USDP~GR Series DAIKIN DECK UNIT

advertisement
ED81-401
DAIKIN DECK UNIT
USDP~GR Series
Cooling
60Hz : 87~165kW
DAIKIN DECK UNIT "USDP~GR" Series
1. Introduction of DAIKIN DECK UNIT
"DECK UNIT" is one of the Central Air Conditioners for accommodation area,which is assembled in
advance by the manufacturer as a self-contained unit and installed in the machine room on the
accommodation deck.
DAIKIN DECK UNIT- "USDP series is optimally designed for marine application and also gentle for the
environment.
2. Features
¡Very Less Operating Vibration and Lower Noise designed for installing in the accommodation
The adoption of Hermetic Scroll Compressors makes the operating vibration and noise remarkably lower.
This allows the units to install in the accommodation area without troublesome problem.
¡High Static Pressure Fan Easily Conforming to Complex Duct System
The high-performance fan can adapt the complex duct system with middle to higher pressure.
¡The Light Weight and Compact Design of Top Level in the Field
Because of low height ranging from 1,550 to 1,650 A, the unit can be easily installed in even space-limited
deck.
Also the light weight from 1,100 to 1,600 O does not interfere with the cruising speed of high-speed ferry.
¡Epoch-making Save Energy in Spite of HFC Unit
Optimally designed Scroll Compressors and heat exchangers combined with high-performance fan
reduce the power consumption by 15 to 20 %, compared with conventional units. This also contributes to
control the CO2 emission from the generator.
¡Excellent Durability for Marine Application
Higher reliability is secured by the concentration of the DAIKIN advanced technology, for sea water, sea
breeze and ship motion.
¡Economical Maintenance on Board
Installing compressors, which realize 40,000h in design service life, in plural not only realizes the free
maintenance on board, but save the service cost of compressors by half, compared with the conventional
unit.
This also enables the unit to continuously operate even in trouble of one compressor.
Furthermore, the lighter compressor provided with lifting hook allows replacing work to be easier on
board.
3.Guide Specifications
Hermetically Sealed Scroll Compressors
The compressor optimally developed for R404A has a longer durability, higher efficiency and very less
vibration, compared with the conventional Semi-hermetic compressor.
Condenser
The condenser is a shell and cross fin tube type highly efficient and highly resistant to sea water.
It is made of aluminum brass in the cooling tubes, naval clad steel in the tube sheet and cast iron with
sacrificial anodes in the water jackets. The joints for water thermometers are provided in the inlet and
outlet headers (USDP30,40,50GR).
Evaporator
The evaporator is a cross fin coil type highly efficient and highly resistant to sea breeze.
It is made of copper tubes and aluminum fins with highly anti-corrosive and hydrophilic treatment.
Steam heater
The steam heater is a cross fin oil type highly resistant to change of air temperature and sea breeze as
well.
It is made of copper tubes and aluminum fins with highly anti-corrosive treatment.
Fan and its relative parts
Highly performed multi-blade fan (USDP25GR,30GR) or turbo fan (USDP40GR,50GR) is mounted based on
those application, driven by V belts with a separate fan motor. The fan bearings are forced oil feed
system,highly durable for sea breeze.
The fan motor is "B" class insulation, totally enclosed fan cooled type, prescribed in JIS C4210.
Control
The unit is operated by the push button switch, and the operating condition can be confirmed by each
pilot lamp.
The meaning of each pilot lamp is -"White": "Normal power into the unit"and "Green" : "Normal
operation".
If "Red" lights up, any safety device works to stop the unit till removing the applied cause.
Multiple compressors are sequentially started in direct-on-line in order to minimize the starting current.
The capacity is controlled in two steps mainly by local thermostat (or possibly by internal thermostat as
well) according to the basis air temperature.
The following electric and safety devices are equipped in the starter or inside the unit to make the
maintenance saving on board.
Non-fuse breakers and ammeters are equipped in the starter for each circuit of comp. or fan motor.
Over current relay(each comp., fan motor), fuses, thermal protectors, high and low pressure switches and
reverse phase protector and so on are equipped in order to prevent the abnormal operation.
The contact terminals indicating "Normal" or "Abnormal" are provided for connecting to the central
observation board.
The power and control cables to/from the central board can be conducted through combing holes on the
bottom side of the starter.
Structure
The outside and inside plates are constructed with the rigid frame in long durability.
Anti-corrosive acrylic powder painting is coated even in every nook and corner-casing, drain pan, bottom
frame, partition plate, fan housing and fan motor base, etc.
Either right or left drain connection allows the condensing drain water to smoothly discharge outside in
rolling angle.
Applicable Standard
The unit is certified by NK standard. This system is so independent only for the air conditioning in the
accommodation that any other rules of classification society are excluded except the ship owner's special
request.
DAIKIN DECK UNIT
USDP~GR
R404A type
USDP25GR
USDP30GR
USDP40GR
USDP50GR
1. Specifications...................................................................................................2
1.1
1.2
1.3
1.4
1.5
2.
3.
4.
5.
Main Specifications ...........................................................................................2
List of Safety Devices and Control Devices .....................................................3
List of Gauge and Thermometer ......................................................................4
List of Test Pressure for Pressure Vessel .........................................................4
List of Optional Accessories .............................................................................5
Dimensions ......................................................................................................6
Wiring Diagrams..............................................................................................9
Electric Characteristics ..................................................................................13
Capacity Tables ..............................................................................................14
5.1 Capacity Tables ................................................................................................14
5.2 Operation Limit ................................................................................................22
6.
7.
8.
9.
Piping Diagrams ............................................................................................23
Installation......................................................................................................26
Installation Instruction...................................................................................28
Appendix ........................................................................................................31
9.1
9.2
9.3
9.4
9.5
Vibration and Sound Level..............................................................................31
Gist of Piping Connection Flexibility..............................................................33
Steam Valve Panel .........................................................................................36
Specifications of Main Structural Parts & External Drawings......................37
Gist to Mount The Mixing Box .......................................................................41
1
1. Specifications
1.1
Main Specifications
¡ R404A type
USDP25GR
Model
Power
Painting Color
Dimensions
HWD
*1 Cooling Capacity
*2 Cooling Water Flow Rate
*3 Heating Capacity
*4 Humidifying Capacity
Head Loss
Compressor
Fan
Heater
– / 87
275 / 300
106
30
19.8 / 20.7
JT335DDFYE2
– / 103
300 / 360
132
36
11.8 / 15.7
Hermetic Scroll Type
2,900/3,450
(7.52)(7.51)
(7.52)(7.52)
9.02
Protective Devices
Thermal & Sound Isorator
Chilled Water Inlet/Outlet
Piping
Upper Drain Outlet
Connection
Lower Drain Outlet
Kind
Refrigerant
Charged
kg
Kind
Lubricant Oil
Charged
R
Machine Weight
kg
Operating Weight
kg
Standard Spare Parts
Applicable Standard
CXS1919B1
(CXS1919B1)(CXS1919B1)
Water Cooled Shell & Finned Tube
Copper Alloy Seamless Tube (C6871T)
Alminium Fins (A1050R-24H)
Steel Tube (KSTPG38)
Naval Clad (C4621P KPV24)
2
2
CRB-USDP30G
CRB-USDP50G
Crossfincoil Type
Copper Tubes
Alminium Fins
D3Y1
TD3B1
Multi Blade Fan
140/140
860/1,225
7.5
100-50-0
165/165
1,100/1,520
11
220/220
920/1,700
11
255/270
860/1,630
15
Belt Drive
Crossfincoil Type
Copper Pipe, Alminium Fins
Steam Spray Type
Polyvinyl Chloride Fiber (Washable)
Thermostatic Expansion Valve
Thermostat
100-67-0
100-50-0
Non-Fuse Breaker, Over-Current Relay (For Comp. & Fan Motor), Fusible Plug, Reverse Phase Protector,
Comp. Motor Protection Thermostat, High Pressure Switch, Low Pressure Switch, Safety Valve
Glass Fiber
2B (With Flanges)
3B (With Flanges)
1 1/4B(32A)
1B(25A)
R404A
11.7
2.72
1,100
1,110
Fuse (100V1, 400V1)
11.210.3
DAPHNE FVC68D
(2.72)(2.71)
1,250
1,265
11.211.2
11.711.7
(2.72)(2.72)
1,575
1,600
1,600
1,625
Fuse (100V1, 400V1), Cooling water thermometer2
NK
Note:
*1. Cooling Capacity is based on the following conditions:
Evaporator :
Inlet air temp. 31°C D.B, 24°C W. B.
*2. Condenser :
Inlet water temp. 32°C.
*3. The heater inlet condition : Inlet air temp. 10°C D.B. Inlet steam press. 0.4MPa
*4 Humidifying capacity's value is the condition of saturated steam at the 0.035MPa.
