UPFC Influence to Transient Stability of Power System Matus Novak, Richard Kravec, Martin Kanalik, Zsolt Conka, Michal Kolcun Department of Electric Power Engineering Teclmical university ofKosice Kosice, Slovakia matus.novak@tuke.sk, martin.kanalik@tuke.sk, zsolt.conka@tuke.sk, michal.kolcun@tuke.sk Abstract- Large-scale [I. power systems operation is faced with many challenges. One of many criteria, which should be fulfilled In foreign countries, specialized devices are used with many advantages. These specialized systems are known under abbreviation FACTS - Flexible AC transmission system. are stability criteria. Interconnecting separated power systems into interconnected network results in large system complexity, and therefore mixed influences from one power system to These devices are defined as alternating current transmission systems based on power electronics and other passive and active elements (capacitors, reactors, or transformers), which provide regulation of one or more parameters, such as current, voltage, impedance, phase shift. [11] another part. Also, new devices are introduced to improve power system performance, like FACTS devices. Main goal of this paper is to examine influence of one of these devices to power system stability. Keywords-power system, stability, PSLF, FACTS, UPFC. I. These devices bring many advantages and possibilities for TSO as for example: INTRODUCTION Safety and reliability of power system operation is discussed in present time very often. Power system stability of interconnected power system, like ENTSO-E - European power system, should be discussed very carefully, mainly due to weak cross-border interconnections between countries, or between control areas (CA). Because of these weak interconnections, any fault, which appears in one CA will influence neighboring CA. Latest trend of shutting down nuclear power plants and building new renewable sources with similar installed power without necessary changes in power system bring new issues for power system stability. [10] Since these problems appeared, great effort has been expended to limit the impact of these problems to power system operation. Previous research has shown that in some operating conditions is power system without direct dispatcher intervention put into risky conditions. Some protective actions had to be taken previously to maintaein power systems safety criteria, like re-dispatching, network reconfiguration, and even "multilateral re-dispatch", which means, that one transmission system operator (TSO) asks other TSO to change configuration of their power system. Solution for these problems can be provided by using new specialized devices for power flow regulation and stability improvement. Since these devices are very expensive, from economical point of view their use is not very convenient, but from view of power system operation, these devices can very well improve power system operation performance and safety, mostly around network bottlenecks. [8][[3] [. Transmission capacity increase for existing lines to their limits without any other compensating devices, 2. Power flow regulation, loop flows reduction, 3. Reliable interconnection of neighboring power systems, and decreasing of needed electricity production on both sides, 4. Reduction of big shunt reactors and series capacitors and therefore reduction of space in power stations, 5. Compactness and modality of new FACTS systems allows their installation everywhere and extending of their size, 6. Power system stability improvement increasing static and transient stability limits, damping of generator electromechanical oscillations and decreasing of short circuit currents. These devices can be divided into four basic categories: 1. Parallel regulators, 2. Serial regulators, 3. Combined serial-serial regulators, 4. Combined serial-paralel regulators. From this, different kinds of FACTS devices are known, such as SVC (Static VAR compensator), STATCOM (Static synchronous compensator), TCSC (Thyristor Controlled Series Capacitor), PST (Phase Shifting Transformer), SSSC (Static Synchronous Series Compensator), UPFC (Universal Power Flow Controler), and we can also mention HVDC This work was supported by The Ministry of Education, Science, Research and Sport of the Slovak Republic and the Slovak Academy of Sciences under the contract No. VEGA 1/0388/13. 978-1-4799-3721-9/14/$31.00 m014 IEEE SPECIALIZED DEVICES 343 (High Yoltage Direct Current) transmiSSIOn system, which have also possibility of controlling real and reactive power, and is used to provide asynchronous connection between two power systems with e.g. different frequency. From view of which power can be regