TIME ec
Air handling units
2 |
TIME ec air handling units
TIME ec
AHU No 07.02.339
DANVENT DV 10-240, TIME 10-40
Confirmed with requirements
TIME ec is a standard air handling
unit with EC-motors and integrated
control system. TIME ec is available in
6 sizes with airflows from
750-11.400 m3/h.
TIME ec is based on Systemair’s wellknown technology in production of
air handling units with more than 40
years of experience. TIME ec is sim­
ple to dimension and easy to order.
TIME ec is delivered in 2 versions
with rotary heat exchanger and 2
versions with counter flow heat
exchanger. It is possible to order a
VDI 6022 approved TIME ec.
TIME ec with rotary heat exchanger, airflows 750-11.400 m3/h in 6 sizes
500
700
1000
1500
2000
3000
5000
10000
15000 m3/h
TIME ec 40
TIME ec 30
TIME ec 25
TIME ec 20
TIME ec 15
TIME ec 10
0,15
0,2
0,3
0,4
0,7
1
2
3
4 m3/s
Airflow for TIME ec with external pressure of 250 Pa and max SFP 2.1 kW/(m3/s) in combination with rotary heat exchanger and hot water coil plus cooler. Other
combinations and exact values must be calculated in the SystemairCAD. Note supply and extract dampers, hot water coils and cooler are additional options.
TIME ec with counter flow heat exchanger, airflows 750-9.600 m3/h in 6 sizes
500
700
1000
1500
2000
3000
5000
10000
15000 m3/h
TIME ec 40
TIME ec 30
TIME ec 25
TIME ec 20
TIME ec 15
TIME ec 10
0,15
0,2
0,3
0,4
0,7
1
2
3
4 m3/s
Airflow for TIME ec with external pressure of 250 Pa and max SFP 2.1 kW/(m3/s) in combination with counter flow heat exchanger and hot water coil plus cooler.
Other combinations and exact values must be calculated in the SystemairCAD. Note supply and extract filter, hot water coils and cooler are additional options.
| 3
TIME ec air handling units
Components
1 Rotary heat exchanger is used when the
need for heat recovery is considerable. At the
same time it can recover humidity from the hot
extract air. It is very energy efficient and
requires limited space due to the short length.
Efficiency up to 85%, variable rotation speed
for adjusted efficiency, purging sector, plus
alarm if unintentional stop.
2 Counter flow heat exchanger is used where
there are special requirements of separation of
the airflows, example to avoid the transfer of
odours to the supply air. As humidity cannot be
transferred between the airflows it can be
used for dehumidification. Efficiency up to
90%, temperature sensor and modulating bypass damper ensures against ice building.
3 EC-motors, low energy consumption, good
control properties, high efficiency maintained
at small loads, low noise level and short length.
4 Supply and extract damper, air tightness
class 3 (EN 1751), aerodynamically damper
blades in extruded aluminum with rubber sealing, steel rods and brass bearings, actuators;
on/off or spring-return (additional option).
5 Supply and extract filters, bag filters in filter
quality F7/F5 (EN 779), fixed with filter rails
1
5
that ensures the tightness requirements (EN
1886), handle for easy replacement, alarm
when the filters need to be replaced.
6 Hot water coil, designed for temperature up
to 100 °C and pressure up to 10 Bar. The coil is
secured against frost (additional option).
7 Integrated control system, installed from
factory. See page 5.
8 Casing complies with air tightness class L3,
has closed frame profile of steel and aluzinc
185 protected panels with 50 mm isolation.
9 Supporting legs, made from strong galvanized steel and equipped with adjustable feet.
4
8
3
7
6
4
3
5
7
9
2
5
4
8
5
4
6
3
3
7
7
9
4 |
TIME ec air handling units
Additional options
Future construction calls for air handling units with great flexibility. This is met by the ability to change a variety of combinations. Below is an overview of standards and the most common additional options.
Standard
• Rotary or counter flow heat
exchanger
• Plug fans with EC-motor
(available in two sizes in each unit
size for optimal operation economy)
• Integrated control systems
(see page 5)
• Supply and extract filters;
filter quality F7/F5
• Supporting legs with adjustable
feet, indoor air handling unit.
Additional options
• Supply and extract damper with
actuators; on/off or spring-return
• Cooler fully mounted,
stepless controllable
• Hot water coil
• Electrical heater
• Cooling coil; cold water or DX
• Change-over coil
• Sound attenuator section with
baffles standard and baffles for
dry or wet cleaning
• Valves with actuator
• Roof, trapezoidal roof plates steel
• Roof, bitumen membrane
• Base frame in galvanized
steel profiles
• Outdoor air section for roof units.
TIME ec air handling units
| 5
Control system
TIME ec air handling units come with fully fitted and fully tested control systems from the factory. It is a user-friendly
system where functions and parameters are selected from the external control panel. The control panel can be placed
freely and be used as a remote control (max 10 m from AHU). The main operational data are displayed continuously on
the control panel display, including alarms, operating values, operating status and time settings. The startup is simplified
because the control system is pre-installed with default temperatures, time settings and regulatory sequences. The default
settings can easily be changed to the desired operational values.
Standard
• Control Panel (max 10 m from AHU)
• Week Schedule
• Choose between:
• Temperature control: Cascaded
room temperature, supply air temperature, outdoor temperature
compensated supply air temperature, outdoor temperature dependent switching between room control and supply air control.
• Air control: 2 fixed air flows, constant ducts pressure (VAV), constant ducts pressure with extract
fan as slave.
•
•
•
•
Extended running
Night cooling
Cooling recovery
Filter guard on supply and extract
filter
• Alarm and safety functions
• Modbus.
Additional options
• Repeater (control panel max
1200 m from AHU)
• External fire signal, flow guard on
the extract fan or 2 pcs fire thermostats
• Heating coil, control plus frost
protection
•E
lectrical heater, modulating with
overheating fuse and control
• Control for cooling coil
• Control for change-over coil
• Control for DV cooler
• Heating- and cooling valves incl.
actuator
• LON or TCP/IP
• TCP/IP web interface and the option
of access via android application.
6 |
TIME ec air handling units
Dimensions
+
B
C
A
A
TIME ec with rotary heat exchanger
TIME ec with counter flow heat exchanger
TIME ec with rotary heat exchanger
TIME ec
TIME ec with counter flow heat exchanger
10
15
20
25
30
40
10
15
20
25
30
40
A: Length
2090
2090
2090
2090
2090
2090
A: Length
3210
3360
3510
3510
3810
3810
B: Height
970
1120
1270
1420
1570
1720
B: Height
970
1120
1270
1420
1570
1720
C: Height of feet
100
100
100
100
100
100
C: Height of feet
100
100
100
100
100
100
Width
970
1120
1270
1420
1570
1720
Width
970
1120
1270
1420
1570
1720
Weight
440
460
590
665
730
970
Weight
542
634
782
864
1131
1248
The above-mentioned weights and dimensions are a combination
of rotary heat exchanger and water coil. Weights and dimensions of
other combinations must be calculated in SystemairCAD. Supplied in
2 sections. Note supply and extract dampers and hot water coils
are additional options.
TIME ec
The above-mentioned weights and dimensions are a combination
of counter flow heat exchanger and water coil. Weights and dimensions of other combinations must be calculated in SystemairCAD.
Supplied in 3 sections. Note supply and extract dampers and hot
water coils are additional options.
TIME ec air handling units
Documentation
Complete order-specific technical documentation produced by SystemairCAD.
Systemair A/S - AirSystemair
handling unit
01-03-2013
01-03-2013
Systemair
A/S design
- Air
handling unit design
A/S design
- Air
handling unit
01-03-2013
Systemair
handling unit
Systemair
A/S design
- AirSystemair
handling unit
01-03-2013
A/S design
- Air
handlingA/S
unit- Air
design
01-03-2013
01-03-2013
SystemairCAD - Version
C2013-01.04.C3
Page
SystemairCAD
- Version
C2012-08.00.00
rc3 6
SystemairCAD
C2012-08.00.00
rc3
Page
- Version
C2012-08.00.00
rc3
Page
4
SystemairCAD
C2012-08.00.00
rc3
Page
5
SystemairCAD
- SystemairCAD
Version C2012-08.00.00
rc3 1 - Version
Page
2 - Version
Page 7
DV TIMEUnit:
25 Danvent Project:
Project:
25 Danvent DV TIME 25
Project: Unit: Danvent Project:
Unit:
TIMEUnit:
25 Danvent DV TIMEUnit:
25 Danvent DV TIMEUnit:
DV TIME
25Danvent DV
4500 m3/h
250 Pa
Dimensions
Fully integrated control
SFP, clean filters incl.
speed control 1.90 kWI(m3/s)
Heat recovery 90.6%
Systemair A/S
: A/S
+45 8738
7500
Systemair
A/S 8738
Telephone
+45 8738 7500
Systemair
A/S 8738
Telephone
+45 8738
7500 :
Systemair
Telephone
:
+45
7500
Systemair
Telephone
:
+45
7500 :
Systemair A/S Telephone
Telephone
: A/S
+45 8738
7500
Ved Milepælen 7
'Ved
Telefax :
'Ved
'Ved: Milepælen 7 Telefax
: Milepælen 7Telefax
'Ved: Milepælen 7Telefax
: Milepælen 7Telefax :
'Ved Milepælen 7Telefax
DK-8361 Hasselager DK-8361 Hasselager
www.systemair.dk
DK-8361 Hasselager
www.systemair.se
DK-8361 Hasselager
www.systemair.se
DK-8361 Hasselager
www.systemair.se
DK-8361 Hasselager
www.systemair.se
www.systemair.se
mailbox@systemair.dk mailbox@systemair.dk
mailbox@systemair.dk mailbox@systemair.dk mailbox@systemair.dk mailbox@systemair.dk
Weight
254 kg
267 kg
276 kg
Pa
mm
Pa
Pa
Pa
m/s
m/s
mm
m3/h
Pa
Pa
Pa
Pa
kW
RPM
RPM
%
%
Weight
2 kg
11 kg
2 kg
01-03-2013
SystemairCAD
- Versionrc3
C2012-08.00.00
rc3 9
- Version
C2012-08.00.00
Page
SystemairCAD -SystemairCAD
Version C2013-01.04.C3
Page
8
Page 12
Order-specific set-up
M8 M
Exhaust
The outdoor
temperature is measured by a sensor inside the unit in the outdoor air entrance. If the
- electrical heating
coil
outdoor
after midnight is below the room temperature set point and the actual extract
- valve for cooling
withtemperature
chilled water.
temperature is above the set point temperature, the fans start during the summer to cool down the
- other sensors
building
during night.
The
components
are not provided
with cable and the above-mentioned components
T102 above-mentioned
T101
are delivered uninstalled.
Control panel with 10 m cable is not connected to controller.DVH
Supply
EF
SF
Controller and control panel
The control panel must be connected by cable (10 m) to the controller in the cabinet placed in supply fan
P
T T
P
T
T
section, and the programming and normal handling is carried out from the control panel with display and
buttons - the Systemair Control Panel - the SCP. The protection class of the control panel is IP 41. It is
P2
R2 R6
P1
R5
R4
possible to control the unit with the control panel up to 1200 metres away from the unit with the
of a repeater (optional). The distance between repeater and control panel is restricted to the
Detailed technicalassistance
specification
Cable of cable
Component
Page/
Analog
Analog
Digital is IP20.
Digital
10 metres
in the control
panel. Protection
class
for the repeater
The cable between the
number
number
index
Output
Input
Inputmust be connected to
controller
in the unit
and the repeater
is not
delivered by
Systemair.Output
The repeater
Basic components
W312
R1
3
cabinet
in supply fan
W313
R2section.
W310
R3
W323
M8
Schedules
W315
R6
The regulator
has individual
schedules for start, stop and high/low air flow rate for each week-day as well
as schedules
for holidays.
W350
P1
2
The regulator
has automatic
summer-winter-time change over.
W351
P2
Filter guard supply airOutside
Internalnormal
wires operating
B1
hours, free cooling is available according to settings. 1
Air volume control
2 fixed Air flows
Filter guard extract air Internal wires
EC motor
CoolingW101.1
recovery
Extract air fan
If the W101.2
extract air
Supply air fan
kW
RPM
A
%
V
kW
01-03-2013
A/Sunit
- Air
handling unit
Systemair
A/S -design
Air handling
unit design
Systemair A/S -Systemair
Air handling
design
01-03-2013
Unit: 25
Danvent DV TIMEUnit:
25 Danvent DV TIME 25
Unit: Danvent DV TIME
Description of functions
CST-25-R-12-1720-Std-2
Temperature control
Cascaded extract
air temperature control 1420 x 1420 x 1720 mm
Drip tray
Standard
CST-25-R-3-970-Std-2
x 970 mm
Fan control
Air flows control m3/h 1420 x 1420
Empty section
2
pcs
Sensors delivered Water trap
No
Pressure drop
1
Feet
Damper motor supply air
Motor ON/OFF
Length
150
Condensate
and frost!
This operationProduct
mode can´t be
usedON/OFF
continuously
without (width
defrosting.
Dimensions
x height x length)
Damper motor extract
air
Motor
limit not considered in the
result ofrunning
the calculation.
External control viaFreezing
digital input
Extended
- normal speed
DVZ-25-1
1420 x 100 x 820 mm
Free cooling
Free cooling without external sensors
DVZ-25-2
1420 x 100 x 1720 mm
Damper
Coil configuration
Heating
DVZ-25-1
1420 x 100 x 970 mm
Pressure drop
2
Fan , Plugheating
Frost protection
Standard frost protection
Damper blades Feets are supplied mounted on the unit casing.
Standard
4500
m3/h
Valve for heating Air flow
2-Way valve, Kvs 1.00, DN15 Inside
External pressure
250
Pa
thread
Duct connections
22
Pa
Pressure drop Pressure drop
15
kPa
Product
Dimensions (width
x height)
Filter
Fan
static
pressure
606
Pa
Fire guards
Fireguard
Dimensioning pressure drop
120
Total pressure
Pa
Outdoor
Motor size
2 x 2.73 1350x600
kW mm629
pressure drop
Absorbed power Initial pressure drop/Final
kW 61/179
Supply
1350x600 mm1.12
Velocity, face area
Fan
1581
RPM 1.78
Extract
1350x600 mm
Mains power supply
forspeed
control system
Velocity, filter area
2040
RPM 0.10
Switch board data Maximum fan speed
VoltageExhaust 3x400V + N + PE 50 1350x600
Hz mm
Filter pressure
class
F7
Fan efficiency by static
67.5
%
Max lk
16
kA
Filterpressure
size
2x[592x592]
Fancontrol
efficiency
by total
70.0
%
TIME air handling units are built with a complete and fully integrated
system
- based
on the
Min lk
650
A
Filter length
535
K-factor (p=1,2 kg/m3)
240
Systemair E28 controller.
Max fuse
25
A
Fan type
L-R3G450-AQ24-01
Min fuse
13
A
Supply
ExtractDirect drive
Extract air fan
16
A
Counter flow heat exchanger
Supply air fan
16
A
Airflow (1,205 kg/m³)
4500.00 m3/h
4500.00 m3/h
Data are stated on supply.
Face velocity (unit)
1.49 m/s
1.49 m/s
Motor
The installer on site
must ensure that additional protection of the mains power supply relating to
External pressure
250 Pa
250Motor
Patype
EC motor
frequency converters is all carried
out according to local statutory requirements.
Filter
F7
F7Motor Fan
size , Plug
M3G 150-FF
Fan speed
1581 RPM
1552Motor
RPM
4500
protection Air flow
Built-in
Motor
2.73The
kWsupply unit consist
2.73Rated
kWof
External pressure
250
power
2.73
kW
Voltage
380 - 480 V
380 - 480Speed
V (nominal) Pressure drop
22
2040
RPM
Rated current
4.20 A
4.20Current,
A
Fan static pressure
579
Amp.
4.20
A
Damper
Total
pressure
602
Efficiency of motor incl. speed control
83.3
%
Pressure drop
2
Pa
Heat recovery
90.6 %
Absorbed
power
1.07
Voltage
380
480
V
Damper blades
Standard
SFP, clean filters including speed control
1.90 kW/(m³/s)
1552
Consumed power Fan
fromspeed
mains power supply, including speed control
1.35
kW
Maximum fan speed
2040
Heating
9.04 kW - Air 16.0/22.0°C - Water 70/50°C - 0.6 kPa - 0.11 l/s
Fan efficiency by static pressure
67.9
Heating coil, Fluid
Pipe connections
1 1/4"Filter
/ 1 1/4"
Fan efficiency by total pressure
Air flow
4500
m3/h 70.5
Dimensioning pressure
drop
120
Pa
K-factor (p=1,2 kg/m3)
240
Pressure
drop drop
19
Pa
Initial pressure drop/Final
pressure
61/179
Pa
Fan
type
L-R3G450-AQ24-01
°C
Velocity, face areaAir temperature before/after
1.78
m/s16.0/22.0
drive
Sound power level
63 125 250 500
1k
2kCapacity
4k
8k HzDirect
Total
8.98
kW
Velocity, filter area
0.10
m/s
1.80
m/s
class79
F7
Supply air
73
72
77Filter75
75Face72velocity
66 dB
82 dB(A)
type 29 dB
Water
size 58
2x[592x592]
Outdoor air
68
68
73Filter64
57Fluid47
67 dB(A)
Motor
temperature
°C
length
535
mm70.0/50.0
Exhaust air
73
72
77Filter76
81
77Fluid74
70 dBinlet/outlet
84 dB(A)
Motor type
flow rate
0.11
l/s EC motor
Extract air
67
67
72
64
58
56Fluid46
29 dB
67 dB(A)
Motor size
M3G
pressure
0.6
kPa 150-FF
Sound break out
66
65
58
48
45
46Fluid38
23 drop
dB
55 dB(A)
Motor protection
0.17
m/s Built-in
Counter flow heat exchangerFluid velocity
Rated power
2.73
Coil
volume
6.1
l
With face and by-pass damper
2040
Connection side Speed (nominal) Supply
Service side
Extract
Current, Amp.
4.20
Connection size inlet/outlet
1 1/4" / 1 1/4"
Air flow
4500
m3/h
Efficiency of motor4500
incl. speed control
83.0
Tube material
Cu
Pressure drop
193
183
Pa
Voltage
380 - 480
Fin material
Al
WINTER Air temperature in Fin
winter
before/afterConsumed power
-20.0/18.0
22.0/-5.5
from mains power supply,
including °C
speed control
1.28
spacing
2.1
mm
Project:
Description of functions
Plan view
25
1420 mm
948 kg
Project:
Damper
- extract or exhaust air, on-off motor
Cabinets and mains
supply
The
damper
is opened
and
closed
an on/off
motor
- torqueare
20 mounted
Nm - running time 150
The 2 cabinets
with
terminal
blocks,
relays,
fuses,
24 by
V AC
powerdamper
supply and
controller
Integrated Systemair
control
system
seconds.
according to the supplied
wiring diagram. The controllers are configured according to the customer’s
The air handling unit is built with a complete and fully integrated control system - based on 2 controllers order and confirmed in the order confirmation. Specification is also delivered with the unit. On the site
the Systemair E28-2 port controller and a Systemair E15 expansion
Filtermust
guard
bag filter
in supply
air
mains power supply
beover
connected
directly
to the cabinet
placed in the supply fan section. The
that are mounted in 2 cabinets. One cabinet is placed in the supply fan section and one cabinet in the
guard over bag
filter in supply
installed and connected
to theadditional
controller for display of alarm when
installer on site hasFilter
full responsibility
to ensure
that anyairunit/installation
which requires
exhaust fan section. The air handling unit can either run stand alone or cabled against a building
the mechanically
limit istoexceeded.
protection of the mains
power supplyset
relating
frequency converters or any other such device is all
management system
carried out according to local statutory requirements.
Before shipment the unit has been assembled and has passed a final functional test and inspection.
Filter guard
over for
bag
filter
air But supply disconnecting device is available
The supply disconnecting
device
the
unitin
is extract
not included.
Order-specific set-up and parameters are stored in the controllers during this process. The test report is
Filter guard-over
bagorder
filter in
extract air installed and connected to the controller for display of alarm
without cable and uninstalled
see the
confirmation.
delivered along with the air handling unit.
when the mechanically set limit is exceeded.
External electrical components
Flow
Communication
systems
with MODBUS
Temperature sensor
for
supplychart
airtoisBMS
provided
with cable
and connected to the cabinet placed in the
supply fan section.The controller has been prepared for communication via RS485 communication port to a MODBUS
R1
R3
B1
B3
BMS choice
systemthere
(Building
Management
Depending on the based
customer’s
are terminals
in theSystem).
board cabinet for;
The controller
canfor
work
as a stand-alone
- pressure
transmitters
in ducts
pressure
controlT system without any support from other controllers.
T
P
P
- valve for heating and circulation pump for heating coil
Outdoor
Extract
Free
cooling
- temperature
sensor
for frost protection of the hot water heating coil
Other components
Unit size
Unit width
Weight
2
90/5
40/97
%
Coil code
DVH-25-W-Z-2-9-600-1160-2.1-CU-Al-H-1
1/4
Condensate
0.4
l/min
Access side
Sections
Capacity
57.72
kW
Product
Dimensions (width x height
Temperature
90.6
% x length)
Language in controller
menu efficiency
English
Dry
efficiency
according
to
EN
308
at
4500
m3/h
80.1
%
of Modbus integrated 1420 x 1420 x 820 mm
CST-25-R-4-820-Std-2
External communication The extract unit consist
Extract unit – components specification
rowsbefore/after
Summary for unit no. 1 Technical specificationAir relative humidityNo.in ofwinter
Other
parts
Project:
Supply unit – components specification
Project:
Technical specifications - control system
Project:
B3
T101
1
1
1
temperature
is lower than the outdoor air temperature, and there is a cooling demand in
T101
the rooms, the cooling recovery will be activated. The heat exchanger signal is reversed to give
W102.1cooling T102
1
1
increasing
recovery on increasing demand.
W102.2
T102
Access rights - passwords
External sensors delivered to be installed on site
There W311
are 3 differentR4log-on levels
Basic components
1
- Operator level or basic level - (no password) - access to read values and to change user relevant
Coil configuration
settings
Heating coil frost protection - water
sensorconcerning schedules, temperature, air flow and to cancel alarm and even to restart the
W314
R5
1 that triggered the alarm.
1
system
after having
removed the reason
Systemair Control panel
W90
- Service
level C1
(password) - access to change fundamental values, access to store new settings,
access to restart the system according to user’s own former settings or original factory settings.
Recovery with counter-flow
heat
exchanger
- System
level
which has the highest authority level (special password) with full read/write access to
The performance of the
counter-flow
heat
exchanger
is
stepless
via
the
control
by
the
modulating
all settings and parameters (also access to the configuration of the
whole system)
actuator that regulates the 2 dampers - one damper in the bypass duct for supply air and one damper in
front of the supply air part of the exchanger for the distribution of air between the counter-flow heat
Systemair A/S Telephone :
Telephone
+45 8738 7500
Systemair A/S
+45 8738
7500 :
Systemair A/S
Telephone :
+45 8738 7500
'Ved Milepælen 7Telefax :
Telefax :
'Ved Milepælen 7
Ved Milepælen 7
Telefax :
www.systemair.se
DK-8361 Hasselager DK-8361 Hasselager
www.systemair.se
DK-8361 Hasselager
www.systemair.dk
mailbox@systemair.dkmailbox@systemair.dk
mailbox@systemair.dk
SystemairCAD
To ensure optimal dimensioning of the functions of the air
handling unit, an advanced design programme,
SystemairCAD has been developed. The programme is
very user-friendly and facilitates a simple and quick way
to combine functions. The software will make a technical
calculation and automatically, a complete technical documentation will be produced. The programme is also able
to generate a specification text for the tender and this text
can be transferred to any word processing system via the
rtf-files. The documentation is presented as a pdf-report
specifically regarding the air handling unit that has been
chosen. Furthermore drawings on the specific combination
will be included in the report. The drawings can be transferred to a CAD system through DXF files, in 2D or 3D.
| 7
Avedøreholmen 50
DK-2650 Hvidovre
Tel. +45 87 38 75 00
mail@systemair.dk
www.systemair.dk
TIME_EC_brochure.uk.09.2013-V5
Systemair A/S
Ved Milepælen 7
DK-8361 Hasselager