Layout advice Run optimisation Installation guide Canalis KTA CanBrass software PD202428 CanBrass software can be used to design the busbar trunking line. The easy-to-use program creates a graphic model of the line, determines the length and draws up the list of Canalis KT parts to order. The Canalis KT line is easy to specify simply by indicating the required dimensions. However, it is strongly advised to use the shortest and simplest path possible between the transformer and the switchboard. It is important to carefully plan the layout of the transformer and switchboard in order to use: b the maximum number of standard components rather than made-to-measure components, b the minimum number of components for changing direction, b straight made-to-measure components rather than made-to-measure components for changing direction. Advice Before defining your busbar trunking run, it is recommended you pay particular attention to the various parameters which could be detrimental to the installation. DD210900 DD210895 Obstacles that obstruct the busbar trunking such as beams, pipes, etc. Design and installation guide DD210903 DD210902 Badly positioned places for going through walls and floors. 2 DD210896 DD210897 Joint positions in the middle of a partition wall. Schneider Electric K9AE41000 Layout advice Run optimisation Installation guide Canalis KTA Insufficient ceiling height. DD210898 DD210899 If the busbar trunking must be installed edgewise between a transformer and switchboard, ensure the ceiling height is sufficient for fitting the joint blocks from the top. Reserve a space between the busbar trunking and the ceiling equal to 2 times the busbar trunking height (variable depending on the rating, see “Catalogue numbers and dimensions”). DD210903 DD210904 Going through a floor to bottom feed a switchboard on the next floor. DD210905 Difference in floor levels of 2 rooms. Design and installation guide Also make sure that as the work progresses other tradesmen do not carry out installations that could hinder your initial layout. K9AE41000 Schneider Electric 3 Layout advice Run optimisation Installation guide Canalis KTA Examples of link optimisation DD210910 Example 1 Reducing the number of changes of direction by modifying the switchboard or transformer layout. DD210911 Example 2 Use of 2 standard elbows in place of a made to measure zed by increasing dimension “L”. DD210912 Modification of the busbar trunking height By slightly increasing dimension “Z”, replace a made to measure elbow feed connector with a standard feed connector and standard elbow section. When choosing the layout of the electrical installation, it is important care is taken when positioning the neutral between the transformer and the switchboard. If the neutral position is different to that planned, it is recommended the transformer is moved, if possible, to align the neutral with respect to the switchboard’s neutral. When it is not possible to move the transformer, it is recommended the phase order in the switchboard is inversed. If this cannot be done, use the phase and neutral transposition section. DD210780 Design and installation guide Neutral position KTAppppTNp10 KTAppppTPp10 4 Schneider Electric K9AE41000 Layout advice Positioning and supports Installation guide DD210935 Canalis KTA Edgewise passage through partition wall DD210933 DD210932 Flat passage through partition wall Rating (A) Height H (mm) Re-filling recommendation 800 74 1000 104 1250 124 1600 164 2000 204 2500 244 3200 324 4000 404 DD210934 We recommend re-filling is carried out as follows. K9AE41000 Schneider Electric Design and installation guide Rock wool Promatect 100 Plaster finishing 5 Layout advice Positioning and supports Installation guide Canalis KTA A support point as close as possible to the connections is needed because transformers, generator sets and switchboards must not support the weight of the busbar trunking. In some industries, for service continuity reasons, transformers may be replaced quickly. The busbar trunking must be able to support itself. Edgewise horizontal installation DD210930 The maximum recommended distance between supports is 3 metres. In all cases, provide for 2 supports for 4 metre sections. For clamping busbar trunking to support brackets, see page K9AE41000/16. Flat horizontal installation DD210931 The recommended distance between supports is 2 metres. In addition, a support must be placed at 300 or 400 mm from the joint block axis. For clamping busbar trunking to support brackets, see page K9AE41000/16. Example of spreading out supports Design and installation guide DD210929 Plan for a maximum distance between supports of 3 metres. 6 Schneider Electric K9AE41000 Layout advice Positioning and supports Installation guide Canalis KTA Defining the layout, dimensions to be provided DD210924 The position of the joint block with respect to the transformer axes and switchboard edges (defined in the “Installation guide”). Edgewise installation DD210928 Rating (A) Height H (mm) 800 74 1000 104 1250 124 1600 164 2000 204 2500 244 3200 324 4000 404 Edgewise installation Design and installation guide DD210925 Distance between busbar trunking (without tap-off units) Flat installation DD210927 Distance of the busbar trunking from the wall (1) Provide 2 times the height if the joint block must be fitted from the top. Direction of fitting joint blocks. DD210926 Flat installation Direction of fitting joint blocks. K9AE41000 Schneider Electric 7 Layout advice Anticipate unexpected worksite problems Installation guide Canalis KTA In order to cope with dimensional differences between the drawings and actual dimensions, it is desirable to provide an adjustable section or to leave a section undecided for each partial run. Adjustable section DD202483 It has an initial length of 1300 mm and can be reduced or extended by the installation contractor at the worksite (± 200 mm). By planning the use of an adjustable section when producing the drawings, it can be ordered with the rest of the material, without needing to wait until the job is finished. It therefore allows the overall project completion time to be reduced. DD210908 Allow a nominal dimension of 1300 mm on the drawing to guarantee an adjustment of ± 200 mm on-site. This section will be ordered after the gap to be filled has been measured at the end of the job. To optimise its delivery to site, prefer a straight section with a length of less than 2 metres rather than made to measure elbows. 1: Standard straight section. 2: Made to measure elbow. DD210906 DD202390 Undecided section DD210907 3: Made to measure straight section. 4: Standard elbow. Layout recommendations for adjustable or undecided sections In order to provide for the place needed for an adjustable or undecided section, install the elbows and the sections attached to the elbows in each angle (support each assembly using 2 supports on each straight section). DD210994 Design and installation guide DD210908 On the drawing, provide a minimum dimension of 700 mm to guarantee an adjustment of ± 200 mm on-site. The minimum length of straight sections being equal to 500 mm. And then complete the layout with standard and made to measure straight sections. 