Selecting the right fan... Is by far the most important aspect of designing a tunnel-ventilated house because a house’s fans determines: A grower’s ability to keep their birds cool during hot weather As well as year round electricity bills 1) 2) Tunnel Fan Selection Michael Czarick The University of Georgia Six factors to consider when selecting a tunnel fan 1) Air moving capacity You can’t tell by simply looking at a fan how much air it will move… Air moving capacity Air moving capacity of a tunnel fan varies from 15,000 to over 50,000 cfm How much air a fan will move is determined by a variety of factors… Such as: Fan diameter Lower rpm = deeper pitch Fan speed More blades = lower rpm Blade pitch Larger = more air Number of blades Higher speed = fewer blades, shallow pitch Orifice design deeper orifice/smaller tip clearance = better performance 1 Couple of the most significant factors that affect fan capacity are shutter design and discharge cones Three basic fan configurations: Fans with exterior shutters Fans with exterior shutters Fans with interior shutters Fans with discharge cones Fans with exterior shutters An exterior shutter adversely affects the air moving capacity of the fan for a couple of reasons: Air exiting a fan rotates Generally the shutter is about the same size as the fan Exterior shutters interferes with the air flow pattern exiting a fan Rotating fan blades cause exiting air to rotate… 2 Exterior shutters disturbs the air flow pattern of the air exiting a fan The spinning pattern can be seen in fans with dual panel shutters Some exterior shutters are less restrictive to air flow than traditional exterior shutters Butterfly shutters offer little restriction to the flow of air out of a fan For example butterfly shutters Split butterfly shutters are even less restrictive Butterfly shutters Dust collection is much less of a problem because the additional weight doesn’t cause the shutters to close 3 Butterfly shutters tend to increase overall fan performance but… Can have closing issues at time Butterfly shutters tend to increase overall fan performance but… Can occasionally scare birds when they close With an interior fan shutter condensation only forms on shutter Cold Butterfly shutters tend to increase overall fan performance but… Allow more light into the house Butterfly shutters tend to increase overall fan performance but… Are prone to condensation problems Butterfly shutter fan condensation will tend to form on all fan surfaces Warm and moist 4 Most do not have slant wall housing so moisture collects in the bottom of the fan So condensation runs down interior walls Moisture collecting on fan surfaces can also end up damaging the fan Another type of exterior shutter is the “Blow away” shutter Ammonia + Water Typically a retrofit shutter for fan with exterior shutter Fans with interior shutters Better than a traditional exterior shutter Can be affected by the wind Difficult to predict fan performance. Commonly referred to as “slant wall” fans 5 Fans with interior shutters Slant wall housing Interior shutter fans Shutter opening is typically larger than fan diameter (+4” to 6”) Air is pulled though shutter instead of being pushed through the shutter. Fan is tilted slightly Slant wall housing Match open shutter angle Fan is tilted slightly Slant wall housing with interior shutters The combination of the slant, interior shutter, and exterior mounting increases air flow 5 to 10% Protects fan from weather Condensation runs outside Interior shutters Relatively easy to clean Fan can be easily winterized 6 Winterizing fan Without plastic 100.0°F 100 90 80 70 60.0°F With plastic Interior “butterfly” shutters 100.0°F 100 90 80 Fan performance is maximized. Maintenance is minimized Heat loss is minimized Condensation problems are minimized 70 60.0°F Interior “Roll seal” shutters Fans with discharge cones Is to get rid of the shutter entirely: Maximum air flow Dust collection problems virtually eliminated But can have problems if not maintained 7 Discharge cones Fan without discharge cone A discharge cone reduces “exit” pressure on fans Fan with discharge cone Discharge cones Bess Labs all fans tested @0.10” The discharge cone can increase air flow from a fan 5 to 10%. Winterizing butterfly shutter fans 30,000 25,000 CFM 20,000 15,000 no cone cone 10,000 5,000 0 36 48 50 52 Fan Size (inches) 53 8 Though… Slant wall tend to move more air than fans with exterior shutters… Fans with cones tend to move more air than fans without cones There can still be significant difference in the amount of air moved by fans of the same configuration This is why you must specify total cfm…at the expected operating static pressure. Tunnel fan specifications Total cfm at expected maximum pressure: 1) 400 ft/min = 0.09” - 0.11” 500 ft/min = 0.10” - 0.12” 600 ft/min = 0.13” - 0.15” 700 ft/min = 0.16” - 0.18” 800 ft/min = 0.18” - 0.20” If exterior should be “butterfly” type shutter. Interior shutter 2) Discharge cone 3) Six factors to consider Energy efficiency 1) Air moving capacity 2) Energy efficiency energy efficiency ratio Not specifying specific energy efficiency ratings for fans can result in... How much power will a fan use? First, an “Energy Efficient/Saver” label on a motor means very little... excessive energy bills for the producer poor bird management loss of income for the grower/company How much power will a fan use? Motor size is not necessarily a good measure either. For instance, a fan with a 1 h.p motor can actually use more power than a 1.5 h.p. motor It all depends on how the motor is loaded… 9 Two different 48” fans with discharge cones Bess #92093 1.5 h.p motor 24,600 cfm 1,300 watts Bess #98229 1.0 hp motor 21,500 cfm 1,310 watts Two different 48” fans Bess # 96321 918 watts Energy efficiency Two different 48” fans Bess #96132 1,116 watts 18% more power Furthermore, just because a fan uses less power does not necessarily mean it will save you money! Bess # 96321 918 watts 16,800 cfm Bess #96132 1,116 watts 24,000 cfm Yes it uses 18% more power but it moves 30% more air To accurately compare two fans… a fan’s energy efficiency must be expressed in terms of how much air it will move per watt of power used: Energy efficiency ratings Typically range between 15 and 30 cfm/watt Cfm/watt 1 cfm/watt….for every 1 cfm moved…the fan will use 1 watt of power 10 Example…two fans that move 20,000 cfm (power cost $0.12 per kw*hr) Fan A = 17 cfm/watt Fan B = 22 cfm/watt To calculate power usage (watts)… Fan A = 17 cfm/watt Fan B = 22 cfm/watt Watts = 20,000 / 17 = 1,176 Watts = 20,000 / 22 = 909 To calculate power usage (watts)… Fan A = 17 cfm/watt Fan B = 22 cfm/watt Watts = 20,000 / 17 = 1,176 = 1.18 Watts = 20,000 / 22 = 909 = 0.91 To calculate power usage (watts)… Watts Kw Kw cfm / cfm per watt Power usage is typically measured in Kilowatts 1 Kw = 1,000 watts To calculate operating cost… Cost per hour = Power rate X Kw = Where “power rate” is the cost of using 1 kw of power for an hour 11 To calculate operating cost… Fan A = 17 cfm/watt 1.18 Kw X $0.12 14.2 cents per hour Ten fans $ 34.08 per day $ 238.53 per week Fan B = 22 cfm/watt 0.91 Kw X $0.12 11.3 cents per hour Ten fans $26.25 per day $183.75 per week Tunnel fan specifications Total cfm at expected maximum pressure 1) 500 ft/min = 0.10” - 0.12” 600 ft/min= 0.13” - 0.15” 700 ft/min= 0.16” - 0.18” 800 ft/min = 0.18” - 0.20” Interior shutter/Butterfly exterior Discharge cone Minimum Cfm/watt = 19 @0.10” 2) 3) $55.78 difference 4) Good = 20.8 Ideal = 22+ Larger fans are generally a better investment than smaller fans: Lower initial cost Lower operating cost Lower maintenance cost Larger fans also tend to be more energy efficient Initial fan cost 24” fan = $350 (5,800 cfm) $0.06 per cfm 36” fan = $550 (9,900 cfm) $0.055 per cfm 48” fan = $750 (19,700 cfm) $0.038 per cfm Bess Labs all fans tested @0.10” Energy efficiency rating How does fan size affect performance and economics? 22 21 20 19 18 17 16 15 14 13 12 no cone cone 36 48 50 52 Fan size (inches) 53 12 How large is too large? Tunnel-ventilated dairy barn Depends to some extent on house size The larger the house…the larger the fan it can handle… Tunnel-ventilated broiler house 70’ X 900’ Turkey house 70’ X 900’ Turkey house Most 72” fans move around 50,000 cfm 13 They could be installed in a 66’ X 600’ The typical 66’ X 600’ broiler house… would require approximately 360,000 cfm of tunnel fan capacity. 5 – 72” fans = 240,000 cfm Plus 5 – 48” fans = 120,000 cfm Six factors to consider Fan Output vs. Static Pressure 1) Air moving capacity 2) Energy efficiency energy efficiency ratio Cfm 3) Air moving capacity vs. static pressure air flow ratio 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 Every fan reacts differently to increases in static pressure 0 0.05 0.1 0.15 0.2 0.25 0.3 Static Pressure We want a fan that holds up well under pressure… Fan capacity vs. static pressure Cfm (Six 48” fans, between 21,000 and 22,000 cfm @ 0.10”) 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 Most houses will operate at a pressure greater than 0.10” And over time it will increase Dirty shutters Evaporative cooling pads But react differently as pressure increases 0 Fan A 0.05 Fan B 0.1 0.15 0.2 Static Pressure Fan C Fan D Fan E 0.25 0.3 Fan F 14 One way to quantify this is comparing fan air flow ratio’s Tunnel fan specifications: Total cfm at expected maximum pressure: 1) Air Flow Ratio = air flow (0.20”)/air flow (0.05”) Air flow ratio’s typically range between 0.65 and 0.85 The closer to 1.0 the better the fan will hold up to high static pressures 2) 3) 4) 500 ft/min = 0.10” - 0.12” 600 ft/min = 0.13” - 0.15” 700 ft/min = 0.16” - 0.18” 800 ft/min = 0.18” - 0.20” Interior shutter/exterior butterfly Discharge cone Minimum cfm/watt = 19.0 @0.10” 5) Good rating = 20.8 Ideal rating = 22 Minimum air flow ratio = 0.70 Good rating = 0.76 Ideal rating = 0.79+ Fan output vs. Static pressure (Six 48” fans, between 21,000 and 22,000 cfm @ 0.10”) (Four 48” fans, between 21,000 and 22,000 cfm @ 0.10”) 0.3 0.28 0.26 0.24 0.2 0.22 0.18 0.16 0.14 0.1 0.12 0.08 0.04 0 0.02 0.3 Static Pressure 19 14.6 0.3 0.28 0.28 0.26 0.06 18.3 0.26 Good rating = 0.76 Ideal rating = 0.79+ 0.24 Minimum air flow ratio = 0.70 0.22 5) Good rating = 20.8 Ideal rating = 22 0.2 0.18 0.16 4) Interior shutter/exterior butterfly Discharge cone Minimum cfm/watt = 19.0 @0.10” 0.14 3) 0.12 0.76 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 0.1 500 ft/min = 0.10” - 0.12” 600 ft/min = 0.13” - 0.15” 700 ft/min = 0.16” - 0.18” 800 ft/min = 0.18” - 0.20” 0.08 0.86 (Four 48” fans, between 21,000 and 22,000 cfm @ 0.10”) Cfm Static Pressure 0.84 Fan Output vs. Static Pressure Total cfm at expected maximum pressure: 1) 2) 0.84 0.06 Tunnel fan specifications 0.67 0.04 0.76 0 0.74 0.24 0.2 Static Pressure 0.86 0.22 0.18 0.16 0.14 0.1 0.12 0.08 0.06 0.84 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 0.02 0.84 0.04 0 Cfm 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 0.02 Cfm Fan output vs. Static pressure 18.2 15 Fan Output vs. Static Pressure Six factors to consider 1) Air moving capacity 2) Energy efficiency 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 energy efficiency ratio 3) Air moving capacity vs. static pressure air flow ratio 0.3 0.28 0.26 0.24 0.2 Static Pressure 0.22 0.18 0.16 0.14 0.1 0.12 0.08 0.06 0.04 0 4) Drive type 0.02 Cfm (One 48” fan, between 21,000 and 22,000 cfm @ 0.10”) 19 cfm/watt and AFR = 0.84 Direct drive vs. Belt drive Direct drive advantages: No belts to tighten No belts to replace Direct drive disadvantages Tend to move less air Tend to be less energy efficient Motors cost more Tend to be louder Direct drive vs. Belt drive Direct drive vs. Belt drive ACME AGD direct drive with cone 19,700 cfm (19 cfm/watt) ACME BDR 48” slant wall with cone 21,400 cfm (21.4 cfm/watt) 10 10 percent less air percent less energy efficient Next generation of direct drive fans Traditionally they have not been a good choice…But, if they meet the previously listed specs, they can/should be used. 16 Belt driven tunnel fans Belt tensioners: Keep the belt tight which reduces wear… Increases belt life Should be a requirement for new fans Can hide a belt wear problem May require maintenance Fiberglass, “plastic”, stainless steel Are a good option for costal area’s Within 20 miles of salt water Are also a good choice for fans with butterfly shutters Six factors to consider 1) Air moving capacity 2) Energy efficiency energy efficiency ratio 3) Air moving capacity vs. static pressure air flow ratio 4) Drive type 5) Construction material Six factors to consider 1) Air moving capacity 2) Energy efficiency energy efficiency ratio 3) Air moving capacity vs. static pressure air flow ratio 4) Drive type 5) Construction material 6) Price Price Least important factor of all… Lets assume a tunnel fan runs 2,000 hours a year 22,000 cfm 18 cfm/watt $0.12 per kw*rh Where do you find reliable fan performance information? Such as: Air moving capacity at various static pressures Energy efficiency ratings Air flow ratio Yearly operating cost is $293 15 year cost is $4,400 40 fans on a farm…$176,000 A fan that uses 25% less power could end up saving a farm owner $44,000 dollars 17 BESS Labs at The University of Illinois BESS Labs at The University of Illinois Testing fans for over 20 years... www.bess.uiuc.edu BESS Labs at The University of Illinois Fan description: BESS Labs at The University of Illinois Test results are published on the BESS Labs website where you can obtain fan performance information for well over 600 types of tunnel fans! BESS Labs at The University of Illinois Test results: With so many fans to choose from it can be a challenge to find the right fan. To narrow the field down each year we take all the tunnel fans (48” or larger) that have been tested and graph their air flow ratio vs. their energy efficiency rating. 18 Then we selected those that meet the “good” criteria: All fans 48” diameter or larger 1 0.9 0.8 0.7 0.6 Air flow ratio Minimum cfm/watt = 19 @0.10” Minimum air flow ratio = 0.70 0.5 0.4 Good rating = 20.8 Ideal rating = 22+ Good rating = 0.76 Ideal rating = 0.79+ 0.3 0.2 0.1 0 0 5 10 15 Cfm/watt 20 25 30 These are the top performers…any of which would be a good choice All fans 48” diameter or larger 1 0.94 0.9 0.92 0.8 0.9 0.7 0.88 Air flow ratio Air flow ratio 0.6 0.5 0.4 0.3 0.2 0.86 0.84 0.82 0.8 0.78 0.1 0 0 5 10 15 Cfm/watt 20 25 30 0.76 20.8 22.8 24.8 Cfm/watt 26.8 28.8 2012 Top performing tunnel fan list 19 Fan performance laws Fan performance laws Cfm is proportional to fan speed Air flow vs. Pressure Air moving capacity (cfm) For example…ACME DDPS50 Increase fan speed 10%...fan output is increased 10% 29,000 27,000 25,000 23,000 21,000 19,000 17,000 15,000 13,000 11,000 9,000 7,000 5,000 468 rpm 2.5” motor pulley 0 Air moving capacity (cfm) Install a larger motor pulley to speed up the fan blades and fan capacity increases 515 rpm 2.8” 0.25 Increase fan speed 10%...fan output is increased 10% Power usage is exponentially related to fan speed 2.5” 0.2 Cfm is proportional to fan speed 468 rpm 0.1 0.15 Static pressure Fan performance laws 29,000 27,000 25,000 23,000 21,000 19,000 17,000 15,000 13,000 11,000 9,000 7,000 5,000 0.05 Increase fan speed 10%...power usage is increased 30% But, what would happen to power usage? 0 0.05 0.1 0.15 Static pressure 0.2 0.25 20 Air flow vs. Pressure 1,500 1,400 1,300 1,200 1,100 1,000 900 800 700 600 500 400 300 200 100 0 30,000 515 rpm Air moving capacity (cfm) Power (watts) Power usage vs. Fan speed 0 50 100 150 200 250 300 350 400 450 500 RPM Fan performance laws 1,090 watts 15,000 10,000 0.05 0.1 0.15 Static pressure 0.2 0.25 Air flow ratio 30,000 Decrease fan speed 10%...fan output is decrease 10% Power usage is exponentially related to fan speed 1,450 watts 20,000 0 Cfm is proportional to fan speed 468 rpm 5,000 Decrease fan speed 10%...power usage is decreased 30% 515 rpm Air moving capacity (cfm) 25,000 25,000 20,000 468 rpm 1,450 watts 397 rpm 1,090 watts 15,000 700 watts 10,000 5,000 0 Sometimes it is better to install more fans spinning slower than fewer fans spinning faster Fan Cfm @.10” Energy Efficiency (cfm/watt) Number of Fans Air Speed (ft/min) Yearly $ $0.10 kw*hr Standard 23,300 19.4 12 590 $3,600 High flow 26,300 17.1 11 610 $4,650 0.05 0.1 0.15 Static pressure 0.2 0.25 What about other fans… 21 30 cfm/watt Vs 22 cfm/watt 22