SECTION 26 2417 DISCONNECT SWITCHES PART 1 GENERAL 1.1 SECTION INCLUDES A. 1.2 Safety disconnect switches. REFERENCES A. National Electrical Manufacturers Association (NEMA). B. Underwriters' Laboratories, Inc. (UL). 1.3 SYSTEM DESCRIPTION A. 1.4 Disconnect switches provide safe disconnecting of electrical power to equipment. SUBMITTALS A. Submit the following information in accordance with Division 01: 1. Outline drawing with dimensions. 2. Equipment Ratings. a. Voltage. b. Capacity. c. Horsepower. d. Short circuit withstand rating. 1.5 QUALIFICATIONS A. Safety switches shall be NEMA heavy-duty type and shall carry the UL label. Fusible switches shall incorporate Class "R" fuse rejection feature and shall be braced to withstand 50,000 ampere RMS symmetrical fault current. B. Switches shall be of the same manufacturer as the panelboards. C. Safety switches used for service entrance equipment shall be UL listed as suitable for service entrance. IDPS Fleet and Supply Building 414222-0 26 2417-1 SECTION 26 2417 DISCONNECT SWITCHES PART 2 PRODUCTS 2.1 REQUIREMENTS A. Provide heavy-duty type, sheet steel enclosed, safety switches. Type, size, and rating shall be as shown on the drawings or as required by the motor or equipment served. B. Switches shall incorporate quick-make, quick-break operating handles. Mechanism shall be an integral part of the box, not the cover, and switches shall have a cover interlock to prevent unauthorized opening of the switch door in the on position or closing of the switch mechanism with the door open. Current carrying parts shall be constructed of high-conductivity copper with silver-tungsten type switch contact. C. Fuse clips shall be positive pressure type reinforced rejection type fuse clips. D. Indoor enclosures shall be NEMA 1. Enclosures for wet locations and for outdoor use shall be NEMA 3R. E. Terminals of the proper size for wire as shown on the drawings for line, load and ground shall be supplied by the disconnect switch manufacturer. PART 3 EXECUTION 3.1 INSTALLATION A. Furnish and install safety disconnect switches (fused and non-fused) shown on the drawings. In addition, furnish a safety disconnect switch for motors and equipment which do not have combination starters or integral disconnecting means. B. For mechanical equipment rated for use only with fuses (such as condensing units, compressors, chillers), provide fusible disconnect switches. Such switches shall be one, two or three pole type, with solid neutral for 4- wire service, and shall have the proper current and voltage rating as required. C. Each motor shall be individually protected. Furnish a safety disconnect for each motor as required by the NEC. D. Disconnect switches shall not be directly mounted to equipment which is mounted on vibration isolation pads or springs, unless a piece of flexible conduit is used between the disconnect switch and the fixed conduit. E. Safety switches shall be mounted securely to walls, columns or machine frames, and provided with brackets, mounting devices, structural pieces and expansion type anchor inserts necessary for this purpose. Switches shall not be mounted directly to metal surfaces or to concrete or masonry walls. Structural channels such as Kindorf or 3/4" plywood shall be used to mount switches at least 3/4 inch away from the mounting surface. F. Switches shall be mounted at a height of 60 inches above the finished floor to the top of the back box. IDPS Fleet and Supply Building 414222-0 26 2417-2 SECTION 26 2417 DISCONNECT SWITCHES G. Coordinate fusible switches and fuse sizes, with mechanical trades, where required by UL listing for mechanical equipment installation. H. Motors larger than 1/8 horsepower and controllers shall have a disconnecting means within sight and within 50'. 1. Combination motor starters, circuit breakers in panelboards, manual motor starters, integral disconnecting means on equipment, and cord/plug connections may be used as disconnecting means where they are within sight and 50' of the equipment. 2. Switches, combination starters, and circuit breakers which are pad-lockable in the "OFF" position may be used as disconnecting means when not in sight or within 50' unless prohibited by local code. 3. Provide a disconnect switch for motors, motor-driven appliances, and controllers not covered by paragraphs 1 or 2 above. I. Transformers shall have a disconnecting means (primary and secondary) within sight and within 50'. 1. Provide primary non-fused disconnect switches where the primary over-current device is more than 50' or not in sight of the transformer. 2. Provide secondary fused disconnect switches or separately enclosed circuit breakers where the secondary over-current device is required to meet the 10 foot or 25 foot tap rule of the currently enforced edition of the national electrical code. END OF SECTION 26 2417 IDPS Fleet and Supply Building 414222-0 26 2417-3