8 Schneider Electric K9AE41000 Layout advice Tips for determining dimensions at the worksite Installation guide Canalis KTA Straight section DD210913 The nominal length “L” of a straight section is measured from the axis of the joint block to the other axis of the joint block, in millimetres (the joint block axis is located 20 mm from the end of the bars). Dimension L of the standard or made to measure section = x - 40 mm. (1) : For the different busbar trunking heights, see page K9AE41000/7. (2) : See “Run sections” in “Catalogue numbers and Dimensions”. x : measured dimension. Example: x = 1860 mm hence L = 1860 - 40 = 1820 mm. Flat elbows Change-of-directions DD210918 DD210916 The nominal length of each branch is measured from the axis of the joint block to the axis of the other branch, in millimetres. The joint block axis is located 20 mm from the end of the bars. Design and installation guide A and B: See “Changes of direction” in “Catalogue numbers and Dimensions”. “Flat” elbow, external positioning A = A1 + A2 + (140 / 2) - 20 “Flat” elbow, internal positioning A = A1 - A2 - (140 / 2) - 20 (1) See “Changes of direction” in “Catalogue numbers and Dimensions”. K9AE41000 Schneider Electric 9 Layout advice Tips for determining dimensions at the worksite Installation guide Canalis KTA DD210917 Edgewise elbows DD210919 The nominal length of each branch is measured from the axis of the joint block to the axis of the other branch, in millimetres. The joint block axis is located 20 mm from the end of the bars. A and B: See “Changes of direction” in “Catalogue numbers and Dimensions”. “Edgewise” elbow, external positioning A = A1 + A2 + (H / 2) - 20 “Edgewise” elbow, internal positioning A = A1 - A2 - (H / 2) - 20 (1) See “Changes of direction” in “Catalogue numbers and Dimensions”. DD210921 Flat Zed Design and installation guide DD210922 The nominal length of each branch is measured from the axis of the joint block to the axis of the other branch, in millimetres. The joint block axis is located 20 mm from the end of the bars. The nominal length of the intermediary branch(es) is measured from the axis of one branch to the axis of another. A, B and C: See “Changes of direction” in “Catalogue numbers and Dimensions”. B = B1 - B2 (1) See “Changes of direction” in “Catalogue numbers and Dimensions”. 10 Schneider Electric K9AE41000 Layout advice Tips for determining dimensions at the worksite Installation guide Canalis KTA DD210920 Edgewise Zed DD210923 The nominal length of each branch is measured from the axis of the joint block to the axis of the other branch, in millimetres. The joint block axis is located 20 mm from the end of the bars. The nominal length of the intermediary branch(es) is measured from the axis of one branch to the axis of another. A, B and C: See “Changes of direction” in “Catalogue numbers and Dimensions”. B = B1 - B2 (1) See “Changes of direction” in “Catalogue numbers and Dimensions”. Definition of final section parameters Reminder: the final section should preferably be a straight section. Take into account the neutral position when choosing the section. DD210914 Tools Tape measure Spirit level Lead line Stick Ruler Laser or infra-red reader Design and installation guide DD210915 Their use K9AE41000 Schneider Electric 11 Horizontal distribution Positioning the tap-off units Installation guide Canalis KTA PD202398 It is possible to combine the following in the same installation: b straight transport sections with straight sections containing fixed or plug-on tapoff points, b straight sections of different lengths, b straight sections with different numbers of fixed or plug-on tap-off points, b … Positioning the tap-off units on the busbar trunking DD210938 Several configurations are possible. Some examples: b on a 2000 mm straight section with plug-on tap-off points (KTAppppEDp20): v 3 x 160 A circuit breaker tap-off units: DD210936 v 1 x 400 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit, DD210939 v 3 x 160 A fuse tap-off units: DD210996 v 1 x 400 A fuse tap-off unit, 1 x 250 A fuse tap-off unit and 1 x160 A fuse tap-off unit: b on a 4000 mm straight section with fixed tap-off points (KTAppppEBp40): v 1 x 400 to 630 A fixed tap-off unit and 1 x 800 to 1000 A fixed tap-off unit: DD210937 Design and installation guide DD210995 b on a 4000 mm straight section with plug-on tap-off points (KTAppppEDp40): v 1 x 400 A circuit breaker tap-off unit, 1 x 250 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit: Cable exit. 12 Schneider Electric K9AE41000 Horizontal distribution Tap-off units Installation guide Canalis KTA DD210997 When the tap-off units have to be distributed along the length of the busbar trunking, use 2 metre sections and alternate the tap-off point positions. Recommendations for installing 2 parallel busbar trunking runs For an installation with tap-off units, provide for a between centres distance that takes into account the minimum dimension of 100 mm and the dimensions A and B of the tap-off units. DD210940 Type Circuit breaker tap-off units Tap-off unit door opening Cat. no. Dimensions (mm) A B KSB160DCp 160 150 KSB250DCp 240 160 KSB400DCp 240 KTB0630CBp 175 160 KTB1000CBp 275 Fuse tap-off KSB160SEp 150 units KSB250SEp 250 275 KSB400SEp 440 160 175 150 160 DD210941 Provide for a minimum distance of 1000 mm between the busbar trunking and the ceiling to allow for the opening of tap-off unit doors. Type Circuit breaker tap-off units Cat. no. Dimensions (mm) X E(1) KSB160DCp 625.5 246 KSB250DCp 726.5 300 KSB400DCp 976,5 Fuse tap-off KSB160SEp 577,5 units KSB250SEp 777 KSB400SEp 855 350 207 258 316 Design and installation guide Installing an isolator or run protective device DD210942 (1) With the handle. Rating (A) 1000 1250 1600 2000 2500 3200 K9AE41000 Schneider Electric Dimensions (mm) A B 159 529 149 539 129 559 109 579 89 599 98 662 13 Horizontal distribution Checking and compensating for expansion Installation guide Canalis KTA DD202446 Expansion poses a problem when: b the runs are made up of long straight sections, b when the busbar trunking passes through an expansion joint between two buildings. Long part runs Electrical busbar trunking can be subjected to a multitude of load variations during its service life (e.g. day / night, summer / winter) which cause temperature rise differences and thus variable expansions. To absorb expansion in a Canalis KT busbar trunking, a specific section must be used: the expansion section. Horizontal runs without tap-off units If the busbar trunking length is greater than 30 metres, provide for expansion sections and appropriate blocking means. The ends and, in some cases, the centre of part runs must be blocked in order to direct the extensions towards the expansion sections. DD210998 Layout of expansion sections and blocking means for the following busbar trunking lengths: b 0 to 30 metres: DD210999 b 31 to 60 metres: DD211000 b 61 to 90 metres: DD211001 91 to 120 metres: Design and installation guide Blocked fixing supports, Expansion section, Direction of expansion. 