Installation and operating instruction Remote control station WP-FS 83279702 • 1/2013-08 Conformity certification Sprachschlüssel 5115000002 Manufacturer: Max Weishaupt GmbH Address: Max-Weishaupt-Straße D-88475 Schwendi Product: Remote control station WP-FS The product described above conforms with the regulations of directives: LVD EMC 2006 / 95 / EC 2004 / 108 / EC This product is labelled as follows: Schwendi, 27.06.2013 ppa. ppa. Dr. Schloen Denkinger Manager Research and Development Manager Production and Quality Management Installation and operating instruction Remote control station WP-FS 1 User instructions ..................................................................................................................... 1.1 User guide ............................................................................................................. 1.1.1 Symbols ................................................................................................................. 1.1.2 Target group ......................................................................................................... 1.2 Guarantee and Liability ....................................................................................... 4 4 4 4 5 2 Safety ............................................................................................................................................ 2.1 Permissible application ....................................................................................... 2.2 Safety measures .................................................................................................. 2.3 Electrical connection ........................................................................................... 2.4 Disposal ................................................................................................................. 6 6 6 6 6 3 Product description ............................................................................................................... 3.1 Type key ................................................................................................................. 3.2 Technical data ...................................................................................................... 3.2.1 Approval data ........................................................................................................ 3.2.2 Electrical data ....................................................................................................... 3.2.3 Ambient conditions .............................................................................................. 7 7 7 7 7 7 4 Installation .................................................................................................................................. 8 5 Electrical installation ........................................................................................................... 10 6 Operation .................................................................................................................................. 11 6.1 Operating interface .......................................................................................... 11 6.1.1 Operating panel ................................................................................................ 11 6.1.2 Display ................................................................................................................. 12 6.2 Displaying and adjusting parameters ........................................................... 14 6.3 Parameters ......................................................................................................... 16 6.3.1 End user level .................................................................................................... 16 6.3.2 Heating engineer level ..................................................................................... 19 6.4 Select preset characteristic curves .............................................................. 26 6.5 Setting characteristic curves individually .................................................... 27 7 Commissioning ...................................................................................................................... 28 7.1 Prerequisite ........................................................................................................ 28 7.2 Steps for commissioning ................................................................................ 29 7.3 Priority function ................................................................................................. 30 8 Troubleshooting .................................................................................................................... 31 8.1 Procedures for fault conditions ..................................................................... 31 8.2 Rectifying faults ................................................................................................. 33 8.2.1 Fault codes ......................................................................................................... 33 9 Notes ........................................................................................................................................... 36 10 Key word index ...................................................................................................................... 37 83279702 • 1/2013-08 • La 3-38 Installation and operating instruction Remote control station WP-FS 1 User instructions 1 User instructions This installation and operating manual forms part of the appliance and must be kept on site. 1.1 User guide 1.1.1 Symbols Immediate danger with high risk. Non observance can lead to serious injury or death. DANGER Danger with medium risk. Non observance can lead to environmental damage, serious injury or death. WARNING Danger with low risk. Non observance can cause damage to the equipment and injury to personnel. CAUTION Important information Requires direct action Result after an action Itemisation Range of values 1.1.2 Target group These installation and operating instructions are intended for the operator and qualified personnel. They should be observed by all personnel working on the unit. Work on the unit must only be carried out by personnel who have the relevant training and instruction. Persons with limited physical, sensory or mental capabilities may only work on the unit if they are supervised or have been trained by an authorised person. Children must not play near or on the unit. 83279702 • 1/2013-08 • La 4-38 Installation and operating instruction Remote control station WP-FS 1 User instructions 1.2 Guarantee and Liability Guarantee and liability claims for personal and equipment damage are excluded, if they can be attributed to one or more of the following causes: ▪ Non approved application of the unit, ▪ non-observance of the Installation and operating instruction, ▪ continual operation despite a fault, ▪ repairs, which have been carried out incorrectly, ▪ the use of non original Weishaupt parts, ▪ acts of God. 83279702 • 1/2013-08 • La 5-38 Installation and operating instruction Remote control station WP-FS 2 Safety 2 Safety 2.1 Permissible application The remote control station WP-FS is suitable for the operation of a Split heat pump. 2.2 Safety measures Safety relevant fault conditions must be eliminated immediately. 2.3 Electrical connection For work carried out on live parts: ▪ Observe the accident prevention instructions BGV A3 and adhere to local directives, ▪ tools in accordance with EN 60900 should be used. 2.4 Disposal Dispose of all materials used in a safe and environmentally friendly way. Observe local regulations. 83279702 • 1/2013-08 • La 6-38 Installation and operating instruction Remote control station WP-FS 3 Product description 3 Product description 3.1 Type key WP -FS Series: Heat pump Model: Remote control station 3.2 Technical data 3.2.1 Approval data EHPA, Germany EHPA, Switzerland DE-HP-00386 CH-HP-00407 Basic standards EN 60730-1 EN 60730-2 EN 60335-1 3.2.2 Electrical data Protection Class, to EN 60730 II 3.2.3 Ambient conditions Temperature in operation Temperature during transport / storage relative humidity 83279702 • 1/2013-08 • La 7-38 0 … +50 °C -25 … +70 °C max 80 %, no dew point Installation and operating instruction Remote control station WP-FS 4 Installation 4 Installation Installing the WP-FS in the hydraulic unit ▶ Open flap. ▶ Clip remote control station into mounting slot. 83279702 • 1/2013-08 • La 8-38 Installation and operating instruction Remote control station WP-FS 4 Installation Fitting the wall bracket A room sensor is integrated into the remote control station. ▶ Place the remote control station in such a way that the room sensor is not influenced by: ▪ additional temperature control in the same room (radiator thermostats), ▪ other heat sources (e.g. direct sun light, chimney etc.), ▪ cooling sources (e. g. if mounted to a cold external wall). ▶ Fix wall bracket to wall. ▶ Connect wiring (see Ch. 5). ▶ Clip remote control unit into the wall bracket. 83279702 • 1/2013-08 • La 9-38 Installation and operating instruction Remote control station WP-FS 5 Electrical installation 5 Electrical installation The electrical installation must only be carried out by qualified electricians. Observe local regulations. ▶ Connect electrical cable to eBUS terminal 1 and 2. ▶ An external room sensor can be fitted to terminals 5 and 6 if required (accessory). Cable cross section 1.5 mm² 0.5 mm² Connection for WP-FS in wall bracket ▶ Connect eBUS in the hydraulic unit: ▪ Terminal 16 to eBUS▪ Terminal 17 an eBUS+ 83279702 • 1/2013-08 • La 10-38 Length max 1260 m max 420 m Installation and operating instruction Remote control station WP-FS 6 Operation 6 Operation 6.1 Operating interface 6.1.1 Operating panel 1 Dial knob 2 Function keys 1 … 4 3 Key not used 4 Menu key 83279702 • 1/2013-08 • La 11-38 Navigation through levels and parameters, change values, switch on illumination. Used to activate functions. Used to activate or exit user level. Installation and operating instruction Remote control station WP-FS 6 Operation 6.1.2 Display Standard display When the display is switched on, the standard display appears. The parameters show the factory setting. Tues 24.Apr 12 HC 12 Room temp 11:24 24 i 26.1°C Heating program 1 1 2 3 4 5 6 Week day, date, time Symbol DHW operation Information Current room temperature Type of operation with symbol Timer program bar Display information The Info menu can only be called up from the standard display. ▶ Press i key. ✓ First information Status HP is displayed. ▶ Press i key. ✓ Next information Status DHW is displayed. Info menu Status HP Frequency Status DHW External TO DHW Temp Flow temp 83279702 • 1/2013-08 • La Explanation Current operating mode of heat pump: heating, cooling or Off Current compressor frequency outdoor unit DHW status: Normal operation = DHW flange heating released Setback operation = DHW flange heating blocked External temperature DHW temperature Flow temperature 12-38 Installation and operating instruction Remote control station WP-FS 6 Operation Symbols for type of operation Heating or DHW operation Cooling or DHW operation Night setback operation Summer (DHW operation only) Standby Lockout display ▶ Note down display and determine fault using Troubleshooting (see Ch. 8.1). 83279702 • 1/2013-08 • La 13-38 Installation and operating instruction Remote control station WP-FS 6 Operation 6.2 Displaying and adjusting parameters Activate level End user level Heating engineer level In the standard display ▶ Briefly press menu key . ▶ Press and hold menu key onds. for 3 sec- In the menu ▶ Press function key End repeatedly – or – briefly press menu key . ✓ Standard display appears again. ▶ Briefly press menu key for 3 seconds. ▶ Press and hold menu key Engineer User 01 End 01 Commissioning Settings Control behaviour Holiday Heating reference line 1 Page number 2 Level 3 Function key for menu selection Display further pages ▶ Turn dial knob. ✓ Further pages of the menu are displayed. User End 01 Remote control Settings Holiday User 02 Ende End Heat pump Time-Date Time programme Select menu ▶ Select menu and press the relevant function key. ✓ Menu is displayed. User End 01 Remote control Settings Holiday Remote control 01 End Room sensor corr Contrast Illumination 83279702 • 1/2013-08 • La End Remote control 14-38 0.1 K 04 30 Installation and operating instruction Remote control station WP-FS 6 Operation Select and set parameter ▶ Select parameter and press the relevant function key. ✓ Parameter is displayed. ▶ Make a selection using the dial knob and save setting with function key OK. Remote control 01 End Room sensor corr 0.1 K Contrast Illumination 04 30 Contrast 102 End 06 Standard 00 - 06 OK Reset parameter to factory settings ▶ Press function key Standard. ✓ Factory setting is displayed. ▶ Press function key OK. ✓ Factory setting is saved. Contrast 102 End 04 Standard 00 - 06 OK Return to the previous menu / level ▶ Press function key End repeatedly – or – briefly press menu key ✓ Standard display appears 83279702 • 1/2013-08 • La 15-38 . Installation and operating instruction Remote control station WP-FS 6 Operation 6.3 Parameters 6.3.1 End user level End user level Menu point Description Remote control Room sensor Corr Contrast Brightness Settings Parameters 101 Function / Selection / Factory setting Room sensor correction 102 Setting range: -5.0 … 5.0 K Factory setting: 0 Set display contrast 103 Setting range: 00 … 06 Factory setting: 04 Adjust brightness of display Setting range: 00 … 30 Factory setting: 30 The setting of parameters 112 … 115 has an effect on the flow temperature. The flow temperature setpoint is adjusted by the values of parameters 117 … 119 relative to the difference between the flow temperature setpoint and the actual flow temperature. 112(1 Roomset heat Room temperature setpoint in heating operation Setback room heat Roomset cool Setback room cool 113(1 114(1 115(1 Setting range: 16 … 35 °C Factory setting: 21.5 °C Setback room temperature setpoint in heating operation (e. g. at night). A time period for this can be set in parameter 160. Setting range: 4 … 21.5 °C Factory setting: 16 °C Room temperature setpoint in cooling operation. Setting range: 18 … 28 °C Factory setting: 24 °C Setback room temperature setpoint in cooling operation. A time period for this can be set in parameter 160. Setting range: 24 … 40 °C Factory setting: 28 °C The setting of parameters 117 … 119 has an effect on parameters 112 … 115. +/- VL HC 1 heat 117 +/- Flow heating circuit 1 heating Adjustment of flow temperature in heating circuit 1 (heating) if there is a deviation between the setpoint temperature and the actual temperature. +/- VL HC 1 cool 119 Setting range: -5 … 5 °C Factory setting: 0 °C +/- Flow heating circuit 1 cooling Adjustment of flow temperature in heating circuit 1 (cooling) if there is a deviation between the setpoint temperature and the actual temperature. Setting range: -5 … 5 °C Factory setting: 0 °C (1 Parameter is effective only when Room influence HC = FS is set in parameter 315 in the heating engineer level. 83279702 • 1/2013-08 • La 16-38 Installation and operating instruction Remote control station WP-FS 6 Operation End user level Menu point Description Settings DHW Setpoint temp Holiday Parameters 132 Pump HC 1 134(1 from 24. Oct 12 to 24. Oct 12 141 Function / Selection / Factory setting Domestic hot water temperature setpoint Effective in all operating modes except in Standby and setback. Prerequisite: DHW sensor B3 is connected. Setting range: 40 … 65 °C Factory setting: 45 °C Operating mode pump heating circuit 1 Selection: Off at roomset = Pump switches off, when room temperature setpoint is reached, or Continuous run. Factory setting: Continuous run Current date is displayed. ▶ Using the [<==] key, go to day, month, year and enter the period of absence. Heat pump HP capacity 2. heat exchanger Time-Date 143 144 2. FS during fault conditions 145 Date 151 Time 152 Summertime start 153 Summertime end 154 Frost protection remains active during the period of absence. To decrease the noise level of the outdoor unit, its compressor frequency can be reduced. The more the frequency and therefore also the capacity is reduced, the quieter the outdoor unit operates. This parameter is only effective, if parameter 164 Hibernation mode is activated. Setting range: 50 … 99 % or Off Factory setting: Off Electric heating can be connected. Selection: active or inactive. Factory setting: active Operation with 2. heat exchanger (electric heating) if heat pump fails. Selection: Yes or No. Factory setting: No ▶ Using the [<==] key go to day, month, year and change the date. ▶ Using the [<==] key, change from hours to minutes and set the time. ▶ Using the [<==] key, change from day to month and set the start of Summertime. Factory setting: 25. March ▶ Using the [<==] key, change from day to month and set the end of Summertime. Factory setting: 25. October Parameter is effective only when Room influence HC = FS is set in parameter 315 in the heating engineer level. (1 83279702 • 1/2013-08 • La 17-38 Installation and operating instruction Remote control station WP-FS 6 Operation End user level Menu point Description Time programs Time program 1 Parameters 160(1 Time program 2 161 Time program 3 162(1 (1 Function / Selection / Factory setting It is possible to set 3 different blocks of time per day. In these blocks of time the heating / cooling runs in daytime operation. ▶ Turn dial knob and set weekday. ▶ Use the [<==] key to change from time start to time end and set the time. DHW 163 Factory setting: Time program 1 (6.00 … 22.00 hrs.) Time program 2 (6.00 … 8.00 hrs. and 16.00 … 22.00 hrs.) Time program 3 (6.00 … 8.00 hrs. and 12.00 … 22.00 hrs.) It is possible to set 3 different blocks of time per day. The DHW setpoint is not affected by this. Here, the time slot is set in which the flange heating is released to achieve the setpoint value. If the DHW temperature drops below the DHW setpoint (hysteresis 2K), the flange heating is activated immediately. ▶ Turn the dial knob and set the weekday. ▶ Use the [<==] key to change from time start to time end and set the time. Hibernation mode 164 Factory setting: -- … -- hrs. It is possible to set 3 different blocks of time per day. In these blocks of time, parameter 143 acts as maximum capacity. ▶ Turn dial knob and set weekday. ▶ Use the [<==] key to change from time start to time end and set the time. Parameter is effective only when Room influence HC = FS is set in parameter 315 in the heating engineer level. (1 83279702 • 1/2013-08 • La 18-38 Installation and operating instruction Remote control station WP-FS 6 Operation 6.3.2 Heating engineer level Heating engineer level Menu point Commissioning Description Language Parameters 311 Number of heating circuits 312 Output test 403 Function / Selection / Factory setting Selection: Deutsch, Français, Italiano, English, Nederlands, Dansk Factory setting: Deutsch Selection: 1 or 2 heating circuits. Factory setting: 1 heating circuit Control output selection: Off HC pump = Heating circuit pump E Heating 1 = Electric heating stage 1 E Heating 2 = only with WWP L 11 AERS: Electric heating stage 2 DHW flange heat = DHW flange heating DHW pump = DHW feed pump Fault output = Fault output terminal 7 Factory setting: Off ▶ Select control output. ✓ Output selected is activated. ✓ Operating mode changes to Standby, until a restart is performed. ▶ Use protection provided on site to isolate the outdoor unit/system from the mains supply. ▶ Reconnect voltage. ✓ Restart is performed. DHW control System frost protect Speed pump HC External flow 404 426 429 451 Heating circuit 1 452 Selection heat/cool 453 Selection of which system influences the DHW control: System = Sensor on hydraulic unit. DHW preparation can be blocked via the DHW thermostat input (see wiring diagram for hydraulic unit). Contact closed: No DHW preparation. ext. thermostat = Thermostat in water heater. Contact closed: DHW supply. Factory setting: External thermostat System frost protection: Reacts immediately when Condens temp (Parameter 482) or Supply temp (Parameter 483) or DHW temp (Parameter 484) drops below the value set here. Setting range: 4 … 10 °C Factory setting: 4 °C Speed of the heating circuit pump Factory setting: 0 … 100 % Factory setting: 80% Selection: Permitted or Not permitted. Heating water flow is permitted or not permitted when the pump is switched off. Factory setting: Permitted Selection: Mixer or Pump. Factory setting: Pump Selection: WP-FS or External contact. Switching between heating/cooling, with remote control station or via external contact. Factory setting: WP-FS 83279702 • 1/2013-08 • La 19-38 Installation and operating instruction Remote control station WP-FS 6 Operation Heating engineer level Menu point Commissioning Description Manual operation Parameters 489 Function / Selection / Factory setting Selection: Off Heating max freq = Heating at maximum frequency / rating Cooling max freq = Cooling at maximum frequency / rating Rating heating = Heating at partial load Rating cooling = Cooling at partial load Draining = Refrigerant is pumped into the outdoor unit (see installation and operating manual of hydraulic unit, Chapter Shutdown). Factory setting: Off Using parameters 503 … 504, it can be determined whether DHW preparation or heating / cooling takes priority (see Ch. 7.3). Room Prio 0.5 503 Heating operation: Room setpoint - Value Room Prio 0.5 = Room priority 0.5. Cooling operation: Room setpoint + Value Room Prio 0.5 = Room priority 0.5. The lower the setting value, the higher the priority. Room Prio 1.0 503 Setting range: 1 … 5 °C Factory setting: 1 °C Heating operation: Room setpoint - Value Room Prio 0.5 - Value Room Prio 1.0 = Room priority 1.0. Cooling operation: Room setpoint + Value Room Prio 0.5 + Value Room Prio 1.0 = Room priority 1.0. The lower the setting value, the higher the priority. DHW Prio 0.5 504 Setting range: 1 … 5 °C Factory setting: 1 °C If the DHW temperature is the same as parameter 132 - Value DHW Prio 0.5 = DHW priority 0.5. The lower the setting value, the higher the priority. DHW Prio 1.0 504 Setting range: 1 … 15 °C Factory setting: 5 °C DHW setpoint temperature - Value DHW Prio 0.5 - Value DHW Prio 1.0 = DHW priority 1.0. The lower the setting value, the higher the priority. Setting range: 1 … 15 °C Factory setting: 5 °C 83279702 • 1/2013-08 • La 20-38 Installation and operating instruction Remote control station WP-FS 6 Operation Heating engineer level Menu point Control behaviour PaFunction / Selection / Factory setting rameters Using parameters 313 … 314, the flow setpoint temperature can be matched to the external temperature: Heating character313 Heating characteristic curve for heating circuit 1 istic curve HC1 Selection: 0 = Manually set heating characteristic curve in menu point Heating characteristic curve (Parameter 317 … 322) is active 01 … 06 = Select preset characteristic curve (see Ch. 6.4) Description Heating characteristic curve HC2 Cooling characteristic curve HC1 313 314 Cooling characteristic curve HC2 314 Room factor HC 315 Factory setting: 0 Heating characteristic curve for heating circuit 2 Selection: 0 = Manually set heating characteristic curve in menu point Heating characteristic curve (Parameter 317 … 322) is active 01 … 06 = Select preset characteristic curve (see Ch. 6.4) Factory setting: 0 Cooling characteristic curve for heating circuit 1 Selection: 0 = Manually set heating characteristic curve in menu point Cooling characteristic curve (Parameter 323 … 328) is active 01 … 02 = Select preset characteristic curve (see Ch. 6.4) Factory setting: 00 Cooling characteristic curve for heating circuit 2 Selection: 0 = Manually set heating characteristic curve in menu point Cooling characteristic curve (Parameter 323 … 328) is active 01 … 02 = Select preset reference line (see Ch. 6.4) Factory setting: 00 Room factor heating circuit Selection: without = without room factor (remote control unit remain on the hydraulic unit) Thermostat = external room thermostat is active (terminal 10) WP-FS = Sensor in remote control station or external sensor is active. The selection Room factor influences parameters 112 … 115. Factory setting: without 83279702 • 1/2013-08 • La 21-38 Installation and operating instruction Remote control station WP-FS 6 Operation Heating engineer PaDescription Function / Selection / Factory setting level rameMenu point ters Heating charac- Using the following parameters, the limit values for the heating characteristic curve can be teristic curve entered manually (see Ch. 6.5). Parameter 317 … 322 are only active, if 313 = 0 has been set in both parameters. 317 External min Minimum external temperature External max Min flow HC1 Max flow HC1 Min flow HC2 Max flow HC2 318 Setting range: -20 … 10 °C Factory setting: -7 °C Maximum external temperature 319 Setting range: 15 … 50 °C Factory setting: 20 °C Minimum flow temperature heating circuit 1 320 Setting range: 20 °C … (value parameter 320) Factory setting: 20 °C Maximum flow temperature heating circuit 1 321 Setting range: (value parameter 319) … 60 °C Factory setting: 35 °C Minimum flow temperature heating circuit 2 322 Setting range: 20 °C … (value parameter 322) Factory setting: 20 °C Maximum flow temperature heating circuit 2 Setting range: (value parameter 321) … 60 °C Factory setting: 35 °C Cooling charac- Using the following parameters, the limit values for the cooling characteristic curve can be teristic curve entered manually (see Ch. 6.5). Parameter 323 … 328 are only active, if 314 = 0 has been set in both parameters. 323 External min Minimum external temperature External max Min flow HC1 Max flow HC1 Min flow HC2 Max flow HC2 324 Setting range: 0 … 25 °C Factory setting: 22 °C Maximum external temperature 325 Setting range: 30 … 50 °C Factory setting: 40 °C Minimum flow temperature heating circuit 1 326 Setting range: 4 … 20 °C Factory setting: 18 °C Maximum flow temperature heating circuit 1 327 Setting range: 4 … 20 °C Factory setting: 18 °C Minimum flow temperature heating circuit 2 328 Setting range: 4 … 20 °C Factory setting: 18 °C Maximum flow temperature heating circuit 2 Setting range: 4 … 20 °C Factory setting: 18 °C 83279702 • 1/2013-08 • La 22-38 Installation and operating instruction Remote control station WP-FS 6 Operation Heating engineer level Menu point System info 83279702 • 1/2013-08 • La Fault messages Version WP-FS Version WP External TO Parameters 338 339 500 410 Evaporation TE 411 Suction side gas TS 412 Pressure side gas TD 413 De-couple temp Flow temp 1 480 481 Flow temp 2 481 Cond temp Flow temp DHW Temp Refrigerant temp 482 483 484 485 Setpoint temp flow HC 1 Setpoint temp flow HC 2 Setpoint temp flow Throughput 486 Type of operation 490 Description 486 487 488 Status HP 491 Max frequency 492 Setp. frequency 493 Frequency 494 23-38 Function / Selection / Factory setting List of the last 10 faults (see Ch. 8.1). Software version is displayed. Version of the hydraulic unit control is displayed. TO sensor on outdoor unit Current external temperature is displayed. TE sensor on outdoor unit Current evaporator temperature (evaporator input) is displayed. TS sensor on outdoor unit Current suction side gas temperature (compressor input) is displayed. TD sensor on outdoor unit Current pressure side gas temperature (compressor output) is displayed. Current de-couple temperature is displayed. Current flow temperature of heating circuit 1 is displayed. Current flow temperature of heating circuit 2 is displayed. Current condenser temperature is displayed. Current hydraulic unit flow temperature is displayed. Current DHW temperature is displayed. TC sensor on the hydraulic unit Current refrigerant temperate is displayed. Calculated setpoint flow temperature of heating circuit 1 is displayed. Calculated setpoint flow temperature of heating circuit 2 is displayed. Setpoint flow temperature of hydraulic unit Display: Yes = Water is flowing, or No = Water is not flowing. Current operating mode of system is displayed: Off, Standby, Cooling, Heating, Manual heating, Manual cooling, Fault or ON delay = Switch on delay. Switch on delay means: 10 minutes pause between 2 starts and 3 minutes waiting time between Off and On switching. These times cannot be interrupted. Current operating mode of heat pump is displayed: Off, Cooling, Heating, Fault, Defrost or DHW operation (DHW preparation). Maximum possible compressor frequency is displayed. Compressor frequency currently requested is displayed. Current compressor frequency is displayed. Installation and