MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 SECTION 27 13 00 - COMMUNICATIONS BACKBONE CABLING PART 1 - GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. Specifications throughout all Divisions of the Project Manual are directly applicable to this Section, and this Section is directly applicable to them. 1.02 SUMMARY Section Includes: 1. Backbone Cabling Description 2. Products Installation of Cables 1.03 REFERENCE STANDARDS See Section 27 05 10 or 27 05 20. 1.04 SCOPE OF WORK Add T-drawing numbers for Communication Design drawings Add scope of project. 1.05 BACKBONE CABLING DESCRIPTION Backbone cabling system shall provide interconnections between communications equipment rooms, telecommunication rooms, main terminal space, and entrance facilities in the telecommunications cabling system structure. Cabling system consists of backbone cables, intermediate and main cross-connects, mechanical terminations, and patch cords or jumpers used for backbone-to-backbone cross-connection. Backbone cabling cross-connects may be located in communications equipment rooms or at entrance facilities. Bridged taps and splitters shall not be used as part of backbone cabling. Color designations for type fiber cable: 1. Single Mode fiber > Yellow 2. Multi Mode fiber 62.5 micron > Orange 3. Multi Mode fiber 50 micron 1GB > Orange 4. Multi Mode fiber 50 micron 10GB > Aqua The University of Texas MD Anderson Cancer Center MS060310 COMMUNICATIONS BACKBONE CABLING 27 13 00 1 OF 5 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 Color and cable type designations for UTP and F/UTP cable: 5. Voice Riser: UTP CAT3 (minimum) > White 6. Nurse Call System Riser: F/UTP CAT5e (minimum) > Purple PART 2 - PRODUCTS 2.01 GENERAL All materials shall meet or exceed all applicable referenced standards, federal, state and local requirements, and conform to codes and ordinances of authorities having jurisdiction. 2.02 MANUFACTURERS The system must be a manufacturer certified System. Current approved manufacturer: Siemon or allies of Siemon. 2.03 SUBMITTALS See Section 27 05 10 or 27 05 20. 2.04 UTP CABLE 24 AWG CAT 3 (or higher rated) plenum riser cable (minimum of 25 pair). Substituted if required by local fire codes. 1. Manufacturers: Siemon, Berk-Tek, General Cable, Mohawk, Superior Essex (Allies for cable only, not for other hardware) 2.05 UTP CABLE HARDWARE Riser cable shall be terminated on Cat3 or higher rated patch panels. Horizontal wire management shall be mounted horizontally between patch panels. Cables will be terminated in numerical order starting with the smallest number. Manufacturer: Siemon 1. Siemon #HD5-96 per 100 pair cable. 2.06 OPTICAL FIBER CABLE (ISP) The optical fiber shall be 12 strands OM3 Multi Mode 50/125um core/cladding diameter and 12 strands OS2 low water-peak single mode 8.3/125um core/cladding diameter. 1. Manufacturer: Siemon, Berk-Tek, General Cable, Mohawk (Siemon part numbers are listed as reference of performance if other manufacturer is chosen and approved by Owner and Siemon) a. MM Fiber - #9BC5P012G-T312A 1) Replace with #9BC5P012G-T512A where distances exceed 300m. The University of Texas MD Anderson Cancer Center MS060310 COMMUNICATIONS BACKBONE CABLING 27 13 00 2 OF 5 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 b. SM Fiber - 9BC8P012G-E205A The optical fiber cable must be Optical Fiber Conductive Plenum rated or as required. The optical fiber must be FDDI and ATM compliant and conform to all relevant ANSI and EIA/TIA standards. Non-Conductive cable shall be aluminum armored type. 2.07 OPTICAL FIBER CABLE HARDWARE Optical fiber connectors shall be ”fusion-spliced pigtails” with SC connector. 1. Manufacturer: Siemon a. MM - #FP1B-SC5L-01AQ b. SM - #FP1B-SCUL-01 c. Splice Tray - #TRAY-3 d. Splice Protector - #HT-60 Interconnect Units for Telecommunication Rooms shall be 2U rack mounted fiber patch panels, equipped with double density, SC Duplex compatible optical fiber adapter strips (coupler panels). 2. Manufacturer: Siemon a. Cabinet - #RIC3-24-01 b. SC Adapter Plate – RIC-F-SC12-01 c. Blank Adapter Plate – RIC-F-BLNK-01 Interconnect Units for the Equipment Rooms shall be 3U Shelf, equipped with SC duplex Connector Modules. 3. Manufacturer: Siemon a. Cabinet - #RIC3-72-01 b. SC Adapter Plate – RIC-F-SC12-01 c. Blank Adapter Plate – RIC-F-BLNK-01 2.08 OPTICAL FIBER CABLE (OSP) OSP Armored Fiber Optic Cable 1. Manufacturer: Draka and Siemon a. Multi-mode – OM3 50 micron b. Single-mode – OS2 Low water-peak The University of Texas MD Anderson Cancer Center MS060310 COMMUNICATIONS BACKBONE CABLING 27 13 00 3 OF 5 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 PART 3 - EXECUTION 3.01 GENERAL Installation shall meet or exceed all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of authorities having jurisdiction. All installation shall be in accordance with manufacturer’s published recommendations. Copper cables shall be terminated with connecting hardware of same category or higher. Install plenum cable in environmental air spaces, including plenum ceilings. 3.02 INSTALLATION OF CABLES General Requirements for Cabling: 1. Terminate all conductors; no cable shall contain un-terminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels. 2. Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 3. Install lacing bars to restrain cables consistently, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer. 4. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii. 5. Use Velcro tie wraps. 6. Do not install bruised, kinked, scored, deformed, or abraded cable. Remove and discard cable if damaged during installation and replace it with new cable. 7. Cold-Weather Installation: Follow manufacturer specifications for installation and storage temperatures. Heat lamps shall not be used for heating. 8. In the communications equipment room, install a 10-foot service loop for backbone cabling on each end of cable. 9. Pulling Cable: Do not exceed manufacturer recommended maximum cable pull tensions. UTP Cable Installation: 10. Do not untwist UTP cables more than 1/2 inch from the point of termination to maintain cable geometry. Optical Fiber Cable Installation: 11. Cable may be terminated on connecting hardware that is rack or cabinet mounted. 12. The metal armor of the optical fiber cable must be grounded. Open-Cable Installation: The University of Texas MD Anderson Cancer Center MS060310 COMMUNICATIONS BACKBONE CABLING 27 13 00 4 OF 5 MDACC Project No. 08-2123 Page Southerland Page PSP Project No. 408370.10 Expansion of Patient Room Services Kitchen Addendum No. 01 May 28, 2010 13. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment. 14. Suspend UTP cable independently from “Other Trades” and not in a wireway or pathway, a minimum of 8 inches above ceilings by cable supports not more than 60 inches apart. 15. Cable shall not be run through or supported from structural members or in contact with pipes, ducts, or other potentially damaging items. Group connecting hardware for cables into separate logical fields. END OF SECTION 27 13 00 The University of Texas MD Anderson Cancer Center MS060310 COMMUNICATIONS BACKBONE CABLING 27 13 00 5 OF 5