14 Schneider Electric K9AE41000 Horizontal distribution Checking and compensating for expansion Installation guide Canalis KTA Horizontal runs with tap-off units DD211002 Layout of expansion sections and blocking means for the following busbar trunking lengths: b 0 to 30 metres: DD211003 b 31 to 60 metres: DD211004 b 61 to 120 metres: Blocked fixing supports, Expansion section, Direction of expansion, Tap-off unit. DD2111005 Transformer / switchboard links Design and installation guide Blocked fixing supports, Expansion section, Direction of expansion. K9AE41000 Schneider Electric 15 Horizontal distribution Checking and compensating for expansion Installation guide Canalis KTA Rules for fixing busbar trunking to the supports DD211006 For correct system operation, the expansion of the part run in question must be directed towards the expansion section. This implies: b the busbar trunking must be free from all longitudinal movement on its supports, b the expansion section must be blocked on the opposite side to that by which it is pushed. 1 2 Free fixings. Blocked fixings. Direction of expansion. Installation of free fixings Flat assembly DD211008 DD211007 Edgewise assembly Installation of blocked fixings DD211010 Flat assembly Design and installation guide DD211009 Edgewise assembly 16 Schneider Electric K9AE41000 Horizontal distribution Checking and compensating for expansion Installation guide Canalis KTA Passing through a joint between 2 buildings DD211012 Here, the expansion section allows the busbar trunking to absorb the forces due to the relative movement between the 2 buildings. Building A Building B DD211011 Blocked fixing supports. 1 Blocked fixings. Installation of blocked fixings Flat assembly Design and installation guide DD211010 DD211009 Edgewise assembly K9AE41000 Schneider Electric 17 Installation guide Rising mains General Canalis KTA PD202319 Canalis KT enables power distribution to each floor of multi-storey buildings (office buildings, hotels, hospitals, etc). In this application, Canalis KT retains all its construction principles: Vertically mounted, the protection degree of the KT busbar trunking is IP55 as standard. Installing a rising main 1 Installation principle Installation at each floor of: b a 2 metre distribution section, b a made to measure transport section to go through the floor slab, b a busbar trunking support, b up to 3 x 160 A tap-off units or a 250 or 400 A tap-off unit and a 160 A tap-off unit. 2 Installation feed The installation feed is achieved using either a cable box or by direct connection to an electrical distribution switchboard. 3 Busbar trunking supports The supports fix the vertical run section to the building structure. a floor slab support. It can be fixed to either the wall, to a wall bracket or directly to the floor, This type of fixing support has the following advantages: b fitting to either the wall, to a wall bracket or directly to the floor, b height adjustment to make up for positioning errors, b depth adjustment from 50 to100 mm, b spring adjustment to ensure distribution of the load at each floor, b absorption of building stresses with respect to the busbar trunking (expansion, vibration, etc) thanks to the springs. 4 Tap-off units Design and installation guide All Canalis KS tap-off units can be mounted vertically on the Canalis KT without the risk of interference with the supports. 2 Schneider Electric K9AE45000 Rising mains Positioning the busbar trunking Installation guide Canalis KTA DD210960 Positioning the neutral The busbar trunking must be positioned with the neutral on the right. Positioning the joint block It is important the joint block is not positioned in the floor slab. DD210961 We recommend you provide for a distance of: b 400 mm between the floor slab and the joint block axis to be able to install a support to the wall or wall bracket to facilitate the re-filling of the hole and to cope with possible building faults (e.g. screed not indicated on the drawings). Provide 500 mm for a floor fixing. b 200 mm between the upper joint block and the ceiling to allow the busbar trunking to be boxed-in when filling-in the hole with plaster or concrete. Positioning the tap-offs Design and installation guide The run sections are fitted with 3 tap-off points. Spaced at 500 mm intervals, they provide a high density of tap-offs per floor. K9AE45000 Schneider Electric 3 Rising mains Positioning the tap-off units Installation guide Canalis KTA DD210962 Positioning the tap-off units on the busbar trunking Several configurations are possible. Some examples: 1 - 3 x 160 A circuit breaker tap-off units, 2 - 1 x 400 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit, 3 - 3 x 160 A fuse tap-off units, 4 - 1 x 800 to 1000 A bolted tap-off unit. Cable exit DD210964 R = 12 x Ø of cable Recommendations for installing 2 rising mains in parallel Cable exit. DD210954 For an installation with tap-off units, provide for a between centres distance that takes into account the minimum dimension of 100 mm and the dimensions A and B of the tap-off units. Type Circuit breaker tap-off units Cat. no Dimensions (mm) A B KSB160DCp 160 150 KSB250DCp 240 160 KSB400DCp 240 160 KTB0630CBp 175 175 Design and installation guide KTB1000CBp 275 Fuse tap-off KSB160SEp 150 units KSB250SEp 250 KSB400SEp 440 275 150 160 160 Tap-off unit door opening DD210963 If installed in a technical room, provide for a minimum distance of 1000 mm between the busbar trunking and the wall in order to be able to open the doors of the tap-off units. 4 Schneider Electric K9AE45000 Rising mains Positioning of supports Installation guide Canalis KTA DD210968 2 fixing systems are available: b a rear wall fixing system for 800 A to 1600 A busbar trunking, b a side wall fixing system for 2000 A to 4000 A busbar trunking. DD210967 Wall support Wall drilling drawing to fix the support. 800 to 1600 A 2000 to 4000 A (1) Dimensions with free springs. Y : 50 mm minimum to 100 mm maximum DD210966 Wall bracket support (if Y > 100 mm) X u 400. 