System for Data Center Grounding

advertisement
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
S TRUCTURED G ROUND ™ GROUNDING SYSTEM
C ATA LO G – W W - P CC B 04
Table of Contents
Introduction
INTRODUCTION
How to Use This Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
The Purpose of Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
GROUNDING ROADMAPS
Common Bonding Network (CBN) . . . . . . . . . . . .
Service Entrance Grounding Roadmap . . . . . . .
Data Center Grounding Roadmap . . . . . . . . . . . .
Data Center Rack Grounding (Raised Floor) . . . .
Telecommunications Room Grounding Roadmap
Telecommunications Room Rack Grounding . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.4
.5
.6
.7
.8
.9
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.....
.....
.....
.....
.....
.....
.....
.....
.....
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.10
.11
.11
.12
.13
.13
.14
.14
.14
Grounding
Roadmaps
EQUIPMENT & RACK GROUNDING KITS
Features and Benefits — PANDUIT ® STRUCTUREDGROUND ™ System
for Data Center Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack Grounding Strip Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common Bonding Network (CBN) to Rack Jumper Kit . . . . . . . . . .
Equipment Jumper Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Paint Piercing Grounding Washer Kits . . . . . . . . . . . . . . . . . . . . . .
Electrostatic Discharge (ESD) Port Kit . . . . . . . . . . . . . . . . . . . . . .
Retrofit Rack Grounding Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thread-Forming Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bonding Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
COMMON BONDING NETWORK (CBN) COMPONENTS
BICSI/J-STD-607-A Telecommunications Grounding Busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Telecommunications Grounding and Bonding Conductor Label Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Ring Terminal, Vinyl Expanded Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Code Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17
Flex Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Code/Flex Conductor HTAP Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Code/Flex Conductor HTAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Clear Covers for HTCT HTAPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Grounding Clamp, U-Bolt, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Grounding Clamp for Water Pipes, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Grounding Rod Clamp, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
CRIMPING TOOLS
Hand Operated Plier Type Tool . . . . . . . . . . . . . . . . . . . . . .
CONTOUR CRIMP ™ Controlled Cycle Tools . . . . . . . . . . . . . . .
Die Type, Manual Hydraulic, 14 Ton, Crimping Tool . . . . . . .
Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool
CD-920 Crimping Dies . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
..
..
..
..
..
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.24
.24
.25
.26
.27
Technical
Information
TECHNICAL INFORMATION
®
™
PANDUIT STRUCTUREDGROUND System for Data Center Grounding Application Standards . . . . . . . . . . . . . . .28
Specification Layout for Data Center Grounding per BICSI TDM Manual, 10th Edition . . . . . . . . . . . . . . . . . . . .29
Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE)
per J-STD-607-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Recommended Cable Sizes for Grounding Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Key Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Index
INDEX
Part Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Related Catalogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
1
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
How to Use This Catalog
Introduction
Common Bonding Network (CBN)
page 4
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Common Bonding Network (CBN)
Introduction
• PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding is a complete, highly reliable line of products to ground
your building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,
IEEE Std 1100 (IEEE Emerald Book), UL and CSA
Telecommunications
Room
(see roadmap on page 8)
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
Data Center
(see roadmap on page 6)
Grounding
Roadmaps
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Service Entrance
(see roadmap on page 5)
Technical
Information
Index
See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.
For more data center grounding information, see www.panduit.com/dcgrounding.
Equipment
& Rack
Grounding
Kits
4
Grounding Roadmaps
pages 5-9
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Data Center Grounding Roadmap
Data Center Rack Grounding (Raised Floor)
• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members
to the rack grounding strip
Introduction
Back of Racks Shown
Introduction
Back of Rack Shown
Paint Piercing Grounding
Washer Kit: RGW
(see page 13)
Data Equipment Racks
3
Bonding Screws are used to
mount patch panels to the front of
the rack: RGTBS (see page 14)
4
Grounding
Roadmaps
Grounding
Roadmaps
5
Equipment Jumper Kit 24" L, 90° Bent: RGEJ
(see page 12)
3
1
Equipment
& Rack
Grounding
Kits
Electrostatic Discharge (ESD)
Port Kit recommended for
use on front and back of rack:
RGESD (see page 13)
3
Common
Bonding
Network
(CBN)
Components
Equipment
& Rack
Grounding
Kits
1
AC Panel*
Telecommunications
Bonding Backbone
(TBB)
Rack Grounding Strip Kit: RGS
(see page 11)
Common
Bonding
Network
(CBN)
Components
Common
Bonding
Network
(CBN)
Components
Conduit
2
Building Steel
Equipment Jumper Kit 36" L, 90° Bent: RGEJ
(see page 12)
Crimping
Tools
Crimping
Tools
Common Bonding Network (CBN)
Raised Floor Pedestal
2
Equipment Jumper Kit 24" L, 45° Bent: RGEJ
(see page 12)
1
Copper Compression HTAP and
Clear Cover: HTWC
(see page 19)
4
Telecommunications Grounding
Busbar (TGB) and Busbar Label
(see page 15)
2
Bronze, U-Bolt Grounding Clamp: GPL
(see page 22)
5
Telecommunications Grounding and Bonding
Conductor Label Kit: LTYK
(see page 15)
3
Copper Compression, Two-Hole, Long
Barrel with Window Lug: LCC-W
(see pages 16-17)
Technical
Information
Technical
Information
Common Bonding Network (CBN) to
Rack Jumper Kit: RGCBNJ
(see page 11)
Common Bonding Network – typically #2 AWG
bare copper code conductor is used underfloor
Index
Index
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of the
raised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance with
applicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.
6
7
For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)
Crimping
Tools
Detailed Product
Information
pages 11-23
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Code/Flex Conductor HTAP
Introduction
For Making Parallel and Multiple Tap Connections on Code and Flex Conductors
• Used to tap into continuous conductors as a
splice or pigtailing
• Each HTAP terminates a wide range of
conductor sizes and combinations of code
and flex conductors Class G, H, I and
Locomotive to suit a variety of applications
• Slotted design allows quick and easy
assembly of conductor to HTAP using 3
PANDUIT 94 V-0 cable ties included
Grounding
Roadmaps
HTAP
Technical
Information
RUN
TAP
Equipment
& Rack
Grounding
Kits
W
W
W
RUN
RUN
• Tap grooves are separated from one another
allowing them to function independently so
HTAP can be used with a single or multiple
taps providing maximum design and
installation flexibility
• Color coded and marked with PANDUIT die
index numbers for proper crimp die selection
• Requires crimping tools and dies, see pages
25, 26 and 27
• UL Listed and CSA Certified for applications
up to 600V when crimped with PANDUIT
and specified competitor crimping tools and
PANDUIT crimping dies
• Tin plated to inhibit corrosion
L
RUN
L
RUN
W
H
H
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool
Introduction
• Two stage rapid advance hydraulic system minimizes
cycle time
• Provides UL Listed and CSA Certified connections on
PANDUIT ® PAN-LUG ™ copper and aluminum lugs and
splices and copper taps
• Open "C-Head" design allows easy loading of crimping
dies and connectors, saves time
• Rubber boot on crimp head provides abrasion protection
• Ram automatically retracts when crimp cycle is complete
Grounding
Roadmaps
H
Part Number
CT-2931
TAP 2
TAP 1
TAP 1
Common
Bonding
Network
(CBN)
Components
HTCT6-6
HTCT2-2
HTCT6-6-1
Wire
Strand
Type
Code
Run
#6 - #10
AWG
Flex
#6 - #10
AWG
Flex
#2 - #6
AWG
STR/SOL
#2 - #8
AWG
Code
HTCT2-2-1
Code
HTCT250-2-1
Technical
Information
HTCT250-250-1
Tap 1
#6 - #14
AWG
#6 - #14
AWG
HTCT250-2
Tap 3
—
—
#2 - #6 AWG #8 - #14 #8 - #14
STR/SOL
AWG
AWG
Common
Bonding
Network
(CBN)
Components
HTCT250-250
L
.61
W
.40
H
.99
PANDUIT
Crimping
Tool
CT-930, CT-2931
.76
.61
1.55
CT-930, CT-2931
Wire
PANDUIT Strip Std.
Die Color Length Pkg.
& Die No. (In.) Qty.
Orange, 11/16
1
PH6
Brown,
PH2
13/16
1
#2 - #6 AWG #8 - #14
STR/SOL
AWG
4/0 - #2
AWG
#2 - #8 AWG #8 - #14
AWG
Code
250 kcmil #2 AWG
4/0 - #2
AWG
•
•
•
•
•
•
•
•
Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor
Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor
Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor
CT-2931 includes:
• Tool
• Two 12 VDC, rechargeable NiMH batteries
• One battery charger
• Steel tool case with storage for batteries, charger and crimp dies
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.
*Makita is a registered trademark of Makita Corporation in the United States.
.92
.96
1.92
CT-930, CT-2931
Purple,
PH25
1
1
.90
.89
1.92
CT-930, CT-2931
Purple,
PH25
1
1
—
250 kcmil #2 AWG
—
Part Description
Terminates PANDUIT ® PAN-LUG ™ Compression Connectors:
Warranty: 3 years
Crimping
Tools
#2 - #8 AWG #8 - #14 #8 - #14
AWG
AWG
250 kcmil #2 AWG
4/0 - #2
AWG
TAP 1
Figure
Dimensions (In.)
Tap 2
Flex
Flex
TAP 2
TAP 1
Copper Conductor Size Range
Part Number
Crimping
Tools
TAP 3
• Tool provided with two, high capacity 12 VDC rechargeable
nickel-metal hydride batteries — provides for continuous
operation and eliminates "memory" build-up, one hour
charge time
• Eight second crimp cycle time provides quick terminations,
saves time
• Uses industry standard Makita* batteries and charger —
industry proven reliability easy to obtain from local
retail sources
• Requires crimping dies, see page 27
• Dies installed using spring loaded die retention pins — no
need for tools
• Crimp head rotates 360 degrees — provides versatility for
use in restricted spaces
Equipment
& Rack
Grounding
Kits
L
L
H
Detailed Tool
Information
pages 24-27
Technical
Information
—
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
Index
Index
20
Index
26
Technical Information — Includes Application Standards and BICSI TDM Manual, 10th Edition
pages 28-30
2
Std.
Pkg.
Qty.