2
(9.02)(9.02)
Direct Start
(CXS1919B1)(CXS1919B1)
Tube
Fin
%
– / 136
440 / 480
170
48
13.7 / 16.7
– / 165
550 / 600
212
60
19.6 / 22.5
(JT300DDFYE2)(JT300DDFYE1) (JT300DDFYE2)(JT300DDFYE2) (JT335DDFYE2)(JT335DDFYE2)
1
CRB-USDP25G
Model
Type
Air Flow Rate m3/min
External Static Press Pa
Motor Power kW
Drive
Type
Material
Humidifier
Air filter
Refrigerant Control
Temperature Control
Capacity Step
USDP50GR
1,5502,0001,800
1,6502,0001,250
Tube
Fin
Shell
Tube Plate
No.
Model
Type
Material
USDP40GR
New Light Blue (7.5BG7/2), DK Black
mm
kW
R/min
kW
kg/h
kPa
Model
Type
Speed
r.p.m
Motor Power kW
Starting Manner
Model
Type
Water Cooling
Condenser
Material
Evaporator
USDP30GR
3 phase AC 380, 400, 415 / 400, 440V 50/60Hz
(1 phase AC 110V 50/60Hz)
Main Circuit
Control Circuit
1.2
List of Safety Devices and Control Devices
¡ R404A type
USDP25GR
Commodities
USDP30GR
USDP50GR
ACB—BB87 (Saginomiya)
High pressure switch
0
OFF : 2.70 0.1 MPa
ON : 2.06
0.15
OFF : 0.03 0.02 MPa
Imposs.
ON : 0.05 0.03 MPa
OSVD12B—278 (DAIKIN)
Safety valve
(relief to the air)
Initial relief pressure : 2.92 Mpa
WTB—K602 (Saginomiya)
Thermostat
Imposs.
Relief pressure : 3.19 Mpa
Note) Be sure to keep the OFF point at more than 20°C.
(15~32°C) Diff2°C
ATX—12220DUS1
Expansion valve
ATX—57080DUS1
ATX—71160DUS1
ATX—71160DUS2
ATX—12220DUS2
(Saginomiya)
OFF : 7 1.5°C
OFF : 135 3 °C
Imposs.
ON : 115 15°C
CLK50JTH—P12
Over current relay
for compressor
21A2
Over current relay
for fan
21A
21A3
21A4
26A
26A,6 sec
CLK—35JTH—P6
21A4
K2CM—1M (Omron)
Thermal control valve
for steam heater
SA33B 3P 30/30AT (Fuji Electric)
EA53B 3P 50/40AT (Fuji Electric)
EA103B—W 3P 100/75AT (Fuji Electric)
Imposs.
Imposs.
34A,6 sec
Cello light fuse UC1 5A (Uthunomiya Electric), Glass tube fuse FGB0 5A
for compressor
Poss.
ON : 71.5 °C
UT12—3515K (UBUKATA Manufacturing Co.)
Compressor thermal protector
for fan
Poss.
DTB—K103 (Saginomiya)
Freeze protection thermostat
Fuse
Set-value
change
on a ship
Imposs.
MPa
LCB—LA74 (Saginomiya)
Low pressure switch
Non fuse breaker
USDP40GR
EA53B 3P 50/50AT (Fuji Electric)
EA103B—W 3P 100/100AT (Fuji Electric)
LEX8(TLV)
Relief temperature : 70°C or less (Control range 50~130°C)
Imposs.
Imposs.
Poss.
3
1.3
List of Gauge and Thermometer
USDP25GR, 30GR, 40GR, 50GR
Models
Commodities
USDP30GR
Toyo Instruments co.
Compound gauge
Cooling water thermostat
Dainichi Instruments Co.
USDP40GR
USDP50GR
Type
Manufacturer
Pressure gauge
1.4
USDP25GR
DUφ60
0~5.0MPa
DUφ60
– 0.1~2.0MPa
––
Cylindrical shape thermometer 0~100°C
List of Test Pressure for Pressure Vessel
USDP25GR, 30GR, 40GR, 50GR
Commodities
Compressor
Condenser
4
high pressure side
Hydraulic test pressure MPa
Air tight test pressure MPa
10.2
3.4
low pressure side
4.8
1.6
refrigerant side
4.17
2.78
1.0
––
Refrigerant circuit in products
water side
––
2.67
Evaporator
––
2.67
Steam heater
––
0.7
Stop valve
––
3.0
1.5
List of Optional Accessories
Models
Commodities
Spare parts
USDP25GR
USDP30GR
USDP40GR
USDP50GR
KSPS25GAR1
KSPS30GAR1
KSPS40GAR1
KSPS50GAR1
Spare Parts List
Types
Miscellaneous
Electric parts
Parts for condenser
Models
KSPS25GAR1 KSPS30GAR1 KSPS40GAR1 KSPS50GAR1
USDP25GR
USDP30GR USDP40GR
USDP50GR
Level gauge
1
2
2
2
O-ring for level gauge
1
2
2
2
Safety valve
1
2
2
2
Sacrifice anode plate
8
16
16
16
Sacrifice anode packing
8
16
16
16
8
8
8
8
Sacrifice anode putty
1 set
1 set
1 set
1 set
Condenser front cover
1
2
2
2
Condenser rear cover
1
2
2
2
Cooling water thermometer
––
1
1
1
Magnetic contactor (Fan)
1
1
1
1
Magnetic contactor (Compressor)
2
3
4
4
Fuse (5A)(UC-1)
2
2
2
2
Fuse (5A)(FGB0)
1
1
1
1
Pilot lamp (RED)
2
2
2
2
Pilot lamp (GREEN)
1
1
1
1
Pilot lamp (WHITE)
1
1
1
1
V belt
3
3
3
3
Bearing, fan
2
2
2
2
Air filter
6
6
6
6
Expansion valve
1
2
2
2
Low pressure switch
1
2
2
2
High pressure switch
2
2
2
2
Pressure gauge
1
2
2
2
Compound gauge
1
2
2
2
Hex key wrench (6mm)
–-
1
––
––
Hex key wrench (10mm)
1
1
1
1
Spare parts box
1
1
1
1
Sacrifice anode fixing screw
5
850
50
Part A
110
M30
62
A DETAIL
110
0
φ6
2000
AIR OUTLET FLANGE
55
REAR
1700
70
9
50
1650
10-φ23HOLES
ANCHOR BOLT
108
2
50
11
HOLE FOR ANCHOR BOLT OF BOTTOM FRAME
FRONT
20
1960
75
62
7
1250
180
25
245
233
560
625
40
3
4
5
6
(FRONT)
(REAR)
600
MIN.SERVICE SPACE
600
1016
1050
1090
11/4B SGP [32A]
JIS5kg/cm2 FLANGE
PIPING SAFTY VALVE
5 STEAM SPRAY INLET
6
3/4B SGP [20A]
JIS5kg/cm2 FLANGE
1/2B SGP [15A]
1B SGP [25A]
7 LOWER DRAIN OUTLET JIS5kg/cm2 FLANGE
UPPER DRAIN OUTLET
9 STARTER BOX
8
20
16-φ4.7HOLES
BOTH SIDE
DETAIL OF AIR INLET FLANGE
14-φ8HOLES
1565=775
NO.
PARTS NAME
3D012811D
REMARK
3/4B SGP [20A]
NOTE:
4 STEAM HEATER OUTLET JIS5kg/cm2 FLANGE
1. STANDARD MODEL IS PIPED AT RIGHT SIDE.
11/4B SGP [32A]
100 2. LEFT SIDE PIPING LOCATION IS SYMMETRICAL
3 STEAM HEATER INLET JIS5kg/cm2 FLANGE
WITH RIGHT SIDE PIPING LOCATION.
3.u IS SET ON BOARD.
2B SGP [50A]
2 CONDENSER WATER OUTLET JIS5kg/cm2 FLANGE
4.TAKE HEIGHT MORE THAN THE STATIC
PRESSURE IN DORAIN-TRAP OUTSIDE THE
2B SGP [50A]
1 CONDENSER WATER INLET
MACHINE.
