ADR239B Introduction: • Switch on to fault (SOTF) function ASHIDA has designed economical & reliable • Power swing function (68) Multifunction ADR239B Protection & Control • Load encroachment function System. compact • POTT / PUTT scheme. construction of ADITYA series ADR239B • Directional / Non Directional Phase & relay The provides simple and integrated Protection, Ground Control and Monitoring functions for Over head Transmission Lines, Underground • • Four Independent Settings Groups • Directional / Non Directional Impedance Function (21/21N) Impedance direction Six Independent Measuring (AB/BC/CA/AN/BN/CN) • Zone1 extension. • Independent Three Stages Directional Stages for of Ground Directional/Non Over Current Protection. • Inverse time Over Current Protection (IEC Zones (Polygon) settable in forward / reverse • Three Current Protection. Key Protection & Control Functions: Independent Function Directional/Non Directional Phase Over Functional Overview: Five Current (50/51/51N/50N/67/67N) cables, and Distributed Feeders. • Over /IEEE curves according to IEC60255). • Two Stages of Inverse & Definite time Negative Phase Sequence Over Current Loop Protection (46). • Broken Conductor Protection (46BC) Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 1 of 16 ADR239B • Negative Phase Sequence Over Voltage Protection (47) • Password Protection. Broken conductor Protection (I2/I1 – Software Support: 46BC) • Setting Editor. Two Stages of Phase Under and Over • Programmable scheme logic Editor. Voltage Protections (27 /59) • Settings upload / download. • Offline Settings Editor. Protection. • Online Measurement / Metering. • Residual Over Voltage Protection (59N). • Disturbance analysis. • Multi • • • Positive Sequence shots Over (4-shots) Voltage Auto-reclosing function. • Breaker Failure detection (50BF) • VT and CT supervision function. • Trip circuit supervision function. • Programmable Inputs & Outputs. • CB Close / Trip from HMI • Programmable & Target LEDs ADR239B numerical multifunction machine terminal protection relay designed for Line, Feeder & Machine protection applications. Relay designed with fast and selective tripping for indication with dual colours (16 nos.) Self Supervision of relay • Metering function. • Disturbance Recording (10 nos.) • Event Recording (1028 nos.) • Fault Recording on HMI display (10nos.) • Fault locator. • Non-Volatile memory. • Fully communicable with IEC standard protocol ensures the stability and availability of electrical power system. ADR239B relay apply for protection, control • open Applications: & monitoring of line radial and ring main feeder to achieve sensitivity and selectivity on phase and ground faults. IEC60870-5-103, MODBUS & IEC 61850. • Separate communication port for communication for SCADA Communication. • PC front port convenient relay settings. • User friendly local operation with key Line Protection application pad. • Large Liquid crystal display (20X4) with backlight Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 2 of 16 ADR239B The functional overview of current Protection ADR239B: 68 Out of Step Protection 50BF Breaker Failure VTS VT Supervision Detection CTS CT Supervision Detection 79 Auto reclosing 86 Lockout (Trip command) Impedance Function (21/21N): The core functionality of ADR239B relay is Protection functions Overview ANSI Code 21 21N Description a full-scheme distance protection. The relay provides five independent polygon impedance zone characteristics to users. Relay provides independent resistive reach Phase Impedance Protection (R) and reactive reach (X) settings. All Ground Voltage Protection zones are used separately Phase to Phase 27 Under Voltage Protection and Phase to Ground faults. High resistive 46 Negative Phase Sequence Protection ground faults can be covered with polygon 46BC Broken Conductor Detection 47 Negative Phase Sequence Over Voltage Protection 50 Instantaneous/Definite Time Phase Over current Protection 51 Inverse Time Phase Over current Protection 50N 51N 59 Instantaneous/Definite Time Ground Over current Protection Inverse Time Ground Over current Protection characteristic by adjusting resistive reach. The resistance section can be set based on high resistive faults and reactive reach can be set based on line parameters. Operating time of each zone shall be independently settable for phase faults and ground faults. Forward and reverse resistive/reactive reach settings are independently set. All the distance (Impedance) zones can be set either for forward or reverse direction or non directional. Over Voltage Protection 59N Residual Over Voltage Protection FLC Fault locator 67P Directional Phase Over current Protection 67N Directional Ground Over Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 3 of 16 ADR239B impedance). ADR239B detect power swing when the impedance passes through ΔR and ΔX zone in more than 35ms. Relay provides polygon “Inner” and “Outer” characteristics to meet the criteria of power swing detection. ADR239B relay provides power swing blocking delay settable. Any of selected zone operation (Z1/Z1ext./Z2/Z3/Z4 /Z5) Zone characteristic can be blocked for preset time delay. Switch on to fault (SOTF) over Distance current function (50S): zones unblock automatically, when asymmetrical faults detected during ADR239B relay provides switch on to fault power swing block condition. Power swing (SOTF) protection against energizing faulty trip delay (out of step trip delay) provides line by switching on circuit breaker. It feature to initiate tripping during unstable provides three pole tripping. Switch on to power swing condition. fault initiation can be detected through digital input of “Manual close command from circuit