xEffect - Industrial Switchgear Range

advertisement
www.eaton.eu
xEffect - Industrial
Switchgear Range
Catalogue 2013
www.eaton.eu
Digital protection switches –
a new era has begun.
Numerous advantages at a glance
Better security with proactive communication!
The digital RCCB from Eaton’s xEffect series are capable
to do more than just switch off: They monitor electrical
installations and issue advance warnings of critical current
flows. Thanks to short time delay and optimized tripping
threshold, briefly occurring malfunctions do not induce the
digital protection switch to shut down.
• Ideal for system monitoring
thanks to preventive information
• Continuous monitoring of
plant/factory status
• Clear status display with
tri-colored LEDs
When a fault current crops up, the information is reported
to the security center of the industrial plant right away
and troubleshooting can start before a plant failure occurs.
Thus the cause of the fault current can be determined
precisely and the system can be serviced easily.
That way, system availability increases and service is
crucially improved by the convenient remote control.
• Longer intervals between
servicing
• As easy to install as a conventional RCCB
The new xEffect Digital Series
Residual Current Devices
Residual Current Devices - General Data
Short description of the most important RCD types:
Symbol
Description
Eaton standard. Suitable for outdoor installation (distribution boxes for outdoor installation and
building sites) up to -25° C.
Conditionally surge-current proof (>250 A, 8/20 µs) for general application.
RCD sensitive to pulsating DC for application where residual pulsating DC may occur. Non-selective, instantaneous. Protects only against special forms of residual pulsating DC which have not
been smoothed.
Type B: All-current sensitive RCD switchgear for applications where DC fault currents may occur.
Non-selective, non-delayed. Protection against all kinds of fault currents.
Type B+: All-current sensitive RCD switchgear for applications where DC fault currents may occur.
Non-selective, non-delayed. Protection against all kinds of fault currents. Also meets the requirements of the VDE 0664-400 standard (formerly known as VDE V 0664-110) and therefore provides
enhanced fire safety.
G
ÖVE E 8601
S
RCD of type G (min 10 ms time delay) surge current-proof up to 3 kA. For system components
where protection against unwanted tripping is compulsory to avoid personal injury and damage to
property (§ 12.1.6 of ÖVE/ÖNORM E 8001-1). Also for systems involving long lines and high line
capacity. Some versions are sensitive to pulsating DC. Some versions are available in all-current
sensitive design.
RCD of type S (selective, min 40 ms time delay) surge current-proof up to 5 kA. Mainly used as
main switch according to ÖVE/ÖNORM E 8001-1 § 12.1.5, as well as in combination with surge
arresters.This is the only RCD suitable for series connection with other types if the rated tripping
current of the downstream RCD does not exceed one third of the rated tripping current of the
device of type S. Some versions are sensitive to pulsating DC. Some versions are available in allcurrent sensitive design.
"X-ray-proof", for avoiding unwanted tripping caused by x-ray devices.
“röntgenfest”
"umrichterfest"
"Frequency converter-proof", for avoiding unwanted tripping caused by frequency converters,
speed-controlled drives, etc.
Chapter 2.1.1. – 1
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Tripping Characteristics (IEC/EN 61008)
Tripping characteristics, tripping time range and selectivity of instantaneous,
surge current-proof "G" and surge current-proof - selective "S" residual current devices.
Tripping time t
surge current.proof - selective
surge currentproof
conditionally
surge currentproof
Residual tripping current
Tripping time range limit values
Tripping time range type S
Tripping time range non-delayed
Tripping time range type G
Area of unwanted tripping
§ 6.1.1 of ÖVE/ÖNORM E 8001-1/A1 deals with additional protection and provides essentially the following:
In circuits with sockets up to 16 A with fault current/residual current
protection by protective earthing, protective multiple earthing or
residual current devices (RCDs), additional residual current protection
devices with a rated tripping current of 0.03 A must be installed.
This means when using RCDs for fault current/residual current
protection two RCDs must be connected in series.
Testing:
RCDs with tripping time delay (Types -G and -S) may be function tested with conventional testing equipment which must be set according
to the instructions for operation of the testing device. Due to reasons
inherent in the measuring process, the tripping time determined in
this way may be longer than expected in accordance with the specifications of the manufacturer of the measuring instrument.
However, the device is ok if the result of measurement is within the
time range specified by the manufacturer of the measuring instrument.
Chapter 2.1.1. – 2
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Hints for the application of our frequency converter-proof RCDs:
Due to the currents flowing off through the filters (designated IF), the sum of
currents through the RCD is not exactly zero, which causes unwanted tripping.
Frequency converters are used in a wide variety of systems and equipment requiring variable speed, such as lifts, escalators, conveyor
belts, and large washing machines. Using them for such purposes in
circuits with conventional residual current devices causes frequent
problems with unwanted tripping.
Motor
Screened motor line
The technical root cause of this phenomenon is the following: Fast
switching operations involving high voltages cause high interference
levels which propagate through the lines on the one hand, and in the
form of interfering radiation on the other. In order to eliminate this
problem, a mains-side filter (also referred to as input filter or EMC-filter) is connected between the RCD and frequency converter. The antiinterference capacitors in the filters produce discharge currents
against earth which may cause unwanted tripping of the RCD due to
the apparent residual currents. Connecting a filter on the output side
between frequency converter and 3-phase AC motor results in the
same behaviour.
Motor
Mains side filter
Frequency
converter
Frequency
converter
Mains-side filter
Mains-side filter
RCD
RCD
Mains
Tripping characteristic
This sample tripping characteristic of a 100 mA RCD and a 300 mA
RCD shows the following: In the frequency range around 50 Hz, the
RCDs trip as required (50 - 100 % of the indicated IΔn).
In the range shown hatched in the diagram, i. e. from approx. 100 to
300 Hz, unwanted tripping occurs frequently due to the use of frequency converters. Frequency converter-proof residual current
devices are much less sensitive in this frequency range than in the 50
- 60 Hz range, which leads to an enormous increase in the reliability of
systems.
Frequency converter
interference range
(approx. 100 - 300 Hz)
Therefore, we recommend to use frequency converter-proof RCDs!
These special residual current devices can be recognised by an extension
of the type designation ("-U"). They meet the requirements of compatibility between RCDs and frequency converters with respect to unwanted
tripping.
These are NOT AC/DC-sensitive RCDs of type B !!!
Our RCDs of type "-U" are characterised by SENSITIVITY TO RESIDUAL
PULSATING DC
and SELECTIVITY S or SHORT-TIME DELAY G .
Protective Measures
The following rules for the application of RCDs of type" -U" are only applicable in those cases where an RCD of type "-B" is not explicitly demanded in the
instructions of the manufacturer of the frequency converter.
How can you make sure that the required protective measures are in place when using RCDs type “-U” and frequency converters in one system?
In Austria, the ÖVE Decision EN 219 is applicable.
In Germany, VDE 0100 is applicable, in Switzerland SEV 1000.
Under this standard
In case of application in any other country than those mentioned
take into account national rules and recommendations.
• frequency converters must be equipped with current limiting
devices in order to ensure disconnection in cause of faults or overload, and
• the installer of a system is obliged to make sure that additional
equipotential bonding is provided (additional inclusion of all metal
components, such as frequency converters, mains filters, motor filters, etc. into the existing equipotential bonding), in order to ensure
that the permissible touch voltage of 50 V AC or 120 V DC is not
exceeded. (In ÖVE/ÖNORM E 8001-1 the term "touch voltage" has
been omitted. There is only a fault voltage limit of 65 V AC or 120 V
DC which must not be exceeded).
Chapter 2.1.1. – 3
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCdM Digital
SG49712
• Line voltage independent RCCB for fault or additional protection with additional digital features.
• System Monitoring: Preventive information / warning before the RCD trips
in case of leakage currents
– Integrated auxiliary contact
– Local Indication
• New level of accuracy -> reduced unwanted tripping
• No monthly test required
• Comprehensive range of accessories
• Real contact position indicator
• Fault current tripping indicator
• Automatic re-setting possible
• Transparent designation plate
Chapter 2.2.1. – 1
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCdM type G/A
Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601)
In/IΔn
(A)
SG49712
Type
Designation
Article No.
Units
per
package
FRCdM-25/4/003-G/A
FRCdM-25/4/03-G/A
FRCdM-40/4/003-G/A
FRCdM-40/4/03-G/A
FRCdM-63/4/003-G/A
FRCdM-63/4/03-G/A
FRCdM-80/4/003-G/A
FRCdM-80/4/03-G/A
168646
168647
168648
168649
168650
168651
168634
168635
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCdM-63/4/003-R
168636
1/30
Type
Designation
Article No.
Units
per
package
FRCdM-40/4/03-S/A
FRCdM-63/4/03-S/A
FRCdM-80/4/03-S/A
168637
168638
168639
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCdM-40/4/003-U
FRCdM-40/4/03-U
FRCdM-63/4/003-U
FRCdM-63/4/03-U
FRCdM-80/4/03-U
168643
168644
168640
168641
168642
1/30
1/30
1/30
1/30
1/30
4-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
80/0.03
80/0.3
Residual Current Devices FRCdM type R
Surge current-proof 3 kA, X-ray application, type R
In/IΔn
(A)
SG49712
4-pole
63/0.03
Residual Current Devices FRCdM type S/A
Selective + surge current-proof typ. 5 kA, sensitive to residual pulsating DC, type S/A
In/IΔn
(A)
SG49712
4-pole
40/0.3
63/0.3
80/0.3
Residual Current Devices FRCdM type U
Selective + surge current-proof typ. 5 kA, frequency converter-proof, type U
In/IΔn
(A)
SG49712
4-pole
40/0.03 *)
40/0.3
63/0.03 *)
63/0.3
80/0.3
*) Short time delayed + surge current-proof 3 kA
Chapter 2.2.1. – 2
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCdM
Description
• Residual current devices
• Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Universal tripping signal switch, also suitable for FAZ, FRBmM-1N
can be mounted subsequently
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Tripping indicator white - blue
• Additional Safety
- possibility to seal
- possibility to lock in ON and OFF position
• Delayed types suitable for being used with standard fluorescent
tubes with or without electronical ballast (30mA-RCD: 30 units per
phase conductor, 100mA-RCD: 90 units per phase conductor).
Notes: Depending of the fluorescent lamp ballast manufacturer
partly more possible. Symmetrical allocation of the fluorescent
lamp ballasts on all phases favourably. Shifting references of the
fluorescent lamp ballast manufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional
protection” within the meaning of the applicable installation rules.
• Mains connection at either side
• The 4-pole device can also be used for 3-pole connection:
See connection possibilities.
• The 4-pole device can also be used for 2-pole connection:
See connection possibilities.
• The test key “T” must be pressed every year. The system operator
must be informed of this obligation and his responsibility in a way
that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). A test is further needed if red and yellow LED
are on together.
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
• Functioning
- The green LED becomes active at 0-30% IΔn
- The yellow LED becomes active at 30-50% IΔn
- The red LED becomes active at >50% IΔn
• Potential-free relay (NO contact, in parallel with the yellow LED, up
to 1 A ohmic load / 230 V~) for external prewarning function.
Bistabile, means the warning stays on also when the breaker trips,
until reset.
• Type -A: Protects against special forms of residual pulsating DC
which have have not been smoothed.
• Type -G: High reliability against unwanted tripping. Compulsory
for any circuit where personal injury or damage to property may
occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Type -G/A: Additionally protects against special forms of residual
pulsating DC which have not been smoothed.
• Type -R: To aviod unwanted tripping due to X-ray devices.
• Type -S: Selective residual current device sensitive to AC, type -S.
Compulsory for systems with surge arresters downstream of the
RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5).
• Type -S/A: Additionally protects against special forms of residual
pulsating pulsating DC which have not been smoothed.
• Type -U: Suitable for speed-controlled drives with frequency converters in household, trade, and industry.
Unwanted tripping is avoided thanks to a tripping characteristic
designed particularly for frequency converters.
See also explanation “Frequency Converter-Proof RCDs - What for?”.
Application according to ÖVE/ÖNORM E 8001-1 and Decision
EN 219 (1989), VDE 0100, SEV 1000.
Accessories:
Auxiliary switch for subsequent installation to the left
Tripping signal contact for subsequent installation to the right
Automatic restarting device
Remote control
Pre-mounted sets
Remote testing module
Sealing cover set
Switching interlock
Z-HK
Z-NHK
Z-FW/LP
Z-FW-LPD
Z-FW-MO
Z-FW-LP/MO
Z-FW-LPD/MO
Z-FW/003
Z-FW/010
Z-FW/030
Z-RC/AK-4TE
IS/SPE-1TE
Chapter 2.2.1. – 3
248432
248434
248296
265244
284730
290171
290172
248298
248299
248300
101062
101911
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Technical Data
FRCdM
Electrical
Design according to
Current test marks as printed onto the device
Tripping
Type G , R
Type S
Type U (only 30 mA)
Type U (except 30 mA)
Rated voltage
Operation voltage electronic
Operation voltage test circuit
Rated tripping current
Sensitivity
Rated insulation voltage
Rated impulse withstand voltage
Rated short circuit capacity
Peak withstand current
Type G, G/A, R, U (30mA)
Type S/A, U (except 30mA)
Electrical isolation
Maximum back-up fuse
In = 16-63A
In = 80A
In = 100A
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Degree of protection in moisture-proof enclosure
Upper and lower terminals
Terminal protection
Terminal capacity
Terminal screw
Terminal capacity warning contact(s)
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Resistance to climatic conditions
Contact position indicator
Tripping indicator
IEC/EN 61008
Type G and G/A acc. to ÖVE E 8601
Un
IΔn
Ui
Uimp
Icn
instantaneous
10 ms delay
40 ms delay - with selective disconnecting function
10 ms delay
40 ms delay - with selective disconnecting function
240/415 V AC, 50Hz
50 – 264V AC
196 – 264V AC
30, 300 mA
AC and pulsating DC
440 V
4 kV (1.2/50µs)
10 kA
3 kA (8/20 µs) surge current proof
typ. 5 kA (8/20 µs) selective + surge current proof
> 4 mm contact space
Short circuit and overload protection
63 A gG/gL
80 A gG/gL
100 A gG/gL
≥ 4,000 operating cycles
≥ 20,000 operating cycles
45 mm
80 mm
70 mm (4MU)
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715
IP40
IP54
open mouthed/lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
1.5 - 35 mm2 single wire
2 x 16 mm2 multi wire
M5 (Pozidriv PZ2)
0.25-1.5 mm2 (plug in terminals)
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
red / green
white / blue
Connection diagram
4-pole
Chapter 2.2.1. – 4
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Local Indication RCCB
Status indication LED
Permanent light green
red / yellow / green
Normal operation
Permanent light yellow
The measured residual current is bigger than 30% of the nominal tripping value.
Permanent light red
The measured residual current is bigger than 50% of the nominal tripping value.
Flashing yellow/red
Check the device with test key. If the LEDs are still flashing check the
direction of connection (supply side / load side).
Remote Indication
Potential-free auxiliary switch for use in control circuits, insulated from main circuit of the switch gear according to IEC/EN60664.
0.25A ohmic load / 240V AC, terminal capacity: 0.25 - 1.5 mm2.
Dimensions (mm)
Correct connection
3+N
(240/415V)
3-phase load without N
(415V AC Phase-Phase)
3-phase load without N
(240V AC AC Phase-Phase)
1+N (240V)
Electronic works within 50-264V AC !
- Disconnect load side of the switch gear, if you make a insulation test of the installation!
Chapter 2.2.1. – 5
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCdM Type B, B+ and Bfq Digital
SG49812
• Line-voltage independent, all-current sensitive RCCB for fault or additional
protection with additional digital features
• System Monitoring: Preventive information / warning before the RCD trips
in case of leakage currents
– Integrated auxiliary contact
– Local Indication through 3 LEDs
• B+ types also meet the requirements of superior fire-protection systems
according to VDE 0664-400 (formerly known as VDE V 0664-110)
• 4-pole types can also be used as 2-pole devices for photovoltaic applications
• New level of accuracy -> reduced unwanted tripping
• No monthly test required
• Comprehensive range of accessories
• Real contact position indicator
• Fault current tripping indicator
• Automatic re-setting possible
• Transparent designation plate
Chapter 2.2.1. – 6
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCdM type G/B
Surge current-proof 3 kA, AC-DC sensitive, type G/B (ÖVE E 8601)
In/IΔn
(A)
SG49812
Type
Designation
Article No.
Units
per
package
FRCdM-25/4/003-G/B
FRCdM-25/4/03-G/B
FRCdM-40/4/003-G/B
FRCdM-40/4/03-G/B
FRCdM-63/4/003-G/B
FRCdM-63/4/03-G/B
167892
167896
167893
167897
167894
167898
1/30
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCdM-25/4/03-S/B
FRCdM-40/4/03-S/B
FRCdM-63/4/03-S/B
167900
167901
167902
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCdM-25/4/003-G/B+
FRCdM-25/4/03-G/B+
FRCdM-40/4/003-G/B+
FRCdM-40/4/03-G/B+
FRCdM-63/4/003-G/B+
FRCdM-63/4/03-G/B+
167880
167884
167881
167885
167882
167886
1/30
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCdM-25/4/03-S/B+
FRCdM-40/4/03-S/B+
FRCdM-63/4/03-S/B+
167888
167889
167890
1/30
1/30
1/30
4-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
Residual Current Devices FRCdM Typ S/B
Selective + surge current-proof 5 kA, type S/B
In/IΔn
(A)
SG49812
4-pole
25/0.3
40/0.3
63/0.3
Residual Current Devices FRCdM Typ G/B+
Surge current-proof 3 kA, type G/B+ (ÖVE E 8601)
In/IΔn
(A)
SG49812
4-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
Residual Current Devices FRCdM Typ S/B+
Selective + surge current-proof 5 kA, type S/B+
In/IΔn
(A)
SG49812
4-pole
25/0.3
40/0.3
63/0.3
Chapter 2.2.1. – 7
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCdM Typ G/Bfq
Surge current-proof 3 kA, AC-DC sensitive, type G/Bfq (ÖVE E 8601)
In/IΔn
(A)
SG49812
Type
Designation
Article No.
Units
per
package
FRCdM-25/4/03-G/Bfq
FRCdM-40/4/03-G/Bfq
FRCdM-63/4/03-G/Bfq
167904
167905
167906
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCdM-25/4/03-S/Bfq
FRCdM-40/4/03-S/Bfq
FRCdM-63/4/03-S/Bfq
167908
167909
167910
1/30
1/30
1/30
4-pole
25/0.3
40/0.3
63/0.3
Residual Current Devices FRCdM Typ S/Bfq
Selective + surge current-proof 5 kA, type S/Bfq
In/IΔn
(A)
SG49812
4-pole
25/0.3
40/0.3
63/0.3
Chapter 2.2.1. – 8
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCdM - digital, Type B and B+
Description
• Residual current devices, all-current sensitive
• Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Universal tripping signal switch, also suitable for FAZ, FRBmM-1N
can be mounted subsequently
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Tripping indicator white - blue
• Additional Safety
- possibility to seal
- possibility to lock in ON and OFF position
• Delayed types (G, S) suitable for being used with standard fluorescent tubes with or without electronical ballast (30mA-RCD: 30 units
per phase conductor, 100mA-RCD: 90 units per phase conductor).
Notes: Depending of the fluorescent lamp ballast manufacturer
partly more possible. Symmetrical allocation of the fluorescent
lamp ballasts on all phases favourably. Shifting references of the
fluorescent lamp ballast manufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional
protection” within the meaning of the applicable installation rules.
• The 4-pole device can also be used for 3-pole connection:
See connection possibilities.
• The 4-pole device can also be used for 2-pole connection:
See connection possibilities.
• The test key “T” must be pressed every year. The system operator
must be informed of this obligation and his responsibility in a way
that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly). A test is further needed if red and yellow LED
are flashing alternately.
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
• Functioning
- The green LED becomes active at 0-30% IΔn
- The yellow LED becomes active at 30-50% IΔn
- The red LED becomes active at >50% IΔn
• Potential-free auxiliary switch for use in control circuits, insulated
from main circuit of the switch gear according to IEC/EN60664
(0.25A ohmic load / 240V AC) in parallel with the yellow LED, for
external prewarning function. Bistabile, means the warning stays
on also when the breaker trips, until reset.
• Type -G/B and G/B+: High reliability against unwanted tripping.
Compulsory for any circuit where personal injury or damage to
property may occur in case of unwanted tripping (ÖVE/ÖNORM
E 8001-1 § 12.1.6).
Protection against all types of fault currents.
• Type -S/B and S/B+: Selective residual current device.
Protection against all types of fault currents.
• Type -S/Bfq: Suitable for speed-controlled drives with frequency
converters inhousehold, trade, and industry.Unwanted tripping is
avoided thanks to a tripping characteristic designedparticularly for
frequency converters.
Protection against all types of fault currents.
Accessories:
Auxiliary switch for subsequent installation to the left
Tripping signal contact for subsequent installation to the right
Automatic restarting device
Remote control
Pre-mounted sets
Remote testing module
Sealing cover set
Switching interlock
Z-HK
Z-NHK
Z-FW/LP
Z-FW-LPD
Z-FW-MO
Z-FW-LP/MO
Z-FW-LPD/MO
Z-FW/001
Z-FW/003
Z-FW/010
Z-FW/030
Z-FW/050
Z-RC/AK-4TE
IS/SPE-1TE
Chapter 2.2.1. – 9
248432
248434
248296
265244
284730
290171
290172
248297
248298
248299
248300
248301
101062
101911
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Technical Data
FRCdM Type B and B+
Electrical
Design according to
Current test marks as printed onto the device
Tripping
Type G
Type S
Rated voltage
Operation voltage electronic
Voltage range test circuit
Rated tripping current
Sensitivity
Rated insulation voltage
Rated impulse withstand voltage
Rated short circuit capacity
Peak withstand current
Type G/B, G/B+ and G/Bfq
Type S/B, S/B+ and S/Bfq
Electrical isolation
Maximum back-up fuse
In = 16-63A
In = 80A
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Degree of protection in moisture-proof enclosure
Upper and lower terminals
Terminal protection
Terminal capacity
Terminal screw
Terminal capacity warning contact
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Resistance to climatic conditions
Contact position indicator
Tripping indicator
Types B and Bfq acc. to IEC/EN 61008, IEC/EN 62423
B+ Type acc. to VDE 0664-400, formerly known as VDE V 0664-110
Type G/B and G/B+ additional acc. to ÖVE E 8601
Un
IΔn
Ui
Uimp
Icn
10 ms delay
40 ms delay - with selective disconnecting function
240/415 V AC, 50 Hz
50 – 254V AC
184 - 440V AV (300mA) / 184 - 264V AV (30mA)
30, 300 mA
Alternating, pulsed and direct currents
440 V
4 kV (1.2/50µs)
10 kA
3 kA (8/20 µs) surge current proof
typ. 5 kA (8/20 µs) selective + surge current proof
> 4 mm contact space
Short circuit and overload protection
63 A gG/gL
80 A gG/gL
≥ 4,000 operating cycles
≥ 20,000 operating cycles
45 mm
80 mm
70 mm (4MU)
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715
IP40
IP54
open mouthed/lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
1.5 - 35 mm2 single wire
2 x 16 mm2 multi wire
M5 (Pozidriv PZ2)
0.25-1.5 mm2 (plug in terminals)
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
red / green
white / blue
Connection diagram
4-pole
Netz
Mains
Last
Load
Chapter 2.2.1. – 10
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Local Indication RCCB
Status indication LED
Permanent light green
red / yellow / green
Normal operation
Permanent light yellow
The measured residual current is bigger than 30% of the nominal tripping value.
Permanent light red
The measured residual current is bigger than 50% of the nominal tripping value.
Flashing yellow/red
Check the device with test key. If the LEDs are still flashing check the
direction of connection (supply side / load side).
Remote Indication
Potential-free auxiliary switch for use in control circuits, insulated from main circuit of the switch gear according to IEC/EN60664.
0.25A ohmic load / 240V AC, terminal capacity: 0.25 - 1.5 mm2.
Dimensions (mm)
Correct connection
Load side
Netzseite
Load
side
Netzseite
Netzseite
Load
side
Lastseite
Supply
side
Lastseite
Supply
side
Supply
Lastseite
side
3+N
(240/415V)
3-phase application
(30mA 184-264V)
(300mA 184-415V)
2-pole
(240V)
Load side
Supply side
4-pole
(240/415V)
Test button works within 184-264V (30mA) bzw. 184-440V (300mA)!
- Disconnect load side of the switch gear, if you make a insulation test of the installation!
- Please take care of supply side and load side!
Chapter 2.2.1. – 11
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM
• A complete spectrum of compact residual current devices for a wide
range of applications
• For fault current/residual current protection and additional protection
• Wide variety of nominal currents
• Comprehensive range of accessories
• Real contact position indicator
• Automatic re-setting possible
Chapter 2.2.1. – 12
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM type AC
Conditionally surge current-proof 250 A, type AC
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCmM-16/2/003
FRCmM-16/2/01
FRCmM-16/2/03
FRCmM-16/2/05
FRCmM-25/2/003
FRCmM-25/2/01
FRCmM-25/2/03
FRCmM-25/2/05
FRCmM-40/2/003
FRCmM-40/2/01
FRCmM-40/2/03
FRCmM-40/2/05
FRCmM-63/2/003
FRCmM-63/2/01
FRCmM-63/2/05
FRCmM-80/2/003
FRCmM-80/2/01
FRCmM-100/2/003
FRCmM-100/2/01
170390
170396
170402
170405
170391
170397
170403
170406
170392
170398
170404
170407
170393
170399
170408
170394
170400
170395
170401
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-16/4/003
FRCmM-16/4/01
FRCmM-16/4/03
FRCmM-16/4/05
FRCmM-25/4/003
FRCmM-25/4/01
FRCmM-25/4/03
FRCmM-25/4/05
FRCmM-40/4/003
FRCmM-40/4/01
FRCmM-40/4/03
FRCmM-40/4/05
FRCmM-63/4/003
FRCmM-63/4/03
FRCmM-63/4/05
FRCmM-80/4/003
FRCmM-80/4/03
FRCmM-80/4/05
FRCmM-100/4/003
FRCmM-100/4/03
FRCmM-100/4/05
170409
170415
170418
170424
170410
170416
170419
170425
170411
170417
170420
170426
170412
170421
170427
170413
170422
170428
170414
170423
170429
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
2-pole
16/0.03
16/0.1
16/0.3
16/0.5
25/0.03
25/0.1
25/0.3
25/0.5
40/0.03
40/0.1
40/0.3
40/0.5
63/0.03
63/0.1
63/0.5
80/0.03
80/0.1
100/0.03
100/0.1
4-pole
16/0.03
16/0.1
16/0.3
16/0.5
25/0.03
25/0.1
25/0.3
25/0.5
40/0.03
40/0.1
40/0.3
40/0.5
63/0.03
63/0.3
63/0.5
80/0.03
80/0.3
80/0.5
100/0.03
100/0.3
100/0.5
Chapter 2.2.1. – 13
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM type A
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCmM-16/2/003-A
FRCmM-16/2/01-A
FRCmM-16/2/03-A
FRCmM-16/2/05-A
FRCmM-25/2/003-A
FRCmM-25/2/01-A
FRCmM-25/2/03-A
FRCmM-25/2/05-A
FRCmM-40/2/003-A
FRCmM-40/2/01-A
FRCmM-40/2/03-A
FRCmM-40/2/05-A
FRCmM-63/2/003-A
FRCmM-63/2/01-A
FRCmM-63/2/05-A
FRCmM-80/2/003-A
FRCmM-80/2/01-A
FRCmM-100/2/003-A
FRCmM-100/2/01-A
170430
170436
170278
170281
170431
170437
170279
170282
170432
170274
170280
170283
170433
170275
170284
170434
170276
170435
170277
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-16/4/003-A
FRCmM-16/4/01-A
FRCmM-16/4/03-A
FRCmM-16/4/05-A
FRCmM-25/4/003-A
FRCmM-25/4/01-A
FRCmM-25/4/03-A
FRCmM-25/4/05-A
FRCmM-40/4/003-A
FRCmM-40/4/01-A
FRCmM-40/4/03-A
FRCmM-40/4/05-A
FRCmM-63/4/003-A
FRCmM-63/4/03-A
FRCmM-63/4/05-A
FRCmM-80/4/003-A
FRCmM-80/4/03-A
FRCmM-80/4/05-A
FRCmM-100/4/003-A
FRCmM-100/4/03-A
FRCmM-100/4/05-A
170285
170337
170340
170346
170332
170338
170341
170347
170333
170339
170342
170348
170334
170343
170349
170335
170344
170350
170336
170345
170351
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
2-pole
16/0.03
16/0.1
16/0.3
16/0.5
25/0.03
25/0.1
25/0.3
25/0.5
40/0.03
40/0.1
40/0.3
40/0.5
63/0.03
63/0.1
63/0.5
80/0.03
80/0.1
100/0.03
100/0.1
4-pole
16/0.03
16/0.1
16/0.3
16/0.5
25/0.03
25/0.1
25/0.3
25/0.5
40/0.03
40/0.1
40/0.3
40/0.5
63/0.03
63/0.3
63/0.5
80/0.03
80/0.3
80/0.5
100/0.03
100/0.3
100/0.5
Chapter 2.2.1. – 14
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM type G
Surge current-proof 3 kA, type G (ÖVE E 8601)
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCmM-16/2/003-G
FRCmM-16/2/01-G
FRCmM-16/2/03-G
FRCmM-25/2/003-G
FRCmM-25/2/01-G
FRCmM-25/2/03-G
FRCmM-40/2/003-G
FRCmM-40/2/01-G
FRCmM-40/2/03-G
FRCmM-63/2/003-G
FRCmM-63/2/01-G
FRCmM-80/2/003-G
FRCmM-80/2/01-G
FRCmM-100/2/003-G
FRCmM-100/2/01-G
170352
170358
170364
170353
170359
170365
170354
170360
170366
170355
170361
170356
170362
170357
170363
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-16/4/003-G
FRCmM-16/4/01-G
FRCmM-16/4/03-G
FRCmM-25/4/003-G
FRCmM-25/4/01-G
FRCmM-25/4/03-G
FRCmM-40/4/003-G
FRCmM-40/4/01-G
FRCmM-40/4/03-G
FRCmM-63/4/003-G
FRCmM-63/4/03-G
FRCmM-80/4/003-G
FRCmM-80/4/03-G
170367
170373
170376
170368
170374
170377
170369
170375
170378
170370
170379
170371
170380
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
2-pole
16/0.03
16/0.1
16/0.3
25/0.03
25/0.1
25/0.3
40/0.03
40/0.1
40/0.3
63/0.03
63/0.1
80/0.03
80/0.1
100/0.03
100/0.1
4-pole
16/0.03
16/0.1
16/0.3
25/0.03
25/0.1
25/0.3
40/0.03
40/0.1
40/0.3
63/0.03
63/0.3
80/0.03
80/0.3
Chapter 2.2.1. – 15
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM type G/A
Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601)
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCmM-16/2/003-G/A
FRCmM-16/2/01-G/A
FRCmM-16/2/03-G/A
FRCmM-25/2/003-G/A
FRCmM-25/2/01-G/A
FRCmM-25/2/03-G/A
FRCmM-40/2/003-G/A
FRCmM-40/2/01-G/A
FRCmM-40/2/03-G/A
FRCmM-63/2/003-G/A
FRCmM-63/2/01-G/A
FRCmM-80/2/003-G/A
FRCmM-80/2/01-G/A
FRCmM-100/2/003-G/A
FRCmM-100/2/01-G/A
170382
170388
170290
170383
170389
170291
170384
170286
170292
170385
170287
170386
170288
170387
170289
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-16/4/003-G/A
FRCmM-16/4/01-G/A
FRCmM-16/4/03-G/A
FRCmM-25/4/003-G/A
FRCmM-25/4/01-G/A
FRCmM-25/4/03-G/A
FRCmM-40/4/003-G/A
FRCmM-40/4/01-G/A
FRCmM-40/4/03-G/A
FRCmM-63/4/003-G/A
FRCmM-63/4/03-G/A
FRCmM-80/4/003-G/A
FRCmM-80/4/03-G/A
170293
170299
170302
170294
170300
170303
170295
170301
170304
170296
170305
170297
170306
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
2-pole
16/0.03
16/0.1
16/0.3
25/0.03
25/0.1
25/0.3
40/0.03
40/0.1
40/0.3
63/0.03
63/0.1
80/0.03
80/0.1
100/0.03
100/0.1
4-pole
16/0.03
16/0.1
16/0.3
25/0.03
25/0.1
25/0.3
40/0.03
40/0.1
40/0.3
63/0.03
63/0.3
80/0.03
80/0.3
Chapter 2.2.1. – 16
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM type S
Selective + surge current-proof 5 kA, type S
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCmM-16/2/01-S
FRCmM-25/2/01-S
FRCmM-40/2/01-S
FRCmM-63/2/01-S
FRCmM-80/2/01-S
FRCmM-100/2/01-S
170314
170315
170316
170317
170318
170319
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-16/4/01-S
FRCmM-16/4/03-S
FRCmM-25/4/01-S
FRCmM-25/4/03-S
FRCmM-40/4/01-S
FRCmM-40/4/03-S
FRCmM-63/4/01-S
FRCmM-63/4/03-S
FRCmM-80/4/03-S
170320
170324
170321
170325
170322
170326
170323
170327
170328
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCmM-16/2/01-S/A
FRCmM-25/2/01-S/A
FRCmM-40/2/01-S/A
FRCmM-63/2/01-S/A
FRCmM-80/2/01-S/A
FRCmM-100/2/01-S/A
170330
170331
170438
170439
170440
170441
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-16/4/01-S/A
FRCmM-16/4/03-S/A
FRCmM-25/4/01-S/A
FRCmM-25/4/03-S/A
FRCmM-40/4/01-S/A
FRCmM-40/4/03-S/A
FRCmM-63/4/01-S/A
FRCmM-63/4/03-S/A
FRCmM-80/4/03-S/A
170442
170446
170443
170447
170444
170448
170445
170449
170450
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
2-pole
16/0.1
25/0.1
40/0.1
63/0.1
80/0.1
100/0.1
4-pole
16/0.1
16/0.3
25/0.1
25/0.3
40/0.1
40/0.3
63/0.1
63/0.3
80/0.3
Residual Current Devices FRCmM type S/A
Selective + surge current-proof 5 kA, sensitive to residual pulsating DC, type S/A
In/IΔn
(A)
2-pole
16/0.1
25/0.1
40/0.1
63/0.1
80/0.1
100/0.1
4-pole
16/0.1
16/0.3
25/0.1
25/0.3
40/0.1
40/0.3
63/0.1
63/0.3
80/0.3
Chapter 2.2.1. – 17
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM type U
Short-time delayed + surge current-proof 3 kA, frequency converter-proof, type U
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCmM-16/4/003-U
FRCmM-25/4/003-U
FRCmM-40/4/003-U
FRCmM-63/4/003-U
FRCmM-80/4/003-U
170452
170453
170454
170455
170456
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCmM-16/4/01-U
FRCmM-16/4/03-U
FRCmM-25/4/01-U
FRCmM-25/4/03-U
FRCmM-40/4/01-U
FRCmM-40/4/03-U
FRCmM-63/4/01-U
FRCmM-63/4/03-U
FRCmM-80/4/03-U
170458
170462
170459
170463
170460
170464
170461
170465
170466
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCmM-16/4/003-R
FRCmM-25/4/003-R
FRCmM-40/4/003-R
FRCmM-63/4/003-R
FRCmM-80/4/003-R
170308
170309
170310
170311
170312
1/30
1/30
1/30
1/30
1/30
4-pole
16/0.03
25/0.03
40/0.03
63/0.03
80/0.03
Residual Current Devices FRCmM type U
Selective + surge current-proof 5 kA, frequency converter-proof, type U
In/IΔn
(A)
4-pole
16/0.1
16/0.3
25/0.1
25/0.3
40/0.1
40/0.3
63/0.1
63/0.3
80/0.3
Residual Current Devices FRCmM type R
Surge current-proof 3 kA, X-ray application, type R
In/IΔn
(A)
4-pole
16/0.03
25/0.03
40/0.03
63/0.03
80/0.03
Chapter 2.2.1. – 18
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCmM
Description
• Residual current devices
• Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Universal tripping signal switch, also suitable for FAZ, FRBmM-1N
can be mounted subsequently
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Delayed types suitable for being used with standard fluorescent
tubes with or without electronical ballast (30mA-RCD: 30 units per
phase conductor, 100mA-RCD: 90 units per phase conductor).
Notes: Depending of the fluorescent lamp ballast manufacturer
partly more possible. Symmetrical allocation of the fluorescent
lamp ballasts on all phases favourably. Shifting references of the
fluorescent lamp ballast manufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional
protection” within the meaning of the applicable installation rules.
• Mains connection at either side
• The 4-pole device can also be used for 3-pole connection:
For this purpose use terminals 1-2, 3-4, and 5-6 (+ cable link).
• The 4-pole device can also be used for 2-pole connection:
For this purpose use terminals 5-6 and N-N.
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven (self-adhesive RCD-label enclosed).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
• Type -A: Protects against special forms of residual pulsating DC
which have have not been smoothed.
• Type -G: High reliability against unwanted tripping. Compulsory
for any circuit where personal injury or damage to property may
occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Type -G/A: Additionally protects against special forms of residual
pulsating DC which have not been smoothed.
• Type -R: To aviod unwanted tripping due to X-ray devices.
• Type -S: Selective residual current device sensitive to AC, type -S.
Compulsory for systems with surge arresters downstream of the
RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5).
• Type -S/A: Additionally protects against special forms of residual
pulsating pulsating DC which have not been smoothed.
• Type -U: Suitable for speed-controlled drives with frequency converters in household, trade, and industry.
Unwanted tripping is avoided thanks to a tripping characteristic
designed particularly for frequency converters.
See also explanation “Frequency Converter-Proof RCDs - What for?”.
Application according to ÖVE/ÖNORM E 8001-1 and Decision
EN 219 (1989), VDE 0100, SEV 1000.
Accessories:
Auxiliary switch for subsequent installation to the left
Tripping signal contact for subsequent installation to the right
Automatic restarting device
Remote control
Pre-mounted sets
Remote testing module
Sealing cover set
Switching interlock
Z-HK
Z-NHK
Z-FW/LP
Z-FW-LPD
Z-FW-MO
Z-FW-LP/MO
Z-FW-LPD/MO
Z-FW/003
Z-FW/010
Z-FW/030
Z-FW/050
Z-RC/AK-4TE
IS/SPE-1TE
248432
248434
248296
265244
284730
290171
290172
248298
248299
248300
248301
101062
101911
Dimensions (mm)
2P
4P
80
5,5
30,5
4,5
45
80
10,5
35
70
44
60
Chapter 2.2.1. – 19
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Technical Data
FRCmM
Electrical
Design according to
IEC/EN 61008
Type G acc. to ÖVE E 8601
Current test marks as printed onto the device
Tripping
Type G, R
Type S
Type U (only 30 mA)
Type U (without 30 mA)
Rated voltage
Rated tripping current
Sensitivity
Rated insulation voltage
Rated impulse withstand voltage
Rated short circuit capacity
Maximum back-up fuse
In = 25A
In = 40A
In = 63A
In = 80A
In = 100A
Rated breaking capacity
or rated fault breaking capacity
In = 16-40 A
In = 63 A
In = 80 A
In = 100 A
Voltage range of test button
2-pole
4-pole
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Degree of protection in moisture-proof enclosure
Upper and lower terminals
Terminal protection
Terminal capacity
Un
IΔn
Ui
Uimp
Icn
instantaneous
10 ms delay
40 ms delay - with selective disconnecting function
10 ms delay
40 ms delay - with selective disconnecting function
240/415V AC, 50Hz
30, 100, 300, 500 mA
AC and pulsating DC
440 V
4 kV (1.2/50µs)
10 kA
Short circuit protection
Overload protection
25 A gG/gL
25 A gG/gL
40 A gG/gL
40 A gG/gL
63 A gG/gL
63 A gG/gL
80 A gG/gL
80 A gG/gL
100 A gG/gL
80 A gG/gL
Im
IΔm
500 A
630 A
800 A
1,000 A
196 - 264 V~
196 - 456 V~
≥ 4,000 operating cycles
≥ 20,000 operating cycles
Terminal screw
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Resistance to climatic conditions
45 mm
80 mm
35 mm (2MU), 70 mm (4MU)
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715
IP40
IP54
open mouthed/lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
1.5 - 35 mm2 single wire
2 x 16 mm2 multi wire
M5 (Pozidriv PZ2)
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
Connection diagram
RCD FRCmM in a Three-Phase AC Network without Neutral Conductor
2-pole
4-pole
L1
L2
L3
L1
L2
L3
1 3 5 N
T
The N-terminal must be connected by a cable link
with the phase L2 (or L1), so that the test loop is
supplied with current and the RCD is tested correctly.
2 4 6 N
Chapter 2.2.1. – 20
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Impact of ambient temperature on the maximum permanent current allowed (A)
Tripping temperature
40°
45°
50°
55°
60°
25A
2p
25
21
18
14
–
4p
25
22
19
16
–
40A
2p
40
37
33
30
26
4p
40
37
34
31
27
63A
2p
63
59
55
50
45
4p
63
59
55
50
45
80A
2p
80
76
72
68
64
4p
80
76
72
68
64
100A
2p
100
95
90
85
80
4p
100
95
90
85
80
Note: Please make sure that these values are not exceeded and that any upstream thermal overload protection switches off in time.
Chapter 2.2.1. – 21
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008
SG49612
• Wide range of compact types of RCDs serving as fault-current and additional protection according to UL1053 & IEC/EN 61008 standards, suitable
for worldwide use
• Comprehensive range of accessories
• Real contact position indicator
• Fault current tripping indicator
• Automatic re-setting possible
• Transparent designation plate
Chapter 2.2.1. – 22
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-NA type A
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG48612
Article No.
Units
per
package
FRCmM-25/2/003-A-NA
FRCmM-25/2/03-A-NA
FRCmM-40/2/003-A-NA
FRCmM-40/2/03-A-NA
FRCmM-63/2/003-A-NA
FRCmM-63/2/03-A-NA
167113
167116
167114
167117
167115
167118
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-25/4/003-A-NA
FRCmM-25/4/03-A-NA
FRCmM-40/4/003-A-NA
FRCmM-40/4/03-A-NA
FRCmM-63/4/003-A-NA
FRCmM-63/4/03-A-NA
167125
167104
167102
167105
167103
167106
1/30
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCmM-25/2/003-G/A-NA
FRCmM-25/2/03-G/A-NA
FRCmM-40/2/003-G/A-NA
FRCmM-40/2/03-G/A-NA
FRCmM-63/2/003-G/A-NA
FRCmM-63/2/03-G/A-NA
167119
167122
167120
167123
167121
167124
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-25/4/003-G/A-NA
FRCmM-25/4/03-G/A-NA
FRCmM-40/4/003-G/A-NA
FRCmM-40/4/03-G/A-NA
FRCmM-63/4/003-G/A-NA
FRCmM-63/4/03-G/A-NA
167107
167110
167108
167111
167109
167112
1/30
1/30
1/30
1/30
1/30
1/30
2-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
SG49612
Type
Designation
4-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
Residual Current Devices FRCmM-NA type G/A
Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601)
In/IΔn
(A)
SG48612
2-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
SG49612
4-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
Chapter 2.2.1. – 23
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCmM-NA
Description
• Residual current devices
• Type -A: Protects against special forms of residual pulsating DC
• Purpose terminal lift above and below
which have have not been smoothed.
• Universal tripping signal switch, also suitable for FAZ, FRBmM-1N • Type -G/A: Additionally protects against special forms of residual
can be mounted subsequently
pulsating DC which have not been smoothed
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Tripping indicator white - blue
• All types suitable for being used with standard fluorescent tubes
with or without electronical ballast (30mA-RCD: 30 units per phase
conductor, 300mA-RCD: 90 units per phase conductor).
Notes: Depending of the fluorescent lamp ballast manufacturer
partly more possible. Symmetrical allocation of the fluorescent
lamp ballasts on all phases favourably. Shifting references of the
fluorescent lamp ballast manufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional
protection” within the meaning of the applicable installation rules.
• Mains connection at either side
• The 4-pole device can also be used for 2-pole connection.
For this purpose use terminals 5-6 and N-N.
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven (self-adhesive RCD-label enclosed).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Auxiliary switch for subsequent installation to the left
Tripping signal contact for subsequent installation to the right
Automatic restarting device
Remote control
Pre-mounted sets
Remote testing module
Sealing cover set
Switching interlock
Z-HK
Z-NHK
Z-FW/LP
Z-FW-LPD
Z-FW-MO
Z-FW-LP/MO
Z-FW-LPD/MO
Z-FW/003
Z-FW/030
Z-RC/AK-4TE
IS/SPE-1TE
248432
248434
248296
265244
284730
290171
290172
248298
248300
101062
101911
Connection diagram
2-pole
4-pole
1 N
T
1 3 5 N
T
2 N
2 4 6 N
Chapter 2.2.1. – 24
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Technical Data
FRCmM-NA
Electrical according to IEC/EN 61008
Design according to
Current test marks as printed onto the device
Tripping
Type G
Rated voltage
Rated tripping current
Sensitivity
Rated insulation voltage
Rated impulse withstand voltage
Rated short circuit capacity
Maximum back-up fuse
Short circuit
Overload protection
Rated breaking capacity
or rated fault breaking capacity
In = 25-40A
In = 63A
Voltage range of test button
2-pole
4-pole
Endurance
electrical components
mechanical components
Overvoltage category
Electrical according to UL1053
Design according to
Current test marks as printed onto the device
Tripping
Type G
Rated voltage
Pick-up Current
Sensitivity
Overvoltage tested
Rated impulse withstand voltage
Rated short circuit capacity
Maximum back-up fuse
Short circuit
Overload protection
Rated breaking capacity
or rated fault breaking capacity
In = 25-40A
In = 63A
Voltage range of test button
2-pole
4-pole
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Degree of protection in moisture-proof enclosure
Upper and lower terminals
Terminal protection
Terminal capacity
Tripping temperature
Resistance to climatic conditions
Humidity
Pollution degree
IEC/EN 61008, ÖVE E 8601
Un
IΔn
Ui
Uimp
Icn
instantaneous
10 ms delay at 50 Hz
240/415 V; 50/60 Hz
30, 300 mA
AC and pulsating DC
440 V
4 kV (1.2/50µs)
10 kA
63 A gG/gL
the operating current shall not exceed the rated current of the RCCB
Im
IΔm
500 A
630 A
196 - 264 V~
196 - 456 V~
≥ 4,000 operating cycles
≥ 10,000 operating cycles
III
UL1053
Un
Uimp
Icn
instantaneous
8 ms delay at 60Hz
480Y/277 V, 60 Hz
22, 200 mA
AC and pulsating DC
530 V
4 kV (1.2/50µs)
5 kA acc. to CSA
70 A J-Class Fuse
the operating current shall not exceed the rated current of the RCCB
Im
IΔm
500 A
630 A
196 - 305 V~
196 - 528 V~
≥ 4,000 operating cycles
≥ 10,000 operating cycles
45 mm
80 mm
35 mm (2MU), 70 mm (4MU)
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715
IP40
IP54
lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
1.5 - 35 mm2 single wire
2 x 16 mm2 multi wire
-25°C to +40°C
according to IEC 61008
5-95%
2
Chapter 2.2.1. – 25
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Dimensions (mm)
Impact of ambient temperature on the maximum permanent current allowed (A)
Tripping temperature
40°
45°
50°
55°
60°
25A
2p
25
21
18
14
–
4p
25
22
19
16
–
40A
2p
40
37
33
30
26
4p
40
37
34
31
27
63A
2p
63
59
55
50
45
4p
63
59
55
50
45
Note: Please make sure that these values are not exceeded and that any upstream thermal overload protection switches off in time.