JIS5kg/cm2 FLANGE
1
8
2665=1690
1780
6255=1530
27-φ4.7HOLES
BOTH SIDE
AIR INLET FLANGE
DETAIL OF AIR OUTLET FLANGE
845
284
1210
35
62
240 140
154
94-φ4.7HOLES
1000
530
1780
26 65=1690
100
1010
194
416
606
500
900
6
20
USDP25GR
2. Dimensions
7
50
110
M30
A DETAIL
110
φ
60
2000
AIR OUTLET FLANGE
REAR
1700
62
62
220
50
2
10-φ23HOLES
ANCHOR BOLT
108
9
50
11
HOLES FOR ANCHOR BOLT OF BOTTOM FRAME
FRONT
1960
75
20
850
94-φ4.7HOLES
1650
1780
7
1250
180
25
245
233
450
625
40
3
8
6
600
FRONT
REAR
600
MIN.SERVICE SPACE
1090
20
16-φ4.7HOLES
BOTH SIDE
4 STEAM HEATER OUTLET
5 STEAM SPRAY INLET
6 PIPING SAFTY VALVE
3D010321D
REMARK
3B SGP [80A]
JIS5kg/cm2 FLANGE
3B SGP [80A]
JIS5kg/cm2 FLANGE
11/4B SGP [32A]
JIS5kg/cm2 FLANGE
3/4B SGP [20A]
JIS5kg/cm2 FLANGE
3/4B SGP [20A]
JIS5kg/cm2 FLANGE
1/2B SGP [15A]
1B SGP [25A]
7 LOWER DRAIN OUTLET JIS5kg/cm2 FLANGE
11/4B SGP [32A]
8 UPPER DRAIN OUTLET JIS5kg/cm2 FLANGE
9 STARTER BOX
DETAIL OF AIR INLET FRANGE
14-φ8HOLES
1016
NOTE:
1. STANDARD MODEL IS PIPED AT RIGHT SIDE. 3 STEAM HEATER INLET
100
2. LEFT SIDE PIPING LOCATION IS SYMMETRICAL
WITH RIGHT SIDE PIPING LOCATION.
2 CONDENSER WATER OUTLET
3.u IS SET ON BOARD.
4.TAKE HEIGHT MORE THAN THE STATIC
1 CONDENSER WATER INLET
PRESSURE IN DORAIN-TRAP OUTSIDE THE
PARTS NAME
NO.
MACHINE.
1
4
5
2665=1690
1780
6255=1530
27-φ4.7HOLES
BOTH SIDE
AIR INLET FRANGE
DETAIL OF AIR OUTLET FLANGE
154
Part A
62
55
214 190
1000
845
2665=1690
284
100
530
1050
20
USDP30GR
1210
35
1010
194
416
606
500
900
1565=775
2278=556
597
165
1320
AIR INLET FLANGE
523
665=390
M30
110
20
A DETAIL
110
0
φ6
9-φ4.7HOLES
BOTH SIDE DETAIL OF AIR OUTLET FLANGE
650
865=520
970
55
Part A
62
40
1550
20
7-φ4.7HOLES
BOTH SIDE
9
REAR
62
1780
1700
1960
94-φ4.7HOLES
2000
220
10-φ23HOLES
ANCHOR BOLT
108
62
50
AIR OUTLET FRANGE
2665=1690
180
50
HOLE FOR ANCHOR BOLT OF BOTTOM FRAME
FRONT
1760
10-φ10HOLES
1550
285
1206
724
3228=684
35
USDP40GR, 50GR
100
7
190
6
1
2
1800
1340
220
160
25
245
900
434
700
40
3
DETAIL OF AIR INLET FLANGE
100
5
8
485
20
11
190
151
214
4
1069
307
FRONT
REAR
600
NO.
PARTS NAME
1 CONDENSER WATER INLET
2 CONDENSER WATER OUTLET
3D010322G
REMARK
3B SGP [80A]
JIS5kg/cm2 FLANGE
3B SGP [80A]
JIS5kg/cm2 FLANGE
11/4B SGP [32A]
JIS5kg/cm2 FLANGE
3/4B SGP [20A]
JIS5kg/cm2 FLANGE
4 STEAM HEATER OUTLET
3 STEAM HEATER INLET
3/4B SGP [20A]
JIS5kg/cm2 FLANGE
1/2B SGP [15A]
5 STEAM SPRAY INLET
6 PIPING SAFTY VALVE
1B SGP [25A]
7 LOWER DRAIN OUTLET JIS5kg/cm2 FLANGE
11/4B SGP [32A]
8 UPPER DRAIN OUTLET JIS5kg/cm2 FLANGE
9 STARTER BOX
NOTE:
1. STANDARD MODEL IS PIPED AT RIGHT SIDE.
2. LEFT SIDE PIPING LOCATION IS SYMMETRICAL
WITH RIGHT SIDE PIPING LOCATION.
3.u IS SET ON BOARD.
4.TAKE HEIGHT MORE THAN THE STATIC
PRESSURE IN DORAIN-TRAP OUTSIDE THE
MACHINE.
600
MIN.SERVICE SPACE
500
900
8
348
USDP25GR
3D012771H
3. Wiring Diagrams
9
10
USDP30GR
3D012772H
11
USDP40GR, 50GR
3D012773J
Electric Parts List
Symbol
Parts Name
USDP25GR
USDP30GR
USDP40GR
2
Timing Relay
3X11
Magnetic Relay
3X12,2
Magnetic Relay
10-1,2,3,4
Timing Relay
23A1
Low Temp. Protection Thermostat
WTB-K602
26L1,L2
Freeze-up Protection Thermostat
DTB-K103
30FX11,21
Magnetic Relay
LY4F 100V(4c)
30FX12,22
Magnetic Relay
LY2F 100V(2c)
47
Reverse Phase Protector
49C1,2,3,4
Thermal Protector (Discharge Pipe)
52C1,2,3,4
Magnetic Contactor (Compressor)
52F
Magnetic Contactor (Fan)
63H1,2
High Pressure Switch
ACB-BB87
63L1,2
Low Pressure Switch
LCB-LA74
84
Magnetic Relay
A1
Ammeter
A2
Ammeter
BS
Push Button Switch
CT1
Current Transformer
CT2
Current Transformer
FuR
Fuse
FGB0 AC250V 5A
FuU
Fuse
UC1 AC500V 5A
GL
Pilot Lamp (Operation-Green)
MC1,2,3,4
Motor (Comp.)
MCCB1
Molded Case Circuit Breaker
MCCB2
Molded Case Circuit Breaker
MF
Motor (Fan)
MR
Motor Relay
RL1,2
Pilot Lamp (Alarm-Red)
SS1
Selector Switch (Heat-Cool)
BTN11-1
SS2
Selector Switch (No.1-No.2)
BTN11-1
TeS1
Terminal Strip
TeS2
Terminal Strip
KST20-12P(1-12)
TeS3
Terminal Strip
6P(13-18)
TeS4
Terminal Strip
KST20-12P(19-30)
TeS5
Terminal Strip
KST20-12P(35-46)
Tr
Transformer
WL
Pilot Lamp (Power-White)
Number of
use points
Number of
empty points
12
USDP50GR
H3CR-A(A mode 10Min)
LY4F 100V(4c)
LY2F 100V(2c)
H3CR-A(A mode 5 Sec)
RPJ-400V
UT12-3515K
CLK-50JTH-P12(2a2b)
CLK-35JTH-P6(1a1b) CLK-35JTH-P6(1a1b)
CLK-35J-P6(1a1b)
CLK-50J-P6(1a1b)
LY4F 100V(4c)
YS-208NAABR 0~30/5-90A
YS-208NAABR 0~20/5-60A
YS-208NAABR 0~60/5-180A
YS-208NAABR 0~75/5-225A
Y3K53E
CW-5LP 20/5A
CW-5LP 30/5A
CW-5L 60AT/5A
CW-5L 75AT/5A
R-KP61A
9.0kW 4P
7.5kW 4P
SA33B/3P30/30AT
EA53B/3P50/40AT
EA53B/3P50/50AT
EA103B-W/3P100/100AT
EA103B-W/3P100/75AT
7.5kW 4P
9.0kW 4P
15kW 4P
11kW 4P
––
K2CM-1M(20~65A)
R-KP62A RED
KT100-3JA
KT150-3JA
TP41-150VA
R-KP61A
Symbol
3X11
3X12
3X2
52C1
52C2
52C3
52C4
52F
84
a point
1
1
0
3
3
1
1
0
0
0
0
1
2
b point
2
0
0
1
1
0
0
0
0
0
0
0
2
a point
0
0
0
0
0
0
0
2
2
2
2
0
0
b point
0
0
0
0
0
0
0
2
2
2
2
1
0
c point
1
1
2
0
0
1
1
0
0
0
0
0
0
30FX11 30FX21 30FX12 30FX22
4. Electric Characteristics
Model
Volts
Phase
Hz
Compressor (each)
No.
380
USDP25GR
400
50
3
MRC
163
21
1
21
63
NRC
current
40.0
181
41.2
190
50
169
42.7
197
60
140
43.4
168
54.1
169
55.2
176
400
50
3
50
127
3
134
21
1
26
89
415
50
139
56.7
183
440
60
115
58.3
160
65.5
180
67.1
187
400
50
3
50
127
4
134
415
50
139
440
60
115
380
USDP50GR
MRC
155
2
Max. inrush
Total
No.
