BG2 Range - MANUAL CALL POINT - crouse

advertisement
BG2 Range - MANUAL CALL POINT
Exed, Intrinsically Safe (Exia), Weatherproof
Features
ᔢ Zone 0, Zone 1 and Zone 2 use.
ᔢ Exed, Exia or weatherproof.
ᔢ ATEX approved – Ex II 1G (Exia)
– Ex II 2G (Exed)
ᔢ BASEEFA certified.
ᔢ IP66 and IP67.
ᔢ Certified temperature: –40°C to +50°C*.
ᔢ Corrosion resistant red painted GRP.
ᔢ Retained stainless steel cover screws.
ᔢ Optional lift flap.
ᔢ Key operated test facility.
ᔢ Lightweight and robust.
ᔢ Breakglass hammer available.
(Contact sales office for details)
*Depending on version.
Introduction
This manual fire alarm call point has been designed for use in flammable
atmospheres and harsh environmental conditions. The GRP enclosure is
suitable for use offshore or onshore where lightweight combined with a high
level of corrosion resistance is required.
Cooper MEDC Limited,
Colliery Road,
Pinxton, Nottingham
NG16 6JF, UK.
Sales Enq. UK: +44 (0)1773 864 100
Cooper MEDC (USA)
3413 North Sam Houston Parkway West
Suite 212
Houston, TX 77086, USA
Sales Enq. USA: +1 (713) 937- 9772
E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS029/L
Specification
Protection:
Certification:
BG2W
BG2E
BG2I
Dust-tight and Weatherproof
Explosion Protected Exed
(Increased Safety)
Explosion Protected Exia
(Intrinsically Safe)
Not Applicable
CENELEC EN50014, 018, 019, 028
Cert. No. BAS02ATEX2105X
ExedIICT6 (switch only)
ExedmIICT4 (other versions)
Suitable for use in Zones 1 & 2
American Bureau of Shipping Type Approval
CENELEC EN50014, 020
Cert. No. Baseefa03ATEX0084X
Exia IIC T4
Suitable for use in Zones 0, 1 & 2
Up to 254V
Up to 250V (Switch only)
Up to 24V (Resistors & Switch)
Up to 28V (IS)
–40°C to +55°C
–20°C to +50°C
–40°C to +50°C
IP66 & 67.
IP66 & 67.
IP66 & 67.
BS 5839 : Part 2 : 1983 (BG).
BS 5839 : Part 2 : 1983 (BG).
BS 5839 : Part 2 : 1983 (BG).
Voltage:
Certified Temperature:
Ingress Protection:
British Standard for Call Points:
Switch Ratings:
Resistor Values:
d.c.: 0-30V 5A (resistive) or 3A (inductive)
30V-50V 1A resistive or inductive
a.c.: 0-254V 5A resistive or inductive
100R Minimum*
NOT APPLICABLE
100R Minimum, 39k Maximum*
Cable Enries:
470R Minimum*
2 x M20 bottom.
6 x 2.5mm2
Terminals:
6 x 2.5mm2
6 x 2.5mm2
Weight:
1.2 Kg.
Material:
U.V. resistant glass reinforced polyester.
Finish:
Painted Red
1. Switch Only
2. End of Line
Resistor / Diode
R1/D1
1 2 3 4 5 6
1 2 3 4 5 6
ALL CIRCUITS SHOWN WITH GLASS INTACT
3. In Line
Resistor / Diode
4. In Line & End of Line
Resistor / Diode
R1/D1
R2/D2
R2/D2
1 2 3 4 5 6
1 2 3 4 5 6
ALL DIMENSIONS IN MILLIMETERS
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box. For standard products, available ex-stock, contact sales office for details.
Model
The MEDC BG Range of Manual Alarm
Call Points caters for numerous options
such as variety of colours, LED
indication, earth continuity, double
switch, etc. See separate catalogue
sheet for details.
Model
BG2W – a.c. or d.c.
BG2I – Up to 28V (I.S.)
BG2E – d.c.
BG2E – a.c.
Options
Code
BG2WNN
BG2INN
BG2EDC
BG2EAC
Options
Code
Switch only
1
End of line resistor
2*
In line resistor
3*
In line and end of line resistor 4*
5
Diode (specify location & value)
Flap
Flap
Fitted
Not Fitted
Finish
Code
F*
N
Finish
Red Painted
Code
R
* Polycarbonate lift flap.
* Specify resistor values.
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12
BG3 Range - MANUAL CALL POINT
Intrinsically Safe (Exia), Weatherproof
Features
ᔢ Zone 0, Zone 1 and Zone 2 use.
ᔢ Exia IIC T4.
ᔢ ATEX Approved Ex II 1 G.
ᔢ BASEEFA certified.
ᔢ Chinese (CQST) certified.
ᔢ Designed in accordance with EN54-11.
ᔢ IP66 and IP67.
ᔢ Certified temperature: –55°C to +55°C.
ᔢ Corrosion free GRP.
ᔢ Optional in line/end of line resistors/diodes.
ᔢ Optional LED indicator.
ᔢ Optional lift flap.
ᔢ Key operated test facility.
ᔢ Various body colours available.
Introduction
This manual fire alarm call point has been designed in accordance with the
latest draft European Call Point Standard (EN54-11).
Weatherproof to IP66 and IP67 and available certified intrinsically safe,
simple apparatus or uncertified. The units are manufactured from glass
reinforced polyester (GRP) which provides a robust, corrosion free
construction and ensures effective and reliable operation in harsh industrial
and offshore environments.
Units are supplied in natural red GRP or painted to customer specification.
'Burning House' duty label is provided as standard, other duty and tag labels
may be supplied to customer specification.
Cooper MEDC Limited,
Colliery Road,
Pinxton, Nottingham
NG16 6JF, UK.
Sales Enq. UK: +44 (0)1773 864 100
Cooper MEDC (USA)
3413 North Sam Houston Parkway West
Suite 212
Houston, TX 77086, USA
Sales Enq. USA: +1 (713) 937- 9772
E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS100/M
Specification
Protection:
Certification:
BG3I
BG3W
Explosion Protected Exi
(Intrinsically Safe)
Dust-tight & Weatherproof
CENELEC EN50014, 020
BASEEFA Exia IIC T4
Cert No. BAS00ATEX1067X
Suitable for use in Zones 0, 1 & 2
Chinese Certification CQST – Exia IIC T4†
Not applicable
Voltage:
Certified Temperature:
Up to 28V (IS)
Up to 250V a.c.
-55°C to +55°C
Not applicable
IP66 & IP67
IP66 & IP67
Ingress protection:
European Standard for Call Points:
EN54-11
EN54-11
6 x 4.0mm2
6 x 4.0mm2
Not Applicable
d.c. 0V - 30V 3A resistive or inductive
30V - 50V 1A resistive or inductive
a.c. 0 - 250V 3A resistive or inductive
Terminals:
Switch Ratings:
Resistor Values:
Cable Entries:
470R Minimum
270R Minimum
2 x M20 top or bottom
2 x M20 top or bottom
Weight:
0.5Kg
0.5Kg
Material:
UV resistant glass reinforced polyester
UV resistant glass reinforced polyester
Natural Red GRP or Painted GRP to Customer requirements
Natural Red GRP or Painted GRP to Customer requirements
Stainless steel as standard
Plastic as standard
Finish:
Duty/Tag Labels:
ALL DIMENSIONS IN MILLIMETERS
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box. Standard products available ex-stock. Please visit www.coopermedc.com for further details.
Model
Labels
Certification
Options
Entries
Finish
BG3
Certification
Weatherproof
Exia
Chinese (CQST)
Code
W
I
Q†
† Not suitable for use in China on fire
alarm systems.
Label
Code
Glass Label
Fire Break Glass 'Press Here' 1
Break Glass 'Press Here'
2
Special
3*
European Standard
4
Duty Label (special)
5*
Burning House
as standard
Tag Label
6*
Options
None
Resistor Series
Resistor EOL
Diode
Polycarbonate Lift flap
Stainless steel Lift flap
LED
Double Changeover
Plastic Element
Code
N
S*
E*
D
F
C
L
T
P
Entries
2 x M20
(bottom)
2 x M20
(top)
Code
B
T
For blanking plugs add “P’ to
code. e.g. BP, 2 x M20
bottom entries with one blanking
plug.
Finish
Natural Red
Blue
Green
White
Yellow
Special
Code
R
B
G
W
Y
S*
* Please specify
(replaces break glass)
* Specify wording
* Please specify
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12
MANUAL CALL POINTS
Exed, Intrinsically Safe (Exia), Weatherproof BG Range & PB Range
Features
ᔢ Polyester enclosure – light, strong and not
subject to corrosion.
ᔢ 2 models:
Breakglass.
Pushbutton.
ᔢ 4 basic versions available:
(1) Explosion protected Exe (ATEX, Chinese
[CQST],Brazilian [Inmetro])
(2) Explosion protected Exi (ATEX, GOST ‘R’,
GOST ‘K’, Chinese (CQST),
Brazilian [Inmetro] or CSA),
(3) Explosion protected: Class I, Div. 2,
Groups A-D
Class II, Div. 2, Groups F & G (PB only)
Class I, Zone 2
(4) Weatherproof & Dust-tight/UL ordinary
locations.
ᔢ In line and end of line resistors and/or zener
diodes can be fitted.
ᔢ Variety of colours available.
ᔢ Up to 9 terminals available.
ᔢ Lift flap available for extra protection against
inadvertent operation.
Introduction
These manual fire alarm call points have been designed for use in
hazardous locations and harsh environmental conditions. The GRP
enclosures are suitable for use offshore or onshore, where lightweight
combined with a high level of corrosion resistance is required.
ᔢ Optional LED – this indicates that the unit has
been operated – useful for testing purposes.
ᔢ Earth continuity option for metal glands.
ᔢ 1 or 2 changeover switches.
ᔢ Captive cover screws.
ᔢ SIL 2 Certified.
Cooper MEDC Limited,
Colliery Road,
Pinxton, Nottingham
NG16 6JF, UK.
Sales Enq. UK: +44 (0)1773 864 100
Cooper MEDC (USA)
3413 North Sam Houston Parkway West
Suite 212
Houston, TX 77086, USA
Sales Enq. USA: +1 (713) 937- 9772
E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS067/S
Features
Breakglass Model
ᔢ No hammer required – the glass is covered by a membrane thus
protecting the operator from glass fragments.
ᔢ A plastic ‘Break glass’ or deformable operating element is
available to replace the break glass*.
Once the flexible element is pressed it bends but will not break.
The unit is reset by repositioning the element. All other functions
remain the same.
ᔢ Complies with the British Standard for call points.
ᔢ Key operated test facility – simple but secure.
ᔢ Breakglass hammer available.
Pushbutton Model
ᔢ Stayput as standard or self reset available.
ᔢ Lift Flap as standard. (Not turn and push model).
*Note: Deformable operating element does not comply with
BS5839 Part 2.
Specification
Model:
BGW & PBW
Protection:
Weatherproof/
dust proof
Certification:
Weatherproof/
dust proof
BGE & PBE
BGI & PBI
Explosion Protected
Class I, Div 2
Class II, Div 2
Explosion Protected
Exed
(Increased Safety)
Explosion Protected
Exia
(Intrinsically Safe)
UL Listed to Class I,
Div 2, Groups A-D
BGUL & PBUL
Class II, Div 2,
Groups F & G
(PBUL only)
Listing No. E186629
ATEX approved Ex II 2GD
BAS02ATEX2105X (PB only)
ATEX approved Ex II 1GD
Baseefa 03ATEX0084X (PB only)
ATEX approved Ex II 1G
Baseefa 03ATEX0084X (BG only)
*BGUL & PBUL
IP66/IP67
ATEX approved Ex II 2G
BAS02ATEX2105X (BG only)
Exia IIC T4
CENELEC EN50014
CENELEC EN50020
Suitable for use in Zones
0, 1 & 2
Exed IICT6 (switch only)
Exedm IICT4 (other versions)
CENELEC EN50014
EN50019
EN50018
EN50028
Suitable for use in Zones 1 & 2
UL listed for
ordinary locations
Listing No. S8117
*Refer to UL data
sheet at rear of
catalogue for
complete information
Chinese Certification (PBE & BGE):†
CQST – Exed IIC T6 (switch only)
Exedm IIC T4 (other versions)
GOST ‘R’ Certification (PBE & BGE):
Exedm IIC T6
Exedm IIC T4 (other versions)
Russian Fire Approved
Brazilian (Inmetro) Certification:
BR-Ex emd IIC T4 or BR-Ex ed IIC T6
CSA Certification to C22.2 (PBI only):
Nos.0-M, 0.4-M, 14-M, 25,
30-M, 94, 142-M1987,
157-M1987, 157-92,
Enclosure Type 4. T4A
Class I Groups A, B, C & D
Cert. No. 79120
GOST ‘R’ Certification (PBI & BGI):
Exia IIC T4 Russian Fire Approved
GOST ‘K’ Certification (PBI only):
Exia IIC T4
SIL 2 Certification to 61508.
Cert. No. Sira 11013 (BGE only).
Chinese Certification (PBI & BGI):
CQST – Exia IIC T4
American Bureau of Shipping Type Approval
BGE only
Brazilian (Inmetro) Certification:
BR-Ex ia IIC T4
American Bureau of Shipping Type Approval
Voltage:
Certified Temp:
Up to 254V
Up to 240V
–40°C to +55°C
Weatherproof
–25°C to +55°C (PBUL)
–25°C to +55°C (BGUL)
Switch Ratings:
(1 or 2 changeover
switches fitted)
Up to 250V
Up to 28V (IS)
–20°C to +50°C
ATEX/CENELEC –40°C to +70°C (PBI)
ATEX/CENELEC –40°C to +50°C (BGI)
UL Version
CSA –50°C to +40°C (PBI only)
d.c. - 0-30v 5A (resistive) or 3A (inductive)
30-50 1A resistive or inductive
a.c. - 0-254V 5A resistive or inductive
NOT APPLICABLE
Note: UL versions Max Rating 240VAC, 3A
Material:
Anti static U.V. resistant glass reinforced polyester.
Finish:
Red painted finish as standard or to Customer specification.
British Standard for Call Points:
BS 5839 : Part 2 : 1983 (BG).
Weight:
1.2 kg. (Varies with model & entries).
Ingress Protection:
IP66 & IP67.
Entries:
Up to 4 entries, M16 or M20 top and bottom (1/2" NPT available on UL version).
Terminals:
6 x 2.5mm2 – standard (BGUL only).
7 x 2.5mm2 – standard.
9 x 2.5mm2 optional – up to 60V only.
Risistors & Diodest:
Various configurations available on versions up to 24V and all "IS" versions.
(Minimum Resistor value 100ΩPBE/BGE, 470ΩPBI/BGI).
Earth Continuity:
Internal & external earth continuity is provided via an optional earth plate.
LED Indication:
A high intensity red LED can be fitted as an optional extra to indicate operation
on versions up to 24V and all "IS" versions.
Labels:
BG Glass label - reads either (1) Fire Break glass – press here
(2) Break glass – press here
(3) Worded to customer requirements.
PB & BG Duty label - worded to customer requirements. Rivetted on.
PB & BG Tag label - worded to customer requirements. Screwed on.
SW1
1 2 3 4 5 6
SW1
SW2
1 2 3 4 5 6
Basic single changeover
switch wiring diagram.
Note: additional
terminal as standard
for ATEX/CENELEC
units.
Basic double changeover
switch wiring diagram.
Note: additional
terminal as standard
for ATEX/CENELEC
units.
For versions containing inline and end of line
resistors or diodes, please specify your requirements.
ALL DIMENSIONS IN INCHES & MILLIMETERS
ALL DIMENSIONS IN MILLIMETERS
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box. Standard products available ex-stock. Please visit www.coopermedc.com for further details.
Model
Certification
BG
PB
Certification
Code
ATEX/CENELEC – Ex ed EB
ATEX/CENELEC – Exi
IB
CSA – Exi (PBI only)
IC
UL – Listed
UL
UL - Ordinary locations UW
GOST ‘R’ – Exi
IG*
GOST ‘R’ – Ex ed
EG*
GOST ‘K’ – Exi (PBI only) IK
CQST – Ex ed
EQ†
CQST – Exi
IQ†
Inmetro – Ex ed
EM
Inmetro – Exi
IM
Uncertified
WN
* Russian Fire Approved as standard.
† Not suitable for use in China on fire
alarm systems
Entries
Labels
Entries
M16
M20
1/2" NPT
Code
*A
*B
*C
Voltage
Voltage
a.c.
d.c.
