Busbar trunking for lighting

advertisement
11082-EN.fm Page 2 Jeudi, 12. février 2004 4:45 16
Characteristics
Busbar trunking for lighting
Canalis KBA 25 and 40 A
Type of trunking
KBA-25
KBA-40
General electrical characteristics
2
Conformity to standards
IEC 439-2 and EN 60439-2
Number of live conductors
2 or 4
2 or 4
Rated nominal current
Inc (average ambient temperature 35°C)
A
25
40
Type of current/
rated frequency
F
Hz
50/60
50/60
Rated insulation voltage
Ui
V
660 (2)
660 (2)
Rated operating voltage
Degree of protection conforming to
IEC 529
Ue
V
230…400
IP54
230…400
IP54
R20 or Rb0 ph (1) average resistance, cold
state (temp. ambiante 20 °C)
mΩ/m
6.83
2.93
R1 or Rb1 ph (1) average resistance at Inc
(ambient temperature 35 °C)
mΩ/m
8.33
3.55
X1 or Xb ph (1) average reactance at Inc
and at 50 Hz rated frequency
mΩ/m
0.21
0.18
Average resistance, cold state
(ambient temperature 20 °C)
mΩ/m
1.57
1.57
Rb1 ph ph or ph N (at thermal
stabilisation temperature θ 1)
mΩ/m
16.66
7.10
Rb2 ph ph or ph N (1) (at conventional
short-circuit temperature)
mΩ/m
20.90
8.52
Xb ph ph
mΩ/m
1.68
0.79
Xb ph N
mΩ/m
2.08
0.83
Rb1 ph PE (at thermal
stabilisation temperature θ 1)
mΩ/m
9.90
5.12
Rb2 ph PE (1) (at conventional
short-circuit temperature)
mΩ/m
11.88
6.14
Xb ph PE
mΩ/m
1.09
1.40
Short-circuit current
withstand
Ipk permissible rated peak current
I2t maximum thermal limit
kA
A2s
4.40
195.103
9.60
900.103
Voltage drop
Voltage drop, for single-phase current 50 Hz, in volts per 100 m and per ampere with loads evenly distributed
along the run (general case for lighting).
Voltage drop for 3-phase: multiply these values by 0.866.
For Cos.ϕ = 0.8
0.29
V/100m/A 0.68
For Cos.ϕ = 0.9
0.33
V/100m/A 0.76
For Cos.ϕ = 1
0.36
V/100m/A 0.83
Normal mounting position
Edgewise
Electrical characteristics of conductors
Live conductors
(per conductor)
Protective conductor
Fault loop characteristics
Average loop resistance between
live connectors
Average loop reactance
Average loop resistance
between live and PE conductors
Average loop reactance
Other characteristics
Permissible current depending
on the temperature
k1 uprating/derating multiplying factor to be applied to the desired rated current Inc of the busbar trunking for an
average daily ambient temperature different to 35 °C
Ambient temperature
15
20
25
30
35
40
45
50
°C
k1 factor
1.13 1.10 1.07 1.04 1.00 0.96 0.93 0.89
(1) In accordance with CENELEC document RO 64-003.
(2) 500 V for busbar trunking fitted with option T and for 16 A tap-off units (KBC-16)
Description: pages 11081EN.fm/2 to 11081-EN.fm/6
11082-EN.fm/2
Mounting and installation
study: pages 11081-EN.fm/7
and 11082-EN.fm/3
References:
pages 11083-EN.fm/2, 11083EN.fm/3, 11085-EN.fm/2 and
11085-EN.fm/3
11082-EN.fm Page 3 Jeudi, 12. février 2004 4:45 16
Characteristics
Busbar trunking for lighting
Canalis KBA 25 and 40 A
Type of trunking
KBC-10
KBC-16CB
KBC-16CF
General electrical characteristics
Conformity to standards
IEC 439-2 and EN 60439-2
Number of live conductors
2
2
2
Rated nominal current
Inc (average ambient temperature 35°C)
A
10
16
16
Type of current/
rated frequency
F
Hz
50/60
50/60
50/60
Rated insulation voltage
Ui
V
690
690
400
Rated operating voltage
Ue
V
230…400
230…400
230…400
IP54
IP54
IP54
Degree of protection conforming to
IEC 529
2
Installation study
Selecting the busbar trunking
Knowing:
p The type of luminaire (types of lamp, power,
compensated or not), their weight, number and
distribution.
p The structure of the premises (option of mounting
busbar trunking).
p External influences (IP degree required).
Reminder of the various stages of selecting the busbar trunking (See the selection and study guides on
page 0120Q-EN.fm/2 and page 0120Q-EN.fm/2 and page 11068-EN.fm/2 to page 11068-EN.fm/11)
p Select the type of busbar trunking depending on the possible fixing distance and/or the weight of the luminaires.
p Select the number of live conductors depending on the distribution scheme chosen or the number of lighting
circuits.
p Select the Inc rating depending on the operating current.
p Select the power supply cable (type and cross-section) depending on the operating current and the type of protection
against overloads.
p Check the voltage drops.
p Select the type of protection against short-circuits and its coordination with the busbar trunking.
Selecting the tap-off units
Tap-off units are always single-phase L + N + PE or 2L + PE.
Their selection depends on the functions required during installation and operation.
Selection criteria
Terminals Pre-wired Pre-wired Terminals Fused
10 A
10 A
10 A
16 A
16 A
KBC-10CB KBC-10CC KBC-10CS KBC-16CB KBC-16CF
Simplicity
Open-ended installation (modification of scheme)
Individual protection of the luminaire and cable
Selectivity of protection on a fault
Remote controlled equipment
Specific cable (type, cross-section, length, etc)
Description: pages 11081EN.fm/2 to 11081-EN.fm/6
Mounting and installation
study: pages 11081-EN.fm/7
and 11082-EN.fm/3
b
b
b
b
b
b
b
References:
pages 11083-EN.fm/2, 11083EN.fm/3, 11085-EN.fm/2 and
b
b
b
b
b
11085-EN.fm/3
11082-EN.fm/3