operating instruction Remote control station WP-FS 6 Operation Heating engineer level Menu point System info Compressor run time Parameters 495 Run time pump HC 496 Run time E heat 1 497 Run time E heat 2 498 Description Rating HP Therm Disinfect Cycle 499 505 Setpoint temp 506 Time 507 Duration Max time Function / Selection / Factory setting Compressor run time in hours from start of operation or last reset up to current point in time is displayed. The hours can be reset to 0 using the Reset key. Run time of heating circuit pump, from commissioning or last reset up to current point in time (display in hours). The hours can be reset to 0 using the Reset key. Run time of electric heating on stage 1, from commissioning or last reset up to current point in time (display in hours). The hours can be reset to 0 using the Reset key. Run time of electric heating on stage 2, from commissioning or last reset up to current point in time (display in hours). The hours can be reset to 0 using the Reset key. The rating of the outdoor unit is displayed. Thermal disinfection of the domestic hot water can be switched off or carried out on a specific day of the week. Selection: Off or Monday ... Sunday = select a weekday. Factory setting: Friday Thermal disinfection setpoint temperature Setting range: 60 … 90 °C Factory setting: 75 °C Time of thermal disinfection 509 Factory setting: 22.00 hrs. Duration of thermal disinfection (duration during which the setpoint temperature will be maintained). 510 Setting range: 5 … 180 minutes Factory setting: 30 minutes Time entry in hours. If the setpoint temperature has not bee reached, the disinfection is terminated after this time. Setting range: 2 … 12 hours Factory setting: 4 hours 83279702 • 1/2013-08 • La 24-38 Installation and operating instruction Remote control station WP-FS 6 Operation Heating engineer level Menu point 2.HE Description Number of 2.HE 2. heat exchanger Parameters 601 602 Function / Selection / Factory setting Number of second heat exchangers (electric heating) Selection: 0 = no electric heating 1 = electric heating, 1 stage or boiler 2 = electric heating, 2 stages Factory setting: 0 (no electric heating) Selection: E heat = electric heating or Boiler If selecting Boiler, parameter 601 must be set to 1. Prio 603 Factory setting: E heat (electric heating) Priority of the 2. heat exchanger Parameter is only active, if parameter 602 has been set to E heat (electric heating). Selection: 0 = If required all 2. heat exchangers are activated. 1 = Maximum two 2. heat exchangers are activated. DHW flange heating has the lowest priority. 2 = Maximum one 2. heat exchanger is activated. The electric heating, stage 1 has the highest priority. 3 = Maximum two 2. heat exchangers are activated. DHW flange heating has the lowest priority. The electric heating, stage 2 never operates. 4 = Maximum one 2. heat exchanger is activated. DHW flange heating has the highest priority. The electric heating, stage 2 never operates. Bivalence temp Hysteresis Flow Delay Limittemp HP 604 Factory setting: 0 Bivalence temperature: When the external temperature drops below this value, the 2. heat exchanger may be used. 605 Setting range: -30 … 40 °C Factory setting: -5 °C Flow hysteresis: If the setpoint/actual value differential is greater than this value, the 2. heat exchanger is activated. 606 607 Setting range: 2.0 K … 10.0 K Factory setting: 3.0 K Time delay in minutes before the second heat exchanger is activated. Setting range: 2 … 60 minutes Factory setting: 10 minutes Heat pump temperature limit: Only the boiler is in operation below this external temperature (see parameter 602). Setting range: -30 …40 °C Factory setting: -5 °C 83279702 • 1/2013-08 • La 25-38 Installation and operating instruction Remote control station WP-FS 6 Operation 6.4 Select preset characteristic curves Heating characteristic curves parameter 313 70 65 06 60 05 55 04 50 03 45 40 02 35 01 30 25 20 15 25 20 10 15 5 0 -5 -10 -15 -20 1 External temperature in °C 2 Flow setpoint temperature in °C Cooling characteristic curves parameter 314 22 20 02 18 16 14 12 01 10 8 6 4 2 0 45 42,5 40 37,5 35 1 External temperature in °C 2 Flow setpoint temperature in °C 83279702 • 1/2013-08 • La 26-38 32,5 30 27,5 25 22,5 20 17,5 15 12,5 Installation and operating instruction Remote control station WP-FS 6 Operation 6.5 Setting characteristic curves individually Heating characteristic curves parameters 317 … 322 Prerequisite: Parameter 313 = 0 42.5 40.0 37.5 320/322 35.0 117 32.5 30.0 27.5 25.0 22.5 319/321 20.0 17.5 317 318 15.0 25 20 10 15 5 0 -5 -10 -15 -20 1 External temperature in °C 2 Flow setpoint temperature in °C Cooling characteristic curves parameters 323 … 328 Prerequisite: Parameter 314 = 0 22 20 326/328 18 16 14 12 10 119 8 325/327 6 4 324 323 2 0 45 40 35 1 External temperature in °C 2 Flow setpoint temperature in °C 83279702 • 1/2013-08 • La 27-38 30 25 20 15 10 Installation and operating instruction Remote control station WP-FS 7 Commissioning 7 Commissioning The installation and operating manual of the hydraulic unit should be observed in addition to this chapter. 7.1 Prerequisite Commissioning must only be carried out by qualified personnel. Only correctly carried out commissioning ensures the operational safety of the unit. Commissioning must only be carried out once the cooling circuit has been installed completely (see installation and operating manual of outdoor unit). ▶ Prior to commissioning ensure: ▪ All installation work has been completed and checked. ▪ Electrical installation duly completed, electric circuits duly fused and measures for contact protection of electrical components and of all wiring checked. ▪ The unit and heating system have been adequately filled with water and vented ▪ Heating or cooling demand is present Additional system-related tests could be necessary. Please observe the operating guidelines for the individual components. 83279702 • 1/2013-08 • La 28-38 Installation and operating instruction Remote control station WP-FS 7 Commissioning 7.2 Steps for commissioning The menu Commissioning is displayed automatically: ▪ following the initial start-up, ▪ after every reset. Setting the language When initially applying voltage when switching on the unit and after every reset, parameter Language is displayed (see Ch. 6.3.2). ▶ Set the language using the dial knob. ▶ Save with function key OK. Language 311 End English OK Additional steps for commissioning During commissioning, all parameters are displayed in sequence. Note parameter list in engineers level (see Ch. 6.3.2). ▶ Set parameters 311 … 504 according to the parameter list in engineer level / commissioning. Resetting to factory settings With Reset, all settings are reset to factory settings. ▶ Interrupt voltage supply. ▶ Reconnect voltage supply and at the same time to start press menu key EEPROM appears in the display. ✓ All settings have been reset to factory settings. 83279702 • 1/2013-08 • La 29-38 until Installation and operating instruction Remote control station WP-FS 7 Commissioning 7.3 Priority function Most heating systems with DHW preparation for single and multi-family homes utilise a hot water priority function in the heating control for added convenience. The remote control station has an alternating dynamic priority function for this. When first delivered, DHW preparation is set to take priority. In systems without room influence (parameter 315 = without) the heating priority/ cooling priority = constant 0.5 is set. The lower the setting value of parameter 503 and parameter 504, the higher the respective priority. Recommendation: Do not change factory settings. Example Factory setting: At 21.5 °C room temperature, the room priority is = 0.3. At 43 °C DHW temperature, the DHW priority is = 0.7 (Parameter 132 DHW Setpoint temp = 50 °C). Result: DHW priority 0.7 > room priority 0.3. Therefore DHW loading takes priority over the heating operation. A B 1.0 1.0 0.7 0.5 0.5 0.3 0 0 20 20.5 21 21.5 22 40 A = Room 1 Rom temperature in °C 2 Room priority 3 Room setpoint temperature 22 °C (Parameter 112) 4 Room Prio 0.5 = 1 °C (Parameter 503) 5 Room Prio 1.0 = 1 °C (Parameter 503) 83279702 • 1/2013-08 • La 42 44 46 48 50 B = DHW 6 DHW temperature in °C 7 DHW priority 8 DHW setpoint temperature 50 °C (Parameter 132) 9 DHW Prio 0.5 = 5 °C (Parameter 504) 0 DHW Prio 1.0 = 5 °C (Parameter 504) 30-38 Installation and operating instruction Remote control station WP-FS 8 Troubleshooting 8 Troubleshooting 8.1 Procedures for fault conditions Fault messages Fault messages from the hydraulic unit, outdoor unit and 2. heating circuit are displayed. A fault is shown in the display with Fault and a number (fault code). If a fault occurs, the systems goes to lockout. Wed 25.Apr 12 09:43 i WP#1 Lockout … Heating program 1 1 Fault location (heat pump) 2 Fault message and fault code ▶ Read the fault code. ▶ Rectify the cause of the fault using the following table (see Ch. 8.2.1). ▶ Use protection provided on site to isolate the outdoor unit/system from the mains supply. ✓ During restart, the fault messages appears only in the fault history. ✓ The system is reset. Display fault history The last 10 fault messages are stored in the fault history. ▶ Activate heating engineer level. ▶ Select menu point System info. ✓ The most recent fault will be displayed. ▶ Turn dial knob. ✓ Faults 1 … 10 can be read. Rectified faults are displayed with fault code 00. Engineer 02 End Cooling reference line System info Therm disinfect System info 01 End Error message Version WP-FS Version WP Error message 338 Error message 01: WP#1 Lockout ... 07.May 12, 08:09 83279702 • 1/2013-08 • La 31-38 Reset 338 End End 02: WP#1 Lockout ... 08.May 12, 09:10 Reset Installation and operating instruction Remote control station WP-FS 8 Troubleshooting Exchanging the unit ▶ Select and check fault history before replacing the remote control station and include a copy when returning the unit for exchange. Delete fault history ▶ Display fault history. ▶ Press [Reset] key. ✓ All 10 fault messages are deleted. 83279702 • 1/2013-08 • La 32-38 Installation and operating instruction Remote control station WP-FS 8 Troubleshooting 8.2 Rectifying faults 8.2.1 Fault codes Hydraulic unit faults Fault code 03 Cause Flow sensor in the hydraulic unit defective Rectification ▶ Check the sensor and cable and replace if necessary ▶ Check the sensor and cable and replace if necessary ▶ Compare characteristic curves ▶ Check the sensor and cable and replace if necessary ▶ Compare characteristic curves ▶ Check wiring of remote control station 04 Sensor in the refrigerant pipework defective 05 DHW sensor defective 06 and 07 08 No connection between hydraulic unit and remote control station Heating water flow despite the pump being off 09 Flow sensor does not detect a flow 10 Electronic fault hydraulic unit ▶ ▶ 11 12 No connection to 2. heating circuit No connection between hydraulic unit and remote control station 2. heating circuit not set No connection to the outdoor unit – or – excess temperature at the compressor ▶ ▶ ▶ ▶ ▶ ▶ ▶ ▶ ▶ 15 ▶ ▶ ▶ ▶ Sensor on the condenser defective (flow temper- ▶ 16 ▶ 13 14 ature in the condenser) Temperature sensor in the remote control station activated or deactivated 83279702 • 1/2013-08 • La 33-38 Check flow sensor, if necessary replace Check setting of parameter 451 Check flow sensor, if necessary replace Check setting of parameter 451 Check wiring Set pump to manual operation Check if thermostat for underfloor heating is connected Interrupt the voltage supply temporarily If necessary, if the fault is still displayed, replace motherboard Check wiring to 2. heating circuit Check wiring of remote control station Set parameter 312 = 2 Check wiring of outdoor unit Measure Bus voltage at outdoor unit (230 V) Check temperature switch on compressor Check the sensor and cable and replace if necessary Change setting of parameter 315 Installation and operating instruction Remote control station WP-FS 8 Troubleshooting Outdoor unit fault Fault code 17 18 20 21 22 23 24 26 27 28 29 30 31 Cause Rectification External temperature sensor on outdoor unit de- ▶ Check the sensor and cable and replace if fective (TO sensor) necessary Overcurrent protection device has tripped ▶ Check wiring of circuit board on outdoor unit ▶ Check circuit board in outdoor unit, if necessary replace Electronic fault outdoor unit ▶ Replace circuit board in outdoor unit Excessive current draw in the outdoor unit ▶ Check circuit board in outdoor unit ▶ Check voltage and wiring TE and/or TS sensor in outdoor unit defective ▶ Check the sensor and cable and replace if necessary ▶ Compare characteristic curves TD sensor in outdoor unit defective ▶ Check the sensor and cable and replace if necessary Fan blocked ▶ Check fan Fault on outdoor unit ▶ Check outdoor unit Compressor defective ▶ Check compressor wiring ▶ If necessary replace compressor Fault on TD sensor in outdoor unit ▶ Check refrigerant pipework is not leaking ▶ Check expansion valve ▶ Check TD sensor in outdoor unit Compressor failure ▶ Check power supply Electronic fault outdoor unit ▶ Check circuit board in outdoor unit, if necessary replace TE sensor in outdoor unit signals excess temper- ▶ Check the sensor and cable and replace if ature necessary Hydraulic unit faults Fault code 34 * 35 37 Cause Rectification Warning message electric heating: Flow temper- ▶ Check electric heating ature does not increase by 1 °C every 30 minutes ▶ Check wiring and electrical connections of electric heating Low DHW temperature ▶ Check DHW flange heating Thermal disinfection failed ▶ Check setting of parameters 505 … 510 ▶ Check DHW flange heating ▶ Check fusing of DHW flange heating ▶ If parameter 602 = Boiler: Check DHW flange heating Temperature sensor in the remote control station ▶ Check sensor and replace if necessary defective ▶ Check setting of parameter 315 ▶ Install remote control station outside of the unit 83279702 • 1/2013-08 • La 34-38 Installation and operating instruction Remote control station WP-FS 8 Troubleshooting Second heating circuit faults Fault code 53 55 57 58 60 61 63 66 Cause De-couple sensor 2. heating circuit defective Rectification ▶ Check the sensor and cable and replace if necessary Flow sensor 1. heating circuit out of range ▶ Check mixer setting ▶ Check the sensor and cable and replace if