CWC PCA GL 0109 E LQ

advertisement
CWC • 2 Î 9 kW
Chilled water cassettes
Main applications
• Any light commercial building
• Offices
• Shops
Why this choice?
•
•
•
•
Easy and quick to install
Best aesthetic metallic diffuser
Electric heater possibility
Different RAL colours for metallic diffuser
General description
Centrifugal water chilled cassettes in 6 capacity sizes, 2 and 4 pipe systems or 2 pipe system with additional electric heater, with plastic
or metal diffuser.
Main components
•
•
•
•
Main structure in galvanized sheet casing, fully insulated inside.
Washable and easily accessible air filter.
Units are supplied with one or two three speed centrifugal direct drive fans. Motor is protected with internal thermal protection.
Heat exchangers with copper tubes and aluminium fins to ensure maximum efficiency:
‚
2 pipe cooling or heating: 1R CWC 20, 2R CWC 30/40, 3R CWC 50, 2R CWC 70, 3R CWC 90
‚
4 pipe cooling: 1R CWC 20, 1 or 3R CWC 30, 2R CWC40, 2R CWC 50/70, 2R CWC 90
‚
4 pipe heating: 1R CWC 20, 2R CWC 30, 1R CWC 40, 2R CWC 50/70/90
• Condensate drain pump as standard
Available accessories - configurations
•
•
•
•
•
•
•
•
•
106
Electric heater
Auxiliary drain pan
2 and 3 way regulating valves
Kit floating switch for condensate pump activation (and alarm)
Fresh air kit (duct connection, fresh air fan, duct supports)
Water level security kit
Kit for air supply to an adjacent room (duct connection, duct supports)
Different RAL colours for metallic diffuser
Thermostats and controls
General Product Catalogue · 01-2009 · Non contractual photos
General data
COMFAIR™ 2 pipe version
Cooling capacity
CWC
20
30
40
50
70
90
(1)
Cooling capacity
kW
1,87
3,41
4,09
5,33
7,40
8,71
Sensible capacity
kW
1,48
2,73
3,19
3,96
5,76
6,49
Chilled water flow
l/h
329
577
712
930
1343
1513
kPa
14,2
22
37,9
37,2
26,2
28,7
kW
2,60
4,05
4,61
6,09
8,31
9,79
Hot water flow
l/h
329
595
712
930
1343
1513
Pressure drop
kPa
17
21,8
37,7
44,4
24,9
24,8
kW
1,5
2
2
-
4
4
0,046
0,046
0,069
0,094
0,180
0,220
A
0,2
0,2
0,3
0,5
0,8
0,9
Minimum airflow
m3/h
445
400
553
650
987
1126
Maximum airflow
m3/h
650
598
779
920
1342
1569
dB(A)
44
40
47
53
51
56
dB(A)
52
50
55
62
60
65
CWC
20
30
40
50
70
90
Pressure drop
Heating capacity
(2)
Heating capacity
Electrical heater
Capacity
Electrical data
Voltage
V / Ph / Hz
Motor power input
kW
Nominal current
230/1/50
Airflow
Sound level
Sound power level at minimum airflow (4)
Sound power level at maximum airflow
(4)
COMFAIR™ 4 pipe version
Cooling capacity
(1)
Cooling capacity
kW
2,03
2,73
3,27
4,25
6,06
7,89
Sensible capacity
kW
1,77
2,25
2,88
3,45
5,01
6,24
Chilled water flow
l/h
358
489
647
809
1124
1369
kPa
13,5
33
27
36,5
18,4
25
kW
1,51
2,26
3,25
4,41
6,75
7,65
Hot water flow
l/h
126
213
295
373
575
653
Pressure drop
kPa
2,6
9,4
34,9
38
27
25,6
Pressure drop
Heating capacity
(3)
Heating capacity
Electrical data
Voltage
V / Ph / Hz
Motor power input
kW
230/1/50
0,046
0,046
0,069
0,094
0,180
0,220
A
0,2
0,2
0,3
0,5
0,8
0,9
Minimum airflow
m3/h
445
400
553
650
987
1126
Maximum airflow
m3/h
650
598
779
920
1342
1569
dB(A)
41
40
47
53
52
56
dB(A)
51
50
55
62
60
64
Nominal current
Airflow
Sound level
Sound power level at minimum airflow (4)
Sound power level at maximum airflow
(4)
Data given at Maximum speed - 0 Pa available static pressure
(1) Max speed : Cooling : Water inlet temperature: 7°C; water outlet temperature: 12°C; air inlet temperature: 27°C D.B - 19°C W.B
(2) Max speed : Heating : Water inlet temperature: 50°C; water flow rate as in cooling mode; air inlet temperature: 20°C
(3) Max speed : Heating : Water inlet temperature: 70°C; water outlet temperature: 60°C; air inlet temperature: 20°C
(4) Sound power level dB(A) ref 10 (-12) W
CWC is part of FC Eurovent Certification Program (www.eurovent-certification.com)
General Product Catalogue · 01-2009 · Non contractual photos
107
COMFAIR™ CWC
Physical data
C
Sizes 20, 30, 40 and 50
A
B
B
A
Plastic diffuser
Metallic diffuser
B
B
C
C
Sizes 70 and 90
A
A
Plastic diffuser
COMFAIR™
Metallic diffuser
CWC
20
30
40
50
70
90
A
mm
575
575
575
575
1175
1178
B
mm
575
575
575
575
575
575
C
mm
298
298
298
298
298
298
kg
21
22
23
24
43
45
A
mm
720
720
720
720
1320
1320
B
mm
720
720
720
720
720
720
C
mm
48
48
48
48
48
48
kg
3
3
3
3
5
5
Casing
Weight
Plastic Diffuser
Weight
Metallic Diffuser
A
mm
619
619
619
619
1219
1219
B
mm
619
619
619
619
619
619
C
mm
27
27
27
27
27
27
kg
5
5
5
5
11
11
Weight
108
General Product Catalogue · 01-2009 · Non contractual photos
Main accessories and components
Drain pan
Condensate pump
Electric heater
Regulating valves
Fresh air supply kit (Coupling flange + antivibrating flange)
Kit discharge air to an adjacent room (Coupling reduction 125/75 mm + coupling flange Ø 75 mm +
antivibrating flange)
General Product Catalogue · 01-2009 · Non contractual photos
109
Download