2000 to 4000 A Design and installation guide 800 to 1600 A DD210965 Floor support 800 to 1600 A K9AE45000 Schneider Electric 2000 to 4000 A 5 Rising mains Going through the floor Installation guide Canalis KTA DD210977 Going through the floor 2000 2500 3200 Design and installation guide 4000 DD210969 DD210970 DD210971 DD210972 DD210973 1600 DD210974 1250 DD210975 1000 Height H (mm) DD210976 Rating (A) 800 Re-filling recommendation DD210934 We recommend re-filling is carried out as follows. Rock wool Promatec 100 Plaster finishing 6 Schneider Electric K9AE45000 Rising mains Installation with feed via a cable box or direct onto the switchboard Installation guide Canalis KTA Design and installation guide Installation with feed via a cable box. DD210979 2 possibilities: b installation with feed direct to the switchboard, b installation with feed via a cable box. K9AE45000 Schneider Electric 7 Rising mains Installation with feed via a cable box or direct onto the switchboard Installation guide Design and installation guide Installation with feed direct to the switchboard DD211013 Canalis KTA 8 Schneider Electric K9AE45000 Installation guide Panorama of connection solutions Canalis KTA The Schneider Electric system The comprehensive Schneider Electric system makes it simple to design a complete transformer / Canalis KT/ switchboard installation. Using dedicated interfaces, the trunking connects directly to the dry-type transformer and the switchboard for: b tested and standardised connections, b fast and flexible installation, b shorter lead times. Advantages b No design work for the connections. b Simplified layout design: v pre-defined position of the jointing unit, v simplified routing (only three dimensions required), v smaller size (no additional covers required). b Transformer and switchboard supplied with connections already mounted. b Short lead times and fewer catalogue numbers for connections. b Adaptable on the worksite: v transformer end: ± 15 mm adjustments along all three axes, v switchboard end: phases can be inverted. b Continuity of service: v transformer can be replaced in less than one hour, v transformer, trunking and switchboard designed to be used together. b Safety: v trunking fully tested in compliance with IEC 60439-1 and 2, v compliance with standards and installation rules, v excellent fire-withstand capability. b Comfort: v low level of electromagnetic radiation, v no noise. Connection to an LV switchboard using a dedicated interface, see page K9AE42000/6. Design and installation guide PD202432 Connection to a dry-type transformer using a dedicated interface, see page K9AE43000/4. 2 Schneider Electric K9AE42000 Installation guide Panorama of connection solutions Canalis KTA Connection to an LV switchboard using a dedicated interface, see page K9AE42000/6. PD202301 Universal connection to a dry-type transformer, see page K9AE43000/7. Universal connection to an oil-filled transformer, see page K9AE44000/4. Design and installation guide PD202302 Universal connection to an LV switchboard, see page K9AE42000/12. K9AE42000 Schneider Electric 3 Installation guide Connection to LV switchboards Selection guide Canalis KTA This guide may be used to: v select the connection best suited to your installation (incoming direction, trunking installed flat or edgewise, different phase order), v check the total height of the connection with respect to the ceiling, i.e. dimension Z0 + Z2 (100 mm minimum clearance required between top of connection and ceiling), v optimise the connection by ensuring that (Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid having to use elbows and zed units, v position the fixing devices used to support the trunking. Connection with an interface DD210755 SB2 DD210754 SB1 Direct connection Without protective covers SB3 DD21v0753 Design and installation guide PD202304 Type of connection see page K9AE42000/6 see page K9AE42000/6 As per manufacturing drawing minimum 74 82 138 maximum - - 472 Z2 Z1 + 140 Z1 + H Z1 + H Phase order can be changed b b Mounting in workshop b b Exit through front or rear b Z0 Z1 b Exit through left or right side b Edgewise installation b Flat installation 4 b b Schneider Electric K9AE42000 Canalis KTA Trunking cross-section Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000 With protective covers SB7 DD210759 SB6 DD210758 SB5 DD210757 SB4 As per manufacturing drawings As per manufacturing drawings As per manufacturing drawings As per manufacturing drawings 473 130 465 H = 74 to 124 mm 195 - H / 2 H = 164 to 244 mm 255 - H / 2 H = 324 to 404 mm 355 - H / 2 - 464 - - Z1 + H Z1 + 140 Z1 + 140 H = 74 or 104 or 124 mm H = 164 or 204 or 244 mm H = 324 or 404 mm b Design and installation guide DD210867 DD202180 Height H (mm) Width W (mm) DD210756 gs Connection to LV switchboards Selection guide Installation guide Z1 + H / 2 + 115 Z1 + H / 2 + 175 Z1 + H / 2 + 255 b b b b b b b b K9AE42000 b Schneider Electric 5 Connection to Okken and Prisma Plus LV switchboards By Canalis interface Installation guide Canalis KTA PD202328 Switchboards can be equipped with connections for Canalis KT. Jointing with the switchboard is via a standard run component (straight length, elbow, etc.) and a jointing unit (identical to those used between line components). The trunking enters the switchboard via the top (roof). Switchboard connections are available from 800 to 4000 A. Type of switchboard Rating of trunking Type of circuit (A) breaker Type of connection Prisma Plus 800 to 1600 Compact NS Top direct and rear Masterpact NT Top direct and rear Okken 800 to 3200 Masterpact NW Top direct and rear 4000 Masterpact NW Rear 800 to 4000 Masterpact NW Top direct and rear Connections are tested and qualified under normal operating conditions in terms of temperature rise (∆θ) and short-circuit currents (Isc). The panel builder receives and connects the Canalis KT interface in the workshop. The phase order at the interface output can be adapted if necessary (this information must be forwarded to the panel builder). The switchboard is then delivered to the site and the trunking can be rapidly connected using a simple jointing unit with torque nuts to ensure the correct tightening torque. Compatibility between Canalis KT and the interface in the switchboard(1) Canalis KT Cat. no. Rating (A) Height (mm) Sealing kit KTA0800 KTA1000 KTA1250 KTA1600 KTA2000 KTA2500 KTA3200 KTA4000 800 1000 1250 1600 2000 2500 3200 4000 74 104 124 164 204 244 324 404 KTB0074TT01 KTB0104TT01 KTB0124TT01 KTB0164TT01 KTB0204TT01 KTB0244TT01 KTB0324TT01 KTB0404TT01 Circuit breakers in Okken et Prisma Plus switchboards NS / NT / NW NS / NW 800 and 1000 A 1250 A 1600 A 2000 A 2500 A Interface 08 / 16 Interface 20 / 25 H164(2) H244(2) NW 3200 A 4000 A Interface 32 Interface 40 H404(2) H404(2) (1) Coordination with a dry-type transformer, see the “Transformer” section, see page K9AE43000/4. (2) Height of the jointing unit in millimetres. Phase order Using the dedicated interface, it is possible to change the phase order if it is different between the trunking and the switchboard. DD210772 Design and installation guide The prefabricated connections installed in the switchboard are designed to operate without derating and can therefore operate at the rated circuit breaker current. 6 Schneider Electric K9AE42000 Connection to Okken switchboards By Canalis interface Installation guide Canalis KTA Top direct connection (TDC) DD202310 To 800 to 4000 A Masterpact NW circuit breakers b Enclosure 600 or 1000 mm deep, access through the front. Position of the jointing unit Circuit breaker Drawout, 3P/ 4P(1) NW08 / 16 NW20 / 25 NW32 NW40 Dimensions (mm) A B 175 325 175 325 175 325 175 325 DD210761 (1) To order, see “Catalogue numbers”, page K9AE23000/4. C 156 156 156 156 Design and installation guide Reference point K9AE42000 Schneider Electric 7 Connection to Okken switchboards By Canalis interface Installation guide Canalis KTA Rear connection (RC) DD202311 To 800 to 4000 A Masterpact NW circuit breakers b Enclosure 1000, 1200 or 1400 mm deep, access through the rear. Position of the jointing unit Circuit breaker Drawout, 3P/ 4P(1) , top position Drawout, 3P/ 4P(1) , medium position Drawout, 3P/ 4P(1) , bottom position Dimensions (mm) A Depth (mm) 1000 1200 1400 NW08 / 16 NW20 / 25 NW32 NW40 NW08 / 16 NW20 / 25 NW32 NW40 NW08 / 16 NW20 / 25 NW32 825 825 825 825 825 825 - 953 953 - 1225 1225 1225 B C 363 363 363 363 363 363 363 363 363 363 363 317 317 317 156 942 942 942 881 1417 1417 1417 DD210763 (1) To order, see “Catalogue numbers”, page K9AE23000/4. Depth: 1200 mm Depth: 1400 mm Design and installation guide DD202384 Top views Depth: 1000 mm Reference point Bottom connection 8 For installations with connections through the bottom, please consult us. Schneider Electric K9AE42000 Connection to Prisma Plus LV switchboards By Canalis interface Installation guide Canalis KTA Top direct connection (TDC) DD202306 To a Compact NS 1250 or Masterpact NT 1200 circuit breaker b Enclosure 400 mm deep, access through the front. Position of the jointing unit Circuit breaker Fixed, 3P/ 4P(2) Drawout, 3P/ 4P(2) Dimensions(1) (mm) A B C NS800 / 1250 NT08 / 12 NS800 / 1250 or 08 / NT16 236 260 260 325 325 325 160 160 170 DD210765 (1) Dimensions measured from switchboard framework. (2) To order, see “Catalogue numbers”, page K9AE23000/2. Reference point DD202304 To 800 to 3200 A Masterpact NW circuit breakers b Enclosure 600 mm deep, access through the front. Position of the jointing unit Circuit breaker Fixed, 3P/ 4P(2) Drawout, 3P/ 4P(2) Dimensions(1) (mm) A B C NW08 / 16 NW20 / 25 NW32 NW08 / 16 NW20 / 25 NW32 185 185 185 185 185 185 325 325 325 344 344 344 264 289 264 164 214 214 DD210767 Design and installation guide (1) Dimensions measured from switchboard framework. (2) To order, see “Catalogue numbers”, page K9AE23000/2. Reference point K9AE42000 Schneider Electric 9 Connection to Prisma Plus LV switchboards By Canalis interface Installation guide Canalis KTA Rear connection (RC) DD202307 To a Compact NS 1600 or Masterpact NT 1600 circuit breaker b Two enclosures combined: v 1 enclosure, 400 mm deep, for the circuit breaker, v 1 enclosure, 400 mm deep, for the Canalis KT/switchboard interface. Position of the jointing unit Circuit breaker Fixed, 3P/ 4P(2) Drawout, 3P/ 4P(2) Dimensions(1) (mm) A B C NS800 / 1600 or NT08 / 16 NS800 / 1600 or NT08 / 16 638 325 160 638 325 170 DD210769 (1) Dimensions measured from switchboard framework. (2) To order, see “Catalogue numbers”, page K9AE23000/2. Reference point DD202305 To 800 to 4000 A Masterpact NW circuit breakers b Two enclosures combined: v 1 enclosure, 600 mm deep, for the circuit breaker, v 1 enclosure, 400 mm deep, for the Canalis KT/switchboard interface. Position of the jointing unit Disjoncteur Fixed, 3P/ 4P(2) Design and installation guide Drawout, 3P/ 4P(2) Dimensions(1) (en mm) A B C NW08 / 16 NW20 / 25 NW32 NW40 NW08 / 16 NW20 / 25 NW32 NW40 815 757 774 790 815 815 815 790 325 325 325 325 317 342 317 325 264 414 414 750 414 414 339 700 DD210771 (1) Dimensions measured from switchboard framework. (2) To order, see “Catalogue numbers”, page K9AE23000/2. Reference point 10 Schneider Electric K9AE42000 Connection to Okken and Prisma Plus LV switchboards By Canalis interface Installation guide Canalis KTA Sealing kit DD210775 DD202314 The sealing kit must be ordered with the KT trunking. The size of the trunking determines that of the sealing kit. For the different types of kit, see the “Catalogue numbers and dimensions” pages. The kit includes a drilling and cut-out drawing for the switchboard roof. DD210774 KTB0ppppTT01 It is advised to cut out the switchboard roof in the workshop. Important. The dimensions are measured from switchboard framework. Design and installation guide DD210776 Cut-out drawing (for all the ratings) Centre lines. K9AE42000 Schneider Electric 11 Connection to LV switchboards By universal feed unit Installation guide Canalis KTA PD202329 Canalis KT can be connected to switchboards via a universal connector. To simplify the work, it is advised to fit the switchboard busbars with a distance between centres of 115 mm. Jointing with the switchboard is via a straight or elbow universal feed unit with a straight or flat outlet. Connections are made using torque nuts offering both ease of use and the possibility of a visual check before energising. Enclosure depth depending on the rating of the trunking Rating of trunking (A) If the order of the phases in the trunking and the switchboard is different, it is advised to invert the phases in the switchboard. If that is not possible, use the phase and neutral crossover components. For more information, see the “Description” section, page K9AE12000/4 and “Catalogue numbers and dimensions” section, page K9AE21020/2. DD210780 Phase order DD210781 Design and installation guide DD210779 Busbars in switchboard (recommended distance between centres = 115 mm) Minimum depth X of switchboard (mm) 400 400 600 DD210778 1000 to 1250 1600 to 2500 3200 to 4000 Depth Y of universal feed unit plate (mm) 230 350 510 KTAppppTNp10 KTAppppTPp10 12 Schneider Electric K9AE42000 Installation guide Connection to LV switchboards By universal feed unit Canalis KTA Cut-out drawing It is advised to cut out the switchboard roof in the workshop. Cut-out for universal feeder unit, with distance between centres = 115 mm Depth Y of universal feed unit plate (mm) 230 350 510 DD210782 Rating of trunking (A) 1000 à 1250 1600 à 2500 3200 à 4000 Design and installation guide Centre lines. K9AE42000 Schneider Electric 13 Connection to LV switchboards By feed and connection plates Installation guide Canalis KTA PD202331 Connection plates are flexible copper bars, insulated or not, and drilled at one or both ends. They are supplied with bolts, washers and torque nuts for connection to straight or elbow universal feed units. To simplify the work, it is advised to universal feed units with a distance between centres of 115 mm. Enclosure depth depending on the rating of the trunking Rating of trunking (A) 1000 to 1250 1600 to 2500 3200 to 4000 Vertical incomer Minimum depth X of switchboard (mm) 400 400 600 Horizontal incomer Design and installation guide DD210779 DD210783 DD202385 Universal feed unit (recommended distance between centres = 115 mm) Depth Y of universal feed unit plate (mm) 230 350 510 KTAppppERpp 14 Schneider Electric K9AE42000 Connection to LV switchboards By feed and connection plates Installation guide Canalis KTA Selection of connection plates The required number of connection plates is indicated in the table below. Busbar trunking rating (A) Short-circuit withstand 1000 