1
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
The Purpose of Grounding
The grounding system is not just an insurance policy against a lightning strike. It is an active,
functioning system that provides protection for personnel and equipment. Proper grounding is
essential for efficient network performance.
Introduction
The purpose of the grounding system is to create a low impedance path to earth ground for electrical
surges and transient voltages. Lightning, fault currents, circuit switching (motors turning on and off),
and electrostatic discharge are the common causes of these surges and transient voltages. An
effective grounding system minimizes the detrimental effects of these electrical surges.
A properly designed grounding system is one that is intentional, visually verifiable, adequately sized
to handle expected currents safely, and one that directs these potentially damaging currents away
from sensitive communication equipment. Any metallic component that is part of the data center
infrastructure (such as equipment, racks, ladder racks, enclosures, cable trays, etc.) must be bonded
to the grounding system.
What are the effects of improper grounding?
Decreased Efficiency
• Electrical noise is introduced on data cables when surges are not properly dissipated by the grounding system.They cause
faulty data signals and dropped packets, thus decreasing the throughput and overall efficiency of your network.
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
Lower Reliability
• According to insurance industry data, improper grounding of communication systems leads to $500 million per year of
damage to property and/or equipment due to lightning. (1)
• The Information Technology Industry Council states that grounding is the single-most important factor in reliable network
equipment performance. (2)
• More than 90% of problems in data communications equipment, including reboot, lockup, and data corruption, are
traced to problems with grounding. (3)
• Industry experts estimate that 27%-33% of damaged equipment in a user's facility is caused by electrostatic discharge.
The component cost of repairing damaged equipment is substantial for complex circuit boards, especially when labor
and downtime are considered. (4)
• According to the IEEE, the typical AC third prong ground is almost never sufficient to prevent damage to network equipment. (5)
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Safety Risks
• Personal injury from electric shock caused by improper grounding can cause immeasurable human suffering and
significant expense.
• Potential fire hazards exist when heat is generated from electrical surges that find a high resistance path to ground.
Can you afford improper grounding?
Network equipment, such as switches, routers and storage devices, costs anywhere from thousands of dollars to hundreds of
thousands of dollars.The cost of proper grounding is only a tiny fraction of the cost of the equipment it is protecting.
Technical
Information
Clearly the biggest cost of improper grounding is the inability to service customers properly.
PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding gives you what you need to properly protect
your investment.
1. Mike Holt, "Prevent Shocks in Your Communications: Understanding How the NEC Relies on Ground Resistance Theory Leads to a
Successful Application of Communications Grounding," Electrical Construction & Maintenance, September 2002.
2. Information Technology Industry Council (ITI, formerly CBEMA), Guidelines for Grounding Information Technology Equipment. Information
Letter, ITI, 15 February 1997.
Index
3. Donald G. Pennington and Paul Holzer, "Doing Battle with Those Ground Transients," Electronic Engineering Times, 8 January 1996.
4. ESDA, "Fundamentals of ESD: Part 1 — An Introduction to ESD," 2001, <http://www.esda.org/basics/part1.cfm> (1 October 2004).
5. Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Powering and Grounding Electronic Equipment, IEEE
Std 1100-1999, 1999.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
3
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Common Bonding Network (CBN)
Introduction
• PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding is a complete, highly reliable line of products to ground
your building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,
IEEE Std 1100 (IEEE Emerald Book), UL and CSA
Telecommunications
Room
(see roadmap on page 8)
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
Data Center
(see roadmap on page 6)
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Service Entrance
(see roadmap on page 5)
Technical
Information
Index
See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.
For more data center grounding information, see www.panduit.com/dcgrounding.
4
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Service Entrance Grounding Roadmap
• Complies with J-STD-607-A and IEEE Std 1100 (IEEE Emerald Book)
• Grounding Equalizer (GE) is required when two or more Telecommunications Bonding Backbones (TBB) are used within a
multi-story building; bond TBBs together with a GE at the top floor and at a minimum of every third floor in between
Introduction
Telecommunications Bonding
Backbone (TBB)**
2
2
Conduit
Grounding Equalizer (GE)
3
Grounding
Roadmaps
1
5
6
Earth Ground
3
7
Equipment
& Rack
Grounding
Kits
3
AC Panel*
Cable Entrance
AC Service Entrance
Common
Bonding
Network
(CBN)
Components
3
4
Water Meter
4
1
Copper Compression HTAP and
Clear Cover: HTWC
(see page 19)
5
Bronze, Grounding Rod Clamp: WB
(see page 23) connected by a cable to
2 (U-Bolt Grounding Clamp)
2
Bronze, U-Bolt Grounding Clamp: GPL
(see page 22) connected by a cable to
1 (HTAP)
6
Telecommunications Main
Grounding Busbar (TMGB) and
Busbar Label (see page 15)
3
Copper Compression, Two-Hole, Long
Barrel with Window Lug: LCC-W
(see pages 16-17)
7
4
Bronze, Water Pipe Grounding Clamp: KP
(see page 23)
Crimping
Tools
Technical
Information
Telecommunications Grounding and Bonding
Conductor Label Kit: LTYK
(see page 15)
Index
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
**Specification J-STD-607-A specifies different size conductors based on the length of the Telecommunications Bonding Backbone (TBB). See page 30 for
Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE) Per J-STD-607-A.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
5
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Data Center Grounding Roadmap
Introduction
• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members
to the rack grounding strip
Back of Racks Shown
Data Equipment Racks
3
4
Grounding
Roadmaps
5
3
1
Equipment
& Rack
Grounding
Kits
3
1
AC Panel*
Telecommunications
Bonding Backbone
(TBB)
Common
Bonding
Network
(CBN)
Components
Conduit
2
Building Steel
Crimping
Tools
Common Bonding Network (CBN)
Raised Floor Pedestal
2
1
Copper Compression HTAP and
Clear Cover: HTWC
(see page 19)
4
Telecommunications Grounding
Busbar (TGB) and Busbar Label
(see page 15)
2
Bronze, U-Bolt Grounding Clamp: GPL
(see page 22)
5
Telecommunications Grounding and Bonding
Conductor Label Kit: LTYK
(see page 15)
3
Copper Compression, Two-Hole, Long
Barrel with Window Lug: LCC-W
(see pages 16-17)
Technical
Information
Index
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of the
raised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance with
applicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.
6
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Data Center Rack Grounding (Raised Floor)
Introduction
Back of Rack Shown
Paint Piercing Grounding
Washer Kit: RGW
(see page 13)
Bonding Screws are used to
mount patch panels to the front of
the rack: RGTBS (see page 14)
Grounding
Roadmaps
Equipment Jumper Kit 24" L, 90° Bent: RGEJ
(see page 12)
Electrostatic Discharge (ESD)
Port Kit recommended for
use on front and back of rack:
RGESD (see page 13)
Rack Grounding Strip Kit: RGS
(see page 11)
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
Equipment Jumper Kit 36" L, 90° Bent: RGEJ
(see page 12)
Crimping
Tools
Equipment Jumper Kit 24" L, 45° Bent: RGEJ
(see page 12)
Technical
Information
Common Bonding Network (CBN) to
Rack Jumper Kit: RGCBNJ
(see page 11)
Common Bonding Network — typically #2 AWG
bare copper code conductor is used underfloor
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
Index
7
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Telecommunications Room Grounding Roadmap
Introduction
• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members
to the rack grounding strip
Back of Racks Shown
Grounding Equalizer (GE)
Grounding
Roadmaps
Conduit
5
1
3
4
Equipment
& Rack
Grounding
Kits
3
1
3
AC Panel*
Common
Bonding
Network
(CBN)
Components
1
Telecommunications
Bonding Backbone
(TBB)
2
Building Steel
Crimping
Tools
1
Copper Compression HTAP and
Clear Cover: HTWC
(see page 19)
4
Telecommunications Grounding
Busbar (TGB) and Busbar Label
(see page 15)
2
Bronze, U-Bolt Grounding Clamp: GPL
(see page 22)
5
Telecommunications Grounding and Bonding
Conductor Label Kit: LTYK
(see page 15)
3
Copper Compression, Two-Hole, Long
Barrel with Window Lug: LCC-W
(see pages 16-17)
Technical
Information
Index
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
A typical overhead cabling system includes a multitude of metallic components which are connected together. It is the responsibility of the installer to insure all
of the metallic components are bonded, which means that they are connected together electrically in accordance with applicable specifications. The PANDUIT
Bonding/Grounding System does not insure required bonding of the overhead cabling system metallic components.
8
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Telecommunications Room Rack Grounding
Introduction
Aisle Ground — typically #2 AWG insulated copper code
conductor is used overhead
Back of Rack Shown
Bonding Screws are used to
mount patch panels to the front of
the rack: RGTBS (see page 14)
Grounding
Roadmaps
Paint Piercing Grounding
Washer Kit: RGW
(see page 13)
Common Bonding Network (CBN) to
Rack Jumper Kit: RGCBNJ
(see page 11)
Equipment
& Rack
Grounding
Kits
Equipment Jumper Kit 24" L, 90° Bent: RGEJ
(see page 12)
Electrostatic Discharge (ESD)
Port Kit recommended for
use on front and back of rack:
RGESD (see page 13)
Common
Bonding
Network
(CBN)
Components
Rack Grounding Strip Kit: RGS
(see page 11)
Crimping
Tools
Equipment Jumper Kit 36" L, 90° Bent: RGEJ
(see page 12)
Equipment Jumper Kit 24" L, 45° Bent: RGEJ
(see page 12)
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
9
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Features and Benefits — PANDUIT ® STRUCTUREDGROUND ™ System for Data
Center Grounding
Introduction
PANDUIT offers a variety of kits with premium components to ensure superior grounding with the highest reliability available.
