page K9AE21020/2.
DD210780
Phase order
DD210781
Design and
installation guide
DD210779
Busbars in switchboard
(recommended distance between
centres = 115 mm)
Minimum depth X of
switchboard (mm)
400
400
600
DD210778
1000 to 1250
1600 to 2500
3200 to 4000
Depth Y of universal feed
unit plate (mm)
230
350
510
KTAppppTNp10
KTAppppTPp10
12
Schneider Electric
K9AE42000
Installation guide
Connection to LV switchboards
By universal feed unit
Canalis KTA
Cut-out drawing
It is advised to cut out the switchboard roof in the workshop.
Cut-out for universal feeder unit, with distance between centres = 115 mm
Depth Y of universal feed unit plate (mm)
230
350
510
DD210782
Rating of trunking (A)
1000 à 1250
1600 à 2500
3200 à 4000
Design and
installation guide
Centre lines.
K9AE42000
Schneider Electric
13
Connection to LV switchboards
By feed and connection plates
Installation guide
Canalis KTA
PD202331
Connection plates are flexible copper bars, insulated or not, and drilled at one or
both ends. They are supplied with bolts, washers and torque nuts for connection to
straight or elbow universal feed units.
To simplify the work, it is advised to universal feed units with a distance between
centres of 115 mm.
Enclosure depth depending on the rating of the trunking
Rating of trunking (A)
1000 to 1250
1600 to 2500
3200 to 4000
Vertical incomer
Minimum depth X of
switchboard (mm)
400
400
600
Horizontal incomer
Design and
installation guide
DD210779
DD210783
DD202385
Universal feed unit
(recommended distance between
centres = 115 mm)
Depth Y of universal feed
unit plate (mm)
230
350
510
KTAppppERpp
14
Schneider Electric
K9AE42000
Connection to LV switchboards
By feed and connection plates
Installation guide
Canalis KTA
Selection of connection plates
The required number of connection plates is indicated in the table below.
Busbar trunking
rating (A)
Short-circuit withstand
1000 to 1600
2000 to 2500 3200
DD210789
DD210788
DD210786
DD210785
Connection
plates
DD210787
DD210764
Busbar trunking rating (A) Connection plates per phase
Number
Section (mm2)
1000
2
1000
1250
2
1000
1600
2
1000
2000
3
1500
2500
3
1500
3200
4
2000
4000
5
2500
4000
Short-circuit withstand table
DD202359
Short-time withstand current (Icw)
y 43 kA
43 kA y Icw y 50 kA
50 kA y Icw y 100 kA
Maximum distance between support
centres X (mm)
400
225
150
Vertical incomer
Phase order
DD210780
DD210781
DD210791
If the order of the phases in the trunking and the switchboard is different, it is
advised to invert the phases in the switchboard. If that is not possible, use the
phase and neutral crossover components.
For more information, see the “Description” section, section, page K9AE12000/4
and “Catalogue numbers and dimensions” section, page K9AE21020/2.
KTAppppTNp10
KTAppppTPp10
K9AE42000
Schneider Electric
15
Design and
installation guide
DD210790
DD202349
Horizontal incomer
Connection to LV switchboards
By feed and connection plates
Installation guide
Canalis KTA
Dimensions of protective covers
Horizontal incomer
DD202326
Rigid horizontal cover KTBppppCR1 for ER straight outlet feed connectors
type N1 to N6
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Dimensions (mm)
Y
D
230
220 to 475
350
220 to 475
510
220 to 475
G
220 to 475
220 to 475
220 to 475
Z
310 to 800
430 to 800
590 to 800
KTBppppCR1
Cut-out drawing
DD210953n
It is advised to cut out the switchboard roof in the workshop.
Design and
installation guide
Centre lines.
16
Schneider Electric
K9AE42000
Connection to LV switchboards
By feed and connection plates
Installation guide
Canalis KTA
DD202322
Vertical incomer
Rigid vertical cover KTBppppCR2 (400 to 800 mm height) for ER straight
outlet feed connectors type N1 to N6
Rating (A)
Dimensions (mm)
Y
D
G
Z
800 to 1250
230
220 to 475
220 to 475
400 to 800
1600 to 2500
350
220 to 475
220 to 475
400 to 800
3200 to 4000
510
220 to 475
220 to 475
400 to 800
KTBppppCR2
Cut-out drawing
DD210953n1
It is advised to cut out the switchboard roof in the workshop.
