HF ESP, POWERPLUS SERIES ELECTRICAL BLOCK DIAGRAM

advertisement
HF ESP, POWERPLUS SERIES
ELECTRICAL BLOCK DIAGRAM
CUSTOMER
SUPPLIED
120 / 240VAC
SOURCE
POWER PLUS -06 SERIES
TYPICAL
MOTOR
STARTER
J2
2.5A
1
1
OUTPUT #4
2
2
NORMALLY OPEN DRY CONTACTS
3
3
OUTPUT #3
4
4
RATED FOR 240VAC, 3A MAX.
5
5
OUTPUT
#2
FUSED FOR 2.5AMPS.
6
6
7
7
OUTPUT #1
8
8
PLUG-IN
HAMMER BOARD
CONNECTOR
OPTION
(26-12AWG) J1
1
1 FEEDBACK #4
2
2 FEEDBACK #3
3
3 FEEDBACK #2
4
4 FEEDBACK #1
5
5 COMMON
6
6 COMMON
7
7 COMMON
8
8 COMMON
PLUG-IN
CONNECTOR
(26-12AWG)
D25193-01
H
N
2TB
21 120 VAC SOURCE FROM 1T (N)
23A 120 VAC SOURCE FROM FU (H)
REMOTE OFF
NOTE 11
28 120 VAC INPUT (H)
NOTE 2
45
44 AUX 3
OR
46 AUX ALARM COMMON
NOTE 3
48 REMOTE ON
REMOTE ON
51 EXTERNAL LOCAL/REMOTE
+
+
4-20 mA
OUTPUT
REMOTE KEYPAD &
DISPLAY MODULE
3 PHASE NOMINAL INPUT
POWER.
CIRCUIT BREAKER CURRENT
RATINGS:
45 AUX 4
46
4-20 mA
OUTPUT
-
70
OPTIONAL kV TRANSDUCER
71
72
OPTIONAL mA TRANSDUCER
73
82
1CON
AUX
83
84
1CB
1CON
AUX
85
35 COM
36 LO (-)
NOTE 6
TB2
SHIELD
LO
61 COM
HI
62 LO (-)
NOTE 7
REMOTE DISPLAY
POWER SUPPLY KIT
MODEL # 110045
1
NETWORK PORT
63 HI (+)
2
SEE NOTE 4
TB1
H
LOCAL PORT
37 HI (+)
COM
RJ45
1CR
ALARM RELAY
N
OPTIONAL
FIELD BUS CONVERTER
kW
Nom. VAC
4.2
8.5
17
21
28
28
35
45
56
56
70
84
96
105
120
128
160
160
200
400-480
400-480
400-480
400-480
400
480
480
400
400
480
480
400
400
480
480
400
400
480
480
Circuit Breaker
Rating - Amps
15
20
40
50
70
60
70
100
150
100
150
200
250
200
250
300
400
300
400
CUSTOMER
COMMUNICATIONS
CABLE COMPLIANT WITH
FIELD BUS STANDARD
GO TO:
http://anybus.com/products/abcc30.shtml
EZ SCOPE PORT
85-265 VAC
SOURCE
NOTE 5
RJ45
mA
BNC
INDICATES
FIELD
WIRING
kV
BNC
CONNECTION PORT FOR LOCAL
KEYPAD & DISPLAY MODULE
(EXTERNAL ACCESS)
EXTERNAL GROUND CONNECTION
HV BUSHING CONNECTION
SEE PHYSICAL O/L FOR DETAILS
NOTES:
1) OPTIONAL AUXILIARY ALARM INPUT. NORMALLY OPEN OR NORMALLY CLOSED CONTACT ADJUSTABLE IN SOFTWARE. SEE MANUAL FOR ADJUSTMENT. IF
EXTERNAL 120VAC SOURCE IS USED, THE NEUTRAL MUST BE CONNECTED TO TERMINAL 46. THE EXISTING JUMPER TO THE INTERNAL 120VAC NEUTRAL MUST
REMAIN.
2) REMOVE JUMPER TO INSTALL NORMALLY CLOSED REMOTE ENABLE INTERLOCK OR REMOTE OFF PUSH BUTTON. A MOMENTARY OPEN ON THE REMOTE ENABLE
CONTACT WILL TURN THE HV OFF.
3) A MOMENTARY CLOSE ON "REMOTE ON" CONTACT WILL ENERGIZE THE HV.
4) ALARM RELAY 1CR ENERGIZES ON ALARM. END USER MUST WIRE DIRECTLY TO THE DPDT CONTACTS ON THE RELAY SOCKET MOUNTED ON 2TB DIN RAIL.
5) EXTERNAL 85-265 VAC SOURCE SHOULD BE APPROXIMATELY 50 VA. EXTERNAL SOURCE IS PREFERRED IF VIEWING MULTIPLE POWER PLUS UNITS WITH SINGLE
DISPLAY. IF EXTERNAL SOURCE NOT AVAILABLE, CONTROL POWER MAY BE TAPPED FROM 2TB-23 AND 2TB-21.
6) WIRE THE DISPLAY POWER SUPPLY TO THE LOCAL PORT WHEN USED ON A SINGLE POWERPLUS.
7) WIRE THE DISPLAY POWER SUPPLY TO THE NETWORK PORT WHEN USE ON TWO OR MORE POWERPLUS. SEE DRAWING B122876 FOR WIRING DETAILS.
8) MAXIMUM RAPPER OUTPUT 240 VAC, 2.5 AMPS. OPTIONAL ROTATING HAMMER/RAPPER CONTROL BOARD REQUIRED.
9) RUN 120 VAC WIRING IN SEPARATE CONDUIT OR TRAY FROM 480 VAC WIRING. RUN COMMUNICATION WIRING (NETWORK OR LOCAL PORT) IN SEPARATE
CONDUIT OR TRAY FROM 120 VAC WIRING AND 480 VAC WIRING.
DATA SHEET: ESPELECT-06-E
10) ALL AUXILIARY CONTACTS, PUSHBUTTONS AND LIGHTS ARE CUSTOMER SUPPLIED AND INSTALLED.
11) REMOVE JUMPER TO INSTALL NORMALLY CLOSED MASTER FUEL TRIP CONTACT.
REVISION DATE: 3/20/15
APPROVED BY: RJK
H:\PROJECTS\ACADPRE\STD_TR\DATASHT3.DWG
N
GROUND FOR
INCOMING
POWER
43 AUX 2
NOTE 1
44
120 VAC
EXTERNAL
SOURCE
29 REMOTE ENABLE
NOTE 1
43
H