to 1600 2000 to 2500 3200 DD210789 DD210788 DD210786 DD210785 Connection plates DD210787 DD210764 Busbar trunking rating (A) Connection plates per phase Number Section (mm2) 1000 2 1000 1250 2 1000 1600 2 1000 2000 3 1500 2500 3 1500 3200 4 2000 4000 5 2500 4000 Short-circuit withstand table DD202359 Short-time withstand current (Icw) y 43 kA 43 kA y Icw y 50 kA 50 kA y Icw y 100 kA Maximum distance between support centres X (mm) 400 225 150 Vertical incomer Phase order DD210780 DD210781 DD210791 If the order of the phases in the trunking and the switchboard is different, it is advised to invert the phases in the switchboard. If that is not possible, use the phase and neutral crossover components. For more information, see the “Description” section, section, page K9AE12000/4 and “Catalogue numbers and dimensions” section, page K9AE21020/2. KTAppppTNp10 KTAppppTPp10 K9AE42000 Schneider Electric 15 Design and installation guide DD210790 DD202349 Horizontal incomer Connection to LV switchboards By feed and connection plates Installation guide Canalis KTA Dimensions of protective covers Horizontal incomer DD202326 Rigid horizontal cover KTBppppCR1 for ER straight outlet feed connectors type N1 to N6 Rating (A) 800 to 1250 1600 to 2500 3200 to 4000 Dimensions (mm) Y D 230 220 to 475 350 220 to 475 510 220 to 475 G 220 to 475 220 to 475 220 to 475 Z 310 to 800 430 to 800 590 to 800 KTBppppCR1 Cut-out drawing DD210953n It is advised to cut out the switchboard roof in the workshop. Design and installation guide Centre lines. 16 Schneider Electric K9AE42000 Connection to LV switchboards By feed and connection plates Installation guide Canalis KTA DD202322 Vertical incomer Rigid vertical cover KTBppppCR2 (400 to 800 mm height) for ER straight outlet feed connectors type N1 to N6 Rating (A) Dimensions (mm) Y D G Z 800 to 1250 230 220 to 475 220 to 475 400 to 800 1600 to 2500 350 220 to 475 220 to 475 400 to 800 3200 to 4000 510 220 to 475 220 to 475 400 to 800 KTBppppCR2 Cut-out drawing DD210953n1 It is advised to cut out the switchboard roof in the workshop. DD202324 Centre lines. Cut-out drawing It is advised to cut out the switchboard roof in the workshop. DD210953n2 Design and installation guide KTBppppCR3 Rigid vertical cover KTBppppCR3 (100 to 400 mm height) for ER straight outlet feed connectors type N1 to N6 Calibre (A) Dimensions (mm) Y D G Z 800 to 1250 230 220 to 475 220 to 475 400 to 800 1600 to 2500 350 220 to 475 220 to 475 400 to 800 3200 to 4000 510 220 to 475 220 to 475 400 to 800 Centre lines. K9AE42000 Schneider Electric 17 Connection to cast resin transformers Selection guide Installation guide Canalis KTA This guide will allow you to: v choose the connection best suited to your layout (incoming direction, flat or edgewise busbar trunking, possibility of adjusting phase order), v check the total height of the link with respect to the premises’ ceiling height, dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link and the ceiling), v optimise your link whilst respecting the following rule: (Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels, v position the sections for the busbar trunking supports. Universal connection TS3 DD202490 TS4 230 238 According to manufacturer’s drawing 350 According to manu drawing 280 - - 350 280(1) Z2 Z1 + 140 Z1 + H Z1 + H 420(1) Selecting phase order Fixed Fixed At time of order At time of order Front or rear exit b b b b b Z0 DD202488 DD202487 Connection with interface to Trihal transformers TS1 TS2 DD202489 Design and installation guide PD202398 Type of connection See page K9AE43000/4 See page K9AE43000/4 Z1 minimum maximum Right or left exit Edgewise layout Flat layout b b b (1) To use standard connection plates L = 406 mm in accordance with our recommendations. 2 Schneider Eletric K9AE43000 Canalis KTA Trunking cross-section Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000 TS7 TS8 DD202494 According to manufacturer’s drawing 350 According to manufacturer’s drawing According to manufacturer’s drawing 280 350 According to manufacturer’s drawing - 350(1) 280(1) 350(1) - Z1 + H 420(1) At time of order At time of order H = 74 or 104 or Z1 + H / 2 + 115 500(1) 124 mm H = 164 or 204 Z1 + H / 2 + 175 or 244 mm H = 324 or Z1 + H / 2 + 255 404 mm At time of order At time of order b b Design and installation guide TS6 DD202492 TS5 DD202493 DD210867 DD202180 Height H (mm) Width W (mm) DD202491 ufacturer’s Connection to cast resin transformers Selection guide Installation guide b b K9AE43000 Schneider Eletric 3 Installation guide Connection to Trihal cast resin transformers By Canalis interface Canalis KTA PD202434 The Trihal dry-type transformers are supplied with a specific interface tested to receive the Canalis KT busbar trunking. Jointing with the switchboard is achieved using a standard run section (straight, elbow section, etc) and a joint block identical to that for connecting run elements. The Canalis KT/ dry type transformer interface, which is fitted to the transformer, is designed to accept the transformer’s 25 % overload in the case of forced ventilation. The connections are tested and qualified in normal operating conditions with respect to temperature rise (∆θ) and short-circuits (Isc). The busbar trunking is quickly connected to the dry-type transformer using a simple joint block with torque nuts, guaranteeing tightening torque. Table of compatibility between Canalis KT and the connection interface for naturally ventilated (AN) dry-type transformers. Dry-type transformer Canalis KT Rating l nominal(1) Interface (kVA) (A) Type Junction Rating (A) Cross-section Type 630 887 1 H124 1250 140 x 104 KTA1000 800 1126 2 H164 1600 140 x 124 KTA1250 1000 1408 3 H204 2000 140 x 164 KTA1600 1250 1760 4 H244 2500 140 x 204 KTA2000 1600 2253 5 H324 3200 140 x 244 KTA2500 2000 2816 6 H404 4000 140 x 324 KTA3200 2500 3520 7 H404 5000 140 x 404 (1) I is given as an indication only and is calculated with U - 410 V. KTA4000 Table of compatibility between Canalis KT and the connection interface for forced ventilated (AF) dry-type transformers. Dry-type transformer Canalis KT Rating l nominal(1) Interface (kVA) (A) Type Junction Rating (A) Cross-section Type 630 1108 1 H124 1250 140 x 124 1250 800 1407 2 H164 1600 140 x 164 1600 1000 1760 3 H204 2000 140 x 204 2000 1250 2253 4 H244 2500 140 x 244 2500 1600 2816 5 H324 3200 140 x 324 3200 2000 3520 6 H404 4000 140 x 404 (1) I is given as an indication only and is calculated with U - 410 V. 4000 If the phase order of the busbar trunking is different to that of the switchboard’s busbars, it is recommended a phase inversion is carried out in the switchboard. If this cannot be done, use the phase and neutral transposition section. For more information, see the “Description” section, page K9AE12000/4 and “Catalogue numbers and dimensions” section, page K9AE21020/2. DD210780 Phase order DD210945 Design and installation guide If, for reasons of busbar trunking operating conditions or performance requirements, you