ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers Experiment No. 1 Three Phase Transformers Objective: The objectives of this experiment are to find the approximate per phase equivalent circuit parameters of a 3-φ transformer bank using short circuit and open circuit tests and to determine the regulation and efficiency of the transformer bank through load test. The regulation and efficiency of the transformer bank determined through load test will be compared with those calculated using the transformer parameters. Apparatus: 1. 1 3-φ variac 2. 2 Test tables 3. 4 multimeters 4. 2 wattmeters 5. 1 15 kVA 3- φ transformer Bank 6. 1 3-φ Resistive load bank with fan 7. 1 3-φ Capacitive Load Bank Procedure: 1. Short Circuit Test: a) Refer to Fig.1 for Short circuit test. Connect the high voltage windings of each 1-φ transformer in parallel and then connect them in STAR configuration. Connect the low voltage windings of each 1-φ transformer in parallel and then connect them in DELTA configuration. Make sure that the transformer is connected according to nameplate specifications. b) Connect the three phases of the low voltage windings to test table 2. Connect the three phases of the high voltage windings through the test table to the output terminals of the variac. Make sure that all test table line switches are open. Connect the input terminals of the variac to the 120V AC power panel. Do not turn on power. Have the lab instructor check your set up. c) With the test table's line switches still open, turn on power and adjust the variac until its output voltage is zero. 1/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers d) Calculate the rated current for the input windings. Check your value with the lab instructor. Make sure that your current transformer is set up to handle this current. e) Protecting the measuring instruments, close the test table line switches. Immediately after closing the line switches check the current in lines 1,2 and 3. The current should be close to zero. If the current is not close to zero de-energize your circuit and recheck it. f) Increase the output voltage of the variac until the ammeter in line 1 indicates rated current. Measure and record VH12, VH23, VH31, IH1, IH2, IH3, IX1, IX2, IX3, PHWM1 and PHWM2. Protect your measuring instruments and de-energize the circuit. Readings should be taken with great precaution as you may see currents as high as 100A! 2. Open Circuit Test: a) Refer to Fig.2 for Open circuit test. Connect the high voltage windings of each 1-φ transformer in parallel and then connect them in STAR configuration. Connect the low voltage windings of each 1-φ transformer in parallel and then connect them in DELTA configuration. Make sure that the transformer is connected according to nameplate specifications. b) Connect the three phases of the high voltage windings to test table 1. Make sure that the output connections are open circuited! Connect the three phases of the low voltage windings through test table 2 to the output terminals of the 120V AC power panel. Make sure that all test table line switches are open. Do not turn on power. Have the lab instructor check your set up. g) Measure and record VX12, VX23, VX31, IX1, IX2, IX3, PXWM1, PXWM2, VH12, VH23 and VH31. Readings should be taken with great precaution as you may see voltages as high as 420V! 3. Transformer with R Load: a) Set up the circuit as shown in Fig.3. b) Make sure that the resistance bank is connected to rated voltage. Open circuit the secondary; i.e., resistance set to infinity. Turn ON the mains and then turn the switches on the test table to ON position. c) Now adjust the resistive load until IH1 = IH2 = IH3 = rated current. Measure and record VX12, VX23, VX31, IX1N, IX2N, IX3N, PXWM1, PXWM2, VH12, VH23, VH31, IH1N, IH2N, IH3N, PHWM1, PHWM2 and PHWM3 for rated current. .ote that a two-wattmeter method is used on LV side and a three-wattmeter method on HV side for measurement of three-phase power. So the selection switch on HV side should be used only between positions 1-. and 3-.. 2/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers d) Now vary the load resistance such that IH1 = IH2 = IH3 equals ½ of rated current. Measure and record the same quantities as in step “c” for each value of IH. 4. Transformer with RC Load: a) Set up the circuit as shown in Fig.4. b) Make sure that the resistance and capacitive bank are connected to rated voltage. Open circuit the secondary by setting the resistance bank and capacitance bank to infinity. Turn ON the mains and then turn the switches on the test table ON. Now adjust the resistive and capacitive loads such that they draw equal currents and the line currents IH1 = IH2 = IH3 = rated current. Measure and record VX12, VX23, VX31, IX1N, IX2N, IX3N, PXWM1, PXWM2, VH12, VH23, VH31, IH1N, IH2N, IH3N, PHWM1, PHWM2 and PHWM3 for rated current. .ote that a two-wattmeter method is used on LV side and a threewattmeter method on HV side for measurement of three-phase power. The selection switch on HV side should be used only between positions 1-. and 3-.. c) Now vary the load resistance such that IH1 = IH2 = IH3 equals ½ of rated current. Measure and record the same quantities as in step “c” for each value of IH. Report: 1. Designate the parallel connected low voltage (X) windings the primary and the parallel connected high voltage (H) windings the secondary. 