POWER RISER DIAGRAM NOTES MOTOR AND EQUIPMENT

advertisement
4#2/0+1#6GRD., IN 2"C.
PULLBOX
ELECTRIC CLOSET 522-2
M.E.R. 526
4#2/0+1#6GRD., IN 2"C.
3
(E) PANEL(E) PANEL
5.0022. 5.0023.
PNL.03.ANPNL.03.AN
PANEL
5.0051.
PNL.03.AN
ROOM 534A
PANEL
PANEL
5.0044. 5.0043.
PNL.04.ANPNL.04.AN
1
4#4/0+1#4GRD., IN 2-1/2"C.
4#3+1#8GRD., IN 1-1/4"C.
ELECTRIC CLOSET 534-3
EX
(E) 5.0006. (E) 5.0005.
BKR.04.A.N BKR.04.A.N
100AT/
225AT/
3P/100AF 3P/225AF
POWER RISER DIAGRAM
EX
2
ELECTRIC CLOSET 531-2
EX
(E) PANEL
5.0008.PNL.04.AN
3
NOTES
NOTES:
ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST." OR "(E)".
VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND COORDINATE ALL
WORK PRIOR TO THE START OF CONSTRUCTION.
PROVIDE A 225A FRAME, 3 POLE, 175A TRIP MOLDED CASE CIRCUIT BREAKER IN
AVAILABLE SPACE IN EXISTING SQUARE-D TYPE PANEL 5.0023.PNL.03.A.N TO SERVE
PANEL 5.0051.PNL.03.A.N.
5TH FLOOR
NOT TO SCALE
EQUIPMENT NAME
A5-3-SF-A
A5-3-SF-B
A5-3-RF-A
EF-534A-2 (MAT ROOM)
EF-534A-1 (BREAK RM)
CIRCULATING PUMP
FPT-1
FPT-2
FPT-3
FPT-4
100/50/10
A5-3-RF-A (1-1/2HP)
100/25/10
MECH. CONTROLS CIRCUIT
ROOM 526 - LIGHTING
ROOM 526 - RECEPTACLES
SPARE
SPARE
SPARE
SPACE
SPACE
SPACE
2
3
4
7
8
5
6
9
10
100/20/10
13
14
100/20/10
17
100/20/10
100/20/10
100/20/10
100/20/10
100/--/-100/--/-100/--/--
11
15
19
21
23
25
27
29
12
100/50/10
100/20/10
KILOWATTS HORSE
POWER
----0.1
------
7-1/2
7-1/2
1-1/2
1/4
-1/4
1/6
1/4
1/4
1/3
05502E601.DWG
055.02
RENOVATE ROOM 534A
E1
SPARE (FUTURE A5-3-RF-B)
CIRCULATING PUMP
100/20/10
16
SPARE
100/20/10
18
SPARE
100/20/10
20
SPARE
100/20/10
22
SPARE
100/20/10
24
SPARE
26 100/--/-- SPACE
28 100/--/-- SPACE
30 100/--/-- SPACE
MOTOR STARTER
NEMA AUX. CONTACTS LOCAL
TYPE
SIZE
N.O.
N.C. CONTROL NO.
VARIABLE FREQUENCY DRIVE
3
VARIABLE FREQUENCY DRIVE
3
VARIABLE FREQUENCY DRIVE
3
2
THERMAL MOTOR SWITCH
THERMAL MOTOR SWITCH
2
THERMAL MOTOR SWITCH
2
THERMAL MOTOR SWITCH
2
2
THERMAL MOTOR SWITCH
THERMAL MOTOR SWITCH
2
THERMAL MOTOR SWITCH
2
FEEDER
WIRE
CONDUIT
SIZE GRD.