have to use a rating other than those defined in the above tables, consult us. KTAppppTNp10 KTAppppTPp10 4 Schneider Eletric K9AE43000 Connection to Trihal cast resin transformers By Canalis interface Installation guide DD210946 Canalis KTA Reference point Dimensions Dimensions X, Y and Z Dimensions (mm) X M X0 Transformer power (kVA) 630 800 1000 1250 147 150 170 147 100 100 108 93 233 215 265 245 1600 150 124 300 2000 170 144 300 2500 153 149 322.5 Interface type 1 5 6 7 2 3 4 Dimensions Y0 and Z0 Y0 = X + L Z0 = C - M Dimensions C and L are different according to country standards. French standard FT no.235627 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 410 V Dimensions (mm) C L Transformer power (kVA) 630 800 1000 1250 1614 1744 1749 1929 220 225 240 240 1600 2089 240 2000 2209 257 2500 2297 275 Dimensions (mm) C L Transformer power (kVA) 630 800 1000 1250 1734 1744 1749 2019 210 220 225 245 1600 1979 255 2000 2199 255 Design and installation guide German standard FT no.235763 rev. 0 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 400 V 2500 2279 265 Spanish standard FT no.235515 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 420 V Dimensions (mm) C L Transformer power (kVA) 630 800 1000 1250 1614 1744 1879 1929 220 225 215 245 1600 1979 250 2000 2194 245 Belgian standard FT no.235820 rev. 0 - Primary voltage: 15 kV - Insulation voltage: 17.5 kV Secondary voltage: 400 V Dimensions (mm) C L K9AE43000 Schneider Eletric Transformer power (kVA) 630 800 1000 1250 1484 1564 1694 1844 215 210 215 225 1600 2054 230 2000 2149 255 2500 2164 235 5 Installation guide Connection to Trihal cast resin transformers By Canalis interface Canalis KTA DD210947 Sealing kit The sealing kit must be ordered with the KT busbar trunking. The busbar trunking size defines the sealing kit size. For the different types of kit, see “Catalogue numbers / Dimensions”. The kit includes a drilling and cut-out template for the dry-type transformer panels. KTB0ppppTT01 It is recommended that the cutting-out of the transformer panels is done in the workshop. DD210776 Cut-out drawing Design and installation guide Junction axis. 6 Schneider Eletric K9AE43000 Connection to cast resin transformers By universal feed and connection plates Installation guide Canalis KTA PD202330 Canalis KT can be connected to cast resin transformers using a universal feed. The connection is made using a flexible busbar (connection plates or braids) to avoid transmitting vibrations and expansions. The connection plates are made up of either insulated or non-insulated flexible copper bars, drilled at one or both ends. A nut and bolt kit allows connection to the feed. The connections use torque-head bolts which provide both ease of installation and visual inspection of correct tightening before energising. If the transformer is supplied with panels, provide for an additional cover to maintain the protection degree. Choice of Canalis KT busbar trunking rating according to transformer power. Transformer Power (kVA) 630 800 1000 1250 1600 2000 2500 I nominal(1) (A) 887 1126 1408 1760 2253 2816 3520 KTA rating at nominal power(2) (A) 1000 1250 1600 2000 2500 3200 4000 (1) I is given as an indication only and is calculated with U = 410 V and at transformer nominal setting, without forced ventilation. (2) The busbar trunking rating is defined for normal operating conditions. TS3 and TS5 universal connection, edgewise mounting Design and installation guide DD210949 Recommended configurations for shortcircuit withstand (connection plate L = 400 mm) KTAppppELp1 or KTAppppELp2 or KTAppppELp3 or KTAppppELp4 DD210948 TS4 and TS6 universal connection, flat mounting (using angle brackets) KTAppppELp1 or KTAppppELp2 or KTAppppELp3 or KTAppppELp4 with angle bracket KTB0000YE1 K9AE43000 Schneider Eletric 7 Connection to cast resin transformers By universal feed and connection plates Installation guide Canalis KTA DD202481 TS7 universal connection, edgewise mounting KTAppppELp5 DD202480 TS7 universal connection, flat mounting (using angle brackets) KTAppppELp5 with angle bracket KTB0000YE The number of connection plates is defined in the table below: Busbar trunking rating (A) 8 Schneider Eletric 1000 to 1600 2000 to 2500 3200 DD210789 DD210788 Connection plates DD210787 Busbar trunking rating (A) Connection plates per phase Number Cross-section (mm2) 1000 2 1000 1250 2 1000 1600 2 1000 2000 3 1500 2500 3 1500 3200 4 2000 4000 5 2500 DD210786 Design and installation guide DD210950 Definition of connection plates 4000 K9AE43000 Connection to cast resin transformers By universal feed and connection plates Installation guide Canalis KTA Phase order Phase selection is made when the feed is ordered. Phase L2 is fixed and can therefore be used as a reference for installing the feed on the transformer. The different phase selection possibilities (T) DD210951 b Dedicated feeds N1 to N4, Design and installation guide Important: the drawings and references above correspond to a phase order of N321, joint block side. If the phase order on the joint block side is N123, inverse T=1 with T=3 and T=2 with T=4. DD210952 b Feed with flat bars N5. Important: the drawings and references above correspond to a phase order of N321, joint block side. If the phase order on the joint block side is N123, inverse L1 and L3 on the transformer side marking. K9AE43000 Schneider Eletric 9 Connection to cast resin transformers By universal feed and connection plates Installation guide Canalis KTA Dimensions of protective covers DD202344n Vertical protection covers for dry-type transformer feeds N1, N2, N3 and N4 Rating (A) Dimensions (mm) Y Z Minimum Maximum 800 to 1250 230 200 350 1600 to 2500 350 200 350 3200 to 4000 510 200 350 KTB0000CR4 Horizontal protection covers for dry-type transformer feeds N1, N2, N3 and N4 Rating (A) Dimensions (mm) Y Z Minimum Maximum 800 to 1250 230 330 480 1600 to 2500 350 330 480 3200 to 4000 510 330 480 Design and installation guide DD202345n KTB0000CR5 10 Schneider Eletric K9AE43000 Connection to cast resin transformers By universal feed and connection plates Installation guide Canalis KTA Horizontal protection cover for dry-type transformer feed N5 Rating (A) Dimensions (mm) Y Z Minimum Maximum 800 to 1250 230 380 530 1600 to 2500 350 500 650 3200 to 4000 510 660 810 DD202347 KTBppppCR6 Cut-out drawing for dry-type transformer panels Design and installation guide DD202501n It is recommended that the cutting-out of the transformer panels is done in the workshop. K9AE43000 Schneider Eletric 11 Installation guide Connection to oil immersed transformers Selection guide Canalis KTA TH2 DD202417 TH3 DD202418 Vertical incomer TH1 Design and installation guide PD202429 Incomer type DD202416 This guide will allow you to: v choose the connection best suited to your layout (incoming direction, flat or edgewise busbar trunking, possibility of adjusting phase order), v check the total height of the link with respect to the premises’ ceiling height, dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link and the ceiling), v optimise your link whilst respecting the following rule: (Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels, v position the sections for the busbar trunking supports. Z0 According to manufacturer’s drawing According to manufacturer’s drawing According minimum 738 1073 730 maximum 1072 - 1064 Z2 Z1 + H Z1 + H Z1 + 140 Front or rear exit Right or left exit Edgewise layout b b b b Z1 b b Flat layout 2 Schneider Electric K9AE44000 Connection to oil immersed transformers Selection guide Installation guide Canalis KTA Trunking cross-section Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000 Direct connection TH5 DD202420 Design and installation guide TH4 DD202419 DD210867 DD202180 Height H (mm) Width W (mm) g to manufacturer’s drawing According to manufacturer’s drawing According to manufacturer’s drawing 1065 Z1 = (Y/ H) / 2 - Z1 = (Y/ H) / 2 Z1 + 140 H = 74 or 104 or 124 mm H = 164 or 204 or244 mm H = 324 or 404 mm b 510 770 850 b b b K9AE44000 Schneider Electric 3 Connection to oil immersed transformers By feed and connection plates or braids Installation guide Canalis KTA PD202300 Connection to an oil immersed transformer is made using flexible bars (connection plates) to avoid transmitting transformer vibrations to the busbar trunking and to limit the stress on connection terminals. Choice of busbar trunking Dry-type transformer Rating (kVA) 500 630 800 1000 1250 1600 2000 2500 l nominal(1) (A) 704 887 1126 1408 1760 2253 2816 3520 Canalis KT aluminium busbar trunking Rating (A) Cross-section 800 1000 1250 1600 2000 2500 3200 4000 140 x 74 140 x 104 140 x 124 140 x 164 140 x 204 140 x 244 140 x 324 140 x 404 (1) I is given as an indication only and is calculated with U - 410 V. Note: If, for reasons of busbar trunking operating conditions or performance requirements, you have to use a rating other than those defined in the above tables, consult us. Protective cover width Busbar trunking rating (A) 1000 to 1250 1600 to 2500 3000 to 4000 Vertical incomer Horizontal incomer Design and installation guide DD202422 DD202421 Recommended configurations for shortcircuit withstand (connection plate L = 400 mm) Dimensions “Y” of the feed 230 350 510 4 Schneider Electric K9AE44000 Connection to oil immersed transformers By feed with connection plates or braids Canalis KTA Several connection possibilities Phase order With connection plates with kink to be drilled DD202424n DD202423n With connection plates with kink and bar clamp With drilled connection plates (KTB0000YC4) or braids DD202425n Installation guide Design and installation guide DD210780 DD210781 DD210791 If the phase order of the busbar trunking is different to that of the switchboard’s busbars, it is recommended a phase inversion is carried out in the switchboard. If this cannot be done, use the phase and neutral transposition section. For more information, see the “Description” section, page K9AE12000/4 and “Catalogue numbers and dimensions” section, page K9AE21020/2. KTAppppTNp10 KTAppppTPp10 K9AE44000 Schneider Electric 5 Canalis KTA Connection to oil immersed transformers By feed with connection plates or braids Definition of connection plates The number of connection plates is defined in the table below: 1000 to 1600 DD210789 2000 to 2500 3200 4000 DD210785 Busbar trunking rating (A) DD210788 DD202426 Connection plates DD210787 Busbar trunking rating (A) Connection plates per phase Number Cross-section (mm2) 1000 2 1000 1250 2 1000 1600 2 1000 2000 3 1500 2500 3 1500 3200 4 2000 4000 5 2500 DD210786 DD210764 Installation guide The number of braids is defined in the table below: Busbar trunking rating (A) Braids per phase Number 1000 1 1250 2 1600 2 2000 2 2500 3 3200 3 4000 4 6 Schneider Electric 1000 1250 to 2000 2500 to 3200 DD202376 DD210773 Busbar trunking rating (A) DD210770 Design and installation guide Braids Cross-section (mm2) 600 1200 1200 1200 1800 1800 2400 DD210768 DD202355 Definition of braids 4000 K9AE44000 Canalis KTA Connection to oil immersed transformers By feed with connection plates or braids Dimensions of protective covers Horizontal incomer Installation guide Rigid horizontal cover KTBppppCR1 for ER straight outlet feed connectors type N1 to N6 Rating (A) 800 to 1250 1600 to 2500 3200 to 4000 Dimensions (mm) Y D 230 220 to 475 350 220 to 475 510 220 to 475 G 220 to 475 220 to 475 220 to 475 Z 310 to 800 430 to 800 590 to 800 DD202326 KTBppppCR1 Adjustable cover KTBppppCR7 for horizontal incomer feed connectors with a between centres distance of 150 or 170 mm Rating (A) 800 to 1250 1600 to 2500 3200 to 4000 Dimensions (mm) Y Z X 230 565 450 350 825 650 510 905 650 A 830 890 960 B 750 810 880 E 330 350 460 F 125 265 185 G 365 485 645 DD210872n KTBppppCR7 Vertical incomer Design and installation guide Rigid vertical cover KTBppppCR2 (400 to 800 mm height) for ER straight outlet feed connectors type N1 to N6 Rating (A) Dimensions (mm) Y D G Z 800 to 1250 230 220 to 475 220 to 475 400 to 800 1600 to 2500 350 220 to 475 220 to 475 400 to 800 3200 to 4000 510 220 to 475 220 to 475 400 to 800 DD202322 KTBppppCR2 K9AE44000 Schneider Electric 7 Connection to oil immersed transformers By feed with connection plates or braids Installation guide Canalis KTA Adjustable cover KTBppppCR8 for vertical incomer feed connectors with a between centres distance of 150 or 170 mm Rating (A) 800 to 1250 1600 to 2500 3200 to 4000 Dimensions (mm) Y Z A 230 600 830 350 600 890 510 600 960 B 750 810 880 C 345 460 625 E 330 350 460 DD210870n KTBppppCR8 Flexible cover KTBppppCR8 for vertical incomer straight outlet feed connectors with a between centres distance of 115 mm Rating (A) Dimensions (mm) Y C 800 to 1250 230 200 to 650 1600 to 2500 350 200 to 650 3200 to 4000 510 200 to 650 Design and installation guide DD202319 KTBppppCS0 8 Schneider Electric K9AE44000 Connection to oil immersed transformers Other connection solutions Installation guide Canalis KTA Connection to bar bushings DD210955 Canalis KT is easily connected to Minera oil immersed transformers (France Transfo offer). For more details of drilling dimensions for the bushings and the connection terminals, refer to the manufacturer’s catalogue. Connections to Minera ground mounted oil immersed transformers from 630 to 3150 kVA - y 24 kV / 400 V K9AE44000 2000 3150 2500 3150 5000 Schneider Electric Design and installation guide 2500 DD202427 1250 1600 DD202428 1600 DD202429 1000 Dimensions (mm) DD202430 Bar bushings (A) 1250 DD2024321 Power (kVA) 630 800 9 Connection to oil immersed transformers Other connection solutions Installation guide Canalis KTA Connection to porcelain bushings DD210959 Connection terminals of the type defined below must be used. These are available in the transformer manufacturers’ catalogues. Cover Design and installation guide DD210957 The transformers can be supplied with or without a low voltage cover. This cover is not used in our solutions. 10 Schneider Electric K9AE44000