415
380
USDP40GR
Fan motor (each)
MRC
440
380
USDP30GR
50
LRA
400
50
3
50
21
1
34,
118
6 Sec
155
4
163
415
50
169
440
60
140
21
1
34,
6 Sec
118
68.8
194
70.9
173
79.7
217
80.6
227
85.9
238
86.2
207
Note:
1. Symbols: LRA : Locked Rotor Amps.
MRC: Max. Running Current
NRC : Total Nominal Running Current
2. Max. inrush current is the total of LRA for the compressor finally operated and MRC for the compressor(s) and the fan motor in operation.
13
5. Capacity Tables
5.1
Capacity Tables
USDP25GR
¡ Cooling Capacity [60Hz]
Entering
condenser
water temp.
Condenser
water
flow rate.
°C
R/min
14.0
20.0
24.0
28.0
32.0
38.0
180
275
300
350
180
275
300
350
180
275
300
350
180
275
300
350
180
275
300
350
180
275
300
350
°CW. B.
Suction air temp.
16.0
19.5
22.0
24.0
26.0
28.0
Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
65
68
69
70
64
68
69
70
63
66
67
68
61
65
65
66
59
63
64
64
57
60
61
62
24.2
22.2
21.7
21.2
25.8
23.7
23.2
22.7
26.8
24.7
24.2
23.5
28.0
25.8
25.2
24.6
29.3
26.9
26.4
25.7
31.4
28.8
28.3
27.6
74
79
80
81
74
78
79
80
72
76
77
78
70
74
75
76
68
72
73
74
65
69
70
71
25.3
23.3
22.9
22.3
27.1
24.9
24.4
23.7
28.2
26.0
25.4
24.8
29.5
27.0
26.5
25.9
30.7
28.3
27.7
27.0
33.0
33.3
29.7
28.9
81
86
87
89
81
86
87
88
80
84
85
86
78
81
82
84
76
80
80
81
73
77
78
79
26.3
24.2
23.6
23.1
28.1
25.9
25.3
24.7
29.3
26.9
26.3
25.7
30.5
28.1
27.5
26.3
31.9
29.4
28.7
28.0
34.1
31.4
30.7
30.0
89
94
95
96
88
93
94
96
86
91
92
93
84
88
90
91
81
86
87
88
79
82
83
85
27.2
25.1
24.6
24.0
29.2
26.8
26.3
25.5
33.3
27.9
27.3
26.6
31.6
29.2
28.5
27.8
33.1
30.4
29.8
29.0
35.4
32.6
31.9
31.2
97
102
104
105
96
102
103
104
94
99
100
102
91
96
98
99
89
94
95
96
85
90
91
92
28.0
25.8
25.2
24.6
29.9
27.5
26.9
26.2
31.1
28.6
28.0
27.3
32.4
29.8
29.3
28.5
33.9
31.2
30.5
29.8
36.4
33.4
32.8
31.9
106
112
113
114
105
111
113
113
102
108
110
111
100
105
107
108
97
102
104
105
93
98
100
101
28.7
26.4
25.9
25.2
30.6
28.2
27.6
26.9
31.9
29.4
28.7
28.0
33.3
30.6
30.0
29.3
34.8
32.0
31.4
30.5
37.3
34.3
33.6
32.8
Note) Cooling capacity at 60Hz.
Correction factors for capacity and power input, and bypass factor to change in air flow rate.
Change of condenser head loss to changes in water folw rate.
Air flow rate m3/min
110
120
130
140
150
160
170
Water flow rate
R/min
180
275
300
350
Capacity
Correction
factor
Power input
0.90
0.94
0.97
1.00
1.03
1.05
1.07
Head loss103Pa
10.2
19.8
20.7
24.1
0.96
0.98
0.99
1.00
1.01
1.02
1.03
Bypass factor
0.10
0.11
0.14
0.15
0.16
0.19
0.21
Limit of condenser water flow rate. (R/min)
Min.
Standard
Max.
180
300
350
AH005172A
14
¡ Fan Performance
:7.5kW
:3B291
:3B211
:B106
:110~170K/min
:1500rpm
2000
200
1800
180
150 0
120
Static Pressure (Pa)
Reference
140 0
140
r.p.m
1600
160
Note:
The Steam heater is a standard accessory.
Static Pressure (mmH2O)
Standard Motor Output
Standard Fan Pulley
Standard Motor Pulley
Standard Belt Size
Operable Range
Max. Fan Revolution Speed
7.5K
11K
W(
W
STA
ND
AR
D)
r.p.m
1400
130 0
r.p.m
60Hz STANDARD
1200
120 0
1000
100
0
110
r.p.m
r.p.m
50Hz STANDARD
80
800
60
600
40
400
STANDARD PRODUCT
(With one row of steam heater.)
20
200
0
0
120
140
Air flow Rate (m3/min)
160
4D010369A
¡ Heating Capacity of Steam Heater
:shows the datas at nominal conditions.
Models
kPa
USDP25GR
Entering Air Temperature
Steam
Pressure
0
5
10
°C.D.B.
15
Capacity Correction for Air Flow
Capacity Capacity Capacity Capacity
kW
kW
kW
kW
300
400
106
103
114
100
110
106
AFR: Air Flow Rate K/X
CF: Correction Factor
97
AFR
130
150
165
180
200
102
CF
0.86
0.94
1.0
1.05
1.13
Note: Allowable working pressure :600kPa
¡ Humidifying Capacity of Steam Spray
:shows the datas at nominal conditions.
Steam Pressure
Models
USDP25GR
kPa
20
30
35
40
Capacity
O/h
Capacity
O/h
Capacity
O/h
Capacity
O/h
23
28
30
32
Note: Allowable working pressure :40kPa
15
USDP30GR
¡ Cooling Capacity [60Hz]
Entering
condenser
water temp.
Condenser
water
flow rate.
°C
R/min
14.0
20.0
24.0
28.0
32.0
38.0
260
330
360
420
260
330
360
420
260
330
360
420
260
330
360
420
260
330
360
420
260
330
360
420
°CW. B.
Suction air temp.
16.0
19.5
22.0
24.0
26.0
28.0
Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
78
81
81
82
78
80
81
82
76
78
80
81
74
76
77
79
72
74
75
76
69
71
72
73
32.9
30.2
29.6
28.8
35.1
32.2
31.6
30.7
36.5
33.6
32.9
32.0
38.1
35.0
34.3
33.4
39.8
36.6
35.8
35.0
42.6
39.2
38.4
37.4
89
92
93
95
89
92
93
94
86
89
91
92
84
87
88
89
82
84
86
87
79
81
82
83
34.5
31.7
31.1
30.3
36.8
33.9
33.2
32.3
38.4
35.3
34.6
33.7
40.0
36.8
36.0
35.1
41.8
38.5
37.6
36.7
44.8
41.2
40.4
39.3
99
102
103
105
98
101
103
104
96
99
100
102
93
96
98
99
90
93
95
96
87
90
91
92
35.7
32.9
32.2
31.4
38.2
35.1
34.3
33.5
39.8
36.6
35.8
34.9
41.4
38.2
37.3
36.5
43.4
39.9
39.0
38.1
46.2
42.7
41.9
40.8
107
111
112
113
107
110
112
113
104
108
109
110
101
105
106
108
98
102
103
104
94
97
99
100
37.1
34.1
33.4
32.5
39.6
36.5
35.7
34.8
41.2
37.9
37.1
36.3
43.0
39.5
38.8
37.7
44.9
41.3
40.5
39.4
48.2
44.3
43.5
42.3
116
120
121
123
115
119
121
122
113
116
118
119
110
113
115
116
107
111
112
113
103
106
108
109
38.1
35.0
34.2
33.4
40.6
37.3
36.6
35.6
42.3
38.9
38.1
37.1
44.1
40.6
39.8
38.7
46.1
42.4
41.6
40.5
49.4
45.5
44.5
43.4
127
131
133
135
126
130
132
134
123
127
129
131
120
124
125
127
116
120
122
123
112
115
117
118
39.0
35.9
35.2
34.2
41.7
38.3
37.5
36.6
43.4
39.9
39.1
38.1
45.3
41.7
40.8
39.8
47.3
43.5
42.6
41.6
50.7
46.6
45.7
44.5
Note) Cooling capacity at 60Hz.
Correction factors for capacity and power input, and bypass factor to change in air flow rate.
Air flow rate m3/min
130
140
150
165
180
190
200
Correction
factor
Power input
0.91
0.94
0.96
1.00
1.03
1.05
1.07
0.97
0.98
0.99
1.00
1.01
1.02
1.02
Bypass factor
0.09
0.10
0.11
0.14
0.17
0.18
0.20
Capacity
Change of condenser head loss to changes in water folw rate.
Water flow rate
R/min
3
Head loss10 Pa
260
330
360
420
7.84
11.8
15.7
19.6
Limit of condenser water flow rate. (R/min)
Min.
Standard
Max.
260
360
420
AH005173A
16
¡ Fan Performance
:11kW
:3B291
:3B247
:B106
:130~200K/min
:1500rpm
Note:
The Steam heater is a standard accessory.