necessary ▶ Compare characteristic curves Underfloor thermostat activated ▶ Check, if the thermostat has been set to a temperature which is too low Flow sensor 2. heating circuit out of range ▶ Check mixer setting ▶ Check the sensor and cable and replace if necessary Electronic fault 2. heating circuit ▶ Replace circuit board on 2. heating circuit Connection from hydraulic unit to 2. heating cir- ▶ Check wiring cuit interrupted Setting 2. heating circuit incorrect ▶ Check setting of parameter 312 Temperature sensor in the remote control station ▶ Check sensor and replace if necessary defective Remote control station faults Fault code 136 154 200 Cause Room sensor fault Rectification ▶ Check wiring of external room sensor ▶ If necessary, replace external room sensor. Error EEPROM ▶ Reset all settings to factory setting using EEPROM Reset (see Ch. 7.2) Bus conflict: only one remote control station can ▶ Check if a second remote control station has be used been connected 83279702 • 1/2013-08 • La 35-38 Installation and operating instruction Remote control station WP-FS 9 Notes 9 Notes 83279702 • 1/2013-08 • La 36-38 Installation and operating instruction Remote control station WP-FS 10 Key word index A G Absence ................................................................................17 Ambient conditions ............................................................... 7 Approval data ......................................................................... 7 Guarantee ............................................................................... 5 B Bivalence temperature .......................................................25 C Cable cross section ...........................................................10 Change date ........................................................................17 Change parameters ...........................................................14 Change time .........................................................................17 Characteristic curve ...........................................................21 Characteristic curve preset ..............................................26 Commissioning ..................................................... 19, 20, 28 Compressor frequency .............................................. 17, 23 Compressor motor temperature ......................................23 Compressor run time .........................................................24 Compressor temperature ..................................................23 Control behaviour ...............................................................21 D DHW temperature ..............................................................23 Dial knob ...............................................................................11 Display ...................................................................................16 Display parameters .............................................................14 Disposal .................................................................................. 6 Domestic hot water temperature .....................................17 Draining .................................................................................20 E EBUS terminal .....................................................................10 Electric heating ............................................................ 17, 25 Electrical installation ...........................................................10 End user level ......................................................................16 Exchanging the unit ............................................................32 Exit level ................................................................................15 External contact ...................................................................19 External flow .........................................................................19 External temperature ..........................................................23 Heat pump operating mode .............................................23 Heating engineer level .......................................................19 Hibernation mode ...............................................................18 Holiday ..................................................................................17 Hysteresis .............................................................................25 I Illumination ............................................................................11 Info menu ..............................................................................12 L Legionella function .............................................................24 Liability ..................................................................................... 5 Limit temperature ................................................................25 Lockout ......................................................................... 13, 31 M Manual operation ................................................................20 Max external temperature ..................................................22 Max. compressor frequency .............................................23 Max. frequency ....................................................................23 Menu key ...............................................................................11 Min external temperature ...................................................22 Moon ......................................................................................13 N Night setback .......................................................................16 Night setback operation ....................................................13 Normal operation ................................................................13 O Operating hours ..................................................................24 Operating mode ..................................................................23 Operating panel ..................................................................11 Operating time .....................................................................24 P F Factory setting .....................................................................29 Fault ............................................................................... 23, 31 Fault code ....................................................... 31, 33, 34, 35 Fault codes ................................................................... 33, 34 Fault history ..........................................................................32 Fault memory .......................................................................31 Fault messages ...................................................................23 Flow .......................................................................................19 Flow setpoint temperature heating circuit 1 .................23 Flow setpoint temperature heating circuit 2 .................23 Flow temperature ........................................................ 16, 23 Flow temperature heating circuit 1 .................................22 Flow temperature heating circuit 2 .................................22 Frost protection ........................................................... 