www.eaton.eu xEffect - Industrial Switchgear Range Catalogue 2013 www.eaton.eu Digital protection switches – a new era has begun. Numerous advantages at a glance Better security with proactive communication! The digital RCCB from Eaton’s xEffect series are capable to do more than just switch off: They monitor electrical installations and issue advance warnings of critical current flows. Thanks to short time delay and optimized tripping threshold, briefly occurring malfunctions do not induce the digital protection switch to shut down. • Ideal for system monitoring thanks to preventive information • Continuous monitoring of plant/factory status • Clear status display with tri-colored LEDs When a fault current crops up, the information is reported to the security center of the industrial plant right away and troubleshooting can start before a plant failure occurs. Thus the cause of the fault current can be determined precisely and the system can be serviced easily. That way, system availability increases and service is crucially improved by the convenient remote control. • Longer intervals between servicing • As easy to install as a conventional RCCB The new xEffect Digital Series Residual Current Devices Residual Current Devices - General Data Short description of the most important RCD types: Symbol Description Eaton standard. Suitable for outdoor installation (distribution boxes for outdoor installation and building sites) up to -25° C. Conditionally surge-current proof (>250 A, 8/20 µs) for general application. RCD sensitive to pulsating DC for application where residual pulsating DC may occur. Non-selective, instantaneous. Protects only against special forms of residual pulsating DC which have not been smoothed. Type B: All-current sensitive RCD switchgear for applications where DC fault currents may occur. Non-selective, non-delayed. Protection against all kinds of fault currents. Type B+: All-current sensitive RCD switchgear for applications where DC fault currents may occur. Non-selective, non-delayed. Protection against all kinds of fault currents. Also meets the requirements of the VDE 0664-400 standard (formerly known as VDE V 0664-110) and therefore provides enhanced fire safety. G ÖVE E 8601 S RCD of type G (min 10 ms time delay) surge current-proof up to 3 kA. For system components where protection against unwanted tripping is compulsory to avoid personal injury and damage to property (§ 12.1.6 of ÖVE/ÖNORM E 8001-1). Also for systems involving long lines and high line capacity. Some versions are sensitive to pulsating DC. Some versions are available in all-current sensitive design. RCD of type S (selective, min 40 ms time delay) surge current-proof up to 5 kA. Mainly used as main switch according to ÖVE/ÖNORM E 8001-1 § 12.1.5, as well as in combination with surge arresters.This is the only RCD suitable for series connection with other types if the rated tripping current of the downstream RCD does not exceed one third of the rated tripping current of the device of type S. Some versions are sensitive to pulsating DC. Some versions are available in allcurrent sensitive design. "X-ray-proof", for avoiding unwanted tripping caused by x-ray devices. “röntgenfest” "umrichterfest" "Frequency converter-proof", for avoiding unwanted tripping caused by frequency converters, speed-controlled drives, etc. Chapter 2.1.1. – 1 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Tripping Characteristics (IEC/EN 61008) Tripping characteristics, tripping time range and selectivity of instantaneous, surge current-proof "G" and surge current-proof - selective "S" residual current devices. Tripping time t surge current.proof - selective surge currentproof conditionally surge currentproof Residual tripping current Tripping time range limit values Tripping time range type S Tripping time range non-delayed Tripping time range type G Area of unwanted tripping § 6.1.1 of ÖVE/ÖNORM E 8001-1/A1 deals with additional protection and provides essentially the following: In circuits with sockets up to 16 A with fault current/residual current protection by protective earthing, protective multiple earthing or residual current devices (RCDs), additional residual current protection devices with a rated tripping current of 0.03 A must be installed. This means when using RCDs for fault current/residual current protection two RCDs must be connected in series. Testing: RCDs with tripping time delay (Types -G and -S) may be function tested with conventional testing equipment which must be set according to the instructions for operation of the testing device. Due to reasons inherent in the measuring process, the tripping time determined in this way may be longer than expected in accordance with the specifications of the manufacturer of the measuring instrument. However, the device is ok if the result of measurement is within the time range specified by the manufacturer of the measuring instrument. Chapter 2.1.1. – 2 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Hints for the application of our frequency converter-proof RCDs: Due to the currents flowing off through the filters (designated IF), the sum of currents through the RCD is not exactly zero, which causes unwanted tripping. Frequency converters are used in a wide variety of systems and equipment requiring variable speed, such as lifts, escalators, conveyor belts, and large washing machines. Using them for such purposes in circuits with conventional residual current devices causes frequent problems with unwanted tripping. Motor Screened motor line The technical root cause of this phenomenon is the following: Fast switching operations involving high voltages cause high interference levels which propagate through the lines on the one hand, and in the form of interfering radiation on the other. In order to eliminate this problem, a mains-side filter (also referred to as input filter or EMC-filter) is connected between the RCD and frequency converter. The antiinterference capacitors in the filters produce discharge currents against earth which may cause unwanted tripping of the RCD due to the apparent residual currents. Connecting a filter on the output side between frequency converter and 3-phase AC motor results in the same behaviour. Motor Mains side filter Frequency converter Frequency converter Mains-side filter Mains-side filter RCD RCD Mains Tripping characteristic This sample tripping characteristic of a 100 mA RCD and a 300 mA RCD shows the following: In the frequency range around 50 Hz, the RCDs trip as required (50 - 100 % of the indicated IΔn). In the range shown hatched in the diagram, i. e. from approx. 100 to 300 Hz, unwanted tripping occurs frequently due to the use of frequency converters. Frequency converter-proof residual current devices are much less sensitive in this frequency range than in the 50 - 60 Hz range, which leads to an enormous increase in the reliability of systems. Frequency converter interference range (approx. 100 - 300 Hz) Therefore, we recommend to use frequency converter-proof RCDs! These special residual current devices can be recognised by an extension of the type designation ("-U"). They meet the requirements of compatibility between RCDs and frequency converters with respect to unwanted tripping. These are NOT AC/DC-sensitive RCDs of type B !!! Our RCDs of type "-U" are characterised by SENSITIVITY TO RESIDUAL PULSATING DC and SELECTIVITY S or SHORT-TIME DELAY G . Protective Measures The following rules for the application of RCDs of type" -U" are only applicable in those cases where an RCD of type "-B" is not explicitly demanded in the instructions of the manufacturer of the frequency converter. How can you make sure that the required protective measures are in place when using RCDs type “-U” and frequency converters in one system? In Austria, the ÖVE Decision EN 219 is applicable. In Germany, VDE 0100 is applicable, in Switzerland SEV 1000. Under this standard In case of application in any other country than those mentioned take into account national rules and recommendations. • frequency converters must be equipped with current limiting devices in order to ensure disconnection in cause of faults or overload, and • the installer of a system is obliged to make sure that additional equipotential bonding is provided (additional inclusion of all metal components, such as frequency converters, mains filters, motor filters, etc. into the existing equipotential bonding), in order to ensure that the permissible touch voltage of 50 V AC or 120 V DC is not exceeded. (In ÖVE/ÖNORM E 8001-1 the term "touch voltage" has been omitted. There is only a fault voltage limit of 65 V AC or 120 V DC which must not be exceeded). Chapter 2.1.1. – 3 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCdM Digital SG49712 • Line voltage independent RCCB for fault or additional protection with additional digital features. • System Monitoring: Preventive information / warning before the RCD trips in case of leakage currents – Integrated auxiliary contact – Local Indication • New level of accuracy -> reduced unwanted tripping • No monthly test required • Comprehensive range of accessories • Real contact position indicator • Fault current tripping indicator • Automatic re-setting possible • Transparent designation plate Chapter 2.2.1. – 1 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCdM type G/A Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601) In/IΔn (A) SG49712 Type Designation Article No. Units per package FRCdM-25/4/003-G/A FRCdM-25/4/03-G/A FRCdM-40/4/003-G/A FRCdM-40/4/03-G/A FRCdM-63/4/003-G/A FRCdM-63/4/03-G/A FRCdM-80/4/003-G/A FRCdM-80/4/03-G/A 168646 168647 168648 168649 168650 168651 168634 168635 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCdM-63/4/003-R 168636 1/30 Type Designation Article No. Units per package FRCdM-40/4/03-S/A FRCdM-63/4/03-S/A FRCdM-80/4/03-S/A 168637 168638 168639 1/30 1/30 1/30 Type Designation Article No. Units per package FRCdM-40/4/003-U FRCdM-40/4/03-U FRCdM-63/4/003-U FRCdM-63/4/03-U FRCdM-80/4/03-U 168643 168644 168640 168641 168642 1/30 1/30 1/30 1/30 1/30 4-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 80/0.03 80/0.3 Residual Current Devices FRCdM type R Surge current-proof 3 kA, X-ray application, type R In/IΔn (A) SG49712 4-pole 63/0.03 Residual Current Devices FRCdM type S/A Selective + surge current-proof typ. 5 kA, sensitive to residual pulsating DC, type S/A In/IΔn (A) SG49712 4-pole 40/0.3 63/0.3 80/0.3 Residual Current Devices FRCdM type U Selective + surge current-proof typ. 5 kA, frequency converter-proof, type U In/IΔn (A) SG49712 4-pole 40/0.03 *) 40/0.3 63/0.03 *) 63/0.3 80/0.3 *) Short time delayed + surge current-proof 3 kA Chapter 2.2.1. – 2 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Specifications | Residual Current Devices FRCdM Description • Residual current devices • Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series • Twin-purpose terminal (lift/open-mouthed) above and below • Busbar positioning optionally above or below • Free terminal space despite installed busbar • Universal tripping signal switch, also suitable for FAZ, FRBmM-1N can be mounted subsequently • Auxiliary switch Z-HK can be mounted subsequently • Contact position indicator red - green • Tripping indicator white - blue • Additional Safety - possibility to seal - possibility to lock in ON and OFF position • Delayed types suitable for being used with standard fluorescent tubes with or without electronical ballast (30mA-RCD: 30 units per phase conductor, 100mA-RCD: 90 units per phase conductor). Notes: Depending of the fluorescent lamp ballast manufacturer partly more possible. Symmetrical allocation of the fluorescent lamp ballasts on all phases favourably. Shifting references of the fluorescent lamp ballast manufacturer consider. • The device functions irrespective of the position of installation • Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional protection” within the meaning of the applicable installation rules. • Mains connection at either side • The 4-pole device can also be used for 3-pole connection: See connection possibilities. • The 4-pole device can also be used for 2-pole connection: See connection possibilities. • The test key “T” must be pressed every year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). A test is further needed if red and yellow LED are on together. • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. • Functioning - The green LED becomes active at 0-30% IΔn - The yellow LED becomes active at 30-50% IΔn - The red LED becomes active at >50% IΔn • Potential-free relay (NO contact, in parallel with the yellow LED, up to 1 A ohmic load / 230 V~) for external prewarning function. Bistabile, means the warning stays on also when the breaker trips, until reset. • Type -A: Protects against special forms of residual pulsating DC which have have not been smoothed. • Type -G: High reliability against unwanted tripping. Compulsory for any circuit where personal injury or damage to property may occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6). • Type -G/A: Additionally protects against special forms of residual pulsating DC which have not been smoothed. • Type -R: To aviod unwanted tripping due to X-ray devices. • Type -S: Selective residual current device sensitive to AC, type -S. Compulsory for systems with surge arresters downstream of the RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5). • Type -S/A: Additionally protects against special forms of residual pulsating pulsating DC which have not been smoothed. • Type -U: Suitable for speed-controlled drives with frequency converters in household, trade, and industry. Unwanted tripping is avoided thanks to a tripping characteristic designed particularly for frequency converters. See also explanation “Frequency Converter-Proof RCDs - What for?”. Application according to ÖVE/ÖNORM E 8001-1 and Decision EN 219 (1989), VDE 0100, SEV 1000. Accessories: Auxiliary switch for subsequent installation to the left Tripping signal contact for subsequent installation to the right Automatic restarting device Remote control Pre-mounted sets Remote testing module Sealing cover set Switching interlock Z-HK Z-NHK Z-FW/LP Z-FW-LPD Z-FW-MO Z-FW-LP/MO Z-FW-LPD/MO Z-FW/003 Z-FW/010 Z-FW/030 Z-RC/AK-4TE IS/SPE-1TE Chapter 2.2.1. – 3 248432 248434 248296 265244 284730 290171 290172 248298 248299 248300 101062 101911 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Technical Data FRCdM Electrical Design according to Current test marks as printed onto the device Tripping Type G , R Type S Type U (only 30 mA) Type U (except 30 mA) Rated voltage Operation voltage electronic Operation voltage test circuit Rated tripping current Sensitivity Rated insulation voltage Rated impulse withstand voltage Rated short circuit capacity Peak withstand current Type G, G/A, R, U (30mA) Type S/A, U (except 30mA) Electrical isolation Maximum back-up fuse In = 16-63A In = 80A In = 100A Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Degree of protection in moisture-proof enclosure Upper and lower terminals Terminal protection Terminal capacity Terminal screw Terminal capacity warning contact(s) Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Resistance to climatic conditions Contact position indicator Tripping indicator IEC/EN 61008 Type G and G/A acc. to ÖVE E 8601 Un IΔn Ui Uimp Icn instantaneous 10 ms delay 40 ms delay - with selective disconnecting function 10 ms delay 40 ms delay - with selective disconnecting function 240/415 V AC, 50Hz 50 – 264V AC 196 – 264V AC 30, 300 mA AC and pulsating DC 440 V 4 kV (1.2/50µs) 10 kA 3 kA (8/20 µs) surge current proof typ. 5 kA (8/20 µs) selective + surge current proof > 4 mm contact space Short circuit and overload protection 63 A gG/gL 80 A gG/gL 100 A gG/gL ≥ 4,000 operating cycles ≥ 20,000 operating cycles 45 mm 80 mm 70 mm (4MU) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP40 IP54 open mouthed/lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 1.5 - 35 mm2 single wire 2 x 16 mm2 multi wire M5 (Pozidriv PZ2) 0.25-1.5 mm2 (plug in terminals) 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 red / green white / blue Connection diagram 4-pole Chapter 2.2.1. – 4 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Local Indication RCCB Status indication LED Permanent light green red / yellow / green Normal operation Permanent light yellow The measured residual current is bigger than 30% of the nominal tripping value. Permanent light red The measured residual current is bigger than 50% of the nominal tripping value. Flashing yellow/red Check the device with test key. If the LEDs are still flashing check the direction of connection (supply side / load side). Remote Indication Potential-free auxiliary switch for use in control circuits, insulated from main circuit of the switch gear according to IEC/EN60664. 0.25A ohmic load / 240V AC, terminal capacity: 0.25 - 1.5 mm2. Dimensions (mm) Correct connection 3+N (240/415V) 3-phase load without N (415V AC Phase-Phase) 3-phase load without N (240V AC AC Phase-Phase) 1+N (240V) Electronic works within 50-264V AC ! - Disconnect load side of the switch gear, if you make a insulation test of the installation! Chapter 2.2.1. – 5 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCdM Type B, B+ and Bfq Digital SG49812 • Line-voltage independent, all-current sensitive RCCB for fault or additional protection with additional digital features • System Monitoring: Preventive information / warning before the RCD trips in case of leakage currents – Integrated auxiliary contact – Local Indication through 3 LEDs • B+ types also meet the requirements of superior fire-protection systems according to VDE 0664-400 (formerly known as VDE V 0664-110) • 4-pole types can also be used as 2-pole devices for photovoltaic applications • New level of accuracy -> reduced unwanted tripping • No monthly test required • Comprehensive range of accessories • Real contact position indicator • Fault current tripping indicator • Automatic re-setting possible • Transparent designation plate Chapter 2.2.1. – 6 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCdM type G/B Surge current-proof 3 kA, AC-DC sensitive, type G/B (ÖVE E 8601) In/IΔn (A) SG49812 Type Designation Article No. Units per package FRCdM-25/4/003-G/B FRCdM-25/4/03-G/B FRCdM-40/4/003-G/B FRCdM-40/4/03-G/B FRCdM-63/4/003-G/B FRCdM-63/4/03-G/B 167892 167896 167893 167897 167894 167898 1/30 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCdM-25/4/03-S/B FRCdM-40/4/03-S/B FRCdM-63/4/03-S/B 167900 167901 167902 1/30 1/30 1/30 Type Designation Article No. Units per package FRCdM-25/4/003-G/B+ FRCdM-25/4/03-G/B+ FRCdM-40/4/003-G/B+ FRCdM-40/4/03-G/B+ FRCdM-63/4/003-G/B+ FRCdM-63/4/03-G/B+ 167880 167884 167881 167885 167882 167886 1/30 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCdM-25/4/03-S/B+ FRCdM-40/4/03-S/B+ FRCdM-63/4/03-S/B+ 167888 167889 167890 1/30 1/30 1/30 4-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 Residual Current Devices FRCdM Typ S/B Selective + surge current-proof 5 kA, type S/B In/IΔn (A) SG49812 4-pole 25/0.3 40/0.3 63/0.3 Residual Current Devices FRCdM Typ G/B+ Surge current-proof 3 kA, type G/B+ (ÖVE E 8601) In/IΔn (A) SG49812 4-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 Residual Current Devices FRCdM Typ S/B+ Selective + surge current-proof 5 kA, type S/B+ In/IΔn (A) SG49812 4-pole 25/0.3 40/0.3 63/0.3 Chapter 2.2.1. – 7 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCdM Typ G/Bfq Surge current-proof 3 kA, AC-DC sensitive, type G/Bfq (ÖVE E 8601) In/IΔn (A) SG49812 Type Designation Article No. Units per package FRCdM-25/4/03-G/Bfq FRCdM-40/4/03-G/Bfq FRCdM-63/4/03-G/Bfq 167904 167905 167906 1/30 1/30 1/30 Type Designation Article No. Units per package FRCdM-25/4/03-S/Bfq FRCdM-40/4/03-S/Bfq FRCdM-63/4/03-S/Bfq 167908 167909 167910 1/30 1/30 1/30 4-pole 25/0.3 40/0.3 63/0.3 Residual Current Devices FRCdM Typ S/Bfq Selective + surge current-proof 5 kA, type S/Bfq In/IΔn (A) SG49812 4-pole 25/0.3 40/0.3 63/0.3 Chapter 2.2.1. – 8 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Specifications | Residual Current Devices FRCdM - digital, Type B and B+ Description • Residual current devices, all-current sensitive • Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series • Twin-purpose terminal (lift/open-mouthed) above and below • Busbar positioning optionally above or below • Free terminal space despite installed busbar • Universal tripping signal switch, also suitable for FAZ, FRBmM-1N can be mounted subsequently • Auxiliary switch Z-HK can be mounted subsequently • Contact position indicator red - green • Tripping indicator white - blue • Additional Safety - possibility to seal - possibility to lock in ON and OFF position • Delayed types (G, S) suitable for being used with standard fluorescent tubes with or without electronical ballast (30mA-RCD: 30 units per phase conductor, 100mA-RCD: 90 units per phase conductor). Notes: Depending of the fluorescent lamp ballast manufacturer partly more possible. Symmetrical allocation of the fluorescent lamp ballasts on all phases favourably. Shifting references of the fluorescent lamp ballast manufacturer consider. • The device functions irrespective of the position of installation • Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional protection” within the meaning of the applicable installation rules. • The 4-pole device can also be used for 3-pole connection: See connection possibilities. • The 4-pole device can also be used for 2-pole connection: See connection possibilities. • The test key “T” must be pressed every year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). A test is further needed if red and yellow LED are flashing alternately. • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. • Functioning - The green LED becomes active at 0-30% IΔn - The yellow LED becomes active at 30-50% IΔn - The red LED becomes active at >50% IΔn • Potential-free auxiliary switch for use in control circuits, insulated from main circuit of the switch gear according to IEC/EN60664 (0.25A ohmic load / 240V AC) in parallel with the yellow LED, for external prewarning function. Bistabile, means the warning stays on also when the breaker trips, until reset. • Type -G/B and G/B+: High reliability against unwanted tripping. Compulsory for any circuit where personal injury or damage to property may occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6). Protection against all types of fault currents. • Type -S/B and S/B+: Selective residual current device. Protection against all types of fault currents. • Type -S/Bfq: Suitable for speed-controlled drives with frequency converters inhousehold, trade, and industry.Unwanted tripping is avoided thanks to a tripping characteristic designedparticularly for frequency converters. Protection against all types of fault currents. Accessories: Auxiliary switch for subsequent installation to the left Tripping signal contact for subsequent installation to the right Automatic restarting device Remote control Pre-mounted sets Remote testing module Sealing cover set Switching interlock Z-HK Z-NHK Z-FW/LP Z-FW-LPD Z-FW-MO Z-FW-LP/MO Z-FW-LPD/MO Z-FW/001 Z-FW/003 Z-FW/010 Z-FW/030 Z-FW/050 Z-RC/AK-4TE IS/SPE-1TE Chapter 2.2.1. – 9 248432 248434 248296 265244 284730 290171 290172 248297 248298 248299 248300 248301 101062 101911 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Technical Data FRCdM Type B and B+ Electrical Design according to Current test marks as printed onto the device Tripping Type G Type S Rated voltage Operation voltage electronic Voltage range test circuit Rated tripping current Sensitivity Rated insulation voltage Rated impulse withstand voltage Rated short circuit capacity Peak withstand current Type G/B, G/B+ and G/Bfq Type S/B, S/B+ and S/Bfq Electrical isolation Maximum back-up fuse In = 16-63A In = 80A Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Degree of protection in moisture-proof enclosure Upper and lower terminals Terminal protection Terminal capacity Terminal screw Terminal capacity warning contact Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Resistance to climatic conditions Contact position indicator Tripping indicator Types B and Bfq acc. to IEC/EN 61008, IEC/EN 62423 B+ Type acc. to VDE 0664-400, formerly known as VDE V 0664-110 Type G/B and G/B+ additional acc. to ÖVE E 8601 Un IΔn Ui Uimp Icn 10 ms delay 40 ms delay - with selective disconnecting function 240/415 V AC, 50 Hz 50 – 254V AC 184 - 440V AV (300mA) / 184 - 264V AV (30mA) 30, 300 mA Alternating, pulsed and direct currents 440 V 4 kV (1.2/50µs) 10 kA 3 kA (8/20 µs) surge current proof typ. 5 kA (8/20 µs) selective + surge current proof > 4 mm contact space Short circuit and overload protection 63 A gG/gL 80 A gG/gL ≥ 4,000 operating cycles ≥ 20,000 operating cycles 45 mm 80 mm 70 mm (4MU) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP40 IP54 open mouthed/lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 1.5 - 35 mm2 single wire 2 x 16 mm2 multi wire M5 (Pozidriv PZ2) 0.25-1.5 mm2 (plug in terminals) 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 red / green white / blue Connection diagram 4-pole Netz Mains Last Load Chapter 2.2.1. – 10 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Local Indication RCCB Status indication LED Permanent light green red / yellow / green Normal operation Permanent light yellow The measured residual current is bigger than 30% of the nominal tripping value. Permanent light red The measured residual current is bigger than 50% of the nominal tripping value. Flashing yellow/red Check the device with test key. If the LEDs are still flashing check the direction of connection (supply side / load side). Remote Indication Potential-free auxiliary switch for use in control circuits, insulated from main circuit of the switch gear according to IEC/EN60664. 0.25A ohmic load / 240V AC, terminal capacity: 0.25 - 1.5 mm2. Dimensions (mm) Correct connection Load side Netzseite Load side Netzseite Netzseite Load side Lastseite Supply side Lastseite Supply side Supply Lastseite side 3+N (240/415V) 3-phase application (30mA 184-264V) (300mA 184-415V) 2-pole (240V) Load side Supply side 4-pole (240/415V) Test button works within 184-264V (30mA) bzw. 184-440V (300mA)! - Disconnect load side of the switch gear, if you make a insulation test of the installation! - Please take care of supply side and load side! Chapter 2.2.1. – 11 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM • A complete spectrum of compact residual current devices for a wide range of applications • For fault current/residual current protection and additional protection • Wide variety of nominal currents • Comprehensive range of accessories • Real contact position indicator • Automatic re-setting possible Chapter 2.2.1. – 12 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM type AC Conditionally surge current-proof 250 A, type AC In/IΔn (A) Type Designation Article No. Units per package FRCmM-16/2/003 FRCmM-16/2/01 FRCmM-16/2/03 FRCmM-16/2/05 FRCmM-25/2/003 FRCmM-25/2/01 FRCmM-25/2/03 FRCmM-25/2/05 FRCmM-40/2/003 FRCmM-40/2/01 FRCmM-40/2/03 FRCmM-40/2/05 FRCmM-63/2/003 FRCmM-63/2/01 FRCmM-63/2/05 FRCmM-80/2/003 FRCmM-80/2/01 FRCmM-100/2/003 FRCmM-100/2/01 170390 170396 170402 170405 170391 170397 170403 170406 170392 170398 170404 170407 170393 170399 170408 170394 170400 170395 170401 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-16/4/003 FRCmM-16/4/01 FRCmM-16/4/03 FRCmM-16/4/05 FRCmM-25/4/003 FRCmM-25/4/01 FRCmM-25/4/03 FRCmM-25/4/05 FRCmM-40/4/003 FRCmM-40/4/01 FRCmM-40/4/03 FRCmM-40/4/05 FRCmM-63/4/003 FRCmM-63/4/03 FRCmM-63/4/05 FRCmM-80/4/003 FRCmM-80/4/03 FRCmM-80/4/05 FRCmM-100/4/003 FRCmM-100/4/03 FRCmM-100/4/05 170409 170415 170418 170424 170410 170416 170419 170425 170411 170417 170420 170426 170412 170421 170427 170413 170422 170428 170414 170423 170429 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 2-pole 16/0.03 16/0.1 16/0.3 16/0.5 25/0.03 25/0.1 25/0.3 25/0.5 40/0.03 40/0.1 40/0.3 40/0.5 63/0.03 63/0.1 63/0.5 80/0.03 80/0.1 100/0.03 100/0.1 4-pole 16/0.03 16/0.1 16/0.3 16/0.5 25/0.03 25/0.1 25/0.3 25/0.5 40/0.03 40/0.1 40/0.3 40/0.5 63/0.03 63/0.3 63/0.5 80/0.03 80/0.3 80/0.5 100/0.03 100/0.3 100/0.5 Chapter 2.2.1. – 13 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM type A Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) Type Designation Article No. Units per package FRCmM-16/2/003-A FRCmM-16/2/01-A FRCmM-16/2/03-A FRCmM-16/2/05-A FRCmM-25/2/003-A FRCmM-25/2/01-A FRCmM-25/2/03-A FRCmM-25/2/05-A FRCmM-40/2/003-A FRCmM-40/2/01-A FRCmM-40/2/03-A FRCmM-40/2/05-A FRCmM-63/2/003-A FRCmM-63/2/01-A FRCmM-63/2/05-A FRCmM-80/2/003-A FRCmM-80/2/01-A FRCmM-100/2/003-A FRCmM-100/2/01-A 170430 170436 170278 170281 170431 170437 170279 170282 170432 170274 170280 170283 170433 170275 170284 170434 170276 170435 170277 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-16/4/003-A FRCmM-16/4/01-A FRCmM-16/4/03-A FRCmM-16/4/05-A FRCmM-25/4/003-A FRCmM-25/4/01-A FRCmM-25/4/03-A FRCmM-25/4/05-A FRCmM-40/4/003-A FRCmM-40/4/01-A FRCmM-40/4/03-A FRCmM-40/4/05-A FRCmM-63/4/003-A FRCmM-63/4/03-A FRCmM-63/4/05-A FRCmM-80/4/003-A FRCmM-80/4/03-A FRCmM-80/4/05-A FRCmM-100/4/003-A FRCmM-100/4/03-A FRCmM-100/4/05-A 170285 170337 170340 170346 170332 170338 170341 170347 170333 170339 170342 170348 170334 170343 170349 170335 170344 170350 170336 170345 170351 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 2-pole 16/0.03 16/0.1 16/0.3 16/0.5 25/0.03 25/0.1 25/0.3 25/0.5 40/0.03 40/0.1 40/0.3 40/0.5 63/0.03 63/0.1 63/0.5 80/0.03 80/0.1 100/0.03 100/0.1 4-pole 16/0.03 16/0.1 16/0.3 16/0.5 25/0.03 25/0.1 25/0.3 25/0.5 40/0.03 40/0.1 40/0.3 40/0.5 63/0.03 63/0.3 63/0.5 80/0.03 80/0.3 80/0.5 100/0.03 100/0.3 100/0.5 Chapter 2.2.1. – 14 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM type G Surge current-proof 3 kA, type G (ÖVE E 8601) In/IΔn (A) Type Designation Article No. Units per package FRCmM-16/2/003-G FRCmM-16/2/01-G FRCmM-16/2/03-G FRCmM-25/2/003-G FRCmM-25/2/01-G FRCmM-25/2/03-G FRCmM-40/2/003-G FRCmM-40/2/01-G FRCmM-40/2/03-G FRCmM-63/2/003-G FRCmM-63/2/01-G FRCmM-80/2/003-G FRCmM-80/2/01-G FRCmM-100/2/003-G FRCmM-100/2/01-G 170352 170358 170364 170353 170359 170365 170354 170360 170366 170355 170361 170356 170362 170357 170363 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-16/4/003-G FRCmM-16/4/01-G FRCmM-16/4/03-G FRCmM-25/4/003-G FRCmM-25/4/01-G FRCmM-25/4/03-G FRCmM-40/4/003-G FRCmM-40/4/01-G FRCmM-40/4/03-G FRCmM-63/4/003-G FRCmM-63/4/03-G FRCmM-80/4/003-G FRCmM-80/4/03-G 170367 170373 170376 170368 170374 170377 170369 170375 170378 170370 170379 170371 170380 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 2-pole 16/0.03 16/0.1 16/0.3 25/0.03 25/0.1 25/0.3 40/0.03 40/0.1 40/0.3 63/0.03 63/0.1 80/0.03 80/0.1 100/0.03 100/0.1 4-pole 16/0.03 16/0.1 16/0.3 25/0.03 25/0.1 25/0.3 40/0.03 40/0.1 40/0.3 63/0.03 63/0.3 80/0.03 80/0.3 Chapter 2.2.1. – 15 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM type G/A Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601) In/IΔn (A) Type Designation Article No. Units per package FRCmM-16/2/003-G/A FRCmM-16/2/01-G/A FRCmM-16/2/03-G/A FRCmM-25/2/003-G/A FRCmM-25/2/01-G/A FRCmM-25/2/03-G/A FRCmM-40/2/003-G/A FRCmM-40/2/01-G/A FRCmM-40/2/03-G/A FRCmM-63/2/003-G/A FRCmM-63/2/01-G/A FRCmM-80/2/003-G/A FRCmM-80/2/01-G/A FRCmM-100/2/003-G/A FRCmM-100/2/01-G/A 170382 170388 170290 170383 170389 170291 170384 170286 170292 170385 170287 170386 170288 170387 170289 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-16/4/003-G/A FRCmM-16/4/01-G/A FRCmM-16/4/03-G/A FRCmM-25/4/003-G/A FRCmM-25/4/01-G/A FRCmM-25/4/03-G/A FRCmM-40/4/003-G/A FRCmM-40/4/01-G/A FRCmM-40/4/03-G/A FRCmM-63/4/003-G/A FRCmM-63/4/03-G/A FRCmM-80/4/003-G/A FRCmM-80/4/03-G/A 170293 170299 170302 170294 170300 170303 170295 170301 170304 170296 170305 170297 170306 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 2-pole 16/0.03 16/0.1 16/0.3 25/0.03 25/0.1 25/0.3 40/0.03 40/0.1 40/0.3 63/0.03 63/0.1 80/0.03 80/0.1 100/0.03 100/0.1 4-pole 16/0.03 16/0.1 16/0.3 25/0.03 25/0.1 25/0.3 40/0.03 40/0.1 40/0.3 63/0.03 63/0.3 80/0.03 80/0.3 Chapter 2.2.1. – 16 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM type S Selective + surge current-proof 5 kA, type S In/IΔn (A) Type Designation Article No. Units per package FRCmM-16/2/01-S FRCmM-25/2/01-S FRCmM-40/2/01-S FRCmM-63/2/01-S FRCmM-80/2/01-S FRCmM-100/2/01-S 170314 170315 170316 170317 170318 170319 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-16/4/01-S FRCmM-16/4/03-S FRCmM-25/4/01-S FRCmM-25/4/03-S FRCmM-40/4/01-S FRCmM-40/4/03-S FRCmM-63/4/01-S FRCmM-63/4/03-S FRCmM-80/4/03-S 170320 170324 170321 170325 170322 170326 170323 170327 170328 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCmM-16/2/01-S/A FRCmM-25/2/01-S/A FRCmM-40/2/01-S/A FRCmM-63/2/01-S/A FRCmM-80/2/01-S/A FRCmM-100/2/01-S/A 170330 170331 170438 170439 170440 170441 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-16/4/01-S/A FRCmM-16/4/03-S/A FRCmM-25/4/01-S/A FRCmM-25/4/03-S/A FRCmM-40/4/01-S/A FRCmM-40/4/03-S/A FRCmM-63/4/01-S/A FRCmM-63/4/03-S/A FRCmM-80/4/03-S/A 170442 170446 170443 170447 170444 170448 170445 170449 170450 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 2-pole 16/0.1 25/0.1 40/0.1 63/0.1 80/0.1 100/0.1 4-pole 16/0.1 16/0.3 25/0.1 25/0.3 40/0.1 40/0.3 63/0.1 63/0.3 80/0.3 Residual Current Devices FRCmM type S/A Selective + surge current-proof 5 kA, sensitive to residual pulsating DC, type S/A In/IΔn (A) 2-pole 16/0.1 25/0.1 40/0.1 63/0.1 80/0.1 100/0.1 4-pole 16/0.1 16/0.3 25/0.1 25/0.3 40/0.1 40/0.3 63/0.1 63/0.3 80/0.3 Chapter 2.2.1. – 17 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM type U Short-time delayed + surge current-proof 3 kA, frequency converter-proof, type U In/IΔn (A) Type Designation Article No. Units per package FRCmM-16/4/003-U FRCmM-25/4/003-U FRCmM-40/4/003-U FRCmM-63/4/003-U FRCmM-80/4/003-U 170452 170453 170454 170455 170456 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCmM-16/4/01-U FRCmM-16/4/03-U FRCmM-25/4/01-U FRCmM-25/4/03-U FRCmM-40/4/01-U FRCmM-40/4/03-U FRCmM-63/4/01-U FRCmM-63/4/03-U FRCmM-80/4/03-U 170458 170462 170459 170463 170460 170464 170461 170465 170466 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCmM-16/4/003-R FRCmM-25/4/003-R FRCmM-40/4/003-R FRCmM-63/4/003-R FRCmM-80/4/003-R 170308 170309 170310 170311 170312 1/30 1/30 1/30 1/30 1/30 4-pole 16/0.03 25/0.03 40/0.03 63/0.03 80/0.03 Residual Current Devices FRCmM type U Selective + surge current-proof 5 kA, frequency converter-proof, type U In/IΔn (A) 4-pole 16/0.1 16/0.3 25/0.1 25/0.3 40/0.1 40/0.3 63/0.1 63/0.3 80/0.3 Residual Current Devices FRCmM type R Surge current-proof 3 kA, X-ray application, type R In/IΔn (A) 4-pole 16/0.03 25/0.03 40/0.03 63/0.03 80/0.03 Chapter 2.2.1. – 18 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Specifications | Residual Current Devices FRCmM Description • Residual current devices • Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series • Twin-purpose terminal (lift/open-mouthed) above and below • Busbar positioning optionally above or below • Free terminal space despite installed busbar • Universal tripping signal switch, also suitable for FAZ, FRBmM-1N can be mounted subsequently • Auxiliary switch Z-HK can be mounted subsequently • Contact position indicator red - green • Delayed types suitable for being used with standard fluorescent tubes with or without electronical ballast (30mA-RCD: 30 units per phase conductor, 100mA-RCD: 90 units per phase conductor). Notes: Depending of the fluorescent lamp ballast manufacturer partly more possible. Symmetrical allocation of the fluorescent lamp ballasts on all phases favourably. Shifting references of the fluorescent lamp ballast manufacturer consider. • The device functions irrespective of the position of installation • Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional protection” within the meaning of the applicable installation rules. • Mains connection at either side • The 4-pole device can also be used for 3-pole connection: For this purpose use terminals 1-2, 3-4, and 5-6 (+ cable link). • The 4-pole device can also be used for 2-pole connection: For this purpose use terminals 5-6 and N-N. • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven (self-adhesive RCD-label enclosed). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. • Type -A: Protects against special forms of residual pulsating DC which have have not been smoothed. • Type -G: High reliability against unwanted tripping. Compulsory for any circuit where personal injury or damage to property may occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6). • Type -G/A: Additionally protects against special forms of residual pulsating DC which have not been smoothed. • Type -R: To aviod unwanted tripping due to X-ray devices. • Type -S: Selective residual current device sensitive to AC, type -S. Compulsory for systems with surge arresters downstream of the RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5). • Type -S/A: Additionally protects against special forms of residual pulsating pulsating DC which have not been smoothed. • Type -U: Suitable for speed-controlled drives with frequency converters in household, trade, and industry. Unwanted tripping is avoided thanks to a tripping characteristic designed particularly for frequency converters. See also explanation “Frequency Converter-Proof RCDs - What for?”. Application according to ÖVE/ÖNORM E 8001-1 and Decision EN 219 (1989), VDE 0100, SEV 1000. Accessories: Auxiliary switch for subsequent installation to the left Tripping signal contact for subsequent installation to the right Automatic restarting device Remote control Pre-mounted sets Remote testing module Sealing cover set Switching interlock Z-HK Z-NHK Z-FW/LP Z-FW-LPD Z-FW-MO Z-FW-LP/MO Z-FW-LPD/MO Z-FW/003 Z-FW/010 Z-FW/030 Z-FW/050 Z-RC/AK-4TE IS/SPE-1TE 248432 248434 248296 265244 284730 290171 290172 248298 248299 248300 248301 101062 101911 Dimensions (mm) 2P 4P 80 5,5 30,5 4,5 45 80 10,5 35 70 44 60 Chapter 2.2.1. – 19 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Technical Data FRCmM Electrical Design according to IEC/EN 61008 Type G acc. to ÖVE E 8601 Current test marks as printed onto the device Tripping Type G, R Type S Type U (only 30 mA) Type U (without 30 mA) Rated voltage Rated tripping current Sensitivity Rated insulation voltage Rated impulse withstand voltage Rated short circuit capacity Maximum back-up fuse In = 25A In = 40A In = 63A In = 80A In = 100A Rated breaking capacity or rated fault breaking capacity In = 16-40 A In = 63 A In = 80 A In = 100 A Voltage range of test button 2-pole 4-pole Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Degree of protection in moisture-proof enclosure Upper and lower terminals Terminal protection Terminal capacity Un IΔn Ui Uimp Icn instantaneous 10 ms delay 40 ms delay - with selective disconnecting function 10 ms delay 40 ms delay - with selective disconnecting function 240/415V AC, 50Hz 30, 100, 300, 500 mA AC and pulsating DC 440 V 4 kV (1.2/50µs) 10 kA Short circuit protection Overload protection 25 A gG/gL 25 A gG/gL 40 A gG/gL 40 A gG/gL 63 A gG/gL 63 A gG/gL 80 A gG/gL 80 A gG/gL 100 A gG/gL 80 A gG/gL Im IΔm 500 A 630 A 800 A 1,000 A 196 - 264 V~ 196 - 456 V~ ≥ 4,000 operating cycles ≥ 20,000 operating cycles Terminal screw Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Resistance to climatic conditions 45 mm 80 mm 35 mm (2MU), 70 mm (4MU) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP40 IP54 open mouthed/lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 1.5 - 35 mm2 single wire 2 x 16 mm2 multi wire M5 (Pozidriv PZ2) 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 Connection diagram RCD FRCmM in a Three-Phase AC Network without Neutral Conductor 2-pole 4-pole L1 L2 L3 L1 L2 L3 1 3 5 N T The N-terminal must be connected by a cable link with the phase L2 (or L1), so that the test loop is supplied with current and the RCD is tested correctly. 2 4 6 N Chapter 2.2.1. – 20 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Impact of ambient temperature on the maximum permanent current allowed (A) Tripping temperature 40° 45° 50° 55° 60° 25A 2p 25 21 18 14 – 4p 25 22 19 16 – 40A 2p 40 37 33 30 26 4p 40 37 34 31 27 63A 2p 63 59 55 50 45 4p 63 59 55 50 45 80A 2p 80 76 72 68 64 4p 80 76 72 68 64 100A 2p 100 95 90 85 80 4p 100 95 90 85 80 Note: Please make sure that these values are not exceeded and that any upstream thermal overload protection switches off in time. Chapter 2.2.1. – 21 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008 SG49612 • Wide range of compact types of RCDs serving as fault-current and additional protection according to UL1053 & IEC/EN 61008 standards, suitable for worldwide use • Comprehensive range of accessories • Real contact position indicator • Fault current tripping indicator • Automatic re-setting possible • Transparent designation plate Chapter 2.2.1. – 22 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-NA type A Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG48612 Article No. Units per package FRCmM-25/2/003-A-NA FRCmM-25/2/03-A-NA FRCmM-40/2/003-A-NA FRCmM-40/2/03-A-NA FRCmM-63/2/003-A-NA FRCmM-63/2/03-A-NA 167113 167116 167114 167117 167115 167118 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-25/4/003-A-NA FRCmM-25/4/03-A-NA FRCmM-40/4/003-A-NA FRCmM-40/4/03-A-NA FRCmM-63/4/003-A-NA FRCmM-63/4/03-A-NA 167125 167104 167102 167105 167103 167106 1/30 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCmM-25/2/003-G/A-NA FRCmM-25/2/03-G/A-NA FRCmM-40/2/003-G/A-NA FRCmM-40/2/03-G/A-NA FRCmM-63/2/003-G/A-NA FRCmM-63/2/03-G/A-NA 167119 167122 167120 167123 167121 167124 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-25/4/003-G/A-NA FRCmM-25/4/03-G/A-NA FRCmM-40/4/003-G/A-NA FRCmM-40/4/03-G/A-NA FRCmM-63/4/003-G/A-NA FRCmM-63/4/03-G/A-NA 167107 167110 167108 167111 167109 167112 1/30 1/30 1/30 1/30 1/30 1/30 2-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 SG49612 Type Designation 4-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 Residual Current Devices FRCmM-NA type G/A Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601) In/IΔn (A) SG48612 2-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 SG49612 4-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 Chapter 2.2.1. – 23 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Specifications | Residual Current Devices FRCmM-NA Description • Residual current devices • Type -A: Protects against special forms of residual pulsating DC • Purpose terminal lift above and below which have have not been smoothed. • Universal tripping signal switch, also suitable for FAZ, FRBmM-1N • Type -G/A: Additionally protects against special forms of residual can be mounted subsequently pulsating DC which have not been smoothed • Auxiliary switch Z-HK can be mounted subsequently • Contact position indicator red - green • Tripping indicator white - blue • All types suitable for being used with standard fluorescent tubes with or without electronical ballast (30mA-RCD: 30 units per phase conductor, 300mA-RCD: 90 units per phase conductor). Notes: Depending of the fluorescent lamp ballast manufacturer partly more possible. Symmetrical allocation of the fluorescent lamp ballasts on all phases favourably. Shifting references of the fluorescent lamp ballast manufacturer consider. • The device functions irrespective of the position of installation • Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional protection” within the meaning of the applicable installation rules. • Mains connection at either side • The 4-pole device can also be used for 2-pole connection. For this purpose use terminals 5-6 and N-N. • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven (self-adhesive RCD-label enclosed). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Auxiliary switch for subsequent installation to the left Tripping signal contact for subsequent installation to the right Automatic restarting device Remote control Pre-mounted sets Remote testing module Sealing cover set Switching interlock Z-HK Z-NHK Z-FW/LP Z-FW-LPD Z-FW-MO Z-FW-LP/MO Z-FW-LPD/MO Z-FW/003 Z-FW/030 Z-RC/AK-4TE IS/SPE-1TE 248432 248434 248296 265244 284730 290171 290172 248298 248300 101062 101911 Connection diagram 2-pole 4-pole 1 N T 1 3 5 N T 2 N 2 4 6 N Chapter 2.2.1. – 24 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Technical Data FRCmM-NA Electrical according to IEC/EN 61008 Design according to Current test marks as printed onto the device Tripping Type G Rated voltage Rated tripping current Sensitivity Rated insulation voltage Rated impulse withstand voltage Rated short circuit capacity Maximum back-up fuse Short circuit Overload protection Rated breaking capacity or rated fault breaking capacity In = 25-40A In = 63A Voltage range of test button 2-pole 4-pole Endurance electrical components mechanical components Overvoltage category Electrical according to UL1053 Design according to Current test marks as printed onto the device Tripping Type G Rated voltage Pick-up Current Sensitivity Overvoltage tested Rated impulse withstand voltage Rated short circuit capacity Maximum back-up fuse Short circuit Overload protection Rated breaking capacity or rated fault breaking capacity In = 25-40A In = 63A Voltage range of test button 2-pole 4-pole Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Degree of protection in moisture-proof enclosure Upper and lower terminals Terminal protection Terminal capacity Tripping temperature Resistance to climatic conditions Humidity Pollution degree IEC/EN 61008, ÖVE E 8601 Un IΔn Ui Uimp Icn instantaneous 10 ms delay at 50 Hz 240/415 V; 50/60 Hz 30, 300 mA AC and pulsating DC 440 V 4 kV (1.2/50µs) 10 kA 63 A gG/gL the operating current shall not exceed the rated current of the RCCB Im IΔm 500 A 630 A 196 - 264 V~ 196 - 456 V~ ≥ 4,000 operating cycles ≥ 10,000 operating cycles III UL1053 Un Uimp Icn instantaneous 8 ms delay at 60Hz 480Y/277 V, 60 Hz 22, 200 mA AC and pulsating DC 530 V 4 kV (1.2/50µs) 5 kA acc. to CSA 70 A J-Class Fuse the operating current shall not exceed the rated current of the RCCB Im IΔm 500 A 630 A 196 - 305 V~ 196 - 528 V~ ≥ 4,000 operating cycles ≥ 10,000 operating cycles 45 mm 80 mm 35 mm (2MU), 70 mm (4MU) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP40 IP54 lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 1.5 - 35 mm2 single wire 2 x 16 mm2 multi wire -25°C to +40°C according to IEC 61008 5-95% 2 Chapter 2.2.1. – 25 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Dimensions (mm) Impact of ambient temperature on the maximum permanent current allowed (A) Tripping temperature 40° 45° 50° 55° 60° 25A 2p 25 21 18 14 – 4p 25 22 19 16 – 40A 2p 40 37 33 30 26 4p 40 37 34 31 27 63A 2p 63 59 55 50 45 4p 63 59 55 50 45 Note: Please make sure that these values are not exceeded and that any upstream thermal overload protection switches off in time. Correct connection 3+N (240/415V) IEC (480Y/277V) UL 3-phase load without N (196V-264V AC Phase-Phase) IEC (196V-277V AC Phase-Phase) UL 3-phase load without N (415V AC Phase-Phase) IEC (480V AC Phase-Phase) UL Chapter 2.2.1. – 26 1+N (250V) IEC (277V) UL EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-NA-110 acc. to UL1053 & IEC/EN 61008 SG49612 • Wide range of compact types of RCDs serving as fault-current and additional protection according to UL1053 & IEC/EN 61008 standards, suitable for worldwide use in the 110 V range of applications • Comprehensive range of accessories • Real contact position indicator • Fault current tripping indicator • Automatic re-setting possible • Transparent designation plate Chapter 2.2.1. – 27 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-NA-110 type A Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG49612 Type Designation Article No. Units per package FRCmM-25/4/003-A-NA-110 FRCmM-25/4/03-A-NA-110 FRCmM-40/4/003-A-NA-110 FRCmM-40/4/03-A-NA-110 FRCmM-63/4/003-A-NA-110 FRCmM-63/4/03-A-NA-110 167699 167702 167700 167703 167701 167704 1/30 1/30 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCmM-25/2/003-G/A-NA-110 FRCmM-25/2/03-G/A-NA-110 FRCmM-40/2/003-G/A-NA-110 FRCmM-40/2/03-G/A-NA-110 FRCmM-63/2/003-G/A-NA-110 FRCmM-63/2/03-G/A-NA-110 167693 167696 167694 167697 167695 167698 1/60 1/60 1/60 1/60 1/60 1/60 FRCmM-25/4/003-G/A-NA-110 FRCmM-25/4/03-G/A-NA-110 FRCmM-40/4/003-G/A-NA-110 FRCmM-40/4/03-G/A-NA-110 FRCmM-63/4/003-G/A-NA-110 FRCmM-63/4/03-G/A-NA-110 167705 167708 167706 167709 167707 167710 1/30 1/30 1/30 1/30 1/30 1/30 4-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 Residual Current Devices FRCmM-NA-110 type G/A Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601) In/IΔn (A) SG48612 2-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 SG49612 4-pole 25/0.03 25/0.3 40/0.03 40/0.3 63/0.03 63/0.3 Chapter 2.2.1. – 28 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Specifications | Residual Current Devices FRCmM-NA-110 Description • Residual current devices • Type -A: Protects against special forms of residual pulsating DC • Purpose terminal lift above and below which have have not been smoothed. • Universal tripping signal switch, also suitable for FAZ, FRBmM-1N • Type -G/A: Additionally protects against special forms of residual can be mounted subsequently pulsating DC which have not been smoothed • Auxiliary switch Z-HK can be mounted subsequently • Contact position indicator red - green • Tripping indicator white - blue • All types suitable for being used with standard fluorescent tubes with or without electronical ballast (30mA-RCD: 30 units per phase conductor, 300mA-RCD: 90 units per phase conductor). Notes: Depending of the fluorescent lamp ballast manufacturer partly more possible. Symmetrical allocation of the fluorescent lamp ballasts on all phases favourably. Shifting references of the fluorescent lamp ballast manufacturer consider. • The device functions irrespective of the position of installation • Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional protection” within the meaning of the applicable installation rules. • Mains connection at either side • The 4-pole device can also be used for 2-pole connection. For this purpose use terminals 5-6 and N-N. • The test key “T” must be pressed every month. The system operator must be informed of this obligation and his responsibility in a way that can be proven (self-adhesive RCD-label enclosed). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Auxiliary switch for subsequent installation to the left Tripping signal contact for subsequent installation to the right Automatic restarting device Remote control Pre-mounted sets Remote testing module Sealing cover set Switching interlock Z-HK Z-NHK Z-FW/LP Z-FW-LPD Z-FW-MO Z-FW-LP/MO Z-FW-LPD/MO Z-FW/003 Z-FW/030 Z-RC/AK-4TE IS/SPE-1TE 248432 248434 248296 265244 284730 290171 290172 248298 248300 101062 101911 Connection diagram 2-pole 4-pole 1 N T 1 3 5 N T 2 N 2 4 6 N Chapter 2.2.1. – 29 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Technical Data FRCmM-NA-110 Electrical according to IEC/EN 61008 Design according to Current test marks as printed onto the device Tripping Type G Rated voltage Rated tripping current Sensitivity Rated insulation voltage Rated impulse withstand voltage Rated short circuit capacity Maximum back-up fuse Short circuit Overload protection Rated breaking capacity or rated fault breaking capacity In = 25-40A In = 63A Voltage range of test button 2-pole 4-pole Endurance electrical components mechanical components Overvoltage category Electrical according to UL1053 Design according to Current test marks as printed onto the device Tripping Type G Rated voltage Pick-up Current Sensitivity Overvoltage tested Rated impulse withstand voltage Rated short circuit capacity Maximum back-up fuse Short circuit Overload protection Rated breaking capacity or rated fault breaking capacity In = 25-40A In = 63A Voltage range of test button 2-pole 4-pole Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Degree of protection in moisture-proof enclosure Upper and lower terminals Terminal protection Terminal capacity Tripping temperature Resistance to climatic conditions Humidity Pollution degree IEC/EN 61008, ÖVE E 8601 Un IΔn Ui Uimp Icn instantaneous 10 ms delay at 50Hz 110/190 V, 50/60Hz 30, 300 mA AC and pulsating DC 440 V 4 kV (1.2/50µs) 10 kA 63 A gG/gL the operating current shall not exceed the rated current of the RCCB Im IΔm 500 A 630 A 94 - 121 V~ 94 - 210 V~ ≥ 4,000 operating cycles ≥ 10,000 operating cycles III UL1053 Un Uimp Icn instantaneous 8 ms delay at 60Hz 208/120 V, 60 Hz 22, 200 mA AC and pulsating DC 530 V 4 kV (1.2/50µs) 5 kA acc. to CSA 70 A J-Class Fuse the operating current shall not exceed the rated current of the RCCB Im IΔm 500 A 630 A 94 - 132 V~ 94 - 230 V~ ≥ 4,000 operating cycles ≥ 10,000 operating cycles 45 mm 80 mm 35 mm (2MU), 70 mm (4MU) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP40 IP54 lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 1.5 - 35 mm2 single wire 2 x 16 mm2 multi wire -25°C to +40°C according to IEC 61008 5-95% 2 Chapter 2.2.1. – 30 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Dimensions (mm) Impact of ambient temperature on the maximum permanent current allowed (A) Tripping temperature 40° 45° 50° 55° 60° 25A 2p 25 21 18 14 – 4p 25 22 19 16 – 40A 2p 40 37 33 30 26 4p 40 37 34 31 27 63A 2p 63 59 55 50 45 4p 63 59 55 50 45 Note: Please make sure that these values are not exceeded and that any upstream thermal overload protection switches off in time. Correct connection 3+N (110/190V) IEC (208/120V) UL 3-phase load without N (110V-120V AC Phase-Phase) IEC (100V-132V AC Phase-Phase) UL 3-phase load without N (190V AC Phase-Phase) IEC (208 AC Phase-Phase) UL Chapter 2.2.1. – 31 1+N (110V) IEC (120V) UL EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-125 • Special residual current devices - all fault-current sensitive • High level of protection against unwanted tripping • Selective versions available • Auxiliary switches available • 30 mA types for operator protection available • Modern RCB for 125 A rated current • For fault current/residual current protection and additional protection Chapter 2.2.1. – 32 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-125 type A Conditionally surge current-proof (0.5µs/100kHz ring-wave test), type A In/IΔn (A) Type Designation Article No. Units per package FRCMM-125/2/003-A FRCMM-125/2/01-A FRCMM-125/2/03-A FRCMM-125/2/05-A 171164 171165 171166 171167 1/60 1/60 1/60 1/60 FRCMM-125/4/003-A FRCMM-125/4/01-A FRCMM-125/4/03-A FRCMM-125/4/05-A 171174 171175 171176 171177 1/30 1/30 1/30 1/30 Type Designation Article No. Units per package FRCMM-125/2/003-G/A FRCMM-125/2/01-G/A FRCMM-125/2/03-G/A 171168 171169 171170 1/60 1/60 1/60 FRCMM-125/4/003-G/A FRCMM-125/4/01-G/A FRCMM-125/4/03-G/A 171178 171179 171180 1/30 1/30 1/30 2-pole 125/0.03 125/0.1 125/0.3 125/0.5 4-pole 125/0.03 125/0.1 125/0.3 125/0.5 Residual Current Devices FRCmM-125 type G/A Surge current-proof 3 kA (0.5µs/100kHz ring-wave test), type G/A In/IΔn (A) 2-pole 125/0.03 125/0.1 125/0.3 4-pole 125/0.03 125/0.1 125/0.3 Chapter 2.2.1. – 33 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-125 type S/A Selective + surge current-proof 5 kA (0.5µs/100kHz ring-wave test), type S/A In/IΔn (A) Type Designation Article No. Units per package FRCMM-125/2/01-S/A FRCMM-125/2/03-S/A FRCMM-125/2/05-S/A 171171 171172 171173 1/60 1/60 1/60 FRCMM-125/4/01-S/A FRCMM-125/4/03-S/A FRCMM-125/4/05-S/A 171181 171182 171183 1/30 1/30 1/30 Type Designation Article No. Units per package FRCMM-125/4/003-B FRCMM-125/4/01-B FRCMM-125/4/03-B FRCMM-125/4/05-B 171184 171185 171186 171187 1/30 1/30 1/30 1/30 Typenbezeichnung Artikel-Nr. VPE (Stk.) FRCMM-125/4/003-G/B 171188 1/30 2-pole 125/0.1 125/0.3 125/0.5 4-pole 125/0.1 125/0.3 125/0.5 Residual Current Devices FRCmM-125 type B Surge current-proof 3 kA, type B In/IΔn (A) 4-pole 125/0.03 125/0.1 125/0.3 125/0.5 Residual Current Devices FRCmM-125 type G/B Surge current-proof 3 kA, type G/B In/IΔn (A) 4-pole 125/0.03 Chapter 2.2.1. – 34 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Residual Current Devices FRCmM-125 type G/B+ Surge current-proof 3 kA, type G/B+ In/IΔn (A) Type Designation Article No. Units per package FRCMM-125/4/003-G/B+ 171189 1/30 Type Designation Article No. Units per package FRCMM-125/4/03-S/BFQ FRCMM-125/4/05-S/BFQ 171190 171191 1/30 1/30 4-pole 125/0.03 Residual Current Devices FRCmM-125 type S/Bfq Selective + surge current-proof 5 kA, type S/Bfq In/IΔn (A) 4-pole 125/0.3 125/0.5 Chapter 2.2.1. – 35 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Specifications | Residual Current Devices FRCmM-125, type .A. Description • Residual current devices • Type -A: Additionally protects against special forms of residual • Tripping is line voltage-independent. Consequently, the RCD is suitpulsating DC which have not been smoothed. able for the protection of humans and additional protection • Type -G/A: Additionally protects against special forms of residual (ÖVE/ÖNORM E 8001-1 § 6.1.2) pulsating DC which have not been smoothed. • Twin-purpose terminal (lift/open-mouthed) above and below • Type -S/A: Compulsory for systems with surge arresters down• Not busbar-compatible with other devices of the xEffect-series stream of the RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5). • Auxiliary switch Z-HD can be mounted subsequently • Contact position indicator red - green • The device functions irrespective of the position of installation • Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional protection” within the the meaning of the applicable installation rules • Mains connection at either side • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven (self-adhesive RCD-label enclosed) Accessories: Auxiliary switch for installation on the left at a later point in time Z-HD 265620 Connection diagram 2-pole 4-pole Chapter 2.2.1. – 36 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Technical Data FRCmM125A, type A. Electrical Design according to Current test marks as printed onto the device Tripping Typ G/A Typ S/A Rated voltage Rated tripping current Sensitivity Rated short circuit strength Maximum back-up fuse Rated breaking capacity or Rated fault breaking capacity Voltage range of test button 2-pole 4-pole Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity Busbar thickness Admitted ambient temperature range Storage and transortation temperature range Resistance to climatic conditions Mounting position IEC/EN 61008 Un IΔn Inc Im IΔm instantaneous 10 ms delay - with selective disconnecting function 40 ms delay - with selective disconnecting function 240/415 V; 50 Hz 30, 100, 300, 500 mA AC and pulsating DC 10 kA with back-up fuse 125 A gG/gL 1250 A 204 - 264 V~ 204 - 440 V~ ≥ 4,000 operating cycles ≥ 20,000 operating cycles 45 mm 80 mm 36 mm (2P), 72 mm (4P) quick fastening with DIN rail EN50022 IP40 open mouthed/lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 1.5 - 50 mm2 0.8 - 2 mm -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 any Dimensions (mm) Chapter 2.2.1. – 37 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Specifications | Residual Current Devices FRCmM-125, type B. Description • Residual current devices - all fault-current sensitive • Type B: All fault-current sensitive protective devices are designed • Twin-purpose terminal (lift/open-mouthed) above and below for use in 50 Hz AC systems with electrical equipment such as fre• Busbar positioning optionally above or below quency converters, uninterruptible power supply systems, switch • Free terminal space despite installed busbar mains adapters or highfrequency power converters. In case of a • Not busbar-compatible with other devices of the P series fault, electronic equipment may not only cause AC residual cur• Auxiliary switch Z-HD can be mounted at a later point in time rents and pulsating DC residual currents, but also pure DC and AC • Contact position indicator red - green residual currents of different frequencies in which case residual • The device functions irrespective of the position of installation current devices of type AC and A will not trip. Residual current • Tripping happens independent from line voltage (type A currents). devices of type FRCmM125A, however, will identify all types of 50 VAC are required to identify currents of type B. fault currents in line with tripping characteristic B of the IEC 60755 • Mains connection is at the top standard, i.e. pure DC residual currents as well. In addition, they • The test key “T” must be pressed every half year. The system operwill also identify all AC residual currents of all frequencies up to ator must be informed of this obligation and his responsibility in a 1 MHz (100 kHz with type B) in undulating (mixed) currents. way that can be proven (self-adhesive RCD-label enclosed). • Type B+: All-current sensitive RCD switchgear for applications • Pressing the test key “T” serves the only purpose of function testwhere DC fault currents may occur. Non-selective, non-delayed. ing the residual current device (RCD). This test does not make Protection against all kinds of fault currents. Also meets the earthing resistance measurement (RE), or proper checking of the requirements of the VDE 0664-400 standard (formerly known as earth conductor condition redundant, which must be performed VDE V 0664-110) and therefore provides enhanced fire safety. separately. • Type Bfq: Suitable for speed-controlled drives with frequency converters; designed for household, commercial and industrial applications. Unwanted tripping is prevented through a tripping characteristic especially adapted to frequency converters. Protection against all kinds of fault currents. Accessories: Auxiliary switch for installation on the left at a later point in time Z-HD 265620 Connection diagram 2-pole 4-pole Tripping current frequency response Tripping current frequency response 30 mA Typ B Tripping current frequency response 30 mA Typ G/B+ Tripping current frequency response 30 mA Typ S/B Tripping current frequency response 100 mA Typ B Chapter 2.2.1. – 38 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Tripping current frequency response 300 mA Typ S/Bfq Tripping current frequency response 500 mA Typ S/Bfq Technical Data FRCmM125A, Type B. Electrical Design according to Current test marks as printed onto the device Tripping Type G/B Type S/B Rated voltage Rated tripping current Sensitivity Rated short circuit capacity Peak withstand current Typ B Typ B selektiv Maximum back-up fuse Voltage range of test button Rated breaking capacity or rated fault breaking capacity Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity Busbar thickness Admitted ambient temperature range Storage and transortation temperature range Resistance to climatic conditions Mounting position IEC/EN 61008 Un IΔn Icn short-time delayed 40 ms delay - with selective disconnecting function 240/415 V; 50 Hz 30, 100, 300, 500 mA All types of fault-current 10 kA 3kA 5kA Short circuit protection 125A gG/gL 204 - 264 V~ Im IΔm 1250 A ≥ 4,000 operating cycles ≥ 10,000 operating cycles 45 mm 80 mm 70 mm (4MU) for 2-pole and 4-pole quick fastening with DIN rail EN50022 IP40 open mouthed/lift terminals finger and hand touch safe, BGV A. 1.5 - 50 mm2 0.8 - 2 mm -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 any Dimensions (mm) Chapter 2.2.1. – 39 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Leakage Current Monitor PDIM SG31211 • Reliable, universal monitoring of residual current • RCD characteristic and sensitivity are freely selectable • Compact design, with integrated transformer • DIN mounting, compatible with shapes and standard busbar connections of other xEffect devices • Local status indication of residual current through 3 LEDs • 2 potential-free signalling contacts Chapter 2.2.1. – 40 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Leakage Current Monitor PDIM + , instantaneous, G , S => adjustable In/IΔn (A) SG31211 Type Designation Article No. Units per package PDIM-40/4 PDIM-100/4 111760 111761 1/30 1/30 4-pole 40/0.03; 0.1; 0.3; 0.5; 1 100/0.03; 0.1; 0.3; 0.5; 1 Specifications | Leackage Current Monitor PDIM Description • Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series • Twin-purpose terminal (lift/open-mouthed) above and below • Busbar positioning optionally above or below • Free terminal space despite installed busbar • Power supply via ‘OR’ disjunction of the 4 conductors • Electronic functioning (line-voltage independent) • The device works irrespective of the position of installation • Mains connection at either side • The 4-pole device can also be used for 3-pole connection. For this purpose use terminals 1-2, 3-4, and 5-6. • The 4-pole device can also be used for 2-pole connection. For this purpose use terminals 5-6 and N-N. • 2 potential-free relays (make contact, in parallel with the yellow and red LED) (up to 10 A / 240 V~) Functioning • The green LED becomes active at 0-30% of the preset IΔn. The yellow LED becomes active at 30-50% of the preset IΔn. The red LED becomes active at >50% of the preset IΔn. • The yellow LED turns off again when the identified residual current is <30% of the preset IΔn. • The red LED stays on even if the identified residual current is <50% of the preset IΔn. • The red LED will only turn off after pressing the reset button. • Only one LED will be active at a time. • An output relay will always be switched simultaneously with the yellow or red LED • Depending on the setting of the type of RCD (instantaneous, G, S), the residual current needs to flow a sufficiently long time before an action is triggered. Test function • The rotary coding switch for the RCD switch function is to be set to “TEST”.The device then alternately simulates residual currents of 30% and 50% of the IΔn. In this process, the yellow and red LED flash alternately (1 Hz), both output relays remain permanently energised. Connection diagram 4-pole Chapter 2.2.1. – 41 EATON CORPORATION xxxxx+xxxx-xxxxEN Residual Current Devices Technical Data PDIM Electrical Design similar to Current test marks as printed onto the device Rated current Tripping behaviour (adjustable) Type G Type S Rated voltage Rated tripping current (adjustable) Sensitivity Rated insulation voltage Rated short circuit capacity Maximum back-up fuse admitted In = 40A In = 100A Switching contacts potential-free Tripping behaviour of the contacts Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Degree of protection in splash-proof enclosure Upper and lower terminals Terminal protection Terminal capacity (1, 2, 3, 4, 5, 6, N, N) Terminal capacity of switching contacts Busbar thickness Admitted ambient temperature range Storage and transortation temperature range Resistance to climatic conditions DIN/EN 62020 In Un IΔn Ui Icn 40 A, 100 A instantaneous 10 ms delay 40 ms delay - with selective disconnecting function 230/400 V, 50/60 Hz 240/415 V, 50/60 Hz 30, 100, 300, 500, 1000 mA AC and pulsating DC 440 V 10 kA Overload protection Short circuit protection 40 A gG/gL 63 A gG/gL 63 A gG/gL 100 A gG/gL 10 A / 240 V~ 1: 30-50% IΔn 2: >50% IΔn ≥ 4,000 operating cycles ≥ 20,000 operating cycles 45 mm 80 mm 70 mm (4MU) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP40 IP54 open mouthed/lift terminals Protection against accidental contact according to BGV A3, ÖVE-EN 6 1.5 - 35 mm2 single-wired 2 x 16 mm2 multi-wired 0.25 - 1.5 mm2 0.8 - 2 mm -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 Dimensions (mm) Chapter 2.2.1. – 42 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBdM, digital SG48312 • High-quality residual current device / miniature circuit breaker combination, line voltage-dependent • 1+N and 2-pole • Contact position indicator red - green • Tripping indicator white - blue • New level of accuracy -> reduced unwanted tripping • Local status indication of residual current through 3 LEDs • 2-position DIN rail clip, permits removal from existing busbar system • Comprehensive range of accessories suitable for subsequent installation • Wide variety of rated tripping currents • Rated currents up to 25 A • Tripping characteristics B, C, D • Rated breaking capacity 10 kA Chapter 3.1.1. – 1 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBdM type G/A 10 kA, 1+N-pole Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601) In/IΔn (A) SG48312 Units per package FRBdM-B10/1N/001-G/A FRBdM-B13/1N/001-G/A FRBdM-B16/1N/001-G/A FRBdM-B10/1N/003-G/A FRBdM-B13/1N/003-G/A FRBdM-B16/1N/003-G/A FRBdM-B10/1N/01-G/A FRBdM-B13/1N/01-G/A FRBdM-B16/1N/01-G/A 168249 168250 168251 168264 168265 168266 168279 168280 168281 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBdM-C6/1N/001-G/A FRBdM-C10/1N/001-G/A FRBdM-C13/1N/001-G/A FRBdM-C16/1N/001-G/A FRBdM-C20/1N/001-G/A FRBdM-C25/1N/001-G/A FRBdM-C6/1N/003-G/A FRBdM-C10/1N/003-G/A FRBdM-C13/1N/003-G/A FRBdM-C16/1N/003-G/A FRBdM-C20/1N/003-G/A FRBdM-C25/1N/003-G/A FRBdM-C6/1N/01-G/A FRBdM-C10/1N/01-G/A FRBdM-C13/1N/01-G/A FRBdM-C16/1N/01-G/A FRBdM-C20/1N/01-G/A FRBdM-C25/1N/01-G/A 168252 168253 168254 168255 168256 168257 168267 168268 168269 168270 168271 168272 168282 168283 168284 168285 168286 168287 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBdM-D6/1N/001-G/A FRBdM-D10/1N/001-G/A FRBdM-D13/1N/001-G/A FRBdM-D16/1N/001-G/A FRBdM-D20/1N/001-G/A FRBdM-D25/1N/001-G/A FRBdM-D6/1N/003-G/A FRBdM-D10/1N/003-G/A FRBdM-D13/1N/003-G/A FRBdM-D16/1N/003-G/A FRBdM-D20/1N/003-G/A FRBdM-D25/1N/003-G/A FRBdM-D6/1N/01-G/A FRBdM-D10/1N/01-G/A FRBdM-D13/1N/01-G/A FRBdM-D16/1N/01-G/A FRBdM-D20/1N/01-G/A FRBdM-D25/1N/01-G/A 168258 168259 168260 168261 168262 168263 168273 168274 168275 168276 168277 168278 168288 168289 168290 168291 168292 168293 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic C 6/0.01 10/0.01 13/0.01 16/0.01 20/0.01 25/0.01 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 SG48312 Article No. Characteristic B 10/0.01 13/0.01 16/0.01 10/0.03 13/0.03 16/0.03 10/0.1 13/0.1 16/0.1 SG48312 Type Designation Characteristic D 6/0.01 10/0.01 13/0.01 16/0.01 20/0.01 25/0.01 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 Chapter 3.1.1. – 2 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBdM type G/A 10 kA, 2-pole Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601) In/IΔn (A) SG48312 Units per package FRBdM-B10/2/001-G/A FRBdM-B13/2/001-G/A FRBdM-B16/2/001-G/A FRBdM-B10/2/003-G/A FRBdM-B13/2/003-G/A FRBdM-B16/2/003-G/A FRBdM-B10/2/01-G/A FRBdM-B13/2/01-G/A FRBdM-B16/2/01-G/A 168294 168295 168296 168198 168199 168200 168213 168214 168215 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBdM-C6/2/001-G/A FRBdM-C10/2/001-G/A FRBdM-C13/2/001-G/A FRBdM-C16/2/001-G/A FRBdM-C20/2/001-G/A FRBdM-C25/2/001-G/A FRBdM-C6/2/003-G/A FRBdM-C10/2/003-G/A FRBdM-C13/2/003-G/A FRBdM-C16/2/003-G/A FRBdM-C20/2/003-G/A FRBdM-C25/2/003-G/A FRBdM-C6/2/01-G/A FRBdM-C10/2/01-G/A FRBdM-C13/2/01-G/A FRBdM-C16/2/01-G/A FRBdM-C20/2/01-G/A FRBdM-C25/2/01-G/A 168297 168298 168299 168300 168301 168302 168201 168202 168203 168204 168205 168206 168216 168217 168218 168219 168220 168221 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBdM-D6/2/001-G/A FRBdM-D10/2/001-G/A FRBdM-D13/2/001-G/A FRBdM-D16/2/001-G/A FRBdM-D20/2/001-G/A FRBdM-D25/2/001-G/A FRBdM-D6/2/003-G/A FRBdM-D10/2/003-G/A FRBdM-D13/2/003-G/A FRBdM-D16/2/003-G/A FRBdM-D20/2/003-G/A FRBdM-D25/2/003-G/A FRBdM-D6/2/01-G/A FRBdM-D10/2/01-G/A FRBdM-D13/2/01-G/A FRBdM-D16/2/01-G/A FRBdM-D20/2/01-G/A FRBdM-D25/2/01-G/A 168303 168304 168305 168195 168196 168197 168207 168208 168209 168210 168211 168212 168222 168223 168224 168225 168226 168227 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic C 6/0.01 10/0.01 13/0.01 16/0.01 20/0.01 25/0.01 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 SG48312 Article No. Characteristic B 10/0.01 13/0.01 16/0.01 10/0.03 13/0.03 16/0.03 10/0.1 13/0.1 16/0.1 SG48312 Type Designation Characteristic D 6/0.01 10/0.01 13/0.01 16/0.01 20/0.01 25/0.01 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 Chapter 3.1.1. – 3 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Specifications | Combined RCD/MCB Devices FRBdM, digital Description • Combined RCD/MCB device • Type -G/A: Additionally protects against special forms of residual • Line voltage-dependent tripping pulsating DC which have not been smoothed. • Compatible with standard busbar • Type -G: High reliability against unwanted tripping. Compulsory • Twin-purpose terminal (lift/open-mouthed) above and below for any circuit where personal injury or damage to property may • Busbar positioning optionally above or below occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6). • Free terminal space despite installed busbar Additionally protects against special forms of residual pulsating DC • Guide for secure terminal connection which have not been smoothed. • Switching toggle (MCB component) in colour designating the rated current • Contact position indicator red - green • Fault current tripping indicator white - blue • Comprehensive range of accessories suitable for subsequent installation • The test key “T” must be pressed every year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Auxiliary switch for subsequent installation Shunt trip release Switching interlock Screws lock 2MU ZP-IHK ZP-WHK ZP-NHK ZP-ASA/.. IS/SPE-1TE Z-CV/SO-2P 286052 286053 248437 248438, 248439 101911 221954800 Connection diagram 1+N-pole 2-pole Dimensions (mm) Chapter 3.1.1. – 4 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Technical Data FRBdM Electrical Design according to Current test marks as printed onto the device Number of protected poles 1+N-pole 2-pole Tripping Type G Rated voltage Rated operational voltage Rated tripping current Rated non-tripping current Sensitivity Press of test button duration Selectivity class Service short circuit capacity Rated short circuit capacity Rated current Rated impulse withstand voltage Characteristic Maximum back-up fuse (short circuit) Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection switch Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity rigid solid/stranded wire Terminal screw Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Climatic conditions Line side (supply) Load side IEC/EN 61009 1 2 Un Ue IΔn IΔno Ics Icn Uimp line voltage-dependent, 10 ms delay 3 kA (8/20µs), surge current-proof 240 V AC, 50 Hz 204-260 V AC 10, 30, 100 mA 0.55 IΔn G/A > 0.5 s 3 7.5 kA 10 kA 6 - 25 A 4 kV (1.2/50µs) B, C, D 100 A gL (>10 kA) ≥ 4,000 operating cycles (In, Un, cosÏ• = 0.87) ≥ 10,000 operating cycles 45 mm 80 mm 35 mm (2MU) 2-position DIN rail clip, permits removal from existing busbar system IP20 IP40 open mouthed/lift terminals finger and hand touch safe, VBG4, ÖVE-EN 6 1 - 25 mm2 M5 (with slotted screw acc. to EN ISO 4757-Z2, Pozidriv PZ2) 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C acc. to IEC 68-2 (25..55°C / 90..95% RH) lower terminals upper terminals Chapter 3.1.1. – 5 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Tripping Characteristic FRBdM, Characteristics B, C and D Chapter 3.1.1. – 6 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Let-through Energy FRBdM Let-through energy