General Specifications AO-543-01 GS48C43Z01-00E-N Annunciator Module ■ GENERAL Figure 1 This module has two independent annunciator circuits. The circuits handle fault signals and operator actions (acknowledge, reset, etc.). AO-543-01 Annunciator Module Each circuit is connected to one indication light. Common outputs like an audible alarm are possible in combination with the KA-549 module. The module has a number of typical characteristics: • • • • • • • Logic-1 or logic-0 fault signal input DC- and current pulse input Galvanically isolated inputs Various annunciator sequences possible (e.g. A, M, F2A, F3A) First-failure detection LED and lamp output Shift register circuit for connection to the communication system The fault input can be inverted depending on de INVERSE strapping. When using the current pulse input, a single pulse can be filtered out by using the build-in time delay. The input signal is used to set two memory circuits. The FIRST (failure) MEMORY and the ALARM MEMORY. Depending on the required sequence, the reset inputs can be connected to acknowledge and reset push buttons. Flash inputs determine, in combination with the memory status, the status of the output light/LED. For first failure detection, AO-543 annunciator circuits are combined in groups by linking their first-failure input/output. The way first-failure signals are handled, depends on the required annunciator sequence. The AO-543 module is used in combination with the KA-549 module. The KA-549 contains the flash signal source and it can handle the (common) claxon pulse signal. Yokogawa Europe Solutions B.V. PO Box 163, 3800 AD, Amersfoort, The Netherlands Tel: (31) 88-464 1000 Fax: (31) 88-464 1111 GS48C43Z01-00E-N Copyright 1998 6th Edition April 2014 AO-543-01 ■ 2 of 16 FUNCTIONAL DIAGRAM Inputs Module Outputs Supply Notes Front z32 24 Vdc field z30 0 Vdc field b32 20 Vdc logic d32 0 Vdc logic d30 A voltage pulse b30 not used Inverse : connect d10 (d24) to z08 (z24) for inverse operation 1 input circuit 1 Timer : connect d06 (z22) to z06 (z22) for extra time delay 2 output circuit 1 Sequence : see typical applications 3 input circuit 2 4 output circuit 2 Audible device driven by KA-549 5 6 7 8 All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 ■ 3 of 16 SPECIFICATIONS Description General Environmental No. of channels Size Connector Identification Temperature (working) Temperature (storage) Relative humidity EMC Explosion protection Data 2 single euro format 6TE (160x100x30 mm) DIN 41612 Bauform F 48p AO-543 on front -20 to +70 °C -25 to +85 °C max. 95%, no condensation EN 61000-6-2 Immunity EN 61000-6-4 Emission (With an EMC system enclosure) IECEx: Ex nA IIC T4 Gc IEC 60079-0 : 2011 Edition 6.0 IEC 60079-15 : 2010 Edition 4 ATEX: Input Output Propagation Supply Isolation Dissipation Shock Vibration Pulse Unit load DC DC threshold Status Indication Flash Non steady Reset alarm Reset first failure First failure input 0V threshold Functional test Lamp test 24 V threshold Serial Clock Level Lamp Voltage/current Fuse LED Status indication Alarm status First failure output Claxon pulse Voltage drop Serial data Level On/off delay, pulse input On/off delay, pulse input, timer activated On/off delay dc input On/off delay, dc input, timer activated Supply voltage Ripple Current consumption Current input DC inputs Alarm off Alarm on All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. II 3 G Ex nA IIC T4 Gc EN 60079-0 : 2012 EN 60079-15 : 2010 10g; 16 ms 10-55 Hz ; ± 0.35 mm Current pulse 500 mA 1 24 Vdc, 1 mA 10-18 Vdc red LED per channel 0 Vdc, 1 mA 0 Vdc, 1 mA 0 Vdc, 1 mA 0 Vdc, 1 mA 0 Vdc, 2 mA pulse 3-9 V +24 Vdc, 2 mA +24 Vdc, 2 mA 6-18 V Clock pulse from MC-573 (min. 20µS) 0/11 V current sink solid state 60 Vdc/1 A 1 A fast 2.2kΩ, current sink red LED per channel 100 mA, current source min. 100 ms 100 mA, current sink 100 mA, current sink, ca. 100 – 150 ms < 1 V, current source <0.5 V, current sink (excl. LED output) 8 bit serial data 0/11 V 1/1 current pulse ca. 4/4 current pulses ca. 5/10 ms ca. 9/14 ms 20 Vdc & 24 Vdc ± 10% (logic & field voltage) < 1 V p-p (24 Vdc) 2 mA & 7-40 mA (off-on) clock signal 0.5 kV (test) 0.5 kV (test) 0.2 W 1.2-2.0 W (load 0-max.) GS48C43Z01-00E-N April 2014 AO-543-01 ■ 4 of 16 NOTES AO-543-01 Typical Applications Sequence A: Automatic reset Sequence features 1. 2. 3. 4. 5. Acknowledge push-button. Alarm audible device. Lock-in of momentary alarms until acknowledged. The audible device is silenced when acknowledged Automatic reset of acknowledged alarm indications when process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 5 of 16 AO-543-01 Typical Applications Sequence A-4-6: Automatic reset, no lock-in, no audible Sequence features 1. Automatic reset of alarm indications when process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 6 of 16 AO-543-01 Typical Applications Sequence A-5: Automatic reset, no flashing Sequence features 1. 2. 3. 4. 5. Acknowledge push-button. Alarm audible device. Lock-in of momentary alarms until acknowledged. The audible device is silenced when acknowledged Automatic reset of acknowledged alarm indications when process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 7 of 16 AO-543-01 Typical Applications Sequence A-4-5-6: Automatic reset, no lock-in, no flashing, no audible Sequence features 1. Automatic reset of alarm indications when process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 8 of 16 AO-543-01 Typical Applications Sequence AS: Automatic reset, special (only flashing) Sequence features 1. 2. 3. 4. 5. Acknowledge push-button. Alarm audible device. Lock-in of momentary alarms until acknowledged. The audible device is silenced when acknowledged. Automatic reset of acknowledged alarm indications when process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 9 of 16 AO-543-01 Typical Applications Sequence M: Manual reset Sequence features 1. 2. 3. 4. 5. Acknowledge push-button. Alarm audible device. Lock-in of momentary alarms until acknowledged. The audible device is silenced and flashing stops when acknowledged Manual reset of acknowledged alarm indications after process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 10 of 16 AO-543-01 Typical Applications Sequence F1AS: First out, no subs. visual alarm, automatic reset, no lock-in Sequence features 1. 2. 3. 4. 5. Acknowledge push-button and alarm audible device. Lock-in of momentary first alarm until acknowledged, no lock-in of momentary subsequent alarms. Visual indication (flashing) for first alarm only. First out indication is reset and the audible device is silenced when acknowledged. Automatic reset of acknowledged alarm indications after process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 11 of 16 AO-543-01 Typical Applications Sequence F1A: First out, no subsequent lock-in, automatic reset Sequence features 1. 2. 3. 4. 5. Acknowledge push-button and alarm audible device. Lock-in of momentary first alarm only (until acknowledged). Flashing indication for first alarm only. Subsequent alarms go to the acknowledged state. First out indication is reset and the audible device is silenced when acknowledged. Automatic reset of acknowledged alarm indications when process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 12 of 16 AO-543-01 Typical Applications Sequence F3A: First out, subsequent alarm flashing and automatic reset Sequence features 1. 2. 3. 4. 5. Acknowledge and first out reset push-buttons. Alarm audible device. Lock-in of momentary alarms until acknowledged. First out flashing different from subsequent flashing. First out reset push-button to change the first out visual indication to be the same as subsequent visual indications. 6. Automatic reset of acknowledged alarm indications when process conditions return to normal. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 13 of 16 AO-543-01 Typical Applications Sequence Connections: A (ISA) connect b10(b24) and d12(d26) to 0V field connect b08(b22) to fast flash connect d14(d28) to acknowledge connect b04(b18) to audible module A-4-6 (ISA) connect b10(b24), d12(d26) and d14(d28) to 0V field, do not connect b08(b22). connect d08(d22) to fast flash A-5 (ISA) connect b10(b24) and d12(d26) to 0V field, do not connect b08(b22) connect d14(d28) to acknowledge connect b04(b18) to audible module A-4-5-6 (ISA) connect b10(b24), d12(d26) and d14(d28) to 0V field AS connect b10(b24) and d12(d26) to 0V field connect d08(d22) and b08(b22) to fast flash connect d14(d28) to acknowledge connect b04(b18) to audible device M (ISA) F1AS connect b08(b22) to b10(b24) connect b06(b20) to fast flash connect d12(d26) to acknowledge connect d14(d28) via RE-520 NC-contact to 0V field. (see NOTE 1) connect RE-520 input to z04(z18). connect b04(b18) to audible device connect b08(b22) to 0V field connect b06(b20) to fast flash connect d12(d26) and d14(d28) to acknowledge connect b10(b24) to first failure line connect b04(b18) to audible device F1A (ISA) connect d14(d28) to 0V field connect b06(b20) to fast flash connect d12(d26) to acknowledge connect b10(b24) to first failure line connect b04(b18) to audible device F3A (ISA) connect b06(b20) to slow flash connect b08(b22) to fast flash connect d12(d26) to reset first failure connect d14(d28) to acknowledge connect b10(b24) to first failure line connect b04(b18) to audible device NOTE1: M-sequence: An additional RE-520 channel per AO-543 channel is needed. All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 ■ 14 of 16 NOTES All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 ■ 15 of 16 NOTES All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014 AO-543-01 ■ 16 of 16 NOTES All Rights Reserved. Copyright Yokogawa Europe Solutions B.V. GS48C43Z01-00E-N April 2014