4#2/0+1#6GRD., IN 2"C. PULLBOX ELECTRIC CLOSET 522-2 M.E.R. 526 4#2/0+1#6GRD., IN 2"C. 3 (E) PANEL(E) PANEL 5.0022. 5.0023. PNL.03.ANPNL.03.AN PANEL 5.0051. PNL.03.AN ROOM 534A PANEL PANEL 5.0044. 5.0043. PNL.04.ANPNL.04.AN 1 4#4/0+1#4GRD., IN 2-1/2"C. 4#3+1#8GRD., IN 1-1/4"C. ELECTRIC CLOSET 534-3 EX (E) 5.0006. (E) 5.0005. BKR.04.A.N BKR.04.A.N 100AT/ 225AT/ 3P/100AF 3P/225AF POWER RISER DIAGRAM EX 2 ELECTRIC CLOSET 531-2 EX (E) PANEL 5.0008.PNL.04.AN 3 NOTES NOTES: ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST." OR "(E)". VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION. PROVIDE A 225A FRAME, 3 POLE, 175A TRIP MOLDED CASE CIRCUIT BREAKER IN AVAILABLE SPACE IN EXISTING SQUARE-D TYPE PANEL 5.0023.PNL.03.A.N TO SERVE PANEL 5.0051.PNL.03.A.N. 5TH FLOOR NOT TO SCALE EQUIPMENT NAME A5-3-SF-A A5-3-SF-B A5-3-RF-A EF-534A-2 (MAT ROOM) EF-534A-1 (BREAK RM) CIRCULATING PUMP FPT-1 FPT-2 FPT-3 FPT-4 100/50/10 A5-3-RF-A (1-1/2HP) 100/25/10 MECH. CONTROLS CIRCUIT ROOM 526 - LIGHTING ROOM 526 - RECEPTACLES SPARE SPARE SPARE SPACE SPACE SPACE 2 3 4 7 8 5 6 9 10 100/20/10 13 14 100/20/10 17 100/20/10 100/20/10 100/20/10 100/20/10 100/--/-100/--/-100/--/-- 11 15 19 21 23 25 27 29 12 100/50/10 100/20/10 KILOWATTS HORSE POWER ----0.1 ------ 7-1/2 7-1/2 1-1/2 1/4 -1/4 1/6 1/4 1/4 1/3 05502E601.DWG 055.02 RENOVATE ROOM 534A E1 SPARE (FUTURE A5-3-RF-B) CIRCULATING PUMP 100/20/10 16 SPARE 100/20/10 18 SPARE 100/20/10 20 SPARE 100/20/10 22 SPARE 100/20/10 24 SPARE 26 100/--/-- SPACE 28 100/--/-- SPACE 30 100/--/-- SPACE MOTOR STARTER NEMA AUX. CONTACTS LOCAL TYPE SIZE N.O. N.C. CONTROL NO. VARIABLE FREQUENCY DRIVE 3 VARIABLE FREQUENCY DRIVE 3 VARIABLE FREQUENCY DRIVE 3 2 THERMAL MOTOR SWITCH THERMAL MOTOR SWITCH 2 THERMAL MOTOR SWITCH 2 THERMAL MOTOR SWITCH 2 2 THERMAL MOTOR SWITCH THERMAL MOTOR SWITCH 2 THERMAL MOTOR SWITCH 2 FEEDER WIRE CONDUIT SIZE GRD. #8 #8 3/4" #8 #8 3/4" 3/4" #10 #10 3/4" #12 #12 3/4" #12 #12 3/4" #12 #12 #12 #12 3/4" #12 #12 3/4" #12 #12 3/4" #12 #12 3/4" PANELBOARD NAME ABBREVIATIONS FULL NAME 5.0043.PNL.04.AN 5.0044.PNL.04.AN 5.0051.PNL.03.A.N FILE NAME: OUR REF: PROJECT: FACTOR: A5-3-SF-B (7.5HP) 100/20/10 MOTOR AND EQUIPMENT SCHEDULE SAFETY SWITCH FULL VOLTAGE PHASE LOAD FUSE FRAME AMPERES SIZE POLES SIZE -200 3Ø 25.3 60A 3 -200 3Ø 25.3 60A 3 -200 3Ø 11.5 30A 3 115 1Ø 5.8 115 1Ø 0.8 115 1Ø 5.8 115 1Ø 4.4 115 1Ø 5.8 115 1Ø 5.8 115 1Ø 7.2 DESCRIPTION ABBREVIATED NAME 43 44 51 DESCRIPTION CIRCUIT BREAKER FRAME/TRIP/KAIC LIGHTING - SUPR. RM 1&2, CONF 100/20/10 100/20/10 LIGHTING - OPEN OFFICE 100/20/10 LIGHTING - OPEN OFFICE LIGHTING - MAT,BREAK,CLASSROOM100/20/10 100/20/10 RECEPTACLE - LASER PRINTER RECEPT. - SUPERVISOR ROOM 1 100/20/10 100/20/10 RECEPT. - CONFERENCE ROOM RECEPT. - SUPERVISOR ROOM 2 100/20/10 100/20/10 A/V EQUIPMENT - CONF. ROOM 100/20/10 RECEPTACLE - OPEN OFFICE 100/20/10 RECEPTACLE - CLASSROOM 100/20/10 RECEPTACLE - MAT ROOM 100/20/10 RECEPTACLE - PANTRY 100/20/10 FPT-VAVs 100/20/10 FPT-VAVs 100/20/10 FPT-VAVs 100/20/10 EF-534A-1 (BREAK ROOM) 100/20/10 EF-534A-2 (MAT ROOM) 100/--/-SPACE 100/--/-SPACE 100/--/-SPACE 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 MOUNTING: SURFACE LOCATION: ROOM 534A ENCLOSURE: NEMA 1 CIRCUIT BREAKER FRAME/TRIP/KAIC DESCRIPTION SYSTEMS FURNITURE 100/20/10 4 SYSTEMS FURNITURE 100/20/10 6 SYSTEMS FURNITURE 100/20/10 8 SYSTEMS FURNITURE 100/20/10 10 SYSTEMS FURNITURE 100/20/10 12 SYSTEMS FURNITURE 100/20/10 14 SYSTEMS FURNITURE 100/20/10 16 SYSTEMS FURNITURE 100/20/10 18 RECEPTACLE - COPIER 100/20/10 20 RECEPTACLE - FAX 100/20/10 22 RECEPTACLE - COPIER 100/20/10 24 RECEPTACLE - FAX 100/20/10 26 RECEPTACLE - COPIER 100/20/10 28 RECEPTACLE - SMALL APPLIANCE 100/20/10 30 RECEPTACLE - SMALL APPLIANCE 100/20/10 32 RECEPTACLE - MICROWAVE 100/20/10 34 RECEPTACLE - REFRIGERATOR 100/20/10 36 VAV BOXES 38 100/--/-- SPACE 40 100/--/-- SPACE 42 100/--/-- SPACE 2 100/20/10 DISCLAIMER: THE SYSTEMS AND EQUIPMENT DEPICTED ON THIS DRAWING ARE BASED ON VISUAL SURVEY OF EXISTING CONDITIONS. WHERE SYSTEMS & EQUIPMENT ARE CONCEALED BY WALLS, CEILINGS, BUILDING STRUCTURE AND THE LIKE; SELECTIVE DEMOLITION MAY BE REQUIRED TO FURTHER VERIFY SYSTEM ROUTING AND SIZES IN THESE LOCATIONS. NOTICE: THIS DOCUMENT IS AND SHALL REMAIN THE PROPERTY OF THE UNITED STATES GOVERNMENT. NO INFORMATION CONTAINED HEREIN MAY BE COPIED, DISCLOSED, OR USED FOR ANY PURPOSE WITHOUT THE WRITTEN AUTHORIZATION OF THE BUREAU OF ENGRAVING AND PRINTING. SUMMER CONSULTANTS, INC. 6845 Elm Street, Suite 200 McLean, VA. 22101 GRAPHIC SCALES: CAUTION: IF THIS DRAWING IS A REDUCTION GRAPHIC SCALES MUST BE USED. KEY PLAN: C STREET D STREET ANNEX BUILDING PANEL 5.0043.PNL.04.AN SCHEDULE 120/208 VOLTS, 3Ø, 4W 100A MAIN LUGS ONLY, 10 KAIC BOLT-ON BRANCH CIRCUIT BREAKERS DESCRIPTION A/V EQUIPMENT - CLASSROOM SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPACE SPACE SPACE SPACE SPACE SPACE CIRCUIT BREAKER FRAME/TRIP/KAIC 100/20/10 1 MOUNTING: SURFACE LOCATION: ROOM 534A ENCLOSURE: NEMA 1 CIRCUIT BREAKER FRAME/TRIP/KAIC 2 100/20/10 6 100/20/10 100/20/10 3 4 100/20/10 7 8 100/20/10 100/20/10 5 9 10 100/20/10 13 14 100/20/10 17 18 21 22 100/20/10 100/20/10 100/--/-100/--/-100/--/-100/--/-100/--/-100/--/-- 11 15 19 23 25 27 29 12 16 100/20/10 100/20/10 100/20/10 100/20/10 100/20/10 100/20/10 100/20/10 20 100/--/-- 24 100/--/-- 26 28 30 100/--/-100/--/-100/--/-- 100/--/-- SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPACE SPACE SPACE SPACE SPACE SPACE SEAL: OFFICE SIGNATURE DATE DATE A5-3-SF-A (7.5HP) 1 CIRCUIT BREAKER FRAME/TRIP/KAIC 120/208 VOLTS, 3Ø, 4W 225A MAIN LUGS ONLY, 10 KAIC BOLT-ON BRANCH CIRCUIT BREAKERS DESCRIPTION REVISION NUMBER REMARKS APPROVAL DATE DEPARTMENT OF THE TREASURY BUREAU OF ENGRAVING AND PRINTING RENOVATION OF ROOM 534A POWER RISER DIAGRAM & SCHEDULES ELECTRICAL DRAWN BY: PHAN BOLT CHECKED BY: DATE OF ISSUE: SHEET: SCALE: DATE: DATE: FINAL SUBMISSION SEPTEMBER 12, 2007 27 OF: AS NOTED 27 1000397 DWG. NO. E-601 THIS DOCUMENT IS AND SHALL REMAIN THE PROPERTY OF THE UNITED STATES GOVERNMENT. NO INFORMATION CONTAINED HEREIN MAY BE COPIED, DISCLOSED, OR USED FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN AUTHORIZATION OF THE BUREAU OF ENGRAVING AND PRINTING. THE ORIGINAL SIGNATURE TO THE RIGHT INDICATES THAT THIS DOCUMENT HAS BEEN REVIEWED AND APPROVED BY THE OFFICE OF SECURITY FOR THE PURPOSE OF ALLOWING THIS DOCUMENT OUTSIDE THE CONFINES OF THE BUREAU OF ENGRAVING AND PRINTING FACILITIES. SIGNATURE CIRCUIT BREAKER FRAME/TRIP/KAIC DESCRIPTION MOUNTING: SURFACE LOCATION: ROOM 522 ENCLOSURE: NEMA 1 13TH STREET 120/208 VOLTS, 3Ø, 4W 225A MAIN LUGS ONLY, 25 KAIC BOLT-ON BRANCH CIRCUIT BREAKERS PANEL 5.0044.PNL.04.AN SCHEDULE 14TH STREET PANEL 5.0051.PNL.03.A.N SCHEDULE