Correct connection
3+N
(240/415V) IEC
(480Y/277V) UL
3-phase load without N
(196V-264V AC Phase-Phase) IEC
(196V-277V AC Phase-Phase) UL
3-phase load without N
(415V AC Phase-Phase) IEC
(480V AC Phase-Phase) UL
Chapter 2.2.1. – 26
1+N
(250V) IEC
(277V) UL
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-NA-110 acc. to UL1053 & IEC/EN 61008
SG49612
• Wide range of compact types of RCDs serving as fault-current and additional protection according to UL1053 & IEC/EN 61008 standards, suitable
for worldwide use in the 110 V range of applications
• Comprehensive range of accessories
• Real contact position indicator
• Fault current tripping indicator
• Automatic re-setting possible
• Transparent designation plate
Chapter 2.2.1. – 27
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-NA-110 type A
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG49612
Type
Designation
Article No.
Units
per
package
FRCmM-25/4/003-A-NA-110
FRCmM-25/4/03-A-NA-110
FRCmM-40/4/003-A-NA-110
FRCmM-40/4/03-A-NA-110
FRCmM-63/4/003-A-NA-110
FRCmM-63/4/03-A-NA-110
167699
167702
167700
167703
167701
167704
1/30
1/30
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCmM-25/2/003-G/A-NA-110
FRCmM-25/2/03-G/A-NA-110
FRCmM-40/2/003-G/A-NA-110
FRCmM-40/2/03-G/A-NA-110
FRCmM-63/2/003-G/A-NA-110
FRCmM-63/2/03-G/A-NA-110
167693
167696
167694
167697
167695
167698
1/60
1/60
1/60
1/60
1/60
1/60
FRCmM-25/4/003-G/A-NA-110
FRCmM-25/4/03-G/A-NA-110
FRCmM-40/4/003-G/A-NA-110
FRCmM-40/4/03-G/A-NA-110
FRCmM-63/4/003-G/A-NA-110
FRCmM-63/4/03-G/A-NA-110
167705
167708
167706
167709
167707
167710
1/30
1/30
1/30
1/30
1/30
1/30
4-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
Residual Current Devices FRCmM-NA-110 type G/A
Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601)
In/IΔn
(A)
SG48612
2-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
SG49612
4-pole
25/0.03
25/0.3
40/0.03
40/0.3
63/0.03
63/0.3
Chapter 2.2.1. – 28
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCmM-NA-110
Description
• Residual current devices
• Type -A: Protects against special forms of residual pulsating DC
• Purpose terminal lift above and below
which have have not been smoothed.
• Universal tripping signal switch, also suitable for FAZ, FRBmM-1N • Type -G/A: Additionally protects against special forms of residual
can be mounted subsequently
pulsating DC which have not been smoothed
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Tripping indicator white - blue
• All types suitable for being used with standard fluorescent tubes
with or without electronical ballast (30mA-RCD: 30 units per phase
conductor, 300mA-RCD: 90 units per phase conductor).
Notes: Depending of the fluorescent lamp ballast manufacturer
partly more possible. Symmetrical allocation of the fluorescent
lamp ballasts on all phases favourably. Shifting references of the
fluorescent lamp ballast manufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional
protection” within the meaning of the applicable installation rules.
• Mains connection at either side
• The 4-pole device can also be used for 2-pole connection.
For this purpose use terminals 5-6 and N-N.
• The test key “T” must be pressed every month. The system operator must be informed of this obligation and his responsibility in a
way that can be proven (self-adhesive RCD-label enclosed).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Auxiliary switch for subsequent installation to the left
Tripping signal contact for subsequent installation to the right
Automatic restarting device
Remote control
Pre-mounted sets
Remote testing module
Sealing cover set
Switching interlock
Z-HK
Z-NHK
Z-FW/LP
Z-FW-LPD
Z-FW-MO
Z-FW-LP/MO
Z-FW-LPD/MO
Z-FW/003
Z-FW/030
Z-RC/AK-4TE
IS/SPE-1TE
248432
248434
248296
265244
284730
290171
290172
248298
248300
101062
101911
Connection diagram
2-pole
4-pole
1 N
T
1 3 5 N
T
2 N
2 4 6 N
Chapter 2.2.1. – 29
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Technical Data
FRCmM-NA-110
Electrical according to IEC/EN 61008
Design according to
Current test marks as printed onto the device
Tripping
Type G
Rated voltage
Rated tripping current
Sensitivity
Rated insulation voltage
Rated impulse withstand voltage
Rated short circuit capacity
Maximum back-up fuse
Short circuit
Overload protection
Rated breaking capacity
or rated fault breaking capacity
In = 25-40A
In = 63A
Voltage range of test button
2-pole
4-pole
Endurance
electrical components
mechanical components
Overvoltage category
Electrical according to UL1053
Design according to
Current test marks as printed onto the device
Tripping
Type G
Rated voltage
Pick-up Current
Sensitivity
Overvoltage tested
Rated impulse withstand voltage
Rated short circuit capacity
Maximum back-up fuse
Short circuit
Overload protection
Rated breaking capacity
or rated fault breaking capacity
In = 25-40A
In = 63A
Voltage range of test button
2-pole
4-pole
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Degree of protection in moisture-proof enclosure
Upper and lower terminals
Terminal protection
Terminal capacity
Tripping temperature
Resistance to climatic conditions
Humidity
Pollution degree
IEC/EN 61008, ÖVE E 8601
Un
IΔn
Ui
Uimp
Icn
instantaneous
10 ms delay at 50Hz
110/190 V, 50/60Hz
30, 300 mA
AC and pulsating DC
440 V
4 kV (1.2/50µs)
10 kA
63 A gG/gL
the operating current shall not exceed the rated current of the RCCB
Im
IΔm
500 A
630 A
94 - 121 V~
94 - 210 V~
≥ 4,000 operating cycles
≥ 10,000 operating cycles
III
UL1053
Un
Uimp
Icn
instantaneous
8 ms delay at 60Hz
208/120 V, 60 Hz
22, 200 mA
AC and pulsating DC
530 V
4 kV (1.2/50µs)
5 kA acc. to CSA
70 A J-Class Fuse
the operating current shall not exceed the rated current of the RCCB
Im
IΔm
500 A
630 A
94 - 132 V~
94 - 230 V~
≥ 4,000 operating cycles
≥ 10,000 operating cycles
45 mm
80 mm
35 mm (2MU), 70 mm (4MU)
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715
IP40
IP54
lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
1.5 - 35 mm2 single wire
2 x 16 mm2 multi wire
-25°C to +40°C
according to IEC 61008
5-95%
2
Chapter 2.2.1. – 30
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Dimensions (mm)
Impact of ambient temperature on the maximum permanent current allowed (A)
Tripping temperature
40°
45°
50°
55°
60°
25A
2p
25
21
18
14
–
4p
25
22
19
16
–
40A
2p
40
37
33
30
26
4p
40
37
34
31
27
63A
2p
63
59
55
50
45
4p
63
59
55
50
45
Note: Please make sure that these values are not exceeded and that any upstream thermal overload protection switches off in time.
Correct connection
3+N
(110/190V) IEC
(208/120V) UL
3-phase load without N
(110V-120V AC Phase-Phase) IEC
(100V-132V AC Phase-Phase) UL
3-phase load without N
(190V AC Phase-Phase) IEC
(208 AC Phase-Phase) UL
Chapter 2.2.1. – 31
1+N
(110V) IEC
(120V) UL
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-125
• Special residual current devices - all fault-current sensitive
• High level of protection against unwanted tripping
• Selective versions available
• Auxiliary switches available
• 30 mA types for operator protection available
• Modern RCB for 125 A rated current
• For fault current/residual current protection and additional protection
Chapter 2.2.1. – 32
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-125 type A
Conditionally surge current-proof (0.5µs/100kHz ring-wave test), type A
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCMM-125/2/003-A
FRCMM-125/2/01-A
FRCMM-125/2/03-A
FRCMM-125/2/05-A
171164
171165
171166
171167
1/60
1/60
1/60
1/60
FRCMM-125/4/003-A
FRCMM-125/4/01-A
FRCMM-125/4/03-A
FRCMM-125/4/05-A
171174
171175
171176
171177
1/30
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCMM-125/2/003-G/A
FRCMM-125/2/01-G/A
FRCMM-125/2/03-G/A
171168
171169
171170
1/60
1/60
1/60
FRCMM-125/4/003-G/A
FRCMM-125/4/01-G/A
FRCMM-125/4/03-G/A
171178
171179
171180
1/30
1/30
1/30
2-pole
125/0.03
125/0.1
125/0.3
125/0.5
4-pole
125/0.03
125/0.1
125/0.3
125/0.5
Residual Current Devices FRCmM-125 type G/A
Surge current-proof 3 kA (0.5µs/100kHz ring-wave test), type G/A
In/IΔn
(A)
2-pole
125/0.03
125/0.1
125/0.3
4-pole
125/0.03
125/0.1
125/0.3
Chapter 2.2.1. – 33
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-125 type S/A
Selective + surge current-proof 5 kA (0.5µs/100kHz ring-wave test), type S/A
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCMM-125/2/01-S/A
FRCMM-125/2/03-S/A
FRCMM-125/2/05-S/A
171171
171172
171173
1/60
1/60
1/60
FRCMM-125/4/01-S/A
FRCMM-125/4/03-S/A
FRCMM-125/4/05-S/A
171181
171182
171183
1/30
1/30
1/30
Type
Designation
Article No.
Units
per
package
FRCMM-125/4/003-B
FRCMM-125/4/01-B
FRCMM-125/4/03-B
FRCMM-125/4/05-B
171184
171185
171186
171187
1/30
1/30
1/30
1/30
Typenbezeichnung
Artikel-Nr.
VPE
(Stk.)
FRCMM-125/4/003-G/B
171188
1/30
2-pole
125/0.1
125/0.3
125/0.5
4-pole
125/0.1
125/0.3
125/0.5
Residual Current Devices FRCmM-125 type B
Surge current-proof 3 kA, type B
In/IΔn
(A)
4-pole
125/0.03
125/0.1
125/0.3
125/0.5
Residual Current Devices FRCmM-125 type G/B
Surge current-proof 3 kA, type G/B
In/IΔn
(A)
4-pole
125/0.03
Chapter 2.2.1. – 34
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Residual Current Devices FRCmM-125 type G/B+
Surge current-proof 3 kA, type G/B+
In/IΔn
(A)
Type
Designation
Article No.
Units
per
package
FRCMM-125/4/003-G/B+
171189
1/30
Type
Designation
Article No.
Units
per
package
FRCMM-125/4/03-S/BFQ
FRCMM-125/4/05-S/BFQ
171190
171191
1/30
1/30
4-pole
125/0.03
Residual Current Devices FRCmM-125 type S/Bfq
Selective + surge current-proof 5 kA, type S/Bfq
In/IΔn
(A)
4-pole
125/0.3
125/0.5
Chapter 2.2.1. – 35
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCmM-125, type .A.
Description
• Residual current devices
• Type -A: Additionally protects against special forms of residual
• Tripping is line voltage-independent. Consequently, the RCD is suitpulsating DC which have not been smoothed.
able for the protection of humans and additional protection
• Type -G/A: Additionally protects against special forms of residual
(ÖVE/ÖNORM E 8001-1 § 6.1.2)
pulsating DC which have not been smoothed.
• Twin-purpose terminal (lift/open-mouthed) above and below
• Type -S/A: Compulsory for systems with surge arresters down• Not busbar-compatible with other devices of the xEffect-series
stream of the RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5).
• Auxiliary switch Z-HD can be mounted subsequently
• Contact position indicator red - green
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for “fault current/residual current protection” and “additional
protection” within the the meaning of the applicable installation
rules
• Mains connection at either side
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven (self-adhesive RCD-label enclosed)
Accessories:
Auxiliary switch for installation on the left at a later point in time
Z-HD 265620
Connection diagram
2-pole
4-pole
Chapter 2.2.1. – 36
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Technical Data
FRCmM125A, type A.
Electrical
Design according to
Current test marks as printed onto the device
Tripping
Typ G/A
Typ S/A
Rated voltage
Rated tripping current
Sensitivity
Rated short circuit strength
Maximum back-up fuse
Rated breaking capacity
or Rated fault breaking capacity
Voltage range of test button
2-pole
4-pole
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity
Busbar thickness
Admitted ambient temperature range
Storage and transortation temperature range
Resistance to climatic conditions
Mounting position
IEC/EN 61008
Un
IΔn
Inc
Im
IΔm
instantaneous
10 ms delay - with selective disconnecting function
40 ms delay - with selective disconnecting function
240/415 V; 50 Hz
30, 100, 300, 500 mA
AC and pulsating DC
10 kA with back-up fuse
125 A gG/gL
1250 A
204 - 264 V~
204 - 440 V~
≥ 4,000 operating cycles
≥ 20,000 operating cycles
45 mm
80 mm
36 mm (2P), 72 mm (4P)
quick fastening with DIN rail EN50022
IP40
open mouthed/lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
1.5 - 50 mm2
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
any
Dimensions (mm)
Chapter 2.2.1. – 37
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Specifications | Residual Current Devices FRCmM-125, type B.
Description
• Residual current devices - all fault-current sensitive
• Type B: All fault-current sensitive protective devices are designed
• Twin-purpose terminal (lift/open-mouthed) above and below
for use in 50 Hz AC systems with electrical equipment such as fre• Busbar positioning optionally above or below
quency converters, uninterruptible power supply systems, switch
• Free terminal space despite installed busbar
mains adapters or highfrequency power converters. In case of a
• Not busbar-compatible with other devices of the P series
fault, electronic equipment may not only cause AC residual cur• Auxiliary switch Z-HD can be mounted at a later point in time
rents and pulsating DC residual currents, but also pure DC and AC
• Contact position indicator red - green
residual currents of different frequencies in which case residual
• The device functions irrespective of the position of installation
current devices of type AC and A will not trip. Residual current
• Tripping happens independent from line voltage (type A currents).
devices of type FRCmM125A, however, will identify all types of
50 VAC are required to identify currents of type B.
fault currents in line with tripping characteristic B of the IEC 60755
• Mains connection is at the top
standard, i.e. pure DC residual currents as well. In addition, they
• The test key “T” must be pressed every half year. The system operwill also identify all AC residual currents of all frequencies up to
ator must be informed of this obligation and his responsibility in a
1 MHz (100 kHz with type B) in undulating (mixed) currents.
way that can be proven (self-adhesive RCD-label enclosed).
• Type B+: All-current sensitive RCD switchgear for applications
• Pressing the test key “T” serves the only purpose of function testwhere DC fault currents may occur. Non-selective, non-delayed.
ing the residual current device (RCD). This test does not make
Protection against all kinds of fault currents. Also meets the
earthing resistance measurement (RE), or proper checking of the
requirements of the VDE 0664-400 standard (formerly known as
earth conductor condition redundant, which must be performed
VDE V 0664-110) and therefore provides enhanced fire safety.
separately.
• Type Bfq: Suitable for speed-controlled drives with frequency converters; designed for household, commercial and industrial applications. Unwanted tripping is prevented through a tripping characteristic especially adapted to frequency converters. Protection against
all kinds of fault currents.
Accessories:
Auxiliary switch for installation on the left at a later point in time
Z-HD 265620
Connection diagram
2-pole
4-pole
Tripping current frequency response
Tripping current frequency response 30 mA Typ B
Tripping current frequency response 30 mA Typ G/B+
Tripping current frequency response 30 mA Typ S/B
Tripping current frequency response 100 mA Typ B
Chapter 2.2.1. – 38
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Tripping current frequency response 300 mA Typ S/Bfq
Tripping current frequency response 500 mA Typ S/Bfq
Technical Data
FRCmM125A, Type B.
Electrical
Design according to
Current test marks as printed onto the device
Tripping
Type G/B
Type S/B
Rated voltage
Rated tripping current
Sensitivity
Rated short circuit capacity
Peak withstand current
Typ B
Typ B selektiv
Maximum back-up fuse
Voltage range of test button
Rated breaking capacity
or rated fault breaking capacity
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity
Busbar thickness
Admitted ambient temperature range
Storage and transortation temperature range
Resistance to climatic conditions
Mounting position
IEC/EN 61008
Un
IΔn
Icn
short-time delayed
40 ms delay - with selective disconnecting function
240/415 V; 50 Hz
30, 100, 300, 500 mA
All types of fault-current
10 kA
3kA
5kA
Short circuit protection 125A gG/gL
204 - 264 V~
Im
IΔm
1250 A
≥ 4,000 operating cycles
≥ 10,000 operating cycles
45 mm
80 mm
70 mm (4MU) for 2-pole and 4-pole
quick fastening with DIN rail EN50022
IP40
open mouthed/lift terminals
finger and hand touch safe, BGV A.
1.5 - 50 mm2
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
any
Dimensions (mm)
Chapter 2.2.1. – 39
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Leakage Current Monitor PDIM
SG31211
• Reliable, universal monitoring of residual current
• RCD characteristic and sensitivity are freely selectable
• Compact design, with integrated transformer
• DIN mounting, compatible with shapes and standard busbar connections
of other xEffect devices
• Local status indication of residual current through 3 LEDs
• 2 potential-free signalling contacts
Chapter 2.2.1. – 40
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Leakage Current Monitor PDIM
+
, instantaneous, G , S => adjustable
In/IΔn
(A)
SG31211
Type
Designation
Article No.
Units
per
package
PDIM-40/4
PDIM-100/4
111760
111761
1/30
1/30
4-pole
40/0.03; 0.1; 0.3; 0.5; 1
100/0.03; 0.1; 0.3; 0.5; 1
Specifications | Leackage Current Monitor PDIM
Description
• Shape compatible with and suitable for standard busbar connection to other devices of the xEffect-series
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Power supply via ‘OR’ disjunction of the 4 conductors
• Electronic functioning (line-voltage independent)
• The device works irrespective of the position of installation
• Mains connection at either side
• The 4-pole device can also be used for 3-pole connection.
For this purpose use terminals 1-2, 3-4, and 5-6.
• The 4-pole device can also be used for 2-pole connection.
For this purpose use terminals 5-6 and N-N.
• 2 potential-free relays (make contact, in parallel with the yellow
and red LED) (up to 10 A / 240 V~)
Functioning
• The green LED becomes active at 0-30% of the preset IΔn.
The yellow LED becomes active at 30-50% of the preset IΔn.
The red LED becomes active at >50% of the preset IΔn.
• The yellow LED turns off again when the identified residual current
is <30% of the preset IΔn.
• The red LED stays on even if the identified residual current is <50%
of the preset IΔn.
• The red LED will only turn off after pressing the reset button.
• Only one LED will be active at a time.
• An output relay will always be switched simultaneously with the
yellow or red LED
• Depending on the setting of the type of RCD (instantaneous, G, S),
the residual current needs to flow a sufficiently long time before an
action is triggered.
Test function
• The rotary coding switch for the RCD switch function is to be set to
“TEST”.The device then alternately simulates residual currents of
30% and 50% of the IΔn. In this process, the yellow and red LED
flash alternately (1 Hz), both output relays remain permanently
energised.
Connection diagram
4-pole
Chapter 2.2.1. – 41
EATON CORPORATION xxxxx+xxxx-xxxxEN
Residual Current Devices
Technical Data
PDIM
Electrical
Design similar to
Current test marks as printed onto the device
Rated current
Tripping behaviour (adjustable)
Type G
Type S
Rated voltage
Rated tripping current (adjustable)
Sensitivity
Rated insulation voltage
Rated short circuit capacity
Maximum back-up fuse admitted
In = 40A
In = 100A
Switching contacts potential-free
Tripping behaviour of the contacts
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Degree of protection in splash-proof enclosure
Upper and lower terminals
Terminal protection
Terminal capacity (1, 2, 3, 4, 5, 6, N, N)
Terminal capacity of switching contacts
Busbar thickness
Admitted ambient temperature range
Storage and transortation temperature range
Resistance to climatic conditions
DIN/EN 62020
In
Un
IΔn
Ui
Icn
40 A, 100 A
instantaneous
10 ms delay
40 ms delay - with selective disconnecting function
230/400 V, 50/60 Hz
240/415 V, 50/60 Hz
30, 100, 300, 500, 1000 mA
AC and pulsating DC
440 V
10 kA
Overload protection
Short circuit protection
40 A gG/gL
63 A gG/gL
63 A gG/gL
100 A gG/gL
10 A / 240 V~
1: 30-50% IΔn
2: >50% IΔn
≥ 4,000 operating cycles
≥ 20,000 operating cycles
45 mm
80 mm
70 mm (4MU)
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715
IP40
IP54
open mouthed/lift terminals
Protection against accidental contact according to BGV A3, ÖVE-EN 6
1.5 - 35 mm2 single-wired
2 x 16 mm2 multi-wired
0.25 - 1.5 mm2
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
Dimensions (mm)
Chapter 2.2.1. – 42
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBdM, digital
SG48312
• High-quality residual current device / miniature circuit breaker combination, line voltage-dependent
• 1+N and 2-pole
• Contact position indicator red - green
• Tripping indicator white - blue
• New level of accuracy -> reduced unwanted tripping
• Local status indication of residual current through 3 LEDs
• 2-position DIN rail clip, permits removal from existing busbar system
• Comprehensive range of accessories suitable for subsequent installation
• Wide variety of rated tripping currents
• Rated currents up to 25 A
• Tripping characteristics B, C, D
• Rated breaking capacity 10 kA
Chapter 3.1.1. – 1
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBdM type G/A
10 kA, 1+N-pole
Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601)
In/IΔn
(A)
SG48312
Units
per
package
FRBdM-B10/1N/001-G/A
FRBdM-B13/1N/001-G/A
FRBdM-B16/1N/001-G/A
FRBdM-B10/1N/003-G/A
FRBdM-B13/1N/003-G/A
FRBdM-B16/1N/003-G/A
FRBdM-B10/1N/01-G/A
FRBdM-B13/1N/01-G/A
FRBdM-B16/1N/01-G/A
168249
168250
168251
168264
168265
168266
168279
168280
168281
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBdM-C6/1N/001-G/A
FRBdM-C10/1N/001-G/A
FRBdM-C13/1N/001-G/A
FRBdM-C16/1N/001-G/A
FRBdM-C20/1N/001-G/A
FRBdM-C25/1N/001-G/A
FRBdM-C6/1N/003-G/A
FRBdM-C10/1N/003-G/A
FRBdM-C13/1N/003-G/A
FRBdM-C16/1N/003-G/A
FRBdM-C20/1N/003-G/A
FRBdM-C25/1N/003-G/A
FRBdM-C6/1N/01-G/A
FRBdM-C10/1N/01-G/A
FRBdM-C13/1N/01-G/A
FRBdM-C16/1N/01-G/A
FRBdM-C20/1N/01-G/A
FRBdM-C25/1N/01-G/A
168252
168253
168254
168255
168256
168257
168267
168268
168269
168270
168271
168272
168282
168283
168284
168285
168286
168287
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBdM-D6/1N/001-G/A
FRBdM-D10/1N/001-G/A
FRBdM-D13/1N/001-G/A
FRBdM-D16/1N/001-G/A
FRBdM-D20/1N/001-G/A
FRBdM-D25/1N/001-G/A
FRBdM-D6/1N/003-G/A
FRBdM-D10/1N/003-G/A
FRBdM-D13/1N/003-G/A
FRBdM-D16/1N/003-G/A
FRBdM-D20/1N/003-G/A
FRBdM-D25/1N/003-G/A
FRBdM-D6/1N/01-G/A
FRBdM-D10/1N/01-G/A
FRBdM-D13/1N/01-G/A
FRBdM-D16/1N/01-G/A
FRBdM-D20/1N/01-G/A
FRBdM-D25/1N/01-G/A
168258
168259
168260
168261
168262
168263
168273
168274
168275
168276
168277
168278
168288
168289
168290
168291
168292
168293
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic C
6/0.01
10/0.01
13/0.01
16/0.01
20/0.01
25/0.01
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
SG48312
Article No.
Characteristic B
10/0.01
13/0.01
16/0.01
10/0.03
13/0.03
16/0.03
10/0.1
13/0.1
16/0.1
SG48312
Type
Designation
Characteristic D
6/0.01
10/0.01
13/0.01
16/0.01
20/0.01
25/0.01
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
Chapter 3.1.1. – 2
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBdM type G/A
10 kA, 2-pole
Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601)
In/IΔn
(A)
SG48312
Units
per
package
FRBdM-B10/2/001-G/A
FRBdM-B13/2/001-G/A
FRBdM-B16/2/001-G/A
FRBdM-B10/2/003-G/A
FRBdM-B13/2/003-G/A
FRBdM-B16/2/003-G/A
FRBdM-B10/2/01-G/A
FRBdM-B13/2/01-G/A
FRBdM-B16/2/01-G/A
168294
168295
168296
168198
168199
168200
168213
168214
168215
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBdM-C6/2/001-G/A
FRBdM-C10/2/001-G/A
FRBdM-C13/2/001-G/A
FRBdM-C16/2/001-G/A
FRBdM-C20/2/001-G/A
FRBdM-C25/2/001-G/A
FRBdM-C6/2/003-G/A
FRBdM-C10/2/003-G/A
FRBdM-C13/2/003-G/A
FRBdM-C16/2/003-G/A
FRBdM-C20/2/003-G/A
FRBdM-C25/2/003-G/A
FRBdM-C6/2/01-G/A
FRBdM-C10/2/01-G/A
FRBdM-C13/2/01-G/A
FRBdM-C16/2/01-G/A
FRBdM-C20/2/01-G/A
FRBdM-C25/2/01-G/A
168297
168298
168299
168300
168301
168302
168201
168202
168203
168204
168205
168206
168216
168217
168218
168219
168220
168221
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBdM-D6/2/001-G/A
FRBdM-D10/2/001-G/A
FRBdM-D13/2/001-G/A
FRBdM-D16/2/001-G/A
FRBdM-D20/2/001-G/A
FRBdM-D25/2/001-G/A
FRBdM-D6/2/003-G/A
FRBdM-D10/2/003-G/A
FRBdM-D13/2/003-G/A
FRBdM-D16/2/003-G/A
FRBdM-D20/2/003-G/A
FRBdM-D25/2/003-G/A
FRBdM-D6/2/01-G/A
FRBdM-D10/2/01-G/A
FRBdM-D13/2/01-G/A
FRBdM-D16/2/01-G/A
FRBdM-D20/2/01-G/A
FRBdM-D25/2/01-G/A
168303
168304
168305
168195
168196
168197
168207
168208
168209
168210
168211
168212
168222
168223
168224
168225
168226
168227
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic C
6/0.01
10/0.01
13/0.01
16/0.01
20/0.01
25/0.01
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
SG48312
Article No.
Characteristic B
10/0.01
13/0.01
16/0.01
10/0.03
13/0.03
16/0.03
10/0.1
13/0.1
16/0.1
SG48312
Type
Designation
Characteristic D
6/0.01
10/0.01
13/0.01
16/0.01
20/0.01
25/0.01
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
Chapter 3.1.1. – 3
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Specifications | Combined RCD/MCB Devices FRBdM, digital
Description
• Combined RCD/MCB device
• Type -G/A: Additionally protects against special forms of residual
• Line voltage-dependent tripping
pulsating DC which have not been smoothed.
• Compatible with standard busbar
• Type -G: High reliability against unwanted tripping. Compulsory
• Twin-purpose terminal (lift/open-mouthed) above and below
for any circuit where personal injury or damage to property may
• Busbar positioning optionally above or below
occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Free terminal space despite installed busbar
Additionally protects against special forms of residual pulsating DC
• Guide for secure terminal connection
which have not been smoothed.
• Switching toggle (MCB component) in colour designating the rated
current
• Contact position indicator red - green
• Fault current tripping indicator white - blue
• Comprehensive range of accessories suitable for subsequent installation
• The test key “T” must be pressed every year. The system operator
must be informed of this obligation and his responsibility in a way
that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it's recommended to test in shorter intervals (e.g. monthly).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Auxiliary switch for subsequent installation
Shunt trip release
Switching interlock
Screws lock 2MU
ZP-IHK
ZP-WHK
ZP-NHK
ZP-ASA/..
IS/SPE-1TE
Z-CV/SO-2P
286052
286053
248437
248438, 248439
101911
221954800
Connection diagram
1+N-pole
2-pole
Dimensions (mm)
Chapter 3.1.1. – 4
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Technical Data
FRBdM
Electrical
Design according to
Current test marks as printed onto the device
Number of protected poles
1+N-pole
2-pole
Tripping
Type G
Rated voltage
Rated operational voltage
Rated tripping current
Rated non-tripping current
Sensitivity
Press of test button duration
Selectivity class
Service short circuit capacity
Rated short circuit capacity
Rated current
Rated impulse withstand voltage
Characteristic
Maximum back-up fuse (short circuit)
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection switch
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity rigid solid/stranded wire
Terminal screw
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Climatic conditions
Line side (supply)
Load side
IEC/EN 61009
1
2
Un
Ue
IΔn
IΔno
Ics
Icn
Uimp
line voltage-dependent, 10 ms delay 3 kA (8/20µs),
surge current-proof
240 V AC, 50 Hz
204-260 V AC
10, 30, 100 mA
0.55 IΔn
G/A
> 0.5 s
3
7.5 kA
10 kA
6 - 25 A
4 kV (1.2/50µs)
B, C, D
100 A gL (>10 kA)
≥ 4,000 operating cycles (In, Un, cosÏ• = 0.87)
≥ 10,000 operating cycles
45 mm
80 mm
35 mm (2MU)
2-position DIN rail clip, permits removal from existing busbar system
IP20
IP40
open mouthed/lift terminals
finger and hand touch safe, VBG4, ÖVE-EN 6
1 - 25 mm2
M5 (with slotted screw acc. to EN ISO 4757-Z2, Pozidriv PZ2)
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
acc. to IEC 68-2 (25..55°C / 90..95% RH)
lower terminals
upper terminals
Chapter 3.1.1. – 5
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Tripping Characteristic FRBdM, Characteristics B, C and D
Chapter 3.1.1. – 6
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Let-through Energy FRBdM
Let-through energy FRBdM, characteristic B
Let-through energy FRBdM, characteristic C
Let-through energy FRBdM, characteristic D
Chapter 3.1.1. – 7
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Let-through Current FRBdM
Let-through current FRBdM, characteristic B
Let-through current FRBdM, characteristic C
Let-through current FRBdM, characteristic D
Chapter 3.1.1. – 8
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Selectivity-limit current Is [kA] for selectivity between FRBdM and NZMB(C)(N)(H)1-A..., NZMB(C)(N)(H)2-A...
Short circuit currents in kA, Rated currents of fuses in A.
Overload and short-circuit release unit NZM at max. value
FRBdM
NZM.1-A…
FRBdM
NZM.2-A…
Icu = 25 (36) (50) (100) kA
Icu = 25 (36) (50) (150) kA
40
50
63
80
100 125
40
50
63
80
100 125 160 200 250
B10
1.2
1.5
2
2
4
10
B10
1
1.5
2.5
3
10
B13
1
1.5
2
2
4
10
B13
1
1.2
2
3
10
10
10
10
10
B16
1
1.2
1.5
2
3
8
B16
1
1.2
1.5
2.5
10
10
10
10
10
C+D6
1.2
1.5
2
2
4
10
C+D6
1
1.5
2.5
3
10
10
10
10
10
C+D10
1.2
1.5
2
2
4
10
C+D10
1
1.5
2.5
3
10
10
10
10
10
C+D13
1
1.5
2
2
4
10
C+D13
1
1.2
2
3
10
10
10
10
10
C+D16
1
1.2
1.5
2
3
8
C+D16
1
1.2
1.5
2.5
10
10
10
10
10
C+D20
0.8
1.2
1.5
1.5
3
8
C+D20
1
1.2
1.5
1.5
10
10
10
10
10
C+D25
0.7
1.1
1.3
1.3
2.5
6
C+D25
0.9
1.1
1.3
1.3
10
10
10
10
10
10
10
10
10
NZMB1(C1)(N1)(H1): Icu (400/415V) = 25(36)(50)(100) kA (acc. to IEC/EN 60947-2)
NZMB2(C2)(N2)(H2): Icu (400/415V) = 25(36)(50)(150) kA (acc. to IEC/EN 60947-2)
Selectivity-limit current Is [kA] for selectivity between FRBdM and NH000/NH00/NH1 gG
Short circuit currents in kA, Rated currents of fuses in A.
FRBdM
NH000/NH00/NH1 gG
25
32
35
40
50
63
80
100 125
B10
<0.5 <0.5 0,9
1,7
2,3
3,4
5,2
6,9
>10
>10
>10
B13
<0.5 <0.5 0,8
1,4
1,9
2,7
4,1
5,2
8,5
>10
>10
B16
<0.5 <0.5 0,7
1,2
1,6
2,2
3,1
3,8
5,7
>10
>10
C6
<0.5 0,5
0,9
1,8
2,5
3,8
8,2
>10
>10
>10
>10
C10
<0.5 <0.5 0,8
1,5
2,0
2,9
4,5
6,6
>10
>10
>10
C13
<0.5 <0.5 0,6
1,2
1,5
2,2
3,3
4,2
6,7
>10
>10
C16
<0.5 <0.5 0,6
1,0
1,3
1,8
2,6
3,3
4,8
>10
>10
C20
<0.5 <0.5 0,5
0,9
1,1
1,6
2,3
2,8
4,1
8,6
>10
C25
<0.5 <0.5 <0.5 0,8
1,0
1,4
2,0
2,5
3,6
7,1
>10
D6
<0.5 0,5
1,0
1,8
2,5
3,8
7,8
>10
>10
>10
>10
D10
<0.5 <0.5 0,7
1,2
1,6
2,4
3,8
5,2
>10
>10
>10
D13
<0.5 <0.5 0,6
1,0
1,3
1,9
2,8
3,6
5,6
>10
>10
D16
<0.5 <0.5 0,5
0,9
1,1
1,6
2,3
2,9
4,3
>10
>10
D20
<0.5 <0.5 <0.5 0,8
1,0
1,4
2,0
2,5
3,6
7,5
>10
D25
<0.5 <0.5 <0.5 0,7
0,8
1,1
1,6
2,1
3,1
5,5
7,7
16
20
Rated breaking capacity (NH) AC 500 V = 120 kA (acc. to IEC/EN 60269)
Chapter 3.1.1. – 9
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Back-up Protection between FRBdM and NZM.1-A…, 240 V
Short circuit currents in kA.
Short circuit currents in kA.
FRBdM
FRBdM
NZMB1-A…
Ue = 240 V
B
NZMC1-A…
Ue = 240 V
C
D
B
C
D
6
-
25
25
6
-
36
36
10
25
25
25
10
36
36
36
13
25
25
25
13
36
36
36
16
25
25
25
16
36
36
36
20
-
20
20
20
-
20
20
25
-
20
20
25
-
20
20
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMB1) = 25 kA (acc. to IEC/EN 60947-2)
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMC1) = 36 kA (acc. to IEC/EN 60947-2)
Short circuit currents in kA.
Short circuit currents in kA.
FRBdM
FRBdM
NZMN1-A…
Ue = 240 V
Ue = 240 V
B
NZMH1-A…
C
D
B
C
D
6
-
40
40
6
-
40
40
10
40
40
40
10
40
40
40
13
40
40
40
13
40
40
40
16
40
40
40
16
40
40
40
20
-
20
20
20
-
20
20
25
-
20
20
25
-
20
20
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMN1) = 50 kA (acc. to IEC/EN 60947-2)
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMH1) = 100 kA (acc. to IEC/EN 60947-2)
Back-up Protection between FRBdM and NZM.2-A…, 240 V
Short circuit currents in kA.
Short circuit currents in kA.
FRBdM
FRBdM
NZMB2-A…
Ue = 240 V
Ue = 240 V
B
NZMC1-A…
C
D
B
C
D
6
-
25
25
6
-
36
36
10
25
25
25
10
36
36
36
13
25
25
25
13
36
36
36
16
25
25
25
16
25
25
25
20
-
20
20
20
-
20
20
25
-
10
10
25
-
10
10
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMB2) = 25 kA (acc. to IEC/EN 60947-2)
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMC2) = 36 kA (acc. to IEC/EN 60947-2)
Short circuit currents in kA.
Short circuit currents in kA.
FRBdM
FRBdM
NZMN1-A…
Ue = 240 V
Ue = 240 V
B
NZMH1-A…
C
D
B
C
D
6
-
40
40
6
-
40
40
10
40
40
40
10
40
40
40
13
40
40
40
13
40
40
40
16
25
25
25
16
25
25
25
20
-
15
15
20
-
15
15
25
-
10
10
25
-
10
10
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMN2) = 50 kA (acc. to IEC/EN 60947-2)
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icu (NZMH2) = 150 kA (acc. to IEC/EN 60947-2)
Chapter 3.1.1. – 10
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Back-up Protection between FRBdM and NH00-125 A, 240 V
Short circuit currents in kA.
FRBdM
NH00-125A gG
Ue = 240 V
B
C
D
6
-
40
40
10
40
40
40
13
40
40
40
16
40
40
40
20
-
20
20
25
-
10
10
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
AC 500 V (NH00-125A gG) = 120 kA (acc. to IEC/EN 60269)
Back-up Protection between FRBdM and PLSM-OV63, 230 V
Short circuit currents in kA.
FRBdM
PLSM-OV63/2,3,4,3N
IT-System U = 230 V
B
C
D
6
-
10
10
10
10
10
10
13
10
10
10
16
10
10
10
20
-
10
10
25
-
10
10
Ue = 240V: Icn (FRBdM) = 10 kA (acc. to IEC/EN 61009)
Ue = 230/400V: Icu (PLSM-OV63) = 10 kA (acc. to IEC/EN 60947-2)
Selectivity-limit current Is [kA] for selectivity between FRBdM and PLSM-OV/PLHT-OV...
Short circuit currents in kA, Rated currents of fuses in A.
FRBdM
PLSM-OV/PLHT-OV
Icu = 10 kA
25
32
40
50
56
63
80
B10
1.5
1.5
1.5
1.5
1.5
1.5
1.5
B13
1.5
1.5
1.5
1.5
1.5
1.5
1.5
B16
1.5
1.5
1.5
1.5
1.5
1.5
1.5
C+D6
1.5
1.5
1.5
1.5
1.5
1.5
1.5
C+D10
1.5
1.5
1.5
1.5
1.5
1.5
1.5
C+D13
1.5
1.5
1.5
1.5
1.5
1.5
1.5
C+D16
1.5
1.5
1.5
1.5
1.5
1.5
1.5
C+D20
-
1.5
1.5
1.5
1.5
1.5
1.5
C+D25
-
-
1.5
1.5
1.5
1.5
1.5
Chapter 3.1.1. – 11
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Local Indication RCD
green
Self check (power ON) 2 s –>
IΔ ≥ 50% IΔn
red
IΔ = 30-50% IΔn
amber
IΔ ≤ 30% IΔn
green
Service Mode (measuring of residual current IΔ)
Pressing test button twice to activate Service-Mode
press
(0.1 - 0.4 s)
release
(0.1 - 0.4 s)
press
(0.1 - 0.4 s)
Measurement delimiter
Measurement delimiter ON time
10 mA measurement color
1 mA measurement color
Double-pressing test button to activate Service Mode
Time duration of Service Mode
red
400 ms
amber
green
press (0.1-0.4 s) -> release (0.1-0.4 s) -> press (0.1-0.4 s)
4 min (during activated Service Mode all protection functions are still
working)
Lamp test
2s
––>
amber
green
red
+
100 mA
amber
amber
+
10 mA
green
+
10 mA
green
+
1 mA
green
+
1 mA
1 mA
⎧
⎜
⎜
⎜
⎜
⎨
⎜
⎜
⎜
⎜
⎩
red
2s
––>
123 mA
Chapter 3.1.1. – 12
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM, 1+N-pole
SG13711
• High-quality residual current device / miniature circuit breaker combination, line voltage-independent
• Contact position indicator red - green
• Fault current tripping indicator
• Guide for secure terminal connection
• 3-position DIN rail clip, permits removal from existing busbar system
• Comprehensive range of accessories suitable for subsequent installation
• Wide variety of rated tripping currents
• Rated currents up to 40 A
• Tripping characteristics B, C, D
• Rated breaking capacity 10 kA
Chapter 3.1.1. – 13
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type AC
10 kA, 1+N-pole
Conditionally surge current-proof 250 A, type AC
In/IΔn
(A)
SG13711
Article No.
Units
per
package
FRBmM-B6/1N/001
FRBmM-B10/1N/001
FRBmM-B13/1N/001
FRBmM-B16/1N/001
FRBmM-B6/1N/003
FRBmM-B10/1N/003
FRBmM-B13/1N/003
FRBmM-B16/1N/003
FRBmM-B20/1N/003
FRBmM-B25/1N/003
FRBmM-B32/1N/003
FRBmM-B40/1N/003
FRBmM-B6/1N/01
FRBmM-B10/1N/01
FRBmM-B13/1N/01
FRBmM-B16/1N/01
FRBmM-B20/1N/01
FRBmM-B25/1N/01
FRBmM-B32/1N/01
FRBmM-B40/1N/01
FRBmM-B6/1N/03
FRBmM-B10/1N/03
FRBmM-B13/1N/03
FRBmM-B16/1N/03
FRBmM-B20/1N/03
FRBmM-B25/1N/03
FRBmM-B32/1N/03
FRBmM-B40/1N/03
170971
170972
170973
170974
170920
170695
170696
170697
170698
170699
170700
170701
170656
170657
170658
170659
170660
170661
170662
170663
170551
170600
170601
170602
170603
170604
170605
170606
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-C2/1N/001
FRBmM-C4/1N/001
FRBmM-C6/1N/001
FRBmM-C10/1N/001
FRBmM-C13/1N/001
FRBmM-C16/1N/001
FRBmM-C2/1N/003
FRBmM-C4/1N/003
FRBmM-C6/1N/003
FRBmM-C10/1N/003
FRBmM-C13/1N/003
FRBmM-C16/1N/003
FRBmM-C20/1N/003
FRBmM-C25/1N/003
FRBmM-C32/1N/003
FRBmM-C40/1N/003
FRBmM-C2/1N/01
FRBmM-C4/1N/01
FRBmM-C6/1N/01
FRBmM-C10/1N/01
FRBmM-C13/1N/01
FRBmM-C16/1N/01
FRBmM-C20/1N/01
FRBmM-C25/1N/01
FRBmM-C32/1N/01
FRBmM-C40/1N/01
FRBmM-C2/1N/03
FRBmM-C4/1N/03
FRBmM-C6/1N/03
FRBmM-C10/1N/03
FRBmM-C13/1N/03
FRBmM-C16/1N/03
FRBmM-C20/1N/03
FRBmM-C25/1N/03
FRBmM-C32/1N/03
FRBmM-C40/1N/03
170979
170980
170981
170982
170983
170984
170532
170533
170534
170535
170536
170537
170538
170539
170612
170613
170672
170673
170674
170675
170676
170677
170678
170679
170680
170681
170561
170562
170563
170564
170565
170566
170567
170568
170569
170570
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic B
6/0.01
10/0.01
13/0.01
16/0.01
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
32/0.1
40/0.1
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
25/0.3
32/0.3
40/0.3
SG13711
Type
Designation
Characteristic C
2/0.01
4/0.01
6/0.01
10/0.01
13/0.01
16/0.01
2/0.03
4/0.03
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
2/0.1
4/0.1
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
32/0.1
40/0.1
2/0.3
4/0.3
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
25/0.3
32/0.3
40/0.3
Chapter 3.1.1. – 14
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
SG13711
Characteristic D
2/0.01
4/0.01
6/0.01
10/0.01
13/0.01
16/0.01
2/0.03
4/0.03
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
2/0.1
4/0.1
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
2/0.3
4/0.3
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
FRBmM-D2/1N/001
FRBmM-D4/1N/001
FRBmM-D6/1N/001
FRBmM-D10/1N/001
FRBmM-D13/1N/001
FRBmM-D16/1N/001
FRBmM-D2/1N/003
FRBmM-D4/1N/003
FRBmM-D6/1N/003
FRBmM-D10/1N/003
FRBmM-D13/1N/003
FRBmM-D16/1N/003
FRBmM-D20/1N/003
FRBmM-D2/1N/01
FRBmM-D4/1N/01
FRBmM-D6/1N/01
FRBmM-D10/1N/01
FRBmM-D13/1N/01
FRBmM-D16/1N/01
FRBmM-D20/1N/01
FRBmM-D2/1N/03
FRBmM-D4/1N/03
FRBmM-D6/1N/03
FRBmM-D10/1N/03
FRBmM-D13/1N/03
FRBmM-D16/1N/03
FRBmM-D20/1N/03
Chapter 3.1.1. – 15
170922
170909
170910
170911
170912
170913
170636
170637
170638
170639
170640
170641
170642
170692
170693
170694
170540
170541
170542
170543
170587
170588
170589
170590
170591
170592
170593
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type A
10 kA, 1+N-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG13711
Article No.
