General Specifications AO-543-01

advertisement
General
Specifications
AO-543-01
GS48C43Z01-00E-N
Annunciator Module
■
GENERAL
Figure 1
This module has two independent
annunciator circuits. The circuits
handle fault signals and operator
actions (acknowledge, reset, etc.).
AO-543-01
Annunciator Module
Each circuit is connected to one indication light. Common outputs like an audible alarm are possible in
combination with the KA-549 module.
The module has a number of typical characteristics:
•
•
•
•
•
•
•
Logic-1 or logic-0 fault signal input
DC- and current pulse input
Galvanically isolated inputs
Various annunciator sequences possible (e.g. A, M, F2A, F3A)
First-failure detection
LED and lamp output
Shift register circuit for connection to the communication system
The fault input can be inverted depending on de INVERSE strapping. When using the current pulse input,
a single pulse can be filtered out by using the build-in time delay. The input signal is used to set two
memory circuits. The FIRST (failure) MEMORY and the ALARM MEMORY. Depending on the required
sequence, the reset inputs can be connected to acknowledge and reset push buttons. Flash inputs
determine, in combination with the memory status, the status of the output light/LED.
For first failure detection, AO-543 annunciator circuits are combined in groups by linking their first-failure
input/output. The way first-failure signals are handled, depends on the required annunciator sequence.
The AO-543 module is used in combination with the KA-549 module. The KA-549 contains the flash signal
source and it can handle the (common) claxon pulse signal.
Yokogawa Europe Solutions B.V.
PO Box 163, 3800 AD, Amersfoort, The Netherlands
Tel: (31) 88-464 1000 Fax: (31) 88-464 1111
GS48C43Z01-00E-N
 Copyright 1998
6th Edition April 2014
AO-543-01
■
2 of 16
FUNCTIONAL DIAGRAM
Inputs
Module
Outputs
Supply
Notes
Front
z32
24 Vdc field
z30
0 Vdc field
b32
20 Vdc logic
d32
0 Vdc logic
d30
A voltage pulse
b30
not used
Inverse
: connect d10 (d24) to z08 (z24) for inverse operation
1 input circuit 1
Timer
: connect d06 (z22) to z06 (z22) for extra time delay
2 output circuit 1
Sequence
: see typical applications
3 input circuit 2
4 output circuit 2
Audible device driven by KA-549
5
6
7
8
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
■
3 of 16
SPECIFICATIONS
Description
General
Environmental
No. of channels
Size
Connector
Identification
Temperature (working)
Temperature (storage)
Relative humidity
EMC
Explosion protection
Data
2
single euro format 6TE (160x100x30 mm)
DIN 41612 Bauform F 48p
AO-543 on front
-20 to +70 °C
-25 to +85 °C
max. 95%, no condensation
EN 61000-6-2 Immunity
EN 61000-6-4 Emission
(With an EMC system enclosure)
IECEx: Ex nA IIC T4 Gc
IEC 60079-0 : 2011 Edition 6.0 IEC 60079-15 : 2010 Edition 4
ATEX:
Input
Output
Propagation
Supply
Isolation
Dissipation
Shock
Vibration
Pulse
Unit load
DC
DC threshold
Status Indication
Flash
Non steady
Reset alarm
Reset first failure
First failure input
0V threshold
Functional test
Lamp test
24 V threshold
Serial Clock
Level
Lamp
Voltage/current
Fuse
LED
Status indication
Alarm status
First failure output
Claxon pulse
Voltage drop
Serial data
Level
On/off delay, pulse input
On/off delay, pulse input, timer activated
On/off delay dc input
On/off delay, dc input, timer activated
Supply voltage
Ripple
Current consumption
Current input
DC inputs
Alarm off
Alarm on
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
II 3 G Ex nA IIC T4 Gc
EN 60079-0 : 2012
EN 60079-15 : 2010
10g; 16 ms
10-55 Hz ; ± 0.35 mm
Current pulse 500 mA
1
24 Vdc, 1 mA
10-18 Vdc
red LED per channel
0 Vdc, 1 mA
0 Vdc, 1 mA
0 Vdc, 1 mA
0 Vdc, 1 mA
0 Vdc, 2 mA pulse
3-9 V
+24 Vdc, 2 mA
+24 Vdc, 2 mA
6-18 V
Clock pulse from MC-573 (min. 20µS)
0/11 V
current sink solid state
60 Vdc/1 A
1 A fast
2.2kΩ, current sink
red LED per channel
100 mA, current source min. 100 ms
100 mA, current sink
100 mA, current sink, ca. 100 – 150 ms
< 1 V, current source
<0.5 V, current sink (excl. LED output)
8 bit serial data
0/11 V
1/1 current pulse
ca. 4/4 current pulses
ca. 5/10 ms
ca. 9/14 ms
20 Vdc & 24 Vdc ± 10% (logic & field voltage)
< 1 V p-p (24 Vdc)
2 mA & 7-40 mA (off-on) clock signal
0.5 kV (test)
0.5 kV (test)
0.2 W
1.2-2.0 W (load 0-max.)
GS48C43Z01-00E-N April 2014
AO-543-01
■
4 of 16
NOTES
AO-543-01 Typical Applications
Sequence A: Automatic reset
Sequence features
1.
2.
3.
4.
5.
Acknowledge push-button.
Alarm audible device.
Lock-in of momentary alarms until acknowledged.
The audible device is silenced when acknowledged
Automatic reset of acknowledged alarm indications when process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
5 of 16
AO-543-01 Typical Applications
Sequence A-4-6: Automatic reset, no lock-in, no audible
Sequence features
1. Automatic reset of alarm indications when process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
6 of 16
AO-543-01 Typical Applications
Sequence A-5: Automatic reset, no flashing
Sequence features
1.
2.
3.
4.
5.
Acknowledge push-button.
Alarm audible device.
Lock-in of momentary alarms until acknowledged.
The audible device is silenced when acknowledged
Automatic reset of acknowledged alarm indications when process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
7 of 16
AO-543-01 Typical Applications
Sequence A-4-5-6: Automatic reset, no lock-in, no flashing, no audible
Sequence features
1. Automatic reset of alarm indications when process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
8 of 16
AO-543-01 Typical Applications
Sequence AS: Automatic reset, special (only flashing)
Sequence features
1.
2.
3.
4.
5.
Acknowledge push-button.
Alarm audible device.
Lock-in of momentary alarms until acknowledged.
The audible device is silenced when acknowledged.
Automatic reset of acknowledged alarm indications when process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
9 of 16
AO-543-01 Typical Applications
Sequence M: Manual reset
Sequence features
1.
2.
3.
4.
5.
Acknowledge push-button.
Alarm audible device.
Lock-in of momentary alarms until acknowledged.
The audible device is silenced and flashing stops when acknowledged
Manual reset of acknowledged alarm indications after process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
10 of 16
AO-543-01 Typical Applications
Sequence F1AS: First out, no subs. visual alarm, automatic reset, no lock-in
Sequence features
1.
2.
3.
4.
5.
Acknowledge push-button and alarm audible device.
Lock-in of momentary first alarm until acknowledged, no lock-in of momentary subsequent alarms.
Visual indication (flashing) for first alarm only.
First out indication is reset and the audible device is silenced when acknowledged.
Automatic reset of acknowledged alarm indications after process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
11 of 16
AO-543-01 Typical Applications
Sequence F1A: First out, no subsequent lock-in, automatic reset
Sequence features
1.
2.
3.
4.
5.
Acknowledge push-button and alarm audible device.
Lock-in of momentary first alarm only (until acknowledged).
Flashing indication for first alarm only. Subsequent alarms go to the acknowledged state.
First out indication is reset and the audible device is silenced when acknowledged.
Automatic reset of acknowledged alarm indications when process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
12 of 16
AO-543-01 Typical Applications
Sequence F3A: First out, subsequent alarm flashing and automatic reset
Sequence features
1.
2.
3.
4.
5.
Acknowledge and first out reset push-buttons.
Alarm audible device.
Lock-in of momentary alarms until acknowledged.
First out flashing different from subsequent flashing.
First out reset push-button to change the first out visual indication to be the same as subsequent
visual indications.
6. Automatic reset of acknowledged alarm indications when process conditions return to normal.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
13 of 16
AO-543-01 Typical Applications
Sequence
Connections:
A
(ISA)
connect b10(b24) and d12(d26) to 0V field
connect b08(b22) to fast flash
connect d14(d28) to acknowledge
connect b04(b18) to audible module
A-4-6
(ISA)
connect b10(b24), d12(d26) and d14(d28) to 0V field, do not connect b08(b22).
connect d08(d22) to fast flash
A-5
(ISA)
connect b10(b24) and d12(d26) to 0V field, do not connect b08(b22)
connect d14(d28) to acknowledge
connect b04(b18) to audible module
A-4-5-6 (ISA)
connect b10(b24), d12(d26) and d14(d28) to 0V field
AS
connect b10(b24) and d12(d26) to 0V field
connect d08(d22) and b08(b22) to fast flash
connect d14(d28) to acknowledge
connect b04(b18) to audible device
M
(ISA)
F1AS
connect b08(b22) to b10(b24)
connect b06(b20) to fast flash
connect d12(d26) to acknowledge
connect d14(d28) via RE-520 NC-contact to 0V field. (see NOTE 1)
connect RE-520 input to z04(z18).
connect b04(b18) to audible device
connect b08(b22) to 0V field
connect b06(b20) to fast flash
connect d12(d26) and d14(d28) to acknowledge
connect b10(b24) to first failure line
connect b04(b18) to audible device
F1A
(ISA)
connect d14(d28) to 0V field
connect b06(b20) to fast flash
connect d12(d26) to acknowledge
connect b10(b24) to first failure line
connect b04(b18) to audible device
F3A
(ISA)
connect b06(b20) to slow flash
connect b08(b22) to fast flash
connect d12(d26) to reset first failure
connect d14(d28) to acknowledge
connect b10(b24) to first failure line
connect b04(b18) to audible device
NOTE1:
M-sequence:
An additional RE-520 channel per AO-543 channel is needed.
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
■
14 of 16
NOTES
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
■
15 of 16
NOTES
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
AO-543-01
■
16 of 16
NOTES
All Rights Reserved.  Copyright Yokogawa Europe Solutions B.V.
GS48C43Z01-00E-N April 2014
Download