DD202324
Centre lines.
Cut-out drawing
It is advised to cut out the switchboard roof in the workshop.
DD210953n2
Design and
installation guide
KTBppppCR3
Rigid vertical cover KTBppppCR3 (100 to 400 mm height) for ER straight
outlet feed connectors type N1 to N6
Calibre (A)
Dimensions (mm)
Y
D
G
Z
800 to 1250
230
220 to 475 220 to 475 400 to 800
1600 to 2500
350
220 to 475 220 to 475 400 to 800
3200 to 4000
510
220 to 475 220 to 475 400 to 800
Centre lines.
K9AE42000
Schneider Electric
17
Connection to cast resin
transformers
Selection guide
Installation guide
Canalis KTA
This guide will allow you to:
v choose the connection best suited to your layout (incoming direction, flat or
edgewise busbar trunking, possibility of adjusting phase order),
v check the total height of the link with respect to the premises’ ceiling height,
dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link
and the ceiling),
v optimise your link whilst respecting the following rule:
(Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels,
v position the sections for the busbar trunking supports.
Universal connection
TS3
DD202490
TS4
230
238
According to manufacturer’s
drawing
350
According to manu
drawing
280
-
-
350
280(1)
Z2
Z1 + 140
Z1 + H
Z1 + H
420(1)
Selecting phase order
Fixed
Fixed
At time of order
At time of order
Front or rear exit
b
b
b
b
b
Z0
DD202488
DD202487
Connection with interface to Trihal transformers
TS1
TS2
DD202489
Design and
installation guide
PD202398
Type of connection
See page K9AE43000/4 See page K9AE43000/4
Z1 minimum
maximum
Right or left exit
Edgewise layout
Flat layout
b
b
b
(1) To use standard connection plates L = 406 mm in accordance with our recommendations.
2
Schneider Eletric
K9AE43000
Canalis KTA
Trunking cross-section
Rating (A)
800(1)
1000
1250
1600
2000
2500
3200
4000
TS7
TS8
DD202494
According to manufacturer’s
drawing
350
According to manufacturer’s drawing According to manufacturer’s
drawing
280
350
According to manufacturer’s
drawing
-
350(1)
280(1)
350(1)
-
Z1 + H
420(1)
At time of order
At time of order
H = 74 or 104 or Z1 + H / 2 + 115 500(1)
124 mm
H = 164 or 204 Z1 + H / 2 + 175
or 244 mm
H = 324 or
Z1 + H / 2 + 255
404 mm
At time of order
At time of order
b
b
Design and
installation guide
TS6
DD202492
TS5
DD202493
DD210867
DD202180
Height H (mm)
Width W (mm)
DD202491
ufacturer’s
Connection to cast resin
transformers
Selection guide
Installation guide
b
b
K9AE43000
Schneider Eletric
3
Installation guide
Connection to Trihal cast resin
transformers
By Canalis interface
Canalis KTA
PD202434
The Trihal dry-type transformers are supplied with a specific interface tested to
receive the Canalis KT busbar trunking. Jointing with the switchboard is achieved
using a standard run section (straight, elbow section, etc) and a joint block identical
to that for connecting run elements.
The Canalis KT/ dry type transformer interface, which is fitted to the transformer,
is designed to accept the transformer’s 25 % overload in the case of forced
ventilation.
The connections are tested and qualified in normal operating conditions with
respect to temperature rise (∆θ) and short-circuits (Isc).
The busbar trunking is quickly connected to the dry-type transformer using a simple
joint block with torque nuts, guaranteeing tightening torque.
Table of compatibility between Canalis KT and the connection interface for
naturally ventilated (AN) dry-type transformers.
Dry-type transformer
Canalis KT
Rating l nominal(1) Interface
(kVA)
(A)
Type Junction Rating (A)
Cross-section
Type
630
887
1
H124
1250
140 x 104
KTA1000
800
1126
2
H164
1600
140 x 124
KTA1250
1000
1408
3
H204
2000
140 x 164
KTA1600
1250
1760
4
H244
2500
140 x 204
KTA2000
1600
2253
5
H324
3200
140 x 244
KTA2500
2000
2816
6
H404
4000
140 x 324
KTA3200
2500
3520
7
H404
5000
140 x 404
(1) I is given as an indication only and is calculated with U - 410 V.
KTA4000
Table of compatibility between Canalis KT and the connection interface for
forced ventilated (AF) dry-type transformers.
Dry-type transformer
Canalis KT
Rating l nominal(1) Interface
(kVA)
(A)
Type Junction Rating (A)
Cross-section
Type
630
1108
1
H124
1250
140 x 124
1250
800
1407
2
H164
1600
140 x 164
1600
1000
1760
3
H204
2000
140 x 204
2000
1250
2253
4
H244
2500
140 x 244
2500
1600
2816
5
H324
3200
140 x 324
3200
2000
3520
6
H404
4000
140 x 404
(1) I is given as an indication only and is calculated with U - 410 V.
4000
If the phase order of
the busbar trunking is
different to that of the
switchboard’s busbars, it
is recommended a phase
inversion is carried out
in the switchboard. If
this cannot be done, use
the phase and neutral
transposition section.
For more information,
see the “Description”
section, page
K9AE12000/4 and
“Catalogue numbers and
dimensions” section,
page K9AE21020/2.
DD210780
Phase order
DD210945
Design and
installation guide
If, for reasons of busbar trunking operating conditions or performance
requirements, you have to use a rating other than those defined in the above
tables, consult us.
KTAppppTNp10
KTAppppTPp10
4
Schneider Eletric
K9AE43000
Connection to Trihal cast resin
transformers
By Canalis interface
Installation guide
DD210946
Canalis KTA
Reference point
Dimensions
Dimensions X, Y and Z
Dimensions
(mm)
X
M
X0
Transformer power (kVA)
630
800
1000 1250
147
150
170
147
100
100
108
93
233
215
265
245
1600
150
124
300
2000
170
144
300
2500
153
149
322.5
Interface type
1
5
6
7
2
3
4
Dimensions Y0 and Z0
Y0 = X + L
Z0 = C - M
Dimensions C and L are different according to country standards.
French standard
FT no.235627 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 410 V
Dimensions
(mm)
C
L
Transformer power (kVA)
630
800
1000 1250
1614
1744
1749 1929
220
225
240
240
1600
2089
240
2000
2209
257
2500
2297
275
Dimensions
(mm)
C
L
Transformer power (kVA)
630
800
1000 1250
1734
1744
1749 2019
210
220
225
245
1600
1979
255
2000
2199
255
Design and
installation guide
German standard
FT no.235763 rev. 0 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 400 V
2500
2279
265
Spanish standard
FT no.235515 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 420 V
Dimensions
(mm)
C
L
Transformer power (kVA)
630
800
1000 1250
1614
1744
1879 1929
220
225
215
245
1600
1979
250
2000
2194
245
Belgian standard
FT no.235820 rev. 0 - Primary voltage: 15 kV - Insulation voltage: 17.5 kV Secondary voltage: 400 V
Dimensions
(mm)
C
L
K9AE43000
Schneider Eletric
Transformer power (kVA)
630
800
1000 1250
1484
1564
1694 1844
215
210
215
225
1600
2054
230
2000
2149
255
2500
2164
235
5
Installation guide
Connection to Trihal cast resin
transformers
By Canalis interface
Canalis KTA
DD210947
Sealing kit
The sealing kit must be ordered with the KT busbar trunking. The busbar trunking
size defines the sealing kit size. For the different types of kit, see “Catalogue
numbers / Dimensions”.
The kit includes a drilling and cut-out template for the dry-type transformer panels.
KTB0ppppTT01
It is recommended that the cutting-out of the transformer panels is done in the
workshop.
DD210776
Cut-out drawing
Design and
installation guide
Junction axis.
6
Schneider Eletric
K9AE43000
Connection to cast resin
transformers
By universal feed and connection
plates
Installation guide
Canalis KTA
PD202330
Canalis KT can be connected to cast resin transformers using a universal feed.
The connection is made using a flexible busbar (connection plates or braids) to
avoid transmitting vibrations and expansions. The connection plates are made up
of either insulated or non-insulated flexible copper bars, drilled at one or both ends.
A nut and bolt kit allows connection to the feed.
The connections use torque-head bolts which provide both ease of installation and
visual inspection of correct tightening before energising.
If the transformer is supplied with panels, provide for an additional cover to
maintain the protection degree.
Choice of Canalis KT busbar trunking rating according to transformer power.
Transformer
Power (kVA)
630
800
1000
1250
1600
2000
2500
I nominal(1) (A)
887
1126
1408
1760
2253
2816
3520
KTA rating at nominal
power(2) (A)
1000
1250
1600
2000
2500
3200
4000
(1) I is given as an indication only and is calculated with U = 410 V and at transformer nominal
setting, without forced ventilation.
(2) The busbar trunking rating is defined for normal operating conditions.
TS3 and TS5 universal connection, edgewise mounting
Design and
installation guide
DD210949
Recommended configurations for shortcircuit withstand
(connection plate L = 400 mm)
KTAppppELp1 or KTAppppELp2 or KTAppppELp3 or KTAppppELp4
DD210948
TS4 and TS6 universal connection, flat mounting (using angle brackets)
KTAppppELp1 or KTAppppELp2 or KTAppppELp3 or KTAppppELp4 with angle
bracket KTB0000YE1
K9AE43000
Schneider Eletric
7
Connection to cast resin
transformers
By universal feed and connection
plates
Installation guide
Canalis KTA
DD202481
TS7 universal connection, edgewise mounting
KTAppppELp5
DD202480
TS7 universal connection, flat mounting (using angle brackets)
KTAppppELp5 with angle bracket KTB0000YE
The number of connection plates is defined in the table below:
Busbar trunking
rating (A)
8
Schneider Eletric
1000 to 1600
2000 to 2500 3200
DD210789
DD210788
Connection
plates
DD210787
Busbar trunking rating (A) Connection plates per phase
Number
Cross-section (mm2)
1000
2
1000
1250
2
1000
1600
2
1000
2000
3
1500
2500
3
1500
3200
4
2000
4000
5
2500
DD210786
Design and
installation guide
DD210950
Definition of connection plates
4000
K9AE43000
Connection to cast resin
transformers
By universal feed and connection
plates
Installation guide
Canalis KTA
Phase order
Phase selection is made when the feed is ordered.
Phase L2 is fixed and can therefore be used as a reference for installing the feed
on the transformer.
The different phase selection possibilities (T)
DD210951
b Dedicated feeds N1 to N4,
Design and
installation guide
Important: the drawings and references above correspond to a phase order of
N321, joint block side. If the phase order on the joint block side is N123, inverse
T=1 with T=3 and T=2 with T=4.
DD210952
b Feed with flat bars N5.
Important: the drawings and references above correspond to a phase order of
N321, joint block side. If the phase order on the joint block side is N123, inverse L1
and L3 on the transformer side marking.
K9AE43000
Schneider Eletric
9
Connection to cast resin
transformers
By universal feed and connection
plates
Installation guide
Canalis KTA
Dimensions of protective covers
DD202344n
Vertical protection covers for dry-type transformer feeds N1, N2, N3
and N4
Rating (A)
Dimensions (mm)
Y
Z
Minimum
Maximum
800 to 1250
230
200
350
1600 to 2500
350
200
350
3200 to 4000
510
200
350
KTB0000CR4
Horizontal protection covers for dry-type transformer feeds N1, N2, N3
and N4
Rating (A)
Dimensions (mm)
Y
Z
Minimum
Maximum
800 to 1250
230
330
480
1600 to 2500
350
330
480
3200 to 4000
510
330
480
Design and
installation guide
DD202345n
KTB0000CR5
10
Schneider Eletric
K9AE43000
Connection to cast resin
transformers
By universal feed and connection
plates
Installation guide
Canalis KTA
Horizontal protection cover for dry-type transformer feed N5
Rating (A)
Dimensions (mm)
Y
Z
Minimum
Maximum
800 to 1250
230
380
530
1600 to 2500
350
500
650
3200 to 4000
510
660
810
DD202347
KTBppppCR6
Cut-out drawing for dry-type
transformer panels
Design and
installation guide
DD202501n
It is recommended that the cutting-out of the transformer panels is done in the
workshop.