Units
per
package
FRBmM-B6/1N/001-A
FRBmM-B10/1N/001-A
FRBmM-B13/1N/001-A
FRBmM-B16/1N/001-A
FRBmM-B6/1N/003-A
FRBmM-B10/1N/003-A
FRBmM-B13/1N/003-A
FRBmM-B16/1N/003-A
FRBmM-B20/1N/003-A
FRBmM-B25/1N/003-A
FRBmM-B32/1N/003-A
FRBmM-B40/1N/003-A
FRBmM-B6/1N/01-A
FRBmM-B10/1N/01-A
FRBmM-B13/1N/01-A
FRBmM-B16/1N/01-A
FRBmM-B20/1N/01-A
FRBmM-B25/1N/01-A
FRBmM-B32/1N/01-A
FRBmM-B40/1N/01-A
FRBmM-B6/1N/03-A
FRBmM-B10/1N/03-A
FRBmM-B13/1N/03-A
FRBmM-B16/1N/03-A
FRBmM-B20/1N/03-A
FRBmM-B25/1N/03-A
FRBmM-B32/1N/03-A
FRBmM-B40/1N/03-A
170975
170976
170977
170978
170702
170703
170704
170705
170706
170707
170708
170709
170664
170665
170666
170667
170668
170669
170670
170671
170607
170608
170609
170610
170611
170552
170553
170554
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-C2/1N/001-A
FRBmM-C4/1N/001-A
FRBmM-C6/1N/001-A
FRBmM-C10/1N/001-A
FRBmM-C13/1N/001-A
FRBmM-C16/1N/001-A
FRBmM-C2/1N/003-A
FRBmM-C4/1N/003-A
FRBmM-C6/1N/003-A
FRBmM-C10/1N/003-A
FRBmM-C13/1N/003-A
FRBmM-C16/1N/003-A
FRBmM-C20/1N/003-A
FRBmM-C25/1N/003-A
FRBmM-C32/1N/003-A
FRBmM-C40/1N/003-A
FRBmM-C2/1N/01-A
FRBmM-C4/1N/01-A
FRBmM-C6/1N/01-A
FRBmM-C10/1N/01-A
FRBmM-C13/1N/01-A
FRBmM-C16/1N/01-A
FRBmM-C20/1N/01-A
FRBmM-C25/1N/01-A
FRBmM-C32/1N/01-A
FRBmM-C40/1N/01-A
FRBmM-C2/1N/03-A
FRBmM-C4/1N/03-A
FRBmM-C6/1N/03-A
FRBmM-C10/1N/03-A
FRBmM-C13/1N/03-A
FRBmM-C16/1N/03-A
FRBmM-C20/1N/03-A
FRBmM-C25/1N/03-A
FRBmM-C32/1N/03-A
FRBmM-C40/1N/03-A
170904
170905
170906
170907
170908
170921
170614
170615
170616
170617
170618
170619
170620
170621
170622
170623
170682
170683
170684
170685
170686
170687
170688
170689
170690
170691
170571
170572
170573
170574
170575
170576
170577
170578
170579
170580
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic B
6/0.01
10/0.01
13/0.01
16/0.01
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
32/0.1
40/0.1
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
25/0.3
32/0.3
40/0.3
SG13711
Type
Designation
Characteristic C
2/0.01
4/0.01
6/0.01
10/0.01
13/0.01
16/0.01
2/0.03
4/0.03
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
2/0.1
4/0.1
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
32/0.1
40/0.1
2/0.3
4/0.3
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
25/0.3
32/0.3
40/0.3
Chapter 3.1.1. – 16
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
SG13711
Characteristic D
2/0.01
4/0.01
6/0.01
10/0.01
13/0.01
16/0.01
2/0.03
4/0.03
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
2/0.1
4/0.1
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
2/0.3
4/0.3
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
FRBmM-D2/1N/001-A
FRBmM-D4/1N/001-A
FRBmM-D6/1N/001-A
FRBmM-D10/1N/001-A
FRBmM-D13/1N/001-A
FRBmM-D16/1N/001-A
FRBmM-D2/1N/003-A
FRBmM-D4/1N/003-A
FRBmM-D6/1N/003-A
FRBmM-D10/1N/003-A
FRBmM-D13/1N/003-A
FRBmM-D16/1N/003-A
FRBmM-D20/1N/003-A
FRBmM-D2/1N/01-A
FRBmM-D4/1N/01-A
FRBmM-D6/1N/01-A
FRBmM-D10/1N/01-A
FRBmM-D13/1N/01-A
FRBmM-D16/1N/01-A
FRBmM-D20/1N/01-A
FRBmM-D2/1N/03-A
FRBmM-D4/1N/03-A
FRBmM-D6/1N/03-A
FRBmM-D10/1N/03-A
FRBmM-D13/1N/03-A
FRBmM-D16/1N/03-A
FRBmM-D20/1N/03-A
Chapter 3.1.1. – 17
170914
170915
170916
170917
170918
170919
170643
170644
170645
170646
170647
170648
170649
170544
170545
170546
170547
170548
170549
170550
170594
170595
170596
170597
170598
170599
170868
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type G
10 kA, 1+N-pole
Surge current-proof 3 kA, type G (ÖVE E 8601)
In/IΔn
(A)
SG13711
Units
per
package
FRBmM-B13/1N/003-G
FRBmM-B16/1N/003-G
FRBmM-B20/1N/003-G
FRBmM-B25/1N/003-G
FRBmM-B32/1N/003-G
FRBmM-B40/1N/003-G
FRBmM-B13/1N/03-G
FRBmM-B16/1N/03-G
FRBmM-B20/1N/03-G
FRBmM-B25/1N/03-G
FRBmM-B32/1N/03-G
FRBmM-B40/1N/03-G
170710
170711
170712
170713
170714
170715
170555
170556
170557
170558
170559
170560
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-C13/1N/003-G
FRBmM-C16/1N/003-G
FRBmM-C20/1N/003-G
FRBmM-C25/1N/003-G
FRBmM-C32/1N/003-G
FRBmM-C40/1N/003-G
FRBmM-C13/1N/03-G
FRBmM-C16/1N/03-G
FRBmM-C20/1N/03-G
FRBmM-C25/1N/03-G
FRBmM-C32/1N/03-G
FRBmM-C40/1N/03-G
170624
170625
170626
170627
170628
170629
170581
170582
170583
170584
170585
170586
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-D13/1N/003-G
FRBmM-D16/1N/003-G
FRBmM-D20/1N/003-G
FRBmM-D13/1N/03-G
FRBmM-D16/1N/03-G
FRBmM-D20/1N/03-G
170650
170651
170652
170869
170870
170871
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic C
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
13/0.3
16/0.3
20/0.3
25/0.3
32/0.3
40/0.3
SG13711
Article No.
Characteristic B
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
13/0.3
16/0.3
20/0.3
25/0.3
32/0.3
40/0.3
SG13711
Type
Designation
Characteristic D
13/0.03
16/0.03
20/0.03
13/0.3
16/0.3
20/0.3
Chapter 3.1.1. – 18
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type G/A
10 kA, 1+N-pole
Surge current-proof 3 kA, sensitive to residual pulsating DC, type G/A (ÖVE E 8601)
In/IΔn
(A)
SG13711
Units
per
package
FRBmM-B13/1N/003-G/A
FRBmM-B16/1N/003-G/A
FRBmM-B20/1N/003-G/A
FRBmM-B25/1N/003-G/A
FRBmM-B32/1N/003-G/A
FRBmM-B40/1N/003-G/A
170716
170717
170528
170529
170530
170531
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-C13/1N/003-G/A
FRBmM-C16/1N/003-G/A
FRBmM-C20/1N/003-G/A
FRBmM-C25/1N/003-G/A
FRBmM-C32/1N/003-G/A
FRBmM-C40/1N/003-G/A
170630
170631
170632
170633
170634
170635
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-D13/1N/003-G/A
FRBmM-D16/1N/003-G/A
FRBmM-D20/1N/003-G/A
170653
170654
170655
1/60
1/60
1/60
Characteristic C
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
SG13711
Article No.
Characteristic B
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
40/0.03
SG13711
Type
Designation
Characteristic D
13/0.03
16/0.03
20/0.03
Chapter 3.1.1. – 19
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Specifications | Combined RCD/MCB Devices FRBmM, 1+N-pole
Description
• Combined RCD/MCB device
• Type -A: Protects against special forms of residual pulsating DC
• Line voltage-independent tripping
which have have not been smoothed.
• Compatible with standard busbar
• Type -G: High reliability against unwanted tripping. Compulsory
• Twin-purpose terminal (lift/open-mouthed) above and below
for any circuit where personal injury or damage to property may
• Busbar positioning optionally above or below
occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Free terminal space despite installed busbar
• Guide for secure terminal connection
• Switching toggle (MCB component) in colour designating the rated
current
• Contact position indicator red - green
• Comprehensive range of accessories suitable for subsequent installation
• Nameplate
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g.
damply or dusty environment), it's recommended to test in shorter
intervals (e.g. monthly).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Auxiliary switch for subsequent installation
Tripping signal switch for subsequent installation
Shunt trip release
Tripping module
Switching interlock
Screws lock 2MU
ZP-IHK
ZP-WHK
ZP-NHK
ZP-ASA/..
Z-KAM
IS/SPE-1TE
286052
286053
248437
248438, 248439
248294
101911
221954800
Connection diagram
1+N-pole
Dimensions (mm)
Chapter 3.1.1. – 20
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Technical Data
FRBmM, 1+N-pole
Electrical
Design according to
Current test marks as printed onto the device
Tripping line voltage-independent
Type G
Rated voltage
Rated tripping current
Rated non-tripping current
Sensitivity
Selectivity class
Rated breaking capacity
Rated current
Rated impulse withstand voltage
Characteristic
Maximum back-up fuse (short circuit)
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection switch
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Climatic conditions
IEC/EN 61009
Un
IΔn
IΔno
Icn
Uimp
instantaneous 250A (8/20µs), surge current-proof
10 ms delay 3kA (8/20µs), surge current-proof
240V AC, 50Hz
10, 30, 100, 300 mA
0.5 IΔn
AC and pulsating DC
3
10 kA
2 - 40 A
4 kV (1.2/50µs)
B, C, D
100 A gL (>10 kA)
≥ 4,000 operating cycles
≥ 10,000 operating cycles
45 mm
80 mm
35 mm (2MU)
3-position DIN rail clip, permits removal from existing busbar system
IP20
IP40
open mouthed/lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
1 - 25 mm2
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Chapter 3.1.1. – 21
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Load Capacity FRBmM-../1N/
Tripping Characteristic FRBmM-../1N/, Characteristics B, C, and D
Effect of ambient temperature (MCB component)
Tripping characteristic according to EN 61009
Ambient temperature
Defined non-tripping current
Defined tripping current
Short Circuit Selectivity FRBmM-../1N/ towards DII-DIV fuse link
In case of short circuit, there is selectivity between the combined RCD/MCB devices FRBmM../1N/ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is , only the MCB will trip, in case of short circuit currents above this value both protective
devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link DII-DIV*)
Short circuit selectivity characteristic C towards fuse link DII-DIV*)
FRBmM DII-DIV gL/gG
FRBmM DII-DIV gL/gG
20
25
35
50
63
In [A]
10
20
25
35
<0.51) 0.7
1.0
2.9
6.9
10.02) 10.02) 10.02)
2
<0.51) <0.51) 1.7
6.0
10.02) 10.02) 10.02) 10.02) 10.02)
10
0.6
0.9
1.9
3.3
7.0
10.02) 10.02)
4
<0.51) <0.51) 0.7
1.3
4.2
8.5
10.02) 10.02) 10.02)
13
0.5
0.7
1.6
2.8
5.7
9.0
10.02)
6
<0.51) 0.6
1.0
2.9
5.8
10.02) 10.02) 10.02)
10
0.7
1.5
2.6
5.3
9.0
10.02)
In [A]
6
16
20
25
32
40
10
16
0.7
80
100
16
50
63
80
100
1.4
2.4
4.4
7.0
10.02)
1.3
2.2
4.0
6.3
10.02)
13
1.4
2.3
4.6
7.6
10.02)
16
1.2
1.8
3.4
5.5
10.02)
1.2
1.7
3.1
5.0
10.02)
1.6
2.9
4.6
10.02)
2.3
3.4
7.7
2.9
6.2
1.3
2.1
3.8
5.8
10.02)
2.0
3.5
5.2
9.5
20
3.1
4.5
8.1
25
<0.5
32
40
1)
Selectivity limit current Is under 0.5 kA
2) Selectivity limit current I = rated breaking capacity I of the RCD/MCB device Short circuit selectivity characteristic D towards fuse link DII-DIV*)
s
cn
Darker areas: no selectivity
FRBmM DII-DIV gL/gG
In [A]
10
20
25
35
50
2
<0.51) <0.51) 1.0
1.8
6.5
10.02) 10.02) 10.02) 10.02)
4
<0.51) 0.8
1.3
3.8
9.0
10.02) 10.02) 10.02)
6
0.6
0.9
2.3
4.7
10.02) 10.02) 10.02)
0.7
1.5
2.6
5.5
9.4
10.02)
1.4
2.2
4.4
7.0
10.02)
16
2.0
3.7
5.5
10.02)
20
1.9
3.4
5.0
10.02)
10
13
Chapter 3.1.1. – 22
16
63
80
100
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Short Circuit Selectivity FRBmM-../1N/ towards D01-D03 fuse link
In case of short circuit, there is selectivity between the combined RCD/MCB devices FRBmM../1N/ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is , only the MCB will trip, in case of short circuit currents above this value both protective
devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link D01-D03*)
FRBmM D01-D03 gL/gG
FRBmM D01-D03 gL/gG
In [A]
10
16
<0.51)
6
10
13
20
Short circuit selectivity characteristic C towards fuse link D01-D03*)
25
35
In [A]
10
10.02)
2
<0.51)
4
<0.51) <0.51) <0.51) 0.9
50
63
80
100
10.02)
0.5
0.8
2.4
8.2
10.02)
0.5
0.8
1.6
3.7
6.0
10.02) 10.02)
6
0.6
16
16
0.5
<0.51)
20
0.5
25
35
50
63
80
100
2.4
10.02)
10.02)
10.02)
10.02)
10.02)
3.4
9.5
10.02) 10.02) 10.02)
<0.51)
0.8
2.3
6.5
10.02) 10.02) 10.02)
<0.5
0.6
1.3
2.9
4.5
8.9
10.02)
0.7
1.4
3.0
4.7
9.0
10.02)
0.6
1.2
2.6
3.9
7.0
10.02)
10
13
1.2
2.5
3.9
7.6
10.02)
20
1.2
2.5
3.6
6.2
10.02)
25
1.2
2.3
3.3
5.7
10.02)
16
1.0
2.1
3.0
5.5
10.02)
3.1
5.1
10.02)
20
1.0
2.0
2.7
5.0
10.02)
2.8
4.5
9.5
25
1.9
2.6
4.5
10.02)
2.1
3.4
10.02)
3.0
8.7
32
2.3
40
32
40
Short circuit selectivity characteristic D towards fuse link D01-D03*)
FRBmM D01-D03 gL/gG
In [A]
10
16
20
25
35
50
2
<0.51) 0.5
0.8
1.2
5.0
10.02) 10.02) 10.02) 10.02)
4
<0.51) 0.7
1.0
3.0
10.02) 10.02) 10.02) 10.02)
6
0.5
0.8
1.9
5.5
10.02) 10.02) 10.02)
0.6
1.3
2.9
4.7
9.2
10.02)
1.2
2.5
3.8
7.0
10.02)
16
2.3
3.2
5.5
10.02)
20
2.2
3.0
3.9
10.02)
10
13
63
80
100
1)
Selectivity limit current Is under 0.5 kA
Selectivity limit current Is = rated breaking capacity Icn of the RCD/MCB device
Darker areas: no selectivity
2)
Chapter 3.1.1. – 23
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Short Circuit Selectivity FRBmM-../1N/ towards NH-00 fuse link
In case of short circuit, there is selectivity between the combined RCD/MCB devices FRBmM../1N/ and the upstream fuses up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is , only the MCB will trip, in case of short circuit currents above this value both protective
devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link NH-00*)
FRBmM
NH-00 gL/gG
In [A] 16
<0.51)
20
25
FRBmM
32
35
40
63
80
100 125 160
10.02)
10.02)
10.02)
2
<0.51)
7.3
10.02) 10.02) 10.02)
4
6
0.8
1.4
2.2
3.3
7.0
10
<0.51) 0.7
0.9
1.5
2.1
3.4
4.3
13
<0.51)
0.5
16
NH-00 gL/gG
50
10.02)
6
Short circuit selectivity characteristic C towards fuse link NH-00*)
10.02)
10.02)
10.02)
In [A] 16
20
25
32
35
40
50
63
80
100 125 160
2.6
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02) 10.02) 10.02)
<0.51) <0.51) 0.9
1.8
3.2
4.8
8.7
10.02) 10.02) 10.02) 10.02) 10.02)
<0.51)
0.7
1.3
2.2
3.3
5.9
8.0
10.02) 10.02) 10.02) 10.02)
0.5
0.8
1.2
1.7
2.7
3.4
5.5
10.02) 10.02) 10.02)
0.6
0.6
0.8
1.4
1.8
2.8
3.6
5.7
10.02)
<0.51)
0.6
0.7
1.2
1.5
2.4
3.0
4.5
10.02) 10.02) 10.02)
10
10.02)
13
1.1
1.5
2.3
2.9
4.7
10.02) 10.02) 10.02)
20
0.7
1.1
1.5
2.2
2.8
4.2
9.2
10.02)
25
0.7
1.1
1.4
2.1
2.6
4.0
8.2
10.02) 10.02)
16
1.0
1.3
1.8
2.3
3.7
8.7
10.02) 10.02)
10.02)
20
0.9
1.1
1.7
2.2
3.4
8.0
10.02) 10.02)
10.02)
25
1.6
2.1
3.2
7.2
10.02) 10.02)
1.7
2.6
5.3
9.0
10.02)
2.4
4.5
7.5
10.0
32
1.0
1.4
2.0
40
2.5
3.7
7.1
10.02)
2.3
3.4
6.2
8.8
32
40
Short circuit selectivity characteristic D towards fuse link NH-00*)
FRBmM
NH-00 gL/gG
In [A] 16
20
25
32
35
40
50
2
<0.51) 0.6
1.3
2.5
4.7
7.7
10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
4
<0.51) 0.5
0.9
1.6
2.8
4.3
9.2
10.02) 10.02) 10.02) 10.02) 10.02)
<0.51) 0.7
1.2
1.8
2.6
4.9
7.0
10.02) 10.02) 10.02) 10.02)
0.5
0.8
1.2
1.7
2.7
3.5
5.6
10.02) 10.02) 10.02)
1.1
1.5
2.3
2.9
4.5
10.02) 10.02) 10.02)
1.4
2.0
2.6
3.9
8.0
10.02) 10.02)
1.9
2.4
3.6
7.0
10.02) 10.02)
6
10
13
16
20
63
80
100 125 160
1)
Selectivity limit current Is under 0.5 kA
Selectivity limit current Is = rated breaking capacity Icn of the RCD/MCB device
Darker areas: no selectivity
2)
Chapter 3.1.1. – 24
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Let-through Energy FRBmM-../1N/
Let-through energy FRBmM, characteristic C, 1+N-pole
Let through energy I2t [A2 sec]
Let through energy I2t [A2 sec]
Let-through energy FRBmM, characteristic B, 1+N-pole
Prospective short-circuit current [A]
Prospective short-circuit current [A]
Let through energy I2t [A2 sec]
Let-through energy FRBmM, characteristic D, 1+N-pole
Prospective short-circuit current [A]
Chapter 3.1.1. – 25
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM, FRBm6, 2-pole
SG14011
• High-quality residual current device / miniature circuit breaker combination, line voltage-independent
• Contact position indicator red - green
• Fault current tripping indicator white - blue
• Guide for secure terminal connection
• 3-position DIN rail clip, permits removal from existing busbar system
• Comprehensive range of accessories suitable for subsequent installation
• Wide variety of rated tripping currents
• Rated currents up to 40 A
• Tripping characteristics B, C
• Rated breaking capacity 10 kA and 6 kA
Chapter 3.1.1. – 26
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type AC
10 kA, 2-pole
Conditionally surge current-proof 250 A, type AC
In/IΔn
(A)
SG14011
Article No.
Units
per
package
FRBmM-B10/2/003
FRBmM-B13/2/003
FRBmM-B16/2/003
FRBmM-B20/2/003
FRBmM-B25/2/003
FRBmM-B10/2/03
FRBmM-B13/2/03
FRBmM-B16/2/03
FRBmM-B20/2/03
FRBmM-B25/2/03
170872
170873
170874
170875
170876
170837
170838
170839
170840
170841
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-C6/2/003
FRBmM-C10/2/003
FRBmM-C13/2/003
FRBmM-C16/2/003
FRBmM-C20/2/003
FRBmM-C25/2/003
FRBmM-C6/2/03
FRBmM-C10/2/03
FRBmM-C13/2/03
FRBmM-C16/2/03
FRBmM-C20/2/03
FRBmM-C25/2/03
170721
170722
170723
170724
170725
170726
170853
170854
170855
170856
170857
170858
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic B
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
10/0.3
13/0.3
16/0.3
20/0.3
25/0.3
SG14011
Type
Designation
Characteristic C
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0,03
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
25/0.3
Chapter 3.1.1. – 27
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type A
10 kA, 2-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG14011
Article No.
Units
per
package
FRBmM-B10/2/003-A
FRBmM-B13/2/003-A
FRBmM-B16/2/003-A
FRBmM-B20/2/003-A
FRBmM-B25/2/003-A
FRBmM-B10/2/01-A
FRBmM-B13/2/01-A
FRBmM-B16/2/01-A
FRBmM-B20/2/01-A
FRBmM-B50/2/01-A
FRBmM-B10/2/03-A
FRBmM-B13/2/03-A
FRBmM-B16/2/03-A
FRBmM-B20/2/03-A
FRBmM-B25/2/03-A
170879
170880
170881
170882
170883
170803
170804
170805
170806
170807
170844
170845
170846
170847
170848
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-C6/2/003-A
FRBmM-C10/2/003-A
FRBmM-C13/2/003-A
FRBmM-C16/2/003-A
FRBmM-C20/2/003-A
FRBmM-C25/2/003-A
FRBmM-C6/2/01-A
FRBmM-C10/2/01-A
FRBmM-C13/2/01-A
FRBmM-C16/2/01-A
FRBmM-C20/2/01-A
FRBmM-C25/2/01-A
FRBmM-C6/2/03-A
FRBmM-C10/2/03-A
FRBmM-C13/2/03-A
FRBmM-C16/2/03-A
FRBmM-C20/2/03-A
FRBmM-C25/2/03-A
170785
170786
170787
170788
170789
170790
170819
170820
170821
170822
170823
170824
170863
170864
170865
170866
170867
170730
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic B
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
10/0.3
13/0.3
16/0.3
20/0.3
20/0,3
SG14011
Type
Designation
Characteristic C
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
6/0.3
10/0.3
13/0.3
16/0.3
20/0.3
25/0.3
Chapter 3.1.1. – 28
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type Super A
10 kA, 2-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, short time delayed, type Super A
In/IΔn
(A)
SG14011
Article No.
Units
per
package
FRBmM-B10/2/003-LiA
FRBmM-B13/2/003-LiA
FRBmM-B16/2/003-LiA
FRBmM-B20/2/003-LiA
FRBmM-B25/2/003-LiA
FRBmM-B10/2/01-LiA
FRBmM-B13/2/01-LiA
FRBmM-B16/2/01-LiA
FRBmM-B20/2/01-LiA
FRBmM-B25/2/01-LiA
170886
170887
170888
170889
170890
170810
170811
170812
170813
170814
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
FRBmM-C6/2/003-LiA
FRBmM-C10/2/003-LiA
FRBmM-C13/2/003-LiA
FRBmM-C16/2/003-LiA
FRBmM-C20/2/003-LiA
FRBmM-C25/2/003-LiA
FRBmM-C6/2/01-LiA
FRBmM-C10/2/01-LiA
FRBmM-C13/2/01-LiA
FRBmM-C16/2/01-LiA
FRBmM-C20/2/01-LiA
FRBmM-C25/2/01-LiA
170795
170796
170797
170798
170799
170800
170829
170830
170831
170832
170833
170834
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic B
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
SG14011
Type
Designation
Characteristic C
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
Chapter 3.1.1. – 29
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm6 type AC
6 kA, 2-pole
Conditionally surge current-proof 250 A, type AC
In/IΔn
(A)
SG14011
Article No.
Units
per
package
FRBm6-B32/2/003
FRBm6-B40/2/003
FRBm6-B32/2/03
FRBm6-B40/2/03
170877
170878
170842
170843
1/60
1/60
1/60
1/60
FRBm6-C32/2/003
FRBm6-C40/2/003
FRBm6-C32/2/03
FRBm6-C40/2/03
170727
170728
170859
170860
1/60
1/60
1/60
1/60
Characteristic B
32/0.03
40/0.03
32/0.3
40/0.3
SG14011
Type
Designation
Characteristic C
32/0.03
40/0.03
32/0.3
40/0.3
Chapter 3.1.1. – 30
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm6 type A
6 kA, 2-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG14011
Article No.
Units
per
package
FRBm6-B32/2/003-A
FRBm6-B40/2/003-A
FRBm6-B32/2/01-A
FRBm6-B40/2/01-A
FRBm6-B32/2/03-A
FRBm6-B40/2/03-A
170884
170885
170808
170809
170849
170850
1/60
1/60
1/60
1/60
1/60
1/60
FRBm6-C32/2/003-A
FRBm6-C40/2/003-A
FRBm6-C32/2/01-A
FRBm6-C40/2/01-A
FRBm6-C32/2/03-A
FRBm6-C40/2/03-A
170791
170792
170825
170826
170731
170732
1/60
1/60
1/60
1/60
1/60
1/60
Characteristic B
32/0.03
40/0.03
32/0.1
40/0.1
32/0.3
40/0.3
SG14011
Type
Designation
Characteristic C
32/0.03
40/0.03
32/0.1
40/0.1
32/0.3
40/0.3
Chapter 3.1.1. – 31
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm6 type Super A
6 kA, 2-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, short time delayed, type Super A
In/IΔn
(A)
SG14011
Article No.
Units
per
package
FRBm6-B32/2/003-LiA
FRBm6-B40/2/003-LiA
FRBm6-B32/2/01-LiA
FRBm6-B40/2/01-LiA
170891
170718
170815
170816
1/60
1/60
1/60
1/60
FRBm6-C32/2/003-LiA
FRBm6-C40/2/003-LiA
FRBm6-C32/2/01-LiA
FRBm6-C40/2/01-LiA
170801
170802
170835
170836
1/60
1/60
1/60
1/60
Characteristic B
32/0.03
40/0.03
32/0.1
40/0.1
SG14011
Type
Designation
Characteristic C
32/0.03
40/0.03
32/0.1
40/0.1
Chapter 3.1.1. – 32
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Specifications | Combined RCD/MCB Devices FRBmM, FRBm6, 2-pole
Description
• Combined RCD/MCB device
• Type -A: Protects against special forms of residual pulsating DC
• Line voltage-independent tripping
which have have not been smoothed.
• Compatible with standard busbar
• Type -Super A: High reliability against unwanted tripping.
• Twin-purpose terminal (lift/open-mouthed) above and below
Compulsory for any circuit where personal injury or damage to
• Busbar positioning optionally above or below
property may occur in case of unwanted tripping.
• Free terminal space despite installed busbar
• Guide for secure terminal connection
• Switching toggle (MCB component) in colour designating the rated
current
• Contact position indicator red - green
• Fault current tripping indicator white - blue
• Comprehensive range of accessories suitable for subsequent installation
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g.
damply or dusty environment), it's recommended to test in shorter
intervals (e.g. monthly).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Auxiliary switch for subsequent installation
Shunt trip release
Switching interlock
Screws lock 2MU
ZP-IHK
ZP-WHK
ZP-NHK
ZP-ASA/..
IS/SPE-1TE
286052
286053
248437
248438, 248439
101911
221954800
Connection diagram
2-pole
Dimensions (mm)
Chapter 3.1.1. – 33
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Technical Data
FRBmM, FRBm6, 2-pole
Electrical
Design according to
Current test marks as printed onto the device
Tripping line voltage-independent
Type Super A
Rated voltage
Rated tripping current
Rated non-tripping current
Sensitivity
Selectivity class
Rated breaking capacity
FRBmM
FRBm6
Rated current
Rated impulse withstand voltage
Characteristic
Maximum back-up fuse (short circuit)
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection switch
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Climatic conditions
IEC/EN 61009
Un
IΔn
IΔno
instantaneous 250A (8/20µs), surge current-proof
10 ms delay, surge current-proof
240V AC, 50Hz
30, 100, 300 mA
0.5 IΔn
AC and pulsating DC
3
Icn
Uimp
10 kA
6 kA
6 - 40 A
4 kV (1.2/50µs)
B, C
100 A gL (>10 kA)
≥ 4,000 operating cycles
≥ 10,000 operating cycles
45 mm
80 mm
35 mm (2MU)
3-position DIN rail clip, permits removal from existing busbar system
IP20
IP40
open mouthed/lift terminals
finger and hand touch safe, VBG4, ÖVE-EN 6
1 - 25 mm2
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Chapter 3.1.1. – 34
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
FRBmM: Influence of ambient temperature on load carrying capacity
• Values = max. allowed current in Ampere at the specific temperature
• Temperature factor (%/K) = 0,5
6
10
13
16
20
Ambient temperature / °C
-40
-30
-25
-20
8,1
7,8
7,7
7,5
13,5
13,0
12,8
12,5
17,6
16,9
16,6
16,3
21,6
20,8
20,4
20,0
27,0
26,0
25,5
25,0
-10
7,2
12,0
15,6
19,2
24,0
0
6,9
11,5
15,0
18,4
23,0
10
6,6
11,0
14,3
17,6
22,0
20
6,3
10,5
13,7
16,8
21,0
30
6,0
10,0
13,0
16,0
20,0
40
5,7
9,5
12,4
15,2
19,0
FRBm6: Influence of ambient temperature on load carrying capacity
• Values = max. allowed current in Ampere at the specific temperature
• Temperature factor (%/K) = 0,5
25
32
40
Ambient temperature / °C
-40
-30
-25
-20
33,8
32,5
31,9
31,3
43,2
41,6
40,8
40,0
54,0
52,0
51,0
50,0
-10
30,0
38,4
48,0
0
28,8
36,8
46,0
10
27,5
35,2
44,0
20
26,3
33,6
42,0
30
25,0
32,0
40,0
40
23,8
30,4
38,0
Tripping Characteristic FRBm., Characteristics B and C
Chapter 3.1.1. – 35
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Short Circuit Selectivity FRBmM towards Neozed1) / Diazed2) / NH003)
Short circuit currents in kA, Rated currents of fuses in A
Short circuit selectivity FRBmM towards fuse link Neozed
1)
Short circuit selectivity FRBmM towards fuse link Diazed
1)
FRBm
Diazed 2)
16
20
25
32
35
50
63
80
100
10
B10
<0,5
0,5
0,9
1,8
2,9
5,6
10
10
10
10
10
B13
<0,5
0,5
0,8
1,5
2,4
4,5
10
10
10
10
10
B16
0,5
0,8
1,3
2
3,4
8
10
10
9,2
10
B20
0,7
1,3
1,9
3,1
7,1
10
10
10
10
C10
<0,5
0,5
0,8
1,5
2,4
4,4
10
10
10
<0,5
0,5
0,8
1,4
2,3
4,2
10
10
10
<0,5
0,7
1,2
1,9
3,2
7,6
10
10
0,7
1,2
1,8
2,9
6,5
9,7
10
FRBm
Neozed
20
25
32
35
40
50
63
80
100
B10
<0,5 0,5
0,9
2
2,3
3,7
8
10
10
B13
<0,5 0,5
0,8
1,7
1,9
3
6
10
B16
0,5
0,7
1,5
1,7
2,4
4,4
6,8
0,7
1,4
1,5
2,2
3,9
6
C10
<0,5 0,5
0,8
1,7
1,9
3
6,1
10
C13
<0,5 0,5
16
B20
0,7
1,6
1,8
2,8
5,5
9,5
10
10
C13
C16
<0,5 0,7
1,3
1,5
2,2
4
6,2
10
10
C16
C20
0,6
1,3
1,4
2,1
3,7
5,6
8,5
10
C20
Short circuit selectivity FRBmM towards fuse link NH00
FRBm
NH00
16
3)
3)
20
25
32
35
40
50
63
80
100 125 160
B10
<0,5 <0,5 0,8 1,5 2,3 3,2 5,7 9,1 10
10
10
10
B13
<0,5 <0,5 0,8 1,3 1,9 2,7 4,4 6,5 10
10
10
10
10
10
10
10
10
10
B16
B20
<0,5 0,7 1,1 1,6 2,2 3,4 4,8 8
0,6 1
1,4 2
3,1 4,3 7
C10
<0,5 <0,5 0,7 1,3 1,9 2,7 4,5 6,9 10
10
10
10
C13
<0,5 <0,5 0,7 1,2 1,8 2,5 4,1 6,1 10
10
10
10
C16
C20
2)
<0,5 0,6 1
10
10
10
0,6 0,9 1,4 1,9 2,9 4,1 6,5 10
1,5 2
3,1 4,4 7,5
10
10
no selectivity
1)
2)
3)
SIEMENS Type 5SE2; Size: D01, D02, D03; Operating class gG; Rated voltage: AC 400 V/DC 250 V
SIEMENS Type 5SB2, 5SB4, 5SC2; Size: DII, DIII, DIV; Operating class gG; Rated voltage: AC 500 V/DC 500 V
SIEMENS Type 3NA3 8, 3NA6 8, 3NA7 8; Size: 000, 00; Operating class gG; Rated voltage: AC 500 V/DC 250 V
Chapter 3.1.1. – 36
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Short Circuit Selectivity FRBm6 towards Neozed1) / Diazed2) / NH003)
Short circuit currents in kA, Rated currents of fuses in A
Short circuit selectivity FRBm6 towards fuse link Neozed
FRBm6 Neozed
16
20
1)
FRBm6 Diazed 2)
25
32
35
40
50
63
80
100
1,2
1,3
1,8
3,1
4,7
6
6
B25
1,2
1,7
2,7
3,8
5,5
6
B32
1,3
1,7
2,2
2,7
4,2
B40
1,3
1,8
2,8
3,9
5,6
6
C25
1,2
1,7
2,6
3,6
5,1
6
C32
1,3
1,9
3,3
3,2
5,8
C40
B32
B40
C25
1,1
C32
C40
Short circuit selectivity FRBm6 towards fuse link NH00
16
Short circuit selectivity FRBm6 towards fuse link Diazed
1)
B25
FRBm6 NH00
1)
16
20
25
32
35
50
63
80
100
1,1
1,5
2,4
5,5
6
6
1,4
2,1
4,3
6
6
1,4
2,4
2,9
5,1
1,5
2,3
4,4
6
6
1,4
2,2
4,1
5,6
6
1,6
2,8
3,6
6
1,1
3)
3)
20
25
32
35
40
50
63
80
100 125 160
B25
0,9 1,2 1,6 2,4 3,4 5,5 6
6
6
B32
1,1 1,4 2,1 2,9 4,3 6
6
6
1,4 1,9 2,8 4,1 6
6
B40
C25
0,9 1,2 1,6 2,3 3
C32
C40
4,6 6
6
6
1,1 1,5 2,1 2,8 4,3 6
6
6
1,5 2,1 3,1 5,4 6
6
no selectivity
1)
2)
3)
SIEMENS Type 5SE2; Size: D01, D02, D03; Operating class gG; Rated voltage: AC 400 V/DC 250 V
SIEMENS Type 5SB2, 5SB4, 5SC2; Size: DII, DIII, DIV; Operating class gG; Rated voltage: AC 500 V/DC 500 V
SIEMENS Type 3NA3 8, 3NA6 8, 3NA7 8; Size: 000, 00; Operating class gG; Rated voltage: AC 500 V/DC 250 V
Chapter 3.1.1. – 37
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Let-through Energy FRBm.-../2/
Let-through energy FRBmM, characteristic B, 2-pole
Let-through energy FRBmM, characteristic C, 2-pole
Let-through energy FRBm6, characteristic B, 2-pole
Let-through energy FRBm6, characteristic C, 2-pole
Chapter 3.1.1. – 38
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM, 3-pole
SG49512
• High-quality residual current device / miniature circuit breaker combination, line voltage-independent
• Contact position indicator red - green
• Fault current tripping indicator white - blue
• Guide for secure terminal connection
• 3-position DIN rail clip, permits removal from existing busbar system
• Comprehensive range of accessories suitable for subsequent installation
• Wide variety of rated tripping currents
• Rated currents up to 32 A
• Tripping characteristics B, C, D
• Rated breaking capacity 10 kA
Chapter 3.1.1. – 39
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBmM type A
10 kA, 3-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG49512
Units
per
package
FRBmM-B10/3/003-A
FRBmM-B13/3/003-A
FRBmM-B16/3/003-A
FRBmM-B20/3/003-A
FRBmM-B10/3/01-A
FRBmM-B13/3/01-A
FRBmM-B16/3/01-A
FRBmM-B20/3/01-A
170733
170734
170735
170736
170780
170781
170782
170783
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
FRBmM-C6/3/003-A
FRBmM-C10/3/003-A
FRBmM-C13/3/003-A
FRBmM-C16/3/003-A
FRBmM-C20/3/003-A
FRBmM-C25/3/003-A
FRBmM-C32/3/003-A
FRBmM-C6/3/01-A
FRBmM-C10/3/01-A
FRBmM-C13/3/01-A
FRBmM-C16/3/01-A
FRBmM-C20/3/01-A
FRBmM-C25/3/01-A
FRBmM-C32/3/01-A
170737
170738
170739
170740
170741
170772
170773
170742
170743
170744
170745
170746
170747
170748
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
FRBmM-D6/3/003-A
FRBmM-D10/3/003-A
FRBmM-D13/3/003-A
FRBmM-D16/3/003-A
FRBmM-D20/3/003-A
FRBmM-D25/3/003-A
FRBmM-D6/3/01-A
FRBmM-D10/3/01-A
FRBmM-D13/3/01-A
FRBmM-D16/3/01-A
FRBmM-D20/3/01-A
FRBmM-D25/3/01-A
170774
170775
170776
170777
170778
170779
170749
170750
170751
170752
170753
170754
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
Characteristic C
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
32/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
32/0.1
SG49512
Article No.
Characteristic B
10/0.03
13/0.03
16/0.03
20/0.03
10/0.1
13/0.1
16/0.1
20/0.1
SG49512
Type
Designation
Characteristic D
6/0.03
10/0.03
13/0.03
16/0.03
20/0.03
25/0.03
6/0.1
10/0.1
13/0.1
16/0.1
20/0.1
25/0.1
Chapter 3.1.1. – 40
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Specifications | Combined RCD/MCB Devices FRBmM, 3-pole
Description
• Combined RCD/MCB device
• Type -A: Protects against special forms of residual pulsating DC
• Line voltage-independent tripping
which have have not been smoothed.
• Compatible with standard busbar
• Type -G: High reliability against unwanted tripping. Compulsory
• Twin-purpose terminal (lift/open-mouthed) above and below
for any circuit where personal injury or damage to property may
• Busbar positioning optionally above or below
occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Free terminal space despite installed busbar
• Guide for secure terminal connection
• Switching toggle (MCB component) in colour designating the rated
current
• Contact position indicator red - green
• Fault current tripping indicator white - blue
• Comprehensive range of accessories suitable for subsequent installation
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g.
damply or dusty environment), it's recommended to test in shorter
intervals (e.g. monthly).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Auxiliary switch for subsequent installation
Tripping signal contact for subsequent installation
Shunt trip release
Undervoltage release
Switching interlock
Screws lock 4MU
ZP-IHK
ZP-WHK
ZP-NHK
ZP-ASA/..
Z-USA
Z-USD
IS/SPE-1TE
286052
286053
248437
248438, 248439
258288, 248289, 248290
248292, 248291
101911
221953900
Connection diagram
3-pole
Dimensions (mm)
Chapter 3.1.1. – 41
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Technical Data
FRBmM, 3-pole
Electrical
Design according to
Current test marks as printed onto the device
Tripping line voltage-independent
Type G
Rated voltage
Rated tripping current
Rated non-tripping current
Sensitivity
Selectivity class
Rated breaking capacity
Rated current
Rated impulse withstand voltage
Characteristic
Maximum back-up fuse (short circuit)
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection switch
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Climatic conditions
IEC/EN 61009
Un
IΔn
IΔno
Icn
Uimp
instantaneous 250A (8/20µs), surge current-proof
10 ms delay, surge current-proof
240/415V AC, 50Hz
30, 100 mA
0.5 IΔn
AC and pulsating DC
3
10 kA
6 - 32 A
4 kV (1.2/50µs)
B, C, D
100 A gL (>10 kA)
≥ 4,000 operating cycles
≥ 10,000 operating cycles
45 mm
80 mm
70 mm (4MU)
3-position DIN rail clip, permits removal from existing busbar system
IP20
IP40
open mouthed/lift terminals
finger and hand touch safe, VBG4, ÖVE-EN 6
1 - 25 mm2
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Tripping Characteristic FRBmM, Characteristics B, C and D
Tripping characteristic
acc. to EN 61009
conventional non-tripping current
conventional tripping current
Chapter 3.1.1. – 42
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Short-Circuit Selectivity
Between FRBmM, 3-pole, characteristic B and NZM 1/2
NZM
FRBmM-B
Selectivity-limit current Is [kA] for selectivity between FRBmM-.../B and NZM (overload and short-circuit release unit NZM at max. value).
NZM...1-A...
NZM...2-A...
In [A]
Icu = 25(36)(50)(100) kA bei Ue = 400/415 V
Icu = 25(36)(50)(150) kA bei Ue = 400/415 V
FRBmM-B
40
50
63
80
100
125
40
50
63
80
100
125
160
200
250
10
1.2
1.5
2
2
4
10
1
1.5
2.5
3
10
10
10
10
10
13
1
1.5
2
2
4
10
1
1.2
2
3
10
10
10
10
10
16
1
1.2
1.5
2
3
8
1
1.2
1.5
2.5
10
10
10
10
10
20
0.8
1.2
1.5
1.5
3
8
1
1.2
1.5
1.5
10
10
10
10
10
Between FRBmM, 3-pole, characteristic C and NZM 1/2
NZM
FRBmM-C
Selectivity-limit current Is [kA] for selectivity between FRBmM-.../C and NZM (overload and short-circuit release unit NZM at max. value).
NZM...1-A...
NZM...2-A...
In [A]
Icu = 25(36)(50)(100) kA bei Ue = 400/415 V
Icu = 25(36)(50)(150) kA bei Ue = 400/415 V
FRBmM-C
40
50
63
80
100
125
40
50
63
80
100
125
160
200
250
6
1.2
2
2.5
3
5
10
1.2
1.5
2.5
3
10
10
10
10
10
10
1.2
1.5
2
2
4
10
1
1.5
2.5
3
10
10
10
10
10
13
1
1.5
2
2
4
10
1
1.2
2
3
10
10
10
10
10
16
1
1.2
1.5
2
3
8
1
1.2
1.5
2.5
10
10
10
10
10
20
0.8
1.2
1.5
1.5
3
8
1
1.2
1.5
1.5
10
10
10
10
10
25
0.7
1.2
1.5
1.5
3
7
0.8
1
1.5
2
10
10
10
10
10
32
-
1.2
1
1.5
2
6
-
1
1.5
2
6
6
6
6
6
Between FRBmM, 3-pole, characteristic D and NZM 1/2
NZM
FRBmM-D
Selectivity-limit current Is [kA] for selectivity between FRBmM-.../D and NZM (overload and short-circuit release unit NZM at max. value).
NZM...1-A...
NZM...2-A...
In [A]
Icu = 25(36)(50)(100) kA bei Ue = 400/415 V
FRBmM-D
40
50
63
80
100
125
Icu = 25(36)(50)(150) kA bei Ue = 400/415 V
40
50
63
80
100
125
160
200
250
6
1.2
2
2.5
3
5
10
1.2
1.5
2.5
3
10
10
10
10
10
10
1.2
1.5
2
2
4
10
1
1.5
2.5
3
10
10
10
10
10
13
1
1.5
2
2
4
10
1
1.2
2
3
10
10
10
10
10
16
1
1.2
1.5
2
3
8
1
1.2
1.5
2.5
10
10
10
10
10
20
0.8
1.2
1.5
1.5
3
8
1
1.2
1.5
1.5
10
10
10
10
10
25
0.7
1.2
1.5
1.5
3
7
0.8
1
1.5
2
10
10
10
10
10
Chapter 3.1.1. – 43
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Back-up Protection FRBmM 3-pole / NZMB(C)(N)(H)1
FRBmM 3-pole / NZMB1
FRBmM 3-pole / NZMC1
Ue = 133 / 230 V
Ue = 133 / 230 V
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMC1
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMB1
In [A]
Type B
Type C
Type D
In [A]
Type B
Type C
Type D
6
-
25kA
25kA
6
-
36kA
36kA
10
25kA
25kA
25kA
10
36kA
36kA
36kA
13
25kA
25kA
25kA
13
36kA
36kA
36kA
16
25kA
25kA
25kA
16
36kA
36kA
36kA
20
25kA
25kA
25kA
20
36kA
36kA
36kA
25
-
25kA
25kA
25
-
36kA
36kA
32
-
25kA
-
32
-
36kA
-
FRBmM 3-pole / NZMN1
FRBmM 3-pole / NZMH1
Ue = 133 / 230 V
Ue = 133 / 230 V
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMH1
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMN1
Type D
In [A]
Type B
50kA
50kA
6
-
70kA
70kA
50kA
50kA
10
70kA
70kA
70kA
50kA
50kA
13
70kA
70kA
70kA
50kA
50kA
16
70kA
70kA
70kA
50kA
50kA
50kA
20
70kA
70kA
70kA
-
50kA
50kA
25
-
70kA
70kA
-
50kA
-
32
-
70kA
-
In [A]
Type B
6
-
10
50kA
13
50kA
16
50kA
20
25
32
Type C
Type C
Type D
Back-up Protection FRBmM 3-pole / NZMB(C)(N)(H)2
FRBmM 3-pole / NZMB2
FRBmM 3-pole / NZMC2
Ue = 133 / 230 V
Ue = 133 / 230 V
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMC2
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMB2
Type D
In [A]
Type B
25kA
25kA
6
-
36kA
36kA
25kA
25kA
10
36kA
36kA
36kA
25kA
25kA
13
36kA
36kA
36kA
25kA
25kA
16
36kA
36kA
36kA
25kA
25kA
25kA
20
36kA
36kA
36kA
-
25kA
25kA
25
-
36kA
36kA
-
25kA
-
32
-
36kA
-
In [A]
Type B
6
-
10
25kA
13
25kA
16
25kA
20
25
32
Type C
Type C
FRBmM 3-pole / NZMN2
FRBmM 3-pole / NZMH2
Ue = 133 / 230 V
Ue = 133 / 230 V
Type D
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMH2
FRBmM-In/3/B(C)(D)/003(01)(03) + NZMN2
Type D
In [A]
Type B
50kA
50kA
6
-
70kA
70kA
50kA
50kA
10
70kA
70kA
70kA
50kA
50kA
13
70kA
70kA
70kA
50kA
50kA
16
70kA
70kA
70kA
50kA
50kA
50kA
20
70kA
70kA
70kA
-
50kA
50kA
25
-
70kA
70kA
-
50kA
-
32
-
70kA
-
In [A]
Type B
6
-
10
50kA
13
50kA
16
50kA
20
25
32
Type C
Chapter 3.1.1. – 44
Type C
Type D
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Back-up Protection FRBmM 3-pole / NH00
FRBmM 3-pole / NH00 125A gG/gL
Ue = 133 / 230 V
FRBmM-In/3/B(C)(D)/003(01)(03) + NH00 125A gG/gL
In [A]
Type B
Type C
Type D
6
-
70kA
70kA
10
70kA
70kA
70kA
13
70kA
70kA
70kA
16
70kA
70kA
70kA
20
70kA
70kA
70kA
25
-
70kA
70kA
32
-
70kA
-
Chapter 3.1.1. – 45
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Maximum Let-Through Energy FRBmM 3-pole
Type B
Type C
Type D
Chapter 3.1.1. – 46
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Maximum Let-Through Current FRBmM 3-pole
Type B
Type C
Type D
Chapter 3.1.1. – 47
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm6, FRBm4, 3+N-pole
SG14211
• High-quality residual current device / miniature circuit breaker combination, line voltage-independent
• Contact position indicator red - green
• Fault current tripping indicator white - blue
• Guide for secure terminal connection
• 3-position DIN rail clip, permits removal from existing busbar system
• Comprehensive range of accessories suitable for subsequent installation
• Wide variety of rated tripping currents
• Rated currents up to 32 A
• Tripping characteristics B, C, D
• Rated breaking capacity 6 kA or 4.5 kA
Chapter 3.1.1. – 48
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm6 type AC
6 kA, 3+N-pole
Conditionally surge current-proof 250 A, type AC
In/IΔn
(A)
SG14211
Units
per
package
FRBm6-B13/3N/003
FRBm6-B16/3N/003
FRBm6-B13/3N/01
FRBm6-B16/3N/01
FRBm6-B13/3N/03
FRBm6-B16/3N/03
170985
170986
170896
170897
170943
170944
1/30
1/30
1/30
1/30
1/30
1/30
FRBm6-C6/3N/003
FRBm6-C10/3N/003
FRBm6-C13/3N/003
FRBm6-C16/3N/003
FRBm6-C6/3N/01
FRBm6-C10/3N/01
FRBm6-C13/3N/01
FRBm6-C16/3N/01
FRBm6-C6/3N/03
FRBm6-C10/3N/03
FRBm6-C13/3N/03
FRBm6-C16/3N/03
170989
170990
170991
170992
170900
170901
170902
170903
170947
170948
170949
170950
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
FRBm6-D6/3N/003
FRBm6-D10/3N/003
FRBm6-D13/3N/003
FRBm6-D16/3N/003
FRBm6-D6/3N/01
FRBm6-D10/3N/01
FRBm6-D13/3N/01
FRBm6-D16/3N/01
FRBm6-D6/3N/03
FRBm6-D10/3N/03
FRBm6-D13/3N/03
FRBm6-D16/3N/03
171003
171004
171005
171006
170933
170934
170935
170936
170961
170962
170963
170964
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
Characteristic C
6/0.03
10/0.03
13/0.03
16/0.03
6/0.1
10/0.1
13/0.1
16/0.1
6/0.3
10/0.3
13/0.3
16/0.3
SG14211
Article No.
