EEL303: Power Engineering I - Tutorial 6 1. Figure 1 shows the one-line diagram of a four-bus system. Table 1 gives the line Figure 1: Sample system for 1Q impedances identified by the buses on which these terminate. The shunt admittance at all the buses is assumed to be negligible. Table 1: Line, Bus to bus 1–2 1–3 2–3 2–4 3–4 R (p.u) 0.05 0.10 0.15 0.10 0.05 X (p.u) 0.15 0.30 0.45 0.30 0.15 (a) Find YBus , assuming that the line shown dotted is not connected. (b) What modifications need to be carried out in YBus if the line shown dotted is connected. [Ans: (a) YBus (b) 0 −1 + j3 0 3 − j9 −2 + j6 −1 + j3 0 0 1.666 − j5 −0.666 + j2 −1 + j3 = −1 + j3 −0.666 + j2 3.666 − j11 −2 + j6 0 −1 + j3 −2 + j6 3 − j9 YBus 1 − j3 −2 + j6 3.666 − j11 −0.666 + j2 −1 + j3 = −1 + j3 −0.666 + j2 3.666 − j11 −2 + j6 0 −1 + j3 −2 + j6 3 − j9 ] Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 6 2. The following is the system data for a load flow solution. The line admittances are given in Table 2. The scheduled active and reactive powers are given in Table 3. Determine the voltages Table 2: The line admittances Line 1–2 1–3 2–3 2–4 3–4 Admittance 2-j8.0 1-j4.0 0.666-j2.664 1-j4.0 2-j8.0 Table 3: Scheduled active and reactive powers Bus No. 1 2 3 4 P Q V — — 1.06 0.5 0.2 — 0.4 0.3 — 0.3 0.1 — Remarks Slack PQ PQ PQ at the end of first iteration using Gauss-Seidal method. Take acceleration factor (α) as 1.6. 1 1 1 [Ans: V2,acc = 1.01899-j0.046208; V3,acc = 0.99059-j0.0467968; V4,acc = 0.954565-j0.1034944] 3. If in above problem, bus 2 is taken as a generator bus with |V2 |=1.04 and reactive power constraint is 0.1 ≤ Q2 ≤ 1.0 Determine the voltages starting with a flat voltage profile and assuming acceleration factor as 1.0. Assume that bus 2 has generator connected on it and injects P2 = 0.5 p.u. 1 1 1 [Ans: V2,acc = 1.0395985+j0.02891158; V3,acc = 0.9978866-j0.015607057; V4,acc = 0.998065j0.022336] 4. For the sample system of Figure 2, the generators are connected at all the four buses, while the loads are at buses 2, 3 and 4. The values of real and reactive powers are listed in Table 4. All buses other than slack are of PQ-type. Line data are given in Table 5. Find the voltages and the bus angles at the three buses using the Newton-Raphson method. [Ans: δ2 = -0.09696 rad; δ3 = -0.11217 rad; δ4 = -0.06928 rad; V2 = 0.94496 p.u.; V3 = 0.92451 p.u.; V4 = 0.95715 p.u.] Electrical Engineering Dept - IIT Delhi EEL303: Power Engineering I - Tutorial 6 Figure 2: Sample system Table 4: Bus 1 2 3 4 Pi (p.u.) Qi (p.u.) — — -0.45 -0.15 -0.51 -0.25 -0.60 -0.30 Vi (p.u.) 1.05 ̸ 0 — — — Type of bus Slack PQ PQ PQ Table 5: Line No. 1 2 3 4 Line (i-j) 1–2 1–4 2–3 3–4 Line impedance 0.08+j0.20 0.05+j0.10 0.04+j0.12 0.04+j0.14 5. For the sample system of Figure 2, the generators are connected at all the four buses, while the loads are at buses 2, 3 and 4. The values of real and reactive powers are listed in Table 6 along with the type of buses. Line data are given in Table 5. Find the voltages Table 6: Bus 1 2 3 4 Pi (p.u.) Qi (p.u.) — — -0.45 -0.15 -0.51 -0.25 -0.60 -0.30 Vi (p.u.) 1.05 ̸ 0 1.00 ̸ 0 — — Type of bus Slack PV PQ PQ and the bus angles at the three buses using the Newton-Raphson method. [Ans: δ2 = -0.11664 rad; δ3 = -0.12567 rad; δ4 = -0.07658 rad; V3 = 0.96146 p.u.; V4 = 0.973 p.u.] Electrical Engineering Dept - IIT Delhi