FRBdM, characteristic B Let-through energy FRBdM, characteristic C Let-through energy FRBdM, characteristic D Chapter 3.1.1. – 7 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Let-through Current FRBdM Let-through current FRBdM, characteristic B Let-through current FRBdM, characteristic C Let-through current FRBdM, characteristic D Chapter 3.1.1. – 8 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Selectivity-limit current Is [kA] for selectivity between FRBdM and NZMB(C)(N)(H)1-A..., NZMB(C)(N)(H)2-A... Short circuit currents in kA, Rated currents of fuses in A. Overload and short-circuit release unit NZM at max. value FRBdM NZM.1-A… FRBdM NZM.2-A… Icu = 25 (36) (50) (100) kA Icu = 25 (36) (50) (150) kA 40 50 63 80 100 125 40 50 63 80 100 125 160 200 250 B10 1.2 1.5 2 2 4 10 B10 1 1.5 2.5 3 10 B13 1 1.5 2 2 4 10 B13 1 1.2 2 3 10 10 10 10 10 B16 1 1.2 1.5 2 3 8 B16 1 1.2 1.5 2.5 10 10 10 10 10 C+D6 1.2 1.5 2 2 4 10 C+D6 1 1.5 2.5 3 10 10 10 10 10 C+D10 1.2 1.5 2 2 4 10 C+D10 1 1.5 2.5 3 10 10 10 10 10 C+D13 1 1.5 2 2 4 10 C+D13 1 1.2 2 3 10 10 10 10 10 C+D16 1 1.2 1.5 2 3 8 C+D16 1 1.2 1.5 2.5 10 10 10 10 10 C+D20 0.8 1.2 1.5 1.5 3 8 C+D20 1 1.2 1.5 1.5 10 10 10 10 10 C+D25 0.7 1.1 1.3 1.3 2.5 6 C+D25 0.9 1.1 1.3 1.3 10 10 10 10 10 10 10 10 10 NZMB1(C1)(N1)(H1): Icu (400/415V) = 25(36)(50)(100) kA (acc. to IEC/EN 60947-2) NZMB2(C2)(N2)(H2): Icu (400/415V) = 25(36)(50)(150) kA (acc. to IEC/EN 60947-2) Selectivity-limit current Is [kA] for selectivity between FRBdM and NH000/NH00/NH1 gG Short circuit currents in kA, Rated currents of fuses in A. FRBdM NH000/NH00/NH1 gG 25 32 35 40 50 63 80 100 125 B10 <0.5 <0.5 0,9 1,7 2,3 3,4 5,2 6,9 >10 >10 >10 B13 <0.5 <0.5 0,8 1,4 1,9 2,7 4,1 5,2 8,5 >10 >10 B16 <0.5 <0.5 0,7 1,2 1,6 2,2 3,1 3,8 5,7 >10 >10 C6 <0.5 0,5 0,9 1,8 2,5 3,8 8,2 >10 >10 >10 >10 C10 <0.5 <0.5 0,8 1,5 2,0 2,9 4,5 6,6 >10 >10 >10 C13 <0.5 <0.5 0,6 1,2 1,5 2,2 3,3 4,2 6,7 >10 >10 C16 <0.5 <0.5 0,6 1,0 1,3 1,8 2,6 3,3 4,8 >10 >10 C20 <0.5 <0.5 0,5 0,9 1,1 1,6 2,3 2,8 4,1 8,6 >10 C25 <0.5 <0.5 <0.5 0,8 1,0 1,4 2,0 2,5 3,6 7,1 >10 D6 <0.5 0,5 1,0 1,8 2,5 3,8 7,8 >10 >10 >10 >10 D10 <0.5 <0.5 0,7 1,2 1,6 2,4 3,8 5,2 >10 >10 >10 D13 <0.5 <0.5 0,6 1,0 1,3 1,9 2,8 3,6 5,6 >10 >10 D16 <0.5 <0.5 0,5 0,9 1,1 1,6 2,3 2,9 4,3 >10 >10 D20 <0.5 <0.5 <0.5 0,8 1,0 1,4 2,0 2,5 3,6 7,5 >10 D25 <0.5 <0.5 <0.5 0,7 0,8 1,1 1,6 2,1 3,1 5,5 7,7 16 20 Rated breaking capacity (NH) AC 500 V = 120 kA (acc. to IEC/EN 60269) Chapter 3.1.1. – 9 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Back-up Protection between FRBdM and NZM.1-A…, 240 V Short circuit currents in kA. Short circuit currents in kA. FRBdM FRBdM NZMB1-A… Ue = 240 V B NZMC1-A… Ue = 240 V C D B C D 6 - 25 25 6 - 36 36 10 25 25 25 10 36 36 36 13 25 25 25 13 36 36 36 16 25 25 25 16 36 36 36 20 - 20 20 20 - 20 20 25 - 20 20 25 - 20 20 Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMB1) = 25 kA (acc. to IEC/EN 60947-2) Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMC1) = 36 kA (acc. to IEC/EN 60947-2) Short circuit currents in kA. Short circuit currents in kA. FRBdM FRBdM NZMN1-A… Ue = 240 V Ue = 240 V B NZMH1-A… C D B C D 6 - 40 40 6 - 40 40 10 40 40 40 10 40 40 40 13 40 40 40 13 40 40 40 16 40 40 40 16 40 40 40 20 - 20 20 20 - 20 20 25 - 20 20 25 - 20 20 Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMN1) = 50 kA (acc. to IEC/EN 60947-2) Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMH1) = 100 kA (acc. to IEC/EN 60947-2) Back-up Protection between FRBdM and NZM.2-A…, 240 V Short circuit currents in kA. Short circuit currents in kA. FRBdM FRBdM NZMB2-A… Ue = 240 V Ue = 240 V B NZMC1-A… C D B C D 6 - 25 25 6 - 36 36 10 25 25 25 10 36 36 36 13 25 25 25 13 36 36 36 16 25 25 25 16 25 25 25 20 - 20 20 20 - 20 20 25 - 10 10 25 - 10 10 Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMB2) = 25 kA (acc. to IEC/EN 60947-2) Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMC2) = 36 kA (acc. to IEC/EN 60947-2) Short circuit currents in kA. Short circuit currents in kA. FRBdM FRBdM NZMN1-A… Ue = 240 V Ue = 240 V B NZMH1-A… C D B C D 6 - 40 40 6 - 40 40 10 40 40 40 10 40 40 40 13 40 40 40 13 40 40 40 16 25 25 25 16 25 25 25 20 - 15 15 20 - 15 15 25 - 10 10 25 - 10 10 Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMN2) = 50 kA (acc. to IEC/EN 60947-2) Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icu (NZMH2) = 150 kA (acc. to IEC/EN 60947-2) Chapter 3.1.1. – 10 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Back-up Protection between FRBdM and NH00-125 A, 240 V Short circuit currents in kA. FRBdM NH00-125A gG Ue = 240 V B C D 6 - 40 40 10 40 40 40 13 40 40 40 16 40 40 40 20 - 20 20 25 - 10 10 Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) AC 500 V (NH00-125A gG) = 120 kA (acc. to IEC/EN 60269) Back-up Protection between FRBdM and PLSM-OV63, 230 V Short circuit currents in kA. FRBdM PLSM-OV63/2,3,4,3N IT-System U = 230 V B C D 6 - 10 10 10 10 10 10 13 10 10 10 16 10 10 10 20 - 10 10 25 - 10 10 Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009) Ue = 230/400V: Icu (PLSM-OV63) = 10 kA (acc. to IEC/EN 60947-2) Selectivity-limit current Is [kA] for selectivity between FRBdM and PLSM-OV/PLHT-OV... Short circuit currents in kA, Rated currents of fuses in A. FRBdM PLSM-OV/PLHT-OV Icu = 10 kA 25 32 40 50 56 63 80 B10 1.5 1.5 1.5 1.5 1.5 1.5 1.5 B13 1.5 1.5 1.5 1.5 1.5 1.5 1.5 B16 1.5 1.5 1.5 1.5 1.5 1.5 1.5 C+D6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 C+D10 1.5 1.5 1.5 1.5 1.5 1.5 1.5 C+D13 1.5 1.5 1.5 1.5 1.5 1.5 1.5 C+D16 1.5 1.5 1.5 1.5 1.5 1.5 1.5 C+D20 - 1.5 1.5 1.5 1.5 1.5 1.5 C+D25 - - 1.5 1.5 1.5 1.5 1.5 Chapter 3.1.1. – 11 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Local Indication RCD green Self check (power ON) 2 s –> IΔ ≥ 50% IΔn red IΔ = 30-50% IΔn amber IΔ ≤ 30% IΔn green Service Mode (measuring of residual current IΔ) Pressing test button twice to activate Service-Mode press (0.1 - 0.4 s) release (0.1 - 0.4 s) press (0.1 - 0.4 s) Measurement delimiter Measurement delimiter ON time 10 mA measurement color 1 mA measurement color Double-pressing test button to activate Service Mode Time duration of Service Mode red 400 ms amber green press (0.1-0.4 s) -> release (0.1-0.4 s) -> press (0.1-0.4 s) 4 min (during activated Service Mode all protection functions are still working) Lamp test 2s ––> amber green red + 100 mA amber amber + 10 mA green + 10 mA green + 1 mA green + 1 mA 1 mA ⎧ ⎜ ⎜ ⎜ ⎜ ⎨ ⎜ ⎜ ⎜ ⎜ ⎩ red 2s ––> 123 mA Chapter 3.1.1. – 12 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM, 1+N-pole SG13711 • High-quality residual current device / miniature circuit breaker combination, line voltage-independent • Contact position indicator red - green • Fault current tripping indicator • Guide for secure terminal connection • 3-position DIN rail clip, permits removal from existing busbar system • Comprehensive range of accessories suitable for subsequent installation • Wide variety of rated tripping currents • Rated currents up to 40 A • Tripping characteristics B, C, D • Rated breaking capacity 10 kA Chapter 3.1.1. – 13 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type AC 10 kA, 1+N-pole Conditionally surge current-proof 250 A, type AC In/IΔn (A) SG13711 Article No. Units per package FRBmM-B6/1N/001 FRBmM-B10/1N/001 FRBmM-B13/1N/001 FRBmM-B16/1N/001 FRBmM-B6/1N/003 FRBmM-B10/1N/003 FRBmM-B13/1N/003 FRBmM-B16/1N/003 FRBmM-B20/1N/003 FRBmM-B25/1N/003 FRBmM-B32/1N/003 FRBmM-B40/1N/003 FRBmM-B6/1N/01 FRBmM-B10/1N/01 FRBmM-B13/1N/01 FRBmM-B16/1N/01 FRBmM-B20/1N/01 FRBmM-B25/1N/01 FRBmM-B32/1N/01 FRBmM-B40/1N/01 FRBmM-B6/1N/03 FRBmM-B10/1N/03 FRBmM-B13/1N/03 FRBmM-B16/1N/03 FRBmM-B20/1N/03 FRBmM-B25/1N/03 FRBmM-B32/1N/03 FRBmM-B40/1N/03 170971 170972 170973 170974 170920 170695 170696 170697 170698 170699 170700 170701 170656 170657 170658 170659 170660 170661 170662 170663 170551 170600 170601 170602 170603 170604 170605 170606 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-C2/1N/001 FRBmM-C4/1N/001 FRBmM-C6/1N/001 FRBmM-C10/1N/001 FRBmM-C13/1N/001 FRBmM-C16/1N/001 FRBmM-C2/1N/003 FRBmM-C4/1N/003 FRBmM-C6/1N/003 FRBmM-C10/1N/003 FRBmM-C13/1N/003 FRBmM-C16/1N/003 FRBmM-C20/1N/003 FRBmM-C25/1N/003 FRBmM-C32/1N/003 FRBmM-C40/1N/003 FRBmM-C2/1N/01 FRBmM-C4/1N/01 FRBmM-C6/1N/01 FRBmM-C10/1N/01 FRBmM-C13/1N/01 FRBmM-C16/1N/01 FRBmM-C20/1N/01 FRBmM-C25/1N/01 FRBmM-C32/1N/01 FRBmM-C40/1N/01 FRBmM-C2/1N/03 FRBmM-C4/1N/03 FRBmM-C6/1N/03 FRBmM-C10/1N/03 FRBmM-C13/1N/03 FRBmM-C16/1N/03 FRBmM-C20/1N/03 FRBmM-C25/1N/03 FRBmM-C32/1N/03 FRBmM-C40/1N/03 170979 170980 170981 170982 170983 170984 170532 170533 170534 170535 170536 170537 170538 170539 170612 170613 170672 170673 170674 170675 170676 170677 170678 170679 170680 170681 170561 170562 170563 170564 170565 170566 170567 170568 170569 170570 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic B 6/0.01 10/0.01 13/0.01 16/0.01 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 32/0.1 40/0.1 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 25/0.3 32/0.3 40/0.3 SG13711 Type Designation Characteristic C 2/0.01 4/0.01 6/0.01 10/0.01 13/0.01 16/0.01 2/0.03 4/0.03 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 2/0.1 4/0.1 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 32/0.1 40/0.1 2/0.3 4/0.3 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 25/0.3 32/0.3 40/0.3 Chapter 3.1.1. – 14 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices SG13711 Characteristic D 2/0.01 4/0.01 6/0.01 10/0.01 13/0.01 16/0.01 2/0.03 4/0.03 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 2/0.1 4/0.1 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 2/0.3 4/0.3 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 FRBmM-D2/1N/001 FRBmM-D4/1N/001 FRBmM-D6/1N/001 FRBmM-D10/1N/001 FRBmM-D13/1N/001 FRBmM-D16/1N/001 FRBmM-D2/1N/003 FRBmM-D4/1N/003 FRBmM-D6/1N/003 FRBmM-D10/1N/003 FRBmM-D13/1N/003 FRBmM-D16/1N/003 FRBmM-D20/1N/003 FRBmM-D2/1N/01 FRBmM-D4/1N/01 FRBmM-D6/1N/01 FRBmM-D10/1N/01 FRBmM-D13/1N/01 FRBmM-D16/1N/01 FRBmM-D20/1N/01 FRBmM-D2/1N/03 FRBmM-D4/1N/03 FRBmM-D6/1N/03 FRBmM-D10/1N/03 FRBmM-D13/1N/03 FRBmM-D16/1N/03 FRBmM-D20/1N/03 Chapter 3.1.1. – 15 170922 170909 170910 170911 170912 170913 170636 170637 170638 170639 170640 170641 170642 170692 170693 170694 170540 170541 170542 170543 170587 170588 170589 170590 170591 170592 170593 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type A 10 kA, 1+N-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG13711 Article No. Units per package FRBmM-B6/1N/001-A FRBmM-B10/1N/001-A FRBmM-B13/1N/001-A FRBmM-B16/1N/001-A FRBmM-B6/1N/003-A FRBmM-B10/1N/003-A FRBmM-B13/1N/003-A FRBmM-B16/1N/003-A FRBmM-B20/1N/003-A FRBmM-B25/1N/003-A FRBmM-B32/1N/003-A FRBmM-B40/1N/003-A FRBmM-B6/1N/01-A FRBmM-B10/1N/01-A FRBmM-B13/1N/01-A FRBmM-B16/1N/01-A FRBmM-B20/1N/01-A FRBmM-B25/1N/01-A FRBmM-B32/1N/01-A FRBmM-B40/1N/01-A FRBmM-B6/1N/03-A FRBmM-B10/1N/03-A FRBmM-B13/1N/03-A FRBmM-B16/1N/03-A FRBmM-B20/1N/03-A FRBmM-B25/1N/03-A FRBmM-B32/1N/03-A FRBmM-B40/1N/03-A 170975 170976 170977 170978 170702 170703 170704 170705 170706 170707 170708 170709 170664 170665 170666 170667 170668 170669 170670 170671 170607 170608 170609 170610 170611 170552 170553 170554 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-C2/1N/001-A FRBmM-C4/1N/001-A FRBmM-C6/1N/001-A FRBmM-C10/1N/001-A FRBmM-C13/1N/001-A FRBmM-C16/1N/001-A FRBmM-C2/1N/003-A FRBmM-C4/1N/003-A FRBmM-C6/1N/003-A FRBmM-C10/1N/003-A FRBmM-C13/1N/003-A FRBmM-C16/1N/003-A FRBmM-C20/1N/003-A FRBmM-C25/1N/003-A FRBmM-C32/1N/003-A FRBmM-C40/1N/003-A FRBmM-C2/1N/01-A FRBmM-C4/1N/01-A FRBmM-C6/1N/01-A FRBmM-C10/1N/01-A FRBmM-C13/1N/01-A FRBmM-C16/1N/01-A FRBmM-C20/1N/01-A FRBmM-C25/1N/01-A FRBmM-C32/1N/01-A FRBmM-C40/1N/01-A FRBmM-C2/1N/03-A FRBmM-C4/1N/03-A FRBmM-C6/1N/03-A FRBmM-C10/1N/03-A FRBmM-C13/1N/03-A FRBmM-C16/1N/03-A FRBmM-C20/1N/03-A FRBmM-C25/1N/03-A FRBmM-C32/1N/03-A FRBmM-C40/1N/03-A 170904 170905 170906 170907 170908 170921 170614 170615 170616 170617 170618 170619 170620 170621 170622 170623 170682 170683 170684 170685 170686 170687 170688 170689 170690 170691 170571 170572 170573 170574 170575 170576 170577 170578 170579 170580 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic B 6/0.01 10/0.01 13/0.01 16/0.01 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 32/0.1 40/0.1 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 25/0.3 32/0.3 40/0.3 SG13711 Type Designation Characteristic C 2/0.01 4/0.01 6/0.01 10/0.01 13/0.01 16/0.01 2/0.03 4/0.03 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 2/0.1 4/0.1 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 32/0.1 40/0.1 2/0.3 4/0.3 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 25/0.3 32/0.3 40/0.3 Chapter 3.1.1. – 16 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices SG13711 Characteristic D 2/0.01 4/0.01 6/0.01 10/0.01 13/0.01 16/0.01 2/0.03 4/0.03 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 2/0.1 4/0.1 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 2/0.3 4/0.3 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 FRBmM-D2/1N/001-A FRBmM-D4/1N/001-A FRBmM-D6/1N/001-A FRBmM-D10/1N/001-A FRBmM-D13/1N/001-A FRBmM-D16/1N/001-A FRBmM-D2/1N/003-A FRBmM-D4/1N/003-A FRBmM-D6/1N/003-A FRBmM-D10/1N/003-A FRBmM-D13/1N/003-A FRBmM-D16/1N/003-A FRBmM-D20/1N/003-A FRBmM-D2/1N/01-A FRBmM-D4/1N/01-A FRBmM-D6/1N/01-A FRBmM-D10/1N/01-A FRBmM-D13/1N/01-A FRBmM-D16/1N/01-A FRBmM-D20/1N/01-A FRBmM-D2/1N/03-A FRBmM-D4/1N/03-A FRBmM-D6/1N/03-A FRBmM-D10/1N/03-A FRBmM-D13/1N/03-A FRBmM-D16/1N/03-A FRBmM-D20/1N/03-A Chapter 3.1.1. – 17 170914 170915 170916 170917 170918 170919 170643 170644 170645 170646 170647 170648 170649 170544 170545 170546 170547 170548 170549 170550 170594 170595 170596 170597 170598 170599 170868 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type G 10 kA, 1+N-pole Surge current-proof 3 kA, type G (ÖVE E 8601) In/IΔn (A) SG13711 Units per package FRBmM-B13/1N/003-G FRBmM-B16/1N/003-G FRBmM-B20/1N/003-G FRBmM-B25/1N/003-G FRBmM-B32/1N/003-G FRBmM-B40/1N/003-G FRBmM-B13/1N/03-G FRBmM-B16/1N/03-G FRBmM-B20/1N/03-G FRBmM-B25/1N/03-G FRBmM-B32/1N/03-G FRBmM-B40/1N/03-G 170710 170711 170712 170713 170714 170715 170555 170556 170557 170558 170559 170560 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-C13/1N/003-G FRBmM-C16/1N/003-G FRBmM-C20/1N/003-G FRBmM-C25/1N/003-G FRBmM-C32/1N/003-G FRBmM-C40/1N/003-G FRBmM-C13/1N/03-G FRBmM-C16/1N/03-G FRBmM-C20/1N/03-G FRBmM-C25/1N/03-G FRBmM-C32/1N/03-G FRBmM-C40/1N/03-G 170624 170625 170626 170627 170628 170629 170581 170582 170583 170584 170585 170586 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-D13/1N/003-G FRBmM-D16/1N/003-G FRBmM-D20/1N/003-G FRBmM-D13/1N/03-G FRBmM-D16/1N/03-G FRBmM-D20/1N/03-G 170650 170651 170652 170869 170870 170871 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic C 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 13/0.3 16/0.3 20/0.3 25/0.3 32/0.3 40/0.3 SG13711 Article No. Characteristic B 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 13/0.3 16/0.3 20/0.3 25/0.3 32/0.3 40/0.3 SG13711 Type Designation Characteristic D 13/0.03 16/0.03 20/0.03 13/0.3 16/0.3 20/0.3 Chapter 3.1.1. – 18 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type G/A 10 kA, 1+N-pole Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601) In/IΔn (A) SG13711 Units per package FRBmM-B13/1N/003-G/A FRBmM-B16/1N/003-G/A FRBmM-B20/1N/003-G/A FRBmM-B25/1N/003-G/A FRBmM-B32/1N/003-G/A FRBmM-B40/1N/003-G/A 170716 170717 170528 170529 170530 170531 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-C13/1N/003-G/A FRBmM-C16/1N/003-G/A FRBmM-C20/1N/003-G/A FRBmM-C25/1N/003-G/A FRBmM-C32/1N/003-G/A FRBmM-C40/1N/003-G/A 170630 170631 170632 170633 170634 170635 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-D13/1N/003-G/A FRBmM-D16/1N/003-G/A FRBmM-D20/1N/003-G/A 170653 170654 170655 1/60 1/60 1/60 Characteristic C 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 SG13711 Article No. Characteristic B 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 40/0.03 SG13711 Type Designation Characteristic D 13/0.03 16/0.03 20/0.03 Chapter 3.1.1. – 19 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Specifications | Combined RCD/MCB Devices FRBmM, 1+N-pole Description • Combined RCD/MCB device • Type -A: Protects against special forms of residual pulsating DC • Line voltage-independent tripping which have have not been smoothed. • Compatible with standard busbar • Type -G: High reliability against unwanted tripping. Compulsory • Twin-purpose terminal (lift/open-mouthed) above and below for any circuit where personal injury or damage to property may • Busbar positioning optionally above or below occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6). • Free terminal space despite installed busbar • Guide for secure terminal connection • Switching toggle (MCB component) in colour designating the rated current • Contact position indicator red - green • Comprehensive range of accessories suitable for subsequent installation • Nameplate • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Auxiliary switch for subsequent installation Tripping signal switch for subsequent installation Shunt trip release Tripping module Switching interlock Screws lock 2MU ZP-IHK ZP-WHK ZP-NHK ZP-ASA/.. Z-KAM IS/SPE-1TE 286052 286053 248437 248438, 248439 248294 101911 221954800 Connection diagram 1+N-pole Dimensions (mm) Chapter 3.1.1. – 20 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Technical Data FRBmM, 1+N-pole Electrical Design according to Current test marks as printed onto the device Tripping line voltage-independent Type G Rated voltage Rated tripping current Rated non-tripping current Sensitivity Selectivity class Rated breaking capacity Rated current Rated impulse withstand voltage Characteristic Maximum back-up fuse (short circuit) Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection switch Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Climatic conditions IEC/EN 61009 Un IΔn IΔno Icn Uimp instantaneous 250A (8/20µs), surge current-proof 10 ms delay 3kA (8/20µs), surge current-proof 240V AC, 50Hz 10, 30, 100, 300 mA 0.5 IΔn AC and pulsating DC 3 10 kA 2 - 40 A 4 kV (1.2/50µs) B, C, D 100 A gL (>10 kA) ≥ 4,000 operating cycles ≥ 10,000 operating cycles 45 mm 80 mm 35 mm (2MU) 3-position DIN rail clip, permits removal from existing busbar system IP20 IP40 open mouthed/lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 1 - 25 mm2 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C acc. to IEC 68-2 (25..55°C / 90..95% RH) Chapter 3.1.1. – 21 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Load Capacity FRBmM-../1N/ Tripping Characteristic FRBmM-../1N/, Characteristics B, C, and D Effect of ambient temperature (MCB component) Tripping characteristic according to EN 61009 Ambient temperature Defined non-tripping current Defined tripping current Short Circuit Selectivity FRBmM-../1N/ towards DII-DIV fuse link In case of short circuit, there is selectivity between the combined RCD/MCB devices FRBmM../1N/ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is , only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic B towards fuse link DII-DIV*) Short circuit selectivity characteristic C towards fuse link DII-DIV*) FRBmM DII-DIV gL/gG FRBmM DII-DIV gL/gG 20 25 35 50 63 In [A] 10 20 25 35 <0.51) 0.7 1.0 2.9 6.9 10.02) 10.02) 10.02) 2 <0.51) <0.51) 1.7 6.0 10.02) 10.02) 10.02) 10.02) 10.02) 10 0.6 0.9 1.9 3.3 7.0 10.02) 10.02) 4 <0.51) <0.51) 0.7 1.3 4.2 8.5 10.02) 10.02) 10.02) 13 0.5 0.7 1.6 2.8 5.7 9.0 10.02) 6 <0.51) 0.6 1.0 2.9 5.8 10.02) 10.02) 10.02) 10 0.7 1.5 2.6 5.3 9.0 10.02) In [A] 6 16 20 25 32 40 10 16 0.7 80 100 16 50 63 80 100 1.4 2.4 4.4 7.0 10.02) 1.3 2.2 4.0 6.3 10.02) 13 1.4 2.3 4.6 7.6 10.02) 16 1.2 1.8 3.4 5.5 10.02) 1.2 1.7 3.1 5.0 10.02) 1.6 2.9 4.6 10.02) 2.3 3.4 7.7 2.9 6.2 1.3 2.1 3.8 5.8 10.02) 2.0 3.5 5.2 9.5 20 3.1 4.5 8.1 25 <0.5 32 40 1) Selectivity limit current Is under 0.5 kA 2) Selectivity limit current I = rated breaking capacity I of the RCD/MCB device Short circuit selectivity characteristic D towards fuse link DII-DIV*) s cn Darker areas: no selectivity FRBmM DII-DIV gL/gG In [A] 10 20 25 35 50 2 <0.51) <0.51) 1.0 1.8 6.5 10.02) 10.02) 10.02) 10.02) 4 <0.51) 0.8 1.3 3.8 9.0 10.02) 10.02) 10.02) 6 0.6 0.9 2.3 4.7 10.02) 10.02) 10.02) 0.7 1.5 2.6 5.5 9.4 10.02) 1.4 2.2 4.4 7.0 10.02) 16 2.0 3.7 5.5 10.02) 20 1.9 3.4 5.0 10.02) 10 13 Chapter 3.1.1. – 22 16 63 80 100 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Short Circuit Selectivity FRBmM-../1N/ towards D01-D03 fuse link In case of short circuit, there is selectivity between the combined RCD/MCB devices FRBmM../1N/ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is , only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic B towards fuse link D01-D03*) FRBmM D01-D03 gL/gG FRBmM D01-D03 gL/gG In [A] 10 16 <0.51) 6 10 13 20 Short circuit selectivity characteristic C towards fuse link D01-D03*) 25 35 In [A] 10 10.02) 2 <0.51) 4 <0.51) <0.51) <0.51) 0.9 50 63 80 100 10.02) 0.5 0.8 2.4 8.2 10.02) 0.5 0.8 1.6 3.7 6.0 10.02) 10.02) 6 0.6 16 16 0.5 <0.51) 20 0.5 25 35 50 63 80 100 2.4 10.02) 10.02) 10.02) 10.02) 10.02) 3.4 9.5 10.02) 10.02) 10.02) <0.51) 0.8 2.3 6.5 10.02) 10.02) 10.02) <0.5 0.6 1.3 2.9 4.5 8.9 10.02) 0.7 1.4 3.0 4.7 9.0 10.02) 0.6 1.2 2.6 3.9 7.0 10.02) 10 13 1.2 2.5 3.9 7.6 10.02) 20 1.2 2.5 3.6 6.2 10.02) 25 1.2 2.3 3.3 5.7 10.02) 16 1.0 2.1 3.0 5.5 10.02) 3.1 5.1 10.02) 20 1.0 2.0 2.7 5.0 10.02) 2.8 4.5 9.5 25 1.9 2.6 4.5 10.02) 2.1 3.4 10.02) 3.0 8.7 32 2.3 40 32 40 Short circuit selectivity characteristic D towards fuse link D01-D03*) FRBmM D01-D03 gL/gG In [A] 10 16 20 25 35 50 2 <0.51) 0.5 0.8 1.2 5.0 10.02) 10.02) 10.02) 10.02) 4 <0.51) 0.7 1.0 3.0 10.02) 10.02) 10.02) 10.02) 6 0.5 0.8 1.9 5.5 10.02) 10.02) 10.02) 0.6 1.3 2.9 4.7 9.2 10.02) 1.2 2.5 3.8 7.0 10.02) 16 2.3 3.2 5.5 10.02) 20 2.2 3.0 3.9 10.02) 10 13 63 80 100 1) Selectivity limit current Is under 0.5 kA Selectivity limit current Is = rated breaking capacity Icn of the RCD/MCB device Darker areas: no selectivity 2) Chapter 3.1.1. – 23 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Short Circuit Selectivity FRBmM-../1N/ towards NH-00 fuse link In case of short circuit, there is selectivity between the combined RCD/MCB devices FRBmM../1N/ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is , only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic B towards fuse link NH-00*) FRBmM NH-00 gL/gG In [A] 16 <0.51) 20 25 FRBmM 32 35 40 63 80 100 125 160 10.02) 10.02) 10.02) 2 <0.51) 7.3 10.02) 10.02) 10.02) 4 6 0.8 1.4 2.2 3.3 7.0 10 <0.51) 0.7 0.9 1.5 2.1 3.4 4.3 13 <0.51) 0.5 16 NH-00 gL/gG 50 10.02) 6 Short circuit selectivity characteristic C towards fuse link NH-00*) 10.02) 10.02) 10.02) In [A] 16 20 25 32 35 40 50 63 80 100 125 160 2.6 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) <0.51) <0.51) 0.9 1.8 3.2 4.8 8.7 10.02) 10.02) 10.02) 10.02) 10.02) <0.51) 0.7 1.3 2.2 3.3 5.9 8.0 10.02) 10.02) 10.02) 10.02) 0.5 0.8 1.2 1.7 2.7 3.4 5.5 10.02) 10.02) 10.02) 0.6 0.6 0.8 1.4 1.8 2.8 3.6 5.7 10.02) <0.51) 0.6 0.7 1.2 1.5 2.4 3.0 4.5 10.02) 10.02) 10.02) 10 10.02) 13 1.1 1.5 2.3 2.9 4.7 10.02) 10.02) 10.02) 20 0.7 1.1 1.5 2.2 2.8 4.2 9.2 10.02) 25 0.7 1.1 1.4 2.1 2.6 4.0 8.2 10.02) 10.02) 16 1.0 1.3 1.8 2.3 3.7 8.7 10.02) 10.02) 10.02) 20 0.9 1.1 1.7 2.2 3.4 8.0 10.02) 10.02) 10.02) 25 1.6 2.1 3.2 7.2 10.02) 10.02) 1.7 2.6 5.3 9.0 10.02) 2.4 4.5 7.5 10.0 32 1.0 1.4 2.0 40 2.5 3.7 7.1 10.02) 2.3 3.4 6.2 8.8 32 40 Short circuit selectivity characteristic D towards fuse link NH-00*) FRBmM NH-00 gL/gG In [A] 16 20 25 32 35 40 50 2 <0.51) 0.6 1.3 2.5 4.7 7.7 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 4 <0.51) 0.5 0.9 1.6 2.8 4.3 9.2 10.02) 10.02) 10.02) 10.02) 10.02) <0.51) 0.7 1.2 1.8 2.6 4.9 7.0 10.02) 10.02) 10.02) 10.02) 0.5 0.8 1.2 1.7 2.7 3.5 5.6 10.02) 10.02) 10.02) 1.1 1.5 2.3 2.9 4.5 10.02) 10.02) 10.02) 1.4 2.0 2.6 3.9 8.0 10.02) 10.02) 1.9 2.4 3.6 7.0 10.02) 10.02) 6 10 13 16 20 63 80 100 125 160 1) Selectivity limit current Is under 0.5 kA Selectivity limit current Is = rated breaking capacity Icn of the RCD/MCB device Darker areas: no selectivity 2) Chapter 3.1.1. – 24 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Let-through Energy FRBmM-../1N/ Let-through energy FRBmM, characteristic C, 1+N-pole Let through energy I2t [A2 sec] Let through energy I2t [A2 sec] Let-through energy FRBmM, characteristic B, 1+N-pole Prospective short-circuit current [A] Prospective short-circuit current [A] Let through energy I2t [A2 sec] Let-through energy FRBmM, characteristic D, 1+N-pole Prospective short-circuit current [A] Chapter 3.1.1. – 25 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM, FRBm6, 2-pole SG14011 • High-quality residual current device / miniature circuit breaker combination, line voltage-independent • Contact position indicator red - green • Fault current tripping indicator white - blue • Guide for secure terminal connection • 3-position DIN rail clip, permits removal from existing busbar system • Comprehensive range of accessories suitable for subsequent installation • Wide variety of rated tripping currents • Rated currents up to 40 A • Tripping characteristics B, C • Rated breaking capacity 10 kA and 6 kA Chapter 3.1.1. – 26 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type AC 10 kA, 2-pole Conditionally surge current-proof 250 A, type AC In/IΔn (A) SG14011 Article No. Units per package FRBmM-B10/2/003 FRBmM-B13/2/003 FRBmM-B16/2/003 FRBmM-B20/2/003 FRBmM-B25/2/003 FRBmM-B10/2/03 FRBmM-B13/2/03 FRBmM-B16/2/03 FRBmM-B20/2/03 FRBmM-B25/2/03 170872 170873 170874 170875 170876 170837 170838 170839 170840 170841 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-C6/2/003 FRBmM-C10/2/003 FRBmM-C13/2/003 FRBmM-C16/2/003 FRBmM-C20/2/003 FRBmM-C25/2/003 FRBmM-C6/2/03 FRBmM-C10/2/03 FRBmM-C13/2/03 FRBmM-C16/2/03 FRBmM-C20/2/03 FRBmM-C25/2/03 170721 170722 170723 170724 170725 170726 170853 170854 170855 170856 170857 170858 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic B 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 10/0.3 13/0.3 16/0.3 20/0.3 25/0.3 SG14011 Type Designation Characteristic C 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0,03 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 25/0.3 Chapter 3.1.1. – 27 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type A 10 kA, 2-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG14011 Article No. Units per package FRBmM-B10/2/003-A FRBmM-B13/2/003-A FRBmM-B16/2/003-A FRBmM-B20/2/003-A FRBmM-B25/2/003-A FRBmM-B10/2/01-A FRBmM-B13/2/01-A FRBmM-B16/2/01-A FRBmM-B20/2/01-A FRBmM-B50/2/01-A FRBmM-B10/2/03-A FRBmM-B13/2/03-A FRBmM-B16/2/03-A FRBmM-B20/2/03-A FRBmM-B25/2/03-A 170879 170880 170881 170882 170883 170803 170804 170805 170806 170807 170844 170845 170846 170847 170848 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-C6/2/003-A FRBmM-C10/2/003-A FRBmM-C13/2/003-A FRBmM-C16/2/003-A FRBmM-C20/2/003-A FRBmM-C25/2/003-A FRBmM-C6/2/01-A FRBmM-C10/2/01-A FRBmM-C13/2/01-A FRBmM-C16/2/01-A FRBmM-C20/2/01-A FRBmM-C25/2/01-A FRBmM-C6/2/03-A FRBmM-C10/2/03-A FRBmM-C13/2/03-A FRBmM-C16/2/03-A FRBmM-C20/2/03-A FRBmM-C25/2/03-A 170785 170786 170787 170788 170789 170790 170819 170820 170821 170822 170823 170824 170863 170864 170865 170866 170867 170730 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic B 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 10/0.3 13/0.3 16/0.3 20/0.3 20/0,3 SG14011 Type Designation Characteristic C 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 6/0.3 10/0.3 13/0.3 16/0.3 20/0.3 25/0.3 Chapter 3.1.1. – 28 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type Super A 10 kA, 2-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, short time delayed, type Super A In/IΔn (A) SG14011 Article No. Units per package FRBmM-B10/2/003-LiA FRBmM-B13/2/003-LiA FRBmM-B16/2/003-LiA FRBmM-B20/2/003-LiA FRBmM-B25/2/003-LiA FRBmM-B10/2/01-LiA FRBmM-B13/2/01-LiA FRBmM-B16/2/01-LiA FRBmM-B20/2/01-LiA FRBmM-B25/2/01-LiA 170886 170887 170888 170889 170890 170810 170811 170812 170813 170814 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 FRBmM-C6/2/003-LiA FRBmM-C10/2/003-LiA FRBmM-C13/2/003-LiA FRBmM-C16/2/003-LiA FRBmM-C20/2/003-LiA FRBmM-C25/2/003-LiA FRBmM-C6/2/01-LiA FRBmM-C10/2/01-LiA FRBmM-C13/2/01-LiA FRBmM-C16/2/01-LiA FRBmM-C20/2/01-LiA FRBmM-C25/2/01-LiA 170795 170796 170797 170798 170799 170800 170829 170830 170831 170832 170833 170834 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic B 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 SG14011 Type Designation Characteristic C 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 Chapter 3.1.1. – 29 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm6 type AC 6 kA, 2-pole Conditionally surge current-proof 250 A, type AC In/IΔn (A) SG14011 Article No. Units per package FRBm6-B32/2/003 FRBm6-B40/2/003 FRBm6-B32/2/03 FRBm6-B40/2/03 170877 170878 170842 170843 1/60 1/60 1/60 1/60 FRBm6-C32/2/003 FRBm6-C40/2/003 FRBm6-C32/2/03 FRBm6-C40/2/03 170727 170728 170859 170860 1/60 1/60 1/60 1/60 Characteristic B 32/0.03 40/0.03 32/0.3 40/0.3 SG14011 Type Designation Characteristic C 32/0.03 40/0.03 32/0.3 40/0.3 Chapter 3.1.1. – 30 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm6 type A 6 kA, 2-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG14011 Article No. Units per package FRBm6-B32/2/003-A FRBm6-B40/2/003-A FRBm6-B32/2/01-A FRBm6-B40/2/01-A FRBm6-B32/2/03-A FRBm6-B40/2/03-A 170884 170885 170808 170809 170849 170850 1/60 1/60 1/60 1/60 1/60 1/60 FRBm6-C32/2/003-A FRBm6-C40/2/003-A FRBm6-C32/2/01-A FRBm6-C40/2/01-A FRBm6-C32/2/03-A FRBm6-C40/2/03-A 170791 170792 170825 170826 170731 170732 1/60 1/60 1/60 1/60 1/60 1/60 Characteristic B 32/0.03 40/0.03 32/0.1 40/0.1 32/0.3 40/0.3 SG14011 Type Designation Characteristic C 32/0.03 40/0.03 32/0.1 40/0.1 32/0.3 40/0.3 Chapter 3.1.1. – 31 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm6 type Super A 6 kA, 2-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, short time delayed, type Super A In/IΔn (A) SG14011 Article No. Units per package FRBm6-B32/2/003-LiA FRBm6-B40/2/003-LiA FRBm6-B32/2/01-LiA FRBm6-B40/2/01-LiA 170891 170718 170815 170816 1/60 1/60 1/60 1/60 FRBm6-C32/2/003-LiA FRBm6-C40/2/003-LiA FRBm6-C32/2/01-LiA FRBm6-C40/2/01-LiA 170801 170802 170835 170836 1/60 1/60 1/60 1/60 Characteristic B 32/0.03 40/0.03 32/0.1 40/0.1 SG14011 Type Designation Characteristic C 32/0.03 40/0.03 32/0.1 40/0.1 Chapter 3.1.1. – 32 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Specifications | Combined RCD/MCB Devices FRBmM, FRBm6, 2-pole Description • Combined RCD/MCB device • Type -A: Protects against special forms of residual pulsating DC • Line voltage-independent tripping which have have not been smoothed. • Compatible with standard busbar • Type -Super A: High reliability against unwanted tripping. • Twin-purpose terminal (lift/open-mouthed) above and below Compulsory for any circuit where personal injury or damage to • Busbar positioning optionally above or below property may occur in case of unwanted tripping. • Free terminal space despite installed busbar • Guide for secure terminal connection • Switching toggle (MCB component) in colour designating the rated current • Contact position indicator red - green • Fault current tripping indicator white - blue • Comprehensive range of accessories suitable for subsequent installation • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Auxiliary switch for subsequent installation Shunt trip release Switching interlock Screws lock 2MU ZP-IHK ZP-WHK ZP-NHK ZP-ASA/.. IS/SPE-1TE 286052 286053 248437 248438, 248439 101911 221954800 Connection diagram 2-pole Dimensions (mm) Chapter 3.1.1. – 33 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Technical Data FRBmM, FRBm6, 2-pole Electrical Design according to Current test marks as printed onto the device Tripping line voltage-independent Type Super A Rated voltage Rated tripping current Rated non-tripping current Sensitivity Selectivity class Rated breaking capacity FRBmM FRBm6 Rated current Rated impulse withstand voltage Characteristic Maximum back-up fuse (short circuit) Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection switch Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Climatic conditions IEC/EN 61009 Un IΔn IΔno instantaneous 250A (8/20µs), surge current-proof 10 ms delay, surge current-proof 240V AC, 50Hz 30, 100, 300 mA 0.5 IΔn AC and pulsating DC 3 Icn Uimp 10 kA 6 kA 6 - 40 A 4 kV (1.2/50µs) B, C 100 A gL (>10 kA) ≥ 4,000 operating cycles ≥ 10,000 operating cycles 45 mm 80 mm 35 mm (2MU) 3-position DIN rail clip, permits removal from existing busbar system IP20 IP40 open mouthed/lift terminals finger and hand touch safe, VBG4, ÖVE-EN 6 1 - 25 mm2 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C acc. to IEC 68-2 (25..55°C / 90..95% RH) Chapter 3.1.1. – 34 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices FRBmM: Influence of ambient temperature on load carrying capacity • Values = max. allowed current in Ampere at the specific temperature • Temperature factor (%/K) = 0,5 6 10 13 16 20 Ambient temperature / °C -40 -30 -25 -20 8,1 7,8 7,7 7,5 13,5 13,0 12,8 12,5 17,6 16,9 16,6 16,3 21,6 20,8 20,4 20,0 27,0 26,0 25,5 25,0 -10 7,2 12,0 15,6 19,2 24,0 0 6,9 11,5 15,0 18,4 23,0 10 6,6 11,0 14,3 17,6 22,0 20 6,3 10,5 13,7 16,8 21,0 30 6,0 10,0 13,0 16,0 20,0 40 5,7 9,5 12,4 15,2 19,0 FRBm6: Influence of ambient temperature on load carrying capacity • Values = max. allowed current in Ampere at the specific temperature • Temperature factor (%/K) = 0,5 25 32 40 Ambient temperature / °C -40 -30 -25 -20 33,8 32,5 31,9 31,3 43,2 41,6 40,8 40,0 54,0 52,0 51,0 50,0 -10 30,0 38,4 48,0 0 28,8 36,8 46,0 10 27,5 35,2 44,0 20 26,3 33,6 42,0 30 25,0 32,0 40,0 40 23,8 30,4 38,0 Tripping Characteristic FRBm., Characteristics B and C Chapter 3.1.1. – 35 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Short Circuit Selectivity FRBmM towards Neozed1) / Diazed2) / NH003) Short circuit currents in kA, Rated currents of fuses in A Short circuit selectivity FRBmM towards fuse link Neozed 1) Short circuit selectivity FRBmM towards fuse link Diazed 1) FRBm Diazed 2) 16 20 25 32 35 50 63 80 100 10 B10 <0,5 0,5 0,9 1,8 2,9 5,6 10 10 10 10 10 B13 <0,5 0,5 0,8 1,5 2,4 4,5 10 10 10 10 10 B16 0,5 0,8 1,3 2 3,4 8 10 10 9,2 10 B20 0,7 1,3 1,9 3,1 7,1 10 10 10 10 C10 <0,5 0,5 0,8 1,5 2,4 4,4 10 10 10 <0,5 0,5 0,8 1,4 2,3 4,2 10 10 10 <0,5 0,7 1,2 1,9 3,2 7,6 10 10 0,7 1,2 1,8 2,9 6,5 9,7 10 FRBm Neozed 20 25 32 35 40 50 63 80 100 B10 <0,5 0,5 0,9 2 2,3 3,7 8 10 10 B13 <0,5 0,5 0,8 1,7 1,9 3 6 10 B16 0,5 0,7 1,5 1,7 2,4 4,4 6,8 0,7 1,4 1,5 2,2 3,9 6 C10 <0,5 0,5 0,8 1,7 1,9 3 6,1 10 C13 <0,5 0,5 16 B20 0,7 1,6 1,8 2,8 5,5 9,5 10 10 C13 C16 <0,5 0,7 1,3 1,5 2,2 4 6,2 10 10 C16 C20 0,6 1,3 1,4 2,1 3,7 5,6 8,5 10 C20 Short circuit selectivity FRBmM towards fuse link NH00 FRBm NH00 16 3) 3) 20 25 32 35 40 50 63 80 100 125 160 B10 <0,5 <0,5 0,8 1,5 2,3 3,2 5,7 9,1 10 10 10 10 B13 <0,5 <0,5 0,8 1,3 1,9 2,7 4,4 6,5 10 10 10 10 10 10 10 10 10 10 B16 B20 <0,5 0,7 1,1 1,6 2,2 3,4 4,8 8 0,6 1 1,4 2 3,1 4,3 7 C10 <0,5 <0,5 0,7 1,3 1,9 2,7 4,5 6,9 10 10 10 10 C13 <0,5 <0,5 0,7 1,2 1,8 2,5 4,1 6,1 10 10 10 10 C16 C20 2) <0,5 0,6 1 10 10 10 0,6 0,9 1,4 1,9 2,9 4,1 6,5 10 1,5 2 3,1 4,4 7,5 10 10 no selectivity 1) 2) 3) SIEMENS Type 5SE2; Size: D01, D02, D03; Operating class gG; Rated voltage: AC 400 V/DC 250 V SIEMENS Type 5SB2, 5SB4, 5SC2; Size: DII, DIII, DIV; Operating class gG; Rated voltage: AC 500 V/DC 500 V SIEMENS Type 3NA3 8, 3NA6 8, 3NA7 8; Size: 000, 00; Operating class gG; Rated voltage: AC 500 V/DC 250 V Chapter 3.1.1. – 36 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Short Circuit Selectivity FRBm6 towards Neozed1) / Diazed2) / NH003) Short circuit currents in kA, Rated currents of fuses in A Short circuit selectivity FRBm6 towards fuse link Neozed FRBm6 Neozed 16 20 1) FRBm6 Diazed 2) 25 32 35 40 50 63 80 100 1,2 1,3 1,8 3,1 4,7 6 6 B25 1,2 1,7 2,7 3,8 5,5 6 B32 1,3 1,7 2,2 2,7 4,2 B40 1,3 1,8 2,8 3,9 5,6 6 C25 1,2 1,7 2,6 3,6 5,1 6 C32 1,3 1,9 3,3 3,2 5,8 C40 B32 B40 C25 1,1 C32 C40 Short circuit selectivity FRBm6 towards fuse link NH00 16 Short circuit selectivity FRBm6 towards fuse link Diazed 1) B25 FRBm6 NH00 1) 16 20 25 32 35 50 63 80 100 1,1 1,5 2,4 5,5 6 6 1,4 2,1 4,3 6 6 1,4 2,4 2,9 5,1 1,5 2,3 4,4 6 6 1,4 2,2 4,1 5,6 6 1,6 2,8 3,6 6 1,1 3) 3) 20 25 32 35 40 50 63 80 100 125 160 B25 0,9 1,2 1,6 2,4 3,4 5,5 6 6 6 B32 1,1 1,4 2,1 2,9 4,3 6 6 6 1,4 1,9 2,8 4,1 6 6 B40 C25 0,9 1,2 1,6 2,3 3 C32 C40 4,6 6 6 6 1,1 1,5 2,1 2,8 4,3 6 6 6 1,5 2,1 3,1 5,4 6 6 no selectivity 1) 2) 3) SIEMENS Type 5SE2; Size: D01, D02, D03; Operating class gG; Rated voltage: AC 400 V/DC 250 V SIEMENS Type 5SB2, 5SB4, 5SC2; Size: DII, DIII, DIV; Operating class gG; Rated voltage: AC 500 V/DC 500 V SIEMENS Type 3NA3 8, 3NA6 8, 3NA7 8; Size: 000, 00; Operating class gG; Rated voltage: AC 500 V/DC 250 V Chapter 3.1.1. – 37 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Let-through Energy FRBm.