2. Using the data found in the open circuit test calculate RC,X1 and XM,X1. GCX1 is given by Poc GMX Poc 3 Voc 3 2 2 Voc BM,X is given by BMX 2 Where Yoc 2 Yoc − GMX Ioc Voc 3 3/11 ECE 420 Spring 2007 on-campus Ioc CT ⋅ Experiment o. 1 Three Phase Transformers IX1 + IX2 + IX3 3 VX13 + VX23 + VX12 Voc PT⋅ Poc WMR⋅PT⋅CT ⋅ PXWM1 + PXWM2 3 ( ) Where WMR is the Wattmeter ratio, CT is the current transformer ratio and PT is the Potential Transformer ratio (Treat PT = 1 for the whole experiment). 3. Using the data found in the short circuit test calculate Req,H and Xeq,H. ReqH is given by Vsc ZeqH 3 Isc Xeq,H is given by XeqH 2 2 ZeqH − ReqH Where ReqH Psc 3 2 Isc Draw the approximate per phase transformer equivalent circuit with all parameters referred to the primary (LV side) as shown in Fig 5. Show the calculated values of each parameter. Remember to include units. Remember the short circuit test was performed with the voltage applied to the high voltage side! Also make a note of the transformation ratio “a”. 4. Efficiency from input and output power measurements: The efficiency of a transformer is given by: P out %η ⋅ 100 P in a) Using the data gathered in Part 3, Transformer with R Load, calculate the efficiency (η) of the transformer for full, ½ and no load. b) Using the data gathered in Part 4, Transformer with RC Load, calculate the efficiency (η) of the transformer for full, ½ and no load. 4/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers 5. Voltage regulation from the voltage measurements: Voltage regulation of a transformer is given by: %Reg VHLLnoload − VHLLload VHLLload Where VHLL = the average Line to Line voltage on HV side. a) Using the data gathered in Part 3, Transformer with R Load, calculate the voltage regulation of the transformer for full, ½ and no load. b) Using the data gathered in Part 4, Transformer with RC Load, calculate the voltage regulation of the transformer for full, ½ and no load. 6. Efficiency from the transformer equivalent circuit parameters: a) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side average current), and PF (power factor), gathered in Part 3, Transformer with R Load, and the equivalent circuit of your transformer, calculate the efficiency of the transformer for full, ½ and no load. b) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side average current), and PF (power factor), gathered in Part 4, Transformer with RC Load, and the equivalent circuit of your transformer, calculate the efficiency for the transformer for full, ½ and no load. 7. Voltage Regulation from the transformer equivalent circuit and its parameters a) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side average current), and PF (power factor), gathered in Part 3, Transformer with R Load, and the equivalent circuit of your transformer, calculate the voltage regulation of the transformer for full, ½ and no load. b) Using the values of VXLN (LV side average line to neutral voltage), IX (LV side average current), and PF (power factor), gathered in Part 4, Transformer with RC Load, and the equivalent circuit of your transformer, calculate the voltage regulation for the transformer for full, ½ and no load. 8. Compare the results found in step 4 with 6 and step 5 with 7 of the report section. Calculate percent differences. What conclusions can you draw? 5/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers Table1: Short Circuit Test: Quantity Measured reading HV Side Readings PHWM1 PHWM2 VH12 VH23 VH13 IH1 IH2 IH3 LV Side Readings IX1 IX2 IX3 Table 2: Open Circuit Test: Quantity Measured reading LV Side Readings PXWM1 PXWM2 VX12 VX23 VX13 IX1 IX2 IX3 HV Side Readings VH1 VH2 VH3 6/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers Table 3: R Load: Quantity Full Load ½ Full Load LV Side Readings PXWM1 PXWM2 VX12 VX23 VX13 IX1 IX2 IX3 HV Side Readings PH1 PH2 PH3 VH1 VH2 VH3 IH1 IH2 IH3 7/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers Table 4: RC Load: Quantity Full Load ½ Full Load LV Side Readings PXWM1 PXWM2 VX12 VX23 VX13 IX1 IX2 IX3 HV Side Readings PH1 PH2 PH3 VH1 VH2 VH3 IH1 IH2 IH3 IHR1 IHR2 IHR3 IHC1 IHC2 IHC3 8/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers 3 VARIAC A TEST TABLE1 1H TEST TABLE2 HV SIDE LV SIDE STAR DELTA H1 H3 1X X1 X3 AC N AC N AC N B C 2H X2 X4 H2 H4 H1 H3 2X X1 X3 N N X2 X4 H2 H4 3H H1 H3 3X X1 X3 N N X2 X4 H2 H4 LOW VOLTAGE SIDE SHORT CIRCUITED Fig.1. Short Circuit Test, Part 1 TEST TABLE 2 A LV SIDE DELTA 1X HV SIDE TEST TABLE 1 STAR H1 H3 1H X1 X3 AC AC N 120 V 240 V X2 X4 AC H2 H4 2X C H1 H3 B 2H X1 X3 120 V 240 V X2 X4 H2 H4 3X X1 X3 120 V H1 H3 3H 240 V N X2 X4 H2 H4 HIGH VOLTAGE SIDE OPEN CIRCUITED Fig.2. Open Circuit Test, Part 2 9/11 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers TEST TABLE 2 A 1 LV SIDE HV SIDE DELTA STAR TEST TABLE 1 H1 H3 1 IHR1 X1 X3 AC AC N 120 V 240 V X2 X4 AC H2 H4 2 C H1 H3 B 2 IHR2 X1 X3 120 V R 240 V R X2 X4 H2 H4 3 X1 X3 120 V H1 H3 3 240 V N X2 X4 H2 H4 Fig.3. Transformer with resistive load, Part 3 Fig.4. Transformer with resistive and capacitive load, Part 4 10/11 R IHR3 ECE 420 Spring 2007 on-campus Experiment o. 1 Three Phase Transformers IH Req,X VXLNAC Xeq,X IX VX a= a GM,X BM,X NX 3⋅ N H aVH a2ZLOAD Fig. 5. Per Phase Equivalent Circuit referred to LV side for the 3φ Transformer. 11/11