2000
200
1800
180
150 0
120
140 0
Static Pressure (Pa)
Reference
140
1400
1200
1300
1200
r.p.m
11K
W(S
TAN
DAR
7.5K
D)
W
r.p.m
r.p.m
50Hz STANDARD
1100
100
r.p.m
60Hz STANDARD
1600
160
Static Pressure (mmH2O)
Standard Motor Output
Standard Fan Pulley
Standard Motor Pulley
Standard Belt Size
Operable Range
Max. Fan Revolution Speed
r.p.m
1000
80
800
60
600
40
400
20
200
0
0
STANDARD PRODUCT
(With one row of steam heater.)
140
160
180
200
Air flow Rate (m3/min)
4D010365A
¡ Heating Capacity of Steam Heater
:shows the datas at nominal conditions.
Models
kPa
USDP30GR
Entering Air Temperature
Steam
Pressure
0
5
10
°C.D.B.
15
Capacity Correction for Air Flow
Capacity Capacity Capacity Capacity
kW
kW
kW
kW
300
400
132
128
142
125
137
132
AFR: Air Flow Rate K/X
CF: Correction Factor
120
AFR
110
125
140
155
170
126
CF
0.86
0.93
1.0
1.07
1.13
Note: Allowable working pressure :600kPa
¡ Humidifying Capacity of Steam Spray
:shows the datas at nominal conditions.
Steam Pressure
Models
USDP30GR
kPa
20
30
35
40
Capacity
O/h
Capacity
O/h
Capacity
O/h
Capacity
O/h
28
33
36
38
Note: Allowable working pressure :40kPa
17
USDP40GR
¡ Cooling Capacity [60Hz]
Entering
condenser
water temp.
Condenser
water
flow rate.
°C
R/min
14.0
20.0
24.0
28.0
32.0
38.0
340
440
480
560
340
440
480
560
340
440
480
560
340
440
480
560
340
440
480
560
340
440
480
560
°CW. B.
Suction air temp.
16.0
19.5
22.0
24.0
26.0
28.0
Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
103
107
108
109
102
106
107
109
100
103
105
106
97
101
102
103
94
98
99
100
90
94
95
96
39.9
36.7
35.9
35.0
42.6
39.1
38.4
37.4
44.3
40.7
40.0
38.9
46.2
42.5
41.7
40.6
48.3
44.4
43.6
42.4
51.8
47.6
46.6
45.5
118
122
123
125
117
121
123
124
114
118
119
121
112
115
116
118
109
112
113
114
104
108
109
111
41.9
38.5
37.7
36.8
44.7
41.1
40.3
39.3
46.5
42.8
42.0
40.9
48.5
44.7
43.8
42.7
50.8
46.7
45.8
44.6
54.4
50.0
49.1
47.8
130
135
137
138
129
134
136
138
126
131
132
134
123
127
129
131
119
123
125
127
114
118
120
122
43.5
40.0
39.1
38.2
46.3
42.6
41.8
40.7
48.2
44.4
43.5
42.4
50.4
46.3
45.4
44.2
52.6
48.4
47.4
46.2
56.4
51.9
50.9
49.6
142
146
147
149
141
146
147
149
137
142
144
146
134
138
140
142
130
134
136
138
124
129
130
132
45.1
41.4
40.6
39.5
48.1
44.2
43.4
42.3
50.0
46.0
45.1
44.0
52.3
48.0
47.1
45.9
54.6
50.2
49.2
47.9
58.5
53.8
52.7
51.4
153
159
161
163
152
158
160
162
149
154
156
158
146
150
152
154
141
146
147
149
136
140
142
144
46.2
42.5
41.6
40.6
49.3
45.4
44.4
43.4
51.3
47.2
46.2
45.1
53.5
49.3
48.2
47.1
56.0
51.5
50.5
49.2
60.0
55.2
54.1
52.7
168
173
176
178
167
172
175
177
163
168
170
173
158
164
166
168
154
159
161
163
147
152
154
157
47.4
43.6
42.7
41.7
50.6
46.5
45.6
44.4
52.7
48.4
47.5
46.2
55.0
50.6
49.5
48.2
57.5
52.8
51.7
50.5
61.6
56.6
55.4
54.1
Note) Cooling capacity at 60Hz.
Correction factors for capacity and power input, and bypass factor to change in air flow rate.
Air flow rate m3/min
175
190
205
220
235
250
260
Correction
factor
Power input
0.91
0.94
0.97
1.00
1.02
1.05
1.06
0.96
0.98
0.99
1.00
1.01
1.02
1.02
Bypass factor
0.09
0.12
0.13
0.14
0.16
0.17
0.19
Capacity
Change of condenser head loss to changes in water folw rate.
Water flow rate
R/min
340
440
480
560
9.8
13.7
16.7
20.6
3
Head loss10 Pa
Limit of condenser water flow rate. (R/min)
Min.
Standard
Max.
340
480
560
AH005174A
18
¡ Fan Performance
:11kW
:3B181
:3B247
:B97
:175~260K/min
:2650rpm
2000
26
00
25
200
00
240
0
r.p
.m
r.p
.m
r.p
.m
1800
180
230
0
1600
Note:
The Steam heater is a standard accessory.
160
60Hz STANDARD
r.p
.m
22
00
r.p
.
Static Pressure (Pa)
Reference
m
Static Pressure (mmH2O)
Standard Motor Output
Standard Fan Pulley
Standard Motor Pulley
Standard Belt Size
Operable Range
Max. Fan Revolution Speed
140
120
1400
21
00
r.p
.m
1200
20
00
r.p
.m
50Hz STANDARD
1000
100
800
80
60
600
40
400
20
200
STANDARD PRODUCT
(With one row of steam heater.)
0
0
180
260
220
Air flow Rate (m3/min)
4D010366B
¡ Heating Capacity of Steam Heater
:shows the datas at nominal conditions.
Models
kPa
USDP40GR
Entering Air Temperature
Steam
Pressure
0
5
10
°C.D.B.
Capacity Correction for Air Flow
AFR: Air Flow Rate K/X
CF: Correction Factor
15
Capacity Capacity Capacity Capacity
kW
kW
kW
kW
300
173
165
161
156
400
183
174
170
164
AFR
180
200
220
240
260
CF
0.89
0.94
1.0
1.06
1.11
Note: Allowable working pressure :600kPa
¡ Humidifying Capacity of Steam Spray
:shows the datas at nominal conditions.
Steam Pressure
Models
USDP40GR
kPa
20
30
35
40
Capacity
O/h
Capacity
O/h
Capacity
O/h
Capacity
O/h
36
44
48
51
Note: Allowable working pressure :40kPa
19
USDP50GR
¡ Cooling Capacity [60Hz]
Entering
condenser
water temp.
Condenser
water
flow rate.
°C
R/min
14.0
20.0
24.0
28.0
32.0
38.0
360
550
600
700
360
550
600
700
360
550
600
700
360
550
600
700
360
550
600
700
360
550
600
700
°CW. B.
Suction air temp.
16.0
19.5
22.0
24.0
26.0
28.0
Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input Capacity Power input
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
122
129
131
133
121
128
130
132
118
125
127
129
115
122
123
125
113
118
120
121
108
113
115
116
41.4
38.2
37.4
36.5
44.3
40.7
40.0
38.9
46.1
42.4
41.6
40.5
48.1
44.3
43.4
42.3
50.2
46.2
45.3
44.2
54.0
49.6
48.5
47.4
140
148
150
152
140
147
149
151
136
144
146
147
133
140
142
144
129
136
138
140
123
131
132
134
43.6
40.1
39.3
38.3
46.5
42.8
42.0
40.9
48.4
44.6
43.7
42.6
50.6
46.5
45.6
44.4
52.9
48.7
47.6
46.4
56.7
52.2
51.1
49.7
155
163
166
168
154
162
165
167
150
158
161
163
146
154
156
159
143
150
152
154
137
145
146
148
45.2
41.6
40.7
39.8
48.2
44.4
43.5
42.4
50.2
46.2
45.3
44.1
52.5
48.2
47.3
46.0
54.8
50.4
49.4
48.1
58.7
54.1
52.9
51.6
168
178
179
182
167
177
178
181
163
172
175
177
159
168
170
172
154
163
165
167
148
156
158
160
46.9
43.1
42.2
41.2
50.0
46.0
45.2
44.0
52.2
47.9
47.0
45.8
54.4
50.0
49.0
47.8
56.8
52.3
51.2
49.9
61.0
56.1
54.9
53.5
182
193
195
198
181
192
194
197
178
187
189
192
173
182
184
187
168
177
179
181
161
170
173
175
48.0
44.2
43.2
42.2
51.3
47.2
46.2
45.1
53.4
49.2
48.1
47.0
55.8
51.3
50.2
49.0
58.3
53.5
52.5
51.2
62.4
57.5
56.3
54.8
199
210
212
215
198
209
211
214
193
204
207
210
188
199
202
204
183
193
196
198
176
185
188
190
49.3
45.4
44.4
43.4
52.7
48.4
47.5
46.2
54.8
50.5
49.4
48.1
57.2
52.6
51.5
50.2
59.8
55.0
53.8
52.5
64.1
58.9
57.7
56.3
Note) Cooling capacity at 60Hz.
Correction factors for capacity and power input, and bypass factor to change in air flow rate.
Air flow rate m3/min
220
240
260
275
280
300
320
Correction
factor
Power input
0.91
0.95
0.98
1.00
1.01
1.03
1.05
0.96
0.98
0.99
1.00
1.00
1.01
1.02
Bypass factor
0.08
0.11
0.12
0.14
0.14
0.17
0.18
Capacity
Change of condenser head loss to changes in water folw rate.
Water flow rate
R/min
3
Head loss10 Pa
360
550
600
700
10.8
19.6
22.5
27.4
Limit of condenser water flow rate. (R/min)
Min.
Standard
Max.
360
600
700
AH005175A
20
¡ Fan Performance
:15kW
:3B181
:3B261
:B98
:220~320K/min
:2650rpm
2000
.m
.m
r.p
.m
r.p
r.p
00
50
00
25
26
26
200
1800
180
24
00
.m
r.p
1600
Note:
The Steam heater is a standard accessory.
60Hz STANDARD
160
1000
KW
11 KW
7.5
.m
r.p
Reference
.m
r.p
1200
00
21
Static Pressure (mmH2O)
D)
AR
ND W
TA 11K
(S
.m
r.p
00
20
100
22
120
W
00
K
15
23
1400
140
Static Pressure (Pa)
Standard Motor Output
Standard Fan Pulley
Standard Motor Pulley
Standard Belt Size
Operable Range
Max. Fan Revolution Speed
00
.m
r.p
50Hz STANDARD
800
80
60
600
40
400
20
200
0
220
0
STANDARD PRODUCT
(With one row of steam heater.)
260
300
320
Air flow Rate (m3/min)
4D010364A
¡ Heating Capacity of Steam Heater
:shows the datas at nominal conditions.
Models
kPa
USDP50GR
Entering Air Temperature
Steam
Pressure
0
5
10
°C.D.B.
Capacity Correction for Air Flow
AFR: Air Flow Rate K/X
CF: Correction Factor
15
Capacity Capacity Capacity Capacity
kW
kW
kW
kW
300
213
206
200
194
400
225
217
212
204
AFR
220
255
270
295
320
CF
0.89
0.97
1.0
1.06
1.12
Note: Allowable working pressure :600kPa
¡ Humidifying Capacity of Steam Spray
:shows the datas at nominal conditions.
Steam Pressure
Models
USDP50GR
kPa
20
30
35
40
Capacity
O/h
Capacity
O/h
Capacity
O/h
Capacity
O/h
46
56
60
64
Note: Allowable working pressure :40kPa
21
5.2
Operation Limit
40
Standard Point
30
25
20
Pull-Down Period
Continuous Operation
Cooling Water Inlet Temperature (°C)
35
15
10
10
15
20
30
25
Indoor Suction Temperature
35
(°CWB)
Note: 1. The above figure shows the range that the standard airflow rate
reduces down to 50%.
2. The above figure shows the range in the following standard
conditions.
USDP25GR USDP30GR USDP40GR USDP50GR
Water Flow Rate (50/60Hz) R/min
275/300
360/400
440/480
550/600
Air Flow Rate (50/60Hz) m3/min 140/140
185/185
220/220
255/270
4D013905
22
HPS
HP
φ19.1C1220T
1
φ31.8C1220T
HPS
D
S
2
φ22.2C1220T
T
φ38.1C1220T
φ19.1C1220T
USDP25GR
LPS
LP
L
φ22.2C1220T
REFRIGERANT CHARGE
M
T
3
2
1
SUCTION LINE
DISCHARGE LINE
D
STEAM LINE
WATER LINE
LIQUID LINE
S
RADIATOR TRAP
GAUGE
SAFETY VALVE
STOP VALVE
COMPRESSOR
FILTER
EXPANSION VALVE
DISTRIBUTOR
CONDENSER
L
T
LOW PRESSURE SWITCH
LPS
CHECK VALVE
FAN MOTOR
HIGH PRESSURE SWITCH
HPS
FAN
2
3
(11/4B) [32A]
(3/4B) [20A]
LOWER DRAIN OUTLET
(1B SGP) [25A] JIS 5K FLANGE
3D010323B
Note: Be sure to provide a drain trap on the drain piping.
(3/4B) [20A]
STEAM SPRAY STEAM HEATER INLET STEAM HEATER OUTLET
1
CONDENSER WATER INLET (2B SGP) [50A] JIS 5K FLANGE
CONDENSER WATER OUTLET (2B SGP) [50A] JIS 5K FLANGE
EMERGENCY FLUOROCARBON GAS OUTLET(1/2B SGP)[15A] OVAL FLANGE
UPPER DRAIN OUTLET
(1 1/4B SGP) [32A]
JIS 5K FLANGE
NAME
EVAPORATOR
M
SYMBOL
6. Piping Diagrams
23
1
φ19.1C1220T
HP
HPS
USDP30GR
φ31.8C1220T
D
T
S
φ19.1C1220T
2
LPS
φ22.2C1220T
LP
φ22.2C1220T
REFRIGERANT
CHARGE
L
HP
HPS
M
3
φ31.8C1220T
S
φ19.1C1220T
24
D
LPS
LP
T
REFRIGERANT
CHARGE
L
φ19.1C1220T
φ38.1C1220T
3
2
1
SUCTION LINE
DISCHARGE LINE
D
STEAM LINE
WATER LINE
LIQUID LINE
S
RADIATOR TRAP
GAUGE
THERMOMETER
SAFETY VALVE
STOP VALVE
FUSIBLE VALVE
COMPRESSOR
FILTER
EXPANSION VALVE
DISTRIBUTOR
CONDENSER
L
T
LOW PRESSURE SWITCH
LPS
CHECK VALVE
FAN MOTOR
HIGH PRESSURE SWITCH
HPS
FAN
3
(11/4B) [32A]
(3/4B) [20A]
LOWER DRAIN OUTLET (1B SGP) [25A] JIS 5K FLANGE
CONDENSER WATER INLET (3B SGP) [80A] JIS 5K FLANGE
3D010324D
STEAM HEATER INLET STEAM HEATER OUTLET
2
Note: Be sure to provide a drain trap on the drain piping.
(3/4B) [20A]
STEAM SPRAY
1
CONDENSER WATER OUTLET (3B SGP) [80A] JIS 5K FLANGE
EMERGENCY FLUOROCARBON GAS OUTLET(1/2B SGP)[15A] OVAL FLANGE
UPPER DRAIN OUTLET
(1 1/4B SGP) [32A]
JIS 5K FLANGE
NAME
EVAPORATOR
M
SYMBOL
25
1
D
φ31.8C1220T
HP
HPS
φ19.1C1220T
T
φ22.2C1220T
USDP40GR, 50GR
φ19.1C1220T
S
2
LPS
LP
REFRIGERANT
CHARGE
L
φ22.2C1220T
φ38.1C1220T
HP
3
HPS
4
D
S
M
LPS
LP
T
REFRIGERANT
CHARGE
L
3
2
1
SUCTION LINE
DISCHARGE LINE
D
THERMOMETER
STEAM LINE
WATER LINE
LIQUID LINE
S
RADIATOR TRAP
GAUGE
SAFETY VALVE
STOP VALVE
COMPRESSOR
FILTER
EXPANSION VALVE
DISTRIBUTOR
CONDENSER
L
T
LOW PRESSURE SWITCH
LPS
CHECK VALVE
FAN MOTOR
HIGH PRESSURE SWITCH
HPS
FAN
3
(11/4B) [32A]
LOWER DRAIN OUTLET (1B SGP) [25A] JIS 5K FLANGE
CONDENSER WATER INLET (3B SGP) [80A] JIS 5K FLANGE
3D010325C
(3/4B) [20A]
STEAM HEATER INLET STEAM HEATER OUTLET
2
Note: Be sure to provide a drain trap on the drain piping.
(3/4B) [20A]
STEAM SPRAY
1
CONDENSER WATER OUTLET (3B SGP) [80A] JIS 5K FLANGE
EMERGENCY FLUOROCARBON GAS OUTLET(1/2B SGP)[15A] OVAL FLANGE
UPPER DRAIN OUTLET
(11/4B SGP) [32A]
JIS 5K FLANGE
NAME
EVAPORATOR
M
SYMBOL
7. Installation
USDP25GR
6
4
3
15
8
9
11
7
10
5
12
14
2
1
13
1
Compressor
7
Steam Spray
13
Safety Valve for Cond.
2
Condenser
8
Starter Box
14
Air Filter
3
Evaporator
9
Control Panel
15
Grease Nipples
4
Fan
10
Pressure Gauge
5
Fan motor
11
Thermostat Box
6
Steam Heater
12
Expansion Valve
3D018688
USDP30GR
26
1
Compressor
7
Steam Spray
13
Safety Valve for Cond.
2
Condenser
8
Starter Box
14
Air Filter
3
Evaporator
9
Control Panel
15
Grease Nipples
4
Fan
10
Pressure Gauge
5
Fan motor
11
Thermostat Box
6
Steam Heater
12
Expansion Valve
3D014780
USDP40GR, 50GR
4
8
6
3
9
15
11
10
7
12
5
14
2
1
13
1
Compressor
7
Steam Spray
13
Safety Valve for Cond.
2
Condenser
8
Starter Box
14
Air Filter
3
Evaporator
9
Control Panel
15
Grease Nipples
4
Fan
10
Pressure Gauge
5
Fan motor
11
Thermostat Box
6
Steam Heater
12
Expansion Valve
3D014781
27
8. Installation Instruction
Warning
¡ Request the installation to the dealer you purchased.
Otherwise it will cause water leak, electric shock and
fire, if you yourself will carry out the installation and
there will be improper works.
¡ Contact the dealer you purchased for the refrigerant
leaks countermeasure.
When unit is installed in a small room, certain
countermeasures are required so that the density of
the refrigerant should not exceed the
permissible density, even if the
refrigerant leaks.If refrigerant leaks
and will be beyond the permissible
density, it may cause an accident with a
short of oxygen.
Caution
¡ Do not install units in a place where there may be
possible leak of a combustible gas.
If the gas leaks and remains around
the units, it may happen to be
ignited.
¡ Grounding wire connection
If a grounding work is not properly done, it
may cause electric shock.
¡ Install a short circuit breaker.
Otherwise, it may cause electric
shock.
¡ Install drain pipes so that the drain can
securely flow out.
Otherwise, it may cause water leak.
Make sure the following instructions so as to operate the unit perfectly and comfortably. If something
inconvenient will be found, be sure to use the unit after it will be amended.
¡ Is the sufficient distance provided to the obstacles around
the unit?
¡ Is the power line only for the use of the airconditioner?
If the power supply line is used together with other electric
equipment, it may cause to cut the breaker or fuse.
¡ Is it not afraid to injure wiring or piping?
¡ Is the unnatural force loaded on the wiring connected in the
field(including grounding wires)?
¡ Is the wiring connected in the field clamped(including
ground wires)?
28
¡ Is the unit installed on the place sufficiently endurable
for the weight of airconditioner? Is the unit fixed tightly with
the foundation bolts onto the floor?
If the bolts are loosened or removed, it will cause noise or
vibration, and unnatural force will be loaded on the piping
or wiring.
¡ Is a drain trap provided on the drain piping?
Unless a trap with the head more than negative pressure is
provided, drainage failure may happen and cause a water
leak.
Carrying in
¡ When hanging up the unit, use the
suspension bolts (Fig 1)and pay
attention to carry out it safely.
Fig 1
B
110
φ 60
C
110
A
D
55
Size
M30
Rope angle θ > 45°
Installation
1. Fix the bottom frame of the unit onto
the foundation with the foundation
bolts(Fig 2).
2. Make the horizontal foundation so as to
be endurable against the unit weight.
3. Select the location of installation based
on the easiness of the drain streaming
out.
4. Attach the piping onto the safety valve
in order to release the gas into the air.
Fig 2
Location of foundation bolt holes on the bottom frame.
Applied
USDP25GR USDP30GR USDP40GR,50GR
models
A
1700
B
1960
C
125
D
F
5. Provide a space around the unit for the
air suction and for maintenance and
service work (Fig 3).
1550
1000
E
20
1760
1210
G
10
H
22
Space for maintenance and air suction
Fig 3
Maintenance space
Air suction space
Air outlet
Air suction
Fig 4
6. When two units will be installed,
provide a space as shown in Fig 4.
7. Equip a remove-free canvas duct onto
the air outlet as a rule.
29
Drain Piping
Be sure to provide a trap on each drain outlet.
That is why the trap will prevent not only the induction of bad smell but also slow action of drain stream
caused by the negative pressure inside the airconditioner during operation.
An example of drain trap installation is shown below.
"Head corresponding to the negative pressure" in the Figure stands for the head corresponding to the
negative pressure arisen in the airconditioner.
Drain at upper part
Drain at lower part
More than the head corresponding
to the negative pressure.
More than the head corresponding
to the negative pressure.
More than the head corresponding
to the negative pressure.
Drain trap
More than the head corresponding
to the negative pressure.
Thermostat
The thermostat(23A1) built in the unit USD(P)~GR is provided as a low temperature protector. Accordingly,
the thermostat should not be used for indoor temperature control. Provide a room thermostat or a
thermostat(23A2) in the return duct in the local field so as to control temperature.
[Location]
¡ Provide a temperature sensor in the return duct or around the inlet part of the return duct flowing into the
room.
¡ Select the location where direct sunshine, chilled air, heated air, and other radiation heat don't influence
the sensor.
¡ Refer to the electric wiring diagram concerning the wiring works.
[Note for the thermostat selection]
¡ Select the thermostat with the differential by 2°C or more, and not to act ON/OFF in a short time.
Caution for the condenser maintenance
(1) Regulate the water flow.
If the water flow rate (water velocity) exceeds the specified amount, tubes can be damaged in a short
time. Control the water flow to maintain the following guidelines.
¡ Condensing temperature : 30°C or higher.
¡ Temp. difference of in- and outlet : 3°C or higher.
(2) Replace the zinc plates.
In order to make the condenser last longer, check the zinc plates for corrosion protection every 3 months.
If worn out, make sure to replace it.
When checking, be sure to turn off the power source of pump.
(3) Cleaning the condenser cooling tubes.
Clean the cooling tubes if necessary.
30
9. Appendix
9.1
Vibration and Sound Level
The following data are not guaranteed value but reference one.
Vibration Level
3 Phase AC 440V 60Hz Unit : µ
Power Source 3phase
q
w
Z
X
Y
Z
X
Y
Z
X
Y
Z
USDP25GR
9
10
4
9
9
5
9
9
4
11 10
6
USDP30GR
10 10
5
9
10
5
10 11
5
13 11
7
USDP40GR
25 24
5
20 20
5
11 11
5
14 14
7
USDP50GR
30 28
6
22 23
5
13 13
6
14 15
8
¡ Location of Microphone
380V 50Hz
(
Suction
1m
)
Duct Connecting,
Microphone
Front
Standard Air Flow Rate and Standard External
1m
On the
r
Y
440V 60Hz
Outlet
e
X
Model
Sound Level
¡ Operating Condition
Position
Direction
Static Pressure
4D015756A
Measuring Place Anechoic Chamber
Note:
Operation noise differs with operation and ambient conditions.
(Conversion Data)
¡ Over All (dB)
Models
Scale
USDP25GR
60Hz
50Hz
Ventilation
Cooling
Ventilation
Cooling
A
78
78
76
77
USDP30GR
A
79
80
77
78
USDP40GR
A
80
81
78
79
USDP50GR
A
82
83
80
81
B.G.N. is already rectified.
31
USDP30GR
OCTAVE BAND SOUND PRESSURE LEVEL dB (0dB=0.0002bar)
OCTAVE BAND SOUND PRESSURE LEVEL dB (0dB=0.0002bar)
USDP25GR
Approximate
threshold hearing
for continuous
noise
Approximate
threshold hearing
for continuous
noise
OCTAVE BAND CENTER FREQUENCY (Hz)
OCTAVE BAND CENTER FREQUENCY (Hz)
4D015757A
4D015756A
USDP50GR
OCTAVE BAND SOUND PRESSURE LEVEL dB (0dB=0.0002bar)
OCTAVE BAND SOUND PRESSURE LEVEL dB (0dB=0.0002bar)
USDP40GR
Approximate
threshold hearing
for continuous
noise
Approximate
threshold hearing
for continuous
noise
OCTAVE BAND CENTER FREQUENCY (Hz)
OCTAVE BAND CENTER FREQUENCY (Hz)
4D015758A
4D015759A
60Hz Cooling
50Hz Cooling
60Hz Ventilation
50Hz Ventilation
32
9.2
Gist of Piping Connection Flexibility
This manual indicates the gist that the standard piping direction of the deck unit with rightward connection
will be changed to the opposite direction with leftward connection.
Cooling Water Piping
[Work Procedure]
1. Remove the front and rear cover of the condenser from the
right and the left.
2. Exchange the front cover with the rear cover together with
the packing.