breaker controls” or “automatic reclosing of circuit breaker”. Power Swing Detection (68/68T): Dynamic/Transient conditions like power power system system faults, network switching, load fluctuations, autoreclosing, sudden line outages, Major Power swing characteristic generation loss can cause power swing in transmission network. Large amount of current flows with small voltages, resulting initiate zones. unwanted To avoid tripping unwanted of distance tripping of distance zones (during recoverable power swing), power ADR239B swing provides detection feature of function. Power swing can be detected under symmetrical load condition (positive sequence Power swing stable Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 4 of 16 ADR239B following tripping characteristics (IEC) are available; • IEC Normal Inverse Curve (C1) for 3s • IEC Normal Inverse Curve (C2) for 1.3s • IEC Very Inverse Curve (C3) • IEC Extremely Inverse Curve (C4) • Long time Inverse Curve (C5) • Definite time Over current (C6) K * a t= current Protection (50/50N/51/51N/67P/67N): The relay provides Directional and Non Directional phase and ground over current with multiple settings (four stages for phase over current and three stages for ground over current) for various power system applications and wide range of protection equipped with settings. The digital filter function 1 Iref Directional / Non Directional over protection b I Power swing unstable is algorithms, providing the rejection of higher harmonics Curve Type Description a b C1 Standard Inverse_1 0.14 0.02 C2 Standard Inverse_2 0.06 0.02 C3 Very Inverse 13.5 1 C4 Extremely inverse 80 2 C5 Long Time Inverse 120 1 C6 Define Time - - & DC offset. Selectable IEC/IEEE inverse ADR239B relay enable to provide users to time curves with directional/non directional set IEEE / ANSI. over current protection will be providing Directional element of relay will be deciding greater selectivity, flexibility and sensitivity faults to users for better relay co-ordinations. voltage & current flows on over head ADR239B relay provides inverse time over transmission current characteristic for phase and ground during faults. RCA/MTA setting range of over current elements. Each stages of relay will provide flexibility to users to set phase and ground over current elements directional angles based on power system are independently settable with inverse parameters. Operating time of directional time or definite time characteristic. The element shall be settable instantaneous or in forward/reverse line / direction underground by cable with definite & inverse time delay. Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 5 of 16 ADR239B head transmission line, underground cable, and feeder. The ground current (3I0>) calculated from three line currents. Directional discrimination for phase to phase fault Derived Zero sequence over current from three phases Sequence over current Protection (50P/46): ADR239B provides sequence over current protection against unbalance faults/condition or high impedance faults over transmission line/under ground cable or over load condition. Sequence over Directional determination for Ground faults current function provided in two modes; Positive sequence and Negative sequence over current function. User can select the mode based on their application and requirement. Directional discrimination for phase to ground fault ADR239B relay provides three stages of definite time/inverse time internally derived zero sequence over current (3I0>) Two independent negative phase sequence protection to detects asymmetrical faults in over current elements can be programmed electrical network. It can apply to over as IDMT or definite time characteristic. Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 6 of 16 ADR239B ADR239B relay provides selectable IEC/IEEE inverse curves for each stage. Over & Under voltage Protections (59/27): ADR239B relay provides independent phase over and under voltage protections with definite time delay range. Relay also provides the positive sequence over voltage protection with definite time characteristic option. Protection functions can be programmed for alarm signal or trip signal through programmable logic. Broken conductor Protection (46BC): ADR239B equipped with broken conductor detection protection. Broken conductor condition can be detected by ratio of Negative sequence sequence current current (I2/I1). to Positive Protection provides higher sensitivity on High resistive fault. Under & Over voltage detection through 3phase VT connection Residual over voltage Protection (59N): ADR239B relay provides zero sequence / residual over and voltage protection with definite time delay range. Protection can be achieved by zero sequence voltage internally calculated from three phases. I0/I1 detection (50BC): ADR239B function provide for independent sensitive ground I0/I1 fault detection. Relay measure the ratio of zero to positive sequence current precisely. Zero sequence over voltage detection through 3-phase VT Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 7 of 16 ADR239B Negative phase sequence over Trip circuit supervision (74T): voltage Protections (47): Any two binary inputs for circuit breaker ADR239B relay provides negative sequence poles can be used for monitoring the circuit over voltage protections with definite time breaker delay range. It provides protection against cables. Relay initiate alarm whenever the high resistive faults and unbalance loading circuit breaker control/DC circuitry gets condition. interrupted. trip coils including connecting Relay monitor Trip coil healthiness through CB NO during close condition and through CB NC during Trip condition. If any