One Lamp, Two Lamp and CFL Ballasts Installation and Userʼs Manual 24VDC ONE LAMP BALLAST MODELS: NB24-T524HO-01D, NB24-T528-01D, NB24-T554-01D, NB24-T832-01D, NB24-BX40-01D 24VDC TWO LAMP BALLAST MODELS: NB24-T528-02D, NB24-T817-02D, NB24-T832-02D 48VDC TWO LAMP BALLAST MODELS: KT2-54-R-S-53, NB5353/2R CFL MODELS: NB24-CF13-01D, NB24-CF18-01D, NB24-CF26-01D, NB24-CF42-01D Rev 031114 Please contact Customer Support at 1-800-24VOLTS for further information. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. One Lamp, Two Lamp and CFL Ballasts Installation and Userʼs Manual TABLE OF CONTENTS ABOUT NEXTEK POWER SYSTEMS 3 INTRODUCTION / OVERVIEW 4 1.0 SAFETY 5 2.0 STANDARDS & REQUIREMENTS 6 3.0 REGULATORY INFORMATION 7 4.0 TRAINING 7 5.0 FEATURES 8 6.0 SPECIFICATIONS 9 7.0 GENERAL REQUIREMENTS 10 8.0 INSTALLATION PROCEDURE 12 8.1 24V ONE-LAMP BALLAST MODELS 12 8.2 24V TWO-LAMP BALLAST MODELS 16 8.3 CFL BALLAST MODELS 20 8.4 48V TWO-LAMP BALLAST MODELS 23 8.5 WIRING A 2-LAMP BALLAST TO AN E-BALLAST FIXTURE 26 9.0 CFL BALLAST INSTALLATION TIP SHEET 10.0 TROUBLESHOOTING 28 11.0 NOTES 29 For more information: 2 27 Nextek Power Systems 461 Burroughs Street Detroit, Michigan 48202 Tel: 313-887-1321 Toll free: 1 (877) 24-VOLTS Fax: 313-887-9433 www.nextekpower.com info@nextekpower.com Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts Installation and Userʼs Manual ABOUT NEXTEK POWER SYSTEMS Nextek Power Systems AC/DC integration technology represents a breakthrough in onsite electrical management, combining the availability of AC power with the quality and efficiency of a DC supply. NEXTEK PRODUCT BENEFITS • Easy conversion of AC lighting fixtures to DC-powered units • Easy conversion of AC grid power into DC power for commercial building applications • Highly efficient management of peak loads • Future-proof lighting and other systems to be developed • Nextek Power Systems Direct Coupling® Technology, directly connects clean power generated at a building to its electronic loads inside cutting down on overall power consumption, boosts electricity generated and stored on-site, and delivers a robust renewable energy ready network. DISCLAIMER Nextek Power Systems has made every reasonable effort to ensure the accuracy of the information in this catalog. Nextek Power Systems does not guarantee that the information is error free, nor do we make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current. Nextek Power Systems, Inc. reserves the right to make any adjustments to the information contained herein at any time without notice. The specifications in this catalog are for reference purposes only and are subject to change without notice. Consult Nextek Power Systems for the latest design specifications. All trademarks are either the exclusive property of Nextek Power Systems, Inc. or other companies. Copyright © 2012-2014 by Nextek Power Systems, Inc. in the United States and other countries throughout the world. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 3 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts Installation and Userʼs Manual INTRODUCTION Nextek Ballasts • Nextekʼs Ballast Installation Kit converts existing luminaires from AC power to safe, lowvoltage Direct Current (DC) power by simply replacing the ballasts. • Convert luminaires without replacing bulbs or system wiring. Nextek ballasts are sized to use pre-existing mounting holes and hardware too. • The simple procedure takes only minutes to complete. Nextek ballasts in a Direct Current power system. 4 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 1.0 Installation and Userʼs Manual SAFETY 1.1 SAVE THESE INSTRUCTIONS– This manual contains important safety and operating instructions for the Nextek Ballast Installation Kit. The following symbols are used throughout this manual to indicate potentially dangerous conditions or mark important safety instructions: DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING: Indicates a potentially dangerous condition. Use extreme caution when performing this task. CAUTION: Indicates a critical procedure for safe and proper operation of the controller. NOTE: Indicates a procedure or function that is important for the safe and proper operation of the controller. 1.2 Before using the Ballast Installation Kit, read all instructions and cautionary markings. 1.3 Electrical hazards are probably the most common hazards throughout the industry. Virtually all workplaces have electrical installations and use electricity. 1.4 It is very important that all industry employees be familiar with electrical hazards and know how to protect themselves when working on, near, or with electricity. In most cases, industry electrical and electronic equipment is designed for both maximum safety and efficiency. However, potentially hazardous conditions such as inadvertent contact with hazardous voltages may exist while performing servicing and maintenance, handling materials, or cleaning. 1.5 The improper use of electrical extension cords and portable electrical equipment can result in hazardous exposure. 1.6 WARNING - RISK OF ELECTRICAL SHOCK 1.6.1 This Ballast Installation Kit requires knowledge of fluorescent lighting luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician. 1.6.2 Install this kit only in luminaires that have similar features and dimensions as the photographs and/or drawings shown here. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 5 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 1.0 Installation and Userʼs Manual SAFETY 1.6.3 The ballast supplied with this kit is not for use with instant-start lampholders. Do not short between the pins in the lampholder. (Not applicable for BIAX lamps.) 1.6.4 To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects. 1.6.5 Only those open holes indicated in the photographs and/or drawings may be made or altered as a result of kit installation. Do not leave any other open holes in an enclosure of wiring or electrical components. 1.6.6 A listed Class 2 24VDC or 48VDC output supply, such as a Nextek PSM, must be used as a power source for the Nextek low voltage ballast. 1.6.7 These Nextek low voltage ballasts are intended for use only with non-IC (Luminaires not intended for Insulation Contact). 1.6.7 Before wiring 24VDC or 48VDC supply to ballasts, remove any old AC wiring, including any ground wires, between the line voltage ballast and the nearest junction box. 1.7 DANGER – TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, CAREFULLY FOLLOW THESE INSTRUCTIONS 1.7.1 Do not disassemble or attempt to repair the ballasts. There are no user serviceable parts inside Nextek ballasts. 1.7.2 Install external fuses/breakers as required. 1.7.3 Disconnect power to the luminaire before installing the ballasts, removing old ballasts or wiring, or otherwise working with the unit. 1.8 INSTALLATION SAFETY PRECAUTIONS 1.8.1 Mount the ballasts indoors only. Prevent exposure to the elements. 1.8.2 Power connections must remain tight to avoid excessive heating from a loose connection. 1.8.3 Use properly sized conductors and circuit interrupters. 1.8.4 The Nextek Ballast Installation Kit is to be connected to DC circuits only. 2.0 STANDARDS AND REQUIREMENTS 2.1 All DC cable types must meet all local and national codes 2.2 Shut off all DC circuit breakers or fuses before installing any unit into the field. 6 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 3.0 Installation and Userʼs Manual REGULATORY INFORMATION 3.1 NOTE: This section contains important information for safety and regulatory requirements. 3.2 The Ballast Installation Kit should be installed by a qualified technician according to the electrical rules of the country in which the product will be installed. 3.3 Nextek ballasts comply with the following EMC standards: 3.3.1 Immunity: EN61000-6-2:1999 3.3.2 Emissions: EN55022:1994 with A1 and A3 Class B1 3.4 A means shall be provided to ensure all the poles are disconnected from the power supply. This disconnection shall be incorporated in the fixed wiring. 3.5 FCC Requirements: This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Changes or modifications not expressly approved by Nextek Power Systems, Inc. for compliance could void the user’s authority to operate the equipment. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communication. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures: 4.0 • Reorient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. • Consult the dealer or an experienced radio/TV technician for help. INSTALLATION QUALIFICATIONS 4.1 Installation work and electrical wiring of permanently-connected power units must be performed only by qualified service personnel in accordance with all applicable codes and standards, including fire-rated construction. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 7 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 5.0 Installation and Userʼs Manual BALLAST FEATURES • Low-voltage, 2 wire (class 2) 0-10Vdc control technology turns lamps off (<1 Volts) at the bottom of the voltage range. Lamps can be switched back on to a previous dimming level instantly. • Programmed rapid start design: Lamps turn on to any dimmed level without flashing to full brightness. • UL 2108 classified. • State-of-the-art Phase Control operation resulting in continuous, flicker-free dimming from 100% to 10%. • Inherent Thermal Protection • Type 1, Class P, Sound rated A • USL 935 Listed. • Input voltage is rated class 2, which does not require grounding. No provision exists for grounding. (Input 24V DC, <4A) MODELS LIST 24VDC ONE LAMP BALLAST MODELS: NB24-T524HO-01D, NB24-T528-01D, NB24-T554-01D, NB24-T832-01D, NB24-BX40-01D 24VDC TWO LAMP BALLAST MODELS: NB24-T528-02D, NB24-T817-02D, NB24-T832-02D 48VDC TWO LAMP BALLAST MODELS: KT2-54-R-S-53, NB5353/2R CFL MODELS: NB24-CF13-01D, NB24-CF18-01D, NB24-CF26-01D, NB24-CF42-01D Kit contents: 1. Ballast 2. Installation and User Manual 3. Installation hardware 8 NOTE: This kit is only for use in a UL 1598 listed fixture Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 6.0 Installation and Userʼs Manual TECHNICAL SPECIFICATIONS T528-1Lamp T528-2Lamp T524HO-1Lamp T528-2Lamp T832-1Lamp T817-2Lamp T832-2Lamp 1.21 Amp @ 24V DC 1.98 Amp @ 24V DC 1.13 Amp @ 24V DC 1.98 Amp @ 24V DC 1.35 Amp @ 24V DC 1.38 Amp @ 24V DC 1.99 Amp @ 24V DC Operating Temperature: 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC Maximum Ballast Factor: 1.0 .075 1.0 .075 1.0 1.0 .075 Peak Efficiency: 95% 95% 95% 95% 94% 94% 94% Crest Factor: <1.55 <1.55 <1.55 <1.55 <1.55 <1.55 <1.55 Operating Voltage: Operating Current: 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% Analog Dimming: 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 V DC - Dimming V DC - Dimming V DC - Dimming V DC - Dimming V DC - Dimming V DC - Dimming V DC - Dimming Dimensions: 1.10"W x 1.10"W x 1.10"W x 1.10"W x 1.10"W x 1.10"W x 1.10"W x 0.96"H x 9.57"L 0.96"H x 9.57"L 0.96"H x 9.57"L 0.96"H x 9.57"L 0.96"H x 9.57"L 0.96"H x 9.57"L 0.96"H x 9.57"L Weight: 16 oz. 16 oz. 16 oz. 16 oz. 16 oz. 16 oz. 16 oz. Construction: Steel Steel Steel Steel Steel Steel Steel F28T5 F28T5 F24T5HO F28T5 Operated With: 40BIAX-1Lamp CFL-13** 1.6 Amp @ 24V DC Operating Temperature: Maximum Ballast Factor: F32T8, FB032, F17T8, F18T8 F32T8, FB032, F32T8ES, FB32* F32T8ES, FB32* *For wattages other than 32, please contact Nextek Power Systems, Inc. at 1-877-24VOLTS CFL-18** CFL-26** CFL-32/42** KT-2-54-RS-53 NB5353/2R 0.65 Amp @ 24V DC 0.84 Amp @ 24V DC 1.10 Amp @ 24V DC 1.54 Amp @ 24V DC 2.2 Amp @ 54V DC 1.0 Amp @ 54V DC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 0ºC-49ºC 1.0 1.0 1.0 1.0 0.9 1.0 0.88 Peak Efficiency: 95% 85% 87% 89% 87%@32W, 93%@42W Crest Factor: <1.55 <1.55 <1.55 <1.55 <1.55 <1.70 meets ANSI n/a n/a Operating Voltage: Operating Current: 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 48 V DC 54 V DC (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% (nominal)±10% Analog Dimming: 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 0 V DC - off, 1-10 V DC - Dimming V DC - Dimming V DC - Dimming V DC - Dimming V DC - Dimming Dimensions: 1.10"W x 1.10"W x 2.96"W x 2.96"W x 2.96"W x 2.25"W x 2"W x 1.125"H 0.96"H x 9.57"L 0.96"H x 9.57"L 1.27"H x 5.03"L 1.27"H x 5.03"L 1.27"H x 5.03"L 1.40"H x 6.25"L x 3.125"L Weight: 16 oz. 16 oz. 16 oz. 16 oz. 16 oz. 8 oz. 10.5 oz. Construction: Steel Steel Steel Steel Steel Steel Steel F40BX, F39BX, FT40 CFQ13, CFT13 CFQ18, CFT18, CFD18 CFT26 CFT32, CFT42 F54T5HO F54T8 Operated With: **For CFL Ballasts, heat and smoke release testing in accordance with UL 2043 was not considered necessary due to the small mass of the exposed polymeric parts. Weight of exposed polymeric parts is less than 5 grams each. CFL Ballasts are Suitable for use in Air Handling Spaces. All specifications are subject to change without notice. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 9 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 7.0 Installation and Userʼs Manual GENERAL REQUIREMENTS 7.1 Every work environment should provide a safe place for every employee, which includes protecting the employee from electrical hazards such as fault currents to ground. 7.2 When an electrical ground fault occurs, the current flows through the path having minimum impedance to ground. It is imperative that an employee does not inadvertently become the conductor of the current. 7.3 Two approved methods of protecting the worker from a ground fault, in addition to other requirements for equipment-grounding conductors, are: 7.3.1 Use of ground fault circuit interrupters (GFCI) 7.3.2 An assured equipment grounding conductor program 7.4 Installers should be advised: 7.4.1 These installation instructions are for use by qualified personnel only. NOTE: Installers must reference the National Electric Code (NEC) sections 250 or 690, when required, to ensure proper system wiring 7.4.2 The equipment contains DC voltages. 7.4.3 and grounding compliance. In addition, all state and federal Occupational Safety and Health Administration (OSHA) guidelines and regulations must be followed. NOTE: Installers must reference the specific site scope and project drawings for additional information and considerations, including the 7.4.4 system layout and any related electrical drawings. 7.4.5 The mounting location is important to the performance and operating life of the unit. The environment must be dry and protected from water ingress. 7.4.6 The installation is straightforward, but it is important each step is done correctly and safely. A mistake can lead to dangerous voltage and current levels. Be sure to carefully follow each instruction in this section. Read all instructions first before beginning installation. 7.4.7 The installation instructions are for installation of a negative grounded system. National Electrical Code (NEC) requirements are noted on occasion for convenience, however, the installer should have a complete understanding of NEC and UL requirements for photovoltaic installations. 10 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 7.0 Installation and Userʼs Manual GENERAL REQUIREMENTS 7.5 Recommended Tools 7.5.1 This installation may require the following, depending on the installation of specific ballasts and existing wiring: #2 and #0 Phillips screwdrivers Slotted screwdriver Wire strippers Wire cutters Pliers Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 11 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.1 24VDC ONE-LAMP BALLAST MODELS T5 1-Lamp Ballast 24W T5 HO (NB24-T524HO01D) 28W T5 (NB24-T528-01D) 54W T5 (NB24-T554-01D) T8 1-Lamp Ballast 32W T8 (NB24-T832-01D) 40W BIAXTM 1-Lamp Ballast 40W BIAX (NB24-BX40-01D) 24VDC ONE-LAMP BALLAST WIRING DIAGRAM NOTE: If an AC ballast has been previously installed in the location, refer to the Nextek Ballast Retrofit Kit Installation and User Manual, Lamp holder must not be shorted 8.1.1 available for download at www.nextekpower.com. 8.1.2 WARNING - Shock Hazard At the supply panel, disconnect power to the luminaire(s). WARNING - Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of unit. Check for enclosed wiring and components. 8.1.3 Mount the new Nextek low voltage ballast using existing studs or screws. If necessary, secure ballasts using appropriately sized sheet metal screws. If no existing hole or stud exists at the correct mounting location, use a self-tapping sheet metal screw. 8.1.4 Prepare the ballast mounting location: Refer to the luminaire manufacturer’s instructions or drawings to identify the mounting locations and any specific electrical location requirements or special instructions. 8.1.4.1 Select a ballast mounting location within the luminaire that leaves sufficient length to route the ballast’s wires to the fixture connections. 8.1.5 Slotted mounting holes for the ballasts are located on the flanges that protrude from the bottom of the unit housing. 8.1.6 For pre-existing mounting studs or holes: 8.1.6.1 Carefully align the ballast slot to one mounting hole or stud and insert a sheet metal screw. 12 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.1.6.2 Do not tighten the screw completely. Leave a 1/4" (6 mm) gap between the mounting surface and screw head. 8.1.6.3 Carefully align the ballast slot to one mounting hole or stud and insert a sheet metal screw. 8.1.6.4 When the ballast is properly positioned, tighten both (2) screws. 8.1.6.5 Proceed to step 8.1.8. 8.1.7 For a surface with no pre-existing mounting studs or holes: 8.1.7.1 Place a mark on the mounting surface for one of the mounting holes in accordance with the luminaire manufacturer’s instructions or drawings. 8.1.7.2 Use a self-tapping sheet metal screw to insert the first screw at the mark. 8.1.7.3 Do not tighten the screw completely. Leave a 1/4" (6 mm) gap between the mounting surface and screw head. 8.1.7.4 Mark the second mounting hole location for the ballast. 8.1.7.5 Carefully align the ballast slot to the second mounting hole and insert a sheet metal screw. 8.1.7.6 When the ballast is properly positioned, tighten both (2) screws. Notes Regarding Lampholders: 8.1.8 Ballast Wiring Instructions 8.1.8.1 8.1.8.1.1 If lampholders are not shunted, or the ballast being installed is a BIAX, then go to step 8.1.8.2. 8.1.8.1.2 If lampholders have a wire shunting the pins, remove the wire and go to step 8.1.8.2. 8.1.8.1.3 If lampholders are shunted, but do not have an external wire shunting the pins, then replace the lampholders with unshunted ones, following the manufacturer’s directions. 8.1.8.2 Connect the lampholder lead wires from the Nextek ballast as shown on the Ballast Wiring Schematic (below) to the lampholder connectors. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 13 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.1.8.3 BALLAST WIRING SCHEMATIC See step 8.1.8 for connections NOTE: Route wires within the Luminaire to maintain 1/4 inch separation between lampholder wires and the low voltage input power and control wires, using included wire ties, if necessary. Failure to maintain these separations will cause dimming performance problems. 