3. Tighten up the covers with bolts.
Note:
Just move the covers horizontally to
each other and don't revolute it upside
down.
4. Tighten up the header with bolts and that's all.
Drain Piping
1) Upper drain piping
[Work Procedure]
Exchange the mating flange in the right with the blind flange in
the left.
2) Below drain piping
[Work Procedure]
1. In case of rightward connection, screw up the short drain
pipe straight to the right side face.
(Use white seal tape on the screw part)
2. In case of leftward connection, remove the left blind cap to
screw up the blind cap to the right.
For the next step, screw up the attached short drain pipe to
the left to finish.
(Use white seal tape on the screw part)
Note:
1. The short drain pipe is accessories part and not to be screwed in
the main unit inherently.
2. The blind cap is attached just in the left side and not attached in
the right side.
33
Relief Gas Piping on Safety Valve
[Work procedure]
Exchange the right side mating flange with the left side blind
flange.
Piping for Steam Heater and Steam Spray.
[Work procedure]
1. Remove the glass fibers in the pass of rightward piping.
2. Remove the short drain pipe at each outlet/inlet piping by
means of a piping wrench. (the short pipe is set to be
screwed).
3. Since the part the piping passes through in the left side
panel is structured as knock punch hole, knock it off.
4. Dismantle the exterior panels in the right and left
7. Restore the exterior panel in the right and left.
8. Wind the glass fibers around the short drain pipe which was
removed, up to the position of 80 mm ~ 90 mm from the
flange face and fix it securely with brass wires. (so that the
steam piping will not touch the casing).
9. Screw the short pipe for piping connection into the left.
10. Attach the blind rubber bush onto the opening in the right
exterior panel(for the prevention of air leakage).
Refer to the next page for the blind rubber bush's size.
Besides, purchase the rubber bush independently.
5. Since the blind plug is screwed in at the left side steam
piping connection, remove it.
6. Screw up the blind plug into the right side piping connection
where the short drain pipe was removed.
34
Note:
When screwing up the blind plug and the pipe for the
connection, wind up the white seal tape on the screw part.
Gist of Heater's Enclosure
List of Blind Rubber Bush
Models
USDP25GR, 30GR, 40GR,
50GR
Hole's diameter in panel
φ 70a
Applied blind rubber bush
Parts No.
Steam heater inlet
Applied piping
RB2-52
355007
Steam heater outlet
φ 61a
RB2-43
355006
Steam spray inlet
φ 53a
RB2-36
355005
35
9.3
Steam Valve Panel
Model
(Reference) When steam valve is produced, Produce it in accordance with this drawing.
Application
USDP25GR, 30GR
USDP40GR, 50GR
1 Marine bronze angle valve
JIS F7302 5K 40A1, 20A1
50A1, 25A1
Parts
2 Needle valve
3 Thermal control valve
4 Strainer
5 Pressure gauge and manual cock
6 Trap
Pressure gauge
10K 20A2
Danfoss
TLV Y3 type
IVTIVR251
25A1, 20A1
capillary length (4m)
40A1
CT type 6K & JIS F7343 3/81
50A1
TLV J5N4 25A1
FUSHIMAN S2 1/2B1
TLV J5N4 20A1
FUSHIMAN S2 1/2B1
CT type 6K1
For USDP25GR, 30GR
For USDP40GR, 50GR
Note:
1. Type with leftward piping is quite symmetrical left and right.
Double dotted line shows the main deck unit.
2. Do not install the steam valve panel separately, but on the
side of the main deck unit.
Do not install the thermo sensor of temperature control in a
place with violent temperature fluctuations.
If the panel must be separately set up, be sure to support and fix
the steam heater inlet and outlet pipes tightly at the main deck
unit.
36
9.4
Specifications of Main Structural Parts & External Drawings
Compressor
Type
JT335DDFYE
JT300DDFYE
USDP25GR
USDP50GR
USDP30GR
USDP40GR
kW
9
7.5
cc/REV
184.2
Models
Rated power output
Displacement
Rated speed
r.p.m
DAPHNE FVC68D
Refrigeration oil
Charged oil volume
163.0
2900/3450
R
2.7
R404A
Refrigerant
Connection at suction
φ 31.8 I.D.
Connection at discharge
φ 19.1 I.D.
Weight (except lubricant)
Capacity control
O
68
––
Finished color
Black
Power supply
3phase 50/60Hz
Voltage
380~415/400~440
37
Condenser
¡ Specifications
Products model name
CXS1919B-7R
Heat transfer area in refrigerant side
USDP40GR, USDP50GR
USDP30GR
USDP25GR
Condenser model name
CXS1919B-7R
m2
10.3
48
24
Pass number
CXS1919B-8R
20.5
2
Number
Cooling tube
CXS1919B-7R
CXS1919B-9R
20.5
Diameterthickness
48
φ15.88t1.2
Refrigerant
R404A
Unit number
1
Holding water volume
R
15.5
9.0
15.5
Dry weight (approx.)
kg
140
120
140
q Front cover
w Rear cover
e Front cover packing
r Rear cover packing
t Tube plate
y Shell
u Cross fin tube assembly
i Refrigerant distribution plate
o Refrigerant inlet tube
!0 Refrigerant outlet header
!1 Refrigerant outlet tube
!2 Safety valve connection base
!3 Feet
!4 Corrosion protection iron piece
!5 Circular liquid indicator(Dia. 27)
!6 Blind cap
370
4
16
5
7
100
15
12
9
1
8
176
209
3
36°
14
114
14
70 70
2
6
10
11
97
1150
215
1310
740
13
1900
1007
A distance in between the tube plates
1070
Note:
The location of the circular liquid indicator is different in model to model.
38
Fan Motor
¡ USDP25~50GR
¡ Specification
Applied model
USDP25GR
USDP30GR,40GR
Toshiba Corp.
Manufacturer
FBK8
Type
Output
Time rated
7.5kW
11kW
15kW
Continuous
Continuous
Continuous
Pole number
Frame number
Insulation class
Bearing number
4P
4P
4P
132M
160M
160L
Class B
Class B
Class B
Coupling side
6308
6310
6310
opposite to the coupling
6208
6208
6208
40°C
Surrounding temperature
JP44
Protection system
According to the external drawings
Revolution direction
kg
Approximate weight
76
109
V
Voltage
Ratings
USDP50GR
131
380,400,415/400,440
Frequency
Hz
Revolution
rpm
1425-1445/1730,1740
1430-1440/1730,1740
1430-1440/1730,1740
A
16.2,15.9,16.3/14.1,13.5
21.9,21.4,21.3/20.3,18.7
29.5,28.8,28.8/27.3,25.3
Current
50/60
Note: Above data is shown in the name plate.
USDP
Revolution direction
¡ Dimension Table
Dimension
mm
Applied models
Power
output
A
B
C
D
E
F
G
H
I
J
L
M
N
R
Z
XB
JK
USDP25GR
7.5kW
229
171
132
285
108
89
15
274
320
50
487
260
213
258
12
89
5
USDP30GR
USDP40GR
11kW
280
205
160
324
127
105
18
322
368
60
603
308
250
323
14.5
108
8
USDP50GR
15kW
302
227
160
324
127
127
18
322
368
60
647
308
294
345
14.5
108
8
Dimension
Applied models
Power
output
mm
Terminal box
Shaft end
KD
KE
KG
KL
Q
QK
QR
S
W
T
U
USDP25GR
7.5kW
35
182
112
212
80
63
0.5
38
10
8
5
USDP30GR
USDP40GR
11kW
52
227
120
280
110
90
2
42
12
8
5
USDP50GR
15kW
52
227
120
280
110
90
2
42
12
8
5
39
Evaporator, Heater
Models
USDP25GR
Evaporator
Cooling Tube
USDP30GR
Copper Tube (mm)
RowStageF.P.
Heater
USDP50GR
φ 9.5
4382.0
4381.8
4482.0
4481.8
Face Area (m )
1.65
1.65
2.08
2.08
Effective Length (m)
1.70
1.70
1.70
1.70
2
Fin Type
Waffle Fin
Heart Transmission Tube
Bare tube
Copper Tube (mm)
RowStageF.P.
φ 15.9
1244.0
1243.5
1313.5
1313.0
Face Area (m )
1.43
1.43
1.904
1.904
Effective Length (m)
1.60
1.60
1.60
1.60
2
Fin Type
40
USDP40GR
Internally processed tube
Flat Fin
9.5
Gist to Mount The Mixing Box
When mounting the mixing box onto the standard deck unit, the mixing box should be mounted by
adjusting to the part of the air filter chamber on the back.
Note:
1. The dimension with the mark * should be adjusted to the main unit.
2. The location to connect a return duct and a fresh air duct should be based on the location where each air can be
sufficiently mixed while referring to the part shown in the drawing.
RA---- Return air connection
FA---- Fresh air connection
41