-../2/ Let-through energy FRBmM, characteristic B, 2-pole Let-through energy FRBmM, characteristic C, 2-pole Let-through energy FRBm6, characteristic B, 2-pole Let-through energy FRBm6, characteristic C, 2-pole Chapter 3.1.1. – 38 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM, 3-pole SG49512 • High-quality residual current device / miniature circuit breaker combination, line voltage-independent • Contact position indicator red - green • Fault current tripping indicator white - blue • Guide for secure terminal connection • 3-position DIN rail clip, permits removal from existing busbar system • Comprehensive range of accessories suitable for subsequent installation • Wide variety of rated tripping currents • Rated currents up to 32 A • Tripping characteristics B, C, D • Rated breaking capacity 10 kA Chapter 3.1.1. – 39 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBmM type A 10 kA, 3-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG49512 Units per package FRBmM-B10/3/003-A FRBmM-B13/3/003-A FRBmM-B16/3/003-A FRBmM-B20/3/003-A FRBmM-B10/3/01-A FRBmM-B13/3/01-A FRBmM-B16/3/01-A FRBmM-B20/3/01-A 170733 170734 170735 170736 170780 170781 170782 170783 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 FRBmM-C6/3/003-A FRBmM-C10/3/003-A FRBmM-C13/3/003-A FRBmM-C16/3/003-A FRBmM-C20/3/003-A FRBmM-C25/3/003-A FRBmM-C32/3/003-A FRBmM-C6/3/01-A FRBmM-C10/3/01-A FRBmM-C13/3/01-A FRBmM-C16/3/01-A FRBmM-C20/3/01-A FRBmM-C25/3/01-A FRBmM-C32/3/01-A 170737 170738 170739 170740 170741 170772 170773 170742 170743 170744 170745 170746 170747 170748 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 FRBmM-D6/3/003-A FRBmM-D10/3/003-A FRBmM-D13/3/003-A FRBmM-D16/3/003-A FRBmM-D20/3/003-A FRBmM-D25/3/003-A FRBmM-D6/3/01-A FRBmM-D10/3/01-A FRBmM-D13/3/01-A FRBmM-D16/3/01-A FRBmM-D20/3/01-A FRBmM-D25/3/01-A 170774 170775 170776 170777 170778 170779 170749 170750 170751 170752 170753 170754 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 Characteristic C 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 32/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 32/0.1 SG49512 Article No. Characteristic B 10/0.03 13/0.03 16/0.03 20/0.03 10/0.1 13/0.1 16/0.1 20/0.1 SG49512 Type Designation Characteristic D 6/0.03 10/0.03 13/0.03 16/0.03 20/0.03 25/0.03 6/0.1 10/0.1 13/0.1 16/0.1 20/0.1 25/0.1 Chapter 3.1.1. – 40 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Specifications | Combined RCD/MCB Devices FRBmM, 3-pole Description • Combined RCD/MCB device • Type -A: Protects against special forms of residual pulsating DC • Line voltage-independent tripping which have have not been smoothed. • Compatible with standard busbar • Type -G: High reliability against unwanted tripping. Compulsory • Twin-purpose terminal (lift/open-mouthed) above and below for any circuit where personal injury or damage to property may • Busbar positioning optionally above or below occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6). • Free terminal space despite installed busbar • Guide for secure terminal connection • Switching toggle (MCB component) in colour designating the rated current • Contact position indicator red - green • Fault current tripping indicator white - blue • Comprehensive range of accessories suitable for subsequent installation • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Auxiliary switch for subsequent installation Tripping signal contact for subsequent installation Shunt trip release Undervoltage release Switching interlock Screws lock 4MU ZP-IHK ZP-WHK ZP-NHK ZP-ASA/.. Z-USA Z-USD IS/SPE-1TE 286052 286053 248437 248438, 248439 258288, 248289, 248290 248292, 248291 101911 221953900 Connection diagram 3-pole Dimensions (mm) Chapter 3.1.1. – 41 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Technical Data FRBmM, 3-pole Electrical Design according to Current test marks as printed onto the device Tripping line voltage-independent Type G Rated voltage Rated tripping current Rated non-tripping current Sensitivity Selectivity class Rated breaking capacity Rated current Rated impulse withstand voltage Characteristic Maximum back-up fuse (short circuit) Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection switch Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Climatic conditions IEC/EN 61009 Un IΔn IΔno Icn Uimp instantaneous 250A (8/20µs), surge current-proof 10 ms delay, surge current-proof 240/415V AC, 50Hz 30, 100 mA 0.5 IΔn AC and pulsating DC 3 10 kA 6 - 32 A 4 kV (1.2/50µs) B, C, D 100 A gL (>10 kA) ≥ 4,000 operating cycles ≥ 10,000 operating cycles 45 mm 80 mm 70 mm (4MU) 3-position DIN rail clip, permits removal from existing busbar system IP20 IP40 open mouthed/lift terminals finger and hand touch safe, VBG4, ÖVE-EN 6 1 - 25 mm2 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C acc. to IEC 68-2 (25..55°C / 90..95% RH) Tripping Characteristic FRBmM, Characteristics B, C and D Tripping characteristic acc. to EN 61009 conventional non-tripping current conventional tripping current Chapter 3.1.1. – 42 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Short-Circuit Selectivity Between FRBmM, 3-pole, characteristic B and NZM 1/2 NZM FRBmM-B Selectivity-limit current Is [kA] for selectivity between FRBmM-.../B and NZM (overload and short-circuit release unit NZM at max. value). NZM...1-A... NZM...2-A... In [A] Icu = 25(36)(50)(100) kA bei Ue = 400/415 V Icu = 25(36)(50)(150) kA bei Ue = 400/415 V FRBmM-B 40 50 63 80 100 125 40 50 63 80 100 125 160 200 250 10 1.2 1.5 2 2 4 10 1 1.5 2.5 3 10 10 10 10 10 13 1 1.5 2 2 4 10 1 1.2 2 3 10 10 10 10 10 16 1 1.2 1.5 2 3 8 1 1.2 1.5 2.5 10 10 10 10 10 20 0.8 1.2 1.5 1.5 3 8 1 1.2 1.5 1.5 10 10 10 10 10 Between FRBmM, 3-pole, characteristic C and NZM 1/2 NZM FRBmM-C Selectivity-limit current Is [kA] for selectivity between FRBmM-.../C and NZM (overload and short-circuit release unit NZM at max. value). NZM...1-A... NZM...2-A... In [A] Icu = 25(36)(50)(100) kA bei Ue = 400/415 V Icu = 25(36)(50)(150) kA bei Ue = 400/415 V FRBmM-C 40 50 63 80 100 125 40 50 63 80 100 125 160 200 250 6 1.2 2 2.5 3 5 10 1.2 1.5 2.5 3 10 10 10 10 10 10 1.2 1.5 2 2 4 10 1 1.5 2.5 3 10 10 10 10 10 13 1 1.5 2 2 4 10 1 1.2 2 3 10 10 10 10 10 16 1 1.2 1.5 2 3 8 1 1.2 1.5 2.5 10 10 10 10 10 20 0.8 1.2 1.5 1.5 3 8 1 1.2 1.5 1.5 10 10 10 10 10 25 0.7 1.2 1.5 1.5 3 7 0.8 1 1.5 2 10 10 10 10 10 32 - 1.2 1 1.5 2 6 - 1 1.5 2 6 6 6 6 6 Between FRBmM, 3-pole, characteristic D and NZM 1/2 NZM FRBmM-D Selectivity-limit current Is [kA] for selectivity between FRBmM-.../D and NZM (overload and short-circuit release unit NZM at max. value). NZM...1-A... NZM...2-A... In [A] Icu = 25(36)(50)(100) kA bei Ue = 400/415 V FRBmM-D 40 50 63 80 100 125 Icu = 25(36)(50)(150) kA bei Ue = 400/415 V 40 50 63 80 100 125 160 200 250 6 1.2 2 2.5 3 5 10 1.2 1.5 2.5 3 10 10 10 10 10 10 1.2 1.5 2 2 4 10 1 1.5 2.5 3 10 10 10 10 10 13 1 1.5 2 2 4 10 1 1.2 2 3 10 10 10 10 10 16 1 1.2 1.5 2 3 8 1 1.2 1.5 2.5 10 10 10 10 10 20 0.8 1.2 1.5 1.5 3 8 1 1.2 1.5 1.5 10 10 10 10 10 25 0.7 1.2 1.5 1.5 3 7 0.8 1 1.5 2 10 10 10 10 10 Chapter 3.1.1. – 43 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Back-up Protection FRBmM 3-pole / NZMB(C)(N)(H)1 FRBmM 3-pole / NZMB1 FRBmM 3-pole / NZMC1 Ue = 133 / 230 V Ue = 133 / 230 V FRBmM-In/3/B(C)(D)/003(01)(03) + NZMC1 FRBmM-In/3/B(C)(D)/003(01)(03) + NZMB1 In [A] Type B Type C Type D In [A] Type B Type C Type D 6 - 25kA 25kA 6 - 36kA 36kA 10 25kA 25kA 25kA 10 36kA 36kA 36kA 13 25kA 25kA 25kA 13 36kA 36kA 36kA 16 25kA 25kA 25kA 16 36kA 36kA 36kA 20 25kA 25kA 25kA 20 36kA 36kA 36kA 25 - 25kA 25kA 25 - 36kA 36kA 32 - 25kA - 32 - 36kA - FRBmM 3-pole / NZMN1 FRBmM 3-pole / NZMH1 Ue = 133 / 230 V Ue = 133 / 230 V FRBmM-In/3/B(C)(D)/003(01)(03) + NZMH1 FRBmM-In/3/B(C)(D)/003(01)(03) + NZMN1 Type D In [A] Type B 50kA 50kA 6 - 70kA 70kA 50kA 50kA 10 70kA 70kA 70kA 50kA 50kA 13 70kA 70kA 70kA 50kA 50kA 16 70kA 70kA 70kA 50kA 50kA 50kA 20 70kA 70kA 70kA - 50kA 50kA 25 - 70kA 70kA - 50kA - 32 - 70kA - In [A] Type B 6 - 10 50kA 13 50kA 16 50kA 20 25 32 Type C Type C Type D Back-up Protection FRBmM 3-pole / NZMB(C)(N)(H)2 FRBmM 3-pole / NZMB2 FRBmM 3-pole / NZMC2 Ue = 133 / 230 V Ue = 133 / 230 V FRBmM-In/3/B(C)(D)/003(01)(03) + NZMC2 FRBmM-In/3/B(C)(D)/003(01)(03) + NZMB2 Type D In [A] Type B 25kA 25kA 6 - 36kA 36kA 25kA 25kA 10 36kA 36kA 36kA 25kA 25kA 13 36kA 36kA 36kA 25kA 25kA 16 36kA 36kA 36kA 25kA 25kA 25kA 20 36kA 36kA 36kA - 25kA 25kA 25 - 36kA 36kA - 25kA - 32 - 36kA - In [A] Type B 6 - 10 25kA 13 25kA 16 25kA 20 25 32 Type C Type C FRBmM 3-pole / NZMN2 FRBmM 3-pole / NZMH2 Ue = 133 / 230 V Ue = 133 / 230 V Type D FRBmM-In/3/B(C)(D)/003(01)(03) + NZMH2 FRBmM-In/3/B(C)(D)/003(01)(03) + NZMN2 Type D In [A] Type B 50kA 50kA 6 - 70kA 70kA 50kA 50kA 10 70kA 70kA 70kA 50kA 50kA 13 70kA 70kA 70kA 50kA 50kA 16 70kA 70kA 70kA 50kA 50kA 50kA 20 70kA 70kA 70kA - 50kA 50kA 25 - 70kA 70kA - 50kA - 32 - 70kA - In [A] Type B 6 - 10 50kA 13 50kA 16 50kA 20 25 32 Type C Chapter 3.1.1. – 44 Type C Type D EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Back-up Protection FRBmM 3-pole / NH00 FRBmM 3-pole / NH00 125A gG/gL Ue = 133 / 230 V FRBmM-In/3/B(C)(D)/003(01)(03) + NH00 125A gG/gL In [A] Type B Type C Type D 6 - 70kA 70kA 10 70kA 70kA 70kA 13 70kA 70kA 70kA 16 70kA 70kA 70kA 20 70kA 70kA 70kA 25 - 70kA 70kA 32 - 70kA - Chapter 3.1.1. – 45 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Maximum Let-Through Energy FRBmM 3-pole Type B Type C Type D Chapter 3.1.1. – 46 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Maximum Let-Through Current FRBmM 3-pole Type B Type C Type D Chapter 3.1.1. – 47 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm6, FRBm4, 3+N-pole SG14211 • High-quality residual current device / miniature circuit breaker combination, line voltage-independent • Contact position indicator red - green • Fault current tripping indicator white - blue • Guide for secure terminal connection • 3-position DIN rail clip, permits removal from existing busbar system • Comprehensive range of accessories suitable for subsequent installation • Wide variety of rated tripping currents • Rated currents up to 32 A • Tripping characteristics B, C, D • Rated breaking capacity 6 kA or 4.5 kA Chapter 3.1.1. – 48 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm6 type AC 6 kA, 3+N-pole Conditionally surge current-proof 250 A, type AC In/IΔn (A) SG14211 Units per package FRBm6-B13/3N/003 FRBm6-B16/3N/003 FRBm6-B13/3N/01 FRBm6-B16/3N/01 FRBm6-B13/3N/03 FRBm6-B16/3N/03 170985 170986 170896 170897 170943 170944 1/30 1/30 1/30 1/30 1/30 1/30 FRBm6-C6/3N/003 FRBm6-C10/3N/003 FRBm6-C13/3N/003 FRBm6-C16/3N/003 FRBm6-C6/3N/01 FRBm6-C10/3N/01 FRBm6-C13/3N/01 FRBm6-C16/3N/01 FRBm6-C6/3N/03 FRBm6-C10/3N/03 FRBm6-C13/3N/03 FRBm6-C16/3N/03 170989 170990 170991 170992 170900 170901 170902 170903 170947 170948 170949 170950 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 FRBm6-D6/3N/003 FRBm6-D10/3N/003 FRBm6-D13/3N/003 FRBm6-D16/3N/003 FRBm6-D6/3N/01 FRBm6-D10/3N/01 FRBm6-D13/3N/01 FRBm6-D16/3N/01 FRBm6-D6/3N/03 FRBm6-D10/3N/03 FRBm6-D13/3N/03 FRBm6-D16/3N/03 171003 171004 171005 171006 170933 170934 170935 170936 170961 170962 170963 170964 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 Characteristic C 6/0.03 10/0.03 13/0.03 16/0.03 6/0.1 10/0.1 13/0.1 16/0.1 6/0.3 10/0.3 13/0.3 16/0.3 SG14211 Article No. Characteristic B 13/0.03 16/0.03 13/0.1 16/0.1 13/0.3 16/0.3 SG14211 Type Designation Characteristic D 6/0.03 10/0.03 13/0.03 16/0.03 6/0.1 10/0.1 13/0.1 16/0.1 6/0.3 10/0.3 13/0.3 16/0.3 Chapter 3.1.1. – 49 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm6 type A 6 kA, 3+N-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG14211 Units per package FRBm6-B13/3N/003-A FRBm6-B16/3N/003-A FRBm6-B13/3N/01-A FRBm6-B16/3N/01-A FRBm6-B13/3N/03-A FRBm6-B16/3N/03-A 170987 170988 170898 170899 170945 170946 1/30 1/30 1/30 1/30 1/30 1/30 FRBm6-C6/3N/003-A FRBm6-C10/3N/003-A FRBm6-C13/3N/003-A FRBm6-C16/3N/003-A FRBm6-C6/3N/01-A FRBm6-C10/3N/01-A FRBm6-C13/3N/01-A FRBm6-C16/3N/01-A FRBm6-C6/3N/03-A FRBm6-C10/3N/03-A FRBm6-C13/3N/03-A FRBm6-C16/3N/03-A 170996 170997 170998 170999 170926 170927 170928 170929 170954 170955 170956 170957 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 FRBm6-D6/3N/003-A FRBm6-D10/3N/003-A FRBm6-D13/3N/003-A FRBm6-D16/3N/003-A FRBm6-D6/3N/01-A FRBm6-D10/3N/01-A FRBm6-D13/3N/01-A FRBm6-D16/3N/01-A FRBm6-D6/3N/03-A FRBm6-D10/3N/03-A FRBm6-D13/3N/03-A FRBm6-D16/3N/03-A 171008 170892 170893 170894 170938 170939 170940 170941 170966 170967 170968 170969 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 Characteristic C 6/0.03 10/0.03 13/0.03 16/0.03 6/0.1 10/0.1 13/0.1 16/0.1 6/0.3 10/0.3 13/0.3 16/0.3 SG14211 Article No. Characteristic B 13/0.03 16/0.03 13/0.1 16/0.1 13/0.3 16/0.3 SG14211 Type Designation Characteristic D 6/0.03 10/0.03 13/0.03 16/0.03 6/0.1 10/0.1 13/0.1 16/0.1 6/0.3 10/0.3 13/0.3 16/0.3 Chapter 3.1.1. – 50 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm4 type AC 4.5 kA, 3+N-pole Conditionally surge current-proof 250 A, type AC In/IΔn (A) SG14211 Article No. Units per package FRBm4-C20/3N/003 FRBm4-C25/3N/003 FRBm4-C32/3N/003 FRBm4-C20/3N/01 FRBm4-C25/3N/01 FRBm4-C32/3N/01 FRBm4-C20/3N/03 FRBm4-C25/3N/03 FRBm4-C32/3N/03 170993 170994 170995 170923 170924 170925 170951 170952 170953 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 FRBm4-D20/3N/003 FRBm4-D20/3N/01 FRBm4-D20/3N/03 171007 170937 170965 1/30 1/30 1/30 Characteristic C 20/0.03 25/0.03 32/0.03 20/0.1 25/0.1 32/0.1 20/0.3 25/0.3 32/0.3 SG14211 Type Designation Characteristic D 20/0.03 20/0.1 20/0.3 Chapter 3.1.1. – 51 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Combined RCD/MCB Devices FRBm4 type A 4.5 kA, 3+N-pole Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A In/IΔn (A) SG14211 Article No. Units per package FRBm4-C20/3N/003-A FRBm4-C25/3N/003-A FRBm4-C32/3N/003-A FRBm4-C20/3N/01-A FRBm4-C25/3N/01-A FRBm4-C32/3N/01-A FRBm4-C20/3N/03-A FRBm4-C25/3N/03-A FRBm4-C32/3N/03-A 171000 171001 171002 170930 170931 170932 170958 170959 170960 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 FRBm4-D20/3N/003-A FRBm4-D20/3N/01-A FRBm4-D20/3N/03-A 170895 170942 170970 1/30 1/30 1/30 Characteristic C 20/0.03 25/0.03 32/0.03 20/0.1 25/0.1 32/0.1 20/0.3 25/0.3 32/0.3 SG14211 Type Designation Characteristic D 20/0.03 20/0.1 20/0.3 Chapter 3.1.1. – 52 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Specifications | Combined RCD/MCB Devices FRBm6, FRBm4, 3+N-pole Description • Combined RCD/MCB device • Type -A: Protects against special forms of residual pulsating DC • Line voltage-independent tripping which have have not been smoothed. • Compatible with standard busbar • Twin-purpose terminal (lift/open-mouthed) above and below • Busbar positioning optionally above or below • Free terminal space despite installed busbar • Guide for secure terminal connection • Switching toggle (MCB component) in colour designating the rated current • Contact position indicator red - green • Fault current tripping indicator white - blue • Comprehensive range of accessories suitable for subsequent installation • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Auxiliary switch for subsequent installation Tripping signal contact for subsequent installation Shunt trip release Switching interlock Screws lock 4MU ZP-IHK ZP-WHK ZP-NHK ZP-ASA/.. IS/SPE-1TE 286052 286053 248437 248438, 248439 101911 221954800 Connection diagram 3+N-pole Dimensions (mm) Chapter 3.1.1. – 53 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Technical Data FRBm6, FRBm4, 3+N-pole Electrical Design according to Current test marks as printed onto the device Tripping Rated voltage Rated tripping current Rated non-tripping current Sensitivity Selectivity class Rated breaking capacity FRBm6 FRBm4 Rated current Rated impulse withstand voltage Characteristic Maximum back-up fuse (short circuit) Endurance electrical components mechanical components Mechanical Frame size Device height Device width Mounting Degree of protection switch Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity rigid solid/stranded wire Terminal torque Busbar thickness Tripping temperature Storage- and transport temperature Climatic conditions IEC/EN 61009 Un IΔn IΔno line voltage-independent, instantaneous 250A (8/20µs), surge current-proof, N protected 240/415V AC, 50Hz 30, 100, 300 mA 0.5 IΔn AC and pulsating DC 3 Icn Uimp 6 kA 4.5 kA 6 - 32 A 4 kV (1.2/50µs) B, C, D 100 A gL (>10 kA) ≥ 4,000 operating cycles ≥ 10,000 operating cycles 45 mm 80 mm 70 mm (4MU) 3-position DIN rail clip, permits removal from existing busbar system IP20 IP40 open mouthed/lift terminals finger and hand touch safe, VBG4, ÖVE-EN 6 1 - 25 mm2 2 - 2.4 Nm 0.8 - 2 mm -25°C to +40°C -35°C to +60°C acc. to IEC 68-2 (25..55°C / 90..95% RH) Tripping Characteristic FRBm, Characteristics B, C and D Chapter 3.1.1. – 54 EATON CORPORATION xxxxx+xxxx-xxxxEN Combined RCD/MCB Devices Back-up Protection between FRBm and NZM1 Back-up Protection between FRBm and NZM2 Short circuit currents in kA. Short circuit currents in kA. FRBm4/FRBm6-In/B,C,D.. +NZMB1(C1)(N1)(H1)-A… FRBm4/FRBm6-In/B,C,D.. +NZMB2(C2)(N2)(H2)-A… Ue = 415 V Ue = 415 V B C D 6 - 20 20 10 - 20 20 20 13 20 20 20 20 16 20 20 20 20 20 20 - 20 20 20 - 25 - 20 - B C D 6 - 20 20 10 - 20 20 13 20 20 16 20 20 20 - 25 - Ue = 415V: Icn (FRBm4) = 4.5 kA (acc. to IEC/EN 61009) Ue = 415V: Icu (FRBm6) = 6 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icn (NZMB1) = 25 kA (acc. to IEC/EN 60947-2) Ue = 400/415V: Icn (NZMC1) = 36 kA (acc. to IEC/EN 60947-2) Ue = 400/415V: Icn (NZMN1) = 50 kA (acc. to IEC/EN 60947-2) Ue = 400/415V: Icn (NZMH1) = 100 kA (acc. to IEC/EN 60947-2) Ue = 415V: Icn (FRBm4) = 4.5 kA (acc. to IEC/EN 61009) Ue = 415V: Icu (FRBm6) = 6 kA (acc. to IEC/EN 61009) Ue = 400/415V: Icn (NZMB2) = 25 kA (acc. to IEC/EN 60947-2) Ue = 400/415V: Icn (NZMC2) = 36 kA (acc. to IEC/EN 60947-2) Ue = 400/415V: Icn (NZMN2) = 50 kA (acc. to IEC/EN 60947-2) Ue = 400/415V: Icn (NZMH2) = 150 kA (acc. to IEC/EN 60947-2) Chapter 3.1.1. – 55 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Add-on Residual Current Protection Unit FBSmV SG18211 • Combining this device with a top-quality miniature circuit breaker of type FAZ (except PLSN) will form a top-quality RCBO unit (combined RCD/MCB device) • Draw-out connection bar locked in installation position • For subsequent mounting onto 2-, 3-, 3+N- and 4-pole miniature circuit breakers FAZ • Rated current 40 and 63 A Chapter 3.1.1. – 56 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Add-on Residual Current Protection Unit FBSmV type AC Conditionally surge-current-proof 250 A, type AC In/IΔn (A) SG17811 Units per package FBSmV-40/2/003 FBSmV-63/2/003 FBSmV-40/2/01 FBSmV-63/2/01 FBSmV-40/2/03 FBSmV-63/2/03 FBSmV-40/2/05 FBSmV-63/2/05 FBSmV-40/2/1 FBSmV-63/2/1 170177 170178 170179 170180 170181 170182 170183 170184 170185 170186 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 FBSmV-40/3/003 FBSmV-63/3/003 FBSmV-40/3/01 FBSmV-63/3/01 FBSmV-40/3/03 FBSmV-63/3/03 FBSmV-40/3/05 FBSmV-63/3/05 FBSmV-40/3/1 FBSmV-63/3/1 170187 170188 170189 170190 170191 170192 170193 170194 170195 170196 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 FBSmV-40/4/003 FBSmV-63/4/003 FBSmV-40/4/01 FBSmV-63/4/01 FBSmV-40/4/03 FBSmV-63/4/03 FBSmV-40/4/05 FBSmV-63/4/05 FBSmV-40/4/1 FBSmV-63/4/1 170197 170198 170199 170200 170201 170202 170203 170204 170205 170206 1/13 1/13 1/13 1/13 1/13 1/13 1/13 1/13 1/13 1/13 3-pole 40/0.03 63/0.03 40/0.1 63/0.1 40/0.3 63/0.3 40/0.5 63/0.5 40/1 63/1 SG18211 Article No. 2-pole 40/0.03 63/0.03 40/0.1 63/0.1 40/0.3 63/0.3 40/0.5 63/0.5 40/1 63/1 SG18111 Type Designation 4-pole 40/0.03 63/0.03 40/0.1 63/0.1 40/0.3 63/0.3 40/0.5 63/0.5 40/1 63/1 Chapter 3.1.1. – 57 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Add-on Residual Current Protection Unit FBSmV type A Sensitive to residual pulsating DC, conditionally surge current-proof 250 A, type A In/IΔn (A) SG17811 Units per package FBSmV-40/2/003-A FBSmV-63/2/003-A FBSmV-40/2/01-A FBSmV-63/2/01-A FBSmV-40/2/03-A FBSmV-63/2/03-A FBSmV-40/2/05-A FBSmV-63/2/05-A FBSmV-40/2/1-A FBSmV-63/2/1-A 170207 170208 170209 170210 170211 170212 170213 170214 170215 170216 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 FBSmV-40/3/003-A FBSmV-63/3/003-A FBSmV-40/3/01-A FBSmV-63/3/01-A FBSmV-40/3/03-A FBSmV-63/3/03-A FBSmV-40/3/05-A FBSmV-63/3/05-A FBSmV-40/3/1-A FBSmV-63/3/1-A 170217 170218 170219 170220 170221 170222 170223 170224 170225 170226 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 1/20 FBSmV-40/4/003-A FBSmV-63/4/003-A FBSmV-40/4/01-A FBSmV-63/4/01-A FBSmV-40/4/03-A FBSmV-63/4/03-A FBSmV-40/4/05-A FBSmV-63/4/05-A FBSmV-40/4/1-A FBSmV-63/4/1-A 170227 170228 170229 170230 170231 170232 170233 170234 170235 170236 1/13 1/13 1/13 1/13 1/13 1/13 1/13 1/13 1/13 1/13 3-pole 40/0.03 63/0.03 40/0.1 63/0.1 40/0.3 63/0.3 40/0.5 63/0.5 40/1 63/1 SG18211 Article No. 2-pole 40/0.03 63/0.03 40/0.1 63/0.1 40/0.3 63/0.3 40/0.5 63/0.5 40/1 63/1 SG18111 Type Designation 4-pole 40/0.03 63/0.03 40/0.1 63/0.1 40/0.3 63/0.3 40/0.5 63/0.5 40/1 63/1 Chapter 3.1.1. – 58 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Add-on Residual Current Protection Unit FBSmV type G Surge current-proof 3 kA, type G (ÖVE E 8601) In/IΔn (A) SG17811 Units per package FBSmV-40/2/003-G 170237 1/20 FBSmV-40/3/003-G 170238 1/20 FBSmV-40/4/003-G 170239 1/13 Type Designation Article No. Units per package FBSmV-40/2/01-S FBSmV-63/2/01-S FBSmV-40/2/03-S FBSmV-63/2/03-S FBSmV-40/2/1-S FBSmV-63/2/1-S 170240 170241 170142 170143 170144 170145 1/20 1/20 1/20 1/20 1/20 1/20 FBSmV-40/3/01-S FBSmV-63/3/01-S FBSmV-40/3/03-S FBSmV-63/3/03-S FBSmV-40/3/1-S FBSmV-63/3/1-S 170146 170147 170148 170149 170150 170151 1/20 1/20 1/20 1/20 1/20 1/20 FBSmV-40/4/01-S FBSmV-63/4/01-S FBSmV-40/4/03-S FBSmV-63/4/03-S FBSmV-40/4/1-S FBSmV-63/4/1-S 170152 170153 170154 170155 170156 170157 1/13 1/13 1/13 1/13 1/13 1/13 3-pole 40/0.03 SG18211 Article No. 2-pole 40/0.03 SG18111 Type Designation 4-pole 40/0.03 Add-on Residual Current Protection Unit FBSmV type S Selective and surge current-proof 5 kA, type S In/IΔn (A) SG17811 2-pole 40/0.1 63/0.1 40/0.3 63/0.3 40/1 63/1 SG18111 3-pole 40/0.1 63/0.1 40/0.3 63/0.3 40/1 63/1 SG18211 4-pole 40/0.1 63/0.1 40/0.3 63/0.3 40/1 63/1 Chapter 3.1.1. – 59 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Specifications | Add-on Residual Current Protection Unit FBSmV Description • Add-on residual current unit • Line voltage-independent tripping • By combining this device with a top-quality miniature circuit breaker type FAZ (exept PLSN.) a top-quality RCBO unit (combined RCD/MCB device) is formed • Rated current 40 and 63 A • Permits combinations with a variety of characteristics thanks to the different rated currents and characteristics of the FAZ-miniature circuit breakers which can be connected • Comrehensive range of accessories suitable for subsequent installation onto FAZ • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. • Type -A: Protects against special forms of residual pulsating DC which have have not been smoothed. • Type -G: High reliability against unwanted tripping. Compulsory for any circuit where personal injury or damage to property may occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6). • Type -S: Selective residual current device sensitive to AC, type -S. Compulsory for systems with surge arresters downstream of the RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5). • Type -S/A: Additionally protects against special forms of residual pulsating pulsating DC which have not been smoothed. Accessories: Cover cap for draw-out connection bar Slotted one-way cheese head screw included included Accessories (on FAZ): Auxiliary switch for subsequent installation ZP-IHK ZP-WHK ZP-NHK Z-FW/LP Z-FW-LPD Z-FW-MO Z-FW-LP/MO Z-FW-LPD/MO Z-FW/001 Z-FW/003 Z-FW/010 Z-FW/030 Z-FW/050 ZP-ASA/.. Z-USA Z-USD IS/SPE-1TE Tripping signal contact for subsequent installation Automatic restarting device Remote control Pre-mounted sets Remote testing module Shunt trip release Undervoltage release Switching interlock Cap for lead seal 2-pole Cap for lead seal 3-pole 286052 286053 248437 248296 265244 284730 290171 290172 248297 248298 248299 248300 248301 248438, 248439 258288, 248289, 248290 248292, 248291 101911 280971500 280971600 Connection diagram 2-pole 2 4 3-pole T 2 4 6 2’ 4’ 4-pole T 2 4 6 8N 2’ 4’ 6’ T 2’ 4’ 6’ 8N’ Chapter 3.1.1. – 60 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Technical Data FBSmV Electrical Design according to Current test marks as printed onto the device Tripping Type G Type S Rated voltage Rated frequency Rated tripping current Rated non-tripping current Sensitivity Rated current Service short circuit breaking capacity Rated breaking capacity Rated fault breaking capacity Un = 240V Un = 415V Mechanical Frame size Device height Device width Mounting Degree of protection switch Degree of protection, built-in Fastening screw Screw head breaking torque Upper and lower terminals Terminal screws Terminal protection Terminal capacity Rigid conductors Flexible conductors (with wire end sleeve) Busbar thickness Ambient temperature range Storage- and transport temperature Resistance to climatic conditions IEC/EN 61009 Un IΔn IΔno In Ics Icn instantaneous 250A (8/20µs), surge current-proof 10 ms delay 3kA (8/20µs), surge current-proof 40 ms delay 5kA (8/20µs) with selective disconnecting function, surge current-proof 240/415V AC 50 Hz 30, 100, 300, 500, 1000 mA 0.5 IΔn AC and pulsating DC ≤ 40 A, ≤ 63 A same as connected FAZ (7.5 kA) same as connected FAZ (10 kA) IΔm 6 kA 3 kA 45 mm 90 mm 70 mm (2p), 107.5 mm (3p), 125 mm (4p) fix mounted onto FAZ IP20 IP40 M2.5 (slotted one-way cheese head screw) > 0.6 Nm lift terminals M5 (combined Philips/standard head screws according to DIN7962-Z2, Pozidrive) finger and hand touch safe, BGV A3, ÖVE-EN 6 1 x (1 - 25) mm2 1 x (0.75 - 16) mm2 0.8 - 2 mm -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 Dimensions (mm) Chapter 3.1.1. – 61 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Add-on Residual Current Protection Unit FBHmV SG17711 • By combining this device with a top-quality miniature circuit breaker of type AZ a top-quality RCBO unit (combined RCD/MCB device) is formed. • Add-on residual current unit (screw connection) for 80 or 125 A (2-pole and 4-pole) • High flexibility and ease of installation thanks to variable wiring • Free selection of main power supply • Auxiliary switch 1 make contact included as standard in all FBHmV versions • Permits combinations with a variety of characteristics thanks to the different rated currents and characteristics of the miniature circuit breakers AZ which can be connected • For commercial and industry applications • For subsequent mounting onto 2, 3, 3+N and 4-pole-miniature circuit breakers AZ • The screw connection to the AZ-device can be unscrewed at any time. Consequently, in case of modifications of the systems to be protected, the installation can be adapted to new requirements at any time. Chapter 3.1.1. – 62 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Add-on Residual Current Protection Unit FBHmV type AC Conditionally surge-current-proof 250 A, type AC In/IΔn (A) SG17611 Article No. Units per package FBHmV-80/2/003 FBHmV-125/2/003 FBHmV-80/2/03 FBHmV-125/2/03 FBHmV-80/2/05 FBHmV-125/2/05 FBHmV-80/2/1 FBHmV-125/2/1 170266 170242 170243 170244 170245 170246 170247 170248 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 FBHmV-80/4/003 FBHmV-125/4/003 FBHmV-80/4/03 FBHmV-125/4/03 FBHmV-80/4/05 FBHmV-125/4/05 FBHmV-80/4/1 FBHmV-125/4/1 170249 170250 170251 170252 170253 170254 170255 170256 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 Type Designation Article No. Units per package FBHmV-80/2/003-A FBHmV-125/2/003-A FBHmV-80/2/03-A FBHmV-125/2/03-A FBHmV-80/2/05-A FBHmV-125/2/05-A FBHmV-80/2/1-A FBHmV-125/2/1-A 170257 170258 170259 170260 170261 170262 170263 170264 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 FBHmV-80/4/003-A FBHmV-125/4/003-A FBHmV-80/4/03-A FBHmV-125/4/03-A FBHmV-80/4/05-A FBHmV-125/4/05-A FBHmV-80/4/1-A FBHmV-125/4/1-A 170265 170130 170131 170132 170133 170134 170135 170136 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 2-pole 80/0.03 125/0.03 80/0.3 125/0.3 80/0.5 125/0.5 80/1 125/1 SG17711 Type Designation 4-pole 80/0.03 125/0.03 80/0.3 125/0.3 80/0.5 125/0.5 80/1 125/1 Add-on Residual Current Protection Unit FBHmV type A Sensitive to residual pulsating DC, conditionally surge current-proof 250 A, type A In/IΔn (A) SG17611 2-pole 80/0.03 125/0.03 80/0.3 125/0.3 80/0.5 125/0.5 80/1 125/1 SG17711 4-pole 80/0.03 125/0.03 80/0.3 125/0.3 80/0.5 125/0.5 80/1 125/1 Chapter 3.1.1. – 63 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Add-on Residual Current Protection Unit FBHmV type S/A Selective + surge current-proof 5 kA, type S/A In/IΔn (A) SG17611 Article No. Units per package FBHmV-80/2/03-S/A FBHmV-125/2/03-S/A FBHmV-80/2/05-S/A FBHmV-125/2/05-S/A FBHmV-80/2/1-S/A FBHmV-125/2/1-S/A 170137 170138 170139 170140 170141 170170 1/4 1/4 1/4 1/4 1/4 1/4 FBHmV-80/4/03-S/A FBHmV-125/4/03-S/A FBHmV-80/4/05-S/A FBHmV-125/4/05-S/A FBHmV-80/4/1-S/A FBHmV-125/4/1-S/A 170171 170172 170173 170174 170175 170176 1/4 1/4 1/4 1/4 1/4 1/4 2-pole 80/0.3 125/0.3 80/0.5 125/0.5 80/1 125/1 SG17711 Type Designation 4-pole 80/0.3 125/0.3 80/0.5 125/0.5 80/1 125/1 Chapter 3.1.1. – 64 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Specifications | Add-on Residual Current Protection Unit FBHmV Description • By combination with miniature circuit breaker AZ => RCBO-Unit (MCCB) • Add-on residual current unit (screw connection) for 80 or 125 A (2-pole and 4-pole) • High flexibility and ease of installation thanks to variable wiring (400 mm flexible connection wires 2p = 2 units, 4p = 4 units included in the set) • Free selection of main power supply • Auxiliary switch 1 NO included as standard in all FBHmV versions • Permits combinations with a variety of characteristics thanks to the different rated currents and characteristics of the miniature circuit breakers AZ which can be connected • For trade and industry applications • For subsequent mounting onto 2, 3, 3+N and 4-pole-miniature circuit breakers AZ • Toggle (serves as switch position- and tripping indicator) • The screw connection to the AZ-device can be unscrewed at any time. Consequently, in case of modifications of the systems to be protected, the installation can be adapted to new requirements at any time. • The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). • Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make earthing resistance measurement (RE), or proper checking of the earth conductor condition redundant, which must be performed separately. Accessories: Flexible connection wires (connection to AZ) are included in the standard set: 2-pole 80A 4-pole 80A 2-pole 125A 4-pole 125A 2 x 16mm2 (400mm each) 4 x 16mm2 (400mm each) 2 x 35mm2 (400mm each) 4 x 35mm2 (400mm each) Connection diagram 2-pole 4-pole Chapter 3.1.1. – 65 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Technical Data FBHmV Electrical current flow paths Design according to Current test marks as printed onto the device Tripping Type S Rated voltage Rated frequency Rated tripping current Rated non-tripping current Sensitivity Rated current Rated service short circuit breaking capacity Rated ultimate circuit breaking capacity Rated fault short circuit breaking capacity Rated impulse withstand voltage Endurance electrical components 80A 125A mechanical components 80A 125A Electrical Auxiliary Contact Utilisation category AC15 Rated voltage Rated operational current Mechanical Frame size Device height Device width Depth of central body Mounting Degree of protection switch Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity Main conductor Auxiliary switch Ambient temperature range Storage- and transport temperature Resistance to climatic conditions IEC/EN 61009 Un IΔn IΔno In Icn Icu IΔ/n Uimp instantaneous 250A (8/20µs), surge current-proof 40 ms delay 5kA (8/20µs) with selective disconnecting function, surge current-proof 240/415V AC 50 Hz 30, 300, 500, 1000 mA 0.5 IΔn AC and pulsating DC 80, 125 A same as connected AZ same as connected AZ = Icu 4 kV (1.2/50µs) ≥ 1,500 operating cycles ≥ 1,000 operating cycles ≥ 10,000 operating cycles ≥ 8,000 operating cycles Ue Ie 250 V AC 16 A AC 45 mm 90 mm 95 mm (5.5MU) 60 mm screwed onto AZ 2-, 3-, 4-pole; Z-BHASA IP20 IP40 lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 2.5 - 50 mm2 1 - 25 mm2 -25°C to +40°C -35°C to +60°C 25-55°C/90-95% relative humidity acc. to IEC 60068-2 Dimensions (mm) FBHmV/2p + AZ/2p FBHmV/4p + AZ/3p+N FBHmV/4p + AZ/3p FBHmV/4p + AZ/4p Chapter 3.1.1. – 66 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Wiring options Mounting FBHmV + AZ SG15402 SG15102 FBHmV + AZ Connection FBHmV/4p + AZ/3p FBHmV/4p SG15202 AZ/3p SG15302 Mounting arrangement residual current protection unit - shunt trip release - miniature circuit breaker - auxiliary contact FBHmV-2-pole Z-BHASA FBHmV-4-pole FBHmV-3+N-pole Z-LHK 13 1 21 + + + 22 2 Chapter 3.1.1. – 67 14 EATON CORPORATION xxxxx+xxxx-xxxxEN Add-on Residual Current Protection Specifications | Accessories for FBHmV - Shunt Trip Release Z-BHASA Description • Can be mounted subsequently • Contact position indicator red - green • Marking labels can be fitted • Wide operational voltage range • Sufficient power of extra low voltage source must be ensured ZBHASA/24: min. 90 VA • Screws for mounting included FBHmV => BHASA => AZ Electrical Minimum pulse duration Internal resistance Duty Tripping time Peak withstand voltage (1.2/50µs) Endurance electrical components mechanical components AC voltage range: Responding limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption DC voltage range: Responding limit DC voltage range Maximum current consumption during switch-on Current flow time at max. current consumption Mechanical Frame size Device height Device width Mounting Degree of protection switch Degree of protection, built-in Upper and lower terminals Terminal protection Terminal capacity Fastening torque of terminal screws Z-BHASA/24 Z-BHASA/230 15 ms 2Ω 100% < 20 ms 2 kV 10 ms 130 Ω 100% < 20 ms 2 kV ≥ 4,000 operating cycles ≥ 4,000 operating cycles 8V 12-60 V 1.4-7 A 4.0 ms 70 V 110-415 V 3.4 A (at 230V) 4.5 ms 11 V 12-60 V 1.7 A typ. 2 ms 90 V 110-230 V 1.7 A typ. 4 ms 45 mm 45 mm 90 mm 90 mm 27 mm 27 mm quick fastening on DIN rail IEC/EN 60715 IP20 IP20 IP40 IP40 lift terminals lift terminals finger and hand touch safe, BGV A3, ÖVE-EN 6 2.5 - 30 mm2 2.5 - 30 mm2 4 Nm 4 Nm Connection diagram 2-pole 1 2 Dimensions (mm) Chapter 3.1.1. – 68 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Miniature Circuit Breakers FAZ, FAZ-PN, FAZ-HS SG07211 FAZ • High-quality miniature circuit breakers for industrial applications and residential applications • Contact position indicator red - green • Guide for secure terminal connection • 3-position DIN rail clip, permits removal from existing busbar system • Comprehensive range of accessories suitable for subsequent installation • Rated currents up to 63 A • Tripping characteristics B, C, D, K, S, Z • Rated breaking capacity up to 15 kA according to IEC/EN 60898-1 FAZ-PN • Tripping characteristic B • Rated breaking capacity up to 6 kA according to IEC/EN 60898-1 • Module width 1MU (1+N-poles) FAZ-HS • Tripping characteristic B • Rated breaking capacity up to 10 kA according to IEC/EN 60898-1 • 1- and 2-poles available Chapter 4.1.1. – 1 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ Miniature Circuit Breakers (MCBs) Characteristic B Rated Rated current voltage In (A) (V) SG06811 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 1-pole 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG06911 Breaking capacity acc. to IEC/EN 60947-2 (kA) 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-B1/1 FAZ-B1,5/1 FAZ-B1,6/1 FAZ-B2/1 FAZ-B2,5/1 FAZ-B3/1 FAZ-B3,5/1 FAZ-B4/1 FAZ-B5/1 FAZ-B6/1 FAZ-B8/1 FAZ-B10/1 FAZ-B12/1 FAZ-B13/1 FAZ-B15/1 FAZ-B16/1 FAZ-B20/1 FAZ-B25/1 FAZ-B32/1 FAZ-B40/1 FAZ-B50/1 FAZ-B63/1 278520 278521 278522 278523 278524 278525 278526 278527 278528 278529 278530 278531 278532 278533 278534 278535 278536 278537 278538 278539 278540 278541 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-B1/1N FAZ-B1,5/1N FAZ-B1,6/1N FAZ-B2/1N FAZ-B2,5/1N FAZ-B3/1N FAZ-B3,5/1N FAZ-B4/1N FAZ-B5/1N FAZ-B6/1N FAZ-B8/1N FAZ-B10/1N FAZ-B12/1N FAZ-B13/1N FAZ-B15/1N FAZ-B16/1N FAZ-B20/1N FAZ-B25/1N FAZ-B32/1N FAZ-B40/1N FAZ-B50/1N FAZ-B63/1N 278633 278634 278635 278636 278637 278638 278639 278640 278641 278642 278643 278644 278645 278646 278647 278648 278649 278650 278651 278652 278653 278654 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1+N-pole 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 Chapter 4.1.1. – 2 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07011 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-B1/2 FAZ-B1,5/2 FAZ-B1,6/2 FAZ-B2/2 FAZ-B2,5/2 FAZ-B3/2 FAZ-B3,5/2 FAZ-B4/2 FAZ-B5/2 FAZ-B6/2 FAZ-B8/2 FAZ-B10/2 FAZ-B12/2 FAZ-B13/2 FAZ-B15/2 FAZ-B16/2 FAZ-B20/2 FAZ-B25/2 FAZ-B32/2 FAZ-B40/2 FAZ-B50/2 FAZ-B63/2 278719 278720 278721 278722 278723 278724 278725 278726 278727 278728 278729 278730 278731 278732 278733 278734 278735 278736 278737 278738 278739 278740 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-B1/3 FAZ-B1,5/3 FAZ-B1,6/3 FAZ-B2/3 FAZ-B2,5/3 FAZ-B3/3 FAZ-B3,5/3 FAZ-B4/3 FAZ-B5/3 FAZ-B6/3 FAZ-B8/3 FAZ-B10/3 FAZ-B12/3 FAZ-B13/3 FAZ-B15/3 FAZ-B16/3 FAZ-B20/3 FAZ-B25/3 FAZ-B32/3 FAZ-B40/3 FAZ-B50/3 FAZ-B63/3 278832 278833 278834 278835 278836 278837 278838 278839 278840 278841 278842 278843 278844 278845 278846 278847 278848 278849 278850 278851 278852 278853 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 2-pole 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG07111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Chapter 4.1.1. – 3 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07311 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-B1/3N FAZ-B1,5/3N FAZ-B1,6/3N FAZ-B2/3N FAZ-B2,5/3N FAZ-B3/3N FAZ-B3,5/3N FAZ-B4/3N FAZ-B5/3N FAZ-B6/3N FAZ-B8/3N FAZ-B10/3N FAZ-B12/3N FAZ-B13/3N FAZ-B15/3N FAZ-B16/3N FAZ-B20/3N FAZ-B25/3N FAZ-B32/3N FAZ-B40/3N FAZ-B50/3N FAZ-B63/3N 278934 278935 278936 278937 278938 278939 278940 278941 278942 278943 278944 278945 278946 278947 278948 278949 278950 278951 278952 278953 278954 278955 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-B1/4 FAZ-B1,5/4 FAZ-B1,6/4 FAZ-B2/4 FAZ-B2,5/4 FAZ-B3/4 FAZ-B3,5/4 FAZ-B4/4 FAZ-B5/4 FAZ-B6/4 FAZ-B8/4 FAZ-B10/4 FAZ-B12/4 FAZ-B13/4 FAZ-B15/4 FAZ-B16/4 FAZ-B20/4 FAZ-B25/4 FAZ-B32/4 FAZ-B40/4 FAZ-B50/4 FAZ-B63/4 279020 279021 279022 279023 279024 279025 279026 279027 279028 279029 279030 279031 279032 279033 279034 279035 279036 279037 279038 279039 279040 279041 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 3+N-pole 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG07211 Breaking capacity acc. to IEC/EN 60947-2 (kA) 4-pole 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Chapter 4.1.1. – 4 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ Miniature Circuit Breakers (MCBs) Characteristic C Rated Rated current voltage In (A) (V) SG06811 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 1-pole 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG06911 Breaking capacity acc. to IEC/EN 60947-2 (kA) 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-C0,16/1 FAZ-C0,25/1 FAZ-C0,5/1 FAZ-C0,75/1 FAZ-C1/1 FAZ-C1,5/1 FAZ-C1,6/1 FAZ-C2/1 FAZ-C2,5/1 FAZ-C3/1 FAZ-C3,5/1 FAZ-C4/1 FAZ-C5/1 FAZ-C6/1 FAZ-C8/1 FAZ-C10/1 FAZ-C12/1 FAZ-C13/1 FAZ-C15/1 FAZ-C16/1 FAZ-C20/1 FAZ-C25/1 FAZ-C32/1 FAZ-C40/1 FAZ-C50/1 FAZ-C63/1 278542 278543 278544 278545 278546 278547 278548 278549 278550 278551 278552 278553 278554 278555 278556 278557 278558 278559 278560 278561 278562 278563 278564 278565 278566 278567 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-C0,16/1N FAZ-C0,25/1N FAZ-C0,5/1N FAZ-C0,75/1N FAZ-C1/1N FAZ-C1,5/1N FAZ-C1,6/1N FAZ-C2/1N FAZ-C2,5/1N FAZ-C3/1N FAZ-C3,5/1N FAZ-C4/1N FAZ-C5/1N FAZ-C6/1N FAZ-C8/1N FAZ-C10/1N FAZ-C12/1N FAZ-C13/1N FAZ-C15/1N FAZ-C16/1N FAZ-C20/1N FAZ-C25/1N FAZ-C32/1N FAZ-C40/1N FAZ-C50/1N FAZ-C63/1N 278655 278656 278657 278658 278659 278660 278661 278662 278663 278664 278665 278666 278667 278668 278669 278670 278671 278672 278673 278674 278675 278676 278677 278678 278679 278680 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1+N-pole 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 Chapter 4.1.1. – 5 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07011 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-C0,16/2 FAZ-C0,25/2 FAZ-C0,5/2 FAZ-C0,75/2 FAZ-C1/2 FAZ-C1,5/2 FAZ-C1,6/2 FAZ-C2/2 FAZ-C2,5/2 FAZ-C3/2 FAZ-C3,5/2 FAZ-C4/2 FAZ-C5/2 FAZ-C6/2 FAZ-C8/2 FAZ-C10/2 FAZ-C12/2 FAZ-C13/2 FAZ-C15/2 FAZ-C16/2 FAZ-C20/2 FAZ-C25/2 FAZ-C32/2 FAZ-C40/2 FAZ-C50/2 FAZ-C63/2 278741 278742 278743 278744 278745 278746 278747 278748 278749 278750 278751 278752 278753 278754 278755 278756 278757 278758 278759 278760 278761 278762 278763 278764 278765 278766 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-C0,16/3 FAZ-C0,25/3 FAZ-C0,5/3 FAZ-C0,75/3 FAZ-C1/3 FAZ-C1,5/3 FAZ-C1,6/3 FAZ-C2/3 FAZ-C2,5/3 FAZ-C3/3 FAZ-C3,5/3 FAZ-C4/3 FAZ-C5/3 FAZ-C6/3 FAZ-C8/3 FAZ-C10/3 FAZ-C12/3 FAZ-C13/3 FAZ-C15/3 FAZ-C16/3 FAZ-C20/3 FAZ-C25/3 FAZ-C32/3 FAZ-C40/3 FAZ-C50/3 FAZ-C63/3 278854 278855 278856 278857 278858 278859 278860 278861 278862 278863 278864 278865 278866 278867 278868 278869 278870 278871 278872 278873 278874 278875 278876 278877 278878 278879 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 2-pole 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG07111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Chapter 4.1.1. – 6 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07311 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-C0,16/3N FAZ-C0,25/3N FAZ-C0,5/3N FAZ-C0,75/3N FAZ-C1/3N FAZ-C1,5/3N FAZ-C1,6/3N FAZ-C2/3N FAZ-C2,5/3N FAZ-C3/3N FAZ-C3,5/3N FAZ-C4/3N FAZ-C5/3N FAZ-C6/3N FAZ-C8/3N FAZ-C10/3N FAZ-C12/3N FAZ-C13/3N FAZ-C15/3N FAZ-C16/3N FAZ-C20/3N FAZ-C25/3N FAZ-C32/3N FAZ-C40/3N FAZ-C50/3N FAZ-C63/3N 278956 278957 278958 278959 278960 278961 278962 278963 278964 278965 278966 278967 278968 278969 278970 278971 278972 278973 278974 278975 278976 278977 278978 278979 278980 278981 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 FAZ-C0,16/4 FAZ-C0,25/4 FAZ-C0,5/4 FAZ-C0,75/4 FAZ-C1/4 FAZ-C1,5/4 FAZ-C1,6/4 FAZ-C2/4 FAZ-C2,5/4 FAZ-C3/4 FAZ-C3,5/4 FAZ-C4/4 FAZ-C5/4 FAZ-C6/4 FAZ-C8/4 FAZ-C10/4 FAZ-C12/4 FAZ-C13/4 FAZ-C15/4 FAZ-C16/4 FAZ-C20/4 FAZ-C25/4 FAZ-C32/4 FAZ-C40/4 FAZ-C50/4 FAZ-C63/4 279042 279043 279044 279045 279046 279047 279048 279049 279050 279051 279052 279053 279054 279055 279056 279057 279058 279059 279060 279061 279062 279063 279064 279065 279066 279067 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 3+N-pole 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG07211 Breaking capacity acc. to IEC/EN 60947-2 (kA) 4-pole 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Chapter 4.1.1. – 7 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ Miniature Circuit Breakers (MCBs) Characteristic D Rated Rated current voltage In (A) (V) SG06811 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 1-pole 0.5 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG06911 Breaking capacity acc. to IEC/EN 60947-2 (kA) 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 10 10 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 - 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 - FAZ-D0,5/1 FAZ-D1/1 FAZ-D1,5/1 FAZ-D1,6/1 FAZ-D2/1 FAZ-D2,5/1 FAZ-D3/1 FAZ-D3,5/1 FAZ-D4/1 FAZ-D5/1 FAZ-D6/1 FAZ-D8/1 FAZ-D10/1 FAZ-D12/1 FAZ-D13/1 FAZ-D15/1 FAZ-D16/1 FAZ-D20/1 FAZ-D25/1 FAZ-D32/1 FAZ-D40/1 FAZ-D50/1 FAZ-D63/1 278568 278569 278570 278571 278572 278573 278574 278575 278576 278577 278578 278579 278580 278581 278582 278583 278584 278585 278586 278587 278588 115370 115371 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 10 10 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 - 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 - FAZ-D0,5/1N FAZ-D1/1N FAZ-D1,5/1N FAZ-D1,6/1N FAZ-D2/1N FAZ-D2,5/1N FAZ-D3/1N FAZ-D3,5/1N FAZ-D4/1N FAZ-D5/1N FAZ-D6/1N FAZ-D8/1N FAZ-D10/1N FAZ-D12/1N FAZ-D13/1N FAZ-D15/1N FAZ-D16/1N FAZ-D20/1N FAZ-D25/1N FAZ-D32/1N FAZ-D40/1N FAZ-D50/1N FAZ-D63/1N 278681 278682 278683 278684 278685 278686 278687 278688 278689 278690 278691 278692 278693 278694 278695 278696 278697 278698 278699 278700 278701 115378 115379 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1+N-pole 0.5 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 Chapter 4.1.1. – 8 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07011 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 10 10 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 - 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 - FAZ-D0,5/2 FAZ-D1/2 FAZ-D1,5/2 FAZ-D1,6/2 FAZ-D2/2 FAZ-D2,5/2 FAZ-D3/2 FAZ-D3,5/2 FAZ-D4/2 FAZ-D5/2 FAZ-D6/2 FAZ-D8/2 FAZ-D10/2 FAZ-D12/2 FAZ-D13/2 FAZ-D15/2 FAZ-D16/2 FAZ-D20/2 FAZ-D25/2 FAZ-D32/2 FAZ-D40/2 FAZ-D50/2 FAZ-D63/2 278767 278768 278769 278770 278771 278772 278773 278774 278775 278776 278777 278778 278779 278780 278781 278782 278783 278784 278785 278786 278787 115372 115373 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 10 10 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 - 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 - FAZ-D0,5/3 FAZ-D1/3 FAZ-D1,5/3 FAZ-D1,6/3 FAZ-D2/3 FAZ-D2,5/3 FAZ-D3/3 FAZ-D3,5/3 FAZ-D4/3 FAZ-D5/3 FAZ-D6/3 FAZ-D8/3 FAZ-D10/3 FAZ-D12/3 FAZ-D13/3 FAZ-D15/3 FAZ-D16/3 FAZ-D20/3 FAZ-D25/3 FAZ-D32/3 FAZ-D40/3 FAZ-D50/3 FAZ-D63/3 278880 278881 278882 278883 278884 278885 278886 278887 278888 278889 278890 278891 278892 278893 278894 278895 278896 278897 278898 278899 278900 115374 115375 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 2-pole 0,5 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG07111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 0.5 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Chapter 4.1.1. – 9 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07311 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 10 10 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 - 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 - FAZ-D,5/3N FAZ-D1/3N FAZ-D1,5/3N FAZ-D1,6/3N FAZ-D2/3N FAZ-D2,5/3N FAZ-D3/3N FAZ-D3,5/3N FAZ-D4/3N FAZ-D5/3N FAZ-D6/3N FAZ-D8/3N FAZ-D10/3N FAZ-D12/3N FAZ-D13/3N FAZ-D15/3N FAZ-D16/3N FAZ-D20/3N FAZ-D25/3N FAZ-D32/3N FAZ-D40/3N FAZ-D50/3N FAZ-D63/3N 278982 278983 278984 278985 278986 278987 278988 278989 278990 278991 278992 278993 278994 278995 278996 278997 278998 278999 279000 279001 279002 115380 115381 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 10 10 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 - 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 - FAZ-D0,5/4 FAZ-D1/4 FAZ-D1,5/4 FAZ-D1,6/4 FAZ-D2/4 FAZ-D2,5/4 FAZ-D3/4 FAZ-D3,5/4 FAZ-D4/4 FAZ-D5/4 FAZ-D6/4 FAZ-D8/4 FAZ-D10/4 FAZ-D12/4 FAZ-D13/4 FAZ-D15/4 FAZ-D16/4 FAZ-D20/4 FAZ-D25/4 FAZ-D32/4 FAZ-D40/4 FAZ-D50/4 FAZ-D63/4 279068 279069 279070 279071 279072 279073 279074 279075 279076 279077 279078 279079 279080 279081 279082 279083 279084 279085 279086 279087 279088 115376 115377 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 3+N-pole 0.5 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 SG07211 Breaking capacity acc. to IEC/EN 60947-2 (kA) 4-pole 0.5 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Chapter 4.1.1. – 10 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ Miniature Circuit Breakers (MCBs) Characteristic K Rated Rated current voltage In (A) (V) SG06811 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 1-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 SG06911 Breaking capacity acc. to IEC/EN 60947-2 (kA) 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-K0,5/1 FAZ-K1/1 FAZ-K1,6/1 FAZ-K2/1 FAZ-K3/1 FAZ-K4/1 FAZ-K6/1 FAZ-K8/1 FAZ-K10/1 FAZ-K13/1 FAZ-K16/1 FAZ-K20/1 FAZ-K25/1 FAZ-K32/1 FAZ-K40/1 FAZ-K50/1 FAZ-K63/1 278589 278590 278591 278592 278593 278594 278595 278596 278597 278598 278599 278600 278601 278602 278603 278604 278605 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-K0,5/1N FAZ-K1/1N FAZ-K1,6/1N FAZ-K2/1N FAZ-K3/1N FAZ-K4/1N FAZ-K6/1N FAZ-K8/1N FAZ-K10/1N FAZ-K13/1N FAZ-K16/1N FAZ-K20/1N FAZ-K25/1N FAZ-K32/1N FAZ-K40/1N FAZ-K50/1N FAZ-K63/1N 278702 278703 278704 278705 278706 278707 278708 278709 278710 278711 278712 278713 278714 278715 278716 278717 278718 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1+N-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 Chapter 4.1.1. – 11 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07011 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-K0,5/2 FAZ-K1/2 FAZ-K1,6/2 FAZ-K2/2 FAZ-K3/2 FAZ-K4/2 FAZ-K6/2 FAZ-K8/2 FAZ-K10/2 FAZ-K13/2 FAZ-K16/2 FAZ-K20/2 FAZ-K25/2 FAZ-K32/2 FAZ-K40/2 FAZ-K50/2 FAZ-K63/2 278788 278789 278790 278791 278792 278793 278794 278795 278796 278797 278798 278799 278800 278801 278802 278803 278804 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-K0,5/3 FAZ-K1/3 FAZ-K1,6/3 FAZ-K2/3 FAZ-K3/3 FAZ-K4/3 FAZ-K6/3 FAZ-K8/3 FAZ-K10/3 FAZ-K13/3 FAZ-K16/3 FAZ-K20/3 FAZ-K25/3 FAZ-K32/3 FAZ-K40/3 FAZ-K50/3 FAZ-K63/3 278901 278902 278903 278904 278905 278906 278907 278908 278909 278910 278911 278912 278913 278914 278915 278916 278917 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 2-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 SG07111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Chapter 4.1.1. – 12 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07311 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-K0,5/3N FAZ-K1/3N FAZ-K1,6/3N FAZ-K2/3N FAZ-K3/3N FAZ-K4/3N FAZ-K6/3N FAZ-K8/3N FAZ-K10/3N FAZ-K13/3N FAZ-K16/3N FAZ-K20/3N FAZ-K25/3N FAZ-K32/3N FAZ-K40/3N FAZ-K50/3N FAZ-K63/3N 279003 279004 279005 279006 279007 279008 279009 279010 279011 279012 279013 279014 279015 279016 279017 279018 279019 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-K0,5/4 FAZ-K1/4 FAZ-K1,6/4 FAZ-K2/4 FAZ-K3/4 FAZ-K4/4 FAZ-K6/4 FAZ-K8/4 FAZ-K10/4 FAZ-K13/4 FAZ-K16/4 FAZ-K20/4 FAZ-K25/4 FAZ-K32/4 FAZ-K40/4 FAZ-K50/4 FAZ-K63/4 279089 279090 279091 279092 279093 279094 279095 279096 279097 279098 279099 279100 279101 279102 279103 279104 279105 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 3+N-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 SG07211 Breaking capacity acc. to IEC/EN 60947-2 (kA) 4-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Chapter 4.1.1. – 13 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ Miniature Circuit Breakers (MCBs) Characteristic S Rated Rated current voltage In (A) (V) SG06811 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 1-pole 1 2 3 4 6 10 16 20 25 32 40 SG07011 Breaking capacity acc. to IEC/EN 60947-2 (kA) 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 10 10 10 10 10 10 10 10 10 10 10 277 277 277 277 277 277 277 277 277 277 277 5 5 5 5 5 5 5 5 5 5 5 FAZ-S1/1 FAZ-S2/1 FAZ-S3/1 FAZ-S4/1 FAZ-S6/1 FAZ-S10/1 FAZ-S16/1 FAZ-S20/1 FAZ-S25/1 FAZ-S32/1 FAZ-S40/1 278606 278607 278608 278609 278610 278611 278612 278613 278614 278615 278616 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 10 10 10 10 10 10 10 10 10 10 10 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 FAZ-S1/2 FAZ-S2/2 FAZ-S3/2 FAZ-S4/2 FAZ-S6/2 FAZ-S10/2 FAZ-S16/2 FAZ-S20/2 FAZ-S25/2 FAZ-S32/2 FAZ-S40/2 278805 278806 278807 278808 278809 278810 278811 278812 278813 278814 278815 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 2-pole 1 2 3 4 6 10 16 20 25 32 40 Chapter 4.1.1. – 14 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ Miniature Circuit Breakers (MCBs) Characteristic Z Rated Rated current voltage In (A) (V) SG06811 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 1-pole 0,5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 SG07011 Breaking capacity acc. to IEC/EN 60947-2 (kA) 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-Z0,5/1 FAZ-Z1/1 FAZ-Z1,6/1 FAZ-Z2/1 FAZ-Z3/1 FAZ-Z4/1 FAZ-Z6/1 FAZ-Z8/1 FAZ-Z10/1 FAZ-Z13/1 FAZ-Z16/1 FAZ-Z20/1 FAZ-Z25/1 FAZ-Z32/1 FAZ-Z40/1 FAZ-Z50/1 FAZ-Z63/1 278617 278618 278619 278620 278621 278622 278623 278624 278625 106020 278626 278627 278628 278629 278630 278631 278632 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-Z0,5/2 FAZ-Z1/2 FAZ-Z1,6/2 FAZ-Z2/2 FAZ-Z3/2 FAZ-Z4/2 FAZ-Z6/2 FAZ-Z8/2 FAZ-Z10/2 FAZ-Z13/2 FAZ-Z16/2 FAZ-Z20/2 FAZ-Z25/2 FAZ-Z32/2 FAZ-Z40/2 FAZ-Z50/2 FAZ-Z63/2 278816 278817 278818 278819 278820 278821 278822 278823 278824 106021 278825 278826 278827 278828 278829 278830 278831 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 2-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Chapter 4.1.1. – 15 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage (V) In (A) SG07111 Rated voltage UL1077 (V) Breaking capacity acc. to UL1077 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-Z0,5/3 FAZ-Z1/3 FAZ-Z1,6/3 FAZ-Z2/3 FAZ-Z3/3 FAZ-Z4/3 FAZ-Z6/3 FAZ-Z8/3 FAZ-Z10/3 FAZ-Z13/3 FAZ-Z16/3 FAZ-Z20/3 FAZ-Z25/3 FAZ-Z32/3 FAZ-Z40/3 FAZ-Z50/3 FAZ-Z63/3 278918 278919 278920 278921 278922 278923 278924 278925 278926 106022 278927 278928 278929 278930 278931 278932 278933 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 FAZ-Z0,5/4 FAZ-Z1/4 FAZ-Z1,6/4 FAZ-Z2/4 FAZ-Z3/4 FAZ-Z4/4 FAZ-Z6/4 FAZ-Z8/4 FAZ-Z10/4 FAZ-Z13/4 FAZ-Z16/4 FAZ-Z20/4 FAZ-Z25/4 FAZ-Z32/4 FAZ-Z40/4 FAZ-Z50/4 FAZ-Z63/4 279106 279107 279108 279109 279110 279111 279112 279113 279114 106023 279115 279116 279117 279118 279119 279120 279121 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 SG07211 Breaking capacity acc. to IEC/EN 60947-2 (kA) 4-pole 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Chapter 4.1.1. – 16 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-PN Miniature Circuit Breakers (MCBs) Characteristic B Rated Rated current voltage In (A) (V) SG08311 Breaking capacity acc. to IEC/EN 60898-1 (kA) Breaking capacity acc. to IEC/EN 60947-2 (kA) Type Designation Article No. Units per package FAZ-PN-B6/1N FAZ-PN-B10/1N FAZ-PN-B13/1N FAZ-PN-B16/1N FAZ-PN-B20/1N FAZ-PN-B25/1N FAZ-PN-B32/1N FAZ-PN-B40/1N 279146 279147 279148 279149 279150 279151 279152 279153 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 Type Designation Article No. Units per package FAZ-PN-C2/1N FAZ-PN-C4/1N FAZ-PN-C6/1N FAZ-PN-C10/1N FAZ-PN-C13/1N FAZ-PN-C16/1N FAZ-PN-C20/1N FAZ-PN-C25/1N FAZ-PN-C32/1N FAZ-PN-C40/1N 279154 279155 279156 279157 279158 279159 279160 279161 279162 279163 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 1+N-pole (1MU) 6 10 13 16 20 25 32 40 240 240 240 240 240 240 240 240 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10 FAZ-PN Miniature Circuit Breakers (MCBs) Characteristic C Rated Rated current voltage In (A) (V) SG08311 Breaking capacity acc. to IEC/EN 60898-1 (kA) Breaking capacity acc. to IEC/EN 60947-2 (kA) 1+N-pole (1MU) 2 4 6 10 13 16 20 25 32 40 240 240 240 240 240 240 240 240 240 240 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10 10 10 Chapter 4.1.1. – 17 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-HS Miniature Circuit Breakers (MCBs) Characteristic B Rated Rated current voltage In (A) (V) SG08411 Type Designation Article No. Units per package 240 10 FAZ-B4/1-HS 279274 12/120 240 10 FAZ-B4/2-HS 279275 1/60 1-pole 4 SG12911 Breaking capacity acc. to IEC/EN 60898-1 (kA) 2-pole 4 FAZ Miniature Circuit Breakers Accessories: Auxiliary switch for subsequent installation Auxiliary switch for subsequent installation Tripping signal contact for subsequent installation Shunt trip release Undervoltage release ZP-IHK ZP-WHK ZP-NHK ZP-ASA Z-USA Z-USD Chapter 4.1.1. – 18 286052 286053 248437 248438, 248439 258288, 248289, 248290 248292, 248291 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications FAZ Technical data B Curve Electrical Approvals Standards Short-circuit trip response Supplementary Protectors—UL/CSA Current range Maximum voltage ratings—UL/CSA Single-pole Two-, three-pole Two poles in series Thermal tripping characteristics Single-pole Multi-pole Short-circuit ratings (at max. voltage) Single-pole Two-, three-pole Single-pole Two poles in series Miniature Circuit Breaker—IEC Current range Maximum voltage ratings—IEC 60947-2 Single-pole Two-, three-pole Maximum Voltage Ratings—IEC 60898 Single-pole Two-, three-pole Thermal tripping characteristics Single-pole Multi-pole Interrupt ratings (at max. voltage) IEC 60947-2 IEC 60898 Operational switching capacity Max. back-up fuse [gL/gG] Rated impulse withstand—Uimp Rated insulation voltage—Ui Environmental/General Selectivity class Lifespan (operations) Shock (IEC 68-2-22) Operating temperature range Mechanical Standard front dimension Device height Terminal protection Mounting width per pole Mounting Degree of protection Terminals top and bottom Supply connection Terminal capacity [mm2] Torque Thickness of busbar material Mounting position C Curve D Curve UR (UL 1077), CSA (CSA 22.2 No. 235) IEC/EN 60947-2 3–5 In 5–10 In 10–20 In 1–63A 0.5–63A 0.5–40A 277 Vac 48 Vdc 480Y/277 Vac 96 Vdc 277 Vac 48 Vdc 480Y/277 Vac 96 Vdc 277 Vac 48 Vdc 480Y/277 Vac 96 Vdc 1.35 x In @ 40°C 1.45 x In @ 40°C 1.35 x In @ 40°C 1.45 x In @ 40°C 1.35 x In @ 40°C 1.45 x In @ 40°C 10 kA (5 kA for 40–63A device) 10 kA (5 kA for 40–63A device) 10 kA @ 48 Vdc 10 kA @ 96 Vdc 10 kA (5 kA for 40–63A device) 10 kA (5 kA for 40–63A device) 10 kA @ 48 Vdc 10 kA @ 96 Vdc 5 kA 5 kA 10 kA @ 48 Vdc 10 kA @ 96 Vdc 1–63A 0.5–63A 0.5–63A 230 Vac 48 Vdc 230/400 Vac 230 Vac 48 Vdc 230/400 Vac 230 Vac 48 Vdc 230/400 Vac 240 Vac 48 Vdc 240/415 Vac 240 Vac 48 Vdc 240/415 Vac 240 Vac 48 Vdc 240/415 Vac > 1 hour @ 1.05 x In < 1 hour @ 1.3 x In > 1 hour @ 1.05 x In < 1 hour @ 1.3 x In > 1 hour @ 1.05 x In < 1 hour @ 1.3 x In 15 kA 10 kA 7.5 kA 125A 4000 Vac 440 Vac 15 kA 10 kA 7.5 kA 125A 4000 Vac 440 Vac 15 kA 10 kA 7.5 kA 125A 4000 Vac 440 Vac 3 > 10000 (1 operation = ON/OFF) 10g–120 ms -40 to +75°C 3 > 10000 (1 operation = ON/OFF) 10g–120 ms -40 to +75°C 3 > 10000 (1 operation = ON/OFF) 10g–120 ms -40 to +75°C 80 mm Finger and back-of-hand proof 17.5 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 / 2 x 10 2.4 Nm 0.8–2 mm As required 80 mm Finger and back-of-hand proof 17.5 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 / 2 x 10 2.4 Nm 0.8–2 mm As required 80 mm Finger and back-of-hand proof 17.5 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 / 2 x 10 2.4 Nm 0.8–2 mm As required Chapter 4.1.1. – 19 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications FAZ Technical Data (continued) K Curve Electrical Approvals Standards Short-circuit trip response Supplementary Protectors—UL/CSA Current range Maximum voltage ratings—UL/CSA Single-pole, single-pole + neutral Two-, three-, four-pole and three-pole + neutral Two poles in series Thermal tripping characteristics Single-pole Multi-pole Short-circuit ratings (at max. voltage) Single-pole Single-pole + neutral Two-, three-, four-pole Miniature Circuit Breaker—IEC Current range Maximum voltage ratings—IEC 60947-2 Single-pole, single-pole + neutral Two-, three-, four-pole, three-pole + neutral Thermal tripping characteristics Single-pole Multi-pole Interrupt ratings (at max. voltage) IEC 60947-2 IEC 60898 Operational switching capacity Max. back-up fuse [gL/gG] Rated impulse withstand—Uimp Rated insulation voltage—Ui Environmental/General Selectivity class Lifespan (operations) Shock (IEC 68-2-22) Operating temperature range Mechanical Standard front dimension Device height Terminal protection Mounting width per pole Mounting Degree of protection Terminals top and bottom Supply connection Terminal capacity [mm2] Torque Thickness of busbar material Mounting position S Curve Z Curve UR (UL 1077), CSA (CSA 22.2 No. 235), CE, VDE IEC/EN 60947-2 8–12 In 13–17 In 2–3 In 0.5–63A 0.5–40A 1–63A 277 Vac 48 Vdc 277 Vac 48 Vdc 277 Vac 48 Vdc 480Y/277 Vac 96 Vdc 480Y/277 Vac 96 Vdc 480Y/277 Vac 96 Vdc 1.35 x In @ 40°C 1.45 x In @ 40°C 1.35 x In @ 40°C 1.45 x In @ 40°C 1.35 x In @ 40°C 1.45 x In @ 40°C 5 kA @ 277 Vac 5 kA @ 277 Vac 5 kA @ 480Y/277 Vac 5 kA @ 277 Vac 5 kA @ 277 Vac 5 kA @ 480Y/277 Vac 5 kA @ 277 Vac 5 kA @ 277 Vac 5 kA @ 480Y/277 Vac 0.5–63A 0.5–40A 1–63A 240 Vac 240 Vac 240 Vac 240/415 Vac 240/415 Vac 240/415 Vac > 1 hour @ 1.05 x In < 1 hour @ 1.3 x In > 1 hour @ 1.05 x In < 1 hour @ 1.3 x In > 1 hour @ 1.05 x In < 1 hour @ 1.3 x In 15 kA 15 kA 7.5 kA 125A 4000 Vac 440 Vac 10 kA 10 kA 7.5 kA 125A 4000 Vac 440 Vac 10 kA 10 kA 7.5 kA 125A 4000 Vac 440 Vac 3 > 10000 (1 operation = ON/OFF) 10g–120 ms -5 to +40°C 3 > 10000 (1 operation = ON/OFF) 10g–120 ms -5 to +40°C 3 > 10000 (1 operation = ON/OFF) 10g–120 ms -5 to +40°C 80 mm Finger and back-of-hand proof 17.5 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 / 2 x 10 2.4 Nm 0.8–2 mm As required 80 mm Finger and back-of-hand proof 17.5 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 / 2 x 10 2.4 Nm 0.8–2 mm As required 80 mm Finger and back-of-hand proof 17.5 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 / 2 x 10 2.4 Nm 0.8–2 mm As required Connection diagram 1-pole 1+N-pole (2MU) 2-pole 3-pole 3+N-pole Chapter 4.1.1. – 20 4-pole EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Dimensions (mm) FAZ 1-pole 1+N-pole, 2-pole 3-pole 3+N-pole, 4-pole Chapter 4.1.1. – 21 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Tripping Characteristic FAZ Characteristics B, C and D - IEC/EN60898-1 Characteristic K - IEC/EN 60947-2 Characteristic S - IEC/EN 60947-2 Characteristic S - UL1077 Chapter 4.1.1. – 22 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Tripping Characteristic FAZ Characteristic Z - IEC/EN 60947-2 Characteristic Z - UL1077 Chapter 4.1.1. – 23 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Internal Resistance FAZ Type B Type C At room temperature (single pole) In [A] 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 * 50Hz Z* [mΩ] 1120 922 922 335 234 211 184 87.7 73.5 46.8 30.5 17.5 16.9 13.4 8.0 8.0 7.2 5.0 3.7 2.6 2.1 2.0 R [mΩ] 1102 912 912 333 230 208 180 87.2 72.8 46.3 30.4 17.4 16.8 13.3 7.9 7.9 7.1 4.9 3.7 2.5 2.1 2.0 At room temperature (single pole) In [A] 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 * 50Hz Z* [mΩ] 68500 27500 4680 2280 1120 589 589 335 234 131 143 87.7 73.5 39.3 30.5 14.1 13.5 13.4 8.0 8.0 7.2 5.0 3.7 2.6 2.1 2.0 R [mΩ] 68300 27400 4670 2250 1100 587 587 333 230 130 141 87.2 72.8 39.1 30.4 14.0 13.4 13.3 7.9 7.9 7.1 4.9 3.7 2.5 2.1 2.0 Type D At room temperature (single pole) In [A] 0.5 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 * 50Hz Z* [mΩ] 4680 772 512 512 250 153 131 143 87.7 65.4 39.3 19.5 14.1 11.3 10.1 8.0 8.0 4.9 3.9 3.5 2.7 R [mΩ] 4670 770 508 508 249 153 130 141 87.2 65.1 39.1 19.5 14.0 11.2 10.1 7.9 7.9 4.9 3.8 3.4 2.6 Chapter 4.1.1. – 24 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Fault Loop Impedance FAZ Max. allowed value for the Fault Loop Impedance ZS (acc. to DIN VDE 0100, part 410) U0 = 230 V Tripping time In/A 1 1.5 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Type B 0,4s Zs (Ω) 40,4 26,9 20,2 16,1 13,5 11,5 10,1 8,1 6,7 5,0 4,0 3,4 3,1 2,7 2,5 2,0 1,6 1,3 1,0 0,8 0,6 5s Zs (Ω) 40,4 26,9 20,2 16,1 13,5 11,5 10,1 8,1 6,7 5,0 4,0 3,4 3,1 2,7 2,5 2,0 1,6 1,3 1,0 0,8 0,6 Type C 0,4s Zs (Ω) 24,3 16,2 12,2 9,7 8,1 7,0 6,1 4,9 4,1 3,0 2,4 2,0 1,9 1,6 1,5 1,2 1,0 0,8 0,6 0,5 0,4 5s Zs (Ω) 40,4 26,9 20,2 16,1 13,5 11,5 10,1 8,1 6,7 5,0 4,0 3,4 3,1 2,7 2,5 2,0 1,6 1,3 1,0 0,8 0,6 Type D 0,4s Zs (Ω) 12,4 8,3 6,2 5,0 4,1 3,6 3,1 2,5 2,1 1,6 1,2 1,0 1,0 0,8 0,8 0,6 0,5 0,4 0,3 0,2 0,2 5s Zs (Ω) 40,4 26,9 20,2 16,1 13,5 11,5 10,1 8,1 6,7 5,0 4,0 3,4 3,1 2,7 2,5 2,0 1,6 1,3 1,0 0,8 0,6 Zs=RM.C.B.+RLoop Data/factors taken from the time-current characteristic FAZ For other rated voltages U0: U0 = 240 V: Zs * 1,04 applies U0 = 127 V: Zs * 0,55 applies Chapter 4.1.1. – 25 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Power Loss at In FAZ Type B Type C 1p In [A] P [W] 1 1.6 1.5 2.3 1.6 2.5 2 1.4 2.5 1.5 3 2.5 3.5 2.5 4 1.4 5 1.9 6 1.8 8 2.1 10 1.9 12 2.8 13 2.5 15 2.1 16 2.2 20 3.2 25 3.0 32 3.7 40 3.4 50 4.5 63 5.2 *symmetrical load 1pN 2p 3p 3pN* P [W] 1.7 2.5 2.7 1.5 1.7 2.7 2.8 1.6 2.1 2.0 2.3 2.1 3.2 2.9 2.4 2.6 3.6 3.5 4.4 4.1 5.4 6.3 P [W] 3.1 4.6 4.9 2.8 3.1 5.0 5.1 2.9 3.8 3.6 4.1 3.9 5.9 5.3 4.4 4.7 6.6 6.4 8.1 7.5 9.9 11.5 P [W 4.7 6.9 7.4 4.1 4.6 7.6 7.8 4.4 5.8 5.5 6.3 5.9 8.7 7.8 6.5 6.9 9.8 9.4 12.1 11.2 14.9 17.2 P [W] 4.8 7.2 7.6 4.3 4.7 7.8 8.0 4.5 6.0 5.6 6.5 6.1 9.0 8.1 6.7 7.2 10.1 9.7 12.5 11.5 15.3 17.7 1pN 2p 3p 3pN* P [W] 1.3 0.9 1.3 1.4 1.1 1.1 1.3 1.4 1.6 1.8 1.6 1.5 1.7 2.0 2.2 2.4 2.6 2.2 2.9 4.0 3.8 P [W] 2.4 1.6 2.3 2.5 2.0 1.9 2.4 2.6 2.9 3.3 2.9 2.6 3.0 3.6 4.0 4.4 4.7 4.1 5.2 7.4 7.0 P [W 3.5 2.4 3.5 3.8 3.0 2.9 3.6 3.9 4.4 5.1 4.4 4.0 4.6 5.3 5.9 6.5 6.9 6.1 7.7 11.1 10.4 P [W] 3.7 2.5 3.6 3.9 3.1 3.0 3.7 4.0 4.5 5.3 4.6 4.2 4.7 5.4 6.1 6.7 7.2 6.2 7.9 11.4 10.7 1p In [A] P [W] 0.16 2.2 0.25 2.0 0.5 1.2 0.75 1.3 1 1.6 1.5 1.5 1.6 1.6 2 1.4 2.5 1.5 3 1.2 3.5 1.3 4 1.4 5 1.9 6 1.5 8 2.1 10 1.5 12 2.1 13 2.5 15 2.1 16 2.2 20 3.2 25 3.0 32 3.7 40 3.4 50 4.5 63 5.2 *symmetrical load 1pN 2p 3p 3pN* P [W] 2.4 2.2 1.3 1.4 1.7 1.6 1.7 1.5 1.7 1.3 1.4 1.6 2.1 1.6 2.3 1.7 2.4 2.9 2.4 2.6 3.6 3.5 4.4 4.1 5.4 6.3 P [W] 4.4 4.0 2.4 2.6 3.1 2.9 3.1 2.8 3.1 2.4 2.6 2.9 3.8 2.9 4.1 3.0 4.4 5.3 4.4 4.7 6.6 6.4 8.1 7.5 9.9 11.5 P [W 6.7 6.1 3.5 3.9 4.7 4.4 4.7 4.1 4.6 3.6 3.9 4.4 5.8 4.4 6.3 4.6 6.5 7.8 6.5 6.9 9.8 9.4 12.1 11.2 14.9 17.2 P [W] 6.9 6.3 3.7 4.1 4.8 4.6 4.9 4.3 4.7 3.7 4.0 4.5 6.0 4.6 6.5 4.7 6.8 8.1 6.7 7.2 10.1 9.7 12.5 11.5 15.3 17.7 Type D 1p In [A] P [W] 0.5 1.2 1 0.8 1.5 1.2 1.6 1.3 2 1.0 2.5 1.0 3 1.2 3.5 1.3 4 1.4 5 1.7 6 1.5 8 1.3 10 1.5 12 1.7 13 1.9 15 2.1 16 2.2 20 2.0 25 2.5 32 3.4 40 3.2 *symmetrical load Chapter 4.1.1. – 26 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Influence of Ambient Temperature FAZ On Load Carrying Capacity (temperature derating) IN [A] 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 Ambient temperature T [°C] -40 -30 -20 -10 0.2 0.2 0.19 0.19 0.32 0.31 0.3 0.29 0.64 0.62 0.6 0.58 0.96 0.93 0.9 0.87 1.3 1.2 1.2 1.2 1.9 1.9 1.8 1.7 2 2 1.9 1.9 2.6 2.5 2.4 2.3 3.2 3.1 3 2.9 3.8 3.7 3.6 3.5 4.5 4.4 4.2 4.1 5.1 5 4.8 4.7 6.4 6.2 6 5.8 7.7 7.5 7.2 7 10.2 9.9 9.6 9.3 13 12 12 12 15 15 14 14 17 16 16 15 19 19 18 17 20 20 19 19 26 25 24 23 32 31 30 29 41 40 38 37 51 50 48 47 64 62 60 58 81 78 76 73 0 0.18 0.28 0.56 0.84 1.1 1.7 1.8 2.2 2.8 3.4 3.9 4.5 5.6 6.7 9 11 13 15 17 18 22 28 36 45 56 71 10 0.17 0.27 0.54 0.81 1.1 1.6 1.7 2.2 2.7 3.3 3.8 4.3 5.4 6.5 8.7 11 13 14 16 17 22 27 35 43 54 68 20 0.17 0.26 0.52 0.78 1 1.6 1.7 2.1 2.6 3.1 3.7 4.2 5.2 6.3 8.4 10 13 14 16 17 21 26 33 42 52 66 30 0.16 0.25 0.5 0.75 1 1.5 1.6 2 2.5 3 3.5 4 5 6 8 10 12 13 15 16 20 25 32 40 50 63 35 0.16 0.25 0.49 0.74 0.99 1.5 1.6 2 2.5 3 3.4 3.9 4.9 5.9 7.9 9.9 12 13 15 16 20 25 32 39 49 62 Chapter 4.1.1. – 27 40 0.15 0.24 0.48 0.73 0.97 1.5 1.5 1.9 2.4 2.9 3.4 3.9 4.8 5.8 7.7 9.7 12 13 15 15 19 24 31 39 48 61 45 0.15 0.24 0.47 0.71 0.95 1.4 1.5 1.9 2.4 2.8 3.3 3.8 4.7 5.7 7.6 9.5 11 12 14 15 19 24 30 38 47 60 50 0.15 0.23 0.46 0.69 0.93 1.4 1.5 1.9 2.3 2.8 3.2 3.7 4.6 5.6 7.4 9.3 11 12 14 15 19 23 30 37 46 58 55 0.14 0.23 0.45 0.68 0.9 1.4 1.4 1.8 2.3 2.7 3.2 3.6 4.5 5.4 7.2 9 11 12 14 14 18 23 29 36 45 57 60 0.14 0.22 0.44 0.66 0.89 1.3 1.4 1.8 2.2 2.7 3.1 3.5 4.4 5.3 7.1 8.9 11 12 13 14 18 22 28 35 44 56 65 0.14 0.22 0.43 0.65 0.87 1.3 1.4 1.7 2.2 2.6 3 3.5 4.3 5.2 6.9 8.7 10 11 13 14 17 22 28 35 43 55 70 0.14 0.21 0.42 0.64 0.85 1.3 1.4 1.7 2.1 2.5 3 3.4 4.2 5.1 6.8 8.5 10 11 13 14 17 21 27 34 42 53 75 0.13 0.21 0.41 0.62 0.83 1.2 1.3 1.7 2.1 2.5 2.9 3.3 4.1 5 6.6 8.3 10 11 12 13 17 21 26 33 41 52 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Energy FAZ Type B (IEC/EN60947-2) Type C (IEC/EN60947-2) Type D (IEC/EN60947-2) Type K Chapter 4.1.1. – 28 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Energy FAZ Type S Type Z Type FAZ-...-HS Chapter 4.1.1. – 29 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Current FAZ Type B (IEC/EN60898) Type C (IEC/EN60898) Type D (IEC/EN60898) Type K Chapter 4.1.1. – 30 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Current FAZ Type S Type B (IEC/EN60947-2) Type C (IEC/EN60947-2) Type D (IEC/EN60947-2) Chapter 4.1.1. – 31 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Short Circuit Selectivity FAZ towards NH-00 Fuses In case of short circuit, there is selectivity between the miniature circuit breakers FAZ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic B towards fuse link NH-00*) Short circuit selectivity characteristic C towards fuse link NH-00*) FAZ FAZ NH-00 gL/gG In [A] 16 20 1.0 0.9 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 0.75 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 0.8 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 0.9 2.0 <0.51) 0.5 2.5 <0.51) 0.5 3.0 <0.51) 0.5 3.5 <0.51) 0.9 4 <0.51) <0.51) 0.8 5 <0.51) 0.7 1.1 1.6 2.2 3.6 4.8 6 <0.51) <0.51) 0.7 1.1 1.5 2.0 3.3 4.3 8 <0.51) 0.5 <0.51) <0.51) 25 32 35 40 50 63 80 100 125 160 NH-00 gL/gG In [A] 16 25 32 35 40 50 63 80 100 125 160 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 2.5 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 <0.51) 0.6 1.3 4.2 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 2.3 10.02) 10.02) 10.02) 2.0 <0.51) 0.6 1.0 2.5 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 0.9 2.1 8.0 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 2.5 <0.51) 0.5 1.0 2.1 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.8 5.5 10.02) 10.02) 10.02) 3.0 <0.51) 0.7 1.2 1.8 2.6 4.7 6.6 10.02) 10.02) 10.02) 10.02) 1.3 2.3 4.3 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) <0.51) 3.5 <0.51) <0.51) 0.7 1.1 1.7 2.4 4.2 6.0 10.02) 10.02) 10.02) 10.02) 8.9 10.02) 10.02) 4 <0.51) 0.7 1.0 1.5 2.1 3.6 5.0 10.0 10.02) 10.02) 10.02) 7.6 10.02) 10.02) 10.02) 5 <0.51) <0.51) 0.6 0.8 1.2 1.7 2.8 3.8 8.7 10.02) 10.02) 10.02) 10.02) 10.02) 6 <0.51) 0.5 0.8 1.2 1.5 2.5 3.3 5.7 10.02) 10.02) 10.02) <0.51) <0.51) 0.5 0.8 1.1 1.5 2.3 2.9 4.9 10.02) 10.02) 10.02) 0.5 0.7 1.0 1.4 2.0 2.5 3.8 8.0 10.02) 10.02) 10.02) 0.6 1.0 1.3 1.7 2.6 3.3 5.2 10.02) 10 <0.51) 0.6 0.9 1.2 1.5 2.2 2.7 4.0 9.0 10.02) 10.02) 8 13 <0.51) 10.02) 10 16 20 <0.51) <0.51) 0.6 0.8 1.1 1.4 2.1 2.6 3.8 7.9 10.02) 0.5 0.7 1.0 1.3 1.9 2.4 3.4 6.4 9.3 10.02) 13 1.0 1.3 1.9 2.4 3.6 7.0 10.02) 10.02) 16 1.0 1.3 1.8 2.3 3.3 6.0 8.8 10.02) 1.0 1.2 1.7 2.2 3.2 5.5 7.7 10.02) 1.6 2.1 3.0 5.2 7.3 10.02) 2.1 2.9 5.0 7.0 10.02) 2.8 4.8 6.7 10.0 4.5 6.3 9.5 5.9 8.4 20 0.7 1.0 1.3 1.9 2.4 3.3 6.0 8.7 10.02) 25 0.7 1.0 1.3 1.8 2.3 3.2 5.7 8.0 10.02) 20 25 2.2 3.1 5.4 7.6 10.02) 40 2.1 3.0 5.1 7.2 10.02) 32 50 1.9 2.8 4.7 6.6 9.5 40 4.4 6.3 8.6 50 32 0.9 1.2 1.7 63 63 Short circuit selectivity characteristic D towards fuse link NH-00*) FAZ NH-00 gL/gG In [A] 16 20 25 32 35 40 50 63 80 100 125 160 0.5 2.1 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 <0.51) 0,6 1.4 4.3 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 <0.51) 0.9 1.6 2.7 4.0 8.0 10.02) 10.02) 10.02) 10.02) 10.02) 2.0 <0.51) <0.51) 0.8 1.3 2.1 3.1 6.0 8.6 10.02) 10.02) 10.02) 10.02) 2.5 <0.51) 0.7 1.2 1.8 2.6 4.8 6.9 10.02) 10.02) 10.02) 10.02) 3.0 <0.51) <0.51) 0.7 1.1 1.7 2.4 4.3 6.0 10.02) 10.02) 10.02) 10.02) 3.5 <0.51) 0.7 1.1 1.7 2.4 4.2 5.6 10.02) 10.02) 10.02) 10.02) 4 <0.51) <0.51) 0.7 1.0 1.6 2.2 3.8 5.2 10.0 10.02) 10.02) 10.02) <0.51) <0.51) <0.51) 5 <0.51) 0.6 0.9 1.4 1.9 3.2 4.1 7.1 10.02) 10.02) 10.02) 6 <0.51) 0.5 0.8 1.2 1.6 2.6 3.3 5.5 10.02) 10.02) 10.02) 8 0.5 0.8 1.1 1.5 2.2 2.7 4.1 8.7 10.02) 10.02) 10 0.5 0.7 1.0 1.3 1.9 2.5 3.6 7.2 10.02) 10.02) 1.0 1.3 1.9 2.3 3.4 6.5 9.5 10.02) 1.1 1.6 2.0 3.0 5.5 8.0 10.02) 1.4 1.8 2.8 5.0 7.5 10.02) 1.8 2.7 4.8 7.0 10.02) 13 16 20 25 32 40 2.4 4.1 6.2 9.3 4.0 6.0 9.0 1) Selectivity limit current Is under 0.5 kA Selectivity limit current Is = rated breaking capacity Icn of the MCB Shaded fields: no selectivity 2) Chapter 4.1.1. – 32 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Short Circuit Selectivity FAZ towards D01-D03 fuse link In case of short circuit, there is selectivity between the miniature circuit breakers FAZ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic B towards fuse link D01-D03*) Short circuit selectivity characteristic C towards fuse link D01-D03*) FAZ D01-D03 gL/gG FAZ In [A] 10 In [A] 10 1.0 <0.51) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 0.75 <0.51) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 <0.51) 4.1 1.0 <0.51) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 2.0 <0.51) <0.51) 0.6 2.5 <0.51) 16 20 25 35 50 63 80 100 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 10.02) 10.02) 10.02) 10.02) 10.02) 0.6 3.0 <0.51) <0.51) 0.5 3.5 <0.51) 0.5 0.9 4 <0.51) <0.51) 0.5 0.9 <0.51) <0.51) D01-D03 gL/gG 16 20 25 35 50 63 80 100 1.5 <0.51) 0.5 0.6 0.9 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 10.02) 10.02) 2.0 <0.51) 0.5 0.7 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) <0.51) 2.5 <0.51) <0.51) 0.5 0.7 10.02) 10.02) 10.02) 10.02) 10.02) 7.0 10.02) 10.02) 3.0 <0.51) 0.6 1.9 5.2 10.02) 10.02) 10.02) 2.5 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) <0.51) <0.51) 3.5 <0.51) <0.51) <0.51) 0.6 1.8 4.7 9.5 10.02) 10.02) 10.02) 4 <0.51) 0.6 1.6 4.0 7.6 10.02) 10.02) 5 <0.51) 0.5 0.8 1.7 4.0 7.0 10.02) 6 <0.51) 0.5 0.8 1.6 3.6 6.0 10.02) 10.02) 5 <0.51) <0.51) 0.5 1.3 3.1 5.7 10.02) 10.02) 6 <0.51) 1.2 2.7 4.5 10.02) 10.02) 8 <0.51) <0.51) <0.51) 1.2 2.5 4.0 8.6 10.02) 1.2 2.3 3.1 5.4 10.02) 8 0.5 0.8 1.4 2.8 4.3 8.2 10.02) 10 0.5 0.7 1.3 2.4 3.4 6.0 10.02) 13 <0.51) 10 <0.51) <0.51) <0.51) 0.7 1.2 2.3 3.2 5.3 10.02) 0.6 1.1 2.2 2.9 4.6 10.0 13 1.1 2.2 3.0 4.9 10.02) 20 1.1 2.1 2.8 4.4 9.3 16 1.1 2.1 2.8 4.4 9.5 25 1.1 2.0 2.7 4.2 8.7 20 1.0 2.0 2.6 4.0 8.3 16 32 2.6 4.0 8.0 25 40 2.0 2.5 3.8 7.5 32 50 2.3 3.4 6.7 40 6.2 50 63 <0.51) <0.51) <0.51) 1.9 2.5 3.8 7.8 2.5 3.7 7.3 3.5 7.0 6.5 63 Short circuit selectivity characteristic D towards fuse link D01-D03*) FAZ D01-D03 gL/gG In [A] 10 16 20 25 35 50 63 80 100 0.5 <0.51) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 <0.51) <0.51) 0.7 1.3 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 <0.51) 0.6 0.9 2.8 9.0 10.02) 10.02) 10.02) 2.0 <0.51) <0.51) 0.6 0.8 2.2 6.7 10.02) 10.02) 10.02) 2.5 <0.51) 0.5 0.7 1.9 5.4 10.02) 10.02) 10.02) 3.0 <0.51) <0.51) 0.5 0.7 1.8 4.8 9.3 10.02) 10.02) 3.5 <0.51) 0.5 0.7 1.7 4.7 8.6 10.02) 10.02) 4 <0.51) 0.5 0.7 1.7 4.6 7.7 10.02) 10.02) 5 <0.51) 0.6 1.5 3.5 5.8 10.02) 10.02) 6 <0.51) 0.5 1.3 2.9 4.5 9.0 10.02) 8 <0.51) 0.5 1.2 2.4 3.5 6.0 10.02) 0.5 1.1 2.2 3.0 5.0 10.02) 1.1 2.1 2.9 4.6 10.02) 16 1.9 2.6 3.9 9.0 20 1.7 10 13 25 32 <0.51) <0.51) <0.51) <0.51) 2.3 3.5 8.0 2.2 3.4 7.5 2.9 40 6.0 5.7 1) Selectivity limit current Is under 0.5 kA Selectivity limit current Is = rated breaking capacity Icn of the MCB Shaded fields: no selectivity 2) Chapter 4.1.1. – 33 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Short Circuit Selectivity FAZ towards DII-DIV fuse link In case of short circuit, there is selectivity between the miniature circuit breakers FAZ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic B towards fuse link DII-DIV*) Short circuit selectivity characteristic C towards fuse link DII-DIV*) FAZ FAZ DII-DIV gL/gG 16 20 25 35 50 63 80 100 DII-DIV gL/gG In [A] 10 In [A] 10 16 1.0 <0.51) 1.2 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 0.75 1.0 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 <0.51) 1.0 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.0 <0.51) 1.2 2.0 <0.51) <0.51) 0.8 2.5 <0.51) 1.6 10.02) 10.02) 10.02) 10.02) 10.02) 0.8 3.0 <0.51) <0.51) 0.8 3.5 <0.51) 20 25 35 50 63 80 100 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 <0.51) <0.51) 1.0 2.2 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 10.02) 10.02) 2.0 <0.51) 0.8 1.6 10.02) 10.02) 10.02) 10.02) 10.02) 1.4 10.02) 10.02) 10.02) 10.02) 10.02) 2.5 <0.51) <0.51) 0.8 1.4 10.02) 10.02) 10.02) 10.02) 10.02) 0.7 1.3 10.02) 10.02) 10.02) 3.0 <0.51) 0.8 0.9 10.02) 10.02) 