Switches
Code
A
D
UL & CSA versions only
available with 1/2" NPT
entries.
Code
0
1
2
3*
4*
5*
Terminals
Options
Code
None
N
LED
A
Lift Flap (BG only)
B
Resistor Series
C*
Resistor EOL
D*
Diode
E†
Earth Continuity
F**
Turn & Push (PB only) T†
Self reset (PB only)
M
Resistor Series & EOL S*‡
Plastic element replaces
Break glass
P
*Prefix entry size (see diagram
above) with entry position
code e.g. 1A, 2A, 4B, 6B.
Labels
None
Glass label (1) reqd.
Glass label (2) reqd.
Glass label (3) reqd.
Duty label reqd.
Tag label reqd.
Options
Finish
Finish
Code
Red (Standard) R
Natural Black N
Blue
B
Yellow
Y
Grey
G
Yellow/Black
X
Stripes
Special
S*
* Please specify
* Specify values
† Not available for UL/CSA versions.
‡ Choose for BGE or PBE only – on
BGI/W or PBI/W choose C & D
** Must be selected when selecting CSA
certification
* Specify wording on 3, 4 or 5 as required.
Switches
Single changeover
Double changeover
Code
S
D
Terminals
Code
6 x 2.5mm2 (standard) 6*
7 x 2.5mm2 (standard) 7
9 x 2.5mm2 (optional) 9
* BGUL only availablewith six terminals
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12
MANUAL CALL POINTS
Exed, Intrinsically Safe (Exia), Weatherproof BG Range & PB Range
Features
ᔢ Polyester enclosure – light, strong and not
subject to corrosion.
ᔢ 2 models:
Breakglass.
Pushbutton.
ᔢ 4 basic versions available:
(1) Explosion protected Exe (ATEX, Chinese
[CQST],Brazilian [Inmetro])
(2) Explosion protected Exi (ATEX, GOST ‘R’,
GOST ‘K’, Chinese (CQST),
Brazilian [Inmetro] or CSA),
(3) Explosion protected: Class I, Div. 2,
Groups A-D
Class II, Div. 2, Groups F & G (PB only)
Class I, Zone 2
(4) Weatherproof & Dust-tight/UL ordinary
locations.
ᔢ In line and end of line resistors and/or zener
diodes can be fitted.
ᔢ Variety of colours available.
ᔢ Up to 9 terminals available.
ᔢ Lift flap available for extra protection against
inadvertent operation.
Introduction
These manual fire alarm call points have been designed for use in
hazardous locations and harsh environmental conditions. The GRP
enclosures are suitable for use offshore or onshore, where lightweight
combined with a high level of corrosion resistance is required.
ᔢ Optional LED – this indicates that the unit has
been operated – useful for testing purposes.
ᔢ Earth continuity option for metal glands.
ᔢ 1 or 2 changeover switches.
ᔢ Captive cover screws.
ᔢ SIL 2 Certified.
Cooper MEDC Limited,
Colliery Road,
Pinxton, Nottingham
NG16 6JF, UK.
Sales Enq. UK: +44 (0)1773 864 100
Cooper MEDC (USA)
3413 North Sam Houston Parkway West
Suite 212
Houston, TX 77086, USA
Sales Enq. USA: +1 (713) 937- 9772
E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS067/S
Features
Breakglass Model
ᔢ No hammer required – the glass is covered by a membrane thus
protecting the operator from glass fragments.
ᔢ A plastic ‘Break glass’ or deformable operating element is
available to replace the break glass*.
Once the flexible element is pressed it bends but will not break.
The unit is reset by repositioning the element. All other functions
remain the same.
ᔢ Complies with the British Standard for call points.
ᔢ Key operated test facility – simple but secure.
ᔢ Breakglass hammer available.
Pushbutton Model
ᔢ Stayput as standard or self reset available.
ᔢ Lift Flap as standard. (Not turn and push model).
*Note: Deformable operating element does not comply with
BS5839 Part 2.
Specification
Model:
BGW & PBW
Protection:
Weatherproof/
dust proof
Certification:
Weatherproof/
dust proof
BGE & PBE
BGI & PBI
Explosion Protected
Class I, Div 2
Class II, Div 2
Explosion Protected
Exed
(Increased Safety)
Explosion Protected
Exia
(Intrinsically Safe)
UL Listed to Class I,
Div 2, Groups A-D
BGUL & PBUL
Class II, Div 2,
Groups F & G
(PBUL only)
Listing No. E186629
ATEX approved Ex II 2GD
BAS02ATEX2105X (PB only)
ATEX approved Ex II 1GD
Baseefa 03ATEX0084X (PB only)
ATEX approved Ex II 1G
Baseefa 03ATEX0084X (BG only)
*BGUL & PBUL
IP66/IP67
ATEX approved Ex II 2G
BAS02ATEX2105X (BG only)
Exia IIC T4
CENELEC EN50014
CENELEC EN50020
Suitable for use in Zones
0, 1 & 2
Exed IICT6 (switch only)
Exedm IICT4 (other versions)
CENELEC EN50014
EN50019
EN50018
EN50028
Suitable for use in Zones 1 & 2
UL listed for
ordinary locations
Listing No. S8117
*Refer to UL data
sheet at rear of
catalogue for
complete information
Chinese Certification (PBE & BGE):†
CQST – Exed IIC T6 (switch only)
Exedm IIC T4 (other versions)
GOST ‘R’ Certification (PBE & BGE):
Exedm IIC T6
Exedm IIC T4 (other versions)
Russian Fire Approved
Brazilian (Inmetro) Certification:
BR-Ex emd IIC T4 or BR-Ex ed IIC T6
CSA Certification to C22.2 (PBI only):
Nos.0-M, 0.4-M, 14-M, 25,
30-M, 94, 142-M1987,
157-M1987, 157-92,
Enclosure Type 4. T4A
Class I Groups A, B, C & D
Cert. No. 79120
GOST ‘R’ Certification (PBI & BGI):
Exia IIC T4 Russian Fire Approved
GOST ‘K’ Certification (PBI only):
Exia IIC T4
SIL 2 Certification to 61508.
Cert. No. Sira 11013 (BGE only).
Chinese Certification (PBI & BGI):
CQST – Exia IIC T4
American Bureau of Shipping Type Approval
BGE only
Brazilian (Inmetro) Certification:
BR-Ex ia IIC T4
American Bureau of Shipping Type Approval
Voltage:
Certified Temp:
Up to 254V
Up to 240V
–40°C to +55°C
Weatherproof
–25°C to +55°C (PBUL)
–25°C to +55°C (BGUL)
Switch Ratings:
(1 or 2 changeover
switches fitted)
Up to 250V
Up to 28V (IS)
–20°C to +50°C
ATEX/CENELEC –40°C to +70°C (PBI)
ATEX/CENELEC –40°C to +50°C (BGI)
UL Version
CSA –50°C to +40°C (PBI only)
d.c. - 0-30v 5A (resistive) or 3A (inductive)
30-50 1A resistive or inductive
a.c. - 0-254V 5A resistive or inductive
NOT APPLICABLE
Note: UL versions Max Rating 240VAC, 3A
Material:
Anti static U.V. resistant glass reinforced polyester.
Finish:
Red painted finish as standard or to Customer specification.
British Standard for Call Points:
BS 5839 : Part 2 : 1983 (BG).
Weight:
1.2 kg. (Varies with model & entries).
Ingress Protection:
IP66 & IP67.
Entries:
Up to 4 entries, M16 or M20 top and bottom (1/2" NPT available on UL version).
Terminals:
6 x 2.5mm2 – standard (BGUL only).
7 x 2.5mm2 – standard.
9 x 2.5mm2 optional – up to 60V only.
Risistors & Diodest:
Various configurations available on versions up to 24V and all "IS" versions.
(Minimum Resistor value 100ΩPBE/BGE, 470ΩPBI/BGI).
Earth Continuity:
Internal & external earth continuity is provided via an optional earth plate.
LED Indication:
A high intensity red LED can be fitted as an optional extra to indicate operation
on versions up to 24V and all "IS" versions.
Labels:
BG Glass label - reads either (1) Fire Break glass – press here
(2) Break glass – press here
(3) Worded to customer requirements.
PB & BG Duty label - worded to customer requirements. Rivetted on.
PB & BG Tag label - worded to customer requirements. Screwed on.
SW1
1 2 3 4 5 6
SW1
SW2
1 2 3 4 5 6
Basic single changeover
switch wiring diagram.
Note: additional
terminal as standard
for ATEX/CENELEC
units.
Basic double changeover
switch wiring diagram.
Note: additional
terminal as standard
for ATEX/CENELEC
units.
For versions containing inline and end of line
resistors or diodes, please specify your requirements.
ALL DIMENSIONS IN INCHES & MILLIMETERS
ALL DIMENSIONS IN MILLIMETERS
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box. Standard products available ex-stock. Please visit www.coopermedc.com for further details.
Model
Certification
BG
PB
Certification
Code
ATEX/CENELEC – Ex ed EB
ATEX/CENELEC – Exi
IB
CSA – Exi (PBI only)
IC
UL – Listed
UL
UL - Ordinary locations UW
GOST ‘R’ – Exi
IG*
GOST ‘R’ – Ex ed
EG*
GOST ‘K’ – Exi (PBI only) IK
CQST – Ex ed
EQ†
CQST – Exi
IQ†
Inmetro – Ex ed
EM
Inmetro – Exi
IM
Uncertified
WN
* Russian Fire Approved as standard.
† Not suitable for use in China on fire
alarm systems
Entries
Labels
Entries
M16
M20
1/2" NPT
Code
*A
*B
*C
Voltage
Voltage
a.c.
d.c.
Switches
Code
A
D
UL & CSA versions only
available with 1/2" NPT
entries.
Code
0
1
2
3*
4*
5*
Terminals
Options
Code
None
N
LED
A
Lift Flap (BG only)
B
Resistor Series
C*
Resistor EOL
D*
Diode
E†
Earth Continuity
F**
Turn & Push (PB only) T†
Self reset (PB only)
M
Resistor Series & EOL S*‡
Plastic element replaces
Break glass
P
*Prefix entry size (see diagram
above) with entry position
code e.g. 1A, 2A, 4B, 6B.
Labels
None
Glass label (1) reqd.
Glass label (2) reqd.
Glass label (3) reqd.
Duty label reqd.
Tag label reqd.
Options
Finish
Finish
Code
Red (Standard) R
Natural Black N
Blue
B
Yellow
Y
Grey
G
Yellow/Black
X
Stripes
Special
S*
* Please specify
* Specify values
† Not available for UL/CSA versions.
‡ Choose for BGE or PBE only – on
BGI/W or PBI/W choose C & D
** Must be selected when selecting CSA
certification
* Specify wording on 3, 4 or 5 as required.
Switches
Single changeover
Double changeover
Code
S
D
Terminals
Code
6 x 2.5mm2 (standard) 6*
7 x 2.5mm2 (standard) 7
9 x 2.5mm2 (optional) 9
* BGUL only availablewith six terminals
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12
PH1 Range - PULL HANDLE CALL POINT
Exd, Weatherproof
Features
ᔢ Zone 1 and Zone 2 use.
ᔢ Ex d IIC T6 Gb
ᔢ Ex tb IIIC T85ºC Db
ᔢ IECEx certified Gb, Db
ᔢ ATEX certified Ex II 2 GD
ᔢ IP66 & 67
ᔢ Certified temperature: -55ºC to +70ºC
ᔢ Corrosion free GRP construction
ᔢ Optional in line, end of line resistors and diodes
ᔢ Retained stainless steel cover screws
Introduction
The PH1 double action pull handle call point has been designed for use
in flammable atmospheres and harsh environmental conditions. The GRP
enclosure is suitable for use offshore or onshore where light weight
combined with a high level of corrosion resistance is required.
Cooper MEDC Limited,
Colliery Road,
Pinxton, Nottingham
NG16 6JF, UK.
Sales Enq. UK: +44 (0)1773 864 100
Cooper MEDC (USA)
3413 North Sam Houston Parkway West
Suite 212
Houston, TX 77086, USA
Sales Enq. USA: +1 (713) 937- 9772
E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS130/A
Specification
Certification:
Certified to IEC60079-0, IEC60079-1 and IEC60079-31
Certified to EN60079-0, EN60079-1 and EN60079-31
IECEx Cert. No. IECEx ITS 11.0021X
Atex Cert. No. ITS11ATEX17308X Ex II 2 GD
Ex d IIC T6 Gb, Ex tb IIIC T85ºC Db
Material:
Body/covers/handles:- GRP (glass reinforced polyester)
Fixings:- Stainless steel grade 316
Finish:
Cover:- natural red, Body:- natural black.
Handles:- natural white.
Cover may be painted to customer's requirements.
Voltage:
0-50Vdc, 0-254Vac.
Switch Rating:
1 or 2 c/o switches, 254V, 3A max.
Weight:
Gross weight 3.2Kg. Net weight 2.6Kg
Certified Temp:
-55°C to +70°C.
Ingress Protection:
IP66 & 67.
Entries:
Up to 2 x M20 or M25, up to 2 x 1/2” or 3/4” NPT.
Terminals:
6 x 2.5mm2 as standard. Contact Cooper MEDC for options.
Earth Continuity:
Earth continuity is provided by internal plate.
Labels:
'Burning house' label fitted as standard on red units.
Blank label fitted as standard on all other colour units.
Tag & Duty label options, worded to customers requirements.
Addr. module:
Consult Cooper MEDC for options.
Resistors:
Various configurations available, 470 Ohms minimum.
Diodes:
Various configurations available.
SINGLE SWITCH
DOUBLE SWITCH
SINGLE SWITCH
DOUBLE SWITCH
SINGLE SWITCH
DOUBLE SWITCH
Standard wiring switch only
Standard wiring c/w EOL resistor
R1 - EOL Resitor
Standard wiring c/w series resistor or
series & EOL resistor
R1 - Series Resitor
R2 - EOL Resitor (if fitted)
ALL DIMENSIONS IN MILLIMETRES
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box.
Model
Entries
Certification
Switches
Features
Finish
PH1
Certification
ATEX
IECEx
Code
B
J
Entries
M20
M25
1/2" NPT
3/4" NPT
Code
*B
*C
*M
*N
Switches
Single changeover
Double changeover
* Prefix entry size with entry position
(see diagram above). E.g. 4B6B.
Maximum 2 Entries
Code
S
D
Features
None
Series resistor
EOL resistor
Diode
Tag label
Duty label
Code
N
G*
H*
E*
T*
D*
Finish
Natural Red
Special
Code
R
S*
* Please specify
* Please specify
NOTE: the units can be internally wired to suit customers specifications. Please discuss your requirements with us.
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12
SM87 BG & PB Range - MANUAL CALL POINTS
Intrinsically Safe (Exia), Exd, Weatherproof
Features
ᔢ Zone 0, Zone 1 and Zone 2 use*.
ᔢ Exia IIC T4 or Exd IIC T5/T6.
ᔢ ATEX aproved, Ex II 1G (Exia) Ex II 2GD (Exd).
ᔢ BASEEFA certified
ᔢ UL Listed (PB only), Class I, Div 1, Groups C & D.
ᔢ CSA certified.
ᔢ IECEx certified Gb, Db.
ᔢ GOST ‘R’ & ‘K’* certified.
ᔢ Chinese (CQST) certified.
ᔢ Brazilian (Inmetro) certified.
ᔢ IP66 and IP67.
ᔢ Certified temperature: –55°C to +70°C*.
ᔢ Stainless steel or marine grade alloy.
ᔢ Robust yet lightweight.
ᔢ Easy to maintain.
*Depending on version.
Introduction
These manual fire alarm, emergency shutdown breakglass and pushbutton
units have been designed for the most arduous environmental conditions.
The units are both easy to install and maintain. Intrinsically safe Exia and
flameproof Exd versions of each model are available.
A choice of either stainless steel or alloy makes the range suitable for either
the offshore or onshore industries.
Cooper MEDC Limited,
Colliery Road,
Pinxton, Nottingham
NG16 6JF, UK.
Sales Enq. UK: +44 (0)1773 864 100
Cooper MEDC (USA)
3413 North Sam Houston Parkway West
Suite 212
Houston, TX 77086, USA
Sales Enq. USA: +1 (713) 937- 9772
E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS015/O
Specification
Type:
Breakglass unit, latching
Lift flap, Breakglass, latching
Push button, latching, key reset
Push button, self reset
Certification:
Ex d certified to IEC60079-0, IEC60079-1, IEC60079-31
Ex d certified to EN60079-0, EN60079-1, EN60079-31
Exia certified to IEC60079-0, IEC60079-11, IEC60079-26
Exia certified to EN60079-0, EN60079-11, EN60079-26
Ex d ATEX Cert. No. Baseefa03ATEX0075
Ex II 2 GD Ex d IIC T5/T6 Gb, Ex tb IIIC T85°C/T100°C Db
Exia ATEX Cert. No. Baseefa02ATEX0152X
Ex II 1 G Ex ia IIC T4 Ga
Ex d IECEx Cert. No. IECEx BAS 09.0060
Ex d IIC T5/6 Gb, Ex tb T85°C/T100°C Db
Exia IECEx Cert. No. IECEx BAS 10.0033X
Exia IIC T4 Ga
UL Listed: Class I, Div1 Groups C & D (PBL only).
Listing No: 186629.
CSA Certification: Class I Groups A-D I.S. version (SM87 PBI only).
Class I, Div 1 & 2, Group D (Exd – SM87 PB & SM87 BG).
GOST ‘R’ Certification: 1Exib IIC T4, 1Exd IIC T4
Russian Fire Approval
GOST ‘K’ Certification: Exib IIC T4.
Chinese Certification: CQST – Exia IIC T4, Exd IIC T5/T6. †
Brazilian (Inmetro) Certification: BR-Ex d IIC T5/T6, BR-Ex ia IIC T4
Material:
Grade 316 ANC4B Stainless Steel or
LM 25 TF Marine Grade Alloy.
Finish:
Paint finish as standard or to customer specification.
Voltage:
Exd 24V a.c./d.c. Exia 28V.
Rating:
2 amp.
Switches
2 pole c/o, wired to terminals.
Optional up to 4 pole (UL version 2 pole only).
Type SM87BGL
Type SM87LBGL
Type SM87PBL
Type SM87PBM
ALL DIMENSIONS IN MILLIMETERS
Both the Exia units and the Exd units have the same external appearance. Also the internal
components are identical throughout the range. Each unit can be wired for either NO, NC or
CO contacts to customer specification.
Optional Indicator: A red high intensity LED can be fitted for alarm indication.
Certified Temp:
Weight:
Exd*–55°C to +70°C. Exi*–55°C to +55°C.
–20°C to +55°C (LED version only).
UL –55°C to +70°C, –20°C to +55°C (LED version only).
CSA –50°C to +55°C (Exd), –50°C to +40°C (Exi).
*Note: includes ATEX, IECEx, GOST, Brazilian & Chinese versions.
3·8 kg. steel (approx.) or 2.5 kg. alloy (approx.).
Ingress Protection: IP66 and IP67. SM87 PB IP68 (40m for 8 hours).
Entries:
Up to 4 x M20 or M25 ISO Exd/Exia.
Up to 4 x 1/2" or 3/4" NPT UL
Terminals:
Will accept up to 2·5mm2 cable.
Resistor Values:
470R minimum (d.c. & I.S. units only).
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box.
Unit
Model
Material
Certification
Entries
Duty Label
Tag Label
Options
Finish
Options
Code
Not required
N
LED
A
Resistor Series G*
Resistor EOL
H*
Diode
D*
3 Pole
T
c/o Switch
4 Pole
F
c/o Switch
Other
O*
Finish
Code
Red
R
Blue
B
Yellow
Y
Yellow/
X
Black Stripes
Special
S*
SM87
*Model
Code
Breakglass Latching
BGL
Lift Flap Breakglass Latching
LBGL
Push Button Latching key reset PBL
Push Button Only
PBM
Momentary Action
* UL version only available in PBL model.
*Material
Code
Stainless Steel S
Alloy
A
* UL version only available
in Alloy.
Certification
Exia
Exd
IECEx Exi
IECEx Exd
UL
CSA – Exi
CSA – Exd
GOST ‘K’ – Exi
GOST ‘R’ Exi
GOST ‘R’ Exd
Chinese Exi
Chinese Exd
Inmetro Exi
Inmetro Exd
Code
I
D
IJ
DJ
UL
IC
DC
IK
IG*
DG*
IQ†
DQ†
IM
DM
* Russian Fire Approval as standard.
† Not suitable for use in China on
fire alarm systems
Entries
M20
M25
1/2" NPT
3/4" NPT
Other
Code
1
2
3
4
5
Position
Top
Bottom
RHS
LHS
*T
*B
*R
*L
* Prefix position with size code
i.e. 1T 1B = 20mm Top and
Bottom.
Duty Label Code
Fire-Breakglass 1
Push Button
2
Fire-Push Button 3
ESDO-Abandon 4
Other
O*
None
N
* Please specify
* Please specify
* Please specify
Label
Code
Required
Y*
Not Required
N
* Please specify
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12
SM87 BG & PB Range - MANUAL CALL POINTS
Intrinsically Safe (Exia), Exd, Weatherproof
Features
ᔢ Zone 0, Zone 1 and Zone 2 use*.
ᔢ Exia IIC T4 or Exd IIC T5/T6.
ᔢ ATEX aproved, Ex II 1G (Exia) Ex II 2GD (Exd).
ᔢ BASEEFA certified
ᔢ UL Listed (PB only), Class I, Div 1, Groups C & D.
ᔢ CSA certified.
ᔢ IECEx certified Gb, Db.
ᔢ GOST ‘R’ & ‘K’* certified.
ᔢ Chinese (CQST) certified.
ᔢ Brazilian (Inmetro) certified.
ᔢ IP66 and IP67.
ᔢ Certified temperature: –55°C to +70°C*.
ᔢ Stainless steel or marine grade alloy.
ᔢ Robust yet lightweight.
ᔢ Easy to maintain.
*Depending on version.
Introduction
These manual fire alarm, emergency shutdown breakglass and pushbutton
units have been designed for the most arduous environmental conditions.
The units are both easy to install and maintain. Intrinsically safe Exia and
flameproof Exd versions of each model are available.
A choice of either stainless steel or alloy makes the range suitable for either
the offshore or onshore industries.
Cooper MEDC Limited,
Colliery Road,
Pinxton, Nottingham
NG16 6JF, UK.
Sales Enq. UK: +44 (0)1773 864 100
Cooper MEDC (USA)
3413 North Sam Houston Parkway West
Suite 212
Houston, TX 77086, USA
Sales Enq. USA: +1 (713) 937- 9772
E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS015/O
Specification
Type:
Breakglass unit, latching
Lift flap, Breakglass, latching
Push button, latching, key reset
Push button, self reset
Certification:
Ex d certified to IEC60079-0, IEC60079-1, IEC60079-31
Ex d certified to EN60079-0, EN60079-1, EN60079-31
Exia certified to IEC60079-0, IEC60079-11, IEC60079-26
Exia certified to EN60079-0, EN60079-11, EN60079-26
Ex d ATEX Cert. No. Baseefa03ATEX0075
Ex II 2 GD Ex d IIC T5/T6 Gb, Ex tb IIIC T85°C/T100°C Db
Exia ATEX Cert. No. Baseefa02ATEX0152X
Ex II 1 G Ex ia IIC T4 Ga
Ex d IECEx Cert. No. IECEx BAS 09.0060
Ex d IIC T5/6 Gb, Ex tb T85°C/T100°C Db
Exia IECEx Cert. No. IECEx BAS 10.0033X
Exia IIC T4 Ga
UL Listed: Class I, Div1 Groups C & D (PBL only).
Listing No: 186629.
CSA Certification: Class I Groups A-D I.S. version (SM87 PBI only).
Class I, Div 1 & 2, Group D (Exd – SM87 PB & SM87 BG).
GOST ‘R’ Certification: 1Exib IIC T4, 1Exd IIC T4
Russian Fire Approval
GOST ‘K’ Certification: Exib IIC T4.
Chinese Certification: CQST – Exia IIC T4, Exd IIC T5/T6. †
Brazilian (Inmetro) Certification: BR-Ex d IIC T5/T6, BR-Ex ia IIC T4
Material:
Grade 316 ANC4B Stainless Steel or
LM 25 TF Marine Grade Alloy.
Finish:
Paint finish as standard or to customer specification.
Voltage:
Exd 24V a.c./d.c. Exia 28V.
Rating:
2 amp.
Switches
2 pole c/o, wired to terminals.
Optional up to 4 pole (UL version 2 pole only).
Type SM87BGL
Type SM87LBGL
Type SM87PBL
Type SM87PBM
ALL DIMENSIONS IN MILLIMETERS
Both the Exia units and the Exd units have the same external appearance. Also the internal
components are identical throughout the range. Each unit can be wired for either NO, NC or
CO contacts to customer specification.
Optional Indicator: A red high intensity LED can be fitted for alarm indication.
Certified Temp:
Weight:
Exd*–55°C to +70°C. Exi*–55°C to +55°C.
–20°C to +55°C (LED version only).
UL –55°C to +70°C, –20°C to +55°C (LED version only).
CSA –50°C to +55°C (Exd), –50°C to +40°C (Exi).
*Note: includes ATEX, IECEx, GOST, Brazilian & Chinese versions.
3·8 kg. steel (approx.) or 2.5 kg. alloy (approx.).
Ingress Protection: IP66 and IP67. SM87 PB IP68 (40m for 8 hours).
Entries:
Up to 4 x M20 or M25 ISO Exd/Exia.
Up to 4 x 1/2" or 3/4" NPT UL
Terminals:
Will accept up to 2·5mm2 cable.
Resistor Values:
470R minimum (d.c. & I.S. units only).
Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box.
Unit
Model
Material
Certification
Entries
Duty Label
Tag Label
Options
Finish
Options
Code
Not required
N
LED
A
Resistor Series G*
Resistor EOL
H*
Diode
D*
3 Pole
T
c/o Switch
4 Pole
F
c/o Switch
Other
O*
Finish
Code
Red
R
Blue
B
Yellow
Y
Yellow/
X
Black Stripes
Special
S*
SM87
*Model
Code
Breakglass Latching
BGL
Lift Flap Breakglass Latching
LBGL
Push Button Latching key reset PBL
Push Button Only
PBM
Momentary Action
* UL version only available in PBL model.
*Material
Code
Stainless Steel S
Alloy
A
* UL version only available
in Alloy.
Certification
Exia
Exd
IECEx Exi
IECEx Exd
UL
CSA – Exi
CSA – Exd
GOST ‘K’ – Exi
GOST ‘R’ Exi
GOST ‘R’ Exd
Chinese Exi
Chinese Exd
Inmetro Exi
Inmetro Exd
Code
I
D
IJ
DJ
UL
IC
DC
IK
IG*
DG*
IQ†
DQ†
IM
DM
* Russian Fire Approval as standard.
† Not suitable for use in China on
fire alarm systems
Entries
M20
M25
1/2" NPT
3/4" NPT
Other
Code
1
2
3
4
5
Position
Top
Bottom
RHS
LHS
*T
*B
*R
*L
* Prefix position with size code
i.e. 1T 1B = 20mm Top and
Bottom.
Duty Label Code
Fire-Breakglass 1
Push Button
2
Fire-Push Button 3
ESDO-Abandon 4
Other
O*
None
N
* Please specify
* Please specify
* Please specify
Label
Code
Required
Y*
Not Required
N
* Please specify
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12
Download