discontinuity observed it generate Alarm signal. B+ TCCOM 1 6 2 Negative Phase Sequence Over voltage detection through 3-phase VT connection locator feature, T1 B1 T2 TC Fault Locator (FLC): Fault CB NO To Relay CPU To Relay CPU 6 2 CB NC calculates fault Trip Circuit Logic impedance and distance to fault based on positive sequence reactance parameter of Reclosing / Auto reclosing (79): protected line. The ADR239B is provides 3-pole/1-pole multi shots (4 shots) Auto reclose function. Breaker failure detection (50BF): Numbers of shots are selectable. There are If the fault current is not interrupted after a 4 timer for auto recloser 1) Dead Time for time delay expired, circuit breaker failures shot 1 (DT1) 2) Dead Time for shot 2 (DT2) detected, and execute trip command to 3) Dead Time for shot 3 (DT3) 4) Dead upstream circuit breaker. ADR239B relay Time for shot 4 (DT4) and 5) Reclaim Time incorporates circuit (RT). protection detect breaker failure After clearing of fault ADR239B tripping trigger dead Time 1 i.e. DT1. After the time command execution due to mechanical or delay, relay provides reclose command and electrical problems in circuit breaker. start reclaim timer RT. If second fault occur to failure of during RT relay trigger Dead Time 2 i.e. DT2. If third fault occur during RT relay trigger Dead Time 3 i.e. DT3, If Fourth fault occur during RT relay trigger Dead Time 4 Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 8 of 16 ADR239B i.e. DT4 and after time delay it again provide reclose command and retrigger RT. If fifth fault occur during RT Relay generate Lock-Out alarm and block further reclose. The Lock-Out condition can be reset locally as well remotely by SCADA through communication digital status input. VT supervision function: ADR239B relay provides VT supervision function to detecting a loss of phase voltage input such as that caused by failure of fuses (figure) or molded case/miniature circuit breaker (MCB). Relay declares the VT supervision when the below logic shall be stratified. CT supervision function: ADR239B relay provides CT supervision function to detecting a loss of phase current due to the failure of ct secondary wiring. If the power system currents are healthy, negligible negative & zero sequence voltage could be derived. If, however, one or more of the AC current inputs are missing, a negative & zero sequence currents would be derived, even if the actual power system phase currents are healthy. CTS works by using these criteria; that is by detecting a Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 9 of 16 ADR239B ratio of derived negative to positive The ADR239B also provides pushbuttons for the sequence currents & ratio of derived zero programmable circuit sequence to positive sequence currents in breaker close and open from HMI of relay. the absence of a corresponding derived Pushbuttons can be programmed through negative & zero sequence voltage from VT. HMI or through RTV2 software. Event recording: ADR239B relay is providing feature to record and store 512 nos. Of events in nonvolatile memory protection and through control internally functions by and externally by triggering of digital inputs, and can be extracted using communication port or viewed on front of LCD display. The Programmable Inputs, Outputs & Logic: The modular version of ADR239B relay event shall be trigger on time stamp through time synchronization or internal clock setting. provides total 62 nos. of programmable digital outputs and optically isolated digital inputs. Disturbance recording: ADR239B analogue Pushbuttons: The modular version provides 16 nos. The LEDs can be programmed either through or software). through PC software is provides built in disturbance recording facility for recoding of Programmable LEDs and HMI relay (RTV2 and digital channels. Relay records 10 nos. of disturbances (FIFO) and store in to non-volatile memory. Disturbance records can be saved in IEEE COMTRADE format and same can be analyzed (Voltage / Current / RMS values / Symmetrical components / Vectors / Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 10 of 16 ADR239B Spectrum analysis /Digital channels etc.) in Metering: disturbance analysis software (COMTRADE Online metering feature of ADR239B relay VIEWER). is providing metering of parameters (i.e voltage/current magnitude, power, power factor measurement etc.) on HMI display or in RTV2 software. Independent Protection settings groups: ADR239B relay provides four independent settings groups to allow operate relay on different power system operating conditions. IEC 60870-5-103 / IEC61850 Protocol: ADR239B relay provides internationally standardized IEC60870-5-103 protocol for communication Fault recording: ADR239B relay is providing fault record facility. The fault records can be display via RS485 port and IEC61850 protocol via Ethernet port of protection relays. worldwide and These protocols supported by are relay manufacturers. either on HMI display or in RTV2 software. The relay can records 10 nos. of fault records in non-volatile memory. Doc ID: ADR239B/PC/01 Rev No.: 01 Page No.: 11 of 16 ADR239B Doc ID: ADR239/PC/01 Rev No.: 01 Page No.: 12 of 16 ADR239B Doc ID: ADR239/PC/01 Rev No.: 01 Page No.: 13 of 16 ADR239B Doc ID: ADR239/PC/01 Rev No.: 01 Page No.: 14 of 16 ADR239B Doc ID: ADR239/PC/01 Rev No.: 01 Page No.: 15 of 16 ADR239B ASHIDA ELECTRONICS PVT LTD. All rights reserved. All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. No ASHIDA trademarks may be used without written permission. The information in this document is provided for informational use only and is subject to change without legal notice. ASHIDA ELECTRONICS PVT LTD. has approved only the English language document.