• Provides highest reliability with an all-copper rack
• Incorporates a flexible design that can be used with
grounding system to maintain data center system
racks which meet EIA-310-D
performance and protect network equipment
• Offers ease of installation — no paint scraping required to
• Complies with data center standard TIA-942 and is UL
bond racks; factory terminated jumpers simply
Listed and CSA Certified
bolt in place
C
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
A
Rack Grounding Strip is made from high
conductivity, low resistance wrought copper
and tin plated to inhibit corrosion, providing
the lowest impedance path to ground
B
Jumper has UL, VW-1 flame rated green
insulation and is factory terminated with
copper compression, two-hole, long barrel
with window lug; lug is UL Listed, CSA
Certified and meets NEBS Level 3 with a single
stud hole and slot which allows mounting for
½" to 5/8" hole spacing and accommodates
stud sizes ¼", #12 and 6mm
C
Paint Piercing Grounding Washer is
made from hardened steel and electro zinc
plated which inhibits corrosion to provide a
superior bond between frame members on
bolt-together racks
D
Thread-Forming Screws are made from
electro zinc plated steel and provide a bond to
the rack by removing paint from threaded
holes without creating metal shavings
E
Electrostatic Discharge (ESD) Port is made
from high conductivity, low resistance copper
and tin plated to inhibit corrosion plus it
functions as an ESD wrist strap hanger
C
F
E
Electrostatic
Discharge (ESD)
Port Kit
(see page 13)
D
Rack
Grounding
Strip Kit
(see page 11)
D
B
F
Electrostatic Discharge (ESD) Protection
Sticker is provided in black and yellow for
high visibility and easy identification as an
ESD port
Equipment
Jumper Kit
(see page 12)
Technical
Information
G
A
D
C
C
Copper Compression HTAP is UL Listed and
CSA Certified; used to make a highly reliable,
permanent bond between the common
bonding network and common bonding
network (CBN) to rack jumper kit
B
C
Index
G
Common Bonding Network (CBN)
to Rack Jumper Kit (see page 11)
10
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Equipment & Rack Grounding Kits
Introduction
Rack Grounding Strip Kits
• Bonds up to 44 RU per rack
• EIA Universal mounting hole pattern
Part Number
RGS134-1
RGS134-10-1
Part Description
Rack grounding strip; 78.65" length; .67" width; .05" thickness;
provided with .16 oz (5cc) of antioxidant and three #12-24 x 1/2"
thread-forming screws*
Std.
Pkg.
Qty.
1
10 rack grounding strips; 78.65" length; .67" width; .05" thickness;
provided with .16 oz (5cc) of antioxidant and 30 #12-24 x 1/2"
thread-forming screws*
Grounding
Roadmaps
1
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
Equipment
& Rack
Grounding
Kits
Common Bonding Network (CBN) to Rack Jumper Kit
• Bonds the rack grounding strip to the CBN
• HTAP, included in kit, requires crimping tool and die; see
the CT-930 crimping tool on page 25, the CT-2931 crimping tool on page 26 and the CD-930H-250 crimping die on
page 27
Part Number
RGCBNJ660P
• HTAP is UL Listed and CSA Certified for applications up to
600V when crimped with PANDUIT and specified
competitor crimping tools and PANDUIT crimping dies;
see the Termination Solutions Catalog SA-TMCB02 for the
complete line of PANDUIT crimping tools
Part Description
#6 AWG jumper; 60" length; 45° bent lug on grounding strip side;
provided with .16 oz (5cc) of antioxidant, two #12-24 x 1/2"
thread-forming screws* and a copper compression HTAP** for
connecting to the CBN in sizes ranging from #2 AWG to 250 kcmil
Common
Bonding
Network
(CBN)
Components
Std. Std.
Pkg. Ctn.
Qty. Qty.
1
10
Crimping
Tools
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
**HTAP also sold separately, see page 20.
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
11
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Equipment Jumper Kits
Introduction
• Bonds network equipment to rack grounding strip
• Jumper kit available with both ends factory terminated to
provide a bolt on solution
• Jumper kit available with one end factory terminated to
attach to the rack grounding strip; free end accommodates
unique equipment terminations
• Use jumpers with 90° bent lug, on grounding strip side, for
high density grounding requirements up to one ground
point per RU
• Use jumpers with 45° bent lugs, on grounding strip side, for
improved cable management
• Use 24" jumpers when network equipment ground point is
located near the grounding strip side of the rack
• Use 36" jumpers when network equipment ground point is
located away from the grounding strip side of the rack
Grounding
Roadmaps
Part Number
Std. Std.
Pkg. Ctn.
Qty. Qty.
Part Description
#10 AWG equipment jumpers factory terminated on both ends
Equipment
& Rack
Grounding
Kits
RGEJ1024PF
RGEJ1024PH
#10 AWG jumper; 24" length; 45° bent lug on grounding strip side
to straight lug on equipment; provided with .16 oz (5cc) of
antioxidant and four #12-24 x 1/2" thread-forming screws*
1
10
RGEJ1024PF
#10 AWG jumper; 24" length; 90° bent lug on grounding strip side
to straight lug on equipment; provided with .16 oz (5cc) of
antioxidant and four #12-24 x 1/2" thread-forming screws*
1
10
RGEJ1036PF
#10 AWG jumper; 36" length; 90° bent lug on grounding strip side
to straight lug on equipment; provided with .16 oz (5cc) of
antioxidant and four #12-24 x 1/2" thread-forming screws*
1
10
#6 AWG equipment jumpers factory terminated on both ends
Common
Bonding
Network
(CBN)
Components
RGEJ624PH
#6 AWG jumper; 24" length; 45° bent lug on grounding strip side to
straight lug on equipment; provided with .16 oz (5cc) of antioxidant
and four #12-24 x 1/2" thread-forming screws*
1
10
RGEJ624PF
#6 AWG jumper; 24" length; 90° bent lug on grounding strip side to
straight lug on equipment; provided with .16 oz (5cc) of antioxidant
and four #12-24 x 1/2" thread-forming screws*
1
10
RGEJ636PF
#6 AWG jumper; 36" length; 90° bent lug on grounding strip side to
straight lug on equipment; provided with .16 oz (5cc) of antioxidant
and four #12-24 x 1/2" thread-forming screws*
1
10
1
10
1
10
#10 AWG equipment jumper factory terminated on one end
RGEJ1057PF
Crimping
Tools
#10 AWG jumper; 57" length; 90° bent lug on grounding strip side;
provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"
thread-forming screws*
#6 AWG equipment jumper factory terminated on one end
RGEJ657PF
RGEJ1057PF
#6 AWG jumper; 57" length; 90° bent lug on grounding strip side;
provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"
thread-forming screws*
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
How to Select the Appropriate Equipment Jumper
Technical
Information
3" or smaller
3" or larger
Index
Select 24" equipment jumpers with 90°
lugs when equipment grounding connection
is close to the grounding strip.
Select 36" equipment jumpers with 90° lugs
when equipment grounding connection is on
the opposite side from the grounding strip.
12
Select equipment jumpers with 45° lugs
for lower density applications or shallow
depth equipment to provide improved cable
management.
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Paint Piercing Grounding Washer Kits
• Bonds frame members on bolt-together racks
• No paint scraping required
Part Number
RGW-12-1
RGW-32-1
RGW-100-1
• Green color coding to indicate bonding application
Part Description
12 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided
with .16 oz (5cc) of antioxidant; for use with standard equipment racks:
CMR19X84, CMR19X84S and CMR23X84
Introduction
Std.
Pkg.
Qty.
1
32 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided
with .16 oz (5cc) of antioxidant; for use with 4 post rack NF4PR84 and
data rack DR84
1
100 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided
with .16 oz (5cc) of antioxidant
1
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
Electrostatic Discharge (ESD) Port Kit
• Accommodates standard ESD wrist strap 4mm plug
• Can be mounted to front or back of rack for
convenient access
Part Number
RGESD-1
• Bent 45°, acts as a hook to hold wrist strap
• Barrel permanently marked with the protective earth
(ground) symbol
Part Description
ESD port kit; provided with an ESD protection sticker, .16 oz (5cc) of
antioxidant and one #12-24 x 1/2" thread-forming screw*
Std.
Pkg.
Qty.
1
Contact your local electrical distributor for their selection of Electrostatic Discharge (ESD) wrist straps.
*One M6 x 12mm thread-forming screw also provided in each kit.
ESD port must be attached to a grounded member.
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
13
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Retrofit Rack Grounding Kits
Introduction
• Provides a dedicated ground system to maintain system
performance and protect network equipment when RGS
rack grounding strip kit cannot be used (see page 11)
• Optimized for installation on 19" racks that meet EIA-310-D,
with functioning equipment, and are deployed in the field
• Provides a complete system of matched components that
can be easily selected to save cost and labor
• Thread-forming screws eliminate the need to manually
remove paint from the rack
Grounding
Roadmaps
RGRKCBNJEJ
Lug
(see pages
16-18)
Network
Equipment
Part Number
RGRKCBNJEJ
Equipment
& Rack
Grounding
Kits
Rack
Rack
Grounding
RGRKCBNJ
Kit
RGRKCBNJEJ
Grounding
Busbar
RGRB19
RGRB19
Grounding
Jumper
RGREJ696
or
RGREJ696
RGREJ1096
HTAP
(see
page 20)
Common
Bonding
Network
(CBN)
Components
Grounding
Jumper
RGREJ696
Rack Grounding Kit
RGRKCBNJ
RGREJ1096
RGRKCBNJ
Part Description
Rack grounding kit to ground the rack and one piece of equipment;
includes one RGRB19 busbar, one HTCT250-2-1 HTAP and two
RGREJ696 grounding jumpers
Std. Std.
Pkg. Ctn.
Qty. Qty.
1
10
Rack grounding kit to ground the rack; includes one RGRB19
busbar, one HTCT250-2-1 HTAP and one RGREJ696
grounding jumper
1
10
Rack grounding busbar; can be positioned anywhere on the rack;
19" length; tin plated; 14 holes arranged for flexibility in mounting;
mounting hole sets have 1/2" spacing; provided with two
#12-24 x 1/2" thread-forming screws* for mounting
Grounding jumper; #6 AWG; 96" length; one end factory
terminated to lug; provided with .16 oz (5cc) of antioxidant and four
#12-24 x 1/2" thread-forming screws* and other mounting hardware
as appropriate
1
10
1
10
Grounding jumper; #10 AWG; 96" length; one end factory
terminated to lug; provided with .16 oz (5cc) of antioxidant and four
#12-24 x 1/2" thread-forming screws* and other mounting hardware
as appropriate
1
10
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
Thread-Forming Screws
Crimping
Tools
• Thread-forming, provides a bond to the rack by removing
paint from threaded holes without creating metal shavings
Part Number
RGTS-C
RGTSM6-C
Technical
Information
Part Description
Thread-forming grounding screw, #12-24 x 1/2"
Thread-forming grounding screw, M6 x 12mm
Part Number
RGTBS-C
RGTBSM6-C
14
Std.
Pkg.
Qty.
100
100
Bonding Screws
• Creates an electrical bond between painted patch panels
and racks
• Serrations on bottom of screw remove paint from patch
panel, thus providing metal-to-metal contact
Index
• Easily installed with 5/16" socket head wrench or flat
blade screwdriver
• Thread-forming, provides a bond to the rack by removing
paint from threaded holes without creating metal shavings
• Easily installed with Phillips screwdriver
Part Description
Thread-forming bonding screw, #12-24 x 1/2"
Thread-forming bonding screw, M6 x 15mm
Std.
Pkg.
Qty.
100
100
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Common Bonding Network (CBN) Components
C
UL
R
US
BICSI/J-STD-607-A Telecommunications Grounding Busbars
• Meets BICSI and J-STD-607-A requirements for network
systems grounding applications
• Made of high conductivity copper and tin plated to
inhibit corrosion
Part Number
Introduction
• Comes pre-assembled with brackets and insulators
attached for quick installation
• Use PANDUIT self-laminating laser/ink jet labels to identify
busbars to meet TIA/EIA-606-A
Bar Size
No. of 5/16"
hole sets,
5/8" spacing
No. of 7/16"
hole sets,
1" spacing
Can Be Clearly
Std.
Identified with PANDUIT Pkg.
Laser/Ink Jet Label*
Qty.
Grounding
Roadmaps
Telecommunications Grounding Busbars (TGB)
GB2B0306TPI-1
1/4" x 2" x 10"
1/4" x 2" x 12"
4
6
3
3
GB2B0312TPI-1
1/4" x 2" x 20"
12
3
GB2B0304TPI-1
TGB
1
1
C200X100FJJ
1
Telecommunications Main Grounding Busbars (TMGB)
GB4B0612TPI-1
GB4B0624TPI-1
TMGB
1/4" x 4" x 12"
1/4" x 4" x 20"
12
24
6
6
1
1
C200X100FJJ
For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identification
products, see the Identification Solutions Catalog SA-IDCB16.
*Busbar labels sold separately.
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
C200X100FJJ
Telecommunications Grounding and Bonding Conductor Label Kit
• Meets labeling requirements of J-STD-607-A; each
• Kit includes everything needed to properly label cables; one
telecommunications grounding and bonding conductor shall
flame retardant cable tie and one rigid plastic yellow tag
be labeled as close as practicable to its point of termination in printed with “IF THIS CONNECTOR OR CABLE IS LOOSE
a readable position
OR MUST BE REMOVED, PLEASE CALL THE BUILDING
• Can be applied as a wrap-around marker (parallel to cable) or TELECOMMUNICATIONS MANAGER”
flag marker (45° or 90°) to cable
Part Number
LTYK
Part Description
Label kit includes printed tag and one flame retardant cable tie
Std.
Pkg.
Qty.
10
Crimping
Tools
Technical
Information
For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identification
products, see the Identification Solutions Catalog SA-IDCB16.
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
15
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Ring Terminal, Vinyl Expanded Insulation
Introduction
• Expanded wire entry allows for large O.D. wire insulation or
multiple wire crimps within one wire barrel
• Industry standard color coding to indicate wire range
Part
Number
PV14-6RX-C
PV14-8RX-C
Grounding
Roadmaps
PV14-10RX-C
PV14-14RX-C
Wire Color
Stock
Range Code Thickness
.03
.03
16-14
Blue
AWG
.03
.03
PV10-6RX-L
PV10-8RX-L
12-10
PV10-10RX-L AWG
PV10-14RX-L
L
Equipment
& Rack
Grounding
Kits
W
• Brazed seam assures a reliable crimp
• Insulation support
• Requires crimping tools, see page 24
Yellow
Max.
Ins.
.200
.200
.200
.200
Figure
Stud Dimensions (In.)
Size
L
W
C
#6
.96 .31 .25
#8
.96 .31 .25
#10 .96 .31 .25
1/4" 1.16 .46 .37
.04
.04
.250
.250
#6
#8
1.10
1.10
.31
.31
.30
.30
.04
.04
.250
.250
#10
1/4"
1.10
1.29
.31
.52
.30
.39
PANDUIT
Crimping
Tool
CT-100‡,
CT-1550‡
CT-100‡,
CT-1550‡
Std.
Pkg.
Qty.**
100
100
100
100
Std.
Ctn.
Qty.
500
500
500
500
50
50
500
500
50
50
500
500
For additional sizes and configurations and to see the complete line of PAN-TERM ® Terminals, see the Termination
Solutions Catalog SA-TMCB02.
‡UL and CSA approved tooling/product combinations. For crimping tools see page 24.
**To order in bulk, replace -C in the part number with -M for a bulk package of 1000 and replace -L with -D for a
bulk package of 500.
C
Common
Bonding
Network
(CBN)
Components
Code Conductor, Two-Hole, Long Barrel with Window Lug
For Use with Stranded Copper Conductors
Crimping
Tools
Technical
Information
Index
16
• Meets J-STD-607-A requirements for
network systems grounding applications
• Tested by Telcordia — meets NEBS
Level 3
• Requires crimping tools and dies, see
pages 24, 25, 26 and 27
• UL Listed for use up to 35KV**, temperature
rated 90°C and CSA Certified to 600V when
crimped with PANDUIT and specified
competitor crimping tools and dies
• UL Listed and CSA Certified for wire
range-taking capability when crimped with
PANDUIT ® UNI-DIE ™ dieless crimping tools
• Color coded barrels marked with PANDUIT
and specified competitor die index numbers
for proper crimp die selection
• Long barrel maximizes number of crimps
and provides premium wire pull-out strength
and electrical performance
• Inspection window to visually assure full
conductor insertion
• Tin plated to inhibit corrosion
• Available with NEMA hole sizes and spacing
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Code Conductor, Two-Hole, Long Barrel with Window Lug (continued)
W
HOLE
SPACING
Introduction
W
W
INSPECTION
WINDOW
W
HOLE
SPACING
HOLE
SPACING
HOLE
SPACING
L
L
INSPECTION
WINDOW
B
INSPECTION
WINDOW
B
B
T
T
T
90Ëš
INSPECTION
WINDOW
45Ëš
T
L
B
Grounding
Roadmaps
L
Figure 1
Figure 2: Slotted Lug
Stud
Stud
Hole
Hole
Copper
Figure Conductor Size Spacing
(In.)
(In.)
Part Number
No.
Size
LCC10-14JAW-L*
2
1/4 .50 – .63
#14 – #10
LCC10-14JAWH-L*
3
AWG STR, 1/4 .50 – .63
LCC10-14JAWF-L*
#12 – #10 1/4 .50 – .63
4
AWG SOL 1/4
LCC10-14BW-L*
1
.75
Figure 3: Slotted Lug
45°Bent
Figure
Dimensions (In.)
W
.42
B
.53
T
L
.05 1.93
.42
.53
.05 1.78
.42
.53
.05 1.56
.42
.53
.05 2.06
Figure 4: Slotted Lug
90°Bent
Wire
Strip Std.
Length Pkg.
(In.)
Qty.
9/16
50
PANDUIT
Crimping
Tool
PANDUIT
Die Color
& Die No.
—
CT-100,
CT-1570
—
—
—
9/16
50
—
—
—
9/16
50
—
—
—
9/16
50
Red P21
49
21
3/4
50
Red P21
49
21
3/4
50
Red P21
49
21
3/4
50
Burndy T&B
Die
Die
No.
No.
—
—
LCC8-10ABW-L
2
#10
.63 – .75
.41
.70
.08 2.14
LCC8-14ABW-L
2
1/4
.63 – .75
.48
.70
.07 2.23
LCC8-14DW-L
1
1/4
1.00
.48
.70
.07 2.48
LCC8-38DW-L
1
3/8
1.00
.60
.70
.05 2.70
Red P21
49
21
3/4
50
LCC6-10ABW-L
2
#10
.63 – .75
.46
1.07 .08 2.52
Blue P24
7
24
1 1/8
50
LCC6-14JAW-L
2
1/4
.50 – .63
.48
1.07 .08 2.49
Blue P24
7
24
1 1/8
50
LCC6-14JAWH-L
3
1/4
.50 – .63
.48
1.07 .08 2.08
Blue P24
7
24
1 1/8
50
LCC6-14JAWF-L
4
1/4
.50 – .63
.48
1.07 .08 1.66
Blue P24
7
24
1 1/8
50
LCC6-14BDW-L
2
1/4
.75 – 1.00
.48
1.07 .08 2.86
Blue P24
7
24
1 1/8
50
LCC6-14EW-L
1
1/4
1.25
.48
1.07 .08 3.11
Blue P24
7
24
1 1/8
50
LCC6-56BW-L
1
5/16
.75
.56
1.07 .07 2.73
Blue P24
7
24
1 1/8
50
LCC6-38BDW-L
2
3/8
.75 – 1.00
.62
1.07 .06 3.08
Blue P24
7
24
1 1/8
50
LCC4-14ADW-L
2
1/4
.63 – 1.00
.55
1.05 .09 2.63
8
29
1 1/8
50
LCC4-38DW-L
1
3/8
1.00
.62
1.05 .08 3.09
CT-1700,
CT-930,
CT-2931
Gray P29
Gray P29
8
29
1 1/8
50
LCC2-14AW-Q
1
1/4
.63
.60
1.16 .10 2.67
Brown P33
10
33
1 1/4
25
3/8
1.00
.66
1.16 .10 3.24
CT-1700,
CT-930,
CT-2931
Brown P33
10
33
1 1/4
25
1/4
.63
.70
1.36 .11 2.89
Green P37
11
37
1 7/16
20
3/8
1.00
.70
1.36 .11 3.46
CT-1700,
CT-930,
CT-2931
Green P37
11
37
1 7/16
20
1/4
.63
.76
1.44 .12 3.07
12
42
1 1/2
10
1.00
.76
1.44 .12 3.57
CT-930,
CT-2931
Pink P42
3/8
Pink P42
12
42
1 1/2
10
1/4
.63
.85
1.50 .13 3.23
13
45
1 9/16
10
3/8
1.00
.85
1.50 .13 3.67
CT-930,
CT-2931
Black P45
3/8
1.00
.96
1.50 .13 3.70
1/2
1.75
.96
1.50 .13 4.87
1/4
.63
1.06 1.56 .14 3.35
3/8
1.00
1.06 1.56 .14 3.81
3/8
1.00
1.17 1.61 .14 3.89
1/2
1.00
1.17 1.61 .14 4.12
LCC2-38DW-Q
1
LCC1-14AW-E
1
LCC1-38DW-E
1
LCC1/0-14AW-X
1
LCC1/0-38DW-X
1
LCC2/0-14AW-X
1
LCC2/0-38DW-X
1
LCC3/0-38DW-X
1
LCC3/0-12W-X
1
LCC4/0-14AW-X
1
LCC4/0-38DW-X
1
LCC250-38DW-X
1
LCC250-12DW-X
1
#8 AWG
#6 AWG
#4 – #3
AWG STR
#2 AWG
#1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
CT-1700,
CT-930,
CT-2931
CT-1700,
CT-930,
CT-2931
Black P45
13
45
1 9/16
10
Orange P50
14
50
1 9/16
10
Orange P50
14
50
1 9/16
10
CT-930,
CT-2931
Purple P54
15
54
1 5/8
10
Purple P54
15
54
1 5/8
10
CT-930,
CT-2931
Yellow P62
16
62
1 11/16
10
Yellow P62
16
62
1 11/16
10
CT-930,
CT-2931
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Technical
Information
Index
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
*Not tested to NEBS Level 3 requirements.
**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
17
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Flex Conductor, Two-Hole, Long Barrel with Window Lug
Introduction
For Use with Flexible, Extra-Flexible and Code Stranded Copper Conductors
• Meets J-STD-607-A requirements for
network systems grounding applications
• Requires crimping tools and dies, see pages
24, 25, 26 and 27
• UL Listed for use up to 35KV**, temperature
rated 90°C and CSA Certified to 600V when
crimped with PANDUIT and specified
competitor crimping tools and dies
• Color coded barrels marked with PANDUIT
and specified competitor die index numbers
for proper crimp die selection
Grounding
Roadmaps
W
W
HOLE
SPACING
HOLE
SPACING
Equipment
& Rack
Grounding
Kits
• Can be used with code conductor and
flex conductor class: G, H, I, K, M and
Locomotive
• Long barrel maximizes number of crimps
and provides premium wire pull-out strength
and electrical performance
• Inspection window to visually assure full
conductor insertion
• Generously beveled wire entry prevents
bent back strands when inserting conductor
into barrel
• Tin plated to inhibit corrosion
• Available with NEMA hole sizes and spacing
L
L
INSPECTION
WINDOW
B
B
T
INSPECTION
WINDOW
T
Figure 1
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Part Number
LCCX8-10AB-L
LCCX8-14AB-L
LCCX8-14D-L
LCCX8-38D-L
LCCX6-10B-L
LCCX6-14AB-L
LCCX6-14D-L
LCCX6-38AC-L
LCCX6-38D-L
LCCX4-14AB-L
LCCX4-38BD-L
Technical
Information
Index
18
Figure 2: Slotted Lug
Flex
Conductor
Stud
Size
Code
Hole
Figure
Class
Conductor Size
No. G, H, I, K, M Locomotive
Size
(In.)
2
#10
2
1/4
#8 AWG
#8 AWG
#8 AWG
1
1/4
1
3/8
1
#10
2
1/4
1
1/4
#6 AWG
#6 AWG
#6 AWG
2
3/8
1
3/8
2
1/4
#5, #4, #3
#4 – #3
#4 AWG
2
AWG
AWG STR 3/8
LCCX2-38D-E
1
LCCX1-14A-X
LCCX1-38D-X
LCCX1/0-14A-X
LCCX1/0-38D-X
LCCX2/0-14A-X
LCCX2/0-38D-X
LCCX3/0-38D-X
1
1
1
1
1
1
1
LCCX4/0-38D-X
LCCX250-38D-X
Figure
Dimensions
(In.)
Stud
Hole
Spacing
(In.)
.63 – .75
.63 – .75
1.00
1.00
.75
.63 – .75
1.00
.63 – .88
1.00
.63 – .75
W
.41
.48
.48
.60
.46
.48
.48
.62
.62
.55
B
.70
.70
.70
.70
1.07
1.07
1.07
1.07
1.07
1.05
.75 – 1.00
.62
1.05 .08 3.09
3/8
1.00
.70
1.36 .11 3.46
.63
1.00
.63
1.00
.63
1.00
1.00
.76
.76
.85
.85
.96
.96
1.06
1.44
1.44
1.50
1.50
1.50
1.50
1.56
T
.08
.07
.07
.05
.08
.08
.08
.06
.06
.09
L
2.14
2.23
2.48
2.70
2.52
2.61
2.86
2.96
3.08
2.63
#2 AWG
#2 AWG
#2 AWG
#1 AWG
#1 AWG
#1 AWG
1/0 AWG
1/0 AWG
1/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
3/0 AWG
3/0 AWG
3/0 AWG
1/4
3/8
1/4
3/8
1/4
3/8
3/8
1
4/0 AWG
4/0 AWG
4/0 AWG
3/8
1.00
1.19 2.24 .16 4.55
1
250 kcmil
262.6 kcmil
—
3/8
1.00
1.28 2.24 .17 4.59
.12
.12
.13
.13
.13
.13
.14
3.07
3.57
3.23
3.67
3.27
3.70
3.81
Wire
PANDUIT PANDUIT Strip Std.
Crimping Die Color Length Pkg.
Tool
& Die No.
(In.) Qty.
Red P21
3/4
50
CT-1700, Red P21
3/4
50
CT-930,
Red P21
3/4
50
CT-2931
Red P21
3/4
50
Blue P24
1 1/8
50
1 1/8
50
CT-1700, Blue P24
1 1/8
50
CT-930, Blue P24
CT-2931 Blue P24
1 1/8
50
Blue P24
1 1/8
50
Gray
P29
1
1/8
50
CT-1700,
CT-930, Gray P29 1 1/8
50
CT-2931
CT-1700,
Brown
1 7/16 20
CT-930,
P33
CT-2931
CT-930, Green P37 1 1/2
CT-2931 Green P37 1 1/2
CT-930, Pink P42 1 9/16
CT-2931 Pink P42 1 9/16
CT-930, Black P45 1 9/16
CT-2931 Black P45 1 9/16
CT-930,
Orange
1 5/8
CT-2931
P50
CT-930,
Purple
2 5/16
CT-2931
P54
CT-930, Yellow P62 2 5/16
CT-2931
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.
10
10
10
10
10
10
10
10
10
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Code/Flex Conductor HTAP Kit
• Includes all components to make a complete HTAP and
cover installation: HTCT HTAP, matching CLRCVR clear
cover and cable ties
• Each HTCT HTAP designed to terminate a wide range of
copper code and flex conductor combinations to
accommodate a variety of applications
• HTAPs incorporate a unique slotted design that allows for
quick and easy installation using supplied PANDUIT cable
ties; saves time and cost
• Matching clear covers are made from high impact plastic
and provide high impact strength and 360° viewing of
installed HTAP
• Clear covers have a UL 94 V-0 flame rating and an
oxygen index of 28 providing self-extinguishing, flame
retardant properties
• Requires crimping tools and dies, see pages 25, 26 and
27
• UL Listed and CSA Certified for applications up to 600V
when crimped with PANDUIT and specified competitor
Introduction
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
W
W
W
RUN
RUN
L
H
H
TAP 2
TAP 1
TAP 1
HTCT6-6
Part Number
HTWC2-2-1
TAP 3
HTCT2-2
Components
Clear
HTAP
Cover
Part No.
Part No.
HTCT6-6-1
CLRCVR1-1
HTCT2-2-1
CLRCVR2-1
HTCT250-2-1
CLRCVR3-1
HTCT250-250-1 CLRCVR3-1
TAP 2
L
Common
Bonding
Network
(CBN)
Components
TAP 1
HTCT250-2
HTCT250-250
Copper Conductor Size Range
Wire
Strand
Type
Code
Flex
Code
Code
Flex
HTWC250-250-1
W
H
TAP 1
Flex
HTWC250-2-1
RUN
L
H
HTWC6-6-1
L
RUN
Code
Flex
Run
#6 – #10 AWG
#6 – #10 AWG
#2 – #6 AWG
STR/SOL
#2 – #8 AWG
250 kcmil – #2
AWG
4/0 – #2 AWG
250 kcmil – #2
AWG
4/0 – #2 AWG
Tap1
#6 – #14 AWG
#6 – #14 AWG
#2 – #6 AWG
STR/SOL
#2 – #8 AWG
#2 – #6 AWG
STR/SOL
#2 – #8 AWG
250 kcmil – #2
AWG
4/0 – #2 AWG
Tap 2
Tap 3
—
—
#8 – #14 AWG
#8 – #14 AWG
#8 – #14 AWG
#8 – #14 AWG
#8 – #14 AWG
Std.
Pkg.
Qty.
1
Crimping
Tools
1
1
—
#8 – #14 AWG
1
—
—
For additional sizes and configurations and to see the complete line of PAN-LUG Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
See pages 20 and 21 for more information on HTAPs and clear covers, including crimping tools.
Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on the LS7 Printer and to see the complete line of
PANDUIT identification products, see the Identification Solutions Catalog SA-IDCB16.
Technical
Information
™
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
19
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Code/Flex Conductor HTAP
Introduction
For Making Parallel and Multiple Tap Connections on Code and Flex Conductors
• Used to tap into continuous conductors as a
splice or pigtailing
• Each HTAP terminates a wide range of
conductor sizes and combinations of code
and flex conductors Class G, H, I and
Locomotive to suit a variety of applications
• Slotted design allows quick and easy
assembly of conductor to HTAP using 3
PANDUIT 94 V-0 cable ties included
Grounding
Roadmaps
HTAP
RUN
TAP
Equipment
& Rack
Grounding
Kits
W
RUN
H
TAP 2
TAP 1
HTCT6-6
TAP 3
Part Number
Wire
Strand
Type
HTCT2-2
Code
Run
#6 – #10
AWG
Tap 1
#6 – #14
AWG
Flex
#6 – #10
AWG
#6 – #14
AWG
HTCT2-2-1
Code
Flex
HTCT250-2-1
HTCT250-250-1
W
RUN
L
Code
#2 – #6
AWG
STR/SOL
#2 – #8
AWG
Tap 2
Tap 3
—
—
#2 – #8 AWG #8 – #14
AWG
#8 – #14
AWG
250 kcmil – #2 – #6 AWG #8 – #14
#2 AWG
STR/SOL
AWG
#2 – #8 AWG #8 – #14
AWG
Code
250 kcmil –
#2 AWG
250 kcmil –
#2 AWG
Flex
4/0 – #2
AWG
4/0 – #2
AWG
—
TAP 1
HTCT250-250
Figure
Dimensions (In.)
#8 – #14
AWG
4/0 – #2
AWG
TAP 2
HTCT250-2
#2 – #6 AWG #8 – #14
STR/SOL
AWG
Flex
H
TAP 1
Copper Conductor Size Range
HTCT6-6-1
Technical
Information
L
H
TAP 1
Common
Bonding
Network
(CBN)
Components
L
RUN
L
H
Crimping
Tools
W
W
RUN
• Tap grooves are separated from one another
allowing them to function independently so
HTAP can be used with a single or multiple
taps providing maximum design and
installation flexibility
• Color coded and marked with PANDUIT die
index numbers for proper crimp die selection
• Requires crimping tools and dies, see
pages 25, 26 and 27
• UL Listed and CSA Certified for applications
up to 600V when crimped with PANDUIT
and specified competitor crimping tools and
PANDUIT crimping dies
• Tin plated to inhibit corrosion
Wire
PANDUIT Strip Std.
Die Color Length Pkg.
& Die No. (In.) Qty.
Orange, 11/16
1
PH6
L
.61
W
.40
H
.99
PANDUIT
Crimping
Tool
CT-930, CT-2931
.76
.61
1.55
CT-930, CT-2931
Brown,
PH2
13/16
1
.92
.96
1.92
CT-930, CT-2931
Purple,
PH25
1
1
.90
.89
1.92
CT-930, CT-2931
Purple,
PH25
1
1
—
—
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
Index
20
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Clear Covers for HTCT HTAPs
For Use with PANDUIT HTCT HTAPs
Introduction
• Made of high impact plastic to provide high impact strength
and 360° inspections of crimped connection to assure the
crimp is complete and the correct die was used
• Incorporate dual self-latching spring loaded latches and
supplied with two PANDUIT UL 94 V-0 cable ties — allow
for easy snap-on assembly and ensure covers are secured
• Low profile design minimizes space requirements
• Each cover half supports installation information labels
inside plastic retainer strips to allow labels to be viewed
on either side of cover and to protect labels from
being removed
Part Number
CLRCVR1-1
CLRCVR2-1
CLRCVR3-1
L
W
• Incorporate molded in flash barriers which encompass the
HTAP installation providing protection against electrical
flash over
• UL 94 V-0 flame rating and oxygen index of 28 providing
self-extinguishing, flame retardant properties
• Part number, voltage rating, temperature rating and HTCT
part number molded into cover for easy identification
• Flexible fingers located at each end of cover prevent
foreign objects from entering cover and are made from
ductile plastic material that allows easy installation and
will not damage conductor insulation
Use With HTAP
Part Number
HTCT6-6
HTCT2-2
HTCT250-2, HTCT250-250
Figure Dimensions Std.
(In.)
Pkg.
Qty.
L
W
H
4.48 1.41 1.20
1
5.10 1.66 1.40
1
5.35 2.16 1.40
1
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding
Connectors, see the Termination Solutions Catalog SA-TMCB02.
Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on the
LS7 Printer and to see the complete line of PANDUIT identification products, see the Identification Solutions
Catalog SA-IDCB16.
H
Common
Bonding
Network
(CBN)
Components
Shown Assembled
Crimping
Tools
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
21
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
C
Introduction
UL
R
US
Grounding Clamp, U-Bolt, Bronze
• Used to ground copper conductor parallel or at a right
angle to a rod, tube or pipe
• Made from high strength, electrolytic cast bronze
• High strength silicon bronze hardware provides long term
reliable assembly
H
Grounding
Roadmaps
W
Part Number
GPL-8-Q
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Technical
Information
Index
22
• Accommodates a wide range of pipe, tube, rod and
conductor sizes — minimizes inventory
• UL Listed for grounding and bonding and suitable for direct
burial in earth or concrete
GPL-14-X
GPL-15-X
Ground
Rod Size
(In.)
7/8 or 1
—
—
Iron
Pipe Size
(In.)
1/2 or 3/4
1
1
L
Conductor
Size Range
#8 SOL – #4 STR
#8 SOL – #4 STR
#4 SOL – 2/0 STR
Figure Dimensions
(In.)
L
W
H
2.38
1.38
2.63
2.63
1.38
2.75
2.63
1.63
2.75
Bolt
Dia.
(In.)
3/8
3/8
3/8
For the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.
Hex
Size
(In.)
9/16
9/16
9/16
Tightening Std.
Torque Pkg.
(In.-Lbs.) Qty.
110
25
110
10
180
10
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Grounding Clamp for Water Pipes, Bronze
• Used to ground copper code conductor to water pipe or
copper tube
• Cast from high strength, electrolytic bronze to provide
reliable grounding connections
• Plated steel screws provide high strength and
inhibit corrosion
Part Number
KP1-C
KP2-L
• Accommodates a wide range of pipe, tube, rod and
conductor sizes — minimizes inventory
• UL Listed for grounding and bonding and suitable for direct
burial in earth or concrete
Figure
Tightening Torque
Water Pipe
Dimensions (In.)
(In.-Lbs.)
Range
Conductor
(In.)
Size Range
L
W
Conductor Clamp
1/2 – 1
#10 SOL – #2 STR 2.28
.66
50
50
1 1/4 – 2 #10 SOL – #2 STR 3.58
.73
50
50
Std.
Pkg.
Qty.
100
50
Introduction
Grounding
Roadmaps
For the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
L
W
Equipment
& Rack
Grounding
Kits
Grounding Rod Clamp, Bronze
• Used for grounding copper conductor parallel to
ground rods
• Made from high strength, seamless electrolytic bronze to
provide long term durability
• High strength silicon bronze hardware provides long term
reliable assembly
Part Number
WB12-L
• Accommodates a wide range of rod and conductor
sizes — minimizes inventory
• UL Listed and CSA Certified for grounding and bonding
and suitable for direct burial in earth and concrete
Ground
Rod
Size
1/2
WB34-X
5/8
3/4
WB58-Q
5/8
Common
Bonding
Network
(CBN)
Components
Conductor Size
Range
#2 – #10 STR
#10 SOL
Figure
Dimensions (In.)
L
W
H
.88
.84
1.28
Hex Tightening Std.
Size
Torque Pkg.
(In.) (In.-Lbs.) Qty.
1/2
180
50
1/0 – #8 STR
#2 – #8 STR
1.03
1.06
1.54
1/2
180
10
1/0 – #8 STR
1.04
.92
1.40
1/2
180
25
Crimping
Tools
For the complete line of PAN-LUG Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
™
Technical
Information
H
W
L
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
23
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Crimping Tools
Introduction
Hand Operated Plier Type Tool
• Plier type
• Installer controlled crimp
Part Number
Grounding
Roadmaps
CT-100
Part Description
Crimps most PANDUIT #26 – #10 AWG insulated and non-insulated
terminals, disconnects and splices. Cuts #4, #6, #8 and #10 screw sizes.
Cuts and strips wire. Excellent all-around application tool of heat treated
finished steel with comfortable cushioned plastic grip handles.
Std.
Pkg.
Qty.
1
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
Equipment
& Rack
Grounding
Kits
CONTOUR CRIMP ™ Controlled Cycle Tools
• Specifically designed for the installation of PAN-TERM ®
terminals, disconnects and splices
• Low handle effort — increases productivity
Common
Bonding
Network
(CBN)
Components
Part Number
CT-1550
CT-1550
Crimping
Tools
CT-1570
• Superior crimp performance
• Reliable — backed by a two year warranty
Part Description
Crimps most PAN-TERM ® #22 – #10 AWG nylon and vinyl insulated
terminals, splices and disconnects. The CT-1550 has the red/blue pocket
closest to the pivot which provides a reduced crimp effort for those who
make red/blue terminations.
Std.
Pkg.
Qty.
1
CT-1570
Crimps most PAN-TERM ® #22 – #10 AWG and .5-6.0mm non-insulated
terminals and disconnects. Crimps PANDUIT #22 – #10 AWG and
.5-6.0mm non-insulated splices, and #10 AWG compression lugs.
1
CT-1700
Crimps PANDUIT #8 – #2 AWG non-insulated tubular terminals (S
series), #8 – #1 AWG copper lugs and splices, #6 – #4 AWG aluminum
lugs and splices and CTAPF copper taps for #14 – #3 AWG. Includes 5
position, color coded rotating die.
1
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CT- 1700
Technical
Information
Index
24
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Die Type, Manual Hydraulic, 14 Ton, Crimping Tool
• Two-stage rapid advance hydraulic system minimizes
number of pumps required to complete a crimp —
saves time
• Cushioned grip prevents hands from slipping on tool —
reduces fatigue
• Provides UL Listed and CSA Certified connections on
PANDUIT ® PAN-LUG ™ copper and aluminum lugs and
splices and copper taps
• Open “C-Head” design allows easy loading of crimping dies
and connectors, saves time
• Requires crimping dies, see page 27
• Dies installed using spring loaded die retention pins, no
need for tools
• Rubber boot on crimp head provides abrasion protection
• Audible “pop-off” valve indicates crimp completion
• Crimp head rotates 180°, provides versatility for use in
restricted spaces
Introduction
Grounding
Roadmaps
Part Number
CT-930
Part Description
Terminates PANDUIT ® PAN-LUG ™ Compression Connectors:
•
•
•
•
•
•
•
•
Std.
Pkg.
Qty.
1
Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor
Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor
Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor
Warranty: 5 years
CT-930 includes:
• Tool
• Plastic tool case with die storage
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.
Crimping
Tools
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
25
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool
Introduction
• Two stage rapid advance hydraulic system minimizes
cycle time
• Provides UL Listed and CSA Certified connections on
PANDUIT ® PAN-LUG ™ copper and aluminum lugs and
splices and copper taps
• Open “C-Head” design allows easy loading of crimping
dies and connectors, saves time
• Rubber boot on crimp head provides abrasion protection
• Ram automatically retracts when crimp cycle is complete
Grounding
Roadmaps
• Tool provided with two, high capacity 12 VDC rechargeable
nickel-metal hydride batteries — provides for continuous
operation and eliminates “memory” build-up, one hour
charge time
• Eight second crimp cycle time provides quick terminations,
saves time
• Uses industry standard Makita* batteries and charger —
industry proven reliability easy to obtain from local
retail sources
• Requires crimping dies, see page 27
• Dies installed using spring loaded die retention pins — no
need for tools
• Crimp head rotates 360° — provides versatility for use in
restricted spaces
Equipment
& Rack
Grounding
Kits
Part Number
CT-2931
Common
Bonding
Network
(CBN)
Components
Part Description
Terminates PANDUIT ® PAN-LUG ™ Compression Connectors:
•
•
•
•
•
•
•
•
Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor
Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor
Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor
Warranty: 3 years
Crimping
Tools
CT-2931 includes:
• Tool
• Two 12 VDC, rechargeable NiMH batteries
• One battery charger
• Steel tool case with storage for batteries, charger and crimp dies
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.
*Makita is a registered trademark of Makita Corporation.
Technical
Information
Index
26
Std.
Pkg.
Qty.
1
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
CD-920 Crimping Dies
• Crimping dies and connectors are color coded for
easy matching
• Embosses die index number on connector barrels for post
crimp inspection
Die
Color
• Part number permanently marked on crimping die for
easy identification
• Provides circumferential crimp results in terminations with
premium electrical and mechanical performance
• Used in PANDUIT crimping tools; see the CT-930 crimping
tool on page 25, the CT-2931 crimping tool on page 26
and the complete line of PANDUIT crimping tools in the
Termination Solutions Catalog SA-TMCB02
Introduction
Grounding
Roadmaps
Die Number
Used to Install PANDUIT Compression Lug & Splice Sizes
Part Number
CD-920-8
CD-920-6
CD-920-4
CD-920-2
CD-920
CD-920-1
CD-920-1/0
CD-920-2/0
CD-920-3/0
CD-920-4/0
CD-920-250
Copper Code Conductor Size and Die Color & Die No.
#8 AWG, Red P21
#6 AWG, Blue P24
#4 AWG, Gray P29
#2 AWG, Brown P33
#1 AWG, Green P37
1/0 AWG, Pink P42
2/0 AWG, Black P45
3/0 AWG, Orange P50
4/0 AWG, Purple P54
250 kcmil, Yellow P62
Used to Install PANDUIT HTAP Part Numbers
Part Number
CD-920H-6
CD-920H-2
CD-930H-250
Copper HTAP and Die Color & Die No.
HTCT6-6-1, Orange PH6
HTCT2-2-1, Brown PH2
HTCT250-2-1,
HTCT250-250-1, Purple PH25
Std.
Pkg.
Qty.
1
1
1
1
1
1
1
1
1
1
Std.
Pkg.
Qty.
1
1
1
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
27
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Introduction
PANDUIT ® STRUCTUREDGROUND ™ System for Data Center Grounding
Application Standards
Alliance for Telecommunications Industry
Solutions ATIS
Grounding
Roadmaps
ATIS is a technical planning and standards development
organization that is committed to rapidly developing and promoting
technical and operations standards for the communications and
related information technologies industry worldwide using a
pragmatic, flexible and open approach. Over 1,200 participants from
more than 400 communications companies are active in ATIS’ 22
industry committees, and its Incubator Solutions Program.
www.atis.org
Telecommunications Industry Association TIA
Equipment
& Rack
Grounding
Kits
The Telecommunications Industry Association is a leading U.S.
non-profit trade association serving the communications and
information technology industry. TIA represents providers of
communications and information technology products and services
for the global marketplace through its core competencies in
standards development.
The Institute of Electrical and Electronics
Engineers, Inc. (IEEE)
Common
Bonding
Network
(CBN)
Components
The IEEE
developing,
electro and
of humanity
promotes the engineering process of creating,
integrating, sharing, and applying knowledge about
information technologies and sciences for the benefit
and the profession.
NEBS Level 3 Approval as Tested by Telcordia Technologies
Crimping
Tools
Telcordia Technologies, formerly known as Bellcore, serves as the
testing agency for the Regional Bell Operating Companies. Network
Equipment-Building Systems (NEBS) was developed by Bellcore
and is currently maintained by Telcordia Technologies. NEBS was
developed to standardize requirements for Central Office Equipment
and to develop criteria for personal safety, protection of property and
operational continuity.
Underwriters Laboratories, Inc.
Technical
Information
Underwriters Laboratories, Inc. is an independent, not-for-profit
safety testing and certification organization based in the
United States.
J-STD-607-A-2002, Commercial Building Grounding
(Earthing) and Bonding Requirements for
Telecommunications is jointly developed by TIA/EIA and ATIS’
technical committee T1E1. This document is available on the
ATIS Document Center at www.atis.org.
Adhering to the grounding principles outlined in J-STD-607-A helps
ensure that telecommunications equipment and systems
operate reliably. As stated in J-STD-607-A, the preferred means of
connecting conductors to busbars is by using two-hole
irreversible compression lugs listed by a nationally recognized
testing laboratory (NRTL) such as UL. PANDUIT ® PAN-LUG ™ Copper
Compression Connectors meet these requirements, in all of the
barrel sizes specified by the 607 standard.
ANSI/TIA-942 Draft 5.0a – Telecommunications
Infrastructure Standard for Data Centers
TIA-942 states that electrical continuity is required throughout the
rack materials. Adhering to these principles protects network
equipment and maintains system performance. PANDUIT ®
STRUCTUREDGROUND ™ System for Data Center Grounding meets
TIA-942 requirements by incorporating an all-copper grounding path.
Paint piercing grounding washers ensure metal to metal contact of
rack members and two-hole compression lugs for a permanent and
reliable connection.
IEEE Std 1100-1999 (IEEE Emerald Book) – IEEE
Recommended Practice for Powering and Grounding
Electronic Equipment
The main objective of the Emerald Book is to provide a consensus of
recommended practices to address electronic equipment
performance issues while maintaining a safe installation, as
specified in the National Electrical Code ® (NEC ®) (NFPA 70-1999)
and recognized testing laboratories' standards.
NEBS Level 3 Criteria is the minimum level of
environmental compatibility needed to provide maximum
assurance of equipment operability within the network
facility environment.
The Level 3 Criteria is the highest assurance of product operability.
Products that meet NEBS Level 3 Criteria are suited for equipment
applications which demand minimal service interruptions over the life
span of the equipment. PANDUIT is the first in the industry to have a
system of copper compression lugs and splices (#8 AWG – 1,000
kcmil) and crimping tools physically and rigorously tested by
Telcordia Technologies to meet NEBS Level 3 compliance.
• UL 467 Grounding and Bonding Equipment
• UL 486A Wire Connectors and Soldering Lugs for Use with
Copper Conductors – Covers pressure wire connectors and
soldering lugs for use with copper conductors according to the
National Electrical Code NFPA 70
• UL VW-1 Flammability Rating
Underwriters Laboratories, Inc. Standards applicable to specified
PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding
and PAN-LUG ™ Power and Grounding Connectors.
Canadian Standards Association
Index
28
Canadian Standards Association is a not-for-profit membership
based association serving business, industry, government, and
consumers in Canada and the global marketplace. C.S.A. works in
Canada and around the world to develop standards that enhance
public safety and health.
• C22.2 NO. 41-M1987 (R2004) Grounding and
Bonding Equipment
• C22.2 NO. 65-03 Wire Connectors
Canadian Standards Association standards that are applicable to
specified PANDUIT ® STRUCTUREDGROUND™ System for Data Center
Grounding and PAN-LUG ™ Power and Grounding Connectors.
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Specification Layout for Data Center Grounding per BICSI TDM Manual,
10th Edition
Introduction
Roof
Red
iron
Backbone pathway
Suspended ceiling area
GE
Building steel
TR
Grounding
Roadmaps
Building steel
TR
GE
TGB
TGB
Equipment
& Rack
Grounding
Kits
Exterior building wall
Red
iron
Backbone pathway
TR
(TBB)
TR
TBB
TGB
TGB
Sleeve
Exterior building wall
Suspended ceiling area
Common
Bonding
Network
(CBN)
Components
Red
iron
Backbone pathway
Suspended ceiling area
TBB within conduit
Panel
board
Primary
cable
protection
Electrical
EF
ER
TMGB
(TBB)
EF
(TBB)
ACEG
Crimping
Tools
TGB
GEC
BCT
Grounding
electrode
system
Source: BICSI TDM Manual, 10th Edition
ACEG
BC
BCT
EF
ER
GE
GEC
TBB
TGB
TMGB
TR
=
=
=
=
=
=
=
=
=
=
=
Alternating current equipment ground
Bonding conductor
Bonding conductor for telecommunications
Entrance facility
Equipment room
Grounding equalizer
Grounding electrode conductor
Telecommunications bonding backbone
Telecommunications grounding busbar
Telecommunications main grounding busbar
Telecommunications room
Technical
Information
Index
For more technical grounding information, please see the Data Center Grounding White Paper at www.panduit.com/dcgrounding.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
29
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Recommended Sizing of the Telecommunications Bonding Backbone (TBB)
and Grounding Equalizer (GE) per J-STD-607-A
Introduction
The TBB shall be a copper conductor. The minimum conductor size shall be a No. 6 AWG. The TBB
shall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of a 3/0 AWG. The
TBB may be insulated. The Bonding conductor for Telecommunications (BCT) shall be, as a minimum,
the same size as the TBB.(1)
Sizing of the TBB
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
TBB Length
linear M (ft)
less than 4 (13)
TBB Size (AWG)
6
4 – 6 (14 – 20)
4
6 – 8 (21 – 26)
3
8 – 10 (27 – 33)
2
10 – 13 (34 – 41)
1
13 – 16 (42 – 52)
1/0
16 – 20 (53 – 66)
2/0
greater than 20 (66)
3/0*
*3/0 may not always be available. 4/0 is a more common size that may be substituted.
Common
Bonding
Network
(CBN)
Components
Recommended Cable Sizes for Grounding Applications
Purpose
Other connections to the TGB and TMGB,
including building steel, main water pipe, etc.
Underfloor CBN
Connections to Underfloor CBN from pipes,
ventilation ducts, etc.
Connection from Underfloor CBN to TGB
Crimping
Tools
Use the
Following
Code Cables
#6 AWG, green insulated
#2 AWG, bare
#6 AWG, bare
2/0 AWG, bare
Key Terminology
Ground
A conducting connection, whether intentional or
accidental, by which an electric circuit or equipment is
connected to the earth, or to some conducting body of
relatively large extent that serves in place of the earth.
Bonding
The permanent joining of metallic parts to form an
electrically conductive path that will assure electrical
continuity and the capacity to conduct safely any
current likely to be imposed.
Common Bonding Network (CBN)
The principal means for affecting bonding and earthing
inside a building.
Technical
Information
Index
1. Telecommunications Industry Association, Commercial Building Grounding (Earthing) and Bonding Requirements For Telecommunications, J-STD-607-A,
October 2002.
30
S TRUCTURED
G ROUND ™GSystem
DataFOR
Center
S TRUCTURED
ROUND ™ for
SYSTEM
DATA Grounding
CENTER GROUNDING
Introduction
Part Number Index
Introduction
Part Number
Page
Number
Part Number
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
LCC1-14AW-E . . .
LCC1-38DW-E . .
LCC1/0-14AW-X .
LCC1/0-38DW-X .
LCC10-14BW-L . .
LCC10-14JAW-L
LCC10-14JAWF-L
LCC10-14JAWH-L
LCC2-14AW-Q . .
LCC2-38DW-Q . .
LCC2/0-14AW-X .
LCC2/0-38DW-X .
LCC250-12DW-X .
LCC250-38DW-X .
LCC3/0-12W-X . .
LCC3/0-38DW-X .
LCC4-14ADW-L . .
LCC4-38DW-L . . .
LCC4/0-14AW-X .
LCC4/0-38DW-X .
LCC6-10ABW-L . .
LCC6-14BDW-L . .
LCC6-14EW-L . . .
LCC6-14JAW-L . .
LCC6-14JAWF-L .
LCC6-14JAWH-L .
LCC6-38BDW-L . .
LCC6-56BW-L . . .
LCC8-10ABW-L . .
LCC8-14ABW-L . .
LCC8-14DW-L . . .
LCC8-38DW-L . . .
LCCX1-14A-X . . .
LCCX1-38D-X . . .
LCCX1/0-14A-X .
LCCX1/0-38D-X .
LCCX2-38D-E . . .
LCCX2/0-14A-X .
LCCX2/0-38D-X .
LCCX250-38D-X .
LCCX3/0-38D-X .
LCCX4-14AB-L . .
LCCX4-38BD-L . .
LCCX4/0-38D-X .
LCCX6-10B-L . . .
LCCX6-14AB-L . .
LCCX6-14D-L . . .
LCCX6-38AC-L . .
LCCX6-38D-L . . .
LCCX8-10AB-L . .
LCCX8-14AB-L . .
LCCX8-14D-L . . .
LCCX8-38D-L . . .
LTYK . . . . . . . . . .
C
CD-920-1 . . .
CD-920-1/0 . .
CD-920-2 . . .
CD-920-2/0 . .
CD-920-250 .
CD-920-3/0 . .
CD-920-4 . . .
CD-920-4/0 . .
CD-920-6 . . .
CD-920-8 . . .
CD-920H-2 . .
CD-920H-6 . .
CD-930H-250
CLRCVR1-1 .
CLRCVR2-1 .
CLRCVR3-1 .
CT-100 . . . . .
CT-1550 . . . .
CT-1570 . . . .
CT-1700 . . . .
CT-2931 . . . .
CT-930 . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.27
.27
.27
.27
.27
.27
.27
.27
.27
.27
.27
.27
.27
.21
.21
.21
.24
.24
.24
.24
.26
.25
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.15
.15
.15
.15
.15
.22
.22
.22
H
HTCT2-2-1 . . . .
HTCT250-2-1 . .
HTCT250-250-1
HTCT6-6-1 . . . .
HTWC2-2-1 . . . .
HTWC250-2-1 . .
HTWC250-250-1
HTWC6-6-1 . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Part Number
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
PV10-10RX-L
PV10-14RX-L
PV10-6RX-L .
PV10-8RX-L .
PV14-10RX-C
PV14-14RX-C
PV14-6RX-C .
PV14-8RX-C .
Page
Number
L
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
G
GB2B0304TPI-1
GB2B0306TPI-1
GB2B0312TPI-1
GB4B0612TPI-1
GB4B0624TPI-1
GPL-14-X . . . . .
GPL-15-X . . . . .
GPL-8-Q . . . . . .
Page
Number
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.20
.20
.20
.20
.19
.19
.19
.19
K
KP1-C . . . . . . . . . . . . . . . . . . . . . . .23
KP2-L . . . . . . . . . . . . . . . . . . . . . . . .23
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
P
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.17
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.18
.15
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
RGCBNJ660P .
RGEJ1024PF .
RGEJ1024PH .
RGEJ1036PF .
RGEJ1057PF .
RGEJ624PF . .
RGEJ624PH . .
RGEJ636PF . .
RGEJ657PF . .
RGESD-1 . . . .
RGRB19 . . . . .
RGREJ1096 . .
RGREJ696 . . .
RGRKCBNJ . .
RGRKCBNJEJ
RGS134-1 . . . .
RGS134-10-1 .
RGTBS-C . . . .
RGTBSM6-C . .
RGTS-C . . . . .
RGTSM6-C . . .
RGW-100-1 . . .
RGW-12-1 . . . .
RGW-32-1 . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.16
.16
.16
.16
.16
.16
.16
.16
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.11
.12
.12
.12
.12
.12
.12
.12
.12
.13
.14
.14
.14
.14
.14
.11
.11
.14
.14
.14
.14
.13
.13
.13
Grounding
Roadmaps
R
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Equipment
& Rack
Grounding
Kits
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
W
WB12-L . . . . . . . . . . . . . . . . . . . . . . .23
WB34-X . . . . . . . . . . . . . . . . . . . . . .23
WB58-Q . . . . . . . . . . . . . . . . . . . . . .23
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).
Technical
Information
Index
31
PANDUIT is a global leader in cabling and communication products,
delivering end-to-end solutions in support of
demanding electrical and networking requirements.
PANDUIT Catalogs
Cable Ties
Termination Solutions
SA-CTCB03
SA-TMCB02
!PAN-TY ® Cable Ties
!CONTOUR-TY ® Cable Ties
!PAN-TERM ® Terminals
!Crimping Tools and Dies
!PAN-TY Clamp Ties
!DURA-TY Cable Ties
!PAN-TERM ® Disconnects
!PAN-LUG ™ Mechanical Connectors
!PAN-TY Push Mount Ties
!BELT-TY In-Line Cable Ties
!PAN-TERM Splices
!PAN-LUG ™ Grounding Connectors
!PAN-TY Marker Ties
!TAK-TY Hook & Loop Cable Ties
!PAN-TERM Ferrules
!Support Products
!DOME-TOP ® Barb Ty Cable Ties
!STA-STRAP ® Cable Ties
!PAN-LUG ™ Compression
!DOME-TOP ® Barb Ty Clamp Ties
!Cable Tie Installation Tools
!DOME-TOP Barb Ty Marker Ties
!Custom Hot Stamping
®
™
®
™
®
®
®
®
Connectors
Wiring Accessories/Abrasion Protection
Stainless Steel Products
SA-CTCB03
SA-SSCB06
!Adhesive Backed Cable Tie
Mounts
!Screw Applied Cable Tie Mounts
!Flat Cable Mounts
!Fixed Diameter Clamps
!Harness Board Accessories
!Spiral Wrap
!Grommet Edging
!PAN-STEEL ® Stainless Steel
!PAN-STEEL® System Accessories
!Braided Expandable Sleeving
Cable Ties
!PAN-STEEL ® Stainless Steel
Strapping
!Installation Tools
!PAN-STEEL® System
!Corrugated Loom Tubing
and Fittings
!Heat Shrink Tubing
!Non-Shrink PVC Tubing
!PAN-WRAP ™ Split Harness Wrap
Permanent Identification
Identification Products
Surface Raceway
SA-IDCB16
SA-SRCB02
!Hand-Held Printers
!Lockout/Tagout Products
!Office Furniture Raceway
!Desktop Printers
!Voltage Markers
!Cove Raceway
!Labeling Software
!Warning Labels
!PAN-WAY TG-70 Surface Raceway
!Computer Printable Labels
!Safety Signs and Tags
!PAN-WAY ® T-70 & Twin-70
!Letters and Numbers
Surface Raceway
!PAN-WAY ® T-45 Surface Raceway
!ULTIMATE ID ® Network
Labeling System
!Wire Markers
32
®
!Faceplates, Surface Mount Outlet
Boxes & Labeling Administration
®
!PAN-WAY ® LD Profile Surface
Raceway
!PAN-WAY ® T130 Surface Raceway
!PAN-POLE ™ Outlet Poles
Wiring Duct
Network Connectivity
SA-WDCB05
SA-NCCB04
!PANDUCT ® Slotted Wall
!PANDUCT ® Hinged Slotted Wall
!Modules
!Racks & Cable Management
Wiring Duct
!PANDUCT ® Solid Wall Raceway
!PANDUCT ® Halogen Free Slotted
Wall Wiring Duct
!PANDUCT ® Flush Cover Round
Hole Wiring Duct
Wiring Duct
!PANDUCT ® Flexible Wiring Duct
!PANDUCT ® Low Smoke Slotted
Wall Wiring Duct
!Wiring Duct Accessories and
Installation Tools
!ULTIMATE ID ® System
!Grounding and Bonding
!Work Area
!Fiber Routing
!Zone Cabling
!Surface Raceway
!Patch Panels, Copper Patch
!Labeling & Administration
Cords & Punchdowns
!Fiber Connectors, Enclosures &
Patch Cords
!Cable Ties & Accessories
Download