11082-EN.fm Page 2 Jeudi, 12. février 2004 4:45 16 Characteristics Busbar trunking for lighting Canalis KBA 25 and 40 A Type of trunking KBA-25 KBA-40 General electrical characteristics 2 Conformity to standards IEC 439-2 and EN 60439-2 Number of live conductors 2 or 4 2 or 4 Rated nominal current Inc (average ambient temperature 35°C) A 25 40 Type of current/ rated frequency F Hz 50/60 50/60 Rated insulation voltage Ui V 660 (2) 660 (2) Rated operating voltage Degree of protection conforming to IEC 529 Ue V 230…400 IP54 230…400 IP54 R20 or Rb0 ph (1) average resistance, cold state (temp. ambiante 20 °C) mΩ/m 6.83 2.93 R1 or Rb1 ph (1) average resistance at Inc (ambient temperature 35 °C) mΩ/m 8.33 3.55 X1 or Xb ph (1) average reactance at Inc and at 50 Hz rated frequency mΩ/m 0.21 0.18 Average resistance, cold state (ambient temperature 20 °C) mΩ/m 1.57 1.57 Rb1 ph ph or ph N (at thermal stabilisation temperature θ 1) mΩ/m 16.66 7.10 Rb2 ph ph or ph N (1) (at conventional short-circuit temperature) mΩ/m 20.90 8.52 Xb ph ph mΩ/m 1.68 0.79 Xb ph N mΩ/m 2.08 0.83 Rb1 ph PE (at thermal stabilisation temperature θ 1) mΩ/m 9.90 5.12 Rb2 ph PE (1) (at conventional short-circuit temperature) mΩ/m 11.88 6.14 Xb ph PE mΩ/m 1.09 1.40 Short-circuit current withstand Ipk permissible rated peak current I2t maximum thermal limit kA A2s 4.40 195.103 9.60 900.103 Voltage drop Voltage drop, for single-phase current 50 Hz, in volts per 100 m and per ampere with loads evenly distributed along the run (general case for lighting). Voltage drop for 3-phase: multiply these values by 0.866. For Cos.ϕ = 0.8 0.29 V/100m/A 0.68 For Cos.ϕ = 0.9 0.33 V/100m/A 0.76 For Cos.ϕ = 1 0.36 V/100m/A 0.83 Normal mounting position Edgewise Electrical characteristics of conductors Live conductors (per conductor) Protective conductor Fault loop characteristics Average loop resistance between live connectors Average loop reactance Average loop resistance between live and PE conductors Average loop reactance Other characteristics Permissible current depending on the temperature k1 uprating/derating multiplying factor to be applied to the desired rated current Inc of the busbar trunking for an average daily ambient temperature different to 35 °C Ambient temperature 15 20 25 30 35 40 45 50 °C k1 factor 1.13 1.10 1.07 1.04 1.00 0.96 0.93 0.89 (1) In accordance with CENELEC document RO 64-003. (2) 500 V for busbar trunking fitted with option T and for 16 A tap-off units (KBC-16) Description: pages 11081EN.fm/2 to 11081-EN.fm/6 11082-EN.fm/2 Mounting and installation study: pages 11081-EN.fm/7 and 11082-EN.fm/3 References: pages 11083-EN.fm/2, 11083EN.fm/3, 11085-EN.fm/2 and 11085-EN.fm/3 11082-EN.fm Page 3 Jeudi, 12. février 2004 4:45 16 Characteristics Busbar trunking for lighting Canalis KBA 25 and 40 A Type of trunking KBC-10 KBC-16CB KBC-16CF General electrical characteristics Conformity to standards IEC 439-2 and EN 60439-2 Number of live conductors 2 2 2 Rated nominal current Inc (average ambient temperature 35°C) A 10 16 16 Type of current/ rated frequency F Hz 50/60 50/60 50/60 Rated insulation voltage Ui V 690 690 400 Rated operating voltage Ue V 230…400 230…400 230…400 IP54 IP54 IP54 Degree of protection conforming to IEC 529 2 Installation study Selecting the busbar trunking Knowing: p The type of luminaire (types of lamp, power, compensated or not), their weight, number and distribution. p The structure of the premises (option of mounting busbar trunking). p External influences (IP degree required). Reminder of the various stages of selecting the busbar trunking (See the selection and study guides on page 0120Q-EN.fm/2 and page 0120Q-EN.fm/2 and page 11068-EN.fm/2 to page 11068-EN.fm/11) p Select the type of busbar trunking depending on the possible fixing distance and/or the weight of the luminaires. p Select the number of live conductors depending on the distribution scheme chosen or the number of lighting circuits. p Select the Inc rating depending on the operating current. p Select the power supply cable (type and cross-section) depending on the operating current and the type of protection against overloads. p Check the voltage drops. p Select the type of protection against short-circuits and its coordination with the busbar trunking. Selecting the tap-off units Tap-off units are always single-phase L + N + PE or 2L + PE. Their selection depends on the functions required during installation and operation. Selection criteria Terminals Pre-wired Pre-wired Terminals Fused 10 A 10 A 10 A 16 A 16 A KBC-10CB KBC-10CC KBC-10CS KBC-16CB KBC-16CF Simplicity Open-ended installation (modification of scheme) Individual protection of the luminaire and cable Selectivity of protection on a fault Remote controlled equipment Specific cable (type, cross-section, length, etc) Description: pages 11081EN.fm/2 to 11081-EN.fm/6 Mounting and installation study: pages 11081-EN.fm/7 and 11082-EN.fm/3 b b b b b b b References: pages 11083-EN.fm/2, 11083EN.fm/3, 11085-EN.fm/2 and b b b b b 11085-EN.fm/3 11082-EN.fm/3