17, 19 Function key .........................................................................11 83279702 • 1/2013-08 • La H Pressure side gas temperature .......................................23 Pump Down .........................................................................20 Pump heating circuit 1 ......................................................17 R Rating ....................................................................................24 Refrigerant temperature ....................................................23 Reset .....................................................................................29 Room sensor ............................................................9, 10, 16 Room temperature ..............................................................16 Run time compressor .........................................................24 Run time electric heating ..................................................24 Run time heating circuit pump .........................................24 37-38 Installation and operating instruction Remote control station WP-FS 10 Key word index S Safety measures ................................................................... 6 Second heat exchanger ............................................ 17, 25 Select menu .........................................................................14 Select parameter ................................................................15 Set factory settings ............................................................15 Set language ........................................................................19 Setback temperature .........................................................16 Setpoint temperature flow heating circuit 1 .................23 Setpoint temperature flow heating circuit 2 .................23 Setting characteristic curves ...........................................27 Software version .................................................................23 Standard display .................................................................12 Standards ............................................................................... 7 Standby .................................................................................13 Storage ................................................................................... 7 Suction side gas temperature ..........................................23 Summertime .........................................................................17 Sun .........................................................................................13 Symbol type of operation ..................................................13 System info ................................................................... 23, 24 T Temperature ........................................................................... 7 Thermal disinfection ...........................................................24 Throughput ...........................................................................23 Time delay second heat exchanger ................................25 Time program .......................................................................18 Transport ................................................................................. 7 Type key .................................................................................. 7 Type of operation ................................................................13 U Umbrella ................................................................................13 V Version Software ................................................................23 Volume level outdoor unit .................................................17 W Wall bracket ........................................................................... 9 83279702 • 1/2013-08 • La 38-38 83279702 • 1/2013-08 • La Max Weishaupt GmbH · 88475 Schwendi Weishaupt close by? Addresses, telephone numbers etc. can be found at www.weishaupt.de We reserve the right to make changes. All rights reserved. The complete program: Reliable technology and prompt, professional service W Burners up to 570 kW Wall-hung condensing boilers for oil and gas up to 240 kW The compact burners, proven millions of times over, are economical and reliable. Available as gas, oil and dual fuel burners for domestic and commercial applications. The purflam® burner version with special mixing head gives almost soot-free combustion of oil with greatly reduced NOx emissions. The wall-hung condensing boilers WTC-GW and WTC-OW have been developed to meet the highest demands in ease of operation and efficiency. Modulating operation means these units operate quietly and economically. monarch® WM Burners and Industrial Burners Floor standing condensing boiler for oil and gas up to 1,200 kW up to 11,700 kW These legendary industrial burners are durable and versatile. Numerous variations of oil, gas and dual fuel burners meet a wide range of applications and capacity requirements. WK Burners up to 28,000 kW The floor-standing boilers WTC-GB and WTC-OB are efficient, low in emissions and versatile. Higher capacities are achieved by cascading up to four gas-fired condensing boilers. Solar systems These industrial burners of modular construction are adaptable, robust and powerful. Even on the toughest industrial applications these oil, gas and dual fuel burners operate reliably. The stylish flat-plate collectors are the ideal complement for any Weishaupt heating system. They are suitable for solar water heating and for combined heating support. With versions for on-roof, in-roof and flat roof installations, solar energy can be utilised on almost any roof. multiflam® Burners Water heaters / energy storage tanks up to 17,000 kW This innovative Weishaupt technology for medium and large burners provides minimum emission values at capacities up to 17 MW. The burners with the patented mixing head are available for oil, gas and dual fuel operation. This attractive program for domestic water heating includes classic water heaters, solar storage tanks, heat pump storage tanks and energy storage tanks. MCR Technology / Building Automation from Neuberger Heat pumps From control panels to complete building management systems - at Weishaupt you can find the entire spectrum of modern control technology. Future orientated, economical and flexible. up to 130 kW The heat pump range offers solutions for the utilisation of heat from the air, the soil or ground water. Some systems are also suitable for cooling buildings. Service Geothermal probe drilling Weishaupt customers can be assured that specialist knowledge and tools are available whenever they are needed. Our service engineers are fully qualified and have extensive product knowledge, be it for burners, heat pumps, condensing boilers or solar collectors. With its daughter company, BauGrund Süd, Weishaupt also offers geothermal probe and well drilling. With the experience of more than 10,000 systems and more than 2 million meters of drilling, BauGrund Süd offers a comprehensive service program. 83279702 • 1/2013-08 • La