K9AE43000
Schneider Eletric
11
Installation guide
Connection to oil immersed
transformers
Selection guide
Canalis KTA
TH2
DD202417
TH3
DD202418
Vertical incomer
TH1
Design and
installation guide
PD202429
Incomer type
DD202416
This guide will allow you to:
v choose the connection best suited to your layout (incoming direction, flat or
edgewise busbar trunking, possibility of adjusting phase order),
v check the total height of the link with respect to the premises’ ceiling height,
dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link
and the ceiling),
v optimise your link whilst respecting the following rule:
(Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels,
v position the sections for the busbar trunking supports.
Z0
According to manufacturer’s drawing
According to manufacturer’s drawing
According
minimum
738
1073
730
maximum
1072
-
1064
Z2
Z1 + H
Z1 + H
Z1 + 140
Front or rear exit
Right or left exit
Edgewise layout
b
b
b
b
Z1
b
b
Flat layout
2
Schneider Electric
K9AE44000
Connection to oil immersed
transformers
Selection guide
Installation guide
Canalis KTA
Trunking cross-section
Rating (A)
800(1)
1000
1250
1600
2000
2500
3200
4000
Direct connection
TH5
DD202420
Design and
installation guide
TH4
DD202419
DD210867
DD202180
Height H (mm)
Width W (mm)
g to manufacturer’s drawing
According to manufacturer’s drawing
According to manufacturer’s drawing
1065
Z1 = (Y/ H) / 2
-
Z1 = (Y/ H) / 2
Z1 + 140
H = 74 or 104 or 124 mm
H = 164 or 204 or244 mm
H = 324 or 404 mm
b
510
770
850
b
b
b
K9AE44000
Schneider Electric
3
Connection to oil immersed
transformers
By feed and connection plates or
braids
Installation guide
Canalis KTA
PD202300
Connection to an oil immersed transformer is made using flexible bars (connection
plates) to avoid transmitting transformer vibrations to the busbar trunking and to
limit the stress on connection terminals.
Choice of busbar trunking
Dry-type transformer
Rating (kVA)
500
630
800
1000
1250
1600
2000
2500
l nominal(1)
(A)
704
887
1126
1408
1760
2253
2816
3520
Canalis KT aluminium busbar
trunking
Rating (A)
Cross-section
800
1000
1250
1600
2000
2500
3200
4000
140 x 74
140 x 104
140 x 124
140 x 164
140 x 204
140 x 244
140 x 324
140 x 404
(1) I is given as an indication only and is calculated with U - 410 V.
Note: If, for reasons of busbar trunking operating conditions or performance requirements, you
have to use a rating other than those defined in the above tables, consult us.
Protective cover width
Busbar trunking rating (A)
1000 to 1250
1600 to 2500
3000 to 4000
Vertical incomer
Horizontal incomer
Design and
installation guide
DD202422
DD202421
Recommended configurations for shortcircuit withstand
(connection plate L = 400 mm)
Dimensions “Y” of the feed
230
350
510
4
Schneider Electric
K9AE44000
Connection to oil immersed
transformers
By feed with connection plates or
braids
Canalis KTA
Several connection possibilities
Phase order
With connection plates
with kink to be drilled
DD202424n
DD202423n
With connection plates
with kink and bar clamp
With drilled connection
plates (KTB0000YC4) or
braids
DD202425n
Installation guide
Design and
installation guide
DD210780
DD210781
DD210791
If the phase order of the busbar trunking is different to that of the switchboard’s
busbars, it is recommended a phase inversion is carried out in the switchboard. If
this cannot be done, use the phase and neutral transposition section.
For more information, see the “Description” section, page K9AE12000/4 and
“Catalogue numbers and dimensions” section, page K9AE21020/2.