#8
#8
3/4"
#8
#8
3/4"
3/4"
#10 #10
3/4"
#12 #12
3/4"
#12 #12
3/4"
#12 #12
#12 #12
3/4"
#12 #12
3/4"
#12 #12
3/4"
#12 #12
3/4"
PANELBOARD NAME ABBREVIATIONS
FULL NAME
5.0043.PNL.04.AN
5.0044.PNL.04.AN
5.0051.PNL.03.A.N
FILE NAME:
OUR REF:
PROJECT:
FACTOR:
A5-3-SF-B (7.5HP)
100/20/10
MOTOR AND EQUIPMENT SCHEDULE
SAFETY SWITCH
FULL
VOLTAGE PHASE LOAD
FUSE
FRAME
AMPERES SIZE POLES SIZE
-200
3Ø
25.3
60A
3
-200
3Ø
25.3
60A
3
-200
3Ø
11.5
30A
3
115
1Ø
5.8
115
1Ø
0.8
115
1Ø
5.8
115
1Ø
4.4
115
1Ø
5.8
115
1Ø
5.8
115
1Ø
7.2
DESCRIPTION
ABBREVIATED NAME
43
44
51
DESCRIPTION
CIRCUIT BREAKER
FRAME/TRIP/KAIC
LIGHTING - SUPR. RM 1&2, CONF 100/20/10
100/20/10
LIGHTING - OPEN OFFICE
100/20/10
LIGHTING - OPEN OFFICE
LIGHTING - MAT,BREAK,CLASSROOM100/20/10
100/20/10
RECEPTACLE - LASER PRINTER
RECEPT. - SUPERVISOR ROOM 1 100/20/10
100/20/10
RECEPT. - CONFERENCE ROOM
RECEPT. - SUPERVISOR ROOM 2 100/20/10
100/20/10
A/V EQUIPMENT - CONF. ROOM
100/20/10
RECEPTACLE - OPEN OFFICE
100/20/10
RECEPTACLE - CLASSROOM
100/20/10
RECEPTACLE - MAT ROOM
100/20/10
RECEPTACLE - PANTRY
100/20/10
FPT-VAVs
100/20/10
FPT-VAVs
100/20/10
FPT-VAVs
100/20/10
EF-534A-1 (BREAK ROOM)
100/20/10
EF-534A-2 (MAT ROOM)
100/--/-SPACE
100/--/-SPACE
100/--/-SPACE
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
MOUNTING: SURFACE
LOCATION: ROOM 534A
ENCLOSURE: NEMA 1
CIRCUIT BREAKER
FRAME/TRIP/KAIC
DESCRIPTION
SYSTEMS FURNITURE
100/20/10
4
SYSTEMS FURNITURE
100/20/10
6
SYSTEMS FURNITURE
100/20/10
8
SYSTEMS FURNITURE
100/20/10
10
SYSTEMS FURNITURE
100/20/10
12
SYSTEMS FURNITURE
100/20/10
14
SYSTEMS FURNITURE
100/20/10
16
SYSTEMS FURNITURE
100/20/10
18
RECEPTACLE - COPIER
100/20/10
20
RECEPTACLE - FAX
100/20/10
22
RECEPTACLE - COPIER
100/20/10
24
RECEPTACLE - FAX
100/20/10
26
RECEPTACLE - COPIER
100/20/10
28
RECEPTACLE - SMALL APPLIANCE
100/20/10
30
RECEPTACLE - SMALL APPLIANCE
100/20/10
32
RECEPTACLE - MICROWAVE
100/20/10
34
RECEPTACLE - REFRIGERATOR
100/20/10
36
VAV BOXES
38 100/--/-- SPACE
40 100/--/-- SPACE
42 100/--/-- SPACE
2
100/20/10
DISCLAIMER: THE SYSTEMS AND EQUIPMENT DEPICTED ON
THIS DRAWING ARE BASED ON VISUAL SURVEY OF EXISTING
CONDITIONS. WHERE SYSTEMS & EQUIPMENT ARE CONCEALED
BY WALLS, CEILINGS, BUILDING STRUCTURE AND THE LIKE;
SELECTIVE DEMOLITION MAY BE REQUIRED TO FURTHER
VERIFY SYSTEM ROUTING AND SIZES IN THESE LOCATIONS.
NOTICE: THIS DOCUMENT IS AND SHALL REMAIN THE PROPERTY
OF THE UNITED STATES GOVERNMENT. NO INFORMATION
CONTAINED HEREIN MAY BE COPIED, DISCLOSED, OR USED FOR
ANY PURPOSE WITHOUT THE WRITTEN AUTHORIZATION OF THE
BUREAU OF ENGRAVING AND PRINTING.
SUMMER CONSULTANTS, INC.
6845 Elm Street, Suite 200
McLean, VA. 22101
GRAPHIC SCALES:
CAUTION: IF THIS DRAWING IS A REDUCTION GRAPHIC SCALES MUST BE USED.
KEY PLAN:
C STREET
D STREET
ANNEX BUILDING
PANEL 5.0043.PNL.04.AN SCHEDULE
120/208 VOLTS, 3Ø, 4W
100A MAIN LUGS ONLY, 10 KAIC
BOLT-ON BRANCH CIRCUIT BREAKERS
DESCRIPTION
A/V EQUIPMENT - CLASSROOM
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
CIRCUIT BREAKER
FRAME/TRIP/KAIC
100/20/10
1
MOUNTING: SURFACE
LOCATION: ROOM 534A
ENCLOSURE: NEMA 1
CIRCUIT BREAKER
FRAME/TRIP/KAIC
2
100/20/10
6
100/20/10
100/20/10
3
4
100/20/10
7
8
100/20/10
100/20/10
5
9
10
100/20/10
13
14
100/20/10
17
18
21
22
100/20/10
100/20/10
100/--/-100/--/-100/--/-100/--/-100/--/-100/--/--
11
15
19
23
25
27
29
12
16
100/20/10
100/20/10
100/20/10
100/20/10
100/20/10
100/20/10
100/20/10
20
100/--/--
24
100/--/--
26
28
30
100/--/-100/--/-100/--/--
100/--/--
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SEAL:
OFFICE
SIGNATURE
DATE
DATE
A5-3-SF-A (7.5HP)
1
CIRCUIT BREAKER
FRAME/TRIP/KAIC
120/208 VOLTS, 3Ø, 4W
225A MAIN LUGS ONLY, 10 KAIC
BOLT-ON BRANCH CIRCUIT BREAKERS
DESCRIPTION
REVISION
NUMBER
REMARKS
APPROVAL
DATE
DEPARTMENT OF
THE TREASURY
BUREAU OF ENGRAVING
AND PRINTING
RENOVATION OF ROOM 534A
POWER RISER DIAGRAM & SCHEDULES
ELECTRICAL
DRAWN BY:
PHAN
BOLT
CHECKED BY:
DATE OF ISSUE:
SHEET:
SCALE:
DATE:
DATE:
FINAL SUBMISSION
SEPTEMBER 12, 2007
27
OF:
AS NOTED
27
1000397
DWG.
NO.
E-601
THIS DOCUMENT IS AND SHALL REMAIN THE PROPERTY OF THE UNITED STATES GOVERNMENT. NO INFORMATION CONTAINED HEREIN MAY BE COPIED, DISCLOSED, OR USED FOR ANY PURPOSE
WITHOUT THE EXPRESS WRITTEN AUTHORIZATION OF THE BUREAU OF ENGRAVING AND PRINTING. THE ORIGINAL SIGNATURE TO THE RIGHT INDICATES THAT THIS DOCUMENT HAS BEEN REVIEWED
AND APPROVED BY THE OFFICE OF SECURITY FOR THE PURPOSE OF ALLOWING THIS DOCUMENT OUTSIDE THE CONFINES OF THE BUREAU OF ENGRAVING AND PRINTING FACILITIES.
SIGNATURE
CIRCUIT BREAKER
FRAME/TRIP/KAIC
DESCRIPTION
MOUNTING: SURFACE
LOCATION: ROOM 522
ENCLOSURE: NEMA 1
13TH STREET
120/208 VOLTS, 3Ø, 4W
225A MAIN LUGS ONLY, 25 KAIC
BOLT-ON BRANCH CIRCUIT BREAKERS
PANEL 5.0044.PNL.04.AN SCHEDULE
14TH STREET
PANEL 5.0051.PNL.03.A.N SCHEDULE
Download