10.02) 10.02) 10.02) 4 <0.51) <0.51) 0.6 1.0 3.6 10.02) 10.02) 10.02) 10.02) 5 <0.51) <0.51) <0.51) <0.51) 10.02) 10.02) 10.02) 10.02) 10.02) <0.51) <0.51) 3.5 <0.51) <0.51) 0.6 0.9 2.2 4.5 10.02) 10.02) 10.02) 10.02) 4 <0.51) 0.6 0.8 1.8 3.6 9.7 10.02) 10.02) 5 <0.51) <0.51) 0.6 0.7 1.5 2.7 7.3 10.02) 10.02) 0.6 0.9 2.0 3.5 8.5 10.02) 6 <0.51) 0.6 0.9 1.8 3.2 7.4 10.02) 10.02) 8 <0.51) 6 <0.51) 0.6 1.4 2.4 5.5 10.02) 10.02) 8 <0.51) <0.51) 0.6 1.3 2.2 4.7 8.7 10.02) 1.3 2.0 3.6 5.4 10.02) 10 0.5 0.8 1.6 2.6 5.2 8.3 10.02) 0.5 0.8 1.4 2.2 3.9 6.0 10.02) 10 <0.51) 0.5 0.7 1.3 2.0 3.6 5.4 10.02) 0.6 1.2 1.9 3.2 4.6 8.4 13 1.3 1.9 3.3 5.0 9.4 20 1.2 1.8 3.1 4.4 7.8 16 1.2 1.8 3.2 4.4 8.0 25 1.2 1.8 3.0 4.2 7.3 20 1.2 1.8 3.1 4.1 7.0 1.7 1.7 2.8 3.8 6.5 2.7 3.7 6.2 3.5 5.9 13 0.5 16 32 2.8 3.9 6.8 25 40 2.7 3.8 6.5 32 50 2.5 3.5 5.7 40 5.3 50 63 <0.51) 0.6 5.5 63 Short circuit selectivity characteristic D towards fuse link DII-DIV*) FAZ DII-DIV gL/gG In [A] 10 16 20 25 35 50 63 80 100 3.0 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 0.5 0.5 1.0 <0.51) <0.51) 1.0 2.4 10.02) 10.02) 10.02) 10.02) 10.02) 1.5 <0.51) 0.7 1.2 3.5 7.7 10.02) 10.02) 10.02) 2.0 <0.51) <0.51) 0.6 1.0 2.8 5.8 10.02) 10.02) 10.02) 2.5 <0.51) 0.6 1.4 2.3 4.6 10.02) 10.02) 10.02) 3.0 <0.51) <0.51) 0.6 0.9 2.3 4.3 10.02) 10.02) 10.02) 3.5 <0.51) 0.6 0.9 2.1 4.0 10.02) 10.02) 10.02) 4 <0.51) 0.6 0.9 2.0 3.8 9.5 10.02) 10.02) 5 <0.51) 0.5 0.7 1.7 3.1 7.0 10.02) 10.02) 6 0.5 0.7 1.5 2.6 5.3 9.1 10.02) 8 <0.51) 0.7 1.4 2.2 3.9 6.0 10.02) 0.7 1.2 1.9 3.4 5.0 9.5 1.2 10 13 <0.51) <0.51) <0.51) 1.8 3.2 4.6 8.6 16 1.6 2.7 4.0 7.4 20 1.5 2.5 3.5 6.7 2.4 3.4 6.2 2.8 5.0 25 32 40 4.8 1) Selectivity limit current Is under 0.5 kA Selectivity limit current Is = rated breaking capacity Icn of the MCB Shaded fields: no selectivity 2) Chapter 4.1.1. – 34 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Short-Circuit Selectivity Between FAZ-B and NZM 1/2 NZM FAZ Selectivity-limit current Is [kA] for selectivity between FAZ-B and NZM (overload and short-circuit release unit NZM at max. value). NZM...1-A... NZM...2-A... In [A] Icu = 25 (50) kA Icu = 25 (50)(100)(150) kA FAZ-B 40 50 63 80 100 125 40 50 63 80 100 125 160 200 250 1 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 2 2 15 15 15 15 15 3 15 15 15 15 15 15 15 15 3 1.2 2 3 3 10 15 1.5 1.5 3 5 15 15 15 15 15 4 1.2 2 3 3 8 15 1.2 1.5 3 4 15 15 15 15 15 6 1.2 2 2.5 3 5 10 1.2 1.5 2.5 3 15 15 15 15 15 10 1.2 1.5 2 2 4 10 1 1.5 2.5 3 10 10 10 10 10 13 1 1.5 2 2 4 10 1 1.2 2 3 10 10 10 10 10 16 1 1.2 1.5 2 3 8 1 1.2 1.5 2.5 10 10 10 10 10 20 0.8 1.2 1.5 1.5 3 8 1 1.2 1.5 1.5 10 10 10 10 10 25 0.7 1.2 1.5 1.5 3 7 0.8 1 1.5 2 10 10 10 10 10 32 - 1.2 1 1.5 2 6 - 1 1.5 2 8 8 8 8 10 40 - - 1 1.5 2 5 - - 1.2 1.5 7 7 7 7 10 50 - - - 1.2 1.5 4 - - - 1.5 6 6 6 6 10 63 - - - - 1.5 3 - - - - 6 6 6 6 10 Between FAZ-C and NZM 1/2 NZM FAZ Selectivity-limit current Is [kA] for selectivity between FAZ-C and NZM (overload and short-circuit release unit NZM at max. value). NZM...1-A... NZM...2-A... In [A] Icu = 25 (50) kA FAZ-C 40 50 63 80 100 125 Icu = 25 (50)(100)(150) kA 40 50 63 80 100 125 160 200 250 0.5 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 1 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 2 2 15 15 15 15 15 3 15 15 15 15 15 15 15 15 3 1.2 2 3 3 10 15 1.5 1.5 3 5 15 15 15 15 15 4 1.2 2 3 3 8 15 1.2 1.5 3 4 15 15 15 15 15 6 1.2 2 2.5 3 5 10 1.2 1.5 2.5 3 15 15 15 15 15 10 1.2 1.5 2 2 4 10 1 1.5 2.5 3 10 10 10 10 10 13 1 1.5 2 2 4 10 1 1.2 2 3 10 10 10 10 10 16 1 1.2 1.5 2 3 8 1 1.2 1.5 2.5 10 10 10 10 10 20 0.8 1.2 1.5 1.5 3 8 1 1.2 1.5 1.5 10 10 10 10 10 25 0.7 1.2 1.5 1.5 3 7 0.8 1 1.5 2 10 10 10 10 10 32 - 1.2 1 1.5 2 6 - 1 1.5 2 8 8 8 8 10 40 - - 1 1.5 2 5 - - 1.2 1.5 7 7 7 7 10 50 - - - 1.2 1.5 4 - - - 1.5 6 6 6 6 10 63 - - - - 1.5 3 - - - - 6 6 6 6 10 Chapter 4.1.1. – 35 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Short-Circuit Selectivity FAZ Between FAZ-D and NZM 1/2 NZM FAZ In [A] Selectivity-limit current Is [kA] for selectivity between FAZ-D and NZM (overload and short-circuit release unit NZM at max. value). NZM...1-A... NZM...2-A... Icu = 25 (50) kA Icu = 25 (50)(100)(150) kA FAZ-D 40 50 63 80 100 125 40 50 63 80 100 125 160 200 250 0.5 9 15 15 15 15 15 9 15 15 15 15 15 15 15 15 1 0.5 0.7 1.1 1.9 4.2 15 0.5 0.7 1.1 1.9 4.2 15 15 15 15 1.5 0.3 0.6 0.8 1.1 1.6 2.6 0.3 0.6 0.8 1.1 1.6 2.6 5 15 15 2 0.3 0.5 0.75 0.95 1.4 2.4 0.3 0.5 0.75 0.95 1.4 2.4 4.5 10 15 2.5 0.3 0.5 0.75 0.95 1.3 2.3 0.3 0.5 0.75 0.95 1.3 2.3 4.2 9 15 3 0.3 0.5 0.7 0.9 1.3 2.1 0.3 0.5 0.7 0.9 1.3 2.1 3.6 7 15 3.5 0.3 0.5 0.7 0.9 1.3 2 0.3 0.5 0.7 0.9 1.3 2 3.3 5.6 10 4 0.3 0.5 0.7 0.9 1.3 1.9 0.3 0.5 0.7 0.9 1.3 1.9 3 4.7 8 5 0.3 0.5 0.7 0.9 1.3 1.9 0.3 0.5 0.7 0.9 1.3 1.9 3 4.4 7 6 0.3 0.5 0.6 0.9 1.3 1.8 0.3 0.5 0.6 0.9 1.3 1.8 2.8 4 6 8 0.3 0.3 0.6 0.75 1 1.3 0.3 0.3 0.6 0.75 1 1.3 1.8 2.7 4 10 0.3 0.3 0.6 0.75 0.95 1.2 0.3 0.3 0.6 0.75 0.95 1.2 1.7 2.4 3.6 13 0.3 0.3 0.5 0.7 0.9 1.1 0.3 0.3 0.5 0.7 0.9 1.1 1.6 2.2 3.2 16 - 0.3 0.5 0.65 0.8 1.1 - 0.3 0.5 0.65 0.8 1.1 1.5 2.1 3 20 - - 0.5 0.65 0.8 1.1 - - 0.5 0.65 0.8 1.1 1.4 2.1 3 25 - - 0.5 0.65 0.8 1.1 - - 0.5 0.65 0.8 1.1 1.4 1.9 2.7 32 - - - - 0.8 1.1 - - - - 0.8 1.1 1.4 1.9 2.7 40 - - - - - 1 - - - - - 1 1.4 1.8 2.6 Chapter 4.1.1. – 36 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Back-up Protection FAZ FAZ/C through PLHT/C Upstream PLHT protects downstream FAZ up to the specified prospective short-circuit current. Test acc. to IEC 60947.2 -A.6 PLHT/C In [A] In [A] FAZ/C 20 25 32 40 50 63 80 100 125 1 25 25 25 25 25 25 20 20 15 kA 2 25 25 25 25 25 25 20 20 15 kA 4 25 25 25 25 25 25 20 20 15 kA 6 25 25 25 25 25 25 20 20 15 kA 10 25 25 25 25 25 25 20 20 15 kA 13 25 25 25 25 25 25 20 20 15 kA 16 25 25 25 25 25 25 20 20 15 kA 20 1) 25 25 25 25 25 20 20 15 kA 25 1) 1) 25 25 25 25 20 20 15 kA 32 1) 1) 1) 25 25 25 20 20 - 40 1) 1) 1) 1) 25 25 20 20 - 50 1) 1) 1) 1) 1) 25 20 20 - 63 1) 1) 1) 1) 1) 1) - - - 1) In (PLHT) ≤ In (FAZ) FAZ / NZM7 FAZ / CL-PKZ0 Back-up tests acc. to EN/IEC 60947-2, App. A: U = 1.05 Ue, (O - t - CO) FAZ-In/1(2,3,4)/B(C) + NZM7-40(...100) FAZ-In/1(2,3,4)/B(C) + CL-PKZ0 In [A] Ue = 230/400 V In [A] Ue = 230/400 V 0.16 65 kA 0.16 25 kA 0.25 65 kA 0.25 25 kA 0.5 65 kA 0.5 25 kA 0.75 65 kA 0.75 25 kA 1 65 kA 1 25 kA 1.5 65 kA 1.5 25 kA 2 65 kA 2 25 kA 2.5 65 kA 2.5 25 kA 3 65 kA 3 25 kA 3.5 65 kA 3.5 25 kA 4 65 kA 4 25 kA 5 45 kA 5 20 kA 6 45 kA 6 20 kA 8 45 kA 8 20 kA 10 45 kA 10 20 kA 12 45 kA 12 20 kA 13 45 kA 13 20 kA 15 45 kA 15 20 kA 16 45 kA 16 20 kA 20 45 kA 20 18 kA 25 45 kA 25 18 kA 32 45 kA 32 18 kA 40 25 kA 40 18 kA 50 25 kA 50 15 kA 63 25 kA 63 15 kA Chapter 4.1.1. – 37 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Back-up Protection FAZ FAZ / NZMB1 FAZ / NZMN1 Ue = 230/400 V: Icu (FAZ) = 15 kA Ue = 230/400 V: Icu (NZMB1) = 25 kA Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO) (Settings NZMB1: Ir, Irm at max. volumes) Ue = 230/400 V: Icu (FAZ) = 15 kA Ue = 230/400 V: Icu (NZMN1) = 25 kA Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO) (Settings NZM at max. values) FAZ-In/1(2,3,4)/B(C) + NZMB1 FAZ-In/1(2,3,4)/B(C) + NZMN1 In [A] Ue = 230/400 V In [A] Ue = 230/400 V 0.16 25 kA 0.16 25 kA 0.25 25 kA 0.25 25 kA 0.5 25 kA 0.5 25 kA 0.75 25 kA 0.75 25 kA 1 25 kA 1 25 kA 1.5 25 kA 1.5 25 kA 2 25 kA 2 25 kA 2.5 25 kA 2.5 25 kA 3 25 kA 3 25 kA 3.5 25 kA 3.5 25 kA 4 25 kA 4 25 kA 5 25 kA 5 25 kA 6 25 kA 6 25 kA 8 25 kA 8 25 kA 10 25 kA 10 25 kA 12 25 kA 12 25 kA 13 25 kA 13 25 kA 15 25 kA 15 25 kA 16 25 kA 16 25 kA 20 20 kA 20 20 kA 25 20 kA 25 20 kA 32 20 kA 32 20 kA 40 20 kA 40 20 kA 50 15 kA 50 15 kA 63 15 kA 63 15 kA Chapter 4.1.1. – 38 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Back-up Protection FAZ FAZ / NZMB2 FAZ / NZMN2 Ue = 230/400 V: Icu (FAZ) = 15 kA Ue = 230/400 V: Icu (NZMB2) = 25 kA Ue = 133/230 V: Icu (FAZ) = 20 kA Ue = 133/230 V: Icu (NZMB2) = 30 kA Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO) (Settings NZM at max. values) Ue = 230/400 V: Icu (FAZ) = 15 kA Ue = 230/400 V: Icu (NZMN2) = 50 kA Ue = 133/230 V: Icu (FAZ) = 20 kA Ue = 133/230 V: Icu (NZMN2) = 85 kA Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO) (Settings NZM at max. values) FAZ-In/1(2,3,4)/B(C) + NZMN2 FAZ-In/1(2,3,4)/B(C) + NZMB2 In [A] Ue = 230/400 V Ue = 133/230 V In [A] Ue = 230/400 V Ue = 133/230 V 0.16 25 kA 30 kA 0.16 50 kA 85 kA 0.25 25 kA 30 kA 0.25 50 kA 85 kA 0.5 25 kA 30 kA 0.5 50 kA 85 kA 0.75 25 kA 30 kA 0.75 50 kA 85 kA 1 25 kA 30 kA 1 50 kA 85 kA 1.5 25 kA 30 kA 1.5 50 kA 85 kA 2 25 kA 30 kA 2 50 kA 85 kA 2.5 25 kA 30 kA 2.5 50 kA 85 kA 3 25 kA 30 kA 3 50 kA 85 kA 3.5 25 kA 30 kA 3.5 50 kA 85 kA 4 25 kA 30 kA 4 50 kA 85 kA 5 25 kA 25 kA 5 50 kA 80 kA 6 25 kA 25 kA 6 50 kA 80 kA 8 25 kA 25 kA 8 50 kA 80 kA 10 25 kA 25 kA 10 50 kA 80 kA 12 20 kA 25 kA 12 30 kA 60 kA 13 20 kA 25 kA 13 30 kA 60 kA 15 20 kA 25 kA 15 30 kA 60 kA 16 20 kA 25 kA 16 30 kA 60 kA 20 20 kA 25 kA 20 30 kA 60 kA 25 20 kA 25 kA 25 30 kA 60 kA 32 20 kA 25 kA 32 30 kA 60 kA 40 15 kA 20 kA 40 20 kA 40 kA 50 15 kA 20 kA 50 20 kA 40 kA 63 15 kA 20 kA 63 20 kA 40 kA Chapter 4.1.1. – 39 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Back-up Protection FAZ FAZ / NZMH2 FAZ / NZML2 Ue = 230/400 V: Icu (FAZ) = 15 kA Ue = 230/400 V: Icu (NZMH2) = 150 kA Ue = 133/230 V: Icu (FAZ) = 20 kA Ue = 133/230 V: Icu (NZMH2) = 150 kA Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO) (Settings NZM at max. values) Ue = 230/400 V: Icu (FAZ) = 15 kA Ue = 230/400 V: Icu (NZML2) = 150 kA Ue = 133/230 V: Icu (FAZ) = 20 kA Ue = 133/230 V: Icu (NZML2) = 150 kA Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO) (Settings NZM at max. values) FAZ-In/1(2,3,4)/B(C) + NZML2 FAZ-In/1(2,3,4)/B(C) + NZMH2 In [A] Ue = 230/400 V Ue = 133/230 V In [A] Ue = 230/400 V Ue = 133/230 V 0.16 50 kA 85 kA 0.16 50 kA 85 kA 0.25 50 kA 85 kA 0.25 50 kA 85 kA 0.5 50 kA 85 kA 0.5 50 kA 85 kA 0.75 50 kA 85 kA 0.75 50 kA 85 kA 1 50 kA 85 kA 1 50 kA 85 kA 1.5 50 kA 85 kA 1.5 50 kA 85 kA 2 50 kA 85 kA 2 50 kA 85 kA 2.5 50 kA 85 kA 2.5 50 kA 85 kA 3 50 kA 85 kA 3 50 kA 85 kA 3.5 50 kA 85 kA 3.5 50 kA 85 kA 4 50 kA 85 kA 4 50 kA 85 kA 5 50 kA 80 kA 5 50 kA 80 kA 6 50 kA 80 kA 6 50 kA 80 kA 8 50 kA 80 kA 8 50 kA 80 kA 10 50 kA 80 kA 10 50 kA 80 kA 12 30 kA 60 kA 12 30 kA 60 kA 13 30 kA 60 kA 13 30 kA 60 kA 15 30 kA 60 kA 15 30 kA 60 kA 16 30 kA 60 kA 16 30 kA 60 kA 20 30 kA 60 kA 20 30 kA 60 kA 25 30 kA 60 kA 25 30 kA 60 kA 32 30 kA 60 kA 32 30 kA 60 kA 40 20 kA 40 kA 40 20 kA 40 kA 50 20 kA 40 kA 50 20 kA 40 kA 63 20 kA 40 kA 63 20 kA 40 kA Chapter 4.1.1. – 40 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Back-up Protection FAZ FAZ / NH Ue = 230 V: Icu (FAZ) = 15 (10) kA (acc. to IEC/EN 60947) Ue = 500 V: Icu (NH00 125 A gL / gG) = 120kA FAZ-In/B,(C),(D)... + NH00 125 A gL/gG In [A] IT-system U = 230 V 0.5 50 kA 1 50 kA 2 50 kA 3 50 kA 4 50 kA 6 50 kA 10 50 kA 13 50 kA 16 50 kA 20 50 kA 25 50 kA 32 50 kA 40 50 kA 50 50 kA 63 50 kA Chapter 4.1.1. – 41 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Overload Selectivity FAZ FAZ-B(C)(D) to FAZ-B FAZ Upstream side FAZ, Characteristic B Downstream side FAZ, Characteristic B, C, D FAZ x ... Selectivity range (i.e. only the downstream switch drops in case I< Is) Downstream side FAZ Characteristic B Upstream side FAZ Characteristic B Type B rated current In [A] 2 3 4 6 Selectivity limiting current Is [A] 7 10.5 14 21 2 x x x 3 x x 4 x 6 10 13 16 20 25 32 40 50 63 Downstream side FAZ Characteristic C Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 0.5 1 2 3 4 6 8 10 13 16 20 25 32 40 50 63 FAZ Characteristic B 2 3 4 6 7 10.5 14 21 x x x x x x x x x x x Downstream side FAZ Characteristic D Upstream side FAZ Characteristic B Type B rated current In [A] 2 3 4 6 Selectivity limiting current Is [A] 7 10.5 14 21 2 4 6 10 13 16 20 25 32 40 10 35 x x x x 13 45.5 x x x x x 16 56 x x x x x x 20 70 x x x x x x x 25 87.5 x x x x x x x x 32 112 x x x x x x x x x 40 140 x x x x x x x x x x 50 175 x x x x x x x x x x x 63 220.5 x x x x x x x x x x x x 10 35 x x x x x 13 45.5 x x x x x x 16 56 x x x x x x x 20 70 x x x x x x x x 25 87.5 x x x x x x x x x 32 112 x x x x x x x x x x 40 140 x x x x x x x x x x x 50 175 x x x x x x x x x x x x 63 220.5 x x x x x x x x x x x x x 10 35 x 13 45.5 x 16 56 x x 20 70 x x x 25 87.5 x x x 32 112 x x x x 40 140 x x x x x 50 175 x x x x x x 63 220.5 x x x x x x x Chapter 4.1.1. – 42 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Overload Selectivity FAZ FAZ-B(C)(D) to FAZ-C FAZ Upstream side FAZ, Characteristic C Downstream side FAZ, Characteristic B, C, D FAZ x ... Selectivity range (i.e. only the downstream switch drops in case I< Is) Downstream side FAZ Characteristic B Upstream side FAZ Characteristic C Type B rated current In [A] 0.5 1 2 3 Selectivity limiting current Is [A] 2.85 5.7 11.4 17.1 2 x 3 4 6 10 13 16 20 25 32 40 50 63 Downstream side FAZ Characteristic C Upstream side FAZ Characteristic C Type B rated current In [A] 0.5 1 2 3 Selectivity limiting current Is [A] 2.85 5.7 11.4 17.1 0.5 x x x 1 x x 2 x 3 4 6 8 10 13 16 20 25 32 40 50 63 Downstream side FAZ Characteristic D Upstream side FAZ Characteristic C Type B rated current In [A] 0.5 1 2 3 Selectivity limiting current Is [A] 2.85 5.7 11.4 17.1 2 4 6 10 13 16 20 25 32 40 4 22.8 x x 6 34.2 x x x 8 45.6 x x x x 10 57 x x x x 13 74.1 x x x x x 16 91.2 x x x x x x 20 114 x x x x x x x 25 142.5 x x x x x x x x 32 182.4 x x x x x x x x x 40 228 x x x x x x x x x x 50 285 x x x x x x x x x x x 63 359.1 x x x x x x x x x x x x 4 22.8 x x x x 6 34.2 x x x x x 8 45.6 x x x x x x 10 57 x x x x x x x 13 74.1 x x x x x x x x 16 91.2 x x x x x x x x x 20 114 x x x x x x x x x x 25 142.5 x x x x x x x x x x x 32 182.4 x x x x x x x x x x x x 40 228 x x x x x x x x x x x x x 50 285 x x x x x x x x x x x x x x 63 359.1 x x x x x x x x x x x x x x x 4 22.8 6 34.2 x 8 45.6 x x 10 57 x x 13 74.1 x x x 16 91.2 x x x 20 114 x x x x 25 142.5 x x x x x 32 182.4 x x x x x x 40 228 x x x x x x x 50 285 x x x x x x x x 63 359.1 x x x x x x x x Chapter 4.1.1. – 43 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Overload Selectivity FAZ FAZ-B(C)(D) to FAZ-D FAZ Upstream side FAZ, Characteristic D Downstream side FAZ, Characteristic B, C, D FAZ x ... Selectivity range (i.e. only the downstream switch drops in case I< Is) Downstream side FAZ Characteristic B Upstream side FAZ Characteristic D Type B rated current In [A] 2 4 6 10 Selectivity limiting current Is [A] 21 42 63 105 2 x x x 3 x x x 4 x x 6 x 10 13 16 20 25 32 40 50 63 Downstream side FAZ Characteristic C Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 0.5 1 2 3 4 6 8 10 13 16 20 25 32 40 50 63 FAZ Characteristic D 2 4 6 10 21 42 63 105 x x x x x x x x x x x x x x x x x x Downstream side FAZ Characteristic D Upstream side FAZ Characteristic D Type B rated current In [A] 2 4 6 10 Selectivity limiting current Is [A] 21 42 63 105 2 x x x 4 x x 6 x 10 13 16 20 25 32 40 13 136.5 x x x x x 16 168 x x x x x x 20 210 x x x x x x x 25 262.5 x x x x x x x x 32 336 x x x x x x x x x 40 420 x x x x x x x x x x 13 136.5 x x x x x x x x 16 168 x x x x x x x x x 20 210 x x x x x x x x x x 25 262.5 x x x x x x x x x x x 32 336 x x x x x x x x x x x x 40 420 x x x x x x x x x x x x x 13 136.5 x x x x 16 168 x x x x x 20 210 x x x x x x 25 262.5 x x x x x x x 32 336 x x x x x x x x 40 420 x x x x x x x x x Chapter 4.1.1. – 44 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Overload Selectivity FAZ FAZ-B(C)(D) to PLHT-B PLHT Upstream side PLHT, Characteristic B Downstream side FAZ, Characteristic B, C, D FAZ x ... Selectivity range (i.e. only the downstream switch drops in case I< Is) PLHT 20 65 x x x x x x x Characteristic B 25 32 40 81 104 130 x x x x x x x x x x x x x x x x x x x x x x x x x x x Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 0.5 1 2 3 4 6 8 10 13 16 20 25 32 40 50 63 PLHT 20 65 x x x x x x x x Characteristic B 25 32 40 81 104 130 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 2 4 6 10 13 16 20 25 32 40 PLHT 20 65 x x Characteristic B 25 32 40 81 104 130 x x x x x x x x x x Downstream side FAZ Characteristic D Downstream side FAZ Characteristic C Downstream side FAZ Characteristic B Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 2 3 4 6 10 13 16 20 25 32 40 50 63 50 163 x x x x x x x x x x x 63 205 x x x x x x x x x x x x 80 260 x x x x x x x x x x x x x 100 325 x x x x x x x x x x x x x 125 406 x x x x x x x x x x x x x 50 163 x x x x x x x x x x x x 63 205 x x x x x x x x x x x x x 80 260 x x x x x x x x x x x x x x 100 325 x x x x x x x x x x x x x x x 125 406 x x x x x x x x x x x x x x x x 50 163 x x x x x 63 205 x x x x x x 80 260 x x x x x x x 100 325 x x x x x x x x 125 406 x x x x x x x x x Chapter 4.1.1. – 45 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Overload Selectivity FAZ FAZ-B(C)(D) to PLHT-C PLHT Upstream side PLHT, Characteristic C Downstream side FAZ, Characteristic B, C, D FAZ x ... Selectivity range (i.e. only the downstream switch drops in case I< Is) PLHT 20 130 x x x x x x x Characteristic C 25 32 40 163 208 260 x x x x x x x x x x x x x x x x x x x x x x x x x x x Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 0.5 1 2 3 4 6 8 10 13 16 20 25 32 40 50 63 PLHT 20 130 x x x x x x x x x x Characteristic C 25 32 40 163 208 260 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 2 4 6 10 13 16 20 25 32 40 PLHT 20 130 x x x x Characteristic C 25 32 40 163 208 260 x x x x x x x x x x x x x x x x x x Downstream side FAZ Characteristic D Downstream side FAZ Characteristic C Downstream side FAZ Characteristic B Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 2 3 4 6 10 13 16 20 25 32 40 50 63 50 325 x x x x x x x x x x x 63 410 x x x x x x x x x x x x 80 520 x x x x x x x x x x x x x 100 650 x x x x x x x x x x x x x 125 813 x x x x x x x x x x x x x 50 325 x x x x x x x x x x x x x x 63 410 x x x x x x x x x x x x x x x 80 520 x x x x x x x x x x x x x x x x 100 650 x x x x x x x x x x x x x x x x 125 813 x x x x x x x x x x x x x x x x 50 325 x x x x x x x x 63 410 x x x x x x x x x 80 520 x x x x x x x x x x 100 650 x x x x x x x x x x 125 813 x x x x x x x x x x Chapter 4.1.1. – 46 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Overload Selectivity FAZ FAZ-B(C)(D) to PLHT-D PLHT Upstream side PLHT, Characteristic D Downstream side FAZ, Characteristic B, C, D FAZ x ... Selectivity range (i.e. only the downstream switch drops in case I< Is) PLHT 20 230 x x x x x x x Characteristic D 25 32 40 285 365 450 x x x x x x x x x x x x x x x x x x x x x x x x x x x Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 0.5 1 2 3 4 6 8 10 13 16 20 25 32 40 50 63 PLHT 20 230 x x x x x x x x x x Characteristic D 25 32 40 285 365 450 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 2 4 6 10 13 16 20 25 32 40 PLHT 20 230 x x x x x x Characteristic D 25 32 40 285 365 450 x x x x x x x x x x x x x x x x x x x x x x x x Downstream side FAZ Characteristic D Downstream side FAZ Characteristic C Downstream side FAZ Characteristic B Upstream side Type B rated current In [A] Selectivity limiting current Is [A] 2 3 4 6 10 13 16 20 25 32 40 50 63 50 550 x x x x x x x x x x x 63 680 x x x x x x x x x x x x 80 850 x x x x x x x x x x x x x 100 1020 x x x x x x x x x x x x x 50 550 x x x x x x x x x x x x x x 63 680 x x x x x x x x x x x x x x x 80 850 x x x x x x x x x x x x x x x x 100 1020 x x x x x x x x x x x x x x x x 50 550 x x x x x x x x x x 63 680 x x x x x x x x x x 80 850 x x x x x x x x x x 100 1020 x x x x x x x x x x Chapter 4.1.1. – 47 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Influence of the Line Frequency FAZ On the Instantaneous Tripping Current IMA IMA(f)/IMA(50Hz) [%] Line Frequency f [Hz] 50 60 162/3 91 100 101 100 106 200 115 300 134 400 141 Chapter 4.1.1. – 48 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers UL508 Busbars for FAZ lb-in 50 Nm 5.5 Z2 Z2 BB-IP/5 BB-UL EC/3 BB-UL-TEPA/35 BB-UL-TE/50 Z2 Z2 lb-in 35 lb-in 22 lb-in 50 Nm 4 BB-UL-TEP/35 Nm 2.5 BB-UL-TE/50 Ue f le Nm 5.5 BB-UL WBCxxx UL508 EN/IEC 60947-2 480 V AC 50/60 Hz ---------115 A @ 40°C 240/690V AC 50/60 Hz 160 A @ 30°C #1-14 AWG 60/75°C Cu 1.5 – 50 mm 2 Cu 0.56 in 14 mm UL508 EN/IEC 60947-2 UL508 BB-UL-TEP/35 / BB-UL-TEPA/35 Ue f lpk le Infeed at the start of the busbar Infeed at the center of the busbar EN/IEC 60947-2 480 V AC 690V AC 50/60 Hz 10kA 15kA 18mm² 25mm² 80A@40 °C 100A@30°C 200A@30°C 160A@40°C * -UL508 SHORT CIRCUIT RATINGS -SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THAN 10,000 RMS Ue f le 480 V AC 240/690V AC 50/60 Hz ---------- 50/60 Hz 115 A@40°C 80 A@30°C #2-14 AWG 60/75°C Cu 2.5 – 35 mm 2 Cu 0.56 in 14 mm SYMETRICAL AMPERES, 600 VOLTS MAXIMUM. -SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THAN 100,000 RMS SYMETRICAL AMPERES, 600 VOLTS MAXIMUM WHEN PROTECTED BY A CL ASS J FUSE RATED 175A. Chapter 4.1.1. – 49 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers BB Busbars for FAZ Article No. 121981 121982 121983 121984 121987 121988 121989 121990 121991 121992 121995 121996 121997 in prep. 121998 121999 122000 122001 A/35 Chapter 4.1.1. – 50 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Auxiliary Contacts and Voltage Trips for FAZ Circuit Diagram Description Rated Operational Voltage Type Designation Article No. Units per package 230 Vac FAZ-XHIN11 286054 1 230 Vac FAZ-XAM002 262414 1 115 Vac FAZ-XUA(115VAC) 212049 1 230 Vac FAZ-XUA(230VAC) 212051 1 400 Vac FAZ-XUA(400VAC) 212053 1 12–110 Vac 12–60 Vdc 110–415 Vac 110–230 Vdc FAZ-XAA-C-12-110VAC 278518 1 FAZ-XAA-C-110-415VAC 278519 1 IS/SPE-1TE 101911 1 221954800 221954900 221953900 1 1 1 Standard Auxiliary Contact SG13411 • 1NO/1NC • Installs on left side of FAZ or shunt trip • Max. one per FAZ (1077) device • Switches when FAZ is tripped electrically or manually Auxiliary/Trip Indicating Contact SG84411 Two-pole auxiliary mode • Small selector screw changes mode • Two Form C (changeover) contacts • Installs on left side of FAZ or shunt trip • Auxiliary contacts switch when FAZ is tripped electrically or manually • Trip indicating contact switches only when FAZ is tripped electrically Trip indicating mode SG85411 Undervoltage Trip • Prevents FAZ from operating unless voltage is present • Installs on left side of FAZ • Includes test button SG12311 Shunt Trip • Allows remote trip of FAZ • Installs on left side of FAZ Padlock Hasp (for all FAZ) • Prevents reactivation of the device during maintenance • Holds one padlock Screw Lock (for all FAZ except -NA and -RT) 2MU 3MU 4MU Chapter 4.1.1. – 51 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications Accessories for FAZ Technical Data FAZ-XHIN FAZ-XAM002 Electrical Contact function FAZ-XAA-C FAZ-XUA — — — 115 Vac 230 Vac 400 Vac — Rated operational voltage Un 1A + 1B 2 C/O 250 Vac Voltage range — Voltage range — Closing threshold [x Un] Tripping threshold [x Un] Rated frequency f General use (UL/CSA) AC—230/240 Vac DC—110/120 Vdc Pilot duty Conventional free air thermal current Ith Rated operational current AC-13 Ie AC-15 Ie DC-13 Ie Rated insulation voltage Ui Minimum operating voltage per contract Umin Rated impulse withstand voltage (1.2/50µ) Uimp Rated conditional short-circuit current with 6A back-up fuse ISC Max. admissible back-up fuse Mechanical Standard front dimension Device height Mounting width Degree of protection enclosed Terminal protection — — 50/60 Hz 12–110 Vac 12–60 Vdc 110–415 Vac 110–230 Vdc — — 50/60 Hz 2/2A 0.5/0.5A A600/Q600 4A — — — — — — — — 3A (250 Vac) 2A (250 Vac) 0.5A (110 Vdc) 250 Vac 5 Vdc 2.5 kV — — — — — — — — — — — — 1 kA 4A gL — — — — 45 mm 80 mm 8.8 mm IP40 Protection against electric shock to IEC 536 Lift terminals 45 mm 80 mm 17.6 mm IP40 Protection against electric shock to IEC 536 Twin-purpose terminals 45 mm 80 mm 17.8 mm IP40 Protection against electric shock to IEC 536 Twin-purpose terminals 0.5–2.5 0.5–2.5 0.8–1.0 Nm (7–9 lb-in) 1–2.5 1–2.5 2.4 Nm (21 lb-in) 2 x (1–2.5) 2 x (1–2.5) 0.8 Nm (7 lb-in) Terminals Terminal capacity [mm2] Solid Flexible Tightening torque of terminal screws — 0.8 0.5 50/60 Hz Allowable Combinations of Accessories Chapter 4.1.1. – 52 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Dimensions (mm) Accessories for FAZ Auxiliary Contacts FAZ-XHI11 FAZ-XAM002 Shunt Releases Undervoltage Releases FAZ-XAA FAZ-XUA Chapter 4.1.1. – 53 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Miniature Circuit Breakers FAZ-T, FAZ-DC, FAZ-NA, FAZ-RT SG13111 FAZ-T • High-quality miniature circuit breakers for industrial and commercial applications • Contact position indicator red - green • Accessories suitable for subsequent installation • Rated currents up to 125 A • Tripping characteristics B, C, D • Rated breaking capacity up to 25 kA according to EN 60947-2 FAZ-T FAZ-(NA)-DC • High-quality miniature circuit breakers for DC-applications SG09211 • Contact position indicator red - green • Guide for secure terminal connection • 3-position DIN rail clip, permits removal from existing busbar system • Comprehensive range of accessories suitable for subsequent installation • Rated currents up to 50 A (Type NA up to 40 A) • Tripping characteristic C • Rated breaking capacity 10 kA according to IEC/EN 60947-2 FAZ-NA • Up to 250 V DC pro pole (Type NA up to 125 V DC per pole) FAZ-NA/-RT • According to UL 489, CSA C22.2 No. 5 and also IEC 60947-2 standard • For Applications, wich are permitted for UL 1077 or CSA C22.2 No. 235 • Auxiliary switch and voltage trips suitable for subsequent installation • Serie with removable terminal screws (Type FAZ-..-RT), for use with ring cable lug • Contact position indicator red - green • Easy mounting at DIN-rail Chapter 4.1.1. – 54 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-T Miniature Circuit Breakers (MCBs) Characteristic B Rated Rated current voltage In (A) IEC/EN 60898-1 (V) SG12411 Breaking capacity acc. to IEC/EN 60947-2 (kA) Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240 240 240 240 240 240 240 240 240 240 240 240 240 240 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-B1/1 FAZT-B2/1 FAZT-B3/1 FAZT-B4/1 FAZT-B6/1 FAZT-B10/1 FAZT-B12/1 FAZT-B13/1 FAZT-B15/1 FAZT-B16/1 FAZT-B20/1 FAZT-B25/1 FAZT-B32/1 FAZT-B40/1 240770 240771 240772 240777 240782 240787 240792 240793 240794 240795 240796 240797 141907 141908 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 240 240 240 240 240 240 240 240 240 240 240 240 240 240 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240 240 240 240 240 240 240 240 240 240 240 240 240 240 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-B1/1N FAZT-B2/1N FAZT-B3/1N FAZT-B4/1N FAZT-B6/1N FAZT-B10/1N FAZT-B12/1N FAZT-B13/1N FAZT-B15/1N FAZT-B16/1N FAZT-B20/1N FAZT-B25/1N FAZT-B32/1N FAZT-B40/1N 240994 240995 240996 240997 240998 240999 241000 241001 241005 241009 241015 241019 142509 142510 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-B1/2 FAZT-B2/2 FAZT-B3/2 FAZT-B4/2 FAZT-B6/2 FAZT-B10/2 FAZT-B12/2 FAZT-B13/2 FAZT-B15/2 FAZT-B16/2 FAZT-B20/2 FAZT-B25/2 FAZT-B32/2 FAZT-B40/2 240820 240821 240822 240823 240824 240825 240826 240827 240828 240829 240830 240831 142485 142486 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1+N-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG12811 Rated voltage IEC/EN 60947-2 (V) 1-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG12711 Breaking capacity acc. to IEC/EN 60898-1 (kA) 2-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 Chapter 4.1.1. – 55 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage In (A) IEC/EN 60898-1 (V) SG13011 Breaking capacity acc. to IEC/EN 60947-2 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-B1/3 FAZT-B2/3 FAZT-B3/3 FAZT-B4/3 FAZT-B6/3 FAZT-B10/3 FAZT-B12/3 FAZT-B13/3 FAZT-B15/3 FAZT-B16/3 FAZT-B20/3 FAZT-B25/3 FAZT-B32/3 FAZT-B40/3 240874 240875 240876 240877 240878 240879 240880 240881 240882 240883 240884 240885 142493 142494 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-B1/3N FAZT-B2/3N FAZT-B3/3N FAZT-B4/3N FAZT-B6/3N FAZT-B10/3N FAZT-B12/3N FAZT-B13/3N FAZT-B15/3N FAZT-B16/3N FAZT-B20/3N FAZT-B25/3N FAZT-B32/3N FAZT-B40/3N 241060 241065 241070 241075 241080 241085 241090 241095 241100 241105 241110 241115 142517 142518 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-B1/4 FAZT-B2/4 FAZT-B3/4 FAZT-B4/4 FAZT-B6/4 FAZT-B10/4 FAZT-B12/4 FAZT-B13/4 FAZT-B15/4 FAZT-B16/4 FAZT-B20/4 FAZT-B25/4 FAZT-B32/4 FAZT-B40/4 240922 240927 240930 240931 240932 240933 240934 240935 240936 240937 240938 240939 142501 142502 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 3+N-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG13111 Rated voltage IEC/EN 60947-2 (V) 3-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG13211 Breaking capacity acc. to IEC/EN 60898-1 (kA) 4-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 Chapter 4.1.1. – 56 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-T Miniature Circuit Breakers (MCBs) Characteristic C Rated Rated current voltage In (A) IEC/EN 60898-1 (V) SG12411 Breaking capacity acc. to IEC/EN 60947-2 (kA) Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240 240 240 240 240 240 240 240 240 240 240 240 240 240 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-C1/1 FAZT-C2/1 FAZT-C3/1 FAZT-C4/1 FAZT-C6/1 FAZT-C10/1 FAZT-C12/1 FAZT-C13/1 FAZT-C15/1 FAZT-C16/1 FAZT-C20/1 FAZT-C25/1 FAZT-C32/1 FAZT-C40/1 240798 240799 240800 240801 240802 240803 240804 240805 240806 240807 240808 240809 141909 142480 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 240 240 240 240 240 240 240 240 240 240 240 240 240 240 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240 240 240 240 240 240 240 240 240 240 240 240 240 240 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-C1/1N FAZT-C2/1N FAZT-C3/1N FAZT-C4/1N FAZT-C6/1N FAZT-C10/1N FAZT-C12/1N FAZT-C13/1N FAZT-C15/1N FAZT-C16/1N FAZT-C20/1N FAZT-C25/1N FAZT-C32/1N FAZT-C40/1N 241022 241023 241024 241025 241026 241027 241028 241029 241030 241034 241038 241044 142511 142512 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-C1/2 FAZT-C2/2 FAZT-C3/2 FAZT-C4/2 FAZT-C6/2 FAZT-C10/2 FAZT-C12/2 FAZT-C13/2 FAZT-C15/2 FAZT-C16/2 FAZT-C20/2 FAZT-C25/2 FAZT-C32/2 FAZT-C40/2 240832 240833 240838 240843 240850 240855 240858 240859 240860 240861 240862 240863 142487 142488 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1+N-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG12811 Rated voltage IEC/EN 60947-2 (V) 1-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG12711 Breaking capacity acc. to IEC/EN 60898-1 (kA) 2-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 Chapter 4.1.1. – 57 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage In (A) IEC/EN 60898-1 (V) SG13011 Breaking capacity acc. to IEC/EN 60947-2 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-C1/3 FAZT-C2/3 FAZT-C3/3 FAZT-C4/3 FAZT-C6/3 FAZT-C10/3 FAZT-C12/3 FAZT-C13/3 FAZT-C15/3 FAZT-C16/3 FAZT-C20/3 FAZT-C25/3 FAZT-C32/3 FAZT-C40/3 240886 240887 240888 240889 240890 240891 240892 240893 240894 240895 240896 240897 142495 142496 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-C1/3N FAZT-C2/3N FAZT-C3/3N FAZT-C4/3N FAZT-C6/3N FAZT-C10/3N FAZT-C12/3N FAZT-C13/3N FAZT-C15/3N FAZT-C16/3N FAZT-C20/3N FAZT-C25/3N FAZT-C32/3N FAZT-C40/3N 241120 241125 241130 241135 241140 241145 241150 241155 241160 241165 241170 241175 142519 142520 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 25 25 20 20 FAZT-C1/4 FAZT-C2/4 FAZT-C3/4 FAZT-C4/4 FAZT-C6/4 FAZT-C10/4 FAZT-C12/4 FAZT-C13/4 FAZT-C15/4 FAZT-C16/4 FAZT-C20/4 FAZT-C25/4 FAZT-C32/4 FAZT-C40/4 240940 240941 240945 240949 240955 240959 240962 240963 240964 240965 240966 240967 142503 142504 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 3+N-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG13111 Rated voltage IEC/EN 60947-2 (V) 3-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG13211 Breaking capacity acc. to IEC/EN 60898-1 (kA) 4-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 Chapter 4.1.1. – 58 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-T Miniature Circuit Breakers (MCBs) Characteristic D Rated Rated current voltage In (A) IEC/EN 60898-1 (V) SG12411 Breaking capacity acc. to IEC/EN 60947-2 (kA) Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 10 10 10 10 240 240 240 240 240 240 240 240 240 240 240 240 240 240 25 25 25 25 25 25 25 25 20 20 20 15 15 15 FAZT-D1/1 FAZT-D2/1 FAZT-D3/1 FAZT-D4/1 FAZT-D6/1 FAZT-D10/1 FAZT-D12/1 FAZT-D13/1 FAZT-D15/1 FAZT-D16/1 FAZT-D20/1 FAZT-D25/1 FAZT-D32/1 FAZT-D40/1 240810 240811 240812 240813 240814 240815 240816 240817 240818 240819 142481 142482 142483 142484 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 240 240 240 240 240 240 240 240 240 240 240 240 240 240 15 15 15 15 15 15 15 15 15 15 10 10 10 10 240 240 240 240 240 240 240 240 240 240 240 240 240 240 25 25 25 25 25 25 25 25 20 20 20 15 15 15 FAZT-D1/1N FAZT-D2/1N FAZT-D3/1N FAZT-D4/1N FAZT-D6/1N FAZT-D10/1N FAZT-D12/1N FAZT-D13/1N FAZT-D15/1N FAZT-D16/1N FAZT-D20/1N FAZT-D25/1N FAZT-D32/1N FAZT-D40/1N 241048 241051 241052 241053 241054 241055 241056 241057 241058 241059 142513 142514 142515 142516 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 10 10 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 20 20 20 15 15 15 FAZT-D1/2 FAZT-D2/2 FAZT-D3/2 FAZT-D4/2 FAZT-D6/2 FAZT-D10/2 FAZT-D12/2 FAZT-D13/2 FAZT-D15/2 FAZT-D16/2 FAZT-D20/2 FAZT-D25/2 FAZT-D32/2 FAZT-D40/2 240864 240865 240866 240867 240868 240869 240870 240871 240872 240873 142489 142490 142491 142492 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1+N-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG12811 Rated voltage IEC/EN 60947-2 (V) 1-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG12711 Breaking capacity acc. to IEC/EN 60898-1 (kA) 2-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 Chapter 4.1.1. – 59 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Rated Rated current voltage In (A) IEC/EN 60898-1 (V) SG13011 Breaking capacity acc. to IEC/EN 60947-2 (kA) Type Designation Article No. Units per package 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 10 10 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 20 15 15 15 FAZT-D1/3 FAZT-D2/3 FAZT-D3/3 FAZT-D4/3 FAZT-D6/3 FAZT-D10/3 FAZT-D12/3 FAZT-D13/3 FAZT-D15/3 FAZT-D16/3 FAZT-D20/3 FAZT-D25/3 FAZT-D32/3 FAZT-D40/3 240898 240899 240900 240901 240902 240903 240904 240905 240910 240915 142497 142498 142499 142500 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 10 10 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 20 15 15 15 FAZT-D1/3N FAZT-D2/3N FAZT-D3/3N FAZT-D4/3N FAZT-D6/3N FAZT-D10/3N FAZT-D12/3N FAZT-D13/3N FAZT-D15/3N FAZT-D16/3N FAZT-D20/3N FAZT-D25/3N FAZT-D32/3N FAZT-D40/3N 241180 241181 241182 241183 241184 241185 241186 241187 241188 241189 142521 142522 142523 142524 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 10 10 10 10 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 25 25 25 25 25 25 25 25 25 25 20 15 15 15 FAZT-D1/4 FAZT-D2/4 FAZT-D3/4 FAZT-D4/4 FAZT-D6/4 FAZT-D10/4 FAZT-D12/4 FAZT-D13/4 FAZT-D15/4 FAZT-D16/4 FAZT-D20/4 FAZT-D25/4 FAZT-D32/4 FAZT-D40/4 240968 240969 240970 240971 240975 240979 240985 240989 240992 240993 142505 142506 142507 142508 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 3+N-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG13111 Rated voltage IEC/EN 60947-2 (V) 3-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 SG13211 Breaking capacity acc. to IEC/EN 60898-1 (kA) 4-pole 1 2 3 4 6 10 12 13 15 16 20 25 32 40 Chapter 4.1.1. – 60 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications FAZ-T Technical data FAZ-T Productstandard IEC/EN 60947-2 IEC/EN 60898-1 1, 1p+N, 2, 3, 3p+N, 4 Number of poles Mechanical specifications Device width 17.7 mm (1p), 27 mm (1p+N), 36 mm (2p), 54 mm (3p), 72mm (3p+N), 72 mm (4p) 45 mm 80 mm 60 mm lift terminal 1-25 mm² M5 (with slotted screw acc. to EN ISO 4757-Z2, PZ2) max. 2.4 Nm tristable (on DIN rail acc. to EN 50022) acc. to VBG4, ÖVE EN-6 Frame size Socket size Device depth Terminals Terminal capacity rigid solid/stranded wire Terminal screw Terminal torque Snap on fixing Finger proof Degree of Protection (DIN VDE 0470) Surface mounted Built-in behind panel Contact position indicator IP 20 IP 40 red / green Electrical specifications Rated voltage Rated current Rated insulation voltage Rated impulse withstand voltage Un In Ui Uimp 240/415 V Type B, C, D: 1, 2, 3, 4, 6, 10, 12, 13, 15, 16, 20, 25, 32, 40 A 440 V 4 kV (1.2/50)µsec Tripping characteristic Conventional non-tripping current Conventional tripping current Reference temperature Temperature factor Instantaneous tripping current Imt Rated ultimate short-circuit braking capacity Icu (IEC/EN 60947-2) type B type C type D Rated service short-circuit braking capacity Ics (IEC/EN 60947-2) Rated short-circuit braking capacity Icn (IEC/EN 60898-1) type B type C type D Selectivity class Number of electrical operations Number of mechanical operations Climatic conditions Int=1.13 In It=1.45 In 30 °C 0.4% /K type B: 3 In < Imt = 5 In:t (Imt) < 0.1 sec type C: 5 In < Imt = 10 In:t (Imt) < 0.1 sec type D: 10 In < Imt = 20 In:t (Imt) < 0.1 sec 1-25 A: 25 kA, 32-40 A: 20 kA 1-25 A: 25 kA, 32-40 A: 20 kA 1p/1p+N/2p - 1-13 A: 25 kA, 15-20 A: 20 kA, 25-40 A: 15 kA 3p/3p+N/4p - 1-16 A: 25 kA, 20 A: 20 kA, 25-40 A: 15 kA for Icu = 25 kA --> Ics = 12.5 kA for Icu = 20 kA --> Ics = 10 kA for Icu = 15 kA --> Ics = 7.5 kA 1-25 A: 15 kA, 32-40 A: 10 kA 1-25 A: 15 kA, 32-40 A: 10 kA 1-16 A: 15 kA, 20-40 A: 10 kA 3 (acc. to EN 60898) > 4000 (IEC/EN 60898) > 10000 (IEC/EN 60947) acc. to IEC 68-2 (25..55°C / 90..95% RH) Connection diagram 1-pole 1+N-pole 2-pole 3-pole 3+N-pole Chapter 4.1.1. – 61 4-pole EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Dimensions (mm) FAZ-T 1-pole 1+N-pole 3-pole 3+N-pole, 4-pole 2-pole Chapter 4.1.1. – 62 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Tripping Characteristic FAZ-T Characteristics B, C and D - EN60898 Chapter 4.1.1. – 63 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Power Loss at In FAZ-T Type B Type C 1p In [A] P [W] 1 1.6 2 1.4 3 2.5 4 1.4 6 1.8 10 1.9 12 2.8 13 2.5 15 2.1 16 2.2 20 3.2 25 3.0 32 3.7 40 3.4 *symmetrical load 1pN 2p 3p 3pN* 4p P [W] 1.7 1.5 2.7 1.6 2.0 2.1 3.2 2.9 2.4 2.6 3.6 3.5 4.4 4.1 P [W] 3.1 2.8 5.0 2.9 3.6 3.9 5.9 5.3 4.4 4.7 6.6 6.4 8.1 7.5 P [W 4.7 4.1 7.6 4.4 5.5 5.9 8.7 7.8 6.5 6.9 9.8 9.4 12.1 11.2 P [W] 4.8 4.3 7.8 4.5 5.6 6.1 9.0 8.1 6.7 7.2 10.1 9.7 12.5 11.5 P [W] 6.3 5.5 10.1 5.8 7.3 7.8 11.5 10.3 8.6 9.1 13.0 12.4 15.8 14.6 1pN 2p 3p 3pN* 4p P [W] 0.9 1.1 1.3 1.6 1.6 1.7 2.0 2.2 2.4 2.6 2.2 2.9 4.0 3.8 P [W] 1.6 2.0 2.4 2.9 2.9 3.0 3.6 4.0 4.4 4.7 4.1 5.2 7.4 7.0 P [W 2.4 3.0 3.6 4.4 4.4 4.6 5.3 5.9 6.5 6.9 6.1 7.7 11.1 10.4 P [W] 2.5 3.1 3.7 4.5 4.6 4.7 5.4 6.1 6.7 7.2 6.2 7.9 11.4 10.7 P [W] 3.2 4.0 4.8 5.8 5.9 6.1 7.0 7.8 8.6 9.1 8.1 10.2 14.5 13.6 1p In [A] P [W] 1 1.6 2 1.4 3 1.2 4 1.4 6 1.5 10 1.5 12 2.1 13 2.5 15 2.1 16 2.2 20 3.2 25 3.0 32 3.7 40 3.4 *symmetrical load 1pN 2p 3p 3pN* 4p P [W] 1.7 1.5 1.3 1.6 1.6 1.7 2.4 2.9 2.4 2.6 3.6 3.5 4.4 4.1 P [W] 3.1 2.8 2.4 2.9 2.9 3.0 4.4 5.3 4.4 4.7 6.6 6.4 8.1 7.5 P [W 4.7 4.1 3.6 4.4 4.4 4.6 6.5 7.8 6.5 6.9 9.8 9.4 12.1 11.2 P [W] 4.8 4.3 3.7 4.5 4.6 4.7 6.8 8.1 6.7 7.2 10.1 9.7 12.5 11.5 P [W] 6.3 5.5 4.8 5.8 5.9 6.1 8.6 10.3 8.6 9.1 13.0 12.4 15.8 14.6 Type D 1p In [A] P [W] 1 0.8 2 1.0 3 1.2 4 1.4 6 1.5 10 1.5 12 1.7 13 1.9 15 2.1 16 2.2 20 2.0 25 2.5 32 3.4 40 3.2 *symmetrical load Chapter 4.1.1. – 64 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Influence of Ambient Temperature FAZ-T On Load Carrying Capacity (temperature derating) IN [A] 1 2 3 4 6 10 12 13 15 16 20 25 32 40 Ambient temperature T [°C] -40 -30 -20 -10 1.3 1.2 1.2 1.2 2.6 2.5 2.4 2.3 3.8 3.7 3.6 3.5 5.1 5 4.8 4.7 7.7 7.5 7.2 7 13 12 12 12 15 15 14 14 17 16 16 15 19 19 18 17 20 20 19 19 26 25 24 23 32 31 30 29 41 40 38 37 51 50 48 47 0 1.1 2.2 3.4 4.5 6.7 11 13 15 17 18 22 28 36 45 10 1.1 2.2 3.3 4.3 6.5 11 13 14 16 17 22 27 35 43 20 1 2.1 3.1 4.2 6.3 10 13 14 16 17 21 26 33 42 30 1 2 3 4 6 10 12 13 15 16 20 25 32 40 300 134 400 141 35 0.99 2 3 3.9 5.9 9.9 12 13 15 16 20 25 32 39 40 0.97 1.9 2.9 3.9 5.8 9.7 12 13 15 15 19 24 31 39 45 0.95 1.9 2.8 3.8 5.7 9.5 11 12 14 15 19 24 30 38 50 0.93 1.9 2.8 3.7 5.6 9.3 11 12 14 15 19 23 30 37 55 0.9 1.8 2.7 3.6 5.4 9 11 12 14 14 18 23 29 36 60 0.89 1.8 2.7 3.5 5.3 8.9 11 12 13 14 18 22 28 35 65 0.87 1.7 2.6 3.5 5.2 8.7 10 11 13 14 17 22 28 35 70 0.85 1.7 2.5 3.4 5.1 8.5 10 11 13 14 17 21 27 34 75 0.83 1.7 2.5 3.3 5 8.3 10 11 12 13 17 21 26 33 Influence of the Line Frequency FAZ-T On the Instantaneous Tripping Current IMA IMA(f)/IMA(50Hz) [%] Line Frequency f [Hz] 50 60 162/3 91 100 101 100 106 200 115 Load rating in case of circuit breakers arranged one next to the other FAZ-T Chapter 4.1.1. – 65 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Energy FAZ-T Type B Type C Type D Chapter 4.1.1. – 66 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Current FAZ-T Type B Type C Type D Chapter 4.1.1. – 67 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-DC Miniature Circuit Breakers (MCBs) Characteristic C Rated Rated current voltage In (A) IEC/EN 60947-2 (V DC) SG08511 Type Designation Article No. Units per package 220 250 250 250 250 250 250 250 250 250 250 250 10 10 10 10 10 10 10 10 10 10 10 10 FAZ-C2/1-DC FAZ-C3/1-DC FAZ-C4/1-DC FAZ-C6/1-DC FAZ-C10/1-DC FAZ-C13/1-DC FAZ-C16/1-DC FAZ-C20/1-DC FAZ-C25/1-DC FAZ-C32/1-DC FAZ-C40/1-DC FAZ-C50/1-DC 279122 279123 279124 279125 279126 279127 279128 279129 279130 279131 279132 279133 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 440 500 500 500 500 500 500 500 500 500 500 500 10 10 10 10 10 10 10 10 10 10 10 10 FAZ-C2/2-DC FAZ-C3/2-DC FAZ-C4/2-DC FAZ-C6/2-DC FAZ-C10/2-DC FAZ-C13/2-DC FAZ-C16/2-DC FAZ-C20/2-DC FAZ-C25/2-DC FAZ-C32/2-DC FAZ-C40/2-DC FAZ-C50/2-DC 279134 279135 279136 279137 279138 279139 279140 279141 279142 279143 279144 279145 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1-pole 2 3 4 6 10 13 16 20 25 32 40 50 SG08611 Breaking capacity acc. to IEC/EN 60947-2 (kA) 2-pole 2 3 4 6 10 13 16 20 25 32 40 50 Chapter 4.1.1. – 68 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications FAZ-DC Technical data FAZ-DC *) Productstandard Number of poles IEC/EN 60947-2 1, 2 Mechanical specifications Device width Frame size Socket size Device depth Terminals Terminal capacity rigid solid/stranded wire Terminal screw Terminal torque Snap on fixing Finger proof Degree of Protection (DIN VDE 0470) Surface mounted Built-in behind panel Contact position indicator 17.7 mm (1p), 36 mm (2p) 45 mm 80 mm 60 mm lift terminal 1-25 mm² M5 (with slotted screw acc. to EN ISO 4757-Z2, PZ2) max. 2.4 Nm tristable (on DIN rail acc. to EN 50022) acc. to VBG4, ÖVE EN-6 IP 20 IP 40 red / green Electrical specifications Rated voltage DC Un Rated current Rated insulation voltage Rated impulse withstand voltage In Ui Uimp 2 A type: 220V (per pole) 3-50 A types: 250V (per pole) Type C: 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 A 440 V 4 kV (1.2/50)µsec Tripping characteristic Conventional non-tripping current Conventional tripping current Reference temperature Temperature factor Instantaneous tripping current Rated short-circuit braking capacity Selectivity class Number of electrical operations Number of mechanical operations Climatic conditions Imt Icu Int=1.13 In It=1.45 In 30 °C 0.4% /K type C: 7 In < Imt = 15 In:t (Imt) < 0.1 sec 10 kA 3 > 4000 > 20000 acc. to IEC 68-2 (25..55°C / 90..95% RH) *) not for PV string protection! Connection diagram 1-pole 2-pole Chapter 4.1.1. – 69 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Dimensions (mm) FAZ-...-DC 1-pole 2-pole Connection examples FAZ-...-DC Connection example at 250V=, 1-pole Connection example at 500V=, 2-pole Tripping Characteristic FAZ-...-DC Maximum Let-Through Energy FAZ-...-DC Characteristics C - IEC/EN 60947-2 Type C Chapter 4.1.1. – 70 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-NA Miniature Circuit Breakers (MCBs) Characteristic B Rated Rated current voltage In (A) IEC/EN 60947-2 (V) SG09011 Breaking SWD capacity acc. to UL489 (kA) NFPA 79 Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-B1/1-NA FAZ-B1,5/1-NA FAZ-B2/1-NA FAZ-B3/1-NA FAZ-B4/1-NA FAZ-B5/1-NA FAZ-B6/1-NA FAZ-B7/1-NA FAZ-B8/1-NA FAZ-B10/1-NA FAZ-B13/1-NA FAZ-B15/1-NA FAZ-B16/1-NA FAZ-B20/1-NA FAZ-B25/1-NA FAZ-B30/1-NA FAZ-B32/1-NA FAZ-B35/1-NA FAZ-B40/1-NA 132414 132415 132416 132417 132418 132419 132680 132681 132682 132683 132684 132685 132686 132687 132688 132689 132690 132691 132692 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-B1/2-NA FAZ-B1,5/2-NA FAZ-B2/2-NA FAZ-B3/2-NA FAZ-B4/2-NA FAZ-B5/2-NA FAZ-B6/2-NA FAZ-B7/2-NA FAZ-B8/2-NA FAZ-B10/2-NA FAZ-B13/2-NA FAZ-B15/2-NA FAZ-B16/2-NA FAZ-B20/2-NA FAZ-B25/2-NA FAZ-B30/2-NA FAZ-B32/2-NA FAZ-B35/2-NA FAZ-B40/2-NA 132693 132694 132695 132696 132697 132698 132699 132700 132701 132702 132703 132704 132705 132706 132707 132708 132709 132710 132711 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-B1/3-NA FAZ-B1,5/3-NA FAZ-B2/3-NA FAZ-B3/3-NA FAZ-B4/3-NA FAZ-B5/3-NA FAZ-B6/3-NA FAZ-B7/3-NA FAZ-B8/3-NA FAZ-B10/3-NA FAZ-B13/3-NA FAZ-B15/3-NA FAZ-B16/3-NA FAZ-B20/3-NA FAZ-B25/3-NA FAZ-B30/3-NA FAZ-B32/3-NA FAZ-B35/3-NA FAZ-B40/3-NA 132712 132713 132714 132715 132716 132717 132718 132719 132720 132721 132722 132723 132724 132725 132726 132727 132728 132729 132730 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 2-pole 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09211 Rated voltage UL489 (V) 1-pole 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 Chapter 4.1.1. – 71 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-NA Miniature Circuit Breakers (MCBs) Characteristic C Rated Rated current voltage In (A) IEC/EN 60947-2 (V) SG09011 Breaking SWD capacity acc. to UL489 (kA) NFPA 79 Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 240 240 10 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-C0,5/1-NA FAZ-C1/1-NA FAZ-C1,5/1-NA FAZ-C2/1-NA FAZ-C3/1-NA FAZ-C4/1-NA FAZ-C5/1-NA FAZ-C6/1-NA FAZ-C7/1-NA FAZ-C8/1-NA FAZ-C10/1-NA FAZ-C13/1-NA FAZ-C15/1-NA FAZ-C16/1-NA FAZ-C20/1-NA FAZ-C25/1-NA FAZ-C30/1-NA FAZ-C32/1-NA FAZ-C35/1-NA FAZ-C40/1-NA 102077 102078 102079 102080 102081 102082 102083 102084 102085 102086 102087 102088 102089 102090 102091 102092 102093 102094 102095 102096 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-C0,5/2-NA FAZ-C1/2-NA FAZ-C1,5/2-NA FAZ-C2/2-NA FAZ-C3/2-NA FAZ-C4/2-NA FAZ-C5/2-NA FAZ-C6/2-NA FAZ-C7/2-NA FAZ-C8/2-NA FAZ-C10/2-NA FAZ-C13/2-NA FAZ-C15/2-NA FAZ-C16/2-NA FAZ-C20/2-NA FAZ-C25/2-NA FAZ-C30/2-NA FAZ-C32/2-NA FAZ-C35/2-NA FAZ-C40/2-NA 102157 102158 102159 102160 102161 102162 102163 102164 102165 102166 102167 102168 102169 102170 102171 102172 102173 102174 102175 102176 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 2-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09211 Rated voltage UL489 (V) 1-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 Chapter 4.1.1. – 72 FAZ-C0,5/3-NA 102237 1/40 FAZ-C1/3-NA 102238 1/40 FAZ-C1,5/3-NA 102239 1/40 FAZ-C2/3-NA 102240 1/40 FAZ-C3/3-NA 102241 1/40 FAZ-C4/3-NA 102242 1/40 FAZ-C5/3-NA 102243 1/40 FAZ-C6/3-NA 102244 1/40 FAZ-C7/3-NA 102245 1/40 FAZ-C8/3-NA 102246 1/40 FAZ-C10/3-NA 102247 1/40 FAZ-C13/3-NA 102248 1/40 FAZ-C15/3-NA 102249 1/40 FAZ-C16/3-NA 102250 1/40 FAZ-C20/3-NA 102251 1/40 FAZ-C25/3-NA 102252 1/40 FAZ-C30/3-NA 102253 1/40 FAZ-C32/3-NA 102254 1/40 FAZ-C35/3-NA 102255 1/40 FAZ-C40/3-NA 102256 1/40 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-NA Miniature Circuit Breakers (MCBs) Characteristic D Rated Rated current voltage In (A) IEC/EN 60947-2 (V) SG09011 Breaking SWD capacity acc. to UL489 (kA) NFPA 79 Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-D0,5/1-NA FAZ-D1/1-NA FAZ-D1,5/1-NA FAZ-D2/1-NA FAZ-D3/1-NA FAZ-D4/1-NA FAZ-D5/1-NA FAZ-D6/1-NA FAZ-D7/1-NA FAZ-D8/1-NA FAZ-D10/1-NA FAZ-D13/1-NA FAZ-D15/1-NA FAZ-D16/1-NA FAZ-D20/1-NA FAZ-D25/1-NA FAZ-D30/1-NA FAZ-D32/1-NA FAZ-D35/1-NA FAZ-D40/1-NA 102097 102098 102099 102100 102101 102102 102103 102104 102105 102106 102107 102108 102109 102110 102111 102112 102113 102114 102115 102116 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-D0,5/2-NA FAZ-D1/2-NA FAZ-D1,5/2-NA FAZ-D2/2-NA FAZ-D3/2-NA FAZ-D4/2-NA FAZ-D5/2-NA FAZ-D6/2-NA FAZ-D7/2-NA FAZ-D8/2-NA FAZ-D10/2-NA FAZ-D13/2-NA FAZ-D15/2-NA FAZ-D16/2-NA FAZ-D20/2-NA FAZ-D25/2-NA FAZ-D30/2-NA FAZ-D32/2-NA FAZ-D35/2-NA FAZ-D40/2-NA 102177 102178 102179 102180 102181 102182 102183 102184 102185 102186 102187 102188 102189 102190 102191 102192 102193 102194 102195 102196 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 2-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09211 Rated voltage UL489 (V) 1-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 Chapter 4.1.1. – 73 FAZ-D0,5/3-NA 102257 1/40 FAZ-D1/3-NA 102258 1/40 FAZ-D1,5/3-NA 102259 1/40 FAZ-D2/3-NA 102260 1/40 FAZ-D3/3-NA 102261 1/40 FAZ-D4/3-NA 102262 1/40 FAZ-D5/3-NA 102263 1/40 FAZ-D6/3-NA 102264 1/40 FAZ-D7/3-NA 102265 1/40 FAZ-D8/3-NA 102266 1/40 FAZ-D10/3-NA 102267 1/40 FAZ-D13/3-NA 102268 1/40 FAZ-D15/3-NA 102269 1/40 FAZ-D16/3-NA 102270 1/40 FAZ-D20/3-NA 102271 1/40 FAZ-D25/3-NA 102272 1/40 FAZ-D30/3-NA 102273 1/40 FAZ-D32/3-NA 102274 1/40 FAZ-D35/3-NA 102275 1/40 FAZ-D40/3-NA 102276 1/40 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-NA-DC Miniature Circuit Breakers (MCBs) Characteristic C Rated Rated current voltage In (A) IEC/EN 60947-2 (V DC) SG09011 Rated voltage UL489 (V) Breaking SWD capacity acc. to UL489 (kA) NFPA 79 Type Designation Article No. Units per package 1-pole 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 220 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 FAZ-C2/1-NA-DC 113752 FAZ-C3/1-NA-DC 113753 FAZ-C4/1-NA-DC 113754 FAZ-C5/1-NA-DC 113755 FAZ-C6/1-NA-DC 113756 FAZ-C7/1-NA-DC 113757 FAZ-C8/1-NA-DC 113758 FAZ-C10/1-NA-DC 113759 FAZ-C13/1-NA-DC 113760 FAZ-C15/1-NA-DC 113761 FAZ-C16/1-NA-DC 113762 FAZ-C20/1-NA-DC 113763 FAZ-C25/1-NA-DC 113764 FAZ-C30/1-NA-DC 113765 FAZ-C32/1-NA-DC 113766 FAZ-C35/1-NA-DC 113767 FAZ-C40/1-NA-DC 113768 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 440 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 FAZ-C2/2-NA-DC 137239 FAZ-C3/2-NA-DC 137250 FAZ-C4/2-NA-DC 137251 FAZ-C5/2-NA-DC 137252 FAZ-C6/2-NA-DC 120638 FAZ-C7/2-NA-DC 120639 FAZ-C8/2-NA-DC 120640 FAZ-C10/2-NA-DC 120641 FAZ-C13/2-NA-DC 120642 FAZ-C15/2-NA-DC 120643 FAZ-C16/2-NA-DC 120644 FAZ-C20/2-NA-DC 120645 FAZ-C25/2-NA-DC 120646 FAZ-C30/2-NA-DC 120647 FAZ-C32/2-NA-DC 120648 FAZ-C35/2-NA-DC 120649 FAZ-C40/2-NA-DC 120650 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 2-pole 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 Chapter 4.1.1. – 74 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications FAZ-NA-DC Technical data FAZ-NA-DC Productstandard Number of poles UL 489, CSA C22.2 No 5-02 1, 2 Mechanical specifications Device width Frame size Socket size Device depth Terminals Terminal capacity rigid solid/stranded wire 1 pole = 0.697 inch, 2 poles = 1.394 inch 1.772 inch 4.134 inch 2.362 inch lift terminal / ring-tongue 1 Wire: AWG 18-6 (Cu only) 2 Wires: AWG 18-10 (Cu only) M5 (with slotted screw Pozidriv PZ2) #18-12 AWG: 21 lb-in #10-8 AWG: 25 lb-in #6 AWG: 36 lb-in tristable (on DIN Rail acc. to IEC/EN 60715) acc.to VBG4, ÖVE EN-6 red / green Terminal screw Terminal torque Snap on fixing Finger proof Contact position indicator Electrical specifications Rated voltage DC Rated current Rated impulse withstand voltage Un In Uimp 125 V d.c. (1p) 250 V d.c. (2p) 6, 7, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40 A 4 kV (1.2/50)µsec Tripping characteristic Conventional non-tripping current Conventional tripping current Reference temperature Temperature factor Instantaneous tripping current Current interrupting rating Number of electrical operating cycles Number of mechanical operating cycles Climatic conditions Imt Int=1.0 In It=1.35 In 40 °C 0.5% /K 7 In < Imt = 15 In:t (Imt) < 0.1 sec 10 kA 6000 10000 acc. to IEC 68-2 (25..55°C / 90..95% RH) Connection diagram 1-pole 2-pole Chapter 4.1.1. – 75 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Dimensions (mm) FAZ-NA-DC 1-pole 2-pole Tripping Characteristic FAZ-NA-DC Characteristics C - UL 489 Chapter 4.1.1. – 76 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-RT Miniature Circuit Breakers (MCBs) Characteristic B Rated Rated current voltage In (A) IEC/EN 60947-2 (V) SG09011 Breaking SWD capacity acc. to UL489 (kA) NFPA 79 Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-B1/1-RT FAZ-B1,5/1-RT FAZ-B2/1-RT FAZ-B3/1-RT FAZ-B4/1-RT FAZ-B5/1-RT FAZ-B6/1-RT FAZ-B7/1-RT FAZ-B8/1-RT FAZ-B10/1-RT FAZ-B13/1-RT FAZ-B15/1-RT FAZ-B16/1-RT FAZ-B20/1-RT FAZ-B25/1-RT FAZ-B30/1-RT FAZ-B32/1-RT FAZ-B35/1-RT FAZ-B40/1-RT 132731 132732 132733 132734 132735 132736 132737 132738 132739 132740 132741 132742 132743 132744 132745 132746 132747 132748 132749 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-B1/2-RT FAZ-B1,5/2-RT FAZ-B2/2-RT FAZ-B3/2-RT FAZ-B4/2-RT FAZ-B5/2-RT FAZ-B6/2-RT FAZ-B7/2-RT FAZ-B8/2-RT FAZ-B10/2-RT FAZ-B13/2-RT FAZ-B15/2-RT FAZ-B16/2-RT FAZ-B20/2-RT FAZ-B25/2-RT FAZ-B30/2-RT FAZ-B32/2-RT FAZ-B35/2-RT FAZ-B40/2-RT 132750 132751 132752 132753 132754 132755 132756 132757 132758 132759 132760 132761 132762 132763 132764 132765 132766 132767 132768 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-B1/3-RT FAZ-B1,5/3-RT FAZ-B2/3-RT FAZ-B3/3-RT FAZ-B4/3-RT FAZ-B5/3-RT FAZ-B6/3-RT FAZ-B7/3-RT FAZ-B8/3-RT FAZ-B10/3-RT FAZ-B13/3-RT FAZ-B15/3-RT FAZ-B16/3-RT FAZ-B20/3-RT FAZ-B25/3-RT FAZ-B30/3-RT FAZ-B32/3-RT FAZ-B35/3-RT FAZ-B40/3-RT 132769 132770 132771 132772 132773 132774 132775 132776 132777 132778 132779 132780 132781 132782 132783 132784 132785 132786 132787 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 2-pole 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09211 Rated voltage UL489 (V) 1-pole 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 Chapter 4.1.1. – 77 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-RT Miniature Circuit Breakers (MCBs) Characteristic C Rated Rated current voltage In (A) IEC/EN 60947-2 (V) SG09011 Breaking SWD capacity acc. to UL489 (kA) NFPA 79 Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 240 240 10 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-C0,5/1-RT FAZ-C1/1-RT FAZ-C1,5/1-RT FAZ-C2/1-RT FAZ-C3/1-RT FAZ-C4/1-RT FAZ-C5/1-RT FAZ-C6/1-RT FAZ-C7/1-RT FAZ-C8/1-RT FAZ-C10/1-RT FAZ-C13/1-RT FAZ-C15/1-RT FAZ-C16/1-RT FAZ-C20/1-RT FAZ-C25/1-RT FAZ-C30/1-RT FAZ-C32/1-RT FAZ-C35/1-RT FAZ-C40/1-RT 102117 102118 102119 102120 102121 102122 102123 102124 102125 102126 102127 102128 102129 102130 102131 102132 102133 102134 102135 102136 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-C0,5/2-RT FAZ-C1/2-RT FAZ-C1,5/2-RT FAZ-C2/2-RT FAZ-C3/2-RT FAZ-C4/2-RT FAZ-C5/2-RT FAZ-C6/2-RT FAZ-C7/2-RT FAZ-C8/2-RT FAZ-C10/2-RT FAZ-C13/2-RT FAZ-C15/2-RT FAZ-C16/2-RT FAZ-C20/2-RT FAZ-C25/2-RT FAZ-C30/2-RT FAZ-C32/2-RT FAZ-C35/2-RT FAZ-C40/2-RT 102197 102198 102199 102200 102201 102202 102203 102204 102205 102206 102207 102208 102209 102210 102211 102212 102213 102214 102215 102216 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 2-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09211 Rated voltage UL489 (V) 1-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 Chapter 4.1.1. – 78 FAZ-C0,5/3-RT 102277 1/40 FAZ-C1/3-RT 102278 1/40 FAZ-C1,5/3-RT 102279 1/40 FAZ-C2/3-RT 102280 1/40 FAZ-C3/3-RT 102281 1/40 FAZ-C4/3-RT 102282 1/40 FAZ-C5/3-RT 102283 1/40 FAZ-C6/3-RT 102284 1/40 FAZ-C7/3-RT 102285 1/40 FAZ-C8/3-RT 102286 1/40 FAZ-C10/3-RT 102287 1/40 FAZ-C13/3-RT 102288 1/40 FAZ-C15/3-RT 102289 1/40 FAZ-C16/3-RT 102290 1/40 FAZ-C20/3-RT 102291 1/40 FAZ-C25/3-RT 102292 1/40 FAZ-C30/3-RT 102293 1/40 FAZ-C32/3-RT 102294 1/40 FAZ-C35/3-RT 102295 1/40 FAZ-C40/3-RT 102296 1/40 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-...-RT Miniature Circuit Breakers (MCBs) Characteristic D Rated Rated current voltage In (A) IEC/EN 60947-2 (V) SG09011 Breaking SWD capacity acc. to UL489 (kA) NFPA 79 Type Designation Article No. Units per package 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 240/415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-D0,5/1-RT FAZ-D1/1-RT FAZ-D1,5/1-RT FAZ-D2/1-RT FAZ-D3/1-RT FAZ-D4/1-RT FAZ-D5/1-RT FAZ-D6/1-RT FAZ-D7/1-RT FAZ-D8/1-RT FAZ-D10/1-RT FAZ-D13/1-RT FAZ-D15/1-RT FAZ-D16/1-RT FAZ-D20/1-RT FAZ-D25/1-RT FAZ-D30/1-RT FAZ-D32/1-RT FAZ-D35/1-RT FAZ-D40/1-RT 102137 102138 102139 102140 102141 102142 102143 102144 102145 102146 102147 102148 102149 102150 102151 102152 102153 102154 102155 102156 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 FAZ-D0,5/2-RT FAZ-D1/2-RT FAZ-D1,5/2-RT FAZ-D2/2-RT FAZ-D3/2-RT FAZ-D4/2-RT FAZ-D5/2-RT FAZ-D6/2-RT FAZ-D7/2-RT FAZ-D8/2-RT FAZ-D10/2-RT FAZ-D13/2-RT FAZ-D15/2-RT FAZ-D16/2-RT FAZ-D20/2-RT FAZ-D25/2-RT FAZ-D30/2-RT FAZ-D32/2-RT FAZ-D35/2-RT FAZ-D40/2-RT 102217 102218 102219 102220 102221 102222 102223 102224 102225 102226 102227 102228 102229 102230 102231 102232 102233 102234 102235 102236 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277 240 240 10 10 10 10 10 10 10 10 10 10 10 14 14 14 14 10 10 10 10 10 SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD SWD AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 16 AWG 16 2-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09211 Rated voltage UL489 (V) 1-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 SG09111 Breaking capacity acc. to IEC/EN 60947-2 (kA) 3-pole 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 Chapter 4.1.1. – 79 FAZ-D0,5/3-RT 102297 1/40 FAZ-D1/3-RT 102298 1/40 FAZ-D1,5/3-RT 102299 1/40 FAZ-D2/3-RT 102300 1/40 FAZ-D3/3-RT 102301 1/40 FAZ-D4/3-RT 102302 1/40 FAZ-D5/3-RT 102303 1/40 FAZ-D6/3-RT 102304 1/40 FAZ-D7/3-RT 102305 1/40 FAZ-D8/3-RT 102306 1/40 FAZ-D10/3-RT 102307 1/40 FAZ-D13/3-RT 102308 1/40 FAZ-D15/3-RT 102309 1/40 FAZ-D16/3-RT 102310 1/40 FAZ-D20/3-RT 102311 1/40 FAZ-D25/3-RT 102312 1/40 FAZ-D30/3-RT 102313 1/40 FAZ-D32/3-RT 102314 1/40 FAZ-D35/3-RT 102315 1/40 FAZ-D40/3-RT 102316 1/40 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers FAZ-NA, -RT Miniature Circuit Breakers Accessories: Auxiliary switch for subsequent installation Tripping signal contact for subsequent installation Shunt trip release Z-IHK-NA Z-NHK FAZ-XAA-NA12-110VAC FAZ-XAA-NA110-415VAC IS/SPE-1TE Switching interlock 113895 248434 102037 102036 101911 Specifications FAZ-NA, FAZ,RT Technical data IEC/EN FAZ-...-NA, -RT Productstandard Number of poles IEC/EN 60947-2 1, 2, 3 Mechanical specifications Device width Frame size Socket size Device depth Terminals Terminal capacity rigid solid/stranded wire Terminal screw Terminal torque Snap on fixing Degree of Protection (DIN VDE 0470) Surface mounted Built-in behind panel Contact position indicator 17.7mm (1-pole), 35.4 mm (2-poles), 53.1 mm (3-poles) 45 mm 105 mm 60 mm lift terminal / ring-tongue 1-25 mm² M5 (with slotted screw Pozidriv PZ2) max. 2.4 Nm tristable (on DIN Rail acc. to IEC/EN 60715) IP 20 IP 40 red / green Electrical specifications Rated voltage Rated current Rated insulation voltage Rated impulse withstand voltage Un In Ui Uimp 240/415 V AC 0.5, 1, 1.5, 2, 3, 4, 5, 6, 7, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40 A 440 V AC 4 kV (1.2/50)µsec Tripping characteristic Conventional non-tripping current Conventional tripping current Reference temperature Temperature factor Instantaneous tripping current Rated short-circuit braking capacity Service short circuit capacity Selectivity class Number of electrical operations Number of mechanical operations Climatic conditions Imt Icu Ics Int=1.05 In It=1.30 In 30 °C 0.5% /K type B: 3 In < Imt = 5 In:t (Imt) < 0.1 sec (IEC/EN 60898-1) type C: 5 In < Imt = 10 In:t (Imt) < 0.1 sec (IEC/EN 60898-1) type D: 10 In < Imt = 20 In:t (Imt) < 0.1 sec (IEC/EN 60898-1) 15 kA 7.5 kA 3 (acc. to EN 60898) > 1500 > 10000 acc. to IEC 68-2 (25..55°C / 90..95% RH) Connection diagram 1-pole 2-pole 3-pole Chapter 4.1.1. – 80 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications FAZ-NA, FAZ-RT Technical data UL FAZ-...-NA, -RT Productstandard Number of poles UL 489 CSA C22.2 No. 5-02 1, 2, 3 Mechanical specifications Device width Frame size Socket size Device depth Terminals Terminal capacity 0.697 in. (1-pole), 1.394 in. (2-poles), 2.090 in. (3-poles) 1.772 in. 4.134 in. 2.362 in. lift terminal / ring-tongue 1 Wire: #18-6 AWG (Cu only) 2 Wires: #18-10 AWG (Cu only) M5 (with slotted screw Pozidriv PZ2) #18-12 AWG: 21 lb-in #10-8 AWG: 25 lb-in #6 AWG: 36 lb-in tristable (on DIN Rail acc. to IEC/EN 60715) red / green Terminal screw Terminal torque Snap on fixing Contact position indicator Electrical specifications Rated voltage Rated current Un In 0.5-32 A: 480Y/277 V AC, 35-40 A: 240 V AC 0.5, 1, 1.5, 2, 3, 4, 5, 6, 7, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40 A Tripping characteristic Conventional non-tripping current Conventional tripping current Reference temperature Temperature factor Instantaneous tripping current Current interrupting rating Current-Limiting at 240 V / 10 kA Current-Limiting at 480Y/277 V / 10 kA Current-Limiting at 480Y/277 V / 14 kA Selectivity class Number of electrical operations Number of mechanical operations Climatic conditions Imt Int=1.00 In It=1.35 In 40 °C 0.5% /K type C: 5 In < Imt = 10 In:t (Imt) < 0.1 sec type D: 10 In < Imt = 20 In:t (Imt) < 0.1 sec 10 kA, 14 kA (types D13, B/C/D15, 16, 20, B/C25 A) 1p, 2p, 3p to I2t = 43 kA2s and Ipeak = 6.2 kA 1p, 2p, 3p to I2t = 60 kA2s and Ipeak = 6.2 kA 1p, 2p, 3p to I2t = 65 kA2s and Ipeak = 7.5 kA 3 (acc. to EN 60898) 6000 10000 acc. to IEC 68-2 (25..55°C / 90..95% RH) Connection diagram 1-pole 2-pole 3-pole Chapter 4.1.1. – 81 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Dimensions (mm) FAZ-...-NA, -RT 1-pole 3-pole 2-pole Tripping Characteristic FAZ-...-NA, -RT Characteristics C and D - EN/IEC 60947-2 Characteristics C and D - UL 489 Chapter 4.1.1. – 82 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Internal Resistance FAZ-...-NA, -RT Type D Type C At room temperature (single pole) At room temperature (single pole) In [A] 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 * 50Hz Z* [mΩ] 6400 1100 560 340 132 86 70 31 28 20 15.8 12.3 7.1 7.1 6.0 4.1 2.8 2.8 2.5 2.1 R [mΩ] 6300 1080 550 330 130 85 69 30 27 19.6 15.5 12.1 7.0 7.0 5.9 4.0 2.7 2.7 2.5 2.1 In [A] 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 * Z* [mΩ] 6400 770 460 250 132 86 57 31 28 18 13.5 10.5 5.9 5.9 4.0 3.4 2.5 2.5 2.5 2.0 50Hz R [mΩ] 6300 755 450 245 130 85 56 30 27 17.6 13.2 10.3 5.8 5.8 3.9 3.3 2.5 2.5 2.5 2.0 1p 2p 3p P* [W] 1.6 0.8 1.0 1.0 1.2 1.4 1.5 1.2 1.4 1.2 1.5 2.0 1.5 1.7 1.8 2.6 2.7 3.1 3.8 3.9 P* [W] 3.2 1.5 2.1 2.1 2.4 2.9 2.9 2.3 2.8 2.4 3.0 4.1 3.1 3.5 3.7 5.1 5.4 6.2 7.6 7.8 P* [W 4.8 2.3 3.1 3.1 3.6 4.3 4.4 3.5 4.3 3.7 4.5 6.1 4.6 5.2 5.5 7.7 8.1 9.3 11.3 11.6 Power Loss at In FAZ-...-NA, -RT Type C In [A] 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 *50Hz Type D 1p 2p 3p P* [W] 1.6 1.1 1.3 1.4 1.2 1.4 1.9 1.2 1.4 1.4 1.8 2.4 1.9 2.1 2.9 3.1 3.0 3.4 3.7 4.0 P* [W] 3.2 2.2 2.6 2.8 2.4 2.9 3.7 2.3 2.8 2.8 3.6 4.7 3.8 4.3 5.8 6.2 6.0 6.8 7.4 8.1 P* [W 4.7 3.4 3.9 4.3 3.6 4.3 5.6 3.5 4.3 4.2 5.3 7.1 5.6 6.4 8.7 9.3 9.0 10.2 11.0 12.1 In [A] 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 *50Hz Chapter 4.1.1. – 83 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Energy FAZ-...-NA, -RT Type C (0.5 - 32 A), 277 V Type C (35 - 40 A), 240 V Type D (0.5 - 32 A), 277 V Type D (35 - 40 A), 240 V Chapter 4.1.1. – 84 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Maximum Let-Through Current FAZ-...-NA, -RT Type C (0.5 - 32 A), 277 V Type C (35 - 40 A), 240 V Type D (0.5 - 32 A), 277 V Type D (35 - 40 A), 240 V Chapter 4.1.1. – 85 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Z-SV/UL-16 Busbars for FAZ-NA ATTENTION: Maximum of 3 commoning links allowed. Any combination of same pole configuration. ATTENTION: 3 liaisons communes autorisées au maximum. Toute combinaison de configurations de polarité identiques. ACHTUNG: Maximal 3 Schienenblöcke. Beliebige Kombination gleichpoliger Konfigurationen. ATTENZIONE: Sono consentiti al massimo 3 pettini di collegamento in qualsiasi combinazione della stessa configurazione di poli. ATENCION: Se permite un máximo de 3 enlaces comunes. Cualquier combinación del mismo tipo de configuración de polo ! ! ATTENTION: Do not cut. ATTENTION: Ne pas couper. ACHTUNG: Nicht durchschneiden. ATTENZIONE: Non tagliare. ATENCION: No corte. UL489 EN/IEC 00947-2 Ue f Uimp 480 V AC 96 V DC 240/415 V AC 50/60 Hz ---------- 50/60 Hz ---------------------------- 9.5 kV Ie Cross section 80 A @ 40oC 80 A @ 30oC ---------------------------- 16 mm² UL489 EN/IEC 00947-2 UL489 EN/IEC 00947-2 Ue f Uimp 480 V AC 96 V DC 240/415 V AC 50/60 Hz ---------- 50/60 Hz ---------------------------- 9.5 kV Ue f Uimp 480 V AC 96 V DC 240/415 V AC 50/60 Hz ---------- 50/60 Hz ---------------------------- 9.5 kV Ie 115 A @ 40oC #1-14 AWG 60/75oC Cu 0.56 in Ie 80 A @ 40oC #2-14 AWG 60/75oC Cu 0.56 in 160 A @ 30oC 1.5-50 mm² Cu 14 mm Chapter 4.1.1. – 86 80 A @ 30oC 2.5-35 mm² Cu 14 mm EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Z-SV/UL-16 Busbars for FAZ-NA Z2 AWG 14 12-8 6-2 FAZ-NA FAZ-RT Ib-in 21 25 36 Nm 2.3 2.8 4.0 ZV-BS-UL 4 mm Z-EK/35/UL IEC/EN 60947-2 Icc Ue VAC Z-SV/UL Icc Amps 240/ 415 15000 UL SCCR FAZ-NA Ue FAZ-RT VAC In Amps Article No. 104892 104893 104894 104895 104896 104897 104898 104899 104900 104901 104902 104904 Z-SV/UL SCCR RMS Sym Amps 0.5-32 480Y/ 277 10000 35-40 240 10000 Z-SV/UL-16/1P-1TE/6 Z-SV/UL-16/1P-1TE/12 Z-SV/UL-16/1P-1TE/18 Z-SV/UL-16/2P-2TE/6 Z-SV/UL-16/2P-2TE/12 Z-SV/UL-16/2P-2TE/18 Z-SV/UL-16/3P-3TE/6 Z-SV/UL-16/3P-3TE/12 Z-SV/UL-16/3P-3TE/18 Z-EK/35/UL Z-EB/50/UL ZV-BS-UL 6 12 18 - 3 6 9 - Chapter 4.1.1. – 87 2 4 6 - EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Auxiliary Contacts and Voltage Trips for FAZ-NA, FAZ-RT Circuit Diagram Description Rated Operational Voltage Type Designation Article No. Units per package Z-IHK-NA 113895 1 248434 1 FAZ-XAA-NA12-110VAC 102037 1 FAZ-XAA-NA110-415VAC 102036 1 IS/SPE-1TE 1 Auxiliary contact SG60711 Same Polarity • Design according to IEC/EN 60947-5-1, 250 Vac IEC/EN 62019 • Field installable • The specified minimum voltages are per contact—take into account particularly in case of series connection • Self-cleaning contacts • Contact material and design particularly suitable for extra low voltage • Tripping signal contact transmits message of electric tripping, not mechanical switch-off • Test key for contact function “electrical tripping” • Will allow for > 480Y/277 Vac rating Two-pole auxiliary contact/trip indicating contact *) SG61011 • Design according to IEC/EN 60947-5-1, 250 Vac IEC/EN 62019 • Field installable • The specified minimum voltages are per contact—take into account particularly in case of series connection • Self-cleaning contacts • Contact material and design particularly suitable for extra low voltage • Tripping signal contact transmits message of electric tripping, not mechanical switch-off • Test key for contact function “electrical tripping” • The function of one of the two change-over contacts can be switched from “auxiliary switch” to “tripping signal switch” *) Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed Z-NHK Shunt Trip SG13511 1 2 • Remote release for subsequent mounting onto FAZ-NA • Additional installation of standard auxiliary switch is possible • Position indicator red–green 12–110 Vac 12–60 Vdc 110–415 Vac 110–230 Vdc Padlock Hasp (for all FAZ) • Prevents reactivation of the device during maintenance • Holds one padlock Chapter 4.1.1. – 88 101911 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications Accessories for FAZ-NA, FAZ-RT Technical Data Electrical Contact function Rated voltage Rated current Rated thermal current Ith Utilization category AC13 Rated operational current Ie Utilization category AC15 Rated operational current Ie Utilization category DC12 Rated operational current Ie Rated insulation voltage U Minimum operational voltage per contact Umin Minimum operational current Imin Rated peak withstand voltage Uimp (1.2/50µ) Conditional short circuit current Ik with Back-Up Fuse 6A Max. back-up fuse, overload and short circuit Mechanical Tripping indicator “electrical tripping” Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection I Terminals Terminal capacity Terminal screws Tightening torque of terminal screws Z-NHK Z-IHK-NA 2CO 230V 2A 2A 1NO + 1NC 250V 6A 6A 3A/250 Vac 3A/250 Vac 2A/250 Vac 2A/250 Vac 0.5A/110 Vdc 250 Vac 5 Vdc 10 mA DC 2.5 kV 0.5A/110 Vdc 0.25A/220 Vdc 250 Vac 5 Vdc 10 mA AC/DC 4 kV 1 kA 6A gL 1 kA — Blue/white 45 mm 80 mm 8.8 mm (0.5MU) Onto switching device IP40 Finger and hand touch safe according to BGV A3, ÖVE-EN 6 Lift terminals 20–14 AWG M3 (Pozidrive Z0) 7 lb-in — 45 mm 80 mm 8.8 mm (0.5MU) — IP40 Finger and hand touch safe according to BGV A3, ÖVE-EN 6 Lift terminals 0.5–2.5 mm2 M3 (Pozidrive Z0) max. 1.2 Nm Two-pole auxiliary contact/trip indicating contact Auxiliary contact Z-NHK Z-IHK-NA Chapter 4.1.1. – 89 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications Accessories for FAZ-NA, FAZ-RT Technical Data Electrical Can be mounted onto Operational voltage range Frequency Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity, one and two wires FAZ-XAA-NA12-110VAC FAZ-XAA-NA110-415VAC FAZ-NA / FAZ-NA-DC / FAZ-RT 12–110 Vac 12–60 Vdc 50/60 Hz FAZ-NA / FAZ-NA-DC / FAZ-RT 110–415 Vac 110–230 Vdc 50/60 Hz 45 mm 45 mm 105 mm 105 mm 17.5 mm 17.5 mm Quick fastening with two lock-in positions on EN 50022 IP40 IP40 Finger and hand touch safe Finger and hand touch safe according to BGV A3, ÖVE-EN 6 according to BGV A3, ÖVE-EN 6 Open mouthed/lift Open mouthed/lift 18–10 AWG 18–10 AWG Chapter 4.1.1. – 90 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Miniature Circuit Breakers AZ SG18811 • High-quality miniature circuit breakers for commercial and industrial applications • Contact position indicator red - green • Accessories suitable for subsequent installation • Rated currents up to 125 A • Tripping characteristics C, D • Rated breaking capacity up to 25 kA according to EN 60947-2 Chapter 4.1.1. – 91 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers AZ Miniature Circuit Breakers (MCBs) Characteristic C Rated current In (A) SG18411 211769 211774 211779 211784 211789 211794 211799 211804 211809 12 12 12 12 12 12 12 12 12 AZ-2-C20 AZ-2-C25 AZ-2-C32 AZ-2-C40 AZ-2-C50 AZ-2-C63 AZ-2-C80 AZ-2-C100 AZ-2-C125 211770 211775 211780 211785 211790 211795 211800 211805 211810 2 2 2 2 2 2 2 2 2 AZ-3-C20 AZ-3-C25 AZ-3-C32 AZ-3-C40 AZ-3-C50 AZ-3-C63 AZ-3-C80 AZ-3-C100 AZ-3-C125 211771 211776 211781 211786 211791 211796 211801 211806 211811 1 1 1 1 1 1 1 1 1 AZ-3N-C20 AZ-3N-C25 AZ-3N-C32 AZ-3N-C40 AZ-3N-C50 AZ-3N-C63 AZ-3N-C80 AZ-3N-C100 AZ-3N-C125 211773 211778 211783 211788 211793 211798 211803 211808 211813 1 1 1 1 1 1 1 1 1 AZ-4-C20 AZ-4-C25 AZ-4-C32 AZ-4-C40 AZ-4-C50 AZ-4-C63 AZ-4-C80 AZ-4-C100 AZ-4-C125 211772 211777 211782 211787 211792 211797 211802 211807 211812 1 1 1 1 1 1 1 1 1 3+N-pole 20 25 32 40 50 63 80 100 125 SG18811 AZ-C20 AZ-C25 AZ-C32 AZ-C40 AZ-C50 AZ-C63 AZ-C80 AZ-C100 AZ-C125 3-pole 20 25 32 40 50 63 80 100 125 SG18711 Units per package 2-pole 20 25 32 40 50 63 80 100 125 SG18611 Article No. 1-pole 20 25 32 40 50 63 80 100 125 SG18511 Type Designation 4-pole 20 25 32 40 50 63 80 100 125 Chapter 4.1.1. – 92 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers AZ Miniature Circuit Breakers (MCBs) Characteristic D Rated current In (A) SG18411 AZ-D50 AZ-D63 AZ-D80 AZ-D100 211814 211818 211822 211826 12 12 12 12 AZ-2-D50 AZ-2-D63 AZ-2-D80 AZ-2-D100 211815 211819 211823 211827 2 2 2 2 AZ-3-D50 AZ-3-D63 AZ-3-D80 AZ-3-D100 211816 211820 211824 211828 1 1 1 1 AZ-3N-D50 AZ-3N-D63 AZ-3N-D80 AZ-3N-D100 211817 211821 211825 211829 1 1 1 1 3-pole 50 63 80 100 SG18711 Units per package 2-pole 50 63 80 100 SG18611 Article No. 1-pole 50 63 80 100 SG18511 Type Designation 3+N-pole 50 63 80 100 Chapter 4.1.1. – 93 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Specifications | Miniature Circuit Breakers AZ Description • Independent switching contacts • With isolator function, meets the requirements of insulation coordination, distance between contacts ≥ 4 mm, for secure isolation Accessories: Auxiliary switch for subsequent installation (0.5 MU) Shunt trip release for subsequent installation (1.5 MU) Z-LHK Z-LHASA/230 Z-LHASA/24 LH-SPL LH-SPE LH-SPA Tripping interlock Switchoff interlock 248440 248442 248441 285752 215999 216000 Connection diagram 1-pole 2-pole 3-pole 3+N-pole 4-pole Technical Data AZ Electrical Standards Rated operating voltage Rated switching capacity Operational switching capacity Characteristic Max. back-up fuse Selectivity class Lifespan Direction of incoming supply Mechanical Standard front dimensions Device height Terminal protection Mounting width per pole Mounting Protection type Terminals top and bottom Terminal capacity (solid) Operations IEC/EN 60947-2 230/400 V AC 60 V DC (per pole) 25 kA 20 kA Similar: C, D 200 A gL/gG Compliant with class 3 >10000 Any 45 mm 90 mm Finger and back-of-proof to BGV A2 27 mm Top-hat rail to IEC/EN 60715 IP20, IP40 (enclosed) Lift terminals 2.5 – 50 mm2 Dimensions (mm) Chapter 4.1.1. – 94 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Load Capacity AZ Effect of ambient temperature Load capacity KT [I/In] Load capacity factor KN Load capacity in case of block installation Number of devices (n) 1-pole Ambient temperature T [°C] Permitted permanent load at ambient temperature T [°C] with n devices: IDL = InKT(T)KN(N). Maximum Let-Through Energy AZ Maximum let-through energy AZ, characteristic D, 1-pole ms Prospective short-circuit current [A] ha lf wa ve t= 10 Let through energy I2t [A2 sec] ha lf wa ve t= 10 m Let through energy I2t [A2 sec] s Maximum let-through energy AZ, characteristic C, 1-pole Prospective short-circuit current [A] Determined according to EN 60898-1. Chapter 4.1.1. – 95 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Short Circuit Selectivity AZ • Short circuit selectivity (in kA) between AZ and upstream fuse D0 or NH, operating class gL/gG • 1,4 . . selectivity up to 1.4 kA; . . . no selectivity Selectivity towards back-up fuses D01, D02, D03 Rated current In AZ in A 35 0,5 1,0 2,0 25 1,0 32 1,0 20 CCharacteristic Rated current of the back-up fuse in A 50 63 25 40 80 100 2,9 3,9 7,6 1,9 2,8 3,8 7,3 1,8 2,7 3,6 7,0 1,6 2,2 3,0 5,6 2,1 2,8 5,2 2,7 4,8 50 63 80 4,3 100 125 20 D-Characteristic 0,5 0,9 1,7 2,5 3,4 6,7 25 0,9 1,6 2,3 3,2 6,2 32 0,9 1,5 2,3 3,0 6,0 1,4 2,0 2,6 4,7 1,8 2,3 4,3 2,1 3,7 40 50 63 80 3,1 100 Selectivity towards back-up fuses NH Gr. 00 25 35 40 Rated current of the back-up fuse in A 50 63 80 100 125 160 200 0,5 1,0 1,3 1,9 2,7 3,7 6,7 17,0 25,0 25,0 25 0,9 1,3 1,8 2,6 3,5 6,5 17,0 25,0 25,0 32 0,9 1,2 1,7 2,4 3,3 6,0 15,0 23,0 25,0 1,4 2,1 2,9 4,8 12,0 18,0 25,0 1,9 2,7 4,5 11,0 17,0 25,0 63 4,2 10,0 15,0 25,0 80 3,8 8,5 12,0 25,0 7,0 10,0 25,0 7,5 25,0 Rated current In AZ in A 20 CCharacteristic 40 50 100 125 20 DCharacteristic 0,8 1,1 1,5 2,3 3,1 5,6 16,0 25,0 25,0 25 0,7 1,0 1,4 2,1 3,0 5,3 14,0 23,0 25,0 32 0,7 1,0 1,3 2,1 2,9 5,0 13,0 22,0 25,0 1,1 1,8 2,5 4,2 10,0 15,0 25,0 1,6 2,3 3,8 8,5 13,0 22,0 2,1 3,2 7,0 10,5 18,0 2,8 5,5 8,4 15,0 4,8 7,5 12,5 40 50 <0,5 63 80 100 Chapter 4.1.1. – 96 EATON CORPORATION xxxxx+xxxx-xxxxEN Miniature Circuit Breakers Short Circuit Selectivity AZ towards NZM 1 In case of short circuit, there is selectivity between the miniature circuit breakers AZ and the upstream NZM up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). Overload and short-circuit release unit NZM at max. value. *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic C towards NZM*) Short circuit selectivity characteristic D towards NZM*) AZ NZM...1-A gL/gG AZ NZM...1-A gL/gG In [A] 40 50 63 80 100 125 In [A] 40 20 0.3 0.4 0.5 0.75 0.9 1.25 50 25 0.3 0.4 0.5 0.7 0.9 1.2 63 0.4 0.5 0.7 0.85 1.2 80 0.5 0.6 0.85 1.1 100 0.6 0.85 1.1 0.8 1 32 40 50 63 80 50 63 80 100 125 1 100 125 no selectivity Short Circuit Selectivity AZ towards NZM 2 In case of short circuit, there is selectivity between the miniature circuit breakers AZ and the upstream NZM up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective devices will respond). Overload and short-circuit release unit NZM at max. value. *) basically in accordance with EN 60898-1 D.5.2.b Short circuit selectivity characteristic C towards NZM*) AZ NZM...2-A gL/gG In [A] 40 50 63 80 100 125 20 0.3 0.4 0.5 0.75 0.9 1.25 1.8 25 0.3 0.4 0.5 0.7 0.9 1.2 1.7 32 40 50 63 80 100 125 0.4 160 Short circuit selectivity characteristic D towards NZM*) AZ NZM...2-A gL/gG 250 In [A] 40 2.5 3.5 2.4 3.3 200 160 200 250 50 1 1.4 2.6 63 1 1.3 2.3 0.5 0.7 0.85 1.2 1.65 2.3 3.2 80 0.5 0.6 0.85 1.1 1.5 2.1 2.9 100 0.6 0.85 1.1 1.5 2 2.8 0.8 1 1.4 1.8 2.5 1 1.4 1.8 2.4 1.3 1.7 2.3 1.6 2.1 50 63 80 100 125 2.1 no selectivity Chapter 4.1.1. – 97 EATON CORPORATION xxxxx+xxxx-xxxxEN Busbar Systems Busbar System Easyvation BB-EV wa_sg05912 Easyvation at a glance: • Yard goods can be cut • No cutting back of copper required • No deburring required • Almost no waste during cutting • End capsavailable with 1- to 4-poles, end caps can be broken out for further extensions • 4-pole end cap molded in pairs (leftand right) Easyvation is the modular design system for busbars. Easyvation busbars • Overlapping rail extension possible are available as yard goods with 1, 2 or 3 poles. Now, there is a special feature: each bar can easily be extended by one-pole bar as you like. The additional pole can be added completely without tools by easy clamping technique. The lugs or forks in the Easyvationbars - available in 10 and 16 mm2 and all common distances - can be broken out at a predetermined breaking • Rails can be extended on demand by 1-pole rails (plug-in technology) • All step distances • 10 and 16 mm2 • Fork and stud point. There is actually no more flexibility available. • Lugs can be broken out at any predetermined breaking point Easyvation saves time and material • Self adhesive phase indication labels available The yard good can be cut with a saw of course. However, there is no need • Contact preventing caps (ZV-BS-G) can be used neither for deburring nor for cutting the conductor. Just cut to the required dimension and close with the fitting end cap -ready! The end caps have also breakable edges, which enable further connecting of the Easyvation. By overlapping assembly, doubling the cross section can be achieved. • Simple, flexible handling • All assembly requirements can be covered by Easyvation • Low storage space requirements due to modular system • Less time consuming (no deburring, no cutting back) Easyvation in use • Individual and self configurable Easyvation is especially well suited for solving flexible busbar applications rack-mounted models in series. Fork-pin combinations for 1+N-applications • Fork-pin combination for 1+N application possible, feeding through rail (terminal clamp) not possible. can be realized by individual combinations - for this also the one-pole version with blue isolation is available besides the one with grey isolation. • Protected technology Even different cross sections can be combined in this case. Accessories, such as feeder terminals and self adhesive phase marking labels will complete the comfortable total package. Existing contact prevention caps can be used. Chapter 5.1.1. – 1 EATON CORPORATION xxxxx+xxxx-xxxxEN Busbar Systems Description Step Distance (mm) Cu-factor Type Designation Article No. Units per package 0.22 0.24 0.24 0.31 0.36 0.46 0.58 0.56 0.58 0.57 0.22 0.24 0.24 BB-EVF-10/1P-1MU BB-EVF-10/1P-2MU BB-EVF-10/1P-3MU BB-EVF-10/2P-1MU BB-EVF-10/2P-2MU BB-EVF-10/3P-1MU BB-EVF-10/3P-2MU BB-EVF-10/3P-3MU BB-EVF-10/3P-1MU/AUX BB-EVF-10/3P-1MU2AUX BB-EVF-10/N-1MU BB-EVF-10/N-2MU BB-EVF-10/N-3MU 168826 168830 168834 168838 168840 168842 168844 168850 168846 168848 168828 168832 168836 10 10 10 10 10 10 10 10 10 10 10 10 10 0.33 0.36 0.32 0.46 0.54 0.69 0.87 0.84 0.87 0.86 0.33 0.36 0.32 BB-EVF-16/1P-1MU BB-EVF-16/1P-2MU BB-EVF-16/1P-3MU BB-EVF-16/2P-1MU BB-EVF-16/2P-2MU BB-EVF-16/3P-1MU BB-EVF-16/3P-2MU BB-EVF-16/3P-3MU BB-EVF-16/3P-1MU/AUX BB-EVF-16/3P-1MU2AUX BB-EVF-16/N-1MU BB-EVF-16/N-2MU BB-EVF-16/N-3MU 168827 168831 168835 168839 168841 168843 168845 168851 168847 168849 168829 168833 168837 10 10 10 10 10 10 10 10 10 10 10 10 10 Easyvation busbar 1m 10mm2, 16mm2 (Fork) BB-EVF for MCBs, RCCBs, RCBOs, SPDs • Delivered without end caps wa_sg05712 10 mm2, Rated Current 63 A 1-phase 2-phase wa_sg05812 3-phase 3-phase + AUX Neutral wa_sg05912 17.8 27 36 17.8 27 17.8 27 36 3x17.5+1x9 3x17.5+2x9 17.8 27 36 16 mm2, Rated Current 80 A 1-phase 2-phase wa_sg06012 3-phase 3-phase + AUX Neutral 17.8 27 36 17.8 27 17.8 27 36 3x17.5+1x9 3x17.5+2x9 17.8 27 36 Chapter 5.1.1. – 2 EATON CORPORATION xxxxx+xxxx-xxxxEN Busbar Systems Description Step Distance (mm) Cu-factor Type Designation Article No. Units per package 0.22 0.24 0.24 0.31 0.36 0.46 0.58 0.56 0.58 0.57 0.22 0.24 0.24 BB-EVP-10/1P-1MU BB-EVP-10/1P-2MU BB-EVP-10/1P-3MU BB-EVP-10/2P-1MU BB-EVP-10/2P-2MU BB-EVP-10/3P-1MU BB-EVP-10/3P-2MU BB-EVP-10/3P-3MU BB-EVP-10/3P-1MU/AUX BB-EVP-10/3P-1MU2AUX BB-EVP-10/N-1MU BB-EVP-10/N-2MU BB-EVP-10/N-3MU 168852 168856 168860 168864 168866 168868 168870 168876 168872 168874 168854 168858 168862 10 10 10 10 10 10 10 10 10 10 10 10 10 0.33 0.36 0.32 0.46 0.54 0.69 0.87 0.84 0.87 0.86 0.33 0.36 0.32 BB-EVP-16/1P-1MU BB-EVP-16/1P-2MU BB-EVP-16/1P-3MU BB-EVP-16/2P-1MU BB-EVP-16/2P-2MU BB-EVP-16/3P-1MU BB-EVP-16/3P-2MU BB-EVP-16/3P-3MU BB-EVP-16/3P-1MU/AUX BB-EVP-16/3P-1MU2AUX BB-EVP-16/N-1MU BB-EVP-16/N-2MU BB-EVP-16/N-3MU 168853 168857 168861 168865 168867 168869 168871 168877 168873 168875 168855 168859 168863 10 10 10 10 10 10 10 10 10 10 10 10 10 Type Designation Article No. Units per package - BB-EV-EC/1P BB-EV-EC/2-3P BB-EV-EC/4P BB-EV-EC/N 168878 168823 168824 168879 40 40 20 20 0.04 BB-EV-TE/35 168825 3 - KLEBEBOGEN-PHASENFOLGE 169831 5 - ZV-BS-G 10/600 Easyvation busbar 1m 10mm2, 16mm2 (Pin) BB-EVP for MCBs, RCCBs, RCBOs, SPDs • Delivered without end caps wa_sg06112 10 mm2, Rated Current 63 A 1-phase 2-phase wa_sg06212 3-phase 3-phase + AUX Neutral wa_sg06312 17.8 27 36 17.8 27 17.8 27 36 3x17.5+1x9 3x17.5+2x9 17.8 27 36 16 mm2, Rated Current 80 A 1-phase 2-phase wa_sg06412 3-phase 3-phase + AUX Neutral 17.8 27 36 17.8 27 17.8 27 36 3x17.5+1x9 3x17.5+2x9 17.8 27 36 Description Cu-factor Accessories End caps BB-EV-EC wa_sg05612 1-phase 2+3-phase 4-phase Neutral Terminal BB-EV-TE/35 wa_sg05312 Sticker phase sequence wa_sg06512 Busbar Tag Shrouds ZV-BS-G SG05705 Chapter 5.1.1. – 3 104903 EATON CORPORATION xxxxx+xxxx-xxxxEN Busbar Systems Technical Data BB-EV. General Heat deflection temperature Standards Climate stability Insulation coordination Electrical Impulse voltage strenght Min. air distance Min. creeping distance Max. operating voltage ≥80°C UL94 VO EN 60947-1:2007 / IEC 60947-1:2007 / IEC 60999:2000 according to DIN EN 60068 Overvoltage category III / Degree of pollution 2 ≥4.5 kV >5.5 mm >5 mm 690 V AC/DC 1,000 V DC 1-pole only Max. current Is/Phase 10 mm2 16 mm2 Protection class Short circuit rating 63 A 80 A IP20 ICC 25kA - NH3 355A gC500V JM PC - ABS >32 kV / mm Dielectric strenght Assembly instruction: Cutting Mounting of an extension busbar Overlapping mounting or further connection, resp. Brecking out of connection lugs Sticking on phase marking Chapter 5.1.1. – 4 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for RCDs, MCBs, Combined RCD/MCB Devices SG30811 • Auxiliary Switch • RCD-Tripping Module • Shunt Trip Release • Undervoltage Release • Remote Control and Automatic Switching Device • Switching Interlocks • Terminal Covers SG60811 Chapter 5.1.1. – 5 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Auxiliary Switch Z-HK, Z-AHK, Z-HD; Tripping Signal Switch Z-NHK Design: for screwing For Protective Device / Function Type Designation Article No. Units per package RCCB / 1NO+1NC Z-HK 248432 4/120 MCB, RCBO, RCCB / 1NO+1NC Z-AHK 248433 4/120 MCB, RCBO, RCCB / 2CO Z-NHK 248434 4/120 RCCB / 1CO+1NC Z-HD 265620 1 SG34812 SG60911 SG61011 SG34412 Specifications | Auxiliary Switch Z-HK, Z-AHK; Tripping Signal Switch Z-NHK Description • Design according to IEC/EN 60947-5-1, IEC/EN 62019 • Can be mounted subsequently (screws) onto FRCmM, FRCdM • The specified minimum voltages are per contact. Take into account particularly in case of series connection! Connection diagram Dimensions (mm) Z-HK Z-HK Z-AHK Z-NHK • Z-AHK, Z-NHK: Contact function with relative movement (selfcleaning contacts) • Contact material and design particularly suitable for extra low voltage • Z-NHK: The function of one of the two change-over contacts can be switched from “auxiliary switch” to “tripping signal switch” • Tripping signal contact transmits message of electric tripping, not mechanical switch-off • Test key for contact function “electrical tripping” Z-AHK Z-NHK 13 21 22 14 Chapter 5.1.1. – 6 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Technical Data Electrical Contact function Rated voltage Frequency Rated current Rated thermal current Utilisation category AC13 Rated operational current Utilisation category AC15 Rated operational current Utilisation category DC12 Rated operational current Utilisation category DC13 Rated operational current Rated insulation voltage Minimum operational voltage per contact Minimum operational current Rated peak withstand voltage Conditional short circuit current with back-up fuse 6A or FAZ-B4-HS Max. back-up fuse, overload and short circuit Mechanical Can be mounted from the left onto Can be mounted from the right onto Tripping indicator “electrical tripping” Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws Z-HK Z-AHK Z-NHK 1NO + 1NC 250 V 50/60 Hz 8A 8A 1NO + 1NC 250 V 50/60 Hz 4A 4A 2CO 250 V 50/60 Hz 4A 4A Ie 6A/250V AC 2A/440V AC 3A/250V AC – 3A/250V AC – Ie – 2A/250V AC 2A/250V AC Ie – 0.5A/110V DC 0.5A/110V DC Ie 0.5A/230V DC 2A/110V DC 4A/60V DC 250 V AC 24 V AC/DC 50 mA AC/DC 2.5 kV – – – 250 V AC 5 V DC 10 mA DC 2.5 kV – – – 250 V AC 5 V DC 10 mA DC 2.5 kV 1 kA 6 A gL / FAZ-4/../B-HS 1 kA 4 A gL / FAZ-4/../B-HS 1 kA 4 A gL / FAZ-4/../B-HS Ith UI Umin Imin Uimp (1.2/50µ) Ik RCCB MCB, RCBO MCB, RCBO – – RCCB – – blue/white 45 mm 45 mm 45 mm 80 mm 80 mm 80 mm 8.8 mm (0.5MU) 8.8 mm (0.5MU) 8.8 mm (0.5MU) onto switching device onto switching device onto switching device IP40 IP40 IP40 finger and hand touch safe according to BGV A3, ÖVE-EN 6 lift terminals lift terminals lift terminals 0.5-2.5 mm2 0.5-2.5 mm2 0.5-2.5 mm2 M3 (Pozidrive Z0) M3 (Pozidrive Z0) M3 (Pozidrive Z0) max. 0.8-1.0 Nm max.0.8-1.0 Nm max. 0.8-1.0 Nm Example: Z-HK+RCCB Example: Z-AHK+MCB 1NO+1NC 24V 50mA min. 1NO+1NC 5V 10mA min. Example: Z-NHK+MCB RCCB+Z-NHK 2CO 5V 10mA min. Chapter 5.1.1. – 7 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Specifications | Auxiliary Switch Z-HD Function Auxiliary Switch Z-HD Tripping signal switch: detects if RCD tripping occured by an fault current Auxiliary switch: shows the contact position of the RCD Connection diagram Z-HD Technical Data Z-HD Electrical Subsequent installation to the left onto Contacts Load rating AC11 DC11 Mechanical Terminal capacity FRCmM-125A 1CO + 1NC 6 A / 230 V AC 1 A / 230 V DC up to 2.5 mm2 Dimensions (mm) Chapter 5.1.1. – 8 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Auxiliary Switch ZP-AHK, ZP-IHK, ZP-WHK; Tripping Signal Switch ZP-NHK Design: for snapping For Protective Device / Function Type Designation Article No. Units per package MCB, RCBO / 1NO+1NC ZP-IHK 286052 4/120 MCB, RCBO / 1CO ZP-WHK 286053 4/120 MCB, RCBO / 2CO ZP-NHK 248437 4/120 SG60811 SG34612 SG34512 Specifications | Auxiliary Switch ZP-IHK, ZP-WHK; Tripping Signal Switch ZP-NHK Description • Design according to IEC/EN 62019 • No screws required. Can be snapped onto FAZ and FRBmM-1N subsequently • ZP-IHK, ZP-WHK: Can be snapped on additionally 1 time onto itself • The specified minimum voltages are per contact. Take into account particularly in case of series connection! • Contact material and design particularly suitable for extra low voltage. • Contact function with relative movement (self-cleaning contacts)e) • ZP-NHK: The function of one of the two change-over contacts can be switched from “auxiliary switch” to "tripping signal switch" • Tripping signal contact transmits message of electric tripping, not mechanical switch-off • ZP-NHK: The “Service button” is used to check whether or not the auxiliary switch is correctly wired in the tripping-signal-switch position. Activating the “service button” will mechanically simulate an electrical switch-off, so the mechanism for the electrical switchoff will disengage and can be checked. The main switchgear (MCB or combined MCB/RCD) connected to the ZP-NHK auxiliary switch does not need to trip as well during an inspection through the service button. Connection diagram ZP-IHK ZP-WHK ZP-NHK Chapter 5.1.1. – 9 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Technical Data Electrical Contact function Rated voltage Frequency Rated current Rated thermal current Utilisation category AC13 Rated operational current Utilisation category AC15 Rated operational current Utilisation category DC12 Rated operational current Rated insulation voltage Minimum operational voltage per contact Minimum operational current Rated peak withstand voltage Conditional short circuit current with back-up fuse 6A or PLSM-B4-HS Max. back-up fuse, overload and short circuit Mechanical Can be mounted from the left onto Accessories: Tripping indicator “electrical tripping” Frame size Device height Device width Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws ZP-IHK ZP-WHK ZP-NHK Ith 1NO + 1NC 250 V 50/60 Hz 6A 6A 1CO 250 V 50/60 Hz 6A 6A 2CO 250 V 50/60 Hz 4A 4A Ie 3A/250V AC 3A/250V AC 3A/250V AC Ie 2A/250V AC 2A/250V AC 2A/250V AC Ie UI 0.5A/110V DC 250 V AC 5 V DC 10 mA DC 2.5 kV 0.5A/110V DC 250 V AC 5 V DC 10 mA DC 2.5 kV 0.5A/110V DC 250 V AC 5 V DC 10 mA DC 2.5 kV 1 kA 6 A gL / FAZ-B4-HS 1 kA 6 A gL / FAZ-B4-HS 1 kA 6 A gL / FAZ-B4-HS Umin Imin Uimp (1.2/50µ) Ik MCB, RCBO MCB, RCBO MCB, RCBO ZP-ASA ZP-ASA ZP-ASA – – blue/white 45 mm 45 mm 45 mm 80 mm 80 mm 80 mm 8.8 mm (0.5MU) 8.8 mm (0.5MU) 8.8 mm (0.5MU) IP40 IP40 IP40 finger and hand touch safe according to BGV A3, ÖVE-EN 6 lift terminals lift terminals lift terminals 0.5-2.5 mm2 0.5-2.5 mm2 0.5-2.5 mm2 M4 (Pozidrive Z2) M4 (Pozidrive Z2) M3 (Pozidrive Z0) max. 1.2 Nm max. 1.2 Nm max. 0.8-1.0 Nm Dimensions (mm) ZP-IHK, ZP-WHK ZP-NHK Example: ZP-IHK/(ZP-WHK)+MCB Example: ZP-NHK+MCB Chapter 5.1.1. – 10 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices RCCB-Tripping Module Z-.AM For Protective Device Type Designation Article No. Units per package RCCB Z-FAM 248293 1/60 RCBO Z-KAM 248294 1/60 SG16011 SG16211 Specifications | RCCB Tripping Module Z-FAM, Z-KAM Description • For remote switch-off of RCCBs, standard and electronic combined RCD/MCB devices • Remote switch-off by one or several parallel potential-free contacts, e.g. pushbutton max. rated current 3 A at 250 V, take into account maximum pushbutton voltage • Remote tripping test by means of remote testing module Z-FW • Can be mounted subsequently, to be wired according to connection diagram with the respective terminals of the RCCB • No undesired voltage rise in the consumer system during remote switch-off thanks to integrated breaker contact K1-K2 Connection diagram Z-FAM W1 Z-KAM K1 W Ω W2 W1 K2 W2 Chapter 5.1.1. – 11 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Technical Data Electrical Rated voltage Frequency Rated tripping current Function IΔn Mechanical Tripping module for Frame size Device height Device width Degree of protection, built-in Terminal capacity Terminal protection Z-FAM Z-KAM 230(400) V AC 50-60 Hz 0.01 - 0.3 A 1NO 230(400) V AC 50-60 Hz 0.01 - 0.3 A 1NO RCCB RCBO 45 mm 45 mm 80 mm 80 mm 8.8 mm (0.5MU) 8.8 mm (0.5MU) IP40 IP40 1 - 2x2.5 mm2 1 - 2x2.5 mm2 finger and hand touch safe, according to BGV A3, ÖVE-EN 6 Dimensions (mm) Z-FAM Z7-FAM Z-KAM Z7-KAM 5,5 23 80 8,8 8,8 8,8 45 44 60 Connection examples Lay lines to the switching devices with double insulation and overload protection, e.g. 4A gL or CLS6-4..-HS Connection diagram: RCCB-2p, RCCB feed above Connection diagram: RCCB-4p, RCCB feed above Z-FAM Z-FAM Connection diagram: RCBO-2p, RCBO feed below Connection diagram: RCCB-4p, RCCB feed below Z-FAM Z-KAM Chapter 5.1.1. – 12 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Shunt Trip Release Z-ASA, ZP-ASA Operational voltage range (V~) Type Designation Article No. Units per package To be glued on 12-110 110-415 Z-ASA/24 Z-ASA/230 248286 248287 1/60 1/60 To be snapped on 12-110 110-415 ZP-ASA/24 ZP-ASA/230 248438 248439 1/60 1/60 SG00712 SG00212 Specifications | Shunt Trip Release Z-ASA, ZP-ASA Description • Remote release for subsequent mounting onto FAZ, FRBmM-1N, Z-MS • Module width 1MU • Additional installation of standard auxiliary switch is possible • Position indicator red - green • Type ZP-ASA for snap-on mounting Connection diagram 1 2 Dimensions (mm) Z-ASA ZP-ASA Chapter 5.1.1. – 13 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Technical Data Z-ASA24 Z-ASA230 ZP-ASA24 ZP-ASA230 15 ms 2.2 Ω 100% < 20 ms 2.5 kV > 4000 operating cycles 10 ms 215 Ω 100% < 20 ms 2.5 kV > 4000 operating cycles 15 ms 2.2 Ω 100% < 20 ms 2.5 kV > 4000 operating cycles 10 ms 215 Ω 100% < 20 ms 2.5 kV > 4000 operating cycles 10 V 12-110 V 15 A 10 ms 60 V 110-415 V 10 V 12-110 V 2.1 A 10 ms 60 V 110-415 V 15 A 10 ms 2.1 A 10 ms 9V 10-60 V 21 A 2 ms 72 V 110-220 V 9V 10-60 V 1A 2 ms 72 V 110-220 V 21 A 2 ms 1A 2 ms 45 mm 80 mm 17.5 mm (1MU) bonding IP40 open mouthed/lift 45 mm 80 mm 17.5 mm (1MU) bonding IP40 open mouthed/lift Klemmquerschnitt Fastening torque of terminal screws 1-25 mm2 max. 2.4 Nm 1-25 mm2 max. 2.4 Nm 45 mm 80 mm 17.5 mm (1MU) to snap on IP40 open mouthed/lift with guide 1-25 mm2 max. 2.4 Nm 45 mm 80 mm 17.5 mm (1MU) to snap on IP40 open mouthed/lift with guide 1-25 mm2 max. 2.4 Nm Connection Example 230 V Connection Example 24 V Example: Z-ASA + MCB Example: ZP-ASA + MCB Electrical Minimum pulse duration Internal resistance Duty cycle Tripping time Rated peak withstand voltage (1.2/50µs) Endurance AC voltage range Operating limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption DC voltage range Operating limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Terminals above/below Chapter 5.1.1. – 14 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Undervoltage Release Z-USA, Z-USD Operational voltage range (V~) / Function Type Designation Article No. Units per package Z-USA/115 Z-USA/230 Z-USA/400 Z-USD/115 Z-USD/230 248288 248289 248290 248292 248291 1/60 1/60 1/60 1/60 1/60 SG78811 To be screwed on 115 / undelayed 230 / undelayed 400 / undelayed 115 / delayed 0.4s 230 / delayed 0.4s Specifications | Undervoltage Release Z-USA, Z-USD Description • Tripping: Instantaneous Z-USA Delayed Z-USD, typ. 0,4 s • Voltage control indicator blue/white • Service key for zero voltage switch-on for testing purposes • Can be used with FAZ Connection diagram 0,4 s Chapter 5.1.1. – 15 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Technical Data Electrical Rated voltage Frequency Making threshold Tripping threshold Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Terminals Terminal capacity Terminal protection Un Z-US./115 Z-US./230 Z-US./400 115 V AC 50-60 Hz 80% of Un 50% of Un 230 V AC 50-60 Hz 80% of Un 50% of Un 400 V AC 50-60 Hz 80% of Un 50% of Un 45 mm 45 mm 45 mm 80 mm 80 mm 80 mm 17.5 mm (1MU) 17.5 mm (1MU) 17.5 mm (1MU) quick fastening on DIN rail IEC/EN 60715 IP40 IP40 IP40 open mouthed/lift open mouthed/lift open mouthed/lift 1 - 2x2.5 mm2 1 - 2x2.5 mm2 1 - 2x2.5 mm2 finger and hand touch safe, according to BGV A3, ÖVE-EN 6 Dimensions (mm) Connection Example Release Connection Examplees 400V and 230V Connection example Z-USA/400 + Z-MS Chapter 5.1.1. – 16 Connection example Z-USA/230 + MCB EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Switching interlocks IS/SPE-1TE, Z-IS/SPE-1TE Description Type Designation Article No. Units per package Switching interlock without lock for Isolators, RCDs, combined RCD/MCBs, ... Switching interlock without lock for MCBs and Circuit Breaker ZP-A IS/SPE-1TE 101911 5/30 Z-IS/SPE-1TE 274418 5/30 SG47812 Specifications | Switching interlocks IS/SPE-1TE, Z-IS/SPE-1TE Description • Without lock Type IS/SPE-1TE: • for Isolators, RCDs, combined RCD/MCBs, ... Type Z-IS/SPE-1TE: • for MCB Chapter 5.1.1. – 17 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for Add-on Residual Current Protection Unit FBHmV Shunt Trip Release Kit Z-BHASA Operational voltage range V~ Type Designation Article No. Units per package 110-415 12-60 Z-BHASA/230 Z-BHASA/24 248445 248444 8 8 SG09411 Specifications | Shunt Trip Release Kit Z-BHASA Description • Can be mounted subsequently • Contact position indicator red - green • Wide operational voltage range • Sufficient power of extra low voltage source must be ensured FBHmV-ASA/24: min. 90 VA • Screws for mounting included FBHmV => BHASA => AZ Connection diagram 1 2 Chapter 5.1.1. – 18 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for Add-on Residual Current Protection Unit FBHmV Technical Data Electrical Minimum pulse duration Internal resistance Duty Tripping time Peak withstand voltage (1.2/50µs) Endurance AC voltage range: Responding limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption DC voltage range: Responding limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminal screws Terminal capacity Fastening torque of terminal screws Z-BHASA/24 Z-BHASA/230 15 ms 2W 100% < 20 ms 2 kV >4,000 operating cycles 10 ms 130 W 100% < 20 ms 2 kV >4,000 operating cycles 8V 12-60 V 14 A 4.0 ms 70 V 110-415 V 3.4 A 4.5 ms 11 V 12-60 V 23.5 A typ. 2 ms 90 V 110-230 V 1.7 A typ. 4 ms 45 mm 45 mm 90 mm 90 mm 27 mm 27 mm quick fastening on DIN rail IEC/EN 60715 IP40 IP40 lift terminals lift terminals 2.5-30 mm2 2.5-30 mm2 4 Nm 4 Nm Dimensions (mm) Chapter 5.1.1. – 19 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for Miniature Circuit Breakers AZ Shunt Trip Release Z-LHASA Operational voltage range V~ Type Designation Article No. Units per package 110-415 12-60 Z-LHASA/230 Z-LHASA/24 248442 248441 8 8 SG09311 Specifications | Shunt Trip Release Z-LHASA Description • Can be mounted subsequently • Contact position indicator red - green • Wide operational voltage range • Sufficient power of extra low voltage source must be ensured Z-LHASA/24: min. 90 VA Connection diagram Dimensions (mm) 1 2 Technical Data Electrical Minimum pulse duration Internal resistance Duty Tripping time Peak withstand voltage (1.2/50µs) Endurance AC voltage range: Responding limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption DC voltage range: Responding limit Operational voltage range Maximum current consumption during switch-on Current flow time at max. current consumption Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminal screws Terminal capacity Fastening torque of terminal screws Z-LHASA/24 Z-LHASA/230 15 ms 2W 100% < 20 ms 2 kV >4,000 operating cycles 10 ms 130 W 100% < 20 ms 2 kV >4,000 operating cycles 8V 12-60 V 14 A 4.0 ms 70 V 110-415 V 3.4 A 4.5 ms 11 V 12-60 V 23.5 A typ. 2 ms 90 V 110-230 V 1.7 A typ. 4 ms 45 mm 45 mm 90 mm 90 mm 27 mm 27 mm quick fastening on DIN rail IEC/EN 60715 IP40 IP40 lift terminals lift terminals 2.5-30 mm2 2.5-30 mm2 4 Nm 4 Nm Chapter 5.1.1. – 20 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for Miniature Circuit Breakers AZ Auxiliary Switch Z-LHK Function Type Designation Article No. Units per package 1NO+1NC Z-LHK 248440 10/100 SG16111 Specifications | Auxiliary Switch Z-LHK Description • Auxiliary switch according to IEC 947-5-1 • Can be mounted subsequently Technical Data Z-LHK Electrical Contact function Rated voltage Frequency Rated current Rated thermal current Utilisation category AC13 Rated operational current Utilisation category AC15 Rated operational current Utilisation category DC12 Rated operational current Utilisation category DC13 Rated operational current Rated insulation voltage Minimum operational voltage per contact Minimum operational current Rated peak withstand voltage Conditional short circuit current with back-up fuse 6A or FAZ-B4-HS Max. back-up fuse, overload and short circuit Mechanical Can be mounted from the left onto Can be mounted from the right onto Tripping indicator “electrical tripping” Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws Ith 1NO + 1NC 250 V 50/60 Hz 8A 8A Ie 6A/250V AC 2A/440V AC Ie – Ie – Ie 0.5A/230V DC 2A/110V DC 4A/60V DC 250 V AC 24 V AC/DC 50 mA AC/DC 2.5 kV UI Umin Imin Uimp (1.2/50µ) Ik 1 kA 6 A gL / FAZ-4/../B-HS AZ – – 45 mm 80 mm 8.8 mm (0.5MU) onto switching device IP40 finger and hand touch safe according to BGV A3, ÖVE-EN 6 lift terminals 0.5-2.5 mm2 M3 (Pozidrive Z0) max. 0.8-1.0 Nm Chapter 5.1.1. – 21 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Connection diagram 13 21 22 14 Dimensions (mm) Chapter 5.1.1. – 22 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for Miniature Circuit Breakers AZ Interlocks LH-SP Function Type Designation Article No. Units per package Tripping interlock Tripping interlock Switchoff interlock LH-SPL LH-SPE LH-SPA 285752 215999 216000 1 1 1 Specifications | Anti-Tamper Device LH-SPE, LH-SPL Description • Prevents undesired switching ON or OFF Specifications | Switchoff Interlock LH-SPA Description • Prevents undesired switch-OFF Dimensions (mm) Chapter 5.1.1. – 23 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for Miniature Circuit Breaker FAZ-..-NA, -RT Auxiliary Contact Z-IHK-NA Operational Voltage Range Type Designation Article No. Units per package 250 VAC Z-IHK-NA 113895 1 SG60711 Specifications | Auxiliary Contact Z-IHK-NA Description • Design according to IEC/EN 60947-5-1, IEC/EN 62019 • Field installable • The specified minimum voltages are per contact—take into account particularly in case of series connection • Self-cleaning contacts • Contact material and design particularly suitable for extra low voltage • Tripping signal contact transmits message of electric tripping, not mechanical switch-off • Test key for contact function “electrical tripping” • Will allow for > 480Y/277 VAC rating Connection diagram Chapter 5.1.1. – 24 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Technical Data Z-IHK-NA Electrical Contact function Rated voltage Rated current Rated thermal current Utilization category AC13 Rated operational current Utilization category AC15 Rated operational current Utilization category DC12 Rated operational current Rated insulation voltage Minimum operational voltage per contact Minimum operational current Rated peak withstand voltage Conditional short circuit current with Back-Up Fuse 6A Max. back-up fuse, overload and short circuit Mechanical Tripping indicator “electrical tripping” Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Tightening torque of terminal screws Ith 1NO + 1NC 250V 6A 6A Ie 3A/250 Vac Ie 2A/250 Vac Ie U 0.5A/110 Vdc 250 Vac 5 Vdc 10 mA AC/DC 4 kV I Umin Imin Uimp (1.2/50µ) Ik 1 kA 6 A gL / FAZ-4/../B-HS — 45 mm 80 mm 8.8 mm (0.5MU) — IP40 Finger and hand touch safe according to BGV A3, ÖVE-EN 6 Lift terminals 0.5–2.5 mm2 M3 (Pozidrive Z2) max. 1.2 Nm Dimensions (mm) Chapter 5.1.1. – 25 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Accessories for Miniature Circuit Breaker FAZ-..-NA, -RT Shunt Trip FAZ-XAA-NA Operational Voltage Range Type Designation Article No. Units per package 12–110 VAC 12–60 VDC 110–415 VAC 110–230 VDC FAZ-XAA-NA12-110VAC 102037 1 FAZ-XAA-NA110-415VAC 102036 1 SG13511 Specifications | Shunt Trip FAZ-XAA-NA Description • Remote release for subsequent mounting onto FAZ-NA • Additional installation of standard auxiliary switch is possible • Position indicator red–green Connection diagram 1 2 Technical Data Electrical Can be mounted onto Operational voltage range Frequency Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity, one and two wires FAZ-XAA-NA12-110VAC FAZ-XAA-NA110-415VAC FAZ-NA / FAZ-NA-DC / FAZ-RT 12–110 Vac 12–60 Vdc 50/60 Hz FAZ-NA / FAZ-NA-DC / FAZ-RT 110–415 Vac 110–230 Vdc 50/60 Hz 45 mm 45 mm 105 mm 105 mm 17.5 mm 17.5 mm Quick fastening with two lock-in positions on EN 50022 IP40 IP40 Finger and hand touch safe Finger and hand touch safe according to BGV A3, ÖVE-EN 6 according to BGV A3, ÖVE-EN 6 Open mouthed/lift Open mouthed/lift 18–10 AWG 18–10 AWG Chapter 5.1.1. – 26 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Terminal Covers Description Type Designation Article No. Units per package Terminal Covers for RCDs 2-pole 4-pole Z-RC/AK-2TE Z-RC/AK-4TE 285385 101062 10 10 Terminal Covers for Add-on Device 2-pole 3+4-pole Z-CV/AO-2P Z-CV/AO-3-4P 221957600 221957500 ? ? Terminal Covers for MCB, RCBO 2-pole 3-pole 4-pole Z-CV/SD-2P Z-CV/SD-3P Z-CV/SD-4P 221954800 221954900 221953900 ? ? ? Terminal Cover for MCB 1-pole Z7-AK-1TE 750754200 ? Chapter 5.1.1. – 27 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Remote Control and Automatic Switching Device Z-ZW Function Type Designation Article No. Units per package Automatic restarting 230VAC Automatic restarting 24-48VDC Z-FW-LP Z-FW-LPD 248296 265244 1/20 1/20 + Remote control Z-FW-MO ON/OFF/TEST (only in connection with Z-FW-LP, -LPD from delivery date 2006!) 284730 1 Operational voltage range Type Designation Article No. Units per package 230 VAC 24-48 VDC Z-FW-LP/MO Z-FW-LPD/MO 290171 290172 1/12 1/12 Operational voltage range Type Designation Article No. Units per package 0.01 A 0.03 A 0.1 A 0.3 A 0.5 A Z-FW/001 Z-FW/003 Z-FW/010 Z-FW/030 Z-FW/050 248297 248298 248299 248300 248301 4/120 4/120 4/120 4/120 4/120 SG30811 SG30711 Pre-mounted sets Z-FW SG31311 Remote Testing Module Z-FW (for Z-FW-LP./MO set use only) SG12111 Specifications | Remote Control and Automatic Switching Z-FW Description • Shape compatible switching device suitable for subsequent installation for automatic re-setting and remote control of CLS6, PFIM, PFHM-4p, dRCM, Z-A40, PFR, Z-MS • Mechanical interlock, can be sealed with leads • Mechanical switching capability up to max. PFIM-100/4p, CLS6-100/4p • Operating and alarm display by green and red LED • Function extension with Switching Modul Z-FW-MO Operating and trouble display by LED pre-assembled only with Z-FW... Connection diagram Z-FW-LP Z-FW-LPD Z-FW-MO Chapter 5.1.1. – 28 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Technical Data Electrical Possible operating voltages Frequency Testing module (0.5MU) for remote testing of RCDs Control voltage for remote control Relay output for tripping test with Z-FW Relay output for alarm, potential-free Functions Function selector Remote control function via telephone with Telecommander Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Scope of delivery Z-FW-LP Z-FW-LPD Z-FW-MO 220-240 V AC 50/60 Hz Z-FW... – – 5A/250V AC automatic restarting Automatic 5x, OFF/RESET – 24-48 V DC – Z-FW... – – 5A/250V AC automatic restarting Automatic 5x, OFF/RESET – – – – 24-230 V AC/DC 400 V AC max. – +ON/OFF/TEST ON, OFF/RESET – 45 mm 45 mm 45 mm 80 mm 80 mm 80 mm 70 mm 70 mm 35 mm quick fastening with 2 lock-in positions – on DIN rail IEC/EN 60715 IP40 IP40 IP40 finger and hand touch safe according to BGV A3, ÖVE-EN 6 lift terminals lift terminals lift terminals 2 x 1.5 mm2 or 2 x 1.5 mm2 or 4 x 1.5 mm2 or 1 x 2.5 mm2 1 x 2.5 mm2 2 x 2.5 mm2 – – Coupling plug Dimensions (mm) Z-FW-MO Z-FW-LP, -LPD Connection example CLS6-4..-HS Z-FWLPD Z-FWMO PFIM-4p PFIM-4p Connection diagram: PFIM-4p RCD feed above Alarm function and lamp *) discretionary polarity Electrical system Z-FW-LP Voltage supply AC /DC 24-230 V Pre-mounted Sets Z-FW-LPD/MO Z-FW-LP/MO Chapter 5.1.1. – 29 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Specifications | Remote Testing Module Z-FW (for Z-FW-LP) Description • External testing module with testing resistor for RCDs • Proper "external" test key function according to the applicable rules thanks to design adapted to the rated tripping current • For remote testing with remote control and automatic switching device Z-FW-LP • No undesired voltage rise in the consumer system during remote switch-off thanks to integrated breaker contact K1-K2 • Can also be used as a remote tripping module for PFIM, PFHM Dimensions (mm) Connection examples Connection diagram: PFIM-2p, RCD feed above Connection diagram: PFIM-4p, RCD feed above Z-FW-LP Z-FW PFIM-2p PFIM-4p Z-FW-LP Z-FW Chapter 5.1.1. – 30 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Main Load Disconnector Switch (Isolator) IS Rated Current (A) Poles Type Designation Article No. Units per package 16 16 16 16 20 20 20 20 25 25 25 25 32 32 32 32 40 40 40 40 63 63 63 63 80 80 80 80 100 100 100 100 125 125 125 125 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 IS-16/1 IS-16/2 IS-16/3 IS-16/4 IS-20/1 IS-20/2 IS-20/3 IS-20/4 IS-25/1 IS-25/2 IS-25/3 IS-25/4 IS-32/1 IS-32/2 IS-32/3 IS-32/4 IS-40/1 IS-40/2 IS-40/3 IS-40/4 IS-63/1 IS-63/2 IS-63/3 IS-63/4 IS-80/1 IS-80/2 IS-80/3 IS-80/4 IS-100/1 IS-100/2 IS-100/3 IS-100/4 IS-125/1 IS-125/2 IS-125/3 IS-125/4 276254 276255 276256 276257 276258 276259 276260 276261 276262 276263 276264 276265 276266 276267 276268 276269 276270 276271 276272 276273 276274 276275 276276 276277 276278 276279 276280 276281 276282 276283 276284 276285 276286 276287 276288 276289 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 12/120 1/60 1/40 1/30 Type Designation Article No. Units per package IS/SPE-1TE Z-IS/AK-1TE 101911 276290 5/30 10/600 SG10611 SG10711 SG10811 SG10911 Accessories Description SG47812 Switching interlock without lock for Isolators, RCDs, combined RCD/MCBs, ... Terminal cover Switching interlock IS/SPE-1TE Terminal Cover Caps Z-IS/AK-1TE • Without lock • Also suitable for PFIM, CFI6, PKNM, CKN6 • Can be sealed with leads • Modular design, width 1 MU Chapter 5.1.1. – 31 EATON CORPORATION xxxxx+xxxx-xxxxEN Accessories for Protective Devices Specifications | Main Load Disconnector Switch (Isolator) IS Description • Load circuit breaker with isolating function • Design according to IEC/EN 60947-3 • Highly wear resistant contacts • Quick make, black toggle • Terminal capacity 50 mm2 • Compatible busbars with switchgear series Xpole by use of the mouth terminal in combination with standard fork busbar Connection diagram 1-pole 2-pole 3-pole 4-pole Technical Data IS-16 IS-20 IS-25 IS-32 IS-40 IS-63 IS-80 IS-100 IS-125 Electrical Design according to IEC/EN 60947-3 Rated voltage 240/415 V Frequency 50/60 Hz Rated insulation voltage Ui 690 V~ Rated peak withstand voltage Uimp 6 kV Pollution degree 3 Rated short-time withstand current Icw 2 kA Rated short-circuit making capacity Icm 2.8 kA Rated current 240/415V, AC23A 16 A 20 A 25 A 32 A 40 A 63 A 80 A 100 A 125 A Number of poles 1-, 2-, 3-, 4-pole Maximum back-up fuse 125 A gG Short circuit strength - with back-up fuse acc. to the applicable rules IEC/EN 60947-3 12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA 10 kA 10 kA Endurance electrical components operation cycles ≥3.000 ≥3.000 ≥ 3.000 ≥3.000 ≥3.000 ≥3.000 ≥3.000 ≥3.000 ≥2.000 mechanical components operation cycles ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥14.000 Mechanical Frame size 45 mm Device height 80 mm Device width 17.5mm/pole Mounting quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 Degree of protection, built-in IP40 Terminal protection finger and hand touch safe according to BGV A3 Terminals open mouthed/lift terminals Terminal capacity 2.5 - 50 mm2 Busbar thickness 0.8 - 2 mm Fastening torque of terminal screws 2.5 - 5 Nm Function irrespective of the position of installation Dimensions (mm) Terminal cover caps Z-IS/AK-1TE Anti-tamper device IS/SPE1TE Chapter 5.1.1. – 32 EATON CORPORATION xxxxx+xxxx-xxxxEN Our focus is on delivering the right solution for the application. But, decision makers demand more than just innovative products. They turn to Eaton for an unwavering commitment to personal support that makes customer success a top priority. For more information, visit www.eaton.eu/electrical To contact an Eaton salesperson or local distributor/agent, please visit www.eaton.eu/electrical/customersupport Eaton Industries (Austria) GmbH Scheydgasse 42 1215 Wien Austria Eaton Industries Manufacturing GmbH EMEA Headquarters Route de la Longeraie 1110 Morges Switzerland © 2013 Eaton Industries (Austria) GmbH Subject to technical modifications. No responsibility is taken for misprints or errata. Printed in Austria (05/13) Publication number Grafics: SRA DigiPics, Lithos: Print: Article number xxxxxx Eaton is dedicated to ensuring that reliable, efficient and safe power is available when it’s needed most. With unparalleled knowledge of electrical power management across industries, experts at Eaton deliver customized, integrated solutions to solve our customers’ most critical challenges.