KTAppppTNp10
KTAppppTPp10
K9AE44000
Schneider Electric
5
Canalis KTA
Connection to oil immersed
transformers
By feed with connection plates or
braids
Definition of connection plates
The number of connection plates is defined in the table below:
1000 to 1600
DD210789
2000 to 2500 3200
4000
DD210785
Busbar trunking
rating (A)
DD210788
DD202426
Connection
plates
DD210787
Busbar trunking rating (A) Connection plates per phase
Number
Cross-section (mm2)
1000
2
1000
1250
2
1000
1600
2
1000
2000
3
1500
2500
3
1500
3200
4
2000
4000
5
2500
DD210786
DD210764
Installation guide
The number of braids is defined in the table below:
Busbar trunking rating (A) Braids per phase
Number
1000
1
1250
2
1600
2
2000
2
2500
3
3200
3
4000
4
6
Schneider Electric
1000
1250 to 2000
2500 to 3200
DD202376
DD210773
Busbar trunking
rating (A)
DD210770
Design and
installation guide
Braids
Cross-section (mm2)
600
1200
1200
1200
1800
1800
2400
DD210768
DD202355
Definition of braids
4000
K9AE44000
Canalis KTA
Connection to oil immersed
transformers
By feed with connection plates or
braids
Dimensions of protective covers
Horizontal incomer
Installation guide
Rigid horizontal cover KTBppppCR1 for ER straight outlet feed connectors
type N1 to N6
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Dimensions (mm)
Y
D
230
220 to 475
350
220 to 475
510
220 to 475
G
220 to 475
220 to 475
220 to 475
Z
310 to 800
430 to 800
590 to 800
DD202326
KTBppppCR1
Adjustable cover KTBppppCR7 for horizontal incomer feed connectors with a
between centres distance of 150 or 170 mm
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Dimensions (mm)
Y
Z
X
230
565
450
350
825
650
510
905
650
A
830
890
960
B
750
810
880
E
330
350
460
F
125
265
185
G
365
485
645
DD210872n
KTBppppCR7
Vertical incomer
Design and
installation guide
Rigid vertical cover KTBppppCR2 (400 to 800 mm height) for ER straight
outlet feed connectors type N1 to N6
Rating (A)
Dimensions (mm)
Y
D
G
Z
800 to 1250
230
220 to 475
220 to 475
400 to 800
1600 to 2500
350
220 to 475
220 to 475
400 to 800
3200 to 4000
510
220 to 475
220 to 475
400 to 800
DD202322
KTBppppCR2
K9AE44000
Schneider Electric
7
Connection to oil immersed
transformers
By feed with connection plates or
braids
Installation guide
Canalis KTA
Adjustable cover KTBppppCR8 for vertical incomer feed connectors with a
between centres distance of 150 or 170 mm
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Dimensions (mm)
Y
Z
A
230
600
830
350
600
890
510
600
960
B
750
810
880
C
345
460
625
E
330
350
460
DD210870n
KTBppppCR8
Flexible cover KTBppppCR8 for vertical incomer straight outlet feed
connectors with a between centres distance of 115 mm
Rating (A)
Dimensions (mm)
Y
C
800 to 1250
230
200 to 650
1600 to 2500
350
200 to 650
3200 to 4000
510
200 to 650
Design and
installation guide
DD202319
KTBppppCS0
8
Schneider Electric
K9AE44000
Connection to oil immersed
transformers
Other connection solutions
Installation guide
Canalis KTA
Connection to bar bushings
DD210955
Canalis KT is easily connected to Minera oil immersed transformers (France
Transfo offer).
For more details of drilling dimensions for the bushings and the connection
terminals, refer to the manufacturer’s catalogue.
Connections to Minera ground mounted oil immersed transformers
from 630 to 3150 kVA - y 24 kV / 400 V
K9AE44000
2000
3150
2500
3150
5000
Schneider Electric
Design and
installation guide
2500
DD202427
1250
1600
DD202428
1600
DD202429
1000
Dimensions (mm)
DD202430
Bar bushings (A)
1250
DD2024321
Power (kVA)
630
800
9
Connection to oil immersed
transformers
Other connection solutions
Installation guide
Canalis KTA
Connection to porcelain bushings
DD210959
Connection terminals of the type defined below must be used. These are available
in the transformer manufacturers’ catalogues.
Cover
Design and
installation guide
DD210957
The transformers can be supplied with or without a low voltage cover. This cover is
not used in our solutions.
10
Schneider Electric
K9AE44000