8.1.8.4 Connect the dimming wires (purple and gray) to the dimming control, if used. If not used, cap off purple and gray wires individually. (Note: Shorting purple and gray wires will prevent ballast from ever turning on.) 8.1.8.5 Connect Nextek low voltage ballast input leads (black wires) to one of the following power inputs: 8.1.8.5.1 Tyco Electronics Load (Device) Cable Assembly (TE Part 2106718-x) for use with emerge standardized low voltage suspended ceiling grid, or to 8.1.8.5.2 A suitably-rated 90ºC cable between 12 and 18 AWG, terminating outside the luminaire, for example with a female 2-position Tyco Electronics Universal MATE-NLOK, or functional equivalent including strain relief, or directly to the next luminaire. There is no equipment ground in a class 2 wiring NOTE: system. Do not attach either 24V DC conductor to any Polarity (+ and –) does not matter on Nextek ballast input. 8.1.8.6 grounding post in the luminaire. Attach 24V DC conductors to the ballast input wires only. The ballast automatically adjusts its polarity. 14 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.1.8.7 NOTE: Class 2 circuits are power limited to 100 Watts. Do not attempt to attach more load on a single circuit, consulting the ballast and Class 2 power supply manufacturers’ specifications. 8.1.9 Replace any covers or diffusers removed during the installation. 8.1.10 Plug any unused openings in the luminaire. 8.1.11 Connect the power wire from the luminaire to: 8.1.11.1 EMerge Registered Busbar grid if terminated in EMerge Load Cable Assembly, or 8.1.11.2 Directly to Nextek PSM if terminated using the MATE-N-LOK type connector. 8.1.11.3 Directly to the adjacent luminaire. 8.1.12 Set Dimming Control to operate as follows: 0-1 Volts = Lamp off 1 Volt = Lamps ON- lowest dim level 1 – 10 Volts = Increasing in brightness with voltage increase 10 Volts = Lamps ON- Full brightness Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 15 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.2 24VDC TWO-LAMP BALLAST MODELS T5 2-Lamp Ballast 28W T5 (NB24-T528-02D) T8 2-Lamp Ballast 17W T8 (NB24-T817-02D) 32W T8 (NB24-T832-02D) 24VDC TWO-LAMP BALLAST WIRING DIAGRAM 8.2.1 NOTE: If an AC ballast has been previously installed in the location, refer to the Nextek Ballast Retrofit Kit Installation and User Manual, available for download at www.nextekpower.com. 8.2.2 WARNING - Shock Hazard At the supply panel, disconnect power to the luminaire(s). WARNING - Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of unit. Check for enclosed wiring and components. 8.2.3 Mount the new Nextek low voltage ballast using existing studs or screws. If necessary, secure ballasts using appropriately sized sheet metal screws. If no existing hole or stud exists at the correct mounting location, use a self-tapping sheet metal screw. 8.2.4 Prepare the ballast mounting location: Refer to the luminaire manufacturer’s instructions or drawings to identify the mounting locations and any specific electrical location requirements or special instructions. 8.2.4.1 Select a ballast mounting location within the luminaire that leaves sufficient length to route the ballast’s wires to the fixture connections. 8.2.5 Slotted mounting holes for the ballasts are located on the flanges that protrude from the bottom of the unit housing. 8.2.6 For pre-existing mounting studs or holes: 16 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.2.6.1 Carefully align the ballast slot to one mounting hole or stud and insert a sheet metal screw. 8.2.6.2 Do not tighten the screw completely. Leave a 1/4" (6 mm) gap between the mounting surface and screw head. 8.2.6.3 Carefully align the ballast slot to one mounting hole or stud and insert a sheet metal screw. 8.2.6.4 When the ballast is properly positioned, tighten both (2) screws. 8.2.6.5 Proceed to step 8.2.8. 8.2.7 For a surface with no pre-existing mounting studs or holes: 8.2.7.1 Place a mark on the mounting surface for one of the mounting holes in accordance with the luminaire manufacturer’s instructions or drawings. 8.2.7.2 Use a self-tapping sheet metal screw to insert the first screw at the mark. 8.2.7.3 Do not tighten the screw completely. Leave a 1/4" (6 mm) gap between the mounting surface and screw head. 8.2.7.4 Mark the second mounting hole location for the ballast. 8.2.7.5 Carefully align the ballast slot to the second mounting hole and insert a sheet metal screw. 8.2.7.6 When the ballast is properly positioned, tighten both (2) screws. Notes Regarding Lampholders: 8.2.8 Ballast Wiring Instructions 8.2.8.1 8.2.8.1.1 If lampholders are not shunted, or the ballast being installed is a BIAX, then go See to step 8.2.8.2. step 8.2.8.4 for connections 8.2.8.1.2 If lampholders have a wire shunting the pins, remove the wire and go to step 8.2.8.2. 8.2.8.1.3 If lampholders are shunted, but do not have an external wire shunting the pins, then replace the lampholders with unshunted ones, following the manufacturer’s directions. 8.2.8.2 Connect the lampholder lead wires from the Nextek ballast as shown on the Ballast Wiring Schematic (below) to the lampholder connectors. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 17 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.2.8.3 BALLAST WIRING SCHEMATIC NOTE: Route wires within the Luminaire to maintain 1/4 inch separation between lampholder wires and the low voltage input power and control wires, using included wire ties, if necessary. Failure to maintain these separations will cause dimming performance problems. NOTE: For single lamp operation, cap off yellow wires. Attach both blue wires to one end and both red wires to other end. 8.2.8.4 Connect the dimming wires (purple and gray) to the dimming control, if used. If not used, cap off purple and gray wires individually. (Note: Shorting purple and gray wires will prevent ballast from ever turning on.) 8.2.8.5 Connect Nextek low voltage ballast input leads (black wires) to one of the following power inputs: 8.2.8.5.1 Tyco Electronics Load (Device) Cable Assembly (TE Part 2106718-x) for use with emerge standardized low voltage suspended ceiling grid, or to 8.2.8.5.2 A suitably-rated 90ºC cable between 12 and 18 AWG, terminating outside the luminaire, for example with a female 2-position Tyco Electronics Universal MATE-NLOK, or functional equivalent including strain relief, or directly to the next luminaire. There is no equipment ground in a class 2 wiring NOTE: system. Do not attach either 24V DC conductor to any Polarity (+ and –) does not matter on Nextek ballast input. 8.2.8.6 grounding post in the luminaire. Attach 24V DC conductors 18 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE NOTE: Class 2 circuits are power limited to 100 Watts. Do not attempt to attach more load on a single circuit, to the ballast input wires only. The ballast automatically adjusts its polarity. 8.2.8.7 consulting the ballast and Class 2 power supply manufacturers’ specifications. 8.2.9 Replace any covers or diffusers removed during the installation. 8.2.10 Plug any unused openings in the luminaire. 8.2.11 Connect the power wire from the luminaire to: 8.2.11.1 EMerge Registered Busbar grid if terminated in EMerge Load Cable Assembly, or 8.2.11.2 Directly to Nextek PSM if terminated using the MATE-N-LOK type connector. 8.2.11.3 Directly to the adjacent luminaire. 8.2.12 Set Dimming Control to operate as follows: 0-1 Volts = Lamp off 1 Volt = Lamps ON- lowest dim level 1 – 10 Volts = Increasing in brightness with voltage increase 10 Volts = Lamps ON- Full brightness Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 19 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.3 CFL LAMP BALLAST MODELS 13W CFL (NB24-CF13-01D) 18W CFL (NB24-CF18-01D) 26W CFL (NB24-CF26-01D) 32/42W CFL (NB24-CF42-01D) CFL BALLAST WIRING DIAGRAM 8.3.1 NOTE: If an AC ballast has been previously installed in the location, refer to the Nextek Ballast Retrofit Kit Installation and User Manual, available for download at www.nextekpower.com. 8.3.2 WARNING - Shock Hazard At the supply panel, disconnect power to the luminaire(s). WARNING - Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of unit. Check for enclosed wiring and components. Notes Regarding Lampholders: 8.3.3 Ballast Wiring Instructions 8.3.3.1 8.3.3.1.1 Existing lampholders are assumed to be standard four (4) pin lampholders. 8.3.3.1.2 Not for use with luminaires that use standard line voltage Edison bases with integral ballasts. 8.3.4 Route the DC power input wires through a wire restraint into the enclosure at least 4 inches past the connector, and tighten the restraint screws. DC power input wires can be one of the following: 8.3.4.1 Tyco Electronics Load (Device) Cable Assembly (TE Part 2106718-x) for use with emerge standardized low voltage suspended ceiling grid, or to 8.3.4.2 a suitably-rated 90ºC cable between 12 and 18 AWG, terminating outside the luminaire, for example with a female 220 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE position Tyco Electronics Universal MATE-N-LOK, or functional equivalent including strain relief, or directly to the next luminaire. Polarity (+ and –) does not matter on Nextek ballast input. BALLAST REWIRING SCHEMATIC 8.3.5 Connect the black wires to the ballast power terminals. NOTE: There is no equipment ground in a class 2 wiring system. Do not attach either 24V DC conductor to any 8.3.6 Connect the blue and red lamp wires to the ballast terminals. 8.3.6.1 grounding post in the luminaire. Attach 24V DC conductors to the ballast input wires only. The ballast automatically adjusts its polarity. 8.3.6.2 NOTE: Class 2 circuits are power limited to 100 Watts. Do not attempt to attach more load on a single circuit, consulting the ballast and Class 2 power supply manufacturers’ specifications. 8.3.7 Replace the ballast wiring enclosure cover, and mount the new Nextek low voltage ballast using existing studs or screws. If necessary, secure ballasts using appropriately sized sheet metal screws. If no existing hole exists at the correct mounting location, use a self-tapping sheet metal screw. 8.3.8 Connect gray and purple control wires to the ballast terminals if a control system is in use. These will be connected to an exterior control box. 8.3.9 Replace any covers or diffusers removed during the installation. 8.3.10 Plug any unused openings in the luminaire. 8.3.11 Set Dimming Control to operate as follows: Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 21 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation Manual INSTALLATION PROCEDURE 0-1 Volts = Lamp off 1 Volt = Lamps ON- lowest dim level 1 – 10 Volts = Increasing in brightness with voltage increase 10 Volts = Lamps ON- Full brightness 22 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation and Userʼs Manual INSTALLATION PROCEDURE 8.4 48VDC TWO-LAMP BALLAST MODELS T5 2-Lamp Ballast KT2-54-R-S-53 T8 2-Lamp Ballast NB5353/2R KT2-54-R-S-53 48VDC TWO-LAMP BALLAST WIRING DIAGRAM SWITCH MODULAR JACK ON OFF RED + RED BLACK - NB5353/2R 48VDC TWO-LAMP BALLAST WIRING DIAGRAM Not actual sizes SWITCH MODULAR JACK ON OFF RED + BLACK - 8.4.1 8.4.2 NOTE: If an AC ballast has been previously installed in the location, refer to the Nextek Ballast Retrofit Kit Installation and User Manual, available for download at www.nextekpower.com. Not actual sizes WARNING - Shock Hazard At the supply panel, disconnect power to the luminaire(s). WARNING - Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of unit. Check for enclosed wiring and components. 23 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation Manual INSTALLATION PROCEDURE 8.4.3 Mount the new Nextek low voltage ballast using existing studs or screws. If necessary, secure ballasts using appropriately sized sheet metal screws. If no existing hole or stud exists at the correct mounting location, use a self-tapping sheet metal screw. 8.4.4 Prepare the ballast mounting location: Refer to the luminaire manufacturer’s instructions or drawings to identify the mounting locations and any specific electrical location requirements or special instructions. 8.4.4.1 Select a ballast mounting location within the luminaire that leaves sufficient length to route the ballast’s wires to the fixture connections. 8.4.5 Mounting holes (KT2-54-R-S-53) or slots (NB5353/2R) for the ballasts are located on the flanges that protrude from the bottom of the unit housing. 8.4.6 For pre-existing mounting studs or holes: 8.4.6.1 Carefully align the ballast slot to one mounting hole or stud and insert a sheet metal screw. 8.4.6.2 Do not tighten the screw completely. Leave a 1/4" (6 mm) gap between the mounting surface and screw head. 8.4.6.3 Carefully align the ballast slot to one mounting hole or stud and insert a sheet metal screw. 8.4.6.4 When the ballast is properly positioned, tighten both (2) screws. 8.4.6.5 Proceed to step 8.4.8. 8.4.7 For a surface with no pre-existing mounting studs or holes: 8.4.7.1 Place a mark on the mounting surface for one of the mounting holes in accordance with the luminaire manufacturer’s instructions or drawings. 8.4.7.2 Use a self-tapping sheet metal screw to insert the first screw at the mark. 8.4.7.3 Do not tighten the screw completely. Leave a 1/4" (6 mm) gap between the mounting surface and screw head. 8.4.7.4 Mark a second mounting hole location for the ballast. 8.4.7.5 Carefully align the ballast slot to a second mounting hole and insert a sheet metal screw. Repeat for additional holes if needed. 8.4.7.6 When the ballast is properly positioned, insert and tighten remaining screws. 24 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation Manual INSTALLATION PROCEDURE Notes Regarding Lampholders: 8.4.8 Ballast Wiring Instructions 8.4.8.1 8.4.8.1.1 If lampholders are not shunted, or the ballast being installed is a BIAX, then go to step 8.4.8.2. 8.4.8.1.2 If lampholders have a wire shunting the pins, remove the wire and go to step 8.4.8.2. 8.4.8.1.3 If lampholders are shunted, but do not have an external wire shunting the pins, then replace the lampholders with unshunted ones, following the manufacturer’s directions. 8.4.8.2 Connect the lampholder lead wires from the Nextek ballast as shown on the Ballast Wiring Diagrams (8.4) to the lampholder connectors. 8.4.8.3 NOTE: For single lamp operation, cap off yellow wires. Attach both blue wires to one end and both red wires to other end. 8.4.8.4 Connect Nextek low voltage ballast input leads (black/red wires) to one of the following power inputs: 8.4.8.4.1 Tyco Electronics Load (Device) Cable Assembly (TE Part 2106718-x) for use with emerge standardized low voltage suspended ceiling grid, or to 8.4.8.4.2 A suitably-rated 90ºC cable between 12 and 18 AWG, terminating outside the luminaire, for example with a female 2-position Tyco Electronics Universal MATE-NLOK, or functional equivalent including strain relief, or directly to the next luminaire. Polarity (+ and –) does not matter on Nextek ballast input. 8.4.8.5 In lieu of connecting wires, plug the RJ11 connector into an appropriate socket. 8.4.8.6 To connect the ballast to a toggle switch, you will need to install an RJ-11 Modular Jack Plate (Nextek #654 or equivalent), and mount the jack plate on a single gang box. The jack plate is typically mounted above a drop ceiling. MODULAR JACK 8.4.8.6.1 Mount the toggle switch (if not already done). 8.4.8.6.2 Connect the switch to the Red and Green contacts of the jack plate. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. CEILING WIRES TO JACK TERMINALS R & G ON OFF 25 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 8.0 Installation Manual INSTALLATION PROCEDURE 8.4.8.7 NOTE: There is no equipment ground in a class 2 wiring system. Do not attach either 24V DC conductor to any grounding post in the luminaire. Attach 24V DC conductors to the ballast input wires only. The ballast automatically adjusts its polarity. 8.4.8.8 NOTE: Class 2 circuits are power limited to 100 Watts. Do not attempt to attach more load on a single circuit, consulting the ballast and Class 2 power supply manufacturers’ specifications. 8.4.9 Replace any covers or diffusers removed during the installation. 8.4.10 Plug any unused openings in the luminaire. 8.4.11 Connect the power wire from the luminaire to: 8.4.11.1 EMerge Registered Busbar grid if terminated in EMerge Load Cable Assembly, or 8.4.11.2 Directly to Nextek PSM if terminated using the MATE-N-LOK type connector. 8.4.11.3 Directly to the adjacent luminaire. 8.5 WIRING A 2-LAMP BALLAST TO AN E-BALLAST FIXTURE 8.5.1 Follow the wiring diagram below to ensure correct connections. 2 LAMP BALLAST YELLOW (2) RED (2) BLUE (2) E-BALLAST RED (1) YELLOW (2) LAMP #1 E-LAMP #2 26 Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 9.0 Installation and Userʼs Manual CFL BALLAST INSTALLATION TIP SHEET 9.1 CFL LAMP BALLAST MODELS Based on light fixture assembly and operation experiences, the following represents a simple check list approach to assure maximum quality and operability for finished product that contains Nextek DC ballasts. 9.1.1 Ballast Location 9.1.1.1 Place ballast in a convenient location for future service access. 9.1.1.2 Where there are multiple ballasts, locate ballasts in a cluster fashion where all ballasts can be serviced conveniently. 9.1.2 Wiring 9.1.2.1 Locate unattached dimming wires (grey and purple), so that they can be easily accessed from the standard fixture access panels without having to disassemble entire fixture. 9.1.2.2 Use of push-in wire connectors, (Ideal brand or equal), is recommended as opposed to twist-on wire nuts. 9.1.2.3 In all cases, specific care must be given to proper stripping of wire insulation. Confirm proper length of exposed conductors and that the stripping process has not cut into or otherwise damaged the wire conductor. 9.1.2.4 Care must be taken for neat and organized wire management within the fixture. Use of tie straps and clustering of loose cabling should be performed. 9.1.2.5 In no case shall any exposed conductors of dimming or other wires be allowed to remain once fixture is closed. 9.1.3 Controls 9.1.3.1 It is expected that controls will be installed in the field for all fixtures. Care should be taken in final fixture assembly to accommodate a variety of controls, (dimming, occupancy sensing, daylight sensing). 9.1.4 Testing / General 9.1.4.1 Finished unit should be tested for basic operation before final packing or shipping. 9.1.4.2 Lamps should be new and in good operating condition. Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 27 Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 10.0 28 Installation Manual TROUBLESHOOTING Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. Rev. 031114 One Lamp, Two Lamp and CFL Ballasts 11.0 Installation and Userʼs Manual NOTES Copyright 2012-2014 all rights reserved by Nextek Power Systems, Inc. in the United States and in other countries throughout the world. 29 Rev. 031114 For more information: Nextek Power Systems 461 Burroughs Street Detroit, Michigan 48202 www.nextekpower.com Tel: 313-887-1321 Toll free: 1 (877) 24-VOLTS Fax: 313-887-9433 info@nextekpower.com