Characteristic B
13/0.03
16/0.03
13/0.1
16/0.1
13/0.3
16/0.3
SG14211
Type
Designation
Characteristic D
6/0.03
10/0.03
13/0.03
16/0.03
6/0.1
10/0.1
13/0.1
16/0.1
6/0.3
10/0.3
13/0.3
16/0.3
Chapter 3.1.1. – 49
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm6 type A
6 kA, 3+N-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG14211
Units
per
package
FRBm6-B13/3N/003-A
FRBm6-B16/3N/003-A
FRBm6-B13/3N/01-A
FRBm6-B16/3N/01-A
FRBm6-B13/3N/03-A
FRBm6-B16/3N/03-A
170987
170988
170898
170899
170945
170946
1/30
1/30
1/30
1/30
1/30
1/30
FRBm6-C6/3N/003-A
FRBm6-C10/3N/003-A
FRBm6-C13/3N/003-A
FRBm6-C16/3N/003-A
FRBm6-C6/3N/01-A
FRBm6-C10/3N/01-A
FRBm6-C13/3N/01-A
FRBm6-C16/3N/01-A
FRBm6-C6/3N/03-A
FRBm6-C10/3N/03-A
FRBm6-C13/3N/03-A
FRBm6-C16/3N/03-A
170996
170997
170998
170999
170926
170927
170928
170929
170954
170955
170956
170957
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
FRBm6-D6/3N/003-A
FRBm6-D10/3N/003-A
FRBm6-D13/3N/003-A
FRBm6-D16/3N/003-A
FRBm6-D6/3N/01-A
FRBm6-D10/3N/01-A
FRBm6-D13/3N/01-A
FRBm6-D16/3N/01-A
FRBm6-D6/3N/03-A
FRBm6-D10/3N/03-A
FRBm6-D13/3N/03-A
FRBm6-D16/3N/03-A
171008
170892
170893
170894
170938
170939
170940
170941
170966
170967
170968
170969
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
Characteristic C
6/0.03
10/0.03
13/0.03
16/0.03
6/0.1
10/0.1
13/0.1
16/0.1
6/0.3
10/0.3
13/0.3
16/0.3
SG14211
Article No.
Characteristic B
13/0.03
16/0.03
13/0.1
16/0.1
13/0.3
16/0.3
SG14211
Type
Designation
Characteristic D
6/0.03
10/0.03
13/0.03
16/0.03
6/0.1
10/0.1
13/0.1
16/0.1
6/0.3
10/0.3
13/0.3
16/0.3
Chapter 3.1.1. – 50
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm4 type AC
4.5 kA, 3+N-pole
Conditionally surge current-proof 250 A, type AC
In/IΔn
(A)
SG14211
Article No.
Units
per
package
FRBm4-C20/3N/003
FRBm4-C25/3N/003
FRBm4-C32/3N/003
FRBm4-C20/3N/01
FRBm4-C25/3N/01
FRBm4-C32/3N/01
FRBm4-C20/3N/03
FRBm4-C25/3N/03
FRBm4-C32/3N/03
170993
170994
170995
170923
170924
170925
170951
170952
170953
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
FRBm4-D20/3N/003
FRBm4-D20/3N/01
FRBm4-D20/3N/03
171007
170937
170965
1/30
1/30
1/30
Characteristic C
20/0.03
25/0.03
32/0.03
20/0.1
25/0.1
32/0.1
20/0.3
25/0.3
32/0.3
SG14211
Type
Designation
Characteristic D
20/0.03
20/0.1
20/0.3
Chapter 3.1.1. – 51
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Combined RCD/MCB Devices FRBm4 type A
4.5 kA, 3+N-pole
Conditionally surge current-proof 250 A, sensitive to residual pulsating DC, type A
In/IΔn
(A)
SG14211
Article No.
Units
per
package
FRBm4-C20/3N/003-A
FRBm4-C25/3N/003-A
FRBm4-C32/3N/003-A
FRBm4-C20/3N/01-A
FRBm4-C25/3N/01-A
FRBm4-C32/3N/01-A
FRBm4-C20/3N/03-A
FRBm4-C25/3N/03-A
FRBm4-C32/3N/03-A
171000
171001
171002
170930
170931
170932
170958
170959
170960
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
FRBm4-D20/3N/003-A
FRBm4-D20/3N/01-A
FRBm4-D20/3N/03-A
170895
170942
170970
1/30
1/30
1/30
Characteristic C
20/0.03
25/0.03
32/0.03
20/0.1
25/0.1
32/0.1
20/0.3
25/0.3
32/0.3
SG14211
Type
Designation
Characteristic D
20/0.03
20/0.1
20/0.3
Chapter 3.1.1. – 52
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Specifications | Combined RCD/MCB Devices FRBm6, FRBm4, 3+N-pole
Description
• Combined RCD/MCB device
• Type -A: Protects against special forms of residual pulsating DC
• Line voltage-independent tripping
which have have not been smoothed.
• Compatible with standard busbar
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Guide for secure terminal connection
• Switching toggle (MCB component) in colour designating the rated
current
• Contact position indicator red - green
• Fault current tripping indicator white - blue
• Comprehensive range of accessories suitable for subsequent installation
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g.
damply or dusty environment), it's recommended to test in shorter
intervals (e.g. monthly).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Auxiliary switch for subsequent installation
Tripping signal contact for subsequent installation
Shunt trip release
Switching interlock
Screws lock 4MU
ZP-IHK
ZP-WHK
ZP-NHK
ZP-ASA/..
IS/SPE-1TE
286052
286053
248437
248438, 248439
101911
221954800
Connection diagram
3+N-pole
Dimensions (mm)
Chapter 3.1.1. – 53
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Technical Data
FRBm6, FRBm4, 3+N-pole
Electrical
Design according to
Current test marks as printed onto the device
Tripping
Rated voltage
Rated tripping current
Rated non-tripping current
Sensitivity
Selectivity class
Rated breaking capacity
FRBm6
FRBm4
Rated current
Rated impulse withstand voltage
Characteristic
Maximum back-up fuse (short circuit)
Endurance
electrical components
mechanical components
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection switch
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity rigid solid/stranded wire
Terminal torque
Busbar thickness
Tripping temperature
Storage- and transport temperature
Climatic conditions
IEC/EN 61009
Un
IΔn
IΔno
line voltage-independent, instantaneous 250A (8/20µs),
surge current-proof, N protected
240/415V AC, 50Hz
30, 100, 300 mA
0.5 IΔn
AC and pulsating DC
3
Icn
Uimp
6 kA
4.5 kA
6 - 32 A
4 kV (1.2/50µs)
B, C, D
100 A gL (>10 kA)
≥ 4,000 operating cycles
≥ 10,000 operating cycles
45 mm
80 mm
70 mm (4MU)
3-position DIN rail clip, permits removal from existing busbar system
IP20
IP40
open mouthed/lift terminals
finger and hand touch safe, VBG4, ÖVE-EN 6
1 - 25 mm2
2 - 2.4 Nm
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Tripping Characteristic FRBm, Characteristics B, C and D
Chapter 3.1.1. – 54
EATON CORPORATION xxxxx+xxxx-xxxxEN
Combined RCD/MCB Devices
Back-up Protection between FRBm and NZM1
Back-up Protection between FRBm and NZM2
Short circuit currents in kA.
Short circuit currents in kA.
FRBm4/FRBm6-In/B,C,D.. +NZMB1(C1)(N1)(H1)-A…
FRBm4/FRBm6-In/B,C,D.. +NZMB2(C2)(N2)(H2)-A…
Ue = 415 V
Ue = 415 V
B
C
D
6
-
20
20
10
-
20
20
20
13
20
20
20
20
16
20
20
20
20
20
20
-
20
20
20
-
25
-
20
-
B
C
D
6
-
20
20
10
-
20
20
13
20
20
16
20
20
20
-
25
-
Ue = 415V: Icn (FRBm4) = 4.5 kA (acc. to IEC/EN 61009)
Ue = 415V: Icu (FRBm6) = 6 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icn (NZMB1) = 25 kA (acc. to IEC/EN 60947-2)
Ue = 400/415V: Icn (NZMC1) = 36 kA (acc. to IEC/EN 60947-2)
Ue = 400/415V: Icn (NZMN1) = 50 kA (acc. to IEC/EN 60947-2)
Ue = 400/415V: Icn (NZMH1) = 100 kA (acc. to IEC/EN 60947-2)
Ue = 415V: Icn (FRBm4) = 4.5 kA (acc. to IEC/EN 61009)
Ue = 415V: Icu (FRBm6) = 6 kA (acc. to IEC/EN 61009)
Ue = 400/415V: Icn (NZMB2) = 25 kA (acc. to IEC/EN 60947-2)
Ue = 400/415V: Icn (NZMC2) = 36 kA (acc. to IEC/EN 60947-2)
Ue = 400/415V: Icn (NZMN2) = 50 kA (acc. to IEC/EN 60947-2)
Ue = 400/415V: Icn (NZMH2) = 150 kA (acc. to IEC/EN 60947-2)
Chapter 3.1.1. – 55
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Add-on Residual Current Protection Unit FBSmV
SG18211
• Combining this device with a top-quality miniature circuit breaker of type
FAZ (except PLSN) will form a top-quality RCBO unit (combined RCD/MCB
device)
• Draw-out connection bar locked in installation position
• For subsequent mounting onto 2-, 3-, 3+N- and 4-pole miniature circuit
breakers FAZ
• Rated current 40 and 63 A
Chapter 3.1.1. – 56
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Add-on Residual Current Protection Unit FBSmV type AC
Conditionally surge-current-proof 250 A, type AC
In/IΔn
(A)
SG17811
Units
per
package
FBSmV-40/2/003
FBSmV-63/2/003
FBSmV-40/2/01
FBSmV-63/2/01
FBSmV-40/2/03
FBSmV-63/2/03
FBSmV-40/2/05
FBSmV-63/2/05
FBSmV-40/2/1
FBSmV-63/2/1
170177
170178
170179
170180
170181
170182
170183
170184
170185
170186
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
FBSmV-40/3/003
FBSmV-63/3/003
FBSmV-40/3/01
FBSmV-63/3/01
FBSmV-40/3/03
FBSmV-63/3/03
FBSmV-40/3/05
FBSmV-63/3/05
FBSmV-40/3/1
FBSmV-63/3/1
170187
170188
170189
170190
170191
170192
170193
170194
170195
170196
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
FBSmV-40/4/003
FBSmV-63/4/003
FBSmV-40/4/01
FBSmV-63/4/01
FBSmV-40/4/03
FBSmV-63/4/03
FBSmV-40/4/05
FBSmV-63/4/05
FBSmV-40/4/1
FBSmV-63/4/1
170197
170198
170199
170200
170201
170202
170203
170204
170205
170206
1/13
1/13
1/13
1/13
1/13
1/13
1/13
1/13
1/13
1/13
3-pole
40/0.03
63/0.03
40/0.1
63/0.1
40/0.3
63/0.3
40/0.5
63/0.5
40/1
63/1
SG18211
Article No.
2-pole
40/0.03
63/0.03
40/0.1
63/0.1
40/0.3
63/0.3
40/0.5
63/0.5
40/1
63/1
SG18111
Type
Designation
4-pole
40/0.03
63/0.03
40/0.1
63/0.1
40/0.3
63/0.3
40/0.5
63/0.5
40/1
63/1
Chapter 3.1.1. – 57
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Add-on Residual Current Protection Unit FBSmV type A
Sensitive to residual pulsating DC, conditionally surge current-proof 250 A, type A
In/IΔn
(A)
SG17811
Units
per
package
FBSmV-40/2/003-A
FBSmV-63/2/003-A
FBSmV-40/2/01-A
FBSmV-63/2/01-A
FBSmV-40/2/03-A
FBSmV-63/2/03-A
FBSmV-40/2/05-A
FBSmV-63/2/05-A
FBSmV-40/2/1-A
FBSmV-63/2/1-A
170207
170208
170209
170210
170211
170212
170213
170214
170215
170216
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
FBSmV-40/3/003-A
FBSmV-63/3/003-A
FBSmV-40/3/01-A
FBSmV-63/3/01-A
FBSmV-40/3/03-A
FBSmV-63/3/03-A
FBSmV-40/3/05-A
FBSmV-63/3/05-A
FBSmV-40/3/1-A
FBSmV-63/3/1-A
170217
170218
170219
170220
170221
170222
170223
170224
170225
170226
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
1/20
FBSmV-40/4/003-A
FBSmV-63/4/003-A
FBSmV-40/4/01-A
FBSmV-63/4/01-A
FBSmV-40/4/03-A
FBSmV-63/4/03-A
FBSmV-40/4/05-A
FBSmV-63/4/05-A
FBSmV-40/4/1-A
FBSmV-63/4/1-A
170227
170228
170229
170230
170231
170232
170233
170234
170235
170236
1/13
1/13
1/13
1/13
1/13
1/13
1/13
1/13
1/13
1/13
3-pole
40/0.03
63/0.03
40/0.1
63/0.1
40/0.3
63/0.3
40/0.5
63/0.5
40/1
63/1
SG18211
Article No.
2-pole
40/0.03
63/0.03
40/0.1
63/0.1
40/0.3
63/0.3
40/0.5
63/0.5
40/1
63/1
SG18111
Type
Designation
4-pole
40/0.03
63/0.03
40/0.1
63/0.1
40/0.3
63/0.3
40/0.5
63/0.5
40/1
63/1
Chapter 3.1.1. – 58
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Add-on Residual Current Protection Unit FBSmV type G
Surge current-proof 3 kA, type G (ÖVE E 8601)
In/IΔn
(A)
SG17811
Units
per
package
FBSmV-40/2/003-G
170237
1/20
FBSmV-40/3/003-G
170238
1/20
FBSmV-40/4/003-G
170239
1/13
Type
Designation
Article No.
Units
per
package
FBSmV-40/2/01-S
FBSmV-63/2/01-S
FBSmV-40/2/03-S
FBSmV-63/2/03-S
FBSmV-40/2/1-S
FBSmV-63/2/1-S
170240
170241
170142
170143
170144
170145
1/20
1/20
1/20
1/20
1/20
1/20
FBSmV-40/3/01-S
FBSmV-63/3/01-S
FBSmV-40/3/03-S
FBSmV-63/3/03-S
FBSmV-40/3/1-S
FBSmV-63/3/1-S
170146
170147
170148
170149
170150
170151
1/20
1/20
1/20
1/20
1/20
1/20
FBSmV-40/4/01-S
FBSmV-63/4/01-S
FBSmV-40/4/03-S
FBSmV-63/4/03-S
FBSmV-40/4/1-S
FBSmV-63/4/1-S
170152
170153
170154
170155
170156
170157
1/13
1/13
1/13
1/13
1/13
1/13
3-pole
40/0.03
SG18211
Article No.
2-pole
40/0.03
SG18111
Type
Designation
4-pole
40/0.03
Add-on Residual Current Protection Unit FBSmV type S
Selective and surge current-proof 5 kA, type S
In/IΔn
(A)
SG17811
2-pole
40/0.1
63/0.1
40/0.3
63/0.3
40/1
63/1
SG18111
3-pole
40/0.1
63/0.1
40/0.3
63/0.3
40/1
63/1
SG18211
4-pole
40/0.1
63/0.1
40/0.3
63/0.3
40/1
63/1
Chapter 3.1.1. – 59
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Specifications | Add-on Residual Current Protection Unit FBSmV
Description
• Add-on residual current unit
• Line voltage-independent tripping
• By combining this device with a top-quality miniature circuit breaker type FAZ (exept PLSN.) a top-quality RCBO unit (combined
RCD/MCB device) is formed
• Rated current 40 and 63 A
• Permits combinations with a variety of characteristics thanks to the
different rated currents and characteristics of the FAZ-miniature circuit breakers which can be connected
• Comrehensive range of accessories suitable for subsequent installation onto FAZ
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g.
damply or dusty environment), it's recommended to test in shorter
intervals (e.g. monthly).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
• Type -A: Protects against special forms of residual pulsating DC
which have have not been smoothed.
• Type -G: High reliability against unwanted tripping. Compulsory
for any circuit where personal injury or damage to property may
occur in case of unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Type -S: Selective residual current device sensitive to AC, type -S.
Compulsory for systems with surge arresters downstream of the
RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5).
• Type -S/A: Additionally protects against special forms of residual
pulsating pulsating DC which have not been smoothed.
Accessories:
Cover cap for draw-out connection bar
Slotted one-way cheese head screw
included
included
Accessories (on FAZ):
Auxiliary switch for subsequent installation
ZP-IHK
ZP-WHK
ZP-NHK
Z-FW/LP
Z-FW-LPD
Z-FW-MO
Z-FW-LP/MO
Z-FW-LPD/MO
Z-FW/001
Z-FW/003
Z-FW/010
Z-FW/030
Z-FW/050
ZP-ASA/..
Z-USA
Z-USD
IS/SPE-1TE
Tripping signal contact for subsequent installation
Automatic restarting device
Remote control
Pre-mounted sets
Remote testing module
Shunt trip release
Undervoltage release
Switching interlock
Cap for lead seal 2-pole
Cap for lead seal 3-pole
286052
286053
248437
248296
265244
284730
290171
290172
248297
248298
248299
248300
248301
248438, 248439
258288, 248289, 248290
248292, 248291
101911
280971500
280971600
Connection diagram
2-pole
2 4
3-pole
T
2 4 6
2’ 4’
4-pole
T
2 4 6 8N
2’ 4’ 6’
T
2’ 4’ 6’ 8N’
Chapter 3.1.1. – 60
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Technical Data
FBSmV
Electrical
Design according to
Current test marks as printed onto the device
Tripping
Type G
Type S
Rated voltage
Rated frequency
Rated tripping current
Rated non-tripping current
Sensitivity
Rated current
Service short circuit breaking capacity
Rated breaking capacity
Rated fault breaking capacity
Un = 240V
Un = 415V
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection switch
Degree of protection, built-in
Fastening screw
Screw head breaking torque
Upper and lower terminals
Terminal screws
Terminal protection
Terminal capacity
Rigid conductors
Flexible conductors (with wire end sleeve)
Busbar thickness
Ambient temperature range
Storage- and transport temperature
Resistance to climatic conditions
IEC/EN 61009
Un
IΔn
IΔno
In
Ics
Icn
instantaneous 250A (8/20µs), surge current-proof
10 ms delay 3kA (8/20µs), surge current-proof
40 ms delay 5kA (8/20µs) with selective disconnecting function,
surge current-proof
240/415V AC
50 Hz
30, 100, 300, 500, 1000 mA
0.5 IΔn
AC and pulsating DC
≤ 40 A, ≤ 63 A
same as connected FAZ (7.5 kA)
same as connected FAZ (10 kA)
IΔm
6 kA
3 kA
45 mm
90 mm
70 mm (2p), 107.5 mm (3p), 125 mm (4p)
fix mounted onto FAZ
IP20
IP40
M2.5 (slotted one-way cheese head screw)
> 0.6 Nm
lift terminals
M5 (combined Philips/standard head screws according to
DIN7962-Z2, Pozidrive)
finger and hand touch safe, BGV A3, ÖVE-EN 6
1 x (1 - 25) mm2
1 x (0.75 - 16) mm2
0.8 - 2 mm
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
Dimensions (mm)
Chapter 3.1.1. – 61
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Add-on Residual Current Protection Unit FBHmV
SG17711
• By combining this device with a top-quality miniature circuit breaker of
type AZ a top-quality RCBO unit (combined RCD/MCB device) is formed.
• Add-on residual current unit (screw connection) for 80 or 125 A (2-pole
and 4-pole)
• High flexibility and ease of installation thanks to variable wiring
• Free selection of main power supply
• Auxiliary switch 1 make contact included as standard in all FBHmV versions
• Permits combinations with a variety of characteristics thanks to the different rated currents and characteristics of the miniature circuit breakers AZ
which can be connected
• For commercial and industry applications
• For subsequent mounting onto 2, 3, 3+N and 4-pole-miniature circuit
breakers AZ
• The screw connection to the AZ-device can be unscrewed at any time.
Consequently, in case of modifications of the systems to be protected, the
installation can be adapted to new requirements at any time.
Chapter 3.1.1. – 62
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Add-on Residual Current Protection Unit FBHmV type AC
Conditionally surge-current-proof 250 A, type AC
In/IΔn
(A)
SG17611
Article No.
Units
per
package
FBHmV-80/2/003
FBHmV-125/2/003
FBHmV-80/2/03
FBHmV-125/2/03
FBHmV-80/2/05
FBHmV-125/2/05
FBHmV-80/2/1
FBHmV-125/2/1
170266
170242
170243
170244
170245
170246
170247
170248
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
FBHmV-80/4/003
FBHmV-125/4/003
FBHmV-80/4/03
FBHmV-125/4/03
FBHmV-80/4/05
FBHmV-125/4/05
FBHmV-80/4/1
FBHmV-125/4/1
170249
170250
170251
170252
170253
170254
170255
170256
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
Type
Designation
Article No.
Units
per
package
FBHmV-80/2/003-A
FBHmV-125/2/003-A
FBHmV-80/2/03-A
FBHmV-125/2/03-A
FBHmV-80/2/05-A
FBHmV-125/2/05-A
FBHmV-80/2/1-A
FBHmV-125/2/1-A
170257
170258
170259
170260
170261
170262
170263
170264
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
FBHmV-80/4/003-A
FBHmV-125/4/003-A
FBHmV-80/4/03-A
FBHmV-125/4/03-A
FBHmV-80/4/05-A
FBHmV-125/4/05-A
FBHmV-80/4/1-A
FBHmV-125/4/1-A
170265
170130
170131
170132
170133
170134
170135
170136
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
2-pole
80/0.03
125/0.03
80/0.3
125/0.3
80/0.5
125/0.5
80/1
125/1
SG17711
Type
Designation
4-pole
80/0.03
125/0.03
80/0.3
125/0.3
80/0.5
125/0.5
80/1
125/1
Add-on Residual Current Protection Unit FBHmV type A
Sensitive to residual pulsating DC, conditionally surge current-proof 250 A, type A
In/IΔn
(A)
SG17611
2-pole
80/0.03
125/0.03
80/0.3
125/0.3
80/0.5
125/0.5
80/1
125/1
SG17711
4-pole
80/0.03
125/0.03
80/0.3
125/0.3
80/0.5
125/0.5
80/1
125/1
Chapter 3.1.1. – 63
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Add-on Residual Current Protection Unit FBHmV type S/A
Selective + surge current-proof 5 kA, type S/A
In/IΔn
(A)
SG17611
Article No.
Units
per
package
FBHmV-80/2/03-S/A
FBHmV-125/2/03-S/A
FBHmV-80/2/05-S/A
FBHmV-125/2/05-S/A
FBHmV-80/2/1-S/A
FBHmV-125/2/1-S/A
170137
170138
170139
170140
170141
170170
1/4
1/4
1/4
1/4
1/4
1/4
FBHmV-80/4/03-S/A
FBHmV-125/4/03-S/A
FBHmV-80/4/05-S/A
FBHmV-125/4/05-S/A
FBHmV-80/4/1-S/A
FBHmV-125/4/1-S/A
170171
170172
170173
170174
170175
170176
1/4
1/4
1/4
1/4
1/4
1/4
2-pole
80/0.3
125/0.3
80/0.5
125/0.5
80/1
125/1
SG17711
Type
Designation
4-pole
80/0.3
125/0.3
80/0.5
125/0.5
80/1
125/1
Chapter 3.1.1. – 64
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Specifications | Add-on Residual Current Protection Unit FBHmV
Description
• By combination with miniature circuit breaker AZ => RCBO-Unit
(MCCB)
• Add-on residual current unit (screw connection) for 80 or 125 A
(2-pole and 4-pole)
• High flexibility and ease of installation thanks to variable wiring
(400 mm flexible connection wires 2p = 2 units, 4p = 4 units included in the set)
• Free selection of main power supply
• Auxiliary switch 1 NO included as standard in all FBHmV versions
• Permits combinations with a variety of characteristics thanks to the
different rated currents and characteristics of the miniature circuit
breakers AZ which can be connected
• For trade and industry applications
• For subsequent mounting onto 2, 3, 3+N and 4-pole-miniature circuit breakers AZ
• Toggle (serves as switch position- and tripping indicator)
• The screw connection to the AZ-device can be unscrewed at any
time. Consequently, in case of modifications of the systems to be
protected, the installation can be adapted to new requirements at
any time.
• The test key “T” must be pressed every half year. The system operator must be informed of this obligation and his responsibility in a
way that can be proven. The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g.
damply or dusty environment), it's recommended to test in shorter
intervals (e.g. monthly).
• Pressing the test key “T” serves the only purpose of function testing the residual current device (RCD). This test does not make
earthing resistance measurement (RE), or proper checking of the
earth conductor condition redundant, which must be performed
separately.
Accessories:
Flexible connection wires (connection to AZ) are included in the standard set:
2-pole 80A
4-pole 80A
2-pole 125A
4-pole 125A
2 x 16mm2 (400mm each)
4 x 16mm2 (400mm each)
2 x 35mm2 (400mm each)
4 x 35mm2 (400mm each)
Connection diagram
2-pole
4-pole
Chapter 3.1.1. – 65
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Technical Data
FBHmV
Electrical current flow paths
Design according to
Current test marks as printed onto the device
Tripping
Type S
Rated voltage
Rated frequency
Rated tripping current
Rated non-tripping current
Sensitivity
Rated current
Rated service short circuit breaking capacity
Rated ultimate circuit breaking capacity
Rated fault short circuit breaking capacity
Rated impulse withstand voltage
Endurance
electrical components
80A
125A
mechanical components
80A
125A
Electrical Auxiliary Contact
Utilisation category AC15
Rated voltage
Rated operational current
Mechanical
Frame size
Device height
Device width
Depth of central body
Mounting
Degree of protection switch
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity
Main conductor
Auxiliary switch
Ambient temperature range
Storage- and transport temperature
Resistance to climatic conditions
IEC/EN 61009
Un
IΔn
IΔno
In
Icn
Icu
IΔ/n
Uimp
instantaneous 250A (8/20µs), surge current-proof
40 ms delay 5kA (8/20µs) with selective disconnecting function,
surge current-proof
240/415V AC
50 Hz
30, 300, 500, 1000 mA
0.5 IΔn
AC and pulsating DC
80, 125 A
same as connected AZ
same as connected AZ
= Icu
4 kV (1.2/50µs)
≥ 1,500 operating cycles
≥ 1,000 operating cycles
≥ 10,000 operating cycles
≥ 8,000 operating cycles
Ue
Ie
250 V AC
16 A AC
45 mm
90 mm
95 mm (5.5MU)
60 mm
screwed onto AZ 2-, 3-, 4-pole; Z-BHASA
IP20
IP40
lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
2.5 - 50 mm2
1 - 25 mm2
-25°C to +40°C
-35°C to +60°C
25-55°C/90-95% relative humidity acc. to IEC 60068-2
Dimensions (mm)
FBHmV/2p + AZ/2p
FBHmV/4p + AZ/3p+N
FBHmV/4p + AZ/3p
FBHmV/4p + AZ/4p
Chapter 3.1.1. – 66
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Wiring options
Mounting FBHmV + AZ
SG15402
SG15102
FBHmV
+
AZ
Connection FBHmV/4p + AZ/3p
FBHmV/4p
SG15202
AZ/3p
SG15302
Mounting arrangement residual current protection unit - shunt trip release - miniature circuit breaker - auxiliary contact
FBHmV-2-pole
Z-BHASA
FBHmV-4-pole
FBHmV-3+N-pole
Z-LHK
13
1
21
+
+
+
22
2
Chapter 3.1.1. – 67
14
EATON CORPORATION xxxxx+xxxx-xxxxEN
Add-on Residual Current Protection
Specifications | Accessories for FBHmV - Shunt Trip Release Z-BHASA
Description
• Can be mounted subsequently
• Contact position indicator red - green
• Marking labels can be fitted
• Wide operational voltage range
• Sufficient power of extra low voltage source must be ensured ZBHASA/24: min. 90 VA
• Screws for mounting included FBHmV => BHASA => AZ
Electrical
Minimum pulse duration
Internal resistance
Duty
Tripping time
Peak withstand voltage (1.2/50µs)
Endurance
electrical components
mechanical components
AC voltage range:
Responding limit
Operational voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
DC voltage range:
Responding limit
DC voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection switch
Degree of protection, built-in
Upper and lower terminals
Terminal protection
Terminal capacity
Fastening torque of terminal screws
Z-BHASA/24
Z-BHASA/230
15 ms
2Ω
100%
< 20 ms
2 kV
10 ms
130 Ω
100%
< 20 ms
2 kV
≥ 4,000 operating cycles
≥ 4,000 operating cycles
8V
12-60 V
1.4-7 A
4.0 ms
70 V
110-415 V
3.4 A (at 230V)
4.5 ms
11 V
12-60 V
1.7 A typ.
2 ms
90 V
110-230 V
1.7 A typ.
4 ms
45 mm
45 mm
90 mm
90 mm
27 mm
27 mm
quick fastening on DIN rail IEC/EN 60715
IP20
IP20
IP40
IP40
lift terminals
lift terminals
finger and hand touch safe, BGV A3, ÖVE-EN 6
2.5 - 30 mm2
2.5 - 30 mm2
4 Nm
4 Nm
Connection diagram
2-pole
1
2
Dimensions (mm)
Chapter 3.1.1. – 68
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Miniature Circuit Breakers FAZ, FAZ-PN, FAZ-HS
SG07211
FAZ
• High-quality miniature circuit breakers for industrial applications and residential applications
• Contact position indicator red - green
• Guide for secure terminal connection
• 3-position DIN rail clip, permits removal from existing busbar system
• Comprehensive range of accessories suitable for subsequent installation
• Rated currents up to 63 A
• Tripping characteristics B, C, D, K, S, Z
• Rated breaking capacity up to 15 kA according to IEC/EN 60898-1
FAZ-PN
• Tripping characteristic B
• Rated breaking capacity up to 6 kA according to IEC/EN 60898-1
• Module width 1MU (1+N-poles)
FAZ-HS
• Tripping characteristic B
• Rated breaking capacity up to 10 kA according to IEC/EN 60898-1
• 1- and 2-poles available
Chapter 4.1.1. – 1
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ Miniature Circuit Breakers (MCBs)
Characteristic B
Rated Rated
current voltage
In (A) (V)
SG06811
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
1-pole
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG06911
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-B1/1
FAZ-B1,5/1
FAZ-B1,6/1
FAZ-B2/1
FAZ-B2,5/1
FAZ-B3/1
FAZ-B3,5/1
FAZ-B4/1
FAZ-B5/1
FAZ-B6/1
FAZ-B8/1
FAZ-B10/1
FAZ-B12/1
FAZ-B13/1
FAZ-B15/1
FAZ-B16/1
FAZ-B20/1
FAZ-B25/1
FAZ-B32/1
FAZ-B40/1
FAZ-B50/1
FAZ-B63/1
278520
278521
278522
278523
278524
278525
278526
278527
278528
278529
278530
278531
278532
278533
278534
278535
278536
278537
278538
278539
278540
278541
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-B1/1N
FAZ-B1,5/1N
FAZ-B1,6/1N
FAZ-B2/1N
FAZ-B2,5/1N
FAZ-B3/1N
FAZ-B3,5/1N
FAZ-B4/1N
FAZ-B5/1N
FAZ-B6/1N
FAZ-B8/1N
FAZ-B10/1N
FAZ-B12/1N
FAZ-B13/1N
FAZ-B15/1N
FAZ-B16/1N
FAZ-B20/1N
FAZ-B25/1N
FAZ-B32/1N
FAZ-B40/1N
FAZ-B50/1N
FAZ-B63/1N
278633
278634
278635
278636
278637
278638
278639
278640
278641
278642
278643
278644
278645
278646
278647
278648
278649
278650
278651
278652
278653
278654
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1+N-pole
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
Chapter 4.1.1. – 2
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07011
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-B1/2
FAZ-B1,5/2
FAZ-B1,6/2
FAZ-B2/2
FAZ-B2,5/2
FAZ-B3/2
FAZ-B3,5/2
FAZ-B4/2
FAZ-B5/2
FAZ-B6/2
FAZ-B8/2
FAZ-B10/2
FAZ-B12/2
FAZ-B13/2
FAZ-B15/2
FAZ-B16/2
FAZ-B20/2
FAZ-B25/2
FAZ-B32/2
FAZ-B40/2
FAZ-B50/2
FAZ-B63/2
278719
278720
278721
278722
278723
278724
278725
278726
278727
278728
278729
278730
278731
278732
278733
278734
278735
278736
278737
278738
278739
278740
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-B1/3
FAZ-B1,5/3
FAZ-B1,6/3
FAZ-B2/3
FAZ-B2,5/3
FAZ-B3/3
FAZ-B3,5/3
FAZ-B4/3
FAZ-B5/3
FAZ-B6/3
FAZ-B8/3
FAZ-B10/3
FAZ-B12/3
FAZ-B13/3
FAZ-B15/3
FAZ-B16/3
FAZ-B20/3
FAZ-B25/3
FAZ-B32/3
FAZ-B40/3
FAZ-B50/3
FAZ-B63/3
278832
278833
278834
278835
278836
278837
278838
278839
278840
278841
278842
278843
278844
278845
278846
278847
278848
278849
278850
278851
278852
278853
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
2-pole
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG07111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Chapter 4.1.1. – 3
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07311
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-B1/3N
FAZ-B1,5/3N
FAZ-B1,6/3N
FAZ-B2/3N
FAZ-B2,5/3N
FAZ-B3/3N
FAZ-B3,5/3N
FAZ-B4/3N
FAZ-B5/3N
FAZ-B6/3N
FAZ-B8/3N
FAZ-B10/3N
FAZ-B12/3N
FAZ-B13/3N
FAZ-B15/3N
FAZ-B16/3N
FAZ-B20/3N
FAZ-B25/3N
FAZ-B32/3N
FAZ-B40/3N
FAZ-B50/3N
FAZ-B63/3N
278934
278935
278936
278937
278938
278939
278940
278941
278942
278943
278944
278945
278946
278947
278948
278949
278950
278951
278952
278953
278954
278955
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-B1/4
FAZ-B1,5/4
FAZ-B1,6/4
FAZ-B2/4
FAZ-B2,5/4
FAZ-B3/4
FAZ-B3,5/4
FAZ-B4/4
FAZ-B5/4
FAZ-B6/4
FAZ-B8/4
FAZ-B10/4
FAZ-B12/4
FAZ-B13/4
FAZ-B15/4
FAZ-B16/4
FAZ-B20/4
FAZ-B25/4
FAZ-B32/4
FAZ-B40/4
FAZ-B50/4
FAZ-B63/4
279020
279021
279022
279023
279024
279025
279026
279027
279028
279029
279030
279031
279032
279033
279034
279035
279036
279037
279038
279039
279040
279041
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
3+N-pole
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG07211
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
4-pole
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Chapter 4.1.1. – 4
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ Miniature Circuit Breakers (MCBs)
Characteristic C
Rated Rated
current voltage
In (A) (V)
SG06811
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
1-pole
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG06911
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-C0,16/1
FAZ-C0,25/1
FAZ-C0,5/1
FAZ-C0,75/1
FAZ-C1/1
FAZ-C1,5/1
FAZ-C1,6/1
FAZ-C2/1
FAZ-C2,5/1
FAZ-C3/1
FAZ-C3,5/1
FAZ-C4/1
FAZ-C5/1
FAZ-C6/1
FAZ-C8/1
FAZ-C10/1
FAZ-C12/1
FAZ-C13/1
FAZ-C15/1
FAZ-C16/1
FAZ-C20/1
FAZ-C25/1
FAZ-C32/1
FAZ-C40/1
FAZ-C50/1
FAZ-C63/1
278542
278543
278544
278545
278546
278547
278548
278549
278550
278551
278552
278553
278554
278555
278556
278557
278558
278559
278560
278561
278562
278563
278564
278565
278566
278567
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-C0,16/1N
FAZ-C0,25/1N
FAZ-C0,5/1N
FAZ-C0,75/1N
FAZ-C1/1N
FAZ-C1,5/1N
FAZ-C1,6/1N
FAZ-C2/1N
FAZ-C2,5/1N
FAZ-C3/1N
FAZ-C3,5/1N
FAZ-C4/1N
FAZ-C5/1N
FAZ-C6/1N
FAZ-C8/1N
FAZ-C10/1N
FAZ-C12/1N
FAZ-C13/1N
FAZ-C15/1N
FAZ-C16/1N
FAZ-C20/1N
FAZ-C25/1N
FAZ-C32/1N
FAZ-C40/1N
FAZ-C50/1N
FAZ-C63/1N
278655
278656
278657
278658
278659
278660
278661
278662
278663
278664
278665
278666
278667
278668
278669
278670
278671
278672
278673
278674
278675
278676
278677
278678
278679
278680
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1+N-pole
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
Chapter 4.1.1. – 5
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07011
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-C0,16/2
FAZ-C0,25/2
FAZ-C0,5/2
FAZ-C0,75/2
FAZ-C1/2
FAZ-C1,5/2
FAZ-C1,6/2
FAZ-C2/2
FAZ-C2,5/2
FAZ-C3/2
FAZ-C3,5/2
FAZ-C4/2
FAZ-C5/2
FAZ-C6/2
FAZ-C8/2
FAZ-C10/2
FAZ-C12/2
FAZ-C13/2
FAZ-C15/2
FAZ-C16/2
FAZ-C20/2
FAZ-C25/2
FAZ-C32/2
FAZ-C40/2
FAZ-C50/2
FAZ-C63/2
278741
278742
278743
278744
278745
278746
278747
278748
278749
278750
278751
278752
278753
278754
278755
278756
278757
278758
278759
278760
278761
278762
278763
278764
278765
278766
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-C0,16/3
FAZ-C0,25/3
FAZ-C0,5/3
FAZ-C0,75/3
FAZ-C1/3
FAZ-C1,5/3
FAZ-C1,6/3
FAZ-C2/3
FAZ-C2,5/3
FAZ-C3/3
FAZ-C3,5/3
FAZ-C4/3
FAZ-C5/3
FAZ-C6/3
FAZ-C8/3
FAZ-C10/3
FAZ-C12/3
FAZ-C13/3
FAZ-C15/3
FAZ-C16/3
FAZ-C20/3
FAZ-C25/3
FAZ-C32/3
FAZ-C40/3
FAZ-C50/3
FAZ-C63/3
278854
278855
278856
278857
278858
278859
278860
278861
278862
278863
278864
278865
278866
278867
278868
278869
278870
278871
278872
278873
278874
278875
278876
278877
278878
278879
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
2-pole
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG07111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Chapter 4.1.1. – 6
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07311
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-C0,16/3N
FAZ-C0,25/3N
FAZ-C0,5/3N
FAZ-C0,75/3N
FAZ-C1/3N
FAZ-C1,5/3N
FAZ-C1,6/3N
FAZ-C2/3N
FAZ-C2,5/3N
FAZ-C3/3N
FAZ-C3,5/3N
FAZ-C4/3N
FAZ-C5/3N
FAZ-C6/3N
FAZ-C8/3N
FAZ-C10/3N
FAZ-C12/3N
FAZ-C13/3N
FAZ-C15/3N
FAZ-C16/3N
FAZ-C20/3N
FAZ-C25/3N
FAZ-C32/3N
FAZ-C40/3N
FAZ-C50/3N
FAZ-C63/3N
278956
278957
278958
278959
278960
278961
278962
278963
278964
278965
278966
278967
278968
278969
278970
278971
278972
278973
278974
278975
278976
278977
278978
278979
278980
278981
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5
5
5
FAZ-C0,16/4
FAZ-C0,25/4
FAZ-C0,5/4
FAZ-C0,75/4
FAZ-C1/4
FAZ-C1,5/4
FAZ-C1,6/4
FAZ-C2/4
FAZ-C2,5/4
FAZ-C3/4
FAZ-C3,5/4
FAZ-C4/4
FAZ-C5/4
FAZ-C6/4
FAZ-C8/4
FAZ-C10/4
FAZ-C12/4
FAZ-C13/4
FAZ-C15/4
FAZ-C16/4
FAZ-C20/4
FAZ-C25/4
FAZ-C32/4
FAZ-C40/4
FAZ-C50/4
FAZ-C63/4
279042
279043
279044
279045
279046
279047
279048
279049
279050
279051
279052
279053
279054
279055
279056
279057
279058
279059
279060
279061
279062
279063
279064
279065
279066
279067
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
3+N-pole
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG07211
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
4-pole
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Chapter 4.1.1. – 7
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ Miniature Circuit Breakers (MCBs)
Characteristic D
Rated Rated
current voltage
In (A) (V)
SG06811
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
1-pole
0.5
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG06911
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
-
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
-
FAZ-D0,5/1
FAZ-D1/1
FAZ-D1,5/1
FAZ-D1,6/1
FAZ-D2/1
FAZ-D2,5/1
FAZ-D3/1
FAZ-D3,5/1
FAZ-D4/1
FAZ-D5/1
FAZ-D6/1
FAZ-D8/1
FAZ-D10/1
FAZ-D12/1
FAZ-D13/1
FAZ-D15/1
FAZ-D16/1
FAZ-D20/1
FAZ-D25/1
FAZ-D32/1
FAZ-D40/1
FAZ-D50/1
FAZ-D63/1
278568
278569
278570
278571
278572
278573
278574
278575
278576
278577
278578
278579
278580
278581
278582
278583
278584
278585
278586
278587
278588
115370
115371
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
-
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
-
FAZ-D0,5/1N
FAZ-D1/1N
FAZ-D1,5/1N
FAZ-D1,6/1N
FAZ-D2/1N
FAZ-D2,5/1N
FAZ-D3/1N
FAZ-D3,5/1N
FAZ-D4/1N
FAZ-D5/1N
FAZ-D6/1N
FAZ-D8/1N
FAZ-D10/1N
FAZ-D12/1N
FAZ-D13/1N
FAZ-D15/1N
FAZ-D16/1N
FAZ-D20/1N
FAZ-D25/1N
FAZ-D32/1N
FAZ-D40/1N
FAZ-D50/1N
FAZ-D63/1N
278681
278682
278683
278684
278685
278686
278687
278688
278689
278690
278691
278692
278693
278694
278695
278696
278697
278698
278699
278700
278701
115378
115379
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1+N-pole
0.5
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
Chapter 4.1.1. – 8
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07011
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
-
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
-
FAZ-D0,5/2
FAZ-D1/2
FAZ-D1,5/2
FAZ-D1,6/2
FAZ-D2/2
FAZ-D2,5/2
FAZ-D3/2
FAZ-D3,5/2
FAZ-D4/2
FAZ-D5/2
FAZ-D6/2
FAZ-D8/2
FAZ-D10/2
FAZ-D12/2
FAZ-D13/2
FAZ-D15/2
FAZ-D16/2
FAZ-D20/2
FAZ-D25/2
FAZ-D32/2
FAZ-D40/2
FAZ-D50/2
FAZ-D63/2
278767
278768
278769
278770
278771
278772
278773
278774
278775
278776
278777
278778
278779
278780
278781
278782
278783
278784
278785
278786
278787
115372
115373
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
-
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
-
FAZ-D0,5/3
FAZ-D1/3
FAZ-D1,5/3
FAZ-D1,6/3
FAZ-D2/3
FAZ-D2,5/3
FAZ-D3/3
FAZ-D3,5/3
FAZ-D4/3
FAZ-D5/3
FAZ-D6/3
FAZ-D8/3
FAZ-D10/3
FAZ-D12/3
FAZ-D13/3
FAZ-D15/3
FAZ-D16/3
FAZ-D20/3
FAZ-D25/3
FAZ-D32/3
FAZ-D40/3
FAZ-D50/3
FAZ-D63/3
278880
278881
278882
278883
278884
278885
278886
278887
278888
278889
278890
278891
278892
278893
278894
278895
278896
278897
278898
278899
278900
115374
115375
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
2-pole
0,5
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG07111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
0.5
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Chapter 4.1.1. – 9
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07311
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
-
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
-
FAZ-D,5/3N
FAZ-D1/3N
FAZ-D1,5/3N
FAZ-D1,6/3N
FAZ-D2/3N
FAZ-D2,5/3N
FAZ-D3/3N
FAZ-D3,5/3N
FAZ-D4/3N
FAZ-D5/3N
FAZ-D6/3N
FAZ-D8/3N
FAZ-D10/3N
FAZ-D12/3N
FAZ-D13/3N
FAZ-D15/3N
FAZ-D16/3N
FAZ-D20/3N
FAZ-D25/3N
FAZ-D32/3N
FAZ-D40/3N
FAZ-D50/3N
FAZ-D63/3N
278982
278983
278984
278985
278986
278987
278988
278989
278990
278991
278992
278993
278994
278995
278996
278997
278998
278999
279000
279001
279002
115380
115381
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
10
10
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
-
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
-
FAZ-D0,5/4
FAZ-D1/4
FAZ-D1,5/4
FAZ-D1,6/4
FAZ-D2/4
FAZ-D2,5/4
FAZ-D3/4
FAZ-D3,5/4
FAZ-D4/4
FAZ-D5/4
FAZ-D6/4
FAZ-D8/4
FAZ-D10/4
FAZ-D12/4
FAZ-D13/4
FAZ-D15/4
FAZ-D16/4
FAZ-D20/4
FAZ-D25/4
FAZ-D32/4
FAZ-D40/4
FAZ-D50/4
FAZ-D63/4
279068
279069
279070
279071
279072
279073
279074
279075
279076
279077
279078
279079
279080
279081
279082
279083
279084
279085
279086
279087
279088
115376
115377
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
3+N-pole
0.5
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
SG07211
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
4-pole
0.5
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Chapter 4.1.1. – 10
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ Miniature Circuit Breakers (MCBs)
Characteristic K
Rated Rated
current voltage
In (A) (V)
SG06811
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
1-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
SG06911
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-K0,5/1
FAZ-K1/1
FAZ-K1,6/1
FAZ-K2/1
FAZ-K3/1
FAZ-K4/1
FAZ-K6/1
FAZ-K8/1
FAZ-K10/1
FAZ-K13/1
FAZ-K16/1
FAZ-K20/1
FAZ-K25/1
FAZ-K32/1
FAZ-K40/1
FAZ-K50/1
FAZ-K63/1
278589
278590
278591
278592
278593
278594
278595
278596
278597
278598
278599
278600
278601
278602
278603
278604
278605
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-K0,5/1N
FAZ-K1/1N
FAZ-K1,6/1N
FAZ-K2/1N
FAZ-K3/1N
FAZ-K4/1N
FAZ-K6/1N
FAZ-K8/1N
FAZ-K10/1N
FAZ-K13/1N
FAZ-K16/1N
FAZ-K20/1N
FAZ-K25/1N
FAZ-K32/1N
FAZ-K40/1N
FAZ-K50/1N
FAZ-K63/1N
278702
278703
278704
278705
278706
278707
278708
278709
278710
278711
278712
278713
278714
278715
278716
278717
278718
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1+N-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
Chapter 4.1.1. – 11
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07011
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-K0,5/2
FAZ-K1/2
FAZ-K1,6/2
FAZ-K2/2
FAZ-K3/2
FAZ-K4/2
FAZ-K6/2
FAZ-K8/2
FAZ-K10/2
FAZ-K13/2
FAZ-K16/2
FAZ-K20/2
FAZ-K25/2
FAZ-K32/2
FAZ-K40/2
FAZ-K50/2
FAZ-K63/2
278788
278789
278790
278791
278792
278793
278794
278795
278796
278797
278798
278799
278800
278801
278802
278803
278804
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-K0,5/3
FAZ-K1/3
FAZ-K1,6/3
FAZ-K2/3
FAZ-K3/3
FAZ-K4/3
FAZ-K6/3
FAZ-K8/3
FAZ-K10/3
FAZ-K13/3
FAZ-K16/3
FAZ-K20/3
FAZ-K25/3
FAZ-K32/3
FAZ-K40/3
FAZ-K50/3
FAZ-K63/3
278901
278902
278903
278904
278905
278906
278907
278908
278909
278910
278911
278912
278913
278914
278915
278916
278917
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
2-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
SG07111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Chapter 4.1.1. – 12
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07311
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-K0,5/3N
FAZ-K1/3N
FAZ-K1,6/3N
FAZ-K2/3N
FAZ-K3/3N
FAZ-K4/3N
FAZ-K6/3N
FAZ-K8/3N
FAZ-K10/3N
FAZ-K13/3N
FAZ-K16/3N
FAZ-K20/3N
FAZ-K25/3N
FAZ-K32/3N
FAZ-K40/3N
FAZ-K50/3N
FAZ-K63/3N
279003
279004
279005
279006
279007
279008
279009
279010
279011
279012
279013
279014
279015
279016
279017
279018
279019
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-K0,5/4
FAZ-K1/4
FAZ-K1,6/4
FAZ-K2/4
FAZ-K3/4
FAZ-K4/4
FAZ-K6/4
FAZ-K8/4
FAZ-K10/4
FAZ-K13/4
FAZ-K16/4
FAZ-K20/4
FAZ-K25/4
FAZ-K32/4
FAZ-K40/4
FAZ-K50/4
FAZ-K63/4
279089
279090
279091
279092
279093
279094
279095
279096
279097
279098
279099
279100
279101
279102
279103
279104
279105
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
3+N-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
SG07211
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
4-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Chapter 4.1.1. – 13
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ Miniature Circuit Breakers (MCBs)
Characteristic S
Rated Rated
current voltage
In (A) (V)
SG06811
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
1-pole
1
2
3
4
6
10
16
20
25
32
40
SG07011
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
10
10
10
10
10
10
10
10
10
10
10
277
277
277
277
277
277
277
277
277
277
277
5
5
5
5
5
5
5
5
5
5
5
FAZ-S1/1
FAZ-S2/1
FAZ-S3/1
FAZ-S4/1
FAZ-S6/1
FAZ-S10/1
FAZ-S16/1
FAZ-S20/1
FAZ-S25/1
FAZ-S32/1
FAZ-S40/1
278606
278607
278608
278609
278610
278611
278612
278613
278614
278615
278616
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
10
10
10
10
10
10
10
10
10
10
10
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
FAZ-S1/2
FAZ-S2/2
FAZ-S3/2
FAZ-S4/2
FAZ-S6/2
FAZ-S10/2
FAZ-S16/2
FAZ-S20/2
FAZ-S25/2
FAZ-S32/2
FAZ-S40/2
278805
278806
278807
278808
278809
278810
278811
278812
278813
278814
278815
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
2-pole
1
2
3
4
6
10
16
20
25
32
40
Chapter 4.1.1. – 14
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ Miniature Circuit Breakers (MCBs)
Characteristic Z
Rated Rated
current voltage
In (A) (V)
SG06811
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
1-pole
0,5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
SG07011
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-Z0,5/1
FAZ-Z1/1
FAZ-Z1,6/1
FAZ-Z2/1
FAZ-Z3/1
FAZ-Z4/1
FAZ-Z6/1
FAZ-Z8/1
FAZ-Z10/1
FAZ-Z13/1
FAZ-Z16/1
FAZ-Z20/1
FAZ-Z25/1
FAZ-Z32/1
FAZ-Z40/1
FAZ-Z50/1
FAZ-Z63/1
278617
278618
278619
278620
278621
278622
278623
278624
278625
106020
278626
278627
278628
278629
278630
278631
278632
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-Z0,5/2
FAZ-Z1/2
FAZ-Z1,6/2
FAZ-Z2/2
FAZ-Z3/2
FAZ-Z4/2
FAZ-Z6/2
FAZ-Z8/2
FAZ-Z10/2
FAZ-Z13/2
FAZ-Z16/2
FAZ-Z20/2
FAZ-Z25/2
FAZ-Z32/2
FAZ-Z40/2
FAZ-Z50/2
FAZ-Z63/2
278816
278817
278818
278819
278820
278821
278822
278823
278824
106021
278825
278826
278827
278828
278829
278830
278831
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
2-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Chapter 4.1.1. – 15
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated
Rated
current voltage
(V)
In (A)
SG07111
Rated
voltage
UL1077
(V)
Breaking
capacity
acc. to
UL1077
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-Z0,5/3
FAZ-Z1/3
FAZ-Z1,6/3
FAZ-Z2/3
FAZ-Z3/3
FAZ-Z4/3
FAZ-Z6/3
FAZ-Z8/3
FAZ-Z10/3
FAZ-Z13/3
FAZ-Z16/3
FAZ-Z20/3
FAZ-Z25/3
FAZ-Z32/3
FAZ-Z40/3
FAZ-Z50/3
FAZ-Z63/3
278918
278919
278920
278921
278922
278923
278924
278925
278926
106022
278927
278928
278929
278930
278931
278932
278933
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
FAZ-Z0,5/4
FAZ-Z1/4
FAZ-Z1,6/4
FAZ-Z2/4
FAZ-Z3/4
FAZ-Z4/4
FAZ-Z6/4
FAZ-Z8/4
FAZ-Z10/4
FAZ-Z13/4
FAZ-Z16/4
FAZ-Z20/4
FAZ-Z25/4
FAZ-Z32/4
FAZ-Z40/4
FAZ-Z50/4
FAZ-Z63/4
279106
279107
279108
279109
279110
279111
279112
279113
279114
106023
279115
279116
279117
279118
279119
279120
279121
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
3-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
SG07211
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
4-pole
0.5
1
1.6
2
3
4
6
8
10
13
16
20
25
32
40
50
63
Chapter 4.1.1. – 16
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-PN Miniature Circuit Breakers (MCBs)
Characteristic B
Rated Rated
current voltage
In (A) (V)
SG08311
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
Type
Designation
Article No.
