Flush Mounting Model 5860 Remote Fire Annunciator Installation Quick Reference Securing Back Box to Wall for Flush Mounting Attach second set of wires to top of back box. Refer to 5820 installation manual (P/N 150972) for complete information. Installation Steps Secure the wires behind this screw. Insert wires at an angle into the first holes past the sheet rock. 1. Make sure power is off at the panel. 2. Annunciator is assembled at the factory. Disassemble as needed. 3. Mount annunciator. See pages 3-4. 4. Wire annunciator to the panel. See page 2. 5. Use dipswitches to set annunciator ID. See page 2. Flush Mounting with Electrical Box (Example) When flush-mounting using an electrical box, the box must be 1-1/4" (min.) from face of wall. Annunciator Parts 1-1/4" Back Box Annunciator back box Electronic Assembly (front view) FIRE ALARM ANNUNCIATOR GENERAL ALARM SUPERVISORY SYSTEM TROUBLE SYSTEM SILENCE SYSTEM POWER MODEL 5860 1 2 3 4 5 6 7 8 9 * 0 # RESET ENTER SILENCE Electrical Box Bezel (external ring) Assembled annunciator also includes mounting wires, 2 set screws. Sheet rock 4 P/N 151042 Connection to the Panel Annunciator Dimensions 5820 Board Assembly Side View Bezel (escutcheon plate) Annunciator back box SBUS OUT 19 18 17 16 - + A B 7-3/8" 6-7/16" 1-1/4" 8-1/8" 9-1/8" 8 annunciators max. per system 1-1/4" 1-9/16" SB SA S+ S- Model 5860 Annunciator (back view) ON 1 2 3 4 5 Dipswitches The Model *5860T-G/R Trim Ring is available to provide a finished look to surface-mounted annunciators. Possible ID Numbers 1 2 3 4 5 Address *0 1 2 3 4 5 Address 16 1 17 2 18 3 19 4 20 5 21 6 22 7 23 8 24 9 25 10 26 11 27 12 28 13 29 14 30 15 31 Surface Mounting *5860T-G is gray 5860T-R is red Assemble trim ring and back box before attaching box to wall. Trim Ring ON OFF Back Box *Note: Address 0 cannot be used. 2 3