INSTALLATION INSTRUCTIONS Emergency Lighting Accessory ELA TSPLP, ELA TSPLP SD, ELA TSPL2 or ELA TSPL2 SD (Patent pending) Test switch pilot light for remote mounting or replacement for PS300, PS600, PSQ500, PS1400 and PSDL3 CAUTION: For safety and proper operation, read and follow instructions carefully before installation. REPLACEMENT 1. Remove existing test switch/pilot light and connect new one. 2. If this is an initial installation, please refer to the TS/PL installation instructions on the next page. 3. If not remoting, dispose of test switchplate. (Refer to Figure 1 on next page.) IMPORTANT SAFEGUARDS 1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS 2. Before wiring to power supply, turn off electricity at fuse or circuit breaker. 3. To reduce the risk of electrical shock, disconnect AC power and unplug Test switch/pilot light connector before servicing. 4. All servicing should be performed by qualified personnel. REMOTE MOUNTING for TS/PL in desired location (not 1. Install switchbox to exceed more than 25 total feet from the fluorescent battery pack). 2. If switchbox distance exceeds length of TS/PL wire (36"), splice the black and white wires from the TS/PL . Using standard wirenuts and clamp connectors, attach minimum of 20-gauge plenum-rated wire in between black and white wires and switchbox. 3. In the lighting fixture, reattach the four-position connector to the black and white wire extension with wirenuts. Plug black connector into mating connector from the battery pack . 4. Fasten test switchplate to switchbox . Note: Connection of the TS/PL leads to the emergency fixture should be made after steps 1 through 4 of the remote test switchplate installation have been completed. CAUTION: Connecting the test switch/pilot light connector also connects the battery to the inverter circuit which can result in high voltage being present between the output leads. 5. Consult your local building code for approved wiring and installation. 6. Do not use standard product outdoors. This product is for use with indoor fixtures sealed or unsealed, except air handling heated outlets or hazardous location applications. Battery packs with DW option are UL listed for installation (0o – 50o C ambient) in: • Dry or damp locations, sealed or unsealed luminaires • Wet locations, only if installed in a sealed and/or gasketed wet location listed luminaire Note: DW option does not make the product suitable for mounting outside the fixture in wet location applications. 7. The emergency ballast must be connected to an unswitched AC power source (120 or 277). 8. Do not mount near gas or electric heater. 9. Do not attempt to service the battery. A sealed nomaintenance battery is used that is not field replaceable. Contact manufacturer for service information. 10. Equipment should be mounted in location and at heights where it will not readily be subjected to tampering by unauthorized personnel. 11. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 12. Do not use this equipment for other than intended use. SAVE THESE INSTRUCTIONS CAUTION: Damage to battery will occur if test switch/pilot light connection is made for a prolonged period of time without AC power provided. CAUTION: A potential electrical shock hazard exists even when AC power supply has been turned off. Disconnect polarized test switch/pilot light connector before servicing fixture. Part no. EMCSA00697 Rev B WIRING DIAGRAM Figure 1 Clamp Connectors Switchbox PARTS DESCRIPTION TS/PL leads Switchbox (not provided) Remote test switchplate TS/PL connector Battery pack connector (Not included) Lighting Fixture TS/PL Battery Pack Plenum Cable or Flex Cable 25' Maximum ELA TSPLP OR ELA TSPLP SD INSTALLATION CAUTION: Do not locate test switch pilot light or route cable within 1" of fixture lamps. Note: If pilot light is not visible through fixture lens both when energized and de-energized, the sticker located in the prepack should be placed on the back side of the lens directly below the TS/PL to identify it as an emergency fixture. 1. Drill or punch a 1/2" diameter hole in fixture wall or wireway cover. 2. Feed test switch pilot light connector insulation. and cable through hole, taking care that the hole edges do not damage the 3. Insert one side of TS/PL into 1/2" hole and then snap other side into place. Slide mounting clip firmly onto TS/PL mounting post. ELA TSPL2 OR ELA TSPL2 SD INSTALLATION CAUTION: Do not locate test switch pilot light or route cable within 1" of fixture lamps. Note: If pilot light is not visible through fixture lens both when energized and de-energized, the sticker located in the prepack should be placed on the back side of the lens directly below the TS/PL to identify it as an emergency fixture. 1. Drill or punch two 1/2" diameter holes in fixture wall or wireway cover. 2. Attach and secure test switch with mounting nut provided in one of the 1/2" mounting holes. 3. Snap pilot light bushing and pilot light in the other 1/2" mounting hole. www.powersentrysafety.com 1-888-300-7017 Page 2 Part no. EMCSA00697 Rev B