Units
per
package
FAZ-PN-B6/1N
FAZ-PN-B10/1N
FAZ-PN-B13/1N
FAZ-PN-B16/1N
FAZ-PN-B20/1N
FAZ-PN-B25/1N
FAZ-PN-B32/1N
FAZ-PN-B40/1N
279146
279147
279148
279149
279150
279151
279152
279153
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
Type
Designation
Article No.
Units
per
package
FAZ-PN-C2/1N
FAZ-PN-C4/1N
FAZ-PN-C6/1N
FAZ-PN-C10/1N
FAZ-PN-C13/1N
FAZ-PN-C16/1N
FAZ-PN-C20/1N
FAZ-PN-C25/1N
FAZ-PN-C32/1N
FAZ-PN-C40/1N
279154
279155
279156
279157
279158
279159
279160
279161
279162
279163
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
1+N-pole (1MU)
6
10
13
16
20
25
32
40
240
240
240
240
240
240
240
240
6
6
6
6
6
6
6
6
10
10
10
10
10
10
10
10
FAZ-PN Miniature Circuit Breakers (MCBs)
Characteristic C
Rated Rated
current voltage
In (A) (V)
SG08311
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
1+N-pole (1MU)
2
4
6
10
13
16
20
25
32
40
240
240
240
240
240
240
240
240
240
240
6
6
6
6
6
6
6
6
6
6
10
10
10
10
10
10
10
10
10
10
Chapter 4.1.1. – 17
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-HS Miniature Circuit Breakers (MCBs)
Characteristic B
Rated Rated
current voltage
In (A) (V)
SG08411
Type
Designation
Article No.
Units
per
package
240
10
FAZ-B4/1-HS
279274
12/120
240
10
FAZ-B4/2-HS
279275
1/60
1-pole
4
SG12911
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
2-pole
4
FAZ Miniature Circuit Breakers
Accessories:
Auxiliary switch for subsequent installation
Auxiliary switch for subsequent installation
Tripping signal contact for subsequent installation
Shunt trip release
Undervoltage release
ZP-IHK
ZP-WHK
ZP-NHK
ZP-ASA
Z-USA
Z-USD
Chapter 4.1.1. – 18
286052
286053
248437
248438, 248439
258288, 248289, 248290
248292, 248291
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications FAZ
Technical data
B Curve
Electrical
Approvals
Standards
Short-circuit trip response
Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole
Two-, three-pole
Two poles in series
Thermal tripping characteristics
Single-pole
Multi-pole
Short-circuit ratings (at max. voltage)
Single-pole
Two-, three-pole
Single-pole
Two poles in series
Miniature Circuit Breaker—IEC
Current range
Maximum voltage ratings—IEC 60947-2
Single-pole
Two-, three-pole
Maximum Voltage Ratings—IEC 60898
Single-pole
Two-, three-pole
Thermal tripping characteristics
Single-pole
Multi-pole
Interrupt ratings (at max. voltage)
IEC 60947-2
IEC 60898
Operational switching capacity
Max. back-up fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole
Mounting
Degree of protection
Terminals top and bottom
Supply connection
Terminal capacity [mm2]
Torque
Thickness of busbar material
Mounting position
C Curve
D Curve
UR (UL 1077), CSA (CSA 22.2 No. 235)
IEC/EN 60947-2
3–5 In
5–10 In
10–20 In
1–63A
0.5–63A
0.5–40A
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
5 kA
5 kA
10 kA @ 48 Vdc
10 kA @ 96 Vdc
1–63A
0.5–63A
0.5–63A
230 Vac
48 Vdc
230/400 Vac
230 Vac
48 Vdc
230/400 Vac
230 Vac
48 Vdc
230/400 Vac
240 Vac
48 Vdc
240/415 Vac
240 Vac
48 Vdc
240/415 Vac
240 Vac
48 Vdc
240/415 Vac
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
3
> 10000 (1 operation = ON/OFF)
10g–120 ms
-40 to +75°C
3
> 10000 (1 operation = ON/OFF)
10g–120 ms
-40 to +75°C
3
> 10000 (1 operation = ON/OFF)
10g–120 ms
-40 to +75°C
80 mm
Finger and back-of-hand proof
17.5 mm
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
1 x 25 / 2 x 10
2.4 Nm
0.8–2 mm
As required
80 mm
Finger and back-of-hand proof
17.5 mm
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
1 x 25 / 2 x 10
2.4 Nm
0.8–2 mm
As required
80 mm
Finger and back-of-hand proof
17.5 mm
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
1 x 25 / 2 x 10
2.4 Nm
0.8–2 mm
As required
Chapter 4.1.1. – 19
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications FAZ
Technical Data (continued)
K Curve
Electrical
Approvals
Standards
Short-circuit trip response
Supplementary Protectors—UL/CSA
Current range
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-, four-pole and
three-pole + neutral
Two poles in series
Thermal tripping characteristics
Single-pole
Multi-pole
Short-circuit ratings (at max. voltage)
Single-pole
Single-pole + neutral
Two-, three-, four-pole
Miniature Circuit Breaker—IEC
Current range
Maximum voltage ratings—IEC 60947-2
Single-pole, single-pole + neutral
Two-, three-, four-pole,
three-pole + neutral
Thermal tripping characteristics
Single-pole
Multi-pole
Interrupt ratings (at max. voltage)
IEC 60947-2
IEC 60898
Operational switching capacity
Max. back-up fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole
Mounting
Degree of protection
Terminals top and bottom
Supply connection
Terminal capacity [mm2]
Torque
Thickness of busbar material
Mounting position
S Curve
Z Curve
UR (UL 1077), CSA (CSA 22.2 No. 235), CE, VDE
IEC/EN 60947-2
8–12 In
13–17 In
2–3 In
0.5–63A
0.5–40A
1–63A
277 Vac
48 Vdc
277 Vac
48 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
480Y/277 Vac
96 Vdc
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
0.5–63A
0.5–40A
1–63A
240 Vac
240 Vac
240 Vac
240/415 Vac
240/415 Vac
240/415 Vac
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
15 kA
15 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
3
> 10000 (1 operation = ON/OFF)
10g–120 ms
-5 to +40°C
3
> 10000 (1 operation = ON/OFF)
10g–120 ms
-5 to +40°C
3
> 10000 (1 operation = ON/OFF)
10g–120 ms
-5 to +40°C
80 mm
Finger and back-of-hand proof
17.5 mm
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
1 x 25 / 2 x 10
2.4 Nm
0.8–2 mm
As required
80 mm
Finger and back-of-hand proof
17.5 mm
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
1 x 25 / 2 x 10
2.4 Nm
0.8–2 mm
As required
80 mm
Finger and back-of-hand proof
17.5 mm
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
1 x 25 / 2 x 10
2.4 Nm
0.8–2 mm
As required
Connection diagram
1-pole
1+N-pole (2MU)
2-pole
3-pole
3+N-pole
Chapter 4.1.1. – 20
4-pole
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Dimensions (mm) FAZ
1-pole
1+N-pole, 2-pole
3-pole
3+N-pole, 4-pole
Chapter 4.1.1. – 21
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Tripping Characteristic FAZ
Characteristics B, C and D - IEC/EN60898-1
Characteristic K - IEC/EN 60947-2
Characteristic S - IEC/EN 60947-2
Characteristic S - UL1077
Chapter 4.1.1. – 22
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Tripping Characteristic FAZ
Characteristic Z - IEC/EN 60947-2
Characteristic Z - UL1077
Chapter 4.1.1. – 23
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Internal Resistance FAZ
Type B
Type C
At room temperature (single pole)
In [A]
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
* 50Hz
Z* [mΩ]
1120
922
922
335
234
211
184
87.7
73.5
46.8
30.5
17.5
16.9
13.4
8.0
8.0
7.2
5.0
3.7
2.6
2.1
2.0
R [mΩ]
1102
912
912
333
230
208
180
87.2
72.8
46.3
30.4
17.4
16.8
13.3
7.9
7.9
7.1
4.9
3.7
2.5
2.1
2.0
At room temperature (single pole)
In [A]
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
* 50Hz
Z* [mΩ]
68500
27500
4680
2280
1120
589
589
335
234
131
143
87.7
73.5
39.3
30.5
14.1
13.5
13.4
8.0
8.0
7.2
5.0
3.7
2.6
2.1
2.0
R [mΩ]
68300
27400
4670
2250
1100
587
587
333
230
130
141
87.2
72.8
39.1
30.4
14.0
13.4
13.3
7.9
7.9
7.1
4.9
3.7
2.5
2.1
2.0
Type D
At room temperature (single pole)
In [A]
0.5
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
* 50Hz
Z* [mΩ]
4680
772
512
512
250
153
131
143
87.7
65.4
39.3
19.5
14.1
11.3
10.1
8.0
8.0
4.9
3.9
3.5
2.7
R [mΩ]
4670
770
508
508
249
153
130
141
87.2
65.1
39.1
19.5
14.0
11.2
10.1
7.9
7.9
4.9
3.8
3.4
2.6
Chapter 4.1.1. – 24
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Fault Loop Impedance FAZ
Max. allowed value for the Fault Loop Impedance ZS
(acc. to DIN VDE 0100, part 410)
U0 = 230 V
Tripping time
In/A
1
1.5
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Type B
0,4s
Zs (Ω)
40,4
26,9
20,2
16,1
13,5
11,5
10,1
8,1
6,7
5,0
4,0
3,4
3,1
2,7
2,5
2,0
1,6
1,3
1,0
0,8
0,6
5s
Zs (Ω)
40,4
26,9
20,2
16,1
13,5
11,5
10,1
8,1
6,7
5,0
4,0
3,4
3,1
2,7
2,5
2,0
1,6
1,3
1,0
0,8
0,6
Type C
0,4s
Zs (Ω)
24,3
16,2
12,2
9,7
8,1
7,0
6,1
4,9
4,1
3,0
2,4
2,0
1,9
1,6
1,5
1,2
1,0
0,8
0,6
0,5
0,4
5s
Zs (Ω)
40,4
26,9
20,2
16,1
13,5
11,5
10,1
8,1
6,7
5,0
4,0
3,4
3,1
2,7
2,5
2,0
1,6
1,3
1,0
0,8
0,6
Type D
0,4s
Zs (Ω)
12,4
8,3
6,2
5,0
4,1
3,6
3,1
2,5
2,1
1,6
1,2
1,0
1,0
0,8
0,8
0,6
0,5
0,4
0,3
0,2
0,2
5s
Zs (Ω)
40,4
26,9
20,2
16,1
13,5
11,5
10,1
8,1
6,7
5,0
4,0
3,4
3,1
2,7
2,5
2,0
1,6
1,3
1,0
0,8
0,6
Zs=RM.C.B.+RLoop
Data/factors taken from the time-current characteristic FAZ
For other rated voltages U0:
U0 = 240 V: Zs * 1,04 applies
U0 = 127 V: Zs * 0,55 applies
Chapter 4.1.1. – 25
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Power Loss at In FAZ
Type B
Type C
1p
In [A]
P [W]
1
1.6
1.5
2.3
1.6
2.5
2
1.4
2.5
1.5
3
2.5
3.5
2.5
4
1.4
5
1.9
6
1.8
8
2.1
10
1.9
12
2.8
13
2.5
15
2.1
16
2.2
20
3.2
25
3.0
32
3.7
40
3.4
50
4.5
63
5.2
*symmetrical load
1pN
2p
3p
3pN*
P [W]
1.7
2.5
2.7
1.5
1.7
2.7
2.8
1.6
2.1
2.0
2.3
2.1
3.2
2.9
2.4
2.6
3.6
3.5
4.4
4.1
5.4
6.3
P [W]
3.1
4.6
4.9
2.8
3.1
5.0
5.1
2.9
3.8
3.6
4.1
3.9
5.9
5.3
4.4
4.7
6.6
6.4
8.1
7.5
9.9
11.5
P [W
4.7
6.9
7.4
4.1
4.6
7.6
7.8
4.4
5.8
5.5
6.3
5.9
8.7
7.8
6.5
6.9
9.8
9.4
12.1
11.2
14.9
17.2
P [W]
4.8
7.2
7.6
4.3
4.7
7.8
8.0
4.5
6.0
5.6
6.5
6.1
9.0
8.1
6.7
7.2
10.1
9.7
12.5
11.5
15.3
17.7
1pN
2p
3p
3pN*
P [W]
1.3
0.9
1.3
1.4
1.1
1.1
1.3
1.4
1.6
1.8
1.6
1.5
1.7
2.0
2.2
2.4
2.6
2.2
2.9
4.0
3.8
P [W]
2.4
1.6
2.3
2.5
2.0
1.9
2.4
2.6
2.9
3.3
2.9
2.6
3.0
3.6
4.0
4.4
4.7
4.1
5.2
7.4
7.0
P [W
3.5
2.4
3.5
3.8
3.0
2.9
3.6
3.9
4.4
5.1
4.4
4.0
4.6
5.3
5.9
6.5
6.9
6.1
7.7
11.1
10.4
P [W]
3.7
2.5
3.6
3.9
3.1
3.0
3.7
4.0
4.5
5.3
4.6
4.2
4.7
5.4
6.1
6.7
7.2
6.2
7.9
11.4
10.7
1p
In [A]
P [W]
0.16
2.2
0.25
2.0
0.5
1.2
0.75
1.3
1
1.6
1.5
1.5
1.6
1.6
2
1.4
2.5
1.5
3
1.2
3.5
1.3
4
1.4
5
1.9
6
1.5
8
2.1
10
1.5
12
2.1
13
2.5
15
2.1
16
2.2
20
3.2
25
3.0
32
3.7
40
3.4
50
4.5
63
5.2
*symmetrical load
1pN
2p
3p
3pN*
P [W]
2.4
2.2
1.3
1.4
1.7
1.6
1.7
1.5
1.7
1.3
1.4
1.6
2.1
1.6
2.3
1.7
2.4
2.9
2.4
2.6
3.6
3.5
4.4
4.1
5.4
6.3
P [W]
4.4
4.0
2.4
2.6
3.1
2.9
3.1
2.8
3.1
2.4
2.6
2.9
3.8
2.9
4.1
3.0
4.4
5.3
4.4
4.7
6.6
6.4
8.1
7.5
9.9
11.5
P [W
6.7
6.1
3.5
3.9
4.7
4.4
4.7
4.1
4.6
3.6
3.9
4.4
5.8
4.4
6.3
4.6
6.5
7.8
6.5
6.9
9.8
9.4
12.1
11.2
14.9
17.2
P [W]
6.9
6.3
3.7
4.1
4.8
4.6
4.9
4.3
4.7
3.7
4.0
4.5
6.0
4.6
6.5
4.7
6.8
8.1
6.7
7.2
10.1
9.7
12.5
11.5
15.3
17.7
Type D
1p
In [A]
P [W]
0.5
1.2
1
0.8
1.5
1.2
1.6
1.3
2
1.0
2.5
1.0
3
1.2
3.5
1.3
4
1.4
5
1.7
6
1.5
8
1.3
10
1.5
12
1.7
13
1.9
15
2.1
16
2.2
20
2.0
25
2.5
32
3.4
40
3.2
*symmetrical load
Chapter 4.1.1. – 26
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Influence of Ambient Temperature FAZ
On Load Carrying Capacity (temperature derating)
IN [A]
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
Ambient temperature T [°C]
-40
-30
-20
-10
0.2
0.2
0.19
0.19
0.32
0.31
0.3
0.29
0.64
0.62
0.6
0.58
0.96
0.93
0.9
0.87
1.3
1.2
1.2
1.2
1.9
1.9
1.8
1.7
2
2
1.9
1.9
2.6
2.5
2.4
2.3
3.2
3.1
3
2.9
3.8
3.7
3.6
3.5
4.5
4.4
4.2
4.1
5.1
5
4.8
4.7
6.4
6.2
6
5.8
7.7
7.5
7.2
7
10.2
9.9
9.6
9.3
13
12
12
12
15
15
14
14
17
16
16
15
19
19
18
17
20
20
19
19
26
25
24
23
32
31
30
29
41
40
38
37
51
50
48
47
64
62
60
58
81
78
76
73
0
0.18
0.28
0.56
0.84
1.1
1.7
1.8
2.2
2.8
3.4
3.9
4.5
5.6
6.7
9
11
13
15
17
18
22
28
36
45
56
71
10
0.17
0.27
0.54
0.81
1.1
1.6
1.7
2.2
2.7
3.3
3.8
4.3
5.4
6.5
8.7
11
13
14
16
17
22
27
35
43
54
68
20
0.17
0.26
0.52
0.78
1
1.6
1.7
2.1
2.6
3.1
3.7
4.2
5.2
6.3
8.4
10
13
14
16
17
21
26
33
42
52
66
30
0.16
0.25
0.5
0.75
1
1.5
1.6
2
2.5
3
3.5
4
5
6
8
10
12
13
15
16
20
25
32
40
50
63
35
0.16
0.25
0.49
0.74
0.99
1.5
1.6
2
2.5
3
3.4
3.9
4.9
5.9
7.9
9.9
12
13
15
16
20
25
32
39
49
62
Chapter 4.1.1. – 27
40
0.15
0.24
0.48
0.73
0.97
1.5
1.5
1.9
2.4
2.9
3.4
3.9
4.8
5.8
7.7
9.7
12
13
15
15
19
24
31
39
48
61
45
0.15
0.24
0.47
0.71
0.95
1.4
1.5
1.9
2.4
2.8
3.3
3.8
4.7
5.7
7.6
9.5
11
12
14
15
19
24
30
38
47
60
50
0.15
0.23
0.46
0.69
0.93
1.4
1.5
1.9
2.3
2.8
3.2
3.7
4.6
5.6
7.4
9.3
11
12
14
15
19
23
30
37
46
58
55
0.14
0.23
0.45
0.68
0.9
1.4
1.4
1.8
2.3
2.7
3.2
3.6
4.5
5.4
7.2
9
11
12
14
14
18
23
29
36
45
57
60
0.14
0.22
0.44
0.66
0.89
1.3
1.4
1.8
2.2
2.7
3.1
3.5
4.4
5.3
7.1
8.9
11
12
13
14
18
22
28
35
44
56
65
0.14
0.22
0.43
0.65
0.87
1.3
1.4
1.7
2.2
2.6
3
3.5
4.3
5.2
6.9
8.7
10
11
13
14
17
22
28
35
43
55
70
0.14
0.21
0.42
0.64
0.85
1.3
1.4
1.7
2.1
2.5
3
3.4
4.2
5.1
6.8
8.5
10
11
13
14
17
21
27
34
42
53
75
0.13
0.21
0.41
0.62
0.83
1.2
1.3
1.7
2.1
2.5
2.9
3.3
4.1
5
6.6
8.3
10
11
12
13
17
21
26
33
41
52
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Energy FAZ
Type B (IEC/EN60947-2)
Type C (IEC/EN60947-2)
Type D (IEC/EN60947-2)
Type K
Chapter 4.1.1. – 28
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Energy FAZ
Type S
Type Z
Type FAZ-...-HS
Chapter 4.1.1. – 29
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Current FAZ
Type B (IEC/EN60898)
Type C (IEC/EN60898)
Type D (IEC/EN60898)
Type K
Chapter 4.1.1. – 30
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Current FAZ
Type S
Type B (IEC/EN60947-2)
Type C (IEC/EN60947-2)
Type D (IEC/EN60947-2)
Chapter 4.1.1. – 31
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Short Circuit Selectivity FAZ towards NH-00 Fuses
In case of short circuit, there is selectivity between the miniature circuit breakers FAZ and the upstream fuses up to the specified values of the selectivity
limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective
devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link NH-00*)
Short circuit selectivity characteristic C towards fuse link NH-00*)
FAZ
FAZ
NH-00 gL/gG
In [A] 16
20
1.0
0.9
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
0.75
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.5
0.8
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.0
0.9
2.0
<0.51) 0.5
2.5
<0.51)
0.5
3.0
<0.51) 0.5
3.5
<0.51)
0.9
4
<0.51) <0.51) 0.8
5
<0.51)
0.7
1.1
1.6
2.2
3.6
4.8
6
<0.51) <0.51) 0.7
1.1
1.5
2.0
3.3
4.3
8
<0.51)
0.5
<0.51)
<0.51)
25
32
35
40
50
63
80
100 125 160
NH-00 gL/gG
In [A] 16
25
32
35
40
50
63
80
100 125 160
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
2.5
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.5
<0.51) 0.6
1.3
4.2
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.0
2.3
10.02)
10.02)
10.02)
2.0
<0.51)
0.6
1.0
2.5
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
0.9
2.1
8.0
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
2.5
<0.51) 0.5
1.0
2.1
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.8
5.5
10.02)
10.02)
10.02)
3.0
<0.51)
0.7
1.2
1.8
2.6
4.7
6.6
10.02) 10.02) 10.02) 10.02)
1.3
2.3
4.3
10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.0
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
<0.51)
3.5
<0.51) <0.51) 0.7
1.1
1.7
2.4
4.2
6.0
10.02) 10.02) 10.02) 10.02)
8.9
10.02)
10.02)
4
<0.51)
0.7
1.0
1.5
2.1
3.6
5.0
10.0
10.02) 10.02) 10.02)
7.6
10.02) 10.02) 10.02)
5
<0.51) <0.51) 0.6
0.8
1.2
1.7
2.8
3.8
8.7
10.02) 10.02) 10.02)
10.02)
10.02)
6
<0.51)
0.5
0.8
1.2
1.5
2.5
3.3
5.7
10.02) 10.02) 10.02)
<0.51) <0.51) 0.5
0.8
1.1
1.5
2.3
2.9
4.9
10.02) 10.02) 10.02)
0.5
0.7
1.0
1.4
2.0
2.5
3.8
8.0
10.02) 10.02)
10.02)
0.6
1.0
1.3
1.7
2.6
3.3
5.2
10.02)
10
<0.51) 0.6
0.9
1.2
1.5
2.2
2.7
4.0
9.0
10.02) 10.02)
8
13
<0.51)
10.02)
10
16
20
<0.51)
<0.51)
0.6
0.8
1.1
1.4
2.1
2.6
3.8
7.9
10.02)
0.5
0.7
1.0
1.3
1.9
2.4
3.4
6.4
9.3
10.02)
13
1.0
1.3
1.9
2.4
3.6
7.0
10.02) 10.02)
16
1.0
1.3
1.8
2.3
3.3
6.0
8.8
10.02)
1.0
1.2
1.7
2.2
3.2
5.5
7.7
10.02)
1.6
2.1
3.0
5.2
7.3
10.02)
2.1
2.9
5.0
7.0
10.02)
2.8
4.8
6.7
10.0
4.5
6.3
9.5
5.9
8.4
20
0.7
1.0
1.3
1.9
2.4
3.3
6.0
8.7
10.02)
25
0.7
1.0
1.3
1.8
2.3
3.2
5.7
8.0
10.02)
20
25
2.2
3.1
5.4
7.6
10.02)
40
2.1
3.0
5.1
7.2
10.02)
32
50
1.9
2.8
4.7
6.6
9.5
40
4.4
6.3
8.6
50
32
0.9
1.2
1.7
63
63
Short circuit selectivity characteristic D towards fuse link NH-00*)
FAZ
NH-00 gL/gG
In [A] 16
20
25
32
35
40
50
63
80
100 125 160
0.5
2.1
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02) 10.02) 10.02)
1.0
<0.51) 0,6
1.4
4.3
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.5
<0.51)
0.9
1.6
2.7
4.0
8.0
10.02) 10.02) 10.02) 10.02) 10.02)
2.0
<0.51) <0.51) 0.8
1.3
2.1
3.1
6.0
8.6
10.02) 10.02) 10.02) 10.02)
2.5
<0.51)
0.7
1.2
1.8
2.6
4.8
6.9
10.02) 10.02) 10.02) 10.02)
3.0
<0.51) <0.51) 0.7
1.1
1.7
2.4
4.3
6.0
10.02) 10.02) 10.02) 10.02)
3.5
<0.51)
0.7
1.1
1.7
2.4
4.2
5.6
10.02) 10.02) 10.02) 10.02)
4
<0.51) <0.51) 0.7
1.0
1.6
2.2
3.8
5.2
10.0
10.02) 10.02) 10.02)
<0.51)
<0.51)
<0.51)
5
<0.51)
0.6
0.9
1.4
1.9
3.2
4.1
7.1
10.02) 10.02) 10.02)
6
<0.51) 0.5
0.8
1.2
1.6
2.6
3.3
5.5
10.02) 10.02) 10.02)
8
0.5
0.8
1.1
1.5
2.2
2.7
4.1
8.7
10.02) 10.02)
10
0.5
0.7
1.0
1.3
1.9
2.5
3.6
7.2
10.02) 10.02)
1.0
1.3
1.9
2.3
3.4
6.5
9.5
10.02)
1.1
1.6
2.0
3.0
5.5
8.0
10.02)
1.4
1.8
2.8
5.0
7.5
10.02)
1.8
2.7
4.8
7.0
10.02)
13
16
20
25
32
40
2.4
4.1
6.2
9.3
4.0
6.0
9.0
1)
Selectivity limit current Is under 0.5 kA
Selectivity limit current Is = rated breaking capacity Icn of the MCB
Shaded fields: no selectivity
2)
Chapter 4.1.1. – 32
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Short Circuit Selectivity FAZ towards D01-D03 fuse link
In case of short circuit, there is selectivity between the miniature circuit breakers FAZ and the upstream fuses up to the specified values of the selectivity
limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective
devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link D01-D03*)
Short circuit selectivity characteristic C towards fuse link D01-D03*)
FAZ
D01-D03 gL/gG
FAZ
In [A]
10
In [A]
10
1.0
<0.51) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
0.75
<0.51) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.5
<0.51) 4.1
1.0
<0.51) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
2.0
<0.51) <0.51) 0.6
2.5
<0.51)
16
20
25
35
50
63
80
100
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.0
10.02) 10.02) 10.02) 10.02) 10.02)
0.6
3.0
<0.51) <0.51) 0.5
3.5
<0.51)
0.5
0.9
4
<0.51) <0.51) 0.5
0.9
<0.51)
<0.51)
D01-D03 gL/gG
16
20
25
35
50
63
80
100
1.5
<0.51) 0.5
0.6
0.9
10.02) 10.02) 10.02) 10.02) 10.02)
1.0
10.02)
10.02)
2.0
<0.51)
0.5
0.7
10.02) 10.02) 10.02) 10.02) 10.02)
1.0
10.02) 10.02) 10.02) 10.02) 10.02)
10.02)
10.02)
10.02)
<0.51)
2.5
<0.51) <0.51) 0.5
0.7
10.02) 10.02) 10.02) 10.02) 10.02)
7.0
10.02)
10.02)
3.0
<0.51)
0.6
1.9
5.2
10.02) 10.02) 10.02)
2.5
10.02) 10.02) 10.02) 10.02)
10.02)
10.02)
<0.51)
<0.51)
3.5
<0.51) <0.51) <0.51) 0.6
1.8
4.7
9.5
10.02) 10.02)
10.02)
4
<0.51)
0.6
1.6
4.0
7.6
10.02) 10.02)
5
<0.51)
0.5
0.8
1.7
4.0
7.0
10.02)
6
<0.51) 0.5
0.8
1.6
3.6
6.0
10.02) 10.02)
5
<0.51) <0.51) 0.5
1.3
3.1
5.7
10.02) 10.02)
6
<0.51)
1.2
2.7
4.5
10.02) 10.02)
8
<0.51) <0.51) <0.51) 1.2
2.5
4.0
8.6
10.02)
1.2
2.3
3.1
5.4
10.02)
8
0.5
0.8
1.4
2.8
4.3
8.2
10.02)
10
0.5
0.7
1.3
2.4
3.4
6.0
10.02)
13
<0.51)
10
<0.51)
<0.51)
<0.51)
0.7
1.2
2.3
3.2
5.3
10.02)
0.6
1.1
2.2
2.9
4.6
10.0
13
1.1
2.2
3.0
4.9
10.02)
20
1.1
2.1
2.8
4.4
9.3
16
1.1
2.1
2.8
4.4
9.5
25
1.1
2.0
2.7
4.2
8.7
20
1.0
2.0
2.6
4.0
8.3
16
32
2.6
4.0
8.0
25
40
2.0
2.5
3.8
7.5
32
50
2.3
3.4
6.7
40
6.2
50
63
<0.51)
<0.51)
<0.51)
1.9
2.5
3.8
7.8
2.5
3.7
7.3
3.5
7.0
6.5
63
Short circuit selectivity characteristic D towards fuse link D01-D03*)
FAZ
D01-D03 gL/gG
In [A]
10
16
20
25
35
50
63
80
100
0.5
<0.51)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
1.0
<0.51) <0.51) 0.7
1.3
10.02) 10.02) 10.02) 10.02) 10.02)
1.5
<0.51)
0.6
0.9
2.8
9.0
10.02) 10.02) 10.02)
2.0
<0.51) <0.51) 0.6
0.8
2.2
6.7
10.02) 10.02) 10.02)
2.5
<0.51)
0.5
0.7
1.9
5.4
10.02) 10.02) 10.02)
3.0
<0.51) <0.51) 0.5
0.7
1.8
4.8
9.3
10.02) 10.02)
3.5
<0.51)
0.5
0.7
1.7
4.7
8.6
10.02) 10.02)
4
<0.51) 0.5
0.7
1.7
4.6
7.7
10.02) 10.02)
5
<0.51)
0.6
1.5
3.5
5.8
10.02) 10.02)
6
<0.51) 0.5
1.3
2.9
4.5
9.0
10.02)
8
<0.51)
0.5
1.2
2.4
3.5
6.0
10.02)
0.5
1.1
2.2
3.0
5.0
10.02)
1.1
2.1
2.9
4.6
10.02)
16
1.9
2.6
3.9
9.0
20
1.7
10
13
25
32
<0.51)
<0.51)
<0.51)
<0.51)
2.3
3.5
8.0
2.2
3.4
7.5
2.9
40
6.0
5.7
1)
Selectivity limit current Is under 0.5 kA
Selectivity limit current Is = rated breaking capacity Icn of the MCB
Shaded fields: no selectivity
2)
Chapter 4.1.1. – 33
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Short Circuit Selectivity FAZ towards DII-DIV fuse link
In case of short circuit, there is selectivity between the miniature circuit breakers FAZ and the upstream fuses up to the specified values of the selectivity
limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective
devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link DII-DIV*)
Short circuit selectivity characteristic C towards fuse link DII-DIV*)
FAZ
FAZ
DII-DIV gL/gG
16
20
25
35
50
63
80
100
DII-DIV gL/gG
In [A]
10
In [A]
10
16
1.0
<0.51) 1.2
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
0.75
1.0
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.5
<0.51) 1.0
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.0
<0.51) 1.2
2.0
<0.51) <0.51) 0.8
2.5
<0.51)
1.6
10.02) 10.02) 10.02) 10.02) 10.02)
0.8
3.0
<0.51) <0.51) 0.8
3.5
<0.51)
20
25
35
50
63
80
100
10.02) 10.02) 10.02) 10.02) 10.02) 10.02) 10.02)
1.5
<0.51) <0.51) 1.0
2.2
10.02) 10.02) 10.02) 10.02) 10.02)
1.5
10.02)
10.02)
2.0
<0.51)
0.8
1.6
10.02) 10.02) 10.02) 10.02) 10.02)
1.4
10.02) 10.02) 10.02) 10.02) 10.02)
2.5
<0.51) <0.51) 0.8
1.4
10.02) 10.02) 10.02) 10.02) 10.02)
0.7
1.3
10.02)
10.02)
10.02)
3.0
<0.51)
0.8
0.9
10.02) 10.02) 10.02) 10.02) 10.02)
4
<0.51) <0.51) 0.6
1.0
3.6
10.02) 10.02) 10.02) 10.02)
5
<0.51)
<0.51)
<0.51)
<0.51)
10.02)
10.02)
10.02)
10.02)
10.02)
<0.51)
<0.51)
3.5
<0.51) <0.51) 0.6
0.9
2.2
4.5
10.02) 10.02) 10.02)
10.02)
4
<0.51)
0.6
0.8
1.8
3.6
9.7
10.02) 10.02)
5
<0.51) <0.51) 0.6
0.7
1.5
2.7
7.3
10.02) 10.02)
0.6
0.9
2.0
3.5
8.5
10.02)
6
<0.51) 0.6
0.9
1.8
3.2
7.4
10.02) 10.02)
8
<0.51)
6
<0.51)
0.6
1.4
2.4
5.5
10.02) 10.02)
8
<0.51) <0.51) 0.6
1.3
2.2
4.7
8.7
10.02)
1.3
2.0
3.6
5.4
10.02)
10
0.5
0.8
1.6
2.6
5.2
8.3
10.02)
0.5
0.8
1.4
2.2
3.9
6.0
10.02)
10
<0.51)
0.5
0.7
1.3
2.0
3.6
5.4
10.02)
0.6
1.2
1.9
3.2
4.6
8.4
13
1.3
1.9
3.3
5.0
9.4
20
1.2
1.8
3.1
4.4
7.8
16
1.2
1.8
3.2
4.4
8.0
25
1.2
1.8
3.0
4.2
7.3
20
1.2
1.8
3.1
4.1
7.0
1.7
1.7
2.8
3.8
6.5
2.7
3.7
6.2
3.5
5.9
13
0.5
16
32
2.8
3.9
6.8
25
40
2.7
3.8
6.5
32
50
2.5
3.5
5.7
40
5.3
50
63
<0.51)
0.6
5.5
63
Short circuit selectivity characteristic D towards fuse link DII-DIV*)
FAZ
DII-DIV gL/gG
In [A]
10
16
20
25
35
50
63
80
100
3.0
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
10.02)
0.5
0.5
1.0
<0.51) <0.51) 1.0
2.4
10.02) 10.02) 10.02) 10.02) 10.02)
1.5
<0.51)
0.7
1.2
3.5
7.7
10.02) 10.02) 10.02)
2.0
<0.51) <0.51) 0.6
1.0
2.8
5.8
10.02) 10.02) 10.02)
2.5
<0.51)
0.6
1.4
2.3
4.6
10.02) 10.02) 10.02)
3.0
<0.51) <0.51) 0.6
0.9
2.3
4.3
10.02) 10.02) 10.02)
3.5
<0.51)
0.6
0.9
2.1
4.0
10.02) 10.02) 10.02)
4
<0.51) 0.6
0.9
2.0
3.8
9.5
10.02) 10.02)
5
<0.51)
0.5
0.7
1.7
3.1
7.0
10.02) 10.02)
6
0.5
0.7
1.5
2.6
5.3
9.1
10.02)
8
<0.51)
0.7
1.4
2.2
3.9
6.0
10.02)
0.7
1.2
1.9
3.4
5.0
9.5
1.2
10
13
<0.51)
<0.51)
<0.51)
1.8
3.2
4.6
8.6
16
1.6
2.7
4.0
7.4
20
1.5
2.5
3.5
6.7
2.4
3.4
6.2
2.8
5.0
25
32
40
4.8
1)
Selectivity limit current Is under 0.5 kA
Selectivity limit current Is = rated breaking capacity Icn of the MCB
Shaded fields: no selectivity
2)
Chapter 4.1.1. – 34
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Short-Circuit Selectivity
Between FAZ-B and NZM 1/2
NZM
FAZ
Selectivity-limit current Is [kA] for selectivity between FAZ-B and NZM (overload and short-circuit release unit NZM at max. value).
NZM...1-A...
NZM...2-A...
In [A]
Icu = 25 (50) kA
Icu = 25 (50)(100)(150) kA
FAZ-B
40
50
63
80
100
125
40
50
63
80
100
125
160
200
250
1
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
2
2
15
15
15
15
15
3
15
15
15
15
15
15
15
15
3
1.2
2
3
3
10
15
1.5
1.5
3
5
15
15
15
15
15
4
1.2
2
3
3
8
15
1.2
1.5
3
4
15
15
15
15
15
6
1.2
2
2.5
3
5
10
1.2
1.5
2.5
3
15
15
15
15
15
10
1.2
1.5
2
2
4
10
1
1.5
2.5
3
10
10
10
10
10
13
1
1.5
2
2
4
10
1
1.2
2
3
10
10
10
10
10
16
1
1.2
1.5
2
3
8
1
1.2
1.5
2.5
10
10
10
10
10
20
0.8
1.2
1.5
1.5
3
8
1
1.2
1.5
1.5
10
10
10
10
10
25
0.7
1.2
1.5
1.5
3
7
0.8
1
1.5
2
10
10
10
10
10
32
-
1.2
1
1.5
2
6
-
1
1.5
2
8
8
8
8
10
40
-
-
1
1.5
2
5
-
-
1.2
1.5
7
7
7
7
10
50
-
-
-
1.2
1.5
4
-
-
-
1.5
6
6
6
6
10
63
-
-
-
-
1.5
3
-
-
-
-
6
6
6
6
10
Between FAZ-C and NZM 1/2
NZM
FAZ
Selectivity-limit current Is [kA] for selectivity between FAZ-C and NZM (overload and short-circuit release unit NZM at max. value).
NZM...1-A...
NZM...2-A...
In [A]
Icu = 25 (50) kA
FAZ-C
40
50
63
80
100
125
Icu = 25 (50)(100)(150) kA
40
50
63
80
100
125
160
200
250
0.5
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
1
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
2
2
15
15
15
15
15
3
15
15
15
15
15
15
15
15
3
1.2
2
3
3
10
15
1.5
1.5
3
5
15
15
15
15
15
4
1.2
2
3
3
8
15
1.2
1.5
3
4
15
15
15
15
15
6
1.2
2
2.5
3
5
10
1.2
1.5
2.5
3
15
15
15
15
15
10
1.2
1.5
2
2
4
10
1
1.5
2.5
3
10
10
10
10
10
13
1
1.5
2
2
4
10
1
1.2
2
3
10
10
10
10
10
16
1
1.2
1.5
2
3
8
1
1.2
1.5
2.5
10
10
10
10
10
20
0.8
1.2
1.5
1.5
3
8
1
1.2
1.5
1.5
10
10
10
10
10
25
0.7
1.2
1.5
1.5
3
7
0.8
1
1.5
2
10
10
10
10
10
32
-
1.2
1
1.5
2
6
-
1
1.5
2
8
8
8
8
10
40
-
-
1
1.5
2
5
-
-
1.2
1.5
7
7
7
7
10
50
-
-
-
1.2
1.5
4
-
-
-
1.5
6
6
6
6
10
63
-
-
-
-
1.5
3
-
-
-
-
6
6
6
6
10
Chapter 4.1.1. – 35
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Short-Circuit Selectivity FAZ
Between FAZ-D and NZM 1/2
NZM
FAZ
In [A]
Selectivity-limit current Is [kA] for selectivity between FAZ-D and NZM (overload and short-circuit release unit NZM at max. value).
NZM...1-A...
NZM...2-A...
Icu = 25 (50) kA
Icu = 25 (50)(100)(150) kA
FAZ-D
40
50
63
80
100
125
40
50
63
80
100
125
160
200
250
0.5
9
15
15
15
15
15
9
15
15
15
15
15
15
15
15
1
0.5
0.7
1.1
1.9
4.2
15
0.5
0.7
1.1
1.9
4.2
15
15
15
15
1.5
0.3
0.6
0.8
1.1
1.6
2.6
0.3
0.6
0.8
1.1
1.6
2.6
5
15
15
2
0.3
0.5
0.75
0.95
1.4
2.4
0.3
0.5
0.75
0.95
1.4
2.4
4.5
10
15
2.5
0.3
0.5
0.75
0.95
1.3
2.3
0.3
0.5
0.75
0.95
1.3
2.3
4.2
9
15
3
0.3
0.5
0.7
0.9
1.3
2.1
0.3
0.5
0.7
0.9
1.3
2.1
3.6
7
15
3.5
0.3
0.5
0.7
0.9
1.3
2
0.3
0.5
0.7
0.9
1.3
2
3.3
5.6
10
4
0.3
0.5
0.7
0.9
1.3
1.9
0.3
0.5
0.7
0.9
1.3
1.9
3
4.7
8
5
0.3
0.5
0.7
0.9
1.3
1.9
0.3
0.5
0.7
0.9
1.3
1.9
3
4.4
7
6
0.3
0.5
0.6
0.9
1.3
1.8
0.3
0.5
0.6
0.9
1.3
1.8
2.8
4
6
8
0.3
0.3
0.6
0.75
1
1.3
0.3
0.3
0.6
0.75
1
1.3
1.8
2.7
4
10
0.3
0.3
0.6
0.75
0.95
1.2
0.3
0.3
0.6
0.75
0.95
1.2
1.7
2.4
3.6
13
0.3
0.3
0.5
0.7
0.9
1.1
0.3
0.3
0.5
0.7
0.9
1.1
1.6
2.2
3.2
16
-
0.3
0.5
0.65
0.8
1.1
-
0.3
0.5
0.65
0.8
1.1
1.5
2.1
3
20
-
-
0.5
0.65
0.8
1.1
-
-
0.5
0.65
0.8
1.1
1.4
2.1
3
25
-
-
0.5
0.65
0.8
1.1
-
-
0.5
0.65
0.8
1.1
1.4
1.9
2.7
32
-
-
-
-
0.8
1.1
-
-
-
-
0.8
1.1
1.4
1.9
2.7
40
-
-
-
-
-
1
-
-
-
-
-
1
1.4
1.8
2.6
Chapter 4.1.1. – 36
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Back-up Protection FAZ
FAZ/C through PLHT/C
Upstream PLHT protects downstream FAZ up to the specified prospective short-circuit current. Test acc. to IEC 60947.2 -A.6
PLHT/C
In [A]
In [A]
FAZ/C
20
25
32
40
50
63
80
100
125
1
25
25
25
25
25
25
20
20
15 kA
2
25
25
25
25
25
25
20
20
15 kA
4
25
25
25
25
25
25
20
20
15 kA
6
25
25
25
25
25
25
20
20
15 kA
10
25
25
25
25
25
25
20
20
15 kA
13
25
25
25
25
25
25
20
20
15 kA
16
25
25
25
25
25
25
20
20
15 kA
20
1)
25
25
25
25
25
20
20
15 kA
25
1)
1)
25
25
25
25
20
20
15 kA
32
1)
1)
1)
25
25
25
20
20
-
40
1)
1)
1)
1)
25
25
20
20
-
50
1)
1)
1)
1)
1)
25
20
20
-
63
1)
1)
1)
1)
1)
1)
-
-
-
1) In (PLHT) ≤ In (FAZ)
FAZ / NZM7
FAZ / CL-PKZ0
Back-up tests acc. to EN/IEC 60947-2, App. A: U = 1.05 Ue, (O - t - CO)
FAZ-In/1(2,3,4)/B(C) + NZM7-40(...100)
FAZ-In/1(2,3,4)/B(C) + CL-PKZ0
In [A]
Ue = 230/400 V
In [A]
Ue = 230/400 V
0.16
65 kA
0.16
25 kA
0.25
65 kA
0.25
25 kA
0.5
65 kA
0.5
25 kA
0.75
65 kA
0.75
25 kA
1
65 kA
1
25 kA
1.5
65 kA
1.5
25 kA
2
65 kA
2
25 kA
2.5
65 kA
2.5
25 kA
3
65 kA
3
25 kA
3.5
65 kA
3.5
25 kA
4
65 kA
4
25 kA
5
45 kA
5
20 kA
6
45 kA
6
20 kA
8
45 kA
8
20 kA
10
45 kA
10
20 kA
12
45 kA
12
20 kA
13
45 kA
13
20 kA
15
45 kA
15
20 kA
16
45 kA
16
20 kA
20
45 kA
20
18 kA
25
45 kA
25
18 kA
32
45 kA
32
18 kA
40
25 kA
40
18 kA
50
25 kA
50
15 kA
63
25 kA
63
15 kA
Chapter 4.1.1. – 37
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Back-up Protection FAZ
FAZ / NZMB1
FAZ / NZMN1
Ue = 230/400 V: Icu (FAZ) = 15 kA
Ue = 230/400 V: Icu (NZMB1) = 25 kA
Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO)
(Settings NZMB1: Ir, Irm at max. volumes)
Ue = 230/400 V: Icu (FAZ) = 15 kA
Ue = 230/400 V: Icu (NZMN1) = 25 kA
Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO)
(Settings NZM at max. values)
FAZ-In/1(2,3,4)/B(C) + NZMB1
FAZ-In/1(2,3,4)/B(C) + NZMN1
In [A]
Ue = 230/400 V
In [A]
Ue = 230/400 V
0.16
25 kA
0.16
25 kA
0.25
25 kA
0.25
25 kA
0.5
25 kA
0.5
25 kA
0.75
25 kA
0.75
25 kA
1
25 kA
1
25 kA
1.5
25 kA
1.5
25 kA
2
25 kA
2
25 kA
2.5
25 kA
2.5
25 kA
3
25 kA
3
25 kA
3.5
25 kA
3.5
25 kA
4
25 kA
4
25 kA
5
25 kA
5
25 kA
6
25 kA
6
25 kA
8
25 kA
8
25 kA
10
25 kA
10
25 kA
12
25 kA
12
25 kA
13
25 kA
13
25 kA
15
25 kA
15
25 kA
16
25 kA
16
25 kA
20
20 kA
20
20 kA
25
20 kA
25
20 kA
32
20 kA
32
20 kA
40
20 kA
40
20 kA
50
15 kA
50
15 kA
63
15 kA
63
15 kA
Chapter 4.1.1. – 38
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Back-up Protection FAZ
FAZ / NZMB2
FAZ / NZMN2
Ue = 230/400 V: Icu (FAZ) = 15 kA
Ue = 230/400 V: Icu (NZMB2) = 25 kA
Ue = 133/230 V: Icu (FAZ) = 20 kA
Ue = 133/230 V: Icu (NZMB2) = 30 kA
Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO)
(Settings NZM at max. values)
Ue = 230/400 V: Icu (FAZ) = 15 kA
Ue = 230/400 V: Icu (NZMN2) = 50 kA
Ue = 133/230 V: Icu (FAZ) = 20 kA
Ue = 133/230 V: Icu (NZMN2) = 85 kA
Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO)
(Settings NZM at max. values)
FAZ-In/1(2,3,4)/B(C) + NZMN2
FAZ-In/1(2,3,4)/B(C) + NZMB2
In [A]
Ue = 230/400 V
Ue = 133/230 V
In [A]
Ue = 230/400 V
Ue = 133/230 V
0.16
25 kA
30 kA
0.16
50 kA
85 kA
0.25
25 kA
30 kA
0.25
50 kA
85 kA
0.5
25 kA
30 kA
0.5
50 kA
85 kA
0.75
25 kA
30 kA
0.75
50 kA
85 kA
1
25 kA
30 kA
1
50 kA
85 kA
1.5
25 kA
30 kA
1.5
50 kA
85 kA
2
25 kA
30 kA
2
50 kA
85 kA
2.5
25 kA
30 kA
2.5
50 kA
85 kA
3
25 kA
30 kA
3
50 kA
85 kA
3.5
25 kA
30 kA
3.5
50 kA
85 kA
4
25 kA
30 kA
4
50 kA
85 kA
5
25 kA
25 kA
5
50 kA
80 kA
6
25 kA
25 kA
6
50 kA
80 kA
8
25 kA
25 kA
8
50 kA
80 kA
10
25 kA
25 kA
10
50 kA
80 kA
12
20 kA
25 kA
12
30 kA
60 kA
13
20 kA
25 kA
13
30 kA
60 kA
15
20 kA
25 kA
15
30 kA
60 kA
16
20 kA
25 kA
16
30 kA
60 kA
20
20 kA
25 kA
20
30 kA
60 kA
25
20 kA
25 kA
25
30 kA
60 kA
32
20 kA
25 kA
32
30 kA
60 kA
40
15 kA
20 kA
40
20 kA
40 kA
50
15 kA
20 kA
50
20 kA
40 kA
63
15 kA
20 kA
63
20 kA
40 kA
Chapter 4.1.1. – 39
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Back-up Protection FAZ
FAZ / NZMH2
FAZ / NZML2
Ue = 230/400 V: Icu (FAZ) = 15 kA
Ue = 230/400 V: Icu (NZMH2) = 150 kA
Ue = 133/230 V: Icu (FAZ) = 20 kA
Ue = 133/230 V: Icu (NZMH2) = 150 kA
Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO)
(Settings NZM at max. values)
Ue = 230/400 V: Icu (FAZ) = 15 kA
Ue = 230/400 V: Icu (NZML2) = 150 kA
Ue = 133/230 V: Icu (FAZ) = 20 kA
Ue = 133/230 V: Icu (NZML2) = 150 kA
Back-up test acc. EN/IEC 60947-2, app. A: U = 1.05Ue, (O - t - CO)
(Settings NZM at max. values)
FAZ-In/1(2,3,4)/B(C) + NZML2
FAZ-In/1(2,3,4)/B(C) + NZMH2
In [A]
Ue = 230/400 V
Ue = 133/230 V
In [A]
Ue = 230/400 V
Ue = 133/230 V
0.16
50 kA
85 kA
0.16
50 kA
85 kA
0.25
50 kA
85 kA
0.25
50 kA
85 kA
0.5
50 kA
85 kA
0.5
50 kA
85 kA
0.75
50 kA
85 kA
0.75
50 kA
85 kA
1
50 kA
85 kA
1
50 kA
85 kA
1.5
50 kA
85 kA
1.5
50 kA
85 kA
2
50 kA
85 kA
2
50 kA
85 kA
2.5
50 kA
85 kA
2.5
50 kA
85 kA
3
50 kA
85 kA
3
50 kA
85 kA
3.5
50 kA
85 kA
3.5
50 kA
85 kA
4
50 kA
85 kA
4
50 kA
85 kA
5
50 kA
80 kA
5
50 kA
80 kA
6
50 kA
80 kA
6
50 kA
80 kA
8
50 kA
80 kA
8
50 kA
80 kA
10
50 kA
80 kA
10
50 kA
80 kA
12
30 kA
60 kA
12
30 kA
60 kA
13
30 kA
60 kA
13
30 kA
60 kA
15
30 kA
60 kA
15
30 kA
60 kA
16
30 kA
60 kA
16
30 kA
60 kA
20
30 kA
60 kA
20
30 kA
60 kA
25
30 kA
60 kA
25
30 kA
60 kA
32
30 kA
60 kA
32
30 kA
60 kA
40
20 kA
40 kA
40
20 kA
40 kA
50
20 kA
40 kA
50
20 kA
40 kA
63
20 kA
40 kA
63
20 kA
40 kA
Chapter 4.1.1. – 40
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Back-up Protection FAZ
FAZ / NH
Ue = 230 V: Icu (FAZ) = 15 (10) kA (acc. to IEC/EN 60947)
Ue = 500 V: Icu (NH00 125 A gL / gG) = 120kA
FAZ-In/B,(C),(D)... + NH00 125 A gL/gG
In [A]
IT-system U = 230 V
0.5
50 kA
1
50 kA
2
50 kA
3
50 kA
4
50 kA
6
50 kA
10
50 kA
13
50 kA
16
50 kA
20
50 kA
25
50 kA
32
50 kA
40
50 kA
50
50 kA
63
50 kA
Chapter 4.1.1. – 41
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Overload Selectivity FAZ
FAZ-B(C)(D) to FAZ-B
FAZ
Upstream side FAZ, Characteristic B
Downstream side FAZ, Characteristic B, C, D
FAZ
x ... Selectivity range (i.e. only the downstream switch drops in case I< Is)
Downstream side
FAZ Characteristic B
Upstream side
FAZ Characteristic B
Type B rated current In [A]
2
3
4
6
Selectivity limiting current Is [A] 7
10.5 14
21
2
x
x
x
3
x
x
4
x
6
10
13
16
20
25
32
40
50
63
Downstream side
FAZ Characteristic C
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
0.5
1
2
3
4
6
8
10
13
16
20
25
32
40
50
63
FAZ Characteristic B
2
3
4
6
7
10.5 14
21
x
x
x
x
x
x
x
x
x
x
x
Downstream side
FAZ Characteristic D
Upstream side
FAZ Characteristic B
Type B rated current In [A]
2
3
4
6
Selectivity limiting current Is [A] 7
10.5 14
21
2
4
6
10
13
16
20
25
32
40
10
35
x
x
x
x
13
45.5
x
x
x
x
x
16
56
x
x
x
x
x
x
20
70
x
x
x
x
x
x
x
25
87.5
x
x
x
x
x
x
x
x
32
112
x
x
x
x
x
x
x
x
x
40
140
x
x
x
x
x
x
x
x
x
x
50
175
x
x
x
x
x
x
x
x
x
x
x
63
220.5
x
x
x
x
x
x
x
x
x
x
x
x
10
35
x
x
x
x
x
13
45.5
x
x
x
x
x
x
16
56
x
x
x
x
x
x
x
20
70
x
x
x
x
x
x
x
x
25
87.5
x
x
x
x
x
x
x
x
x
32
112
x
x
x
x
x
x
x
x
x
x
40
140
x
x
x
x
x
x
x
x
x
x
x
50
175
x
x
x
x
x
x
x
x
x
x
x
x
63
220.5
x
x
x
x
x
x
x
x
x
x
x
x
x
10
35
x
13
45.5
x
16
56
x
x
20
70
x
x
x
25
87.5
x
x
x
32
112
x
x
x
x
40
140
x
x
x
x
x
50
175
x
x
x
x
x
x
63
220.5
x
x
x
x
x
x
x
Chapter 4.1.1. – 42
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Overload Selectivity FAZ
FAZ-B(C)(D) to FAZ-C
FAZ
Upstream side FAZ, Characteristic C
Downstream side FAZ, Characteristic B, C, D
FAZ
x ... Selectivity range (i.e. only the downstream switch drops in case I< Is)
Downstream side
FAZ Characteristic B
Upstream side
FAZ Characteristic C
Type B rated current In [A]
0.5
1
2
3
Selectivity limiting current Is [A] 2.85 5.7
11.4 17.1
2
x
3
4
6
10
13
16
20
25
32
40
50
63
Downstream side
FAZ Characteristic C
Upstream side
FAZ Characteristic C
Type B rated current In [A]
0.5
1
2
3
Selectivity limiting current Is [A] 2.85 5.7
11.4 17.1
0.5
x
x
x
1
x
x
2
x
3
4
6
8
10
13
16
20
25
32
40
50
63
Downstream side
FAZ Characteristic D
Upstream side
FAZ Characteristic C
Type B rated current In [A]
0.5
1
2
3
Selectivity limiting current Is [A] 2.85 5.7
11.4 17.1
2
4
6
10
13
16
20
25
32
40
4
22.8
x
x
6
34.2
x
x
x
8
45.6
x
x
x
x
10
57
x
x
x
x
13
74.1
x
x
x
x
x
16
91.2
x
x
x
x
x
x
20
114
x
x
x
x
x
x
x
25
142.5
x
x
x
x
x
x
x
x
32
182.4
x
x
x
x
x
x
x
x
x
40
228
x
x
x
x
x
x
x
x
x
x
50
285
x
x
x
x
x
x
x
x
x
x
x
63
359.1
x
x
x
x
x
x
x
x
x
x
x
x
4
22.8
x
x
x
x
6
34.2
x
x
x
x
x
8
45.6
x
x
x
x
x
x
10
57
x
x
x
x
x
x
x
13
74.1
x
x
x
x
x
x
x
x
16
91.2
x
x
x
x
x
x
x
x
x
20
114
x
x
x
x
x
x
x
x
x
x
25
142.5
x
x
x
x
x
x
x
x
x
x
x
32
182.4
x
x
x
x
x
x
x
x
x
x
x
x
40
228
x
x
x
x
x
x
x
x
x
x
x
x
x
50
285
x
x
x
x
x
x
x
x
x
x
x
x
x
x
63
359.1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
4
22.8
6
34.2
x
8
45.6
x
x
10
57
x
x
13
74.1
x
x
x
16
91.2
x
x
x
20
114
x
x
x
x
25
142.5
x
x
x
x
x
32
182.4
x
x
x
x
x
x
40
228
x
x
x
x
x
x
x
50
285
x
x
x
x
x
x
x
x
63
359.1
x
x
x
x
x
x
x
x
Chapter 4.1.1. – 43
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Overload Selectivity FAZ
FAZ-B(C)(D) to FAZ-D
FAZ
Upstream side FAZ, Characteristic D
Downstream side FAZ, Characteristic B, C, D
FAZ
x ... Selectivity range (i.e. only the downstream switch drops in case I< Is)
Downstream side
FAZ Characteristic B
Upstream side
FAZ Characteristic D
Type B rated current In [A]
2
4
6
10
Selectivity limiting current Is [A] 21
42
63
105
2
x
x
x
3
x
x
x
4
x
x
6
x
10
13
16
20
25
32
40
50
63
Downstream side
FAZ Characteristic C
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
0.5
1
2
3
4
6
8
10
13
16
20
25
32
40
50
63
FAZ Characteristic D
2
4
6
10
21
42
63
105
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Downstream side
FAZ Characteristic D
Upstream side
FAZ Characteristic D
Type B rated current In [A]
2
4
6
10
Selectivity limiting current Is [A] 21
42
63
105
2
x
x
x
4
x
x
6
x
10
13
16
20
25
32
40
13
136.5
x
x
x
x
x
16
168
x
x
x
x
x
x
20
210
x
x
x
x
x
x
x
25
262.5
x
x
x
x
x
x
x
x
32
336
x
x
x
x
x
x
x
x
x
40
420
x
x
x
x
x
x
x
x
x
x
13
136.5
x
x
x
x
x
x
x
x
16
168
x
x
x
x
x
x
x
x
x
20
210
x
x
x
x
x
x
x
x
x
x
25
262.5
x
x
x
x
x
x
x
x
x
x
x
32
336
x
x
x
x
x
x
x
x
x
x
x
x
40
420
x
x
x
x
x
x
x
x
x
x
x
x
x
13
136.5
x
x
x
x
16
168
x
x
x
x
x
20
210
x
x
x
x
x
x
25
262.5
x
x
x
x
x
x
x
32
336
x
x
x
x
x
x
x
x
40
420
x
x
x
x
x
x
x
x
x
Chapter 4.1.1. – 44
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Overload Selectivity FAZ
FAZ-B(C)(D) to PLHT-B
PLHT
Upstream side PLHT, Characteristic B
Downstream side FAZ, Characteristic B, C, D
FAZ
x ... Selectivity range (i.e. only the downstream switch drops in case I< Is)
PLHT
20
65
x
x
x
x
x
x
x
Characteristic B
25
32
40
81
104
130
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
0.5
1
2
3
4
6
8
10
13
16
20
25
32
40
50
63
PLHT
20
65
x
x
x
x
x
x
x
x
Characteristic B
25
32
40
81
104
130
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
2
4
6
10
13
16
20
25
32
40
PLHT
20
65
x
x
Characteristic B
25
32
40
81
104
130
x
x
x
x
x
x
x
x
x
x
Downstream side
FAZ Characteristic D
Downstream side
FAZ Characteristic C
Downstream side
FAZ Characteristic B
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
2
3
4
6
10
13
16
20
25
32
40
50
63
50
163
x
x
x
x
x
x
x
x
x
x
x
63
205
x
x
x
x
x
x
x
x
x
x
x
x
80
260
x
x
x
x
x
x
x
x
x
x
x
x
x
100
325
x
x
x
x
x
x
x
x
x
x
x
x
x
125
406
x
x
x
x
x
x
x
x
x
x
x
x
x
50
163
x
x
x
x
x
x
x
x
x
x
x
x
63
205
x
x
x
x
x
x
x
x
x
x
x
x
x
80
260
x
x
x
x
x
x
x
x
x
x
x
x
x
x
100
325
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
125
406
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
50
163
x
x
x
x
x
63
205
x
x
x
x
x
x
80
260
x
x
x
x
x
x
x
100
325
x
x
x
x
x
x
x
x
125
406
x
x
x
x
x
x
x
x
x
Chapter 4.1.1. – 45
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Overload Selectivity FAZ
FAZ-B(C)(D) to PLHT-C
PLHT
Upstream side PLHT, Characteristic C
Downstream side FAZ, Characteristic B, C, D
FAZ
x ... Selectivity range (i.e. only the downstream switch drops in case I< Is)
PLHT
20
130
x
x
x
x
x
x
x
Characteristic C
25
32
40
163 208 260
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
0.5
1
2
3
4
6
8
10
13
16
20
25
32
40
50
63
PLHT
20
130
x
x
x
x
x
x
x
x
x
x
Characteristic C
25
32
40
163 208 260
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
2
4
6
10
13
16
20
25
32
40
PLHT
20
130
x
x
x
x
Characteristic C
25
32
40
163 208 260
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Downstream side
FAZ Characteristic D
Downstream side
FAZ Characteristic C
Downstream side
FAZ Characteristic B
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
2
3
4
6
10
13
16
20
25
32
40
50
63
50
325
x
x
x
x
x
x
x
x
x
x
x
63
410
x
x
x
x
x
x
x
x
x
x
x
x
80
520
x
x
x
x
x
x
x
x
x
x
x
x
x
100
650
x
x
x
x
x
x
x
x
x
x
x
x
x
125
813
x
x
x
x
x
x
x
x
x
x
x
x
x
50
325
x
x
x
x
x
x
x
x
x
x
x
x
x
x
63
410
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
80
520
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
100
650
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
125
813
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
50
325
x
x
x
x
x
x
x
x
63
410
x
x
x
x
x
x
x
x
x
80
520
x
x
x
x
x
x
x
x
x
x
100
650
x
x
x
x
x
x
x
x
x
x
125
813
x
x
x
x
x
x
x
x
x
x
Chapter 4.1.1. – 46
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Overload Selectivity FAZ
FAZ-B(C)(D) to PLHT-D
PLHT
Upstream side PLHT, Characteristic D
Downstream side FAZ, Characteristic B, C, D
FAZ
x ... Selectivity range (i.e. only the downstream switch drops in case I< Is)
PLHT
20
230
x
x
x
x
x
x
x
Characteristic D
25
32
40
285 365 450
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
0.5
1
2
3
4
6
8
10
13
16
20
25
32
40
50
63
PLHT
20
230
x
x
x
x
x
x
x
x
x
x
Characteristic D
25
32
40
285 365 450
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
2
4
6
10
13
16
20
25
32
40
PLHT
20
230
x
x
x
x
x
x
Characteristic D
25
32
40
285 365 450
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Downstream side
FAZ Characteristic D
Downstream side
FAZ Characteristic C
Downstream side
FAZ Characteristic B
Upstream side
Type B rated current In [A]
Selectivity limiting current Is [A]
2
3
4
6
10
13
16
20
25
32
40
50
63
50
550
x
x
x
x
x
x
x
x
x
x
x
63
680
x
x
x
x
x
x
x
x
x
x
x
x
80
850
x
x
x
x
x
x
x
x
x
x
x
x
x
100
1020
x
x
x
x
x
x
x
x
x
x
x
x
x
50
550
x
x
x
x
x
x
x
x
x
x
x
x
x
x
63
680
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
80
850
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
100
1020
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
50
550
x
x
x
x
x
x
x
x
x
x
63
680
x
x
x
x
x
x
x
x
x
x
80
850
x
x
x
x
x
x
x
x
x
x
100
1020
x
x
x
x
x
x
x
x
x
x
Chapter 4.1.1. – 47
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Influence of the Line Frequency FAZ
On the Instantaneous Tripping Current IMA
IMA(f)/IMA(50Hz) [%]
Line Frequency f [Hz]
50
60
162/3
91
100
101
100
106
200
115
300
134
400
141
Chapter 4.1.1. – 48
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
UL508 Busbars for FAZ
lb-in
50
Nm
5.5
Z2
Z2
BB-IP/5
BB-UL EC/3
BB-UL-TEPA/35
BB-UL-TE/50
Z2
Z2
lb-in
35
lb-in
22
lb-in
50
Nm
4
BB-UL-TEP/35
Nm
2.5
BB-UL-TE/50
Ue
f
le
Nm
5.5
BB-UL
WBCxxx
UL508
EN/IEC
60947-2
480 V AC
50/60 Hz ---------115 A @ 40°C
240/690V AC
50/60 Hz
160 A @ 30°C
#1-14 AWG
60/75°C Cu
1.5 – 50 mm 2
Cu
0.56 in
14 mm
UL508
EN/IEC
60947-2
UL508
BB-UL-TEP/35 /
BB-UL-TEPA/35
Ue
f
lpk
le
Infeed at the
start of the busbar
Infeed at the
center of the busbar
EN/IEC
60947-2
480 V AC
690V AC
50/60 Hz
10kA
15kA
18mm²
25mm²
80A@40 °C
100A@30°C
200A@30°C
160A@40°C
*
-UL508 SHORT CIRCUIT RATINGS
-SUITABLE FOR USE ON A CIRCUIT CAPABLE OF
DELIVERING NOT MORE THAN 10,000 RMS
Ue
f
le
480 V AC
240/690V AC
50/60 Hz ---------- 50/60 Hz
115 A@40°C
80 A@30°C
#2-14 AWG
60/75°C Cu
2.5 – 35 mm 2
Cu
0.56 in
14 mm
SYMETRICAL AMPERES, 600 VOLTS MAXIMUM.
-SUITABLE FOR USE ON A CIRCUIT CAPABLE OF
DELIVERING NOT MORE THAN 100,000 RMS
SYMETRICAL AMPERES, 600 VOLTS MAXIMUM
WHEN PROTECTED BY A CL ASS J FUSE RATED
175A.
Chapter 4.1.1. – 49
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
BB Busbars for FAZ
Article No.
121981
121982
121983
121984
121987
121988
121989
121990
121991
121992
121995
121996
121997
in prep.
121998
121999
122000
122001
A/35
Chapter 4.1.1. – 50
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Auxiliary Contacts and Voltage Trips for FAZ
Circuit
Diagram
Description
Rated Operational
Voltage
Type
Designation
Article No.
Units
per
package
230 Vac
FAZ-XHIN11
286054
1
230 Vac
FAZ-XAM002
262414
1
115 Vac
FAZ-XUA(115VAC) 212049
1
230 Vac
FAZ-XUA(230VAC) 212051
1
400 Vac
FAZ-XUA(400VAC) 212053
1
12–110 Vac
12–60 Vdc
110–415 Vac
110–230 Vdc
FAZ-XAA-C-12-110VAC 278518
1
FAZ-XAA-C-110-415VAC 278519
1
IS/SPE-1TE
101911
1
221954800
221954900
221953900
1
1
1
Standard Auxiliary Contact
SG13411
• 1NO/1NC
• Installs on left side of FAZ or shunt trip
• Max. one per FAZ (1077) device
• Switches when FAZ is tripped
electrically or manually
Auxiliary/Trip Indicating Contact
SG84411
Two-pole auxiliary
mode
• Small selector screw changes mode
• Two Form C (changeover) contacts
• Installs on left side of FAZ or shunt trip
• Auxiliary contacts switch when FAZ is
tripped electrically or manually
• Trip indicating contact switches only
when FAZ is tripped electrically
Trip indicating
mode
SG85411
Undervoltage Trip
• Prevents FAZ from operating unless
voltage is present
• Installs on left side of FAZ
• Includes test button
SG12311
Shunt Trip
• Allows remote trip of FAZ
• Installs on left side of FAZ
Padlock Hasp (for all FAZ)
• Prevents reactivation of the device
during maintenance
• Holds one padlock
Screw Lock (for all FAZ except -NA and -RT)
2MU
3MU
4MU
Chapter 4.1.1. – 51
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications Accessories for FAZ
Technical Data
FAZ-XHIN
FAZ-XAM002
Electrical
Contact function
FAZ-XAA-C
FAZ-XUA
—
—
—
115 Vac
230 Vac
400 Vac
—
Rated operational voltage Un
1A + 1B
2 C/O
250 Vac
Voltage range
—
Voltage range
—
Closing threshold [x Un]
Tripping threshold [x Un]
Rated frequency f
General use (UL/CSA)
AC—230/240 Vac
DC—110/120 Vdc
Pilot duty
Conventional free air thermal current Ith
Rated operational current
AC-13 Ie
AC-15 Ie
DC-13 Ie
Rated insulation voltage Ui
Minimum operating voltage per contract Umin
Rated impulse withstand voltage (1.2/50µ) Uimp
Rated conditional short-circuit current
with 6A back-up fuse ISC
Max. admissible back-up fuse
Mechanical
Standard front dimension
Device height
Mounting width
Degree of protection enclosed
Terminal protection
—
—
50/60 Hz
12–110 Vac
12–60 Vdc
110–415 Vac
110–230 Vdc
—
—
50/60 Hz
2/2A
0.5/0.5A
A600/Q600
4A
—
—
—
—
—
—
—
—
3A (250 Vac)
2A (250 Vac)
0.5A (110 Vdc)
250 Vac
5 Vdc
2.5 kV
—
—
—
—
—
—
—
—
—
—
—
—
1 kA
4A gL
—
—
—
—
45 mm
80 mm
8.8 mm
IP40
Protection against
electric shock to IEC 536
Lift terminals
45 mm
80 mm
17.6 mm
IP40
Protection against
electric shock to IEC 536
Twin-purpose terminals
45 mm
80 mm
17.8 mm
IP40
Protection against
electric shock to IEC 536
Twin-purpose terminals
0.5–2.5
0.5–2.5
0.8–1.0 Nm (7–9 lb-in)
1–2.5
1–2.5
2.4 Nm (21 lb-in)
2 x (1–2.5)
2 x (1–2.5)
0.8 Nm (7 lb-in)
Terminals
Terminal capacity [mm2]
Solid
Flexible
Tightening torque of terminal screws
—
0.8
0.5
50/60 Hz
Allowable Combinations of Accessories
Chapter 4.1.1. – 52
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Dimensions (mm) Accessories for FAZ
Auxiliary Contacts
FAZ-XHI11
FAZ-XAM002
Shunt Releases
Undervoltage Releases
FAZ-XAA
FAZ-XUA
Chapter 4.1.1. – 53
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Miniature Circuit Breakers FAZ-T, FAZ-DC, FAZ-NA, FAZ-RT
SG13111
FAZ-T
• High-quality miniature circuit breakers for industrial and commercial
applications
• Contact position indicator red - green
• Accessories suitable for subsequent installation
• Rated currents up to 125 A
• Tripping characteristics B, C, D
• Rated breaking capacity up to 25 kA according to EN 60947-2
FAZ-T
FAZ-(NA)-DC
• High-quality miniature circuit breakers for DC-applications
SG09211
• Contact position indicator red - green
• Guide for secure terminal connection
• 3-position DIN rail clip, permits removal from existing busbar system
• Comprehensive range of accessories suitable for subsequent installation
• Rated currents up to 50 A (Type NA up to 40 A)
• Tripping characteristic C
• Rated breaking capacity 10 kA according to IEC/EN 60947-2
FAZ-NA
• Up to 250 V DC pro pole (Type NA up to 125 V DC per pole)
FAZ-NA/-RT
• According to UL 489, CSA C22.2 No. 5 and also IEC 60947-2 standard
• For Applications, wich are permitted for UL 1077 or CSA C22.2 No. 235
• Auxiliary switch and voltage trips suitable for subsequent installation
• Serie with removable terminal screws (Type FAZ-..-RT), for use with ring
cable lug
• Contact position indicator red - green
• Easy mounting at DIN-rail
Chapter 4.1.1. – 54
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-T Miniature Circuit Breakers (MCBs)
Characteristic B
Rated Rated
current voltage
In (A) IEC/EN
60898-1
(V)
SG12411
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240
240
240
240
240
240
240
240
240
240
240
240
240
240
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-B1/1
FAZT-B2/1
FAZT-B3/1
FAZT-B4/1
FAZT-B6/1
FAZT-B10/1
FAZT-B12/1
FAZT-B13/1
FAZT-B15/1
FAZT-B16/1
FAZT-B20/1
FAZT-B25/1
FAZT-B32/1
FAZT-B40/1
240770
240771
240772
240777
240782
240787
240792
240793
240794
240795
240796
240797
141907
141908
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
240
240
240
240
240
240
240
240
240
240
240
240
240
240
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240
240
240
240
240
240
240
240
240
240
240
240
240
240
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-B1/1N
FAZT-B2/1N
FAZT-B3/1N
FAZT-B4/1N
FAZT-B6/1N
FAZT-B10/1N
FAZT-B12/1N
FAZT-B13/1N
FAZT-B15/1N
FAZT-B16/1N
FAZT-B20/1N
FAZT-B25/1N
FAZT-B32/1N
FAZT-B40/1N
240994
240995
240996
240997
240998
240999
241000
241001
241005
241009
241015
241019
142509
142510
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-B1/2
FAZT-B2/2
FAZT-B3/2
FAZT-B4/2
FAZT-B6/2
FAZT-B10/2
FAZT-B12/2
FAZT-B13/2
FAZT-B15/2
FAZT-B16/2
FAZT-B20/2
FAZT-B25/2
FAZT-B32/2
FAZT-B40/2
240820
240821
240822
240823
240824
240825
240826
240827
240828
240829
240830
240831
142485
142486
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1+N-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG12811
Rated
voltage
IEC/EN
60947-2
(V)
1-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG12711
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
2-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
Chapter 4.1.1. – 55
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated Rated
current voltage
In (A) IEC/EN
60898-1
(V)
SG13011
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-B1/3
FAZT-B2/3
FAZT-B3/3
FAZT-B4/3
FAZT-B6/3
FAZT-B10/3
FAZT-B12/3
FAZT-B13/3
FAZT-B15/3
FAZT-B16/3
FAZT-B20/3
FAZT-B25/3
FAZT-B32/3
FAZT-B40/3
240874
240875
240876
240877
240878
240879
240880
240881
240882
240883
240884
240885
142493
142494
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-B1/3N
FAZT-B2/3N
FAZT-B3/3N
FAZT-B4/3N
FAZT-B6/3N
FAZT-B10/3N
FAZT-B12/3N
FAZT-B13/3N
FAZT-B15/3N
FAZT-B16/3N
FAZT-B20/3N
FAZT-B25/3N
FAZT-B32/3N
FAZT-B40/3N
241060
241065
241070
241075
241080
241085
241090
241095
241100
241105
241110
241115
142517
142518
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-B1/4
FAZT-B2/4
FAZT-B3/4
FAZT-B4/4
FAZT-B6/4
FAZT-B10/4
FAZT-B12/4
FAZT-B13/4
FAZT-B15/4
FAZT-B16/4
FAZT-B20/4
FAZT-B25/4
FAZT-B32/4
FAZT-B40/4
240922
240927
240930
240931
240932
240933
240934
240935
240936
240937
240938
240939
142501
142502
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
3+N-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG13111
Rated
voltage
IEC/EN
60947-2
(V)
3-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG13211
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
4-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
Chapter 4.1.1. – 56
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-T Miniature Circuit Breakers (MCBs)
Characteristic C
Rated Rated
current voltage
In (A) IEC/EN
60898-1
(V)
SG12411
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240
240
240
240
240
240
240
240
240
240
240
240
240
240
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-C1/1
FAZT-C2/1
FAZT-C3/1
FAZT-C4/1
FAZT-C6/1
FAZT-C10/1
FAZT-C12/1
FAZT-C13/1
FAZT-C15/1
FAZT-C16/1
FAZT-C20/1
FAZT-C25/1
FAZT-C32/1
FAZT-C40/1
240798
240799
240800
240801
240802
240803
240804
240805
240806
240807
240808
240809
141909
142480
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
240
240
240
240
240
240
240
240
240
240
240
240
240
240
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240
240
240
240
240
240
240
240
240
240
240
240
240
240
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-C1/1N
FAZT-C2/1N
FAZT-C3/1N
FAZT-C4/1N
FAZT-C6/1N
FAZT-C10/1N
FAZT-C12/1N
FAZT-C13/1N
FAZT-C15/1N
FAZT-C16/1N
FAZT-C20/1N
FAZT-C25/1N
FAZT-C32/1N
FAZT-C40/1N
241022
241023
241024
241025
241026
241027
241028
241029
241030
241034
241038
241044
142511
142512
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-C1/2
FAZT-C2/2
FAZT-C3/2
FAZT-C4/2
FAZT-C6/2
FAZT-C10/2
FAZT-C12/2
FAZT-C13/2
FAZT-C15/2
FAZT-C16/2
FAZT-C20/2
FAZT-C25/2
FAZT-C32/2
FAZT-C40/2
240832
240833
240838
240843
240850
240855
240858
240859
240860
240861
240862
240863
142487
142488
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1+N-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG12811
Rated
voltage
IEC/EN
60947-2
(V)
1-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG12711
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
2-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
Chapter 4.1.1. – 57
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated Rated
current voltage
In (A) IEC/EN
60898-1
(V)
SG13011
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-C1/3
FAZT-C2/3
FAZT-C3/3
FAZT-C4/3
FAZT-C6/3
FAZT-C10/3
FAZT-C12/3
FAZT-C13/3
FAZT-C15/3
FAZT-C16/3
FAZT-C20/3
FAZT-C25/3
FAZT-C32/3
FAZT-C40/3
240886
240887
240888
240889
240890
240891
240892
240893
240894
240895
240896
240897
142495
142496
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-C1/3N
FAZT-C2/3N
FAZT-C3/3N
FAZT-C4/3N
FAZT-C6/3N
FAZT-C10/3N
FAZT-C12/3N
FAZT-C13/3N
FAZT-C15/3N
FAZT-C16/3N
FAZT-C20/3N
FAZT-C25/3N
FAZT-C32/3N
FAZT-C40/3N
241120
241125
241130
241135
241140
241145
241150
241155
241160
241165
241170
241175
142519
142520
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
25
25
20
20
FAZT-C1/4
FAZT-C2/4
FAZT-C3/4
FAZT-C4/4
FAZT-C6/4
FAZT-C10/4
FAZT-C12/4
FAZT-C13/4
FAZT-C15/4
FAZT-C16/4
FAZT-C20/4
FAZT-C25/4
FAZT-C32/4
FAZT-C40/4
240940
240941
240945
240949
240955
240959
240962
240963
240964
240965
240966
240967
142503
142504
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
3+N-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG13111
Rated
voltage
IEC/EN
60947-2
(V)
3-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG13211
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
4-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
Chapter 4.1.1. – 58
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-T Miniature Circuit Breakers (MCBs)
Characteristic D
Rated Rated
current voltage
In (A) IEC/EN
60898-1
(V)
SG12411
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
10
10
10
10
240
240
240
240
240
240
240
240
240
240
240
240
240
240
25
25
25
25
25
25
25
25
20
20
20
15
15
15
FAZT-D1/1
FAZT-D2/1
FAZT-D3/1
FAZT-D4/1
FAZT-D6/1
FAZT-D10/1
FAZT-D12/1
FAZT-D13/1
FAZT-D15/1
FAZT-D16/1
FAZT-D20/1
FAZT-D25/1
FAZT-D32/1
FAZT-D40/1
240810
240811
240812
240813
240814
240815
240816
240817
240818
240819
142481
142482
142483
142484
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
240
240
240
240
240
240
240
240
240
240
240
240
240
240
15
15
15
15
15
15
15
15
15
15
10
10
10
10
240
240
240
240
240
240
240
240
240
240
240
240
240
240
25
25
25
25
25
25
25
25
20
20
20
15
15
15
FAZT-D1/1N
FAZT-D2/1N
FAZT-D3/1N
FAZT-D4/1N
FAZT-D6/1N
FAZT-D10/1N
FAZT-D12/1N
FAZT-D13/1N
FAZT-D15/1N
FAZT-D16/1N
FAZT-D20/1N
FAZT-D25/1N
FAZT-D32/1N
FAZT-D40/1N
241048
241051
241052
241053
241054
241055
241056
241057
241058
241059
142513
142514
142515
142516
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
10
10
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
20
20
20
15
15
15
FAZT-D1/2
FAZT-D2/2
FAZT-D3/2
FAZT-D4/2
FAZT-D6/2
FAZT-D10/2
FAZT-D12/2
FAZT-D13/2
FAZT-D15/2
FAZT-D16/2
FAZT-D20/2
FAZT-D25/2
FAZT-D32/2
FAZT-D40/2
240864
240865
240866
240867
240868
240869
240870
240871
240872
240873
142489
142490
142491
142492
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1+N-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG12811
Rated
voltage
IEC/EN
60947-2
(V)
1-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG12711
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
2-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
Chapter 4.1.1. – 59
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Rated Rated
current voltage
In (A) IEC/EN
60898-1
(V)
SG13011
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
Type
Designation
Article No.
Units
per
package
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
10
10
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
20
15
15
15
FAZT-D1/3
FAZT-D2/3
FAZT-D3/3
FAZT-D4/3
FAZT-D6/3
FAZT-D10/3
FAZT-D12/3
FAZT-D13/3
FAZT-D15/3
FAZT-D16/3
FAZT-D20/3
FAZT-D25/3
FAZT-D32/3
FAZT-D40/3
240898
240899
240900
240901
240902
240903
240904
240905
240910
240915
142497
142498
142499
142500
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
10
10
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
20
15
15
15
FAZT-D1/3N
FAZT-D2/3N
FAZT-D3/3N
FAZT-D4/3N
FAZT-D6/3N
FAZT-D10/3N
FAZT-D12/3N
FAZT-D13/3N
FAZT-D15/3N
FAZT-D16/3N
FAZT-D20/3N
FAZT-D25/3N
FAZT-D32/3N
FAZT-D40/3N
241180
241181
241182
241183
241184
241185
241186
241187
241188
241189
142521
142522
142523
142524
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
10
10
10
10
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
25
25
25
25
25
25
25
25
25
25
20
15
15
15
FAZT-D1/4
FAZT-D2/4
FAZT-D3/4
FAZT-D4/4
FAZT-D6/4
FAZT-D10/4
FAZT-D12/4
FAZT-D13/4
FAZT-D15/4
FAZT-D16/4
FAZT-D20/4
FAZT-D25/4
FAZT-D32/4
FAZT-D40/4
240968
240969
240970
240971
240975
240979
240985
240989
240992
240993
142505
142506
142507
142508
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
1/30
3+N-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG13111
Rated
voltage
IEC/EN
60947-2
(V)
3-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
SG13211
Breaking
capacity
acc. to
IEC/EN
60898-1
(kA)
4-pole
1
2
3
4
6
10
12
13
15
16
20
25
32
40
Chapter 4.1.1. – 60
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications FAZ-T
Technical data
FAZ-T
Productstandard
IEC/EN 60947-2
IEC/EN 60898-1
1, 1p+N, 2, 3, 3p+N, 4
Number of poles
Mechanical specifications
Device width
17.7 mm (1p), 27 mm (1p+N), 36 mm (2p), 54 mm (3p), 72mm (3p+N),
72 mm (4p)
45 mm
80 mm
60 mm
lift terminal
1-25 mm²
M5 (with slotted screw acc. to EN ISO 4757-Z2, PZ2)
max. 2.4 Nm
tristable (on DIN rail acc. to EN 50022)
acc. to VBG4, ÖVE EN-6
Frame size
Socket size
Device depth
Terminals
Terminal capacity rigid solid/stranded wire
Terminal screw
Terminal torque
Snap on fixing
Finger proof
Degree of Protection (DIN VDE 0470)
Surface mounted
Built-in behind panel
Contact position indicator
IP 20
IP 40
red / green
Electrical specifications
Rated voltage
Rated current
Rated insulation voltage
Rated impulse withstand voltage
Un
In
Ui
Uimp
240/415 V
Type B, C, D: 1, 2, 3, 4, 6, 10, 12, 13, 15, 16, 20, 25, 32, 40 A
440 V
4 kV (1.2/50)µsec
Tripping characteristic
Conventional non-tripping current
Conventional tripping current
Reference temperature
Temperature factor
Instantaneous tripping current
Imt
Rated ultimate short-circuit braking capacity Icu (IEC/EN 60947-2)
type B
type C
type D
Rated service short-circuit braking capacity
Ics (IEC/EN 60947-2)
Rated short-circuit braking capacity
Icn (IEC/EN 60898-1)
type B
type C
type D
Selectivity class
Number of electrical operations
Number of mechanical operations
Climatic conditions
Int=1.13 In
It=1.45 In
30 °C
0.4% /K
type B: 3 In < Imt = 5 In:t (Imt) < 0.1 sec
type C: 5 In < Imt = 10 In:t (Imt) < 0.1 sec
type D: 10 In < Imt = 20 In:t (Imt) < 0.1 sec
1-25 A: 25 kA, 32-40 A: 20 kA
1-25 A: 25 kA, 32-40 A: 20 kA
1p/1p+N/2p - 1-13 A: 25 kA, 15-20 A: 20 kA, 25-40 A: 15 kA
3p/3p+N/4p - 1-16 A: 25 kA, 20 A: 20 kA, 25-40 A: 15 kA
for Icu = 25 kA --> Ics = 12.5 kA
for Icu = 20 kA --> Ics = 10 kA
for Icu = 15 kA --> Ics = 7.5 kA
1-25 A: 15 kA, 32-40 A: 10 kA
1-25 A: 15 kA, 32-40 A: 10 kA
1-16 A: 15 kA, 20-40 A: 10 kA
3 (acc. to EN 60898)
> 4000 (IEC/EN 60898)
> 10000 (IEC/EN 60947)
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Connection diagram
1-pole
1+N-pole
2-pole
3-pole
3+N-pole
Chapter 4.1.1. – 61
4-pole
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Dimensions (mm) FAZ-T
1-pole
1+N-pole
3-pole
3+N-pole, 4-pole
2-pole
Chapter 4.1.1. – 62
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Tripping Characteristic FAZ-T
Characteristics B, C and D - EN60898
Chapter 4.1.1. – 63
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Power Loss at In FAZ-T
Type B
Type C
1p
In [A]
P [W]
1
1.6
2
1.4
3
2.5
4
1.4
6
1.8
10
1.9
12
2.8
13
2.5
15
2.1
16
2.2
20
3.2
25
3.0
32
3.7
40
3.4
*symmetrical load
1pN
2p
3p
3pN*
4p
P [W]
1.7
1.5
2.7
1.6
2.0
2.1
3.2
2.9
2.4
2.6
3.6
3.5
4.4
4.1
P [W]
3.1
2.8
5.0
2.9
3.6
3.9
5.9
5.3
4.4
4.7
6.6
6.4
8.1
7.5
P [W
4.7
4.1
7.6
4.4
5.5
5.9
8.7
7.8
6.5
6.9
9.8
9.4
12.1
11.2
P [W]
4.8
4.3
7.8
4.5
5.6
6.1
9.0
8.1
6.7
7.2
10.1
9.7
12.5
11.5
P [W]
6.3
5.5
10.1
5.8
7.3
7.8
11.5
10.3
8.6
9.1
13.0
12.4
15.8
14.6
1pN
2p
3p
3pN*
4p
P [W]
0.9
1.1
1.3
1.6
1.6
1.7
2.0
2.2
2.4
2.6
2.2
2.9
4.0
3.8
P [W]
1.6
2.0
2.4
2.9
2.9
3.0
3.6
4.0
4.4
4.7
4.1
5.2
7.4
7.0
P [W
2.4
3.0
3.6
4.4
4.4
4.6
5.3
5.9
6.5
6.9
6.1
7.7
11.1
10.4
P [W]
2.5
3.1
3.7
4.5
4.6
4.7
5.4
6.1
6.7
7.2
6.2
7.9
11.4
10.7
P [W]
3.2
4.0
4.8
5.8
5.9
6.1
7.0
7.8
8.6
9.1
8.1
10.2
14.5
13.6
1p
In [A]
P [W]
1
1.6
2
1.4
3
1.2
4
1.4
6
1.5
10
1.5
12
2.1
13
2.5
15
2.1
16
2.2
20
3.2
25
3.0
32
3.7
40
3.4
*symmetrical load
1pN
2p
3p
3pN*
4p
P [W]
1.7
1.5
1.3
1.6
1.6
1.7
2.4
2.9
2.4
2.6
3.6
3.5
4.4
4.1
P [W]
3.1
2.8
2.4
2.9
2.9
3.0
4.4
5.3
4.4
4.7
6.6
6.4
8.1
7.5
P [W
4.7
4.1
3.6
4.4
4.4
4.6
6.5
7.8
6.5
6.9
9.8
9.4
12.1
11.2
P [W]
4.8
4.3
3.7
4.5
4.6
4.7
6.8
8.1
6.7
7.2
10.1
9.7
12.5
11.5
P [W]
6.3
5.5
4.8
5.8
5.9
6.1
8.6
10.3
8.6
9.1
13.0
12.4
15.8
14.6
Type D
1p
In [A]
P [W]
1
0.8
2
1.0
3
1.2
4
1.4
6
1.5
10
1.5
12
1.7
13
1.9
15
2.1
16
2.2
20
2.0
25
2.5
32
3.4
40
3.2
*symmetrical load
Chapter 4.1.1. – 64
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Influence of Ambient Temperature FAZ-T
On Load Carrying Capacity (temperature derating)
IN [A]
1
2
3
4
6
10
12
13
15
16
20
25
32
40
Ambient temperature T [°C]
-40
-30
-20
-10
1.3
1.2
1.2
1.2
2.6
2.5
2.4
2.3
3.8
3.7
3.6
3.5
5.1
5
4.8
4.7
7.7
7.5
7.2
7
13
12
12
12
15
15
14
14
17
16
16
15
19
19
18
17
20
20
19
19
26
25
24
23
32
31
30
29
41
40
38
37
51
50
48
47
0
1.1
2.2
3.4
4.5
6.7
11
13
15
17
18
22
28
36
45
10
1.1
2.2
3.3
4.3
6.5
11
13
14
16
17
22
27
35
43
20
1
2.1
3.1
4.2
6.3
10
13
14
16
17
21
26
33
42
30
1
2
3
4
6
10
12
13
15
16
20
25
32
40
300
134
400
141
35
0.99
2
3
3.9
5.9
9.9
12
13
15
16
20
25
32
39
40
0.97
1.9
2.9
3.9
5.8
9.7
12
13
15
15
19
24
31
39
45
0.95
1.9
2.8
3.8
5.7
9.5
11
12
14
15
19
24
30
38
50
0.93
1.9
2.8
3.7
5.6
9.3
11
12
14
15
19
23
30
37
55
0.9
1.8
2.7
3.6
5.4
9
11
12
14
14
18
23
29
36
60
0.89
1.8
2.7
3.5
5.3
8.9
11
12
13
14
18
22
28
35
65
0.87
1.7
2.6
3.5
5.2
8.7
10
11
13
14
17
22
28
35
70
0.85
1.7
2.5
3.4
5.1
8.5
10
11
13
14
17
21
27
34
75
0.83
1.7
2.5
3.3
5
8.3
10
11
12
13
17
21
26
33
Influence of the Line Frequency FAZ-T
On the Instantaneous Tripping Current IMA
IMA(f)/IMA(50Hz) [%]
Line Frequency f [Hz]
50
60
162/3
91
100
101
100
106
200
115
Load rating in case of circuit breakers arranged one next to the other FAZ-T
Chapter 4.1.1. – 65
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Energy FAZ-T
Type B
Type C
Type D
Chapter 4.1.1. – 66
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Current FAZ-T
Type B
Type C
Type D
Chapter 4.1.1. – 67
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-DC Miniature Circuit Breakers (MCBs)
Characteristic C
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V DC)
SG08511
Type
Designation
Article No.
Units
per
package
220
250
250
250
250
250
250
250
250
250
250
250
10
10
10
10
10
10
10
10
10
10
10
10
FAZ-C2/1-DC
FAZ-C3/1-DC
FAZ-C4/1-DC
FAZ-C6/1-DC
FAZ-C10/1-DC
FAZ-C13/1-DC
FAZ-C16/1-DC
FAZ-C20/1-DC
FAZ-C25/1-DC
FAZ-C32/1-DC
FAZ-C40/1-DC
FAZ-C50/1-DC
279122
279123
279124
279125
279126
279127
279128
279129
279130
279131
279132
279133
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
440
500
500
500
500
500
500
500
500
500
500
500
10
10
10
10
10
10
10
10
10
10
10
10
FAZ-C2/2-DC
FAZ-C3/2-DC
FAZ-C4/2-DC
FAZ-C6/2-DC
FAZ-C10/2-DC
FAZ-C13/2-DC
FAZ-C16/2-DC
FAZ-C20/2-DC
FAZ-C25/2-DC
FAZ-C32/2-DC
FAZ-C40/2-DC
FAZ-C50/2-DC
279134
279135
279136
279137
279138
279139
279140
279141
279142
279143
279144
279145
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1-pole
2
3
4
6
10
13
16
20
25
32
40
50
SG08611
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
2-pole
2
3
4
6
10
13
16
20
25
32
40
50
Chapter 4.1.1. – 68
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications FAZ-DC
Technical data
FAZ-DC *)
Productstandard
Number of poles
IEC/EN 60947-2
1, 2
Mechanical specifications
Device width
Frame size
Socket size
Device depth
Terminals
Terminal capacity rigid solid/stranded wire
Terminal screw
Terminal torque
Snap on fixing
Finger proof
Degree of Protection (DIN VDE 0470)
Surface mounted
Built-in behind panel
Contact position indicator
17.7 mm (1p), 36 mm (2p)
45 mm
80 mm
60 mm
lift terminal
1-25 mm²
M5 (with slotted screw acc. to EN ISO 4757-Z2, PZ2)
max. 2.4 Nm
tristable (on DIN rail acc. to EN 50022)
acc. to VBG4, ÖVE EN-6
IP 20
IP 40
red / green
Electrical specifications
Rated voltage DC
Un
Rated current
Rated insulation voltage
Rated impulse withstand voltage
In
Ui
Uimp
2 A type: 220V (per pole)
3-50 A types: 250V (per pole)
Type C: 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 A
440 V
4 kV (1.2/50)µsec
Tripping characteristic
Conventional non-tripping current
Conventional tripping current
Reference temperature
Temperature factor
Instantaneous tripping current
Rated short-circuit braking capacity
Selectivity class
Number of electrical operations
Number of mechanical operations
Climatic conditions
Imt
Icu
Int=1.13 In
It=1.45 In
30 °C
0.4% /K
type C: 7 In < Imt = 15 In:t (Imt) < 0.1 sec
10 kA
3
> 4000
> 20000
acc. to IEC 68-2 (25..55°C / 90..95% RH)
*) not for PV string protection!
Connection diagram
1-pole
2-pole
Chapter 4.1.1. – 69
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Dimensions (mm) FAZ-...-DC
1-pole
2-pole
Connection examples FAZ-...-DC
Connection example at 250V=, 1-pole
Connection example at 500V=, 2-pole
Tripping Characteristic FAZ-...-DC
Maximum Let-Through Energy FAZ-...-DC
Characteristics C - IEC/EN 60947-2
Type C
Chapter 4.1.1. – 70
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-NA Miniature Circuit Breakers (MCBs)
Characteristic B
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V)
SG09011
Breaking SWD
capacity
acc. to
UL489
(kA)
NFPA 79
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-B1/1-NA
FAZ-B1,5/1-NA
FAZ-B2/1-NA
FAZ-B3/1-NA
FAZ-B4/1-NA
FAZ-B5/1-NA
FAZ-B6/1-NA
FAZ-B7/1-NA
FAZ-B8/1-NA
FAZ-B10/1-NA
FAZ-B13/1-NA
FAZ-B15/1-NA
FAZ-B16/1-NA
FAZ-B20/1-NA
FAZ-B25/1-NA
FAZ-B30/1-NA
FAZ-B32/1-NA
FAZ-B35/1-NA
FAZ-B40/1-NA
132414
132415
132416
132417
132418
132419
132680
132681
132682
132683
132684
132685
132686
132687
132688
132689
132690
132691
132692
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-B1/2-NA
FAZ-B1,5/2-NA
FAZ-B2/2-NA
FAZ-B3/2-NA
FAZ-B4/2-NA
FAZ-B5/2-NA
FAZ-B6/2-NA
FAZ-B7/2-NA
FAZ-B8/2-NA
FAZ-B10/2-NA
FAZ-B13/2-NA
FAZ-B15/2-NA
FAZ-B16/2-NA
FAZ-B20/2-NA
FAZ-B25/2-NA
FAZ-B30/2-NA
FAZ-B32/2-NA
FAZ-B35/2-NA
FAZ-B40/2-NA
132693
132694
132695
132696
132697
132698
132699
132700
132701
132702
132703
132704
132705
132706
132707
132708
132709
132710
132711
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-B1/3-NA
FAZ-B1,5/3-NA
FAZ-B2/3-NA
FAZ-B3/3-NA
FAZ-B4/3-NA
FAZ-B5/3-NA
FAZ-B6/3-NA
FAZ-B7/3-NA
FAZ-B8/3-NA
FAZ-B10/3-NA
FAZ-B13/3-NA
FAZ-B15/3-NA
FAZ-B16/3-NA
FAZ-B20/3-NA
FAZ-B25/3-NA
FAZ-B30/3-NA
FAZ-B32/3-NA
FAZ-B35/3-NA
FAZ-B40/3-NA
132712
132713
132714
132715
132716
132717
132718
132719
132720
132721
132722
132723
132724
132725
132726
132727
132728
132729
132730
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
2-pole
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09211
Rated
voltage
UL489
(V)
1-pole
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
Chapter 4.1.1. – 71
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-NA Miniature Circuit Breakers (MCBs)
Characteristic C
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V)
SG09011
Breaking SWD
capacity
acc. to
UL489
(kA)
NFPA 79
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
240
240
10
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-C0,5/1-NA
FAZ-C1/1-NA
FAZ-C1,5/1-NA
FAZ-C2/1-NA
FAZ-C3/1-NA
FAZ-C4/1-NA
FAZ-C5/1-NA
FAZ-C6/1-NA
FAZ-C7/1-NA
FAZ-C8/1-NA
FAZ-C10/1-NA
FAZ-C13/1-NA
FAZ-C15/1-NA
FAZ-C16/1-NA
FAZ-C20/1-NA
FAZ-C25/1-NA
FAZ-C30/1-NA
FAZ-C32/1-NA
FAZ-C35/1-NA
FAZ-C40/1-NA
102077
102078
102079
102080
102081
102082
102083
102084
102085
102086
102087
102088
102089
102090
102091
102092
102093
102094
102095
102096
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-C0,5/2-NA
FAZ-C1/2-NA
FAZ-C1,5/2-NA
FAZ-C2/2-NA
FAZ-C3/2-NA
FAZ-C4/2-NA
FAZ-C5/2-NA
FAZ-C6/2-NA
FAZ-C7/2-NA
FAZ-C8/2-NA
FAZ-C10/2-NA
FAZ-C13/2-NA
FAZ-C15/2-NA
FAZ-C16/2-NA
FAZ-C20/2-NA
FAZ-C25/2-NA
FAZ-C30/2-NA
FAZ-C32/2-NA
FAZ-C35/2-NA
FAZ-C40/2-NA
102157
102158
102159
102160
102161
102162
102163
102164
102165
102166
102167
102168
102169
102170
102171
102172
102173
102174
102175
102176
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
2-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09211
Rated
voltage
UL489
(V)
1-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
Chapter 4.1.1. – 72
FAZ-C0,5/3-NA 102237
1/40
FAZ-C1/3-NA
102238
1/40
FAZ-C1,5/3-NA 102239
1/40
FAZ-C2/3-NA
102240
1/40
FAZ-C3/3-NA
102241
1/40
FAZ-C4/3-NA
102242
1/40
FAZ-C5/3-NA
102243
1/40
FAZ-C6/3-NA
102244
1/40
FAZ-C7/3-NA
102245
1/40
FAZ-C8/3-NA
102246
1/40
FAZ-C10/3-NA
102247
1/40
FAZ-C13/3-NA
102248
1/40
FAZ-C15/3-NA
102249
1/40
FAZ-C16/3-NA
102250
1/40
FAZ-C20/3-NA
102251
1/40
FAZ-C25/3-NA
102252
1/40
FAZ-C30/3-NA
102253
1/40
FAZ-C32/3-NA
102254
1/40
FAZ-C35/3-NA
102255
1/40
FAZ-C40/3-NA
102256
1/40
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-NA Miniature Circuit Breakers (MCBs)
Characteristic D
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V)
SG09011
Breaking SWD
capacity
acc. to
UL489
(kA)
NFPA 79
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-D0,5/1-NA
FAZ-D1/1-NA
FAZ-D1,5/1-NA
FAZ-D2/1-NA
FAZ-D3/1-NA
FAZ-D4/1-NA
FAZ-D5/1-NA
FAZ-D6/1-NA
FAZ-D7/1-NA
FAZ-D8/1-NA
FAZ-D10/1-NA
FAZ-D13/1-NA
FAZ-D15/1-NA
FAZ-D16/1-NA
FAZ-D20/1-NA
FAZ-D25/1-NA
FAZ-D30/1-NA
FAZ-D32/1-NA
FAZ-D35/1-NA
FAZ-D40/1-NA
102097
102098
102099
102100
102101
102102
102103
102104
102105
102106
102107
102108
102109
102110
102111
102112
102113
102114
102115
102116
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-D0,5/2-NA
FAZ-D1/2-NA
FAZ-D1,5/2-NA
FAZ-D2/2-NA
FAZ-D3/2-NA
FAZ-D4/2-NA
FAZ-D5/2-NA
FAZ-D6/2-NA
FAZ-D7/2-NA
FAZ-D8/2-NA
FAZ-D10/2-NA
FAZ-D13/2-NA
FAZ-D15/2-NA
FAZ-D16/2-NA
FAZ-D20/2-NA
FAZ-D25/2-NA
FAZ-D30/2-NA
FAZ-D32/2-NA
FAZ-D35/2-NA
FAZ-D40/2-NA
102177
102178
102179
102180
102181
102182
102183
102184
102185
102186
102187
102188
102189
102190
102191
102192
102193
102194
102195
102196
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
2-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09211
Rated
voltage
UL489
(V)
1-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
Chapter 4.1.1. – 73
FAZ-D0,5/3-NA 102257
1/40
FAZ-D1/3-NA
102258
1/40
FAZ-D1,5/3-NA 102259
1/40
FAZ-D2/3-NA
102260
1/40
FAZ-D3/3-NA
102261
1/40
FAZ-D4/3-NA
102262
1/40
FAZ-D5/3-NA
102263
1/40
FAZ-D6/3-NA
102264
1/40
FAZ-D7/3-NA
102265
1/40
FAZ-D8/3-NA
102266
1/40
FAZ-D10/3-NA
102267
1/40
FAZ-D13/3-NA
102268
1/40
FAZ-D15/3-NA
102269
1/40
FAZ-D16/3-NA
102270
1/40
FAZ-D20/3-NA
102271
1/40
FAZ-D25/3-NA
102272
1/40
FAZ-D30/3-NA
102273
1/40
FAZ-D32/3-NA
102274
1/40
FAZ-D35/3-NA
102275
1/40
FAZ-D40/3-NA
102276
1/40
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-NA-DC Miniature Circuit Breakers (MCBs)
Characteristic C
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V DC)
SG09011
Rated
voltage
UL489
(V)
Breaking SWD
capacity
acc. to
UL489
(kA)
NFPA 79
Type
Designation
Article No.
Units
per
package
1-pole
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
220
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
FAZ-C2/1-NA-DC 113752
FAZ-C3/1-NA-DC 113753
FAZ-C4/1-NA-DC 113754
FAZ-C5/1-NA-DC 113755
FAZ-C6/1-NA-DC 113756
FAZ-C7/1-NA-DC 113757
FAZ-C8/1-NA-DC 113758
FAZ-C10/1-NA-DC 113759
FAZ-C13/1-NA-DC 113760
FAZ-C15/1-NA-DC 113761
FAZ-C16/1-NA-DC 113762
FAZ-C20/1-NA-DC 113763
FAZ-C25/1-NA-DC 113764
FAZ-C30/1-NA-DC 113765
FAZ-C32/1-NA-DC 113766
FAZ-C35/1-NA-DC 113767
FAZ-C40/1-NA-DC 113768
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
440
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
FAZ-C2/2-NA-DC 137239
FAZ-C3/2-NA-DC 137250
FAZ-C4/2-NA-DC 137251
FAZ-C5/2-NA-DC 137252
FAZ-C6/2-NA-DC 120638
FAZ-C7/2-NA-DC 120639
FAZ-C8/2-NA-DC 120640
FAZ-C10/2-NA-DC 120641
FAZ-C13/2-NA-DC 120642
FAZ-C15/2-NA-DC 120643
FAZ-C16/2-NA-DC 120644
FAZ-C20/2-NA-DC 120645
FAZ-C25/2-NA-DC 120646
FAZ-C30/2-NA-DC 120647
FAZ-C32/2-NA-DC 120648
FAZ-C35/2-NA-DC 120649
FAZ-C40/2-NA-DC 120650
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
2-pole
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
Chapter 4.1.1. – 74
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications FAZ-NA-DC
Technical data
FAZ-NA-DC
Productstandard
Number of poles
UL 489, CSA C22.2 No 5-02
1, 2
Mechanical specifications
Device width
Frame size
Socket size
Device depth
Terminals
Terminal capacity rigid solid/stranded wire
1 pole = 0.697 inch, 2 poles = 1.394 inch
1.772 inch
4.134 inch
2.362 inch
lift terminal / ring-tongue
1 Wire: AWG 18-6 (Cu only)
2 Wires: AWG 18-10 (Cu only)
M5 (with slotted screw Pozidriv PZ2)
#18-12 AWG: 21 lb-in
#10-8 AWG: 25 lb-in
#6 AWG: 36 lb-in
tristable (on DIN Rail acc. to IEC/EN 60715)
acc.to VBG4, ÖVE EN-6
red / green
Terminal screw
Terminal torque
Snap on fixing
Finger proof
Contact position indicator
Electrical specifications
Rated voltage DC
Rated current
Rated impulse withstand voltage
Un
In
Uimp
125 V d.c. (1p)
250 V d.c. (2p)
6, 7, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40 A
4 kV (1.2/50)µsec
Tripping characteristic
Conventional non-tripping current
Conventional tripping current
Reference temperature
Temperature factor
Instantaneous tripping current
Current interrupting rating
Number of electrical operating cycles
Number of mechanical operating cycles
Climatic conditions
Imt
Int=1.0 In
It=1.35 In
40 °C
0.5% /K
7 In < Imt = 15 In:t (Imt) < 0.1 sec
10 kA
6000
10000
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Connection diagram
1-pole
2-pole
Chapter 4.1.1. – 75
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Dimensions (mm) FAZ-NA-DC
1-pole
2-pole
Tripping Characteristic FAZ-NA-DC
Characteristics C - UL 489
Chapter 4.1.1. – 76
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-RT Miniature Circuit Breakers (MCBs)
Characteristic B
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V)
SG09011
Breaking SWD
capacity
acc. to
UL489
(kA)
NFPA 79
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-B1/1-RT
FAZ-B1,5/1-RT
FAZ-B2/1-RT
FAZ-B3/1-RT
FAZ-B4/1-RT
FAZ-B5/1-RT
FAZ-B6/1-RT
FAZ-B7/1-RT
FAZ-B8/1-RT
FAZ-B10/1-RT
FAZ-B13/1-RT
FAZ-B15/1-RT
FAZ-B16/1-RT
FAZ-B20/1-RT
FAZ-B25/1-RT
FAZ-B30/1-RT
FAZ-B32/1-RT
FAZ-B35/1-RT
FAZ-B40/1-RT
132731
132732
132733
132734
132735
132736
132737
132738
132739
132740
132741
132742
132743
132744
132745
132746
132747
132748
132749
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-B1/2-RT
FAZ-B1,5/2-RT
FAZ-B2/2-RT
FAZ-B3/2-RT
FAZ-B4/2-RT
FAZ-B5/2-RT
FAZ-B6/2-RT
FAZ-B7/2-RT
FAZ-B8/2-RT
FAZ-B10/2-RT
FAZ-B13/2-RT
FAZ-B15/2-RT
FAZ-B16/2-RT
FAZ-B20/2-RT
FAZ-B25/2-RT
FAZ-B30/2-RT
FAZ-B32/2-RT
FAZ-B35/2-RT
FAZ-B40/2-RT
132750
132751
132752
132753
132754
132755
132756
132757
132758
132759
132760
132761
132762
132763
132764
132765
132766
132767
132768
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-B1/3-RT
FAZ-B1,5/3-RT
FAZ-B2/3-RT
FAZ-B3/3-RT
FAZ-B4/3-RT
FAZ-B5/3-RT
FAZ-B6/3-RT
FAZ-B7/3-RT
FAZ-B8/3-RT
FAZ-B10/3-RT
FAZ-B13/3-RT
FAZ-B15/3-RT
FAZ-B16/3-RT
FAZ-B20/3-RT
FAZ-B25/3-RT
FAZ-B30/3-RT
FAZ-B32/3-RT
FAZ-B35/3-RT
FAZ-B40/3-RT
132769
132770
132771
132772
132773
132774
132775
132776
132777
132778
132779
132780
132781
132782
132783
132784
132785
132786
132787
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
2-pole
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09211
Rated
voltage
UL489
(V)
1-pole
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
Chapter 4.1.1. – 77
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-RT Miniature Circuit Breakers (MCBs)
Characteristic C
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V)
SG09011
Breaking SWD
capacity
acc. to
UL489
(kA)
NFPA 79
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
240
240
10
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-C0,5/1-RT
FAZ-C1/1-RT
FAZ-C1,5/1-RT
FAZ-C2/1-RT
FAZ-C3/1-RT
FAZ-C4/1-RT
FAZ-C5/1-RT
FAZ-C6/1-RT
FAZ-C7/1-RT
FAZ-C8/1-RT
FAZ-C10/1-RT
FAZ-C13/1-RT
FAZ-C15/1-RT
FAZ-C16/1-RT
FAZ-C20/1-RT
FAZ-C25/1-RT
FAZ-C30/1-RT
FAZ-C32/1-RT
FAZ-C35/1-RT
FAZ-C40/1-RT
102117
102118
102119
102120
102121
102122
102123
102124
102125
102126
102127
102128
102129
102130
102131
102132
102133
102134
102135
102136
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-C0,5/2-RT
FAZ-C1/2-RT
FAZ-C1,5/2-RT
FAZ-C2/2-RT
FAZ-C3/2-RT
FAZ-C4/2-RT
FAZ-C5/2-RT
FAZ-C6/2-RT
FAZ-C7/2-RT
FAZ-C8/2-RT
FAZ-C10/2-RT
FAZ-C13/2-RT
FAZ-C15/2-RT
FAZ-C16/2-RT
FAZ-C20/2-RT
FAZ-C25/2-RT
FAZ-C30/2-RT
FAZ-C32/2-RT
FAZ-C35/2-RT
FAZ-C40/2-RT
102197
102198
102199
102200
102201
102202
102203
102204
102205
102206
102207
102208
102209
102210
102211
102212
102213
102214
102215
102216
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
2-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09211
Rated
voltage
UL489
(V)
1-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
Chapter 4.1.1. – 78
FAZ-C0,5/3-RT
102277
1/40
FAZ-C1/3-RT
102278
1/40
FAZ-C1,5/3-RT
102279
1/40
FAZ-C2/3-RT
102280
1/40
FAZ-C3/3-RT
102281
1/40
FAZ-C4/3-RT
102282
1/40
FAZ-C5/3-RT
102283
1/40
FAZ-C6/3-RT
102284
1/40
FAZ-C7/3-RT
102285
1/40
FAZ-C8/3-RT
102286
1/40
FAZ-C10/3-RT
102287
1/40
FAZ-C13/3-RT
102288
1/40
FAZ-C15/3-RT
102289
1/40
FAZ-C16/3-RT
102290
1/40
FAZ-C20/3-RT
102291
1/40
FAZ-C25/3-RT
102292
1/40
FAZ-C30/3-RT
102293
1/40
FAZ-C32/3-RT
102294
1/40
FAZ-C35/3-RT
102295
1/40
FAZ-C40/3-RT
102296
1/40
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-...-RT Miniature Circuit Breakers (MCBs)
Characteristic D
Rated Rated
current voltage
In (A) IEC/EN
60947-2
(V)
SG09011
Breaking SWD
capacity
acc. to
UL489
(kA)
NFPA 79
Type
Designation
Article No.
Units
per
package
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
240/415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-D0,5/1-RT
FAZ-D1/1-RT
FAZ-D1,5/1-RT
FAZ-D2/1-RT
FAZ-D3/1-RT
FAZ-D4/1-RT
FAZ-D5/1-RT
FAZ-D6/1-RT
FAZ-D7/1-RT
FAZ-D8/1-RT
FAZ-D10/1-RT
FAZ-D13/1-RT
FAZ-D15/1-RT
FAZ-D16/1-RT
FAZ-D20/1-RT
FAZ-D25/1-RT
FAZ-D30/1-RT
FAZ-D32/1-RT
FAZ-D35/1-RT
FAZ-D40/1-RT
102137
102138
102139
102140
102141
102142
102143
102144
102145
102146
102147
102148
102149
102150
102151
102152
102153
102154
102155
102156
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
12/120
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
FAZ-D0,5/2-RT
FAZ-D1/2-RT
FAZ-D1,5/2-RT
FAZ-D2/2-RT
FAZ-D3/2-RT
FAZ-D4/2-RT
FAZ-D5/2-RT
FAZ-D6/2-RT
FAZ-D7/2-RT
FAZ-D8/2-RT
FAZ-D10/2-RT
FAZ-D13/2-RT
FAZ-D15/2-RT
FAZ-D16/2-RT
FAZ-D20/2-RT
FAZ-D25/2-RT
FAZ-D30/2-RT
FAZ-D32/2-RT
FAZ-D35/2-RT
FAZ-D40/2-RT
102217
102218
102219
102220
102221
102222
102223
102224
102225
102226
102227
102228
102229
102230
102231
102232
102233
102234
102235
102236
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
480Y/277
240
240
10
10
10
10
10
10
10
10
10
10
10
14
14
14
14
10
10
10
10
10
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
SWD
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 18
AWG 16
AWG 16
2-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09211
Rated
voltage
UL489
(V)
1-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
SG09111
Breaking
capacity
acc. to
IEC/EN
60947-2
(kA)
3-pole
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
Chapter 4.1.1. – 79
FAZ-D0,5/3-RT
102297
1/40
FAZ-D1/3-RT
102298
1/40
FAZ-D1,5/3-RT
102299
1/40
FAZ-D2/3-RT
102300
1/40
FAZ-D3/3-RT
102301
1/40
FAZ-D4/3-RT
102302
1/40
FAZ-D5/3-RT
102303
1/40
FAZ-D6/3-RT
102304
1/40
FAZ-D7/3-RT
102305
1/40
FAZ-D8/3-RT
102306
1/40
FAZ-D10/3-RT
102307
1/40
FAZ-D13/3-RT
102308
1/40
FAZ-D15/3-RT
102309
1/40
FAZ-D16/3-RT
102310
1/40
FAZ-D20/3-RT
102311
1/40
FAZ-D25/3-RT
102312
1/40
FAZ-D30/3-RT
102313
1/40
FAZ-D32/3-RT
102314
1/40
FAZ-D35/3-RT
102315
1/40
FAZ-D40/3-RT
102316
1/40
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
FAZ-NA, -RT Miniature Circuit Breakers
Accessories:
Auxiliary switch for subsequent installation
Tripping signal contact for subsequent installation
Shunt trip release
Z-IHK-NA
Z-NHK
FAZ-XAA-NA12-110VAC
FAZ-XAA-NA110-415VAC
IS/SPE-1TE
Switching interlock
113895
248434
102037
102036
101911
Specifications FAZ-NA, FAZ,RT
Technical data IEC/EN
FAZ-...-NA, -RT
Productstandard
Number of poles
IEC/EN 60947-2
1, 2, 3
Mechanical specifications
Device width
Frame size
Socket size
Device depth
Terminals
Terminal capacity rigid solid/stranded wire
Terminal screw
Terminal torque
Snap on fixing
Degree of Protection (DIN VDE 0470)
Surface mounted
Built-in behind panel
Contact position indicator
17.7mm (1-pole), 35.4 mm (2-poles), 53.1 mm (3-poles)
45 mm
105 mm
60 mm
lift terminal / ring-tongue
1-25 mm²
M5 (with slotted screw Pozidriv PZ2)
max. 2.4 Nm
tristable (on DIN Rail acc. to IEC/EN 60715)
IP 20
IP 40
red / green
Electrical specifications
Rated voltage
Rated current
Rated insulation voltage
Rated impulse withstand voltage
Un
In
Ui
Uimp
240/415 V AC
0.5, 1, 1.5, 2, 3, 4, 5, 6, 7, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40 A
440 V AC
4 kV (1.2/50)µsec
Tripping characteristic
Conventional non-tripping current
Conventional tripping current
Reference temperature
Temperature factor
Instantaneous tripping current
Rated short-circuit braking capacity
Service short circuit capacity
Selectivity class
Number of electrical operations
Number of mechanical operations
Climatic conditions
Imt
Icu
Ics
Int=1.05 In
It=1.30 In
30 °C
0.5% /K
type B: 3 In < Imt = 5 In:t (Imt) < 0.1 sec (IEC/EN 60898-1)
type C: 5 In < Imt = 10 In:t (Imt) < 0.1 sec (IEC/EN 60898-1)
type D: 10 In < Imt = 20 In:t (Imt) < 0.1 sec (IEC/EN 60898-1)
15 kA
7.5 kA
3 (acc. to EN 60898)
> 1500
> 10000
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Connection diagram
1-pole
2-pole
3-pole
Chapter 4.1.1. – 80
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications FAZ-NA, FAZ-RT
Technical data UL
FAZ-...-NA, -RT
Productstandard
Number of poles
UL 489 CSA C22.2 No. 5-02
1, 2, 3
Mechanical specifications
Device width
Frame size
Socket size
Device depth
Terminals
Terminal capacity
0.697 in. (1-pole), 1.394 in. (2-poles), 2.090 in. (3-poles)
1.772 in.
4.134 in.
2.362 in.
lift terminal / ring-tongue
1 Wire: #18-6 AWG (Cu only)
2 Wires: #18-10 AWG (Cu only)
M5 (with slotted screw Pozidriv PZ2)
#18-12 AWG: 21 lb-in
#10-8 AWG: 25 lb-in
#6 AWG: 36 lb-in
tristable (on DIN Rail acc. to IEC/EN 60715)
red / green
Terminal screw
Terminal torque
Snap on fixing
Contact position indicator
Electrical specifications
Rated voltage
Rated current
Un
In
0.5-32 A: 480Y/277 V AC, 35-40 A: 240 V AC
0.5, 1, 1.5, 2, 3, 4, 5, 6, 7, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40 A
Tripping characteristic
Conventional non-tripping current
Conventional tripping current
Reference temperature
Temperature factor
Instantaneous tripping current
Current interrupting rating
Current-Limiting at 240 V / 10 kA
Current-Limiting at 480Y/277 V / 10 kA
Current-Limiting at 480Y/277 V / 14 kA
Selectivity class
Number of electrical operations
Number of mechanical operations
Climatic conditions
Imt
Int=1.00 In
It=1.35 In
40 °C
0.5% /K
type C: 5 In < Imt = 10 In:t (Imt) < 0.1 sec
type D: 10 In < Imt = 20 In:t (Imt) < 0.1 sec
10 kA, 14 kA (types D13, B/C/D15, 16, 20, B/C25 A)
1p, 2p, 3p to I2t = 43 kA2s and Ipeak = 6.2 kA
1p, 2p, 3p to I2t = 60 kA2s and Ipeak = 6.2 kA
1p, 2p, 3p to I2t = 65 kA2s and Ipeak = 7.5 kA
3 (acc. to EN 60898)
6000
10000
acc. to IEC 68-2 (25..55°C / 90..95% RH)
Connection diagram
1-pole
2-pole
3-pole
Chapter 4.1.1. – 81
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Dimensions (mm) FAZ-...-NA, -RT
1-pole
3-pole
2-pole
Tripping Characteristic FAZ-...-NA, -RT
Characteristics C and D - EN/IEC 60947-2
Characteristics C and D - UL 489
Chapter 4.1.1. – 82
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Internal Resistance FAZ-...-NA, -RT
Type D
Type C
At room temperature (single pole)
At room temperature (single pole)
In [A]
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
* 50Hz
Z* [mΩ]
6400
1100
560
340
132
86
70
31
28
20
15.8
12.3
7.1
7.1
6.0
4.1
2.8
2.8
2.5
2.1
R [mΩ]
6300
1080
550
330
130
85
69
30
27
19.6
15.5
12.1
7.0
7.0
5.9
4.0
2.7
2.7
2.5
2.1
In [A]
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
*
Z* [mΩ]
6400
770
460
250
132
86
57
31
28
18
13.5
10.5
5.9
5.9
4.0
3.4
2.5
2.5
2.5
2.0
50Hz
R [mΩ]
6300
755
450
245
130
85
56
30
27
17.6
13.2
10.3
5.8
5.8
3.9
3.3
2.5
2.5
2.5
2.0
1p
2p
3p
P* [W]
1.6
0.8
1.0
1.0
1.2
1.4
1.5
1.2
1.4
1.2
1.5
2.0
1.5
1.7
1.8
2.6
2.7
3.1
3.8
3.9
P* [W]
3.2
1.5
2.1
2.1
2.4
2.9
2.9
2.3
2.8
2.4
3.0
4.1
3.1
3.5
3.7
5.1
5.4
6.2
7.6
7.8
P* [W
4.8
2.3
3.1
3.1
3.6
4.3
4.4
3.5
4.3
3.7
4.5
6.1
4.6
5.2
5.5
7.7
8.1
9.3
11.3
11.6
Power Loss at In FAZ-...-NA, -RT
Type C
In [A]
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
*50Hz
Type D
1p
2p
3p
P* [W]
1.6
1.1
1.3
1.4
1.2
1.4
1.9
1.2
1.4
1.4
1.8
2.4
1.9
2.1
2.9
3.1
3.0
3.4
3.7
4.0
P* [W]
3.2
2.2
2.6
2.8
2.4
2.9
3.7
2.3
2.8
2.8
3.6
4.7
3.8
4.3
5.8
6.2
6.0
6.8
7.4
8.1
P* [W
4.7
3.4
3.9
4.3
3.6
4.3
5.6
3.5
4.3
4.2
5.3
7.1
5.6
6.4
8.7
9.3
9.0
10.2
11.0
12.1
In [A]
0.5
1
1.5
2
3
4
5
6
7
8
10
13
15
16
20
25
30
32
35
40
*50Hz
Chapter 4.1.1. – 83
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Energy FAZ-...-NA, -RT
Type C (0.5 - 32 A), 277 V
Type C (35 - 40 A), 240 V
Type D (0.5 - 32 A), 277 V
Type D (35 - 40 A), 240 V
Chapter 4.1.1. – 84
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Maximum Let-Through Current FAZ-...-NA, -RT
Type C (0.5 - 32 A), 277 V
Type C (35 - 40 A), 240 V
Type D (0.5 - 32 A), 277 V
Type D (35 - 40 A), 240 V
Chapter 4.1.1. – 85
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Z-SV/UL-16 Busbars for FAZ-NA
ATTENTION: Maximum of 3 commoning links
allowed. Any combination of same pole configuration.
ATTENTION: 3 liaisons communes autorisées au maximum.
Toute combinaison de configurations de polarité identiques.
ACHTUNG: Maximal 3 Schienenblöcke. Beliebige Kombination gleichpoliger Konfigurationen.
ATTENZIONE: Sono consentiti al massimo 3 pettini di collegamento
in qualsiasi combinazione della stessa configurazione di poli.
ATENCION: Se permite un máximo de 3 enlaces comunes.
Cualquier combinación del mismo tipo de configuración de polo
!
!
ATTENTION: Do not cut.
ATTENTION: Ne pas couper.
ACHTUNG: Nicht durchschneiden.
ATTENZIONE: Non tagliare.
ATENCION: No corte.
UL489
EN/IEC
00947-2
Ue
f
Uimp
480 V AC 96 V DC 240/415 V AC
50/60 Hz
---------- 50/60 Hz
---------------------------- 9.5 kV
Ie
Cross section
80 A @ 40oC
80 A @ 30oC
---------------------------- 16 mm²
UL489
EN/IEC
00947-2
UL489
EN/IEC
00947-2
Ue
f
Uimp
480 V AC 96 V DC 240/415 V AC
50/60 Hz
---------- 50/60 Hz
---------------------------- 9.5 kV
Ue
f
Uimp
480 V AC 96 V DC 240/415 V AC
50/60 Hz
---------- 50/60 Hz
---------------------------- 9.5 kV
Ie
115 A @ 40oC
#1-14 AWG
60/75oC Cu
0.56 in
Ie
80 A @ 40oC
#2-14 AWG
60/75oC Cu
0.56 in
160 A @ 30oC
1.5-50 mm²
Cu
14 mm
Chapter 4.1.1. – 86
80 A @ 30oC
2.5-35 mm²
Cu
14 mm
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Z-SV/UL-16 Busbars for FAZ-NA
Z2
AWG
14
12-8
6-2
FAZ-NA
FAZ-RT
Ib-in
21
25
36
Nm
2.3
2.8
4.0
ZV-BS-UL
4 mm
Z-EK/35/UL
IEC/EN 60947-2 Icc
Ue
VAC
Z-SV/UL
Icc Amps
240/
415
15000
UL SCCR
FAZ-NA Ue
FAZ-RT VAC
In
Amps
Article No.
104892
104893
104894
104895
104896
104897
104898
104899
104900
104901
104902
104904
Z-SV/UL
SCCR RMS
Sym Amps
0.5-32
480Y/
277
10000
35-40
240
10000
Z-SV/UL-16/1P-1TE/6
Z-SV/UL-16/1P-1TE/12
Z-SV/UL-16/1P-1TE/18
Z-SV/UL-16/2P-2TE/6
Z-SV/UL-16/2P-2TE/12
Z-SV/UL-16/2P-2TE/18
Z-SV/UL-16/3P-3TE/6
Z-SV/UL-16/3P-3TE/12
Z-SV/UL-16/3P-3TE/18
Z-EK/35/UL
Z-EB/50/UL
ZV-BS-UL
6
12
18
-
3
6
9
-
Chapter 4.1.1. – 87
2
4
6
-
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Auxiliary Contacts and Voltage Trips for FAZ-NA, FAZ-RT
Circuit
Diagram
Description
Rated Operational
Voltage
Type
Designation
Article No.
Units
per
package
Z-IHK-NA
113895
1
248434
1
FAZ-XAA-NA12-110VAC 102037
1
FAZ-XAA-NA110-415VAC 102036
1
IS/SPE-1TE
1
Auxiliary contact
SG60711
Same Polarity
• Design according to IEC/EN 60947-5-1,
250 Vac
IEC/EN 62019
• Field installable
• The specified minimum voltages are per
contact—take into account particularly in
case of series connection
• Self-cleaning contacts
• Contact material and design particularly
suitable for extra low voltage
• Tripping signal contact transmits message
of electric tripping, not mechanical switch-off
• Test key for contact function “electrical
tripping”
• Will allow for > 480Y/277 Vac rating
Two-pole auxiliary contact/trip indicating contact *)
SG61011
• Design according to IEC/EN 60947-5-1,
250 Vac
IEC/EN 62019
• Field installable
• The specified minimum voltages are per
contact—take into account particularly in
case of series connection
• Self-cleaning contacts
• Contact material and design particularly
suitable for extra low voltage
• Tripping signal contact transmits message
of electric tripping, not mechanical switch-off
• Test key for contact function “electrical
tripping”
• The function of one of the two change-over
contacts can be switched from “auxiliary
switch” to “tripping signal switch”
*) Voltage of FAZ-NA circuit breaker is limited
to 300V with this auxiliary contact installed
Z-NHK
Shunt Trip
SG13511
1
2
• Remote release for subsequent
mounting onto FAZ-NA
• Additional installation of standard
auxiliary switch is possible
• Position indicator red–green
12–110 Vac
12–60 Vdc
110–415 Vac
110–230 Vdc
Padlock Hasp (for all FAZ)
• Prevents reactivation of the device
during maintenance
• Holds one padlock
Chapter 4.1.1. – 88
101911
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications Accessories for FAZ-NA, FAZ-RT
Technical Data
Electrical
Contact function
Rated voltage
Rated current
Rated thermal current Ith
Utilization category AC13
Rated operational current Ie
Utilization category AC15
Rated operational current Ie
Utilization category DC12
Rated operational current Ie
Rated insulation voltage U
Minimum operational voltage per contact Umin
Minimum operational current Imin
Rated peak withstand voltage Uimp (1.2/50µ)
Conditional short circuit current Ik
with Back-Up Fuse 6A
Max. back-up fuse, overload and short circuit
Mechanical
Tripping indicator “electrical tripping”
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminal protection
I
Terminals
Terminal capacity
Terminal screws
Tightening torque of terminal screws
Z-NHK
Z-IHK-NA
2CO
230V
2A
2A
1NO + 1NC
250V
6A
6A
3A/250 Vac
3A/250 Vac
2A/250 Vac
2A/250 Vac
0.5A/110 Vdc
250 Vac
5 Vdc
10 mA DC
2.5 kV
0.5A/110 Vdc
0.25A/220 Vdc
250 Vac
5 Vdc
10 mA AC/DC
4 kV
1 kA
6A gL
1 kA
—
Blue/white
45 mm
80 mm
8.8 mm (0.5MU)
Onto switching device
IP40
Finger and hand touch safe
according to BGV A3, ÖVE-EN 6
Lift terminals
20–14 AWG
M3 (Pozidrive Z0)
7 lb-in
—
45 mm
80 mm
8.8 mm (0.5MU)
—
IP40
Finger and hand touch safe
according to BGV A3, ÖVE-EN 6
Lift terminals
0.5–2.5 mm2
M3 (Pozidrive Z0)
max. 1.2 Nm
Two-pole auxiliary contact/trip indicating contact
Auxiliary contact
Z-NHK
Z-IHK-NA
Chapter 4.1.1. – 89
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications Accessories for FAZ-NA, FAZ-RT
Technical Data
Electrical
Can be mounted onto
Operational voltage range
Frequency
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminal protection
Terminals
Terminal capacity, one and two wires
FAZ-XAA-NA12-110VAC
FAZ-XAA-NA110-415VAC
FAZ-NA / FAZ-NA-DC / FAZ-RT
12–110 Vac
12–60 Vdc
50/60 Hz
FAZ-NA / FAZ-NA-DC / FAZ-RT
110–415 Vac
110–230 Vdc
50/60 Hz
45 mm
45 mm
105 mm
105 mm
17.5 mm
17.5 mm
Quick fastening with two lock-in positions on EN 50022
IP40
IP40
Finger and hand touch safe
Finger and hand touch safe
according to BGV A3, ÖVE-EN 6 according to BGV A3, ÖVE-EN 6
Open mouthed/lift
Open mouthed/lift
18–10 AWG
18–10 AWG
Chapter 4.1.1. – 90
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Miniature Circuit Breakers AZ
SG18811
• High-quality miniature circuit breakers for commercial and industrial
applications
• Contact position indicator red - green
• Accessories suitable for subsequent installation
• Rated currents up to 125 A
• Tripping characteristics C, D
• Rated breaking capacity up to 25 kA according to EN 60947-2
Chapter 4.1.1. – 91
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
AZ Miniature Circuit Breakers (MCBs)
Characteristic C
Rated
current
In (A)
SG18411
211769
211774
211779
211784
211789
211794
211799
211804
211809
12
12
12
12
12
12
12
12
12
AZ-2-C20
AZ-2-C25
AZ-2-C32
AZ-2-C40
AZ-2-C50
AZ-2-C63
AZ-2-C80
AZ-2-C100
AZ-2-C125
211770
211775
211780
211785
211790
211795
211800
211805
211810
2
2
2
2
2
2
2
2
2
AZ-3-C20
AZ-3-C25
AZ-3-C32
AZ-3-C40
AZ-3-C50
AZ-3-C63
AZ-3-C80
AZ-3-C100
AZ-3-C125
211771
211776
211781
211786
211791
211796
211801
211806
211811
1
1
1
1
1
1
1
1
1
AZ-3N-C20
AZ-3N-C25
AZ-3N-C32
AZ-3N-C40
AZ-3N-C50
AZ-3N-C63
AZ-3N-C80
AZ-3N-C100
AZ-3N-C125
211773
211778
211783
211788
211793
211798
211803
211808
211813
1
1
1
1
1
1
1
1
1
AZ-4-C20
AZ-4-C25
AZ-4-C32
AZ-4-C40
AZ-4-C50
AZ-4-C63
AZ-4-C80
AZ-4-C100
AZ-4-C125
211772
211777
211782
211787
211792
211797
211802
211807
211812
1
1
1
1
1
1
1
1
1
3+N-pole
20
25
32
40
50
63
80
100
125
SG18811
AZ-C20
AZ-C25
AZ-C32
AZ-C40
AZ-C50
AZ-C63
AZ-C80
AZ-C100
AZ-C125
3-pole
20
25
32
40
50
63
80
100
125
SG18711
Units
per
package
2-pole
20
25
32
40
50
63
80
100
125
SG18611
Article No.
1-pole
20
25
32
40
50
63
80
100
125
SG18511
Type
Designation
4-pole
20
25
32
40
50
63
80
100
125
Chapter 4.1.1. – 92
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
AZ Miniature Circuit Breakers (MCBs)
Characteristic D
Rated
current
In (A)
SG18411
AZ-D50
AZ-D63
AZ-D80
AZ-D100
211814
211818
211822
211826
12
12
12
12
AZ-2-D50
AZ-2-D63
AZ-2-D80
AZ-2-D100
211815
211819
211823
211827
2
2
2
2
AZ-3-D50
AZ-3-D63
AZ-3-D80
AZ-3-D100
211816
211820
211824
211828
1
1
1
1
AZ-3N-D50
AZ-3N-D63
AZ-3N-D80
AZ-3N-D100
211817
211821
211825
211829
1
1
1
1
3-pole
50
63
80
100
SG18711
Units
per
package
2-pole
50
63
80
100
SG18611
Article No.
1-pole
50
63
80
100
SG18511
Type
Designation
3+N-pole
50
63
80
100
Chapter 4.1.1. – 93
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Specifications | Miniature Circuit Breakers AZ
Description
• Independent switching contacts
• With isolator function, meets the requirements of insulation coordination, distance between contacts ≥ 4 mm, for secure isolation
Accessories:
Auxiliary switch for subsequent installation (0.5 MU)
Shunt trip release for subsequent installation (1.5 MU)
Z-LHK
Z-LHASA/230
Z-LHASA/24
LH-SPL
LH-SPE
LH-SPA
Tripping interlock
Switchoff interlock
248440
248442
248441
285752
215999
216000
Connection diagram
1-pole
2-pole
3-pole
3+N-pole
4-pole
Technical Data
AZ
Electrical
Standards
Rated operating voltage
Rated switching capacity
Operational switching capacity
Characteristic
Max. back-up fuse
Selectivity class
Lifespan
Direction of incoming supply
Mechanical
Standard front dimensions
Device height
Terminal protection
Mounting width per pole
Mounting
Protection type
Terminals top and bottom
Terminal capacity (solid)
Operations
IEC/EN 60947-2
230/400 V AC
60 V DC (per pole)
25 kA
20 kA
Similar: C, D
200 A gL/gG
Compliant with class 3
>10000
Any
45 mm
90 mm
Finger and back-of-proof to BGV A2
27 mm
Top-hat rail to IEC/EN 60715
IP20, IP40 (enclosed)
Lift terminals
2.5 – 50 mm2
Dimensions (mm)
Chapter 4.1.1. – 94
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Load Capacity AZ
Effect of ambient temperature
Load capacity KT [I/In]
Load capacity factor KN
Load capacity in case of block installation
Number of devices (n) 1-pole
Ambient temperature T [°C]
Permitted permanent load at ambient temperature T [°C] with n devices: IDL = InKT(T)KN(N).
Maximum Let-Through Energy AZ
Maximum let-through energy AZ, characteristic D, 1-pole
ms
Prospective short-circuit current [A]
ha
lf
wa
ve
t=
10
Let through energy I2t [A2 sec]
ha
lf
wa
ve
t=
10
m
Let through energy I2t [A2 sec]
s
Maximum let-through energy AZ, characteristic C, 1-pole
Prospective short-circuit current [A]
Determined according to EN 60898-1.
Chapter 4.1.1. – 95
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Short Circuit Selectivity AZ
• Short circuit selectivity (in kA) between AZ and upstream fuse D0 or NH, operating class gL/gG
• 1,4 . . selectivity up to 1.4 kA;
. . . no selectivity
Selectivity towards back-up fuses D01, D02, D03
Rated current In
AZ in A
35
0,5
1,0
2,0
25
1,0
32
1,0
20
CCharacteristic
Rated current of the back-up fuse in A
50
63
25
40
80
100
2,9
3,9
7,6
1,9
2,8
3,8
7,3
1,8
2,7
3,6
7,0
1,6
2,2
3,0
5,6
2,1
2,8
5,2
2,7
4,8
50
63
80
4,3
100
125
20
D-Characteristic
0,5
0,9
1,7
2,5
3,4
6,7
25
0,9
1,6
2,3
3,2
6,2
32
0,9
1,5
2,3
3,0
6,0
1,4
2,0
2,6
4,7
1,8
2,3
4,3
2,1
3,7
40
50
63
80
3,1
100
Selectivity towards back-up fuses NH Gr. 00
25
35
40
Rated current of the back-up fuse in A
50
63
80
100
125
160
200
0,5
1,0
1,3
1,9
2,7
3,7
6,7
17,0
25,0
25,0
25
0,9
1,3
1,8
2,6
3,5
6,5
17,0
25,0
25,0
32
0,9
1,2
1,7
2,4
3,3
6,0
15,0
23,0
25,0
1,4
2,1
2,9
4,8
12,0
18,0
25,0
1,9
2,7
4,5
11,0
17,0
25,0
63
4,2
10,0
15,0
25,0
80
3,8
8,5
12,0
25,0
7,0
10,0
25,0
7,5
25,0
Rated current In
AZ in A
20
CCharacteristic
40
50
100
125
20
DCharacteristic
0,8
1,1
1,5
2,3
3,1
5,6
16,0
25,0
25,0
25
0,7
1,0
1,4
2,1
3,0
5,3
14,0
23,0
25,0
32
0,7
1,0
1,3
2,1
2,9
5,0
13,0
22,0
25,0
1,1
1,8
2,5
4,2
10,0
15,0
25,0
1,6
2,3
3,8
8,5
13,0
22,0
2,1
3,2
7,0
10,5
18,0
2,8
5,5
8,4
15,0
4,8
7,5
12,5
40
50
<0,5
63
80
100
Chapter 4.1.1. – 96
EATON CORPORATION xxxxx+xxxx-xxxxEN
Miniature Circuit Breakers
Short Circuit Selectivity AZ towards NZM 1
In case of short circuit, there is selectivity between the miniature circuit breakers AZ and the upstream NZM up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective devices will
respond). Overload and short-circuit release unit NZM at max. value.
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic C towards NZM*)
Short circuit selectivity characteristic D towards NZM*)
AZ
NZM...1-A gL/gG
AZ
NZM...1-A gL/gG
In [A]
40
50
63
80
100
125
In [A]
40
20
0.3
0.4
0.5
0.75
0.9
1.25
50
25
0.3
0.4
0.5
0.7
0.9
1.2
63
0.4
0.5
0.7
0.85
1.2
80
0.5
0.6
0.85
1.1
100
0.6
0.85
1.1
0.8
1
32
40
50
63
80
50
63
80
100
125
1
100
125
no selectivity
Short Circuit Selectivity AZ towards NZM 2
In case of short circuit, there is selectivity between the miniature circuit breakers AZ and the upstream NZM up to the specified values of the selectivity limit current Is [kA] (i. e. in case of short-circuit currents Iks under Is, only the MCB will trip, in case of short circuit currents above this value both protective devices will
respond). Overload and short-circuit release unit NZM at max. value.
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic C towards NZM*)
AZ
NZM...2-A gL/gG
In [A]
40
50
63
80
100
125
20
0.3
0.4
0.5
0.75
0.9
1.25
1.8
25
0.3
0.4
0.5
0.7
0.9
1.2
1.7
32
40
50
63
80
100
125
0.4
160
Short circuit selectivity characteristic D towards NZM*)
AZ
NZM...2-A gL/gG
250
In [A]
40
2.5
3.5
2.4
3.3
200
160
200
250
50
1
1.4
2.6
63
1
1.3
2.3
0.5
0.7
0.85
1.2
1.65
2.3
3.2
80
0.5
0.6
0.85
1.1
1.5
2.1
2.9
100
0.6
0.85
1.1
1.5
2
2.8
0.8
1
1.4
1.8
2.5
1
1.4
1.8
2.4
1.3
1.7
2.3
1.6
2.1
50
63
80
100
125
2.1
no selectivity
Chapter 4.1.1. – 97
EATON CORPORATION xxxxx+xxxx-xxxxEN
Busbar Systems
Busbar System Easyvation BB-EV
wa_sg05912
Easyvation at a glance:
• Yard goods can be cut
• No cutting back of copper required
• No deburring required
• Almost no waste during cutting
• End capsavailable with 1- to 4-poles, end caps can be broken out for further extensions
• 4-pole end cap molded in pairs (leftand right)
Easyvation is the modular design system for busbars. Easyvation busbars
• Overlapping rail extension possible
are available as yard goods with 1, 2 or 3 poles. Now, there is a special feature: each bar can easily be extended by one-pole bar as you like. The additional pole can be added completely without tools by easy clamping technique. The lugs or forks in the Easyvationbars - available in 10 and 16 mm2
and all common distances - can be broken out at a predetermined breaking
• Rails can be extended on demand by 1-pole rails (plug-in technology)
• All step distances
• 10 and 16 mm2
• Fork and stud
point. There is actually no more flexibility available.
• Lugs can be broken out at any predetermined breaking point
Easyvation saves time and material
• Self adhesive phase indication labels available
The yard good can be cut with a saw of course. However, there is no need
• Contact preventing caps (ZV-BS-G) can be used
neither for deburring nor for cutting the conductor. Just cut to the required
dimension and close with the fitting end cap -ready! The end caps have
also breakable edges, which enable further connecting of the Easyvation.
By overlapping assembly, doubling the cross section can be achieved.
• Simple, flexible handling
• All assembly requirements can be covered by Easyvation
• Low storage space requirements due to modular system
• Less time consuming (no deburring, no cutting back)
Easyvation in use
• Individual and self configurable
Easyvation is especially well suited for solving flexible busbar applications
rack-mounted models in series. Fork-pin combinations for 1+N-applications • Fork-pin combination for 1+N application possible, feeding through rail
(terminal clamp) not possible.
can be realized by individual combinations - for this also the one-pole version with blue isolation is available besides the one with grey isolation.
• Protected technology
Even different cross sections can be combined in this case.
Accessories, such as feeder terminals and self adhesive phase marking
labels will complete the comfortable total package. Existing contact prevention caps can be used.
Chapter 5.1.1. – 1
EATON CORPORATION xxxxx+xxxx-xxxxEN
Busbar Systems
Description
Step
Distance
(mm)
Cu-factor
Type
Designation
Article No.
Units
per
package
0.22
0.24
0.24
0.31
0.36
0.46
0.58
0.56
0.58
0.57
0.22
0.24
0.24
BB-EVF-10/1P-1MU
BB-EVF-10/1P-2MU
BB-EVF-10/1P-3MU
BB-EVF-10/2P-1MU
BB-EVF-10/2P-2MU
BB-EVF-10/3P-1MU
BB-EVF-10/3P-2MU
BB-EVF-10/3P-3MU
BB-EVF-10/3P-1MU/AUX
BB-EVF-10/3P-1MU2AUX
BB-EVF-10/N-1MU
BB-EVF-10/N-2MU
BB-EVF-10/N-3MU
168826
168830
168834
168838
168840
168842
168844
168850
168846
168848
168828
168832
168836
10
10
10
10
10
10
10
10
10
10
10
10
10
0.33
0.36
0.32
0.46
0.54
0.69
0.87
0.84
0.87
0.86
0.33
0.36
0.32
BB-EVF-16/1P-1MU
BB-EVF-16/1P-2MU
BB-EVF-16/1P-3MU
BB-EVF-16/2P-1MU
BB-EVF-16/2P-2MU
BB-EVF-16/3P-1MU
BB-EVF-16/3P-2MU
BB-EVF-16/3P-3MU
BB-EVF-16/3P-1MU/AUX
BB-EVF-16/3P-1MU2AUX
BB-EVF-16/N-1MU
BB-EVF-16/N-2MU
BB-EVF-16/N-3MU
168827
168831
168835
168839
168841
168843
168845
168851
168847
168849
168829
168833
168837
10
10
10
10
10
10
10
10
10
10
10
10
10
Easyvation busbar 1m 10mm2, 16mm2 (Fork) BB-EVF
for MCBs, RCCBs, RCBOs, SPDs
• Delivered without end caps
wa_sg05712
10 mm2, Rated Current 63 A
1-phase
2-phase
wa_sg05812
3-phase
3-phase + AUX
Neutral
wa_sg05912
17.8
27
36
17.8
27
17.8
27
36
3x17.5+1x9
3x17.5+2x9
17.8
27
36
16 mm2, Rated Current 80 A
1-phase
2-phase
wa_sg06012
3-phase
3-phase + AUX
Neutral
17.8
27
36
17.8
27
17.8
27
36
3x17.5+1x9
3x17.5+2x9
17.8
27
36
Chapter 5.1.1. – 2
EATON CORPORATION xxxxx+xxxx-xxxxEN
Busbar Systems
Description
Step
Distance
(mm)
Cu-factor
Type
Designation
Article No.
Units
per
package
0.22
0.24
0.24
0.31
0.36
0.46
0.58
0.56
0.58
0.57
0.22
0.24
0.24
BB-EVP-10/1P-1MU
BB-EVP-10/1P-2MU
BB-EVP-10/1P-3MU
BB-EVP-10/2P-1MU
BB-EVP-10/2P-2MU
BB-EVP-10/3P-1MU
BB-EVP-10/3P-2MU
BB-EVP-10/3P-3MU
BB-EVP-10/3P-1MU/AUX
BB-EVP-10/3P-1MU2AUX
BB-EVP-10/N-1MU
BB-EVP-10/N-2MU
BB-EVP-10/N-3MU
168852
168856
168860
168864
168866
168868
168870
168876
168872
168874
168854
168858
168862
10
10
10
10
10
10
10
10
10
10
10
10
10
0.33
0.36
0.32
0.46
0.54
0.69
0.87
0.84
0.87
0.86
0.33
0.36
0.32
BB-EVP-16/1P-1MU
BB-EVP-16/1P-2MU
BB-EVP-16/1P-3MU
BB-EVP-16/2P-1MU
BB-EVP-16/2P-2MU
BB-EVP-16/3P-1MU
BB-EVP-16/3P-2MU
BB-EVP-16/3P-3MU
BB-EVP-16/3P-1MU/AUX
BB-EVP-16/3P-1MU2AUX
BB-EVP-16/N-1MU
BB-EVP-16/N-2MU
BB-EVP-16/N-3MU
168853
168857
168861
168865
168867
168869
168871
168877
168873
168875
168855
168859
168863
10
10
10
10
10
10
10
10
10
10
10
10
10
Type
Designation
Article No.
Units
per
package
-
BB-EV-EC/1P
BB-EV-EC/2-3P
BB-EV-EC/4P
BB-EV-EC/N
168878
168823
168824
168879
40
40
20
20
0.04
BB-EV-TE/35
168825
3
-
KLEBEBOGEN-PHASENFOLGE 169831
5
-
ZV-BS-G
10/600
Easyvation busbar 1m 10mm2, 16mm2 (Pin) BB-EVP
for MCBs, RCCBs, RCBOs, SPDs
• Delivered without end caps
wa_sg06112
10 mm2, Rated Current 63 A
1-phase
2-phase
wa_sg06212
3-phase
3-phase + AUX
Neutral
wa_sg06312
17.8
27
36
17.8
27
17.8
27
36
3x17.5+1x9
3x17.5+2x9
17.8
27
36
16 mm2, Rated Current 80 A
1-phase
2-phase
wa_sg06412
3-phase
3-phase + AUX
Neutral
17.8
27
36
17.8
27
17.8
27
36
3x17.5+1x9
3x17.5+2x9
17.8
27
36
Description
Cu-factor
Accessories
End caps BB-EV-EC
wa_sg05612
1-phase
2+3-phase
4-phase
Neutral
Terminal BB-EV-TE/35
wa_sg05312
Sticker phase sequence
wa_sg06512
Busbar Tag Shrouds ZV-BS-G
SG05705
Chapter 5.1.1. – 3
104903
EATON CORPORATION xxxxx+xxxx-xxxxEN
Busbar Systems
Technical Data
BB-EV.
General
Heat deflection temperature
Standards
Climate stability
Insulation coordination
Electrical
Impulse voltage strenght
Min. air distance
Min. creeping distance
Max. operating voltage
≥80°C UL94 VO
EN 60947-1:2007 / IEC 60947-1:2007 / IEC 60999:2000
according to DIN EN 60068
Overvoltage category III / Degree of pollution 2
≥4.5 kV
>5.5 mm
>5 mm
690 V AC/DC
1,000 V DC 1-pole only
Max. current Is/Phase
10 mm2
16 mm2
Protection class
Short circuit rating
63 A
80 A
IP20
ICC 25kA - NH3 355A
gC500V JM
PC - ABS >32 kV / mm
Dielectric strenght
Assembly instruction:
Cutting
Mounting of an extension busbar
Overlapping mounting or further connection, resp.
Brecking out of connection lugs
Sticking on phase marking
Chapter 5.1.1. – 4
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for RCDs, MCBs, Combined RCD/MCB Devices
SG30811
• Auxiliary Switch
• RCD-Tripping Module
• Shunt Trip Release
• Undervoltage Release
• Remote Control and Automatic Switching Device
• Switching Interlocks
• Terminal Covers
SG60811
Chapter 5.1.1. – 5
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Auxiliary Switch Z-HK, Z-AHK, Z-HD; Tripping Signal Switch Z-NHK
Design: for screwing
For Protective Device / Function
Type
Designation
Article No.
Units
per
package
RCCB / 1NO+1NC
Z-HK
248432
4/120
MCB, RCBO, RCCB / 1NO+1NC
Z-AHK
248433
4/120
MCB, RCBO, RCCB / 2CO
Z-NHK
248434
4/120
RCCB / 1CO+1NC
Z-HD
265620
1
SG34812
SG60911
SG61011
SG34412
Specifications | Auxiliary Switch Z-HK, Z-AHK; Tripping Signal Switch Z-NHK
Description
• Design according to IEC/EN 60947-5-1, IEC/EN 62019
• Can be mounted subsequently (screws) onto FRCmM, FRCdM
• The specified minimum voltages are per contact.
Take into account particularly in case of series connection!
Connection diagram
Dimensions (mm)
Z-HK
Z-HK
Z-AHK
Z-NHK
• Z-AHK, Z-NHK: Contact function with relative movement (selfcleaning contacts)
• Contact material and design particularly suitable for extra low voltage
• Z-NHK: The function of one of the two change-over contacts can
be switched from “auxiliary switch” to “tripping signal switch”
• Tripping signal contact transmits message of electric tripping, not
mechanical switch-off
• Test key for contact function “electrical tripping”
Z-AHK
Z-NHK
13
21
22
14
Chapter 5.1.1. – 6
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Technical Data
Electrical
Contact function
Rated voltage
Frequency
Rated current
Rated thermal current
Utilisation category AC13
Rated operational current
Utilisation category AC15
Rated operational current
Utilisation category DC12
Rated operational current
Utilisation category DC13
Rated operational current
Rated insulation voltage
Minimum operational voltage per contact
Minimum operational current
Rated peak withstand voltage
Conditional short circuit current
with back-up fuse 6A or FAZ-B4-HS
Max. back-up fuse, overload and short circuit
Mechanical
Can be mounted from the left onto
Can be mounted from the right onto
Tripping indicator “electrical tripping”
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminal protection
Terminals
Terminal capacity
Terminal screws
Fastening torque of terminal screws
Z-HK
Z-AHK
Z-NHK
1NO + 1NC
250 V
50/60 Hz
8A
8A
1NO + 1NC
250 V
50/60 Hz
4A
4A
2CO
250 V
50/60 Hz
4A
4A
Ie
6A/250V AC
2A/440V AC
3A/250V AC
–
3A/250V AC
–
Ie
–
2A/250V AC
2A/250V AC
Ie
–
0.5A/110V DC
0.5A/110V DC
Ie
0.5A/230V DC
2A/110V DC
4A/60V DC
250 V AC
24 V AC/DC
50 mA AC/DC
2.5 kV
–
–
–
250 V AC
5 V DC
10 mA DC
2.5 kV
–
–
–
250 V AC
5 V DC
10 mA DC
2.5 kV
1 kA
6 A gL / FAZ-4/../B-HS
1 kA
4 A gL / FAZ-4/../B-HS
1 kA
4 A gL / FAZ-4/../B-HS
Ith
UI
Umin
Imin
Uimp (1.2/50µ)
Ik
RCCB
MCB, RCBO
MCB, RCBO
–
–
RCCB
–
–
blue/white
45 mm
45 mm
45 mm
80 mm
80 mm
80 mm
8.8 mm (0.5MU)
8.8 mm (0.5MU)
8.8 mm (0.5MU)
onto switching device
onto switching device
onto switching device
IP40
IP40
IP40
finger and hand touch safe according to BGV A3, ÖVE-EN 6
lift terminals
lift terminals
lift terminals
0.5-2.5 mm2
0.5-2.5 mm2
0.5-2.5 mm2
M3 (Pozidrive Z0)
M3 (Pozidrive Z0)
M3 (Pozidrive Z0)
max. 0.8-1.0 Nm
max.0.8-1.0 Nm
max. 0.8-1.0 Nm
Example: Z-HK+RCCB
Example: Z-AHK+MCB
1NO+1NC 24V 50mA min.
1NO+1NC 5V 10mA min.
Example: Z-NHK+MCB RCCB+Z-NHK
2CO 5V 10mA min.
Chapter 5.1.1. – 7
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Specifications | Auxiliary Switch Z-HD
Function Auxiliary Switch Z-HD
Tripping signal switch: detects if RCD tripping occured by
an fault current
Auxiliary switch: shows the contact position of the RCD
Connection diagram
Z-HD
Technical Data
Z-HD
Electrical
Subsequent installation to the left onto
Contacts
Load rating
AC11
DC11
Mechanical
Terminal capacity
FRCmM-125A
1CO + 1NC
6 A / 230 V AC
1 A / 230 V DC
up to 2.5 mm2
Dimensions (mm)
Chapter 5.1.1. – 8
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Auxiliary Switch ZP-AHK, ZP-IHK, ZP-WHK; Tripping Signal Switch ZP-NHK
Design: for snapping
For Protective Device / Function
Type
Designation
Article No.
Units
per
package
MCB, RCBO / 1NO+1NC
ZP-IHK
286052
4/120
MCB, RCBO / 1CO
ZP-WHK
286053
4/120
MCB, RCBO / 2CO
ZP-NHK
248437
4/120
SG60811
SG34612
SG34512
Specifications | Auxiliary Switch ZP-IHK, ZP-WHK; Tripping Signal Switch ZP-NHK
Description
• Design according to IEC/EN 62019
• No screws required. Can be snapped onto FAZ and FRBmM-1N
subsequently
• ZP-IHK, ZP-WHK: Can be snapped on additionally 1 time onto
itself
• The specified minimum voltages are per contact. Take into account
particularly in case of series connection!
• Contact material and design particularly suitable for extra low voltage.
• Contact function with relative movement (self-cleaning contacts)e)
• ZP-NHK: The function of one of the two change-over contacts can
be switched from “auxiliary switch” to "tripping signal switch"
• Tripping signal contact transmits message of electric tripping, not
mechanical switch-off
• ZP-NHK: The “Service button” is used to check whether or not the
auxiliary switch is correctly wired in the tripping-signal-switch position. Activating the “service button” will mechanically simulate an
electrical switch-off, so the mechanism for the electrical switchoff
will disengage and can be checked. The main switchgear (MCB or
combined MCB/RCD) connected to the ZP-NHK auxiliary switch
does not need to trip as well during an inspection through the service button.
Connection diagram
ZP-IHK
ZP-WHK
ZP-NHK
Chapter 5.1.1. – 9
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Technical Data
Electrical
Contact function
Rated voltage
Frequency
Rated current
Rated thermal current
Utilisation category AC13
Rated operational current
Utilisation category AC15
Rated operational current
Utilisation category DC12
Rated operational current
Rated insulation voltage
Minimum operational voltage per contact
Minimum operational current
Rated peak withstand voltage
Conditional short circuit current
with back-up fuse 6A or PLSM-B4-HS
Max. back-up fuse, overload and short circuit
Mechanical
Can be mounted from the left onto
Accessories:
Tripping indicator “electrical tripping”
Frame size
Device height
Device width
Degree of protection, built-in
Terminal protection
Terminals
Terminal capacity
Terminal screws
Fastening torque of terminal screws
ZP-IHK
ZP-WHK
ZP-NHK
Ith
1NO + 1NC
250 V
50/60 Hz
6A
6A
1CO
250 V
50/60 Hz
6A
6A
2CO
250 V
50/60 Hz
4A
4A
Ie
3A/250V AC
3A/250V AC
3A/250V AC
Ie
2A/250V AC
2A/250V AC
2A/250V AC
Ie
UI
0.5A/110V DC
250 V AC
5 V DC
10 mA DC
2.5 kV
0.5A/110V DC
250 V AC
5 V DC
10 mA DC
2.5 kV
0.5A/110V DC
250 V AC
5 V DC
10 mA DC
2.5 kV
1 kA
6 A gL / FAZ-B4-HS
1 kA
6 A gL / FAZ-B4-HS
1 kA
6 A gL / FAZ-B4-HS
Umin
Imin
Uimp (1.2/50µ)
Ik
MCB, RCBO
MCB, RCBO
MCB, RCBO
ZP-ASA
ZP-ASA
ZP-ASA
–
–
blue/white
45 mm
45 mm
45 mm
80 mm
80 mm
80 mm
8.8 mm (0.5MU)
8.8 mm (0.5MU)
8.8 mm (0.5MU)
IP40
IP40
IP40
finger and hand touch safe according to BGV A3, ÖVE-EN 6
lift terminals
lift terminals
lift terminals
0.5-2.5 mm2
0.5-2.5 mm2
0.5-2.5 mm2
M4 (Pozidrive Z2)
M4 (Pozidrive Z2)
M3 (Pozidrive Z0)
max. 1.2 Nm
max. 1.2 Nm
max. 0.8-1.0 Nm
Dimensions (mm)
ZP-IHK, ZP-WHK
ZP-NHK
Example: ZP-IHK/(ZP-WHK)+MCB
Example: ZP-NHK+MCB
Chapter 5.1.1. – 10
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
RCCB-Tripping Module Z-.AM
For Protective Device
Type
Designation
Article No.
Units
per
package
RCCB
Z-FAM
248293
1/60
RCBO
Z-KAM
248294
1/60
SG16011
SG16211
Specifications | RCCB Tripping Module Z-FAM, Z-KAM
Description
• For remote switch-off of RCCBs, standard and electronic combined
RCD/MCB devices
• Remote switch-off by one or several parallel potential-free contacts,
e.g. pushbutton max. rated current 3 A at 250 V, take into account
maximum pushbutton voltage
• Remote tripping test by means of remote testing module Z-FW
• Can be mounted subsequently, to be wired according to connection
diagram with the respective terminals of the RCCB
• No undesired voltage rise in the consumer system during remote
switch-off thanks to integrated breaker contact K1-K2
Connection diagram
Z-FAM
W1
Z-KAM
K1
W
Ω
W2
W1
K2
W2
Chapter 5.1.1. – 11
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Technical Data
Electrical
Rated voltage
Frequency
Rated tripping current
Function
IΔn
Mechanical
Tripping module for
Frame size
Device height
Device width
Degree of protection, built-in
Terminal capacity
Terminal protection
Z-FAM
Z-KAM
230(400) V AC
50-60 Hz
0.01 - 0.3 A
1NO
230(400) V AC
50-60 Hz
0.01 - 0.3 A
1NO
RCCB
RCBO
45 mm
45 mm
80 mm
80 mm
8.8 mm (0.5MU)
8.8 mm (0.5MU)
IP40
IP40
1 - 2x2.5 mm2
1 - 2x2.5 mm2
finger and hand touch safe, according to BGV A3, ÖVE-EN 6
Dimensions (mm)
Z-FAM
Z7-FAM
Z-KAM
Z7-KAM
5,5
23
80
8,8
8,8
8,8
45
44
60
Connection examples Lay lines to the switching devices with double insulation and overload protection, e.g. 4A gL or CLS6-4..-HS
Connection diagram:
RCCB-2p, RCCB feed above
Connection diagram:
RCCB-4p, RCCB feed above
Z-FAM
Z-FAM
Connection diagram:
RCBO-2p, RCBO feed below
Connection diagram:
RCCB-4p, RCCB feed below
Z-FAM
Z-KAM
Chapter 5.1.1. – 12
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Shunt Trip Release Z-ASA, ZP-ASA
Operational voltage range (V~)
Type
Designation
Article No.
Units
per
package
To be glued on
12-110
110-415
Z-ASA/24
Z-ASA/230
248286
248287
1/60
1/60
To be snapped on
12-110
110-415
ZP-ASA/24
ZP-ASA/230
248438
248439
1/60
1/60
SG00712
SG00212
Specifications | Shunt Trip Release Z-ASA, ZP-ASA
Description
• Remote release for subsequent mounting onto FAZ, FRBmM-1N,
Z-MS
• Module width 1MU
• Additional installation of standard auxiliary switch is possible
• Position indicator red - green
• Type ZP-ASA for snap-on mounting
Connection diagram
1
2
Dimensions (mm)
Z-ASA
ZP-ASA
Chapter 5.1.1. – 13
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Technical Data
Z-ASA24
Z-ASA230
ZP-ASA24
ZP-ASA230
15 ms
2.2 Ω
100%
< 20 ms
2.5 kV
> 4000 operating cycles
10 ms
215 Ω
100%
< 20 ms
2.5 kV
> 4000 operating cycles
15 ms
2.2 Ω
100%
< 20 ms
2.5 kV
> 4000 operating cycles
10 ms
215 Ω
100%
< 20 ms
2.5 kV
> 4000 operating cycles
10 V
12-110 V
15 A
10 ms
60 V
110-415 V
10 V
12-110 V
2.1 A
10 ms
60 V
110-415 V
15 A
10 ms
2.1 A
10 ms
9V
10-60 V
21 A
2 ms
72 V
110-220 V
9V
10-60 V
1A
2 ms
72 V
110-220 V
21 A
2 ms
1A
2 ms
45 mm
80 mm
17.5 mm (1MU)
bonding
IP40
open mouthed/lift
45 mm
80 mm
17.5 mm (1MU)
bonding
IP40
open mouthed/lift
Klemmquerschnitt
Fastening torque of terminal screws
1-25 mm2
max. 2.4 Nm
1-25 mm2
max. 2.4 Nm
45 mm
80 mm
17.5 mm (1MU)
to snap on
IP40
open mouthed/lift
with guide
1-25 mm2
max. 2.4 Nm
45 mm
80 mm
17.5 mm (1MU)
to snap on
IP40
open mouthed/lift
with guide
1-25 mm2
max. 2.4 Nm
Connection Example 230 V
Connection Example 24 V
Example: Z-ASA + MCB
Example: ZP-ASA + MCB
Electrical
Minimum pulse duration
Internal resistance
Duty cycle
Tripping time
Rated peak withstand voltage (1.2/50µs)
Endurance
AC voltage range
Operating limit
Operational voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
DC voltage range
Operating limit
Operational voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminals above/below
Chapter 5.1.1. – 14
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Undervoltage Release Z-USA, Z-USD
Operational voltage range (V~) / Function
Type
Designation
Article No.
Units
per
package
Z-USA/115
Z-USA/230
Z-USA/400
Z-USD/115
Z-USD/230
248288
248289
248290
248292
248291
1/60
1/60
1/60
1/60
1/60
SG78811
To be screwed on
115 / undelayed
230 / undelayed
400 / undelayed
115 / delayed 0.4s
230 / delayed 0.4s
Specifications | Undervoltage Release Z-USA, Z-USD
Description
• Tripping:
Instantaneous Z-USA
Delayed Z-USD, typ. 0,4 s
• Voltage control indicator blue/white
• Service key for zero voltage switch-on for testing purposes
• Can be used with FAZ
Connection diagram
0,4 s
Chapter 5.1.1. – 15
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Technical Data
Electrical
Rated voltage
Frequency
Making threshold
Tripping threshold
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminals
Terminal capacity
Terminal protection
Un
Z-US./115
Z-US./230
Z-US./400
115 V AC
50-60 Hz
80% of Un
50% of Un
230 V AC
50-60 Hz
80% of Un
50% of Un
400 V AC
50-60 Hz
80% of Un
50% of Un
45 mm
45 mm
45 mm
80 mm
80 mm
80 mm
17.5 mm (1MU)
17.5 mm (1MU)
17.5 mm (1MU)
quick fastening on DIN rail IEC/EN 60715
IP40
IP40
IP40
open mouthed/lift
open mouthed/lift
open mouthed/lift
1 - 2x2.5 mm2
1 - 2x2.5 mm2
1 - 2x2.5 mm2
finger and hand touch safe, according to BGV A3, ÖVE-EN 6
Dimensions (mm)
Connection Example Release
Connection Examplees 400V and 230V
Connection example
Z-USA/400 + Z-MS
Chapter 5.1.1. – 16
Connection example
Z-USA/230 + MCB
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Switching interlocks IS/SPE-1TE, Z-IS/SPE-1TE
Description
Type
Designation
Article No.
Units
per
package
Switching interlock without lock
for Isolators, RCDs, combined RCD/MCBs, ...
Switching interlock without lock
for MCBs and Circuit Breaker ZP-A
IS/SPE-1TE
101911
5/30
Z-IS/SPE-1TE
274418
5/30
SG47812
Specifications | Switching interlocks IS/SPE-1TE, Z-IS/SPE-1TE
Description
• Without lock
Type IS/SPE-1TE:
• for Isolators, RCDs, combined RCD/MCBs, ...
Type Z-IS/SPE-1TE:
• for MCB
Chapter 5.1.1. – 17
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for Add-on Residual Current Protection Unit FBHmV
Shunt Trip Release Kit Z-BHASA
Operational voltage range V~
Type
Designation
Article No.
Units
per
package
110-415
12-60
Z-BHASA/230
Z-BHASA/24
248445
248444
8
8
SG09411
Specifications | Shunt Trip Release Kit Z-BHASA
Description
• Can be mounted subsequently
• Contact position indicator red - green
• Wide operational voltage range
• Sufficient power of extra low voltage source must be ensured
FBHmV-ASA/24: min. 90 VA
• Screws for mounting included FBHmV => BHASA => AZ
Connection diagram
1
2
Chapter 5.1.1. – 18
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for Add-on Residual Current Protection Unit FBHmV
Technical Data
Electrical
Minimum pulse duration
Internal resistance
Duty
Tripping time
Peak withstand voltage (1.2/50µs)
Endurance
AC voltage range:
Responding limit
Operational voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
DC voltage range:
Responding limit
Operational voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Upper and lower terminal screws
Terminal capacity
Fastening torque of terminal screws
Z-BHASA/24
Z-BHASA/230
15 ms
2W
100%
< 20 ms
2 kV
>4,000 operating cycles
10 ms
130 W
100%
< 20 ms
2 kV
>4,000 operating cycles
8V
12-60 V
14 A
4.0 ms
70 V
110-415 V
3.4 A
4.5 ms
11 V
12-60 V
23.5 A typ.
2 ms
90 V
110-230 V
1.7 A typ.
4 ms
45 mm
45 mm
90 mm
90 mm
27 mm
27 mm
quick fastening on DIN rail IEC/EN 60715
IP40
IP40
lift terminals
lift terminals
2.5-30 mm2
2.5-30 mm2
4 Nm
4 Nm
Dimensions (mm)
Chapter 5.1.1. – 19
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for Miniature Circuit Breakers AZ
Shunt Trip Release Z-LHASA
Operational voltage range V~
Type
Designation
Article No.
Units
per
package
110-415
12-60
Z-LHASA/230
Z-LHASA/24
248442
248441
8
8
SG09311
Specifications | Shunt Trip Release Z-LHASA
Description
• Can be mounted subsequently
• Contact position indicator red - green
• Wide operational voltage range
• Sufficient power of extra low voltage source must be ensured
Z-LHASA/24: min. 90 VA
Connection diagram
Dimensions (mm)
1
2
Technical Data
Electrical
Minimum pulse duration
Internal resistance
Duty
Tripping time
Peak withstand voltage (1.2/50µs)
Endurance
AC voltage range:
Responding limit
Operational voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
DC voltage range:
Responding limit
Operational voltage range
Maximum current consumption during switch-on
Current flow time at max. current consumption
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Upper and lower terminal screws
Terminal capacity
Fastening torque of terminal screws
Z-LHASA/24
Z-LHASA/230
15 ms
2W
100%
< 20 ms
2 kV
>4,000 operating cycles
10 ms
130 W
100%
< 20 ms
2 kV
>4,000 operating cycles
8V
12-60 V
14 A
4.0 ms
70 V
110-415 V
3.4 A
4.5 ms
11 V
12-60 V
23.5 A typ.
2 ms
90 V
110-230 V
1.7 A typ.
4 ms
45 mm
45 mm
90 mm
90 mm
27 mm
27 mm
quick fastening on DIN rail IEC/EN 60715
IP40
IP40
lift terminals
lift terminals
2.5-30 mm2
2.5-30 mm2
4 Nm
4 Nm
Chapter 5.1.1. – 20
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for Miniature Circuit Breakers AZ
Auxiliary Switch Z-LHK
Function
Type
Designation
Article No.
Units
per
package
1NO+1NC
Z-LHK
248440
10/100
SG16111
Specifications | Auxiliary Switch Z-LHK
Description
• Auxiliary switch according to IEC 947-5-1
• Can be mounted subsequently
Technical Data
Z-LHK
Electrical
Contact function
Rated voltage
Frequency
Rated current
Rated thermal current
Utilisation category AC13
Rated operational current
Utilisation category AC15
Rated operational current
Utilisation category DC12
Rated operational current
Utilisation category DC13
Rated operational current
Rated insulation voltage
Minimum operational voltage per contact
Minimum operational current
Rated peak withstand voltage
Conditional short circuit current
with back-up fuse 6A or FAZ-B4-HS
Max. back-up fuse, overload and short circuit
Mechanical
Can be mounted from the left onto
Can be mounted from the right onto
Tripping indicator “electrical tripping”
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminal protection
Terminals
Terminal capacity
Terminal screws
Fastening torque of terminal screws
Ith
1NO + 1NC
250 V
50/60 Hz
8A
8A
Ie
6A/250V AC
2A/440V AC
Ie
–
Ie
–
Ie
0.5A/230V DC
2A/110V DC
4A/60V DC
250 V AC
24 V AC/DC
50 mA AC/DC
2.5 kV
UI
Umin
Imin
Uimp (1.2/50µ)
Ik
1 kA
6 A gL / FAZ-4/../B-HS
AZ
–
–
45 mm
80 mm
8.8 mm (0.5MU)
onto switching device
IP40
finger and hand touch safe according to BGV A3, ÖVE-EN 6
lift terminals
0.5-2.5 mm2
M3 (Pozidrive Z0)
max. 0.8-1.0 Nm
Chapter 5.1.1. – 21
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Connection diagram
13
21
22
14
Dimensions (mm)
Chapter 5.1.1. – 22
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for Miniature Circuit Breakers AZ
Interlocks LH-SP
Function
Type
Designation
Article No.
Units
per
package
Tripping interlock
Tripping interlock
Switchoff interlock
LH-SPL
LH-SPE
LH-SPA
285752
215999
216000
1
1
1
Specifications | Anti-Tamper Device LH-SPE, LH-SPL
Description
• Prevents undesired switching ON or OFF
Specifications | Switchoff Interlock LH-SPA
Description
• Prevents undesired switch-OFF
Dimensions (mm)
Chapter 5.1.1. – 23
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for Miniature Circuit Breaker FAZ-..-NA, -RT
Auxiliary Contact Z-IHK-NA
Operational Voltage Range
Type
Designation
Article No.
Units
per
package
250 VAC
Z-IHK-NA
113895
1
SG60711
Specifications | Auxiliary Contact Z-IHK-NA
Description
• Design according to IEC/EN 60947-5-1, IEC/EN 62019
• Field installable
• The specified minimum voltages are per contact—take into account
particularly in case of series connection
• Self-cleaning contacts
• Contact material and design particularly suitable for extra low voltage
• Tripping signal contact transmits message of electric tripping, not
mechanical switch-off
• Test key for contact function “electrical tripping”
• Will allow for > 480Y/277 VAC rating
Connection diagram
Chapter 5.1.1. – 24
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Technical Data
Z-IHK-NA
Electrical
Contact function
Rated voltage
Rated current
Rated thermal current
Utilization category AC13
Rated operational current
Utilization category AC15
Rated operational current
Utilization category DC12
Rated operational current
Rated insulation voltage
Minimum operational voltage per contact
Minimum operational current
Rated peak withstand voltage
Conditional short circuit current
with Back-Up Fuse 6A
Max. back-up fuse, overload and short circuit
Mechanical
Tripping indicator “electrical tripping”
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminal protection
Terminals
Terminal capacity
Terminal screws
Tightening torque of terminal screws
Ith
1NO + 1NC
250V
6A
6A
Ie
3A/250 Vac
Ie
2A/250 Vac
Ie
U
0.5A/110 Vdc
250 Vac
5 Vdc
10 mA AC/DC
4 kV
I
Umin
Imin
Uimp (1.2/50µ)
Ik
1 kA
6 A gL / FAZ-4/../B-HS
—
45 mm
80 mm
8.8 mm (0.5MU)
—
IP40
Finger and hand touch safe according to BGV A3, ÖVE-EN 6
Lift terminals
0.5–2.5 mm2
M3 (Pozidrive Z2)
max. 1.2 Nm
Dimensions (mm)
Chapter 5.1.1. – 25
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Accessories for Miniature Circuit Breaker FAZ-..-NA, -RT
Shunt Trip FAZ-XAA-NA
Operational Voltage Range
Type
Designation
Article No.
Units
per
package
12–110 VAC
12–60 VDC
110–415 VAC
110–230 VDC
FAZ-XAA-NA12-110VAC
102037
1
FAZ-XAA-NA110-415VAC 102036
1
SG13511
Specifications | Shunt Trip FAZ-XAA-NA
Description
• Remote release for subsequent mounting onto FAZ-NA
• Additional installation of standard auxiliary switch is possible
• Position indicator red–green
Connection diagram
1
2
Technical Data
Electrical
Can be mounted onto
Operational voltage range
Frequency
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminal protection
Terminals
Terminal capacity, one and two wires
FAZ-XAA-NA12-110VAC
FAZ-XAA-NA110-415VAC
FAZ-NA / FAZ-NA-DC / FAZ-RT
12–110 Vac
12–60 Vdc
50/60 Hz
FAZ-NA / FAZ-NA-DC / FAZ-RT
110–415 Vac
110–230 Vdc
50/60 Hz
45 mm
45 mm
105 mm
105 mm
17.5 mm
17.5 mm
Quick fastening with two lock-in positions on EN 50022
IP40
IP40
Finger and hand touch safe
Finger and hand touch safe
according to BGV A3, ÖVE-EN 6 according to BGV A3, ÖVE-EN 6
Open mouthed/lift
Open mouthed/lift
18–10 AWG
18–10 AWG
Chapter 5.1.1. – 26
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Terminal Covers
Description
Type
Designation
Article No.
Units
per
package
Terminal Covers for RCDs
2-pole
4-pole
Z-RC/AK-2TE
Z-RC/AK-4TE
285385
101062
10
10
Terminal Covers for Add-on Device
2-pole
3+4-pole
Z-CV/AO-2P
Z-CV/AO-3-4P
221957600
221957500
?
?
Terminal Covers for MCB, RCBO
2-pole
3-pole
4-pole
Z-CV/SD-2P
Z-CV/SD-3P
Z-CV/SD-4P
221954800
221954900
221953900
?
?
?
Terminal Cover for MCB
1-pole
Z7-AK-1TE
750754200
?
Chapter 5.1.1. – 27
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Remote Control and Automatic Switching Device Z-ZW
Function
Type
Designation
Article No.
Units
per
package
Automatic restarting 230VAC
Automatic restarting 24-48VDC
Z-FW-LP
Z-FW-LPD
248296
265244
1/20
1/20
+ Remote control
Z-FW-MO
ON/OFF/TEST
(only in connection with Z-FW-LP, -LPD from delivery date 2006!)
284730
1
Operational voltage range
Type
Designation
Article No.
Units
per
package
230 VAC
24-48 VDC
Z-FW-LP/MO
Z-FW-LPD/MO
290171
290172
1/12
1/12
Operational voltage range
Type
Designation
Article No.
Units
per
package
0.01 A
0.03 A
0.1 A
0.3 A
0.5 A
Z-FW/001
Z-FW/003
Z-FW/010
Z-FW/030
Z-FW/050
248297
248298
248299
248300
248301
4/120
4/120
4/120
4/120
4/120
SG30811
SG30711
Pre-mounted sets Z-FW
SG31311
Remote Testing Module Z-FW
(for Z-FW-LP./MO set use only)
SG12111
Specifications | Remote Control and Automatic Switching Z-FW
Description
• Shape compatible switching device suitable for subsequent installation for automatic re-setting and remote control of CLS6, PFIM,
PFHM-4p, dRCM, Z-A40, PFR, Z-MS
• Mechanical interlock, can be sealed with leads
• Mechanical switching capability up to max. PFIM-100/4p,
CLS6-100/4p
• Operating and alarm display by green and red LED
• Function extension with Switching Modul Z-FW-MO
Operating and trouble display by LED pre-assembled only with
Z-FW...
Connection diagram
Z-FW-LP
Z-FW-LPD
Z-FW-MO
Chapter 5.1.1. – 28
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Technical Data
Electrical
Possible operating voltages
Frequency
Testing module (0.5MU) for remote testing of RCDs
Control voltage for remote control
Relay output for tripping test with Z-FW
Relay output for alarm, potential-free
Functions
Function selector
Remote control function via telephone with Telecommander
Mechanical
Frame size
Device height
Device width
Mounting
Degree of protection, built-in
Terminal protection
Terminals
Terminal capacity
Scope of delivery
Z-FW-LP
Z-FW-LPD
Z-FW-MO
220-240 V AC
50/60 Hz
Z-FW...
–
–
5A/250V AC
automatic restarting
Automatic 5x,
OFF/RESET
–
24-48 V DC
–
Z-FW...
–
–
5A/250V AC
automatic restarting
Automatic 5x,
OFF/RESET
–
–
–
–
24-230 V AC/DC
400 V AC max.
–
+ON/OFF/TEST
ON, OFF/RESET
–
45 mm
45 mm
45 mm
80 mm
80 mm
80 mm
70 mm
70 mm
35 mm
quick fastening with 2 lock-in positions
–
on DIN rail IEC/EN 60715
IP40
IP40
IP40
finger and hand touch safe according to BGV A3, ÖVE-EN 6
lift terminals
lift terminals
lift terminals
2 x 1.5 mm2 or
2 x 1.5 mm2 or
4 x 1.5 mm2 or
1 x 2.5 mm2
1 x 2.5 mm2
2 x 2.5 mm2
–
–
Coupling plug
Dimensions (mm)
Z-FW-MO
Z-FW-LP, -LPD
Connection example
CLS6-4..-HS
Z-FWLPD
Z-FWMO
PFIM-4p
PFIM-4p
Connection diagram:
PFIM-4p RCD feed above
Alarm function and lamp
*) discretionary polarity
Electrical system
Z-FW-LP
Voltage supply
AC /DC 24-230 V
Pre-mounted Sets
Z-FW-LPD/MO
Z-FW-LP/MO
Chapter 5.1.1. – 29
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Specifications | Remote Testing Module Z-FW (for Z-FW-LP)
Description
• External testing module with testing resistor for RCDs
• Proper "external" test key function according to the applicable rules
thanks to design adapted to the rated tripping current
• For remote testing with remote control and automatic switching
device Z-FW-LP
• No undesired voltage rise in the consumer system during remote
switch-off thanks to integrated breaker contact K1-K2
• Can also be used as a remote tripping module for PFIM, PFHM
Dimensions (mm)
Connection examples
Connection diagram:
PFIM-2p, RCD feed above
Connection diagram:
PFIM-4p, RCD feed above
Z-FW-LP
Z-FW
PFIM-2p
PFIM-4p
Z-FW-LP
Z-FW
Chapter 5.1.1. – 30
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Main Load Disconnector Switch (Isolator) IS
Rated Current (A)
Poles
Type
Designation
Article No.
Units
per
package
16
16
16
16
20
20
20
20
25
25
25
25
32
32
32
32
40
40
40
40
63
63
63
63
80
80
80
80
100
100
100
100
125
125
125
125
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
IS-16/1
IS-16/2
IS-16/3
IS-16/4
IS-20/1
IS-20/2
IS-20/3
IS-20/4
IS-25/1
IS-25/2
IS-25/3
IS-25/4
IS-32/1
IS-32/2
IS-32/3
IS-32/4
IS-40/1
IS-40/2
IS-40/3
IS-40/4
IS-63/1
IS-63/2
IS-63/3
IS-63/4
IS-80/1
IS-80/2
IS-80/3
IS-80/4
IS-100/1
IS-100/2
IS-100/3
IS-100/4
IS-125/1
IS-125/2
IS-125/3
IS-125/4
276254
276255
276256
276257
276258
276259
276260
276261
276262
276263
276264
276265
276266
276267
276268
276269
276270
276271
276272
276273
276274
276275
276276
276277
276278
276279
276280
276281
276282
276283
276284
276285
276286
276287
276288
276289
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
12/120
1/60
1/40
1/30
Type
Designation
Article No.
Units
per
package
IS/SPE-1TE
Z-IS/AK-1TE
101911
276290
5/30
10/600
SG10611
SG10711
SG10811
SG10911
Accessories
Description
SG47812
Switching interlock without lock for Isolators,
RCDs, combined RCD/MCBs, ...
Terminal cover
Switching interlock IS/SPE-1TE
Terminal Cover Caps Z-IS/AK-1TE
• Without lock
• Also suitable for PFIM, CFI6, PKNM, CKN6
• Can be sealed with leads
• Modular design, width 1 MU
Chapter 5.1.1. – 31
EATON CORPORATION xxxxx+xxxx-xxxxEN
Accessories for Protective Devices
Specifications | Main Load Disconnector Switch (Isolator) IS
Description
• Load circuit breaker with isolating function
• Design according to IEC/EN 60947-3
• Highly wear resistant contacts
• Quick make, black toggle
• Terminal capacity 50 mm2
• Compatible busbars with switchgear series Xpole by use of the
mouth terminal in combination with standard fork busbar
Connection diagram
1-pole
2-pole
3-pole
4-pole
Technical Data
IS-16
IS-20 IS-25 IS-32 IS-40 IS-63 IS-80 IS-100 IS-125
Electrical
Design
according to IEC/EN 60947-3
Rated voltage
240/415 V
Frequency
50/60 Hz
Rated insulation voltage
Ui 690 V~
Rated peak withstand voltage
Uimp 6 kV
Pollution degree
3
Rated short-time withstand current
Icw 2 kA
Rated short-circuit making capacity
Icm 2.8 kA
Rated current
240/415V, AC23A
16 A
20 A
25 A
32 A
40 A
63 A
80 A
100 A 125 A
Number of poles
1-, 2-, 3-, 4-pole
Maximum back-up fuse
125 A gG
Short circuit strength - with back-up fuse acc. to the applicable rules
IEC/EN 60947-3
12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA 10 kA 10 kA
Endurance
electrical components operation cycles
≥3.000 ≥3.000 ≥ 3.000 ≥3.000 ≥3.000 ≥3.000 ≥3.000 ≥3.000 ≥2.000
mechanical components operation cycles
≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥16.000 ≥14.000
Mechanical
Frame size
45 mm
Device height
80 mm
Device width
17.5mm/pole
Mounting
quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715
Degree of protection, built-in
IP40
Terminal protection
finger and hand touch safe according to BGV A3
Terminals
open mouthed/lift terminals
Terminal capacity
2.5 - 50 mm2
Busbar thickness
0.8 - 2 mm
Fastening torque of terminal screws
2.5 - 5 Nm
Function
irrespective of the position of installation
Dimensions (mm)
Terminal cover caps
Z-IS/AK-1TE
Anti-tamper
device
IS/SPE1TE
Chapter 5.1.1. – 32
EATON CORPORATION xxxxx+xxxx-xxxxEN
Our focus is on delivering the right solution for the application. But,
decision makers demand more than just innovative products. They
turn to Eaton for an unwavering commitment to personal support
that makes customer success a top priority.
For more information, visit www.eaton.eu/electrical
To contact an Eaton salesperson
or local distributor/agent, please visit
www.eaton.eu/electrical/customersupport
Eaton Industries (Austria) GmbH
Scheydgasse 42
1215 Wien
Austria
Eaton Industries Manufacturing GmbH
EMEA Headquarters
Route de la Longeraie
1110 Morges
Switzerland
© 2013 Eaton Industries (Austria) GmbH
Subject to technical modifications. No
responsibility is taken for misprints or errata.
Printed in Austria (05/13)
Publication number
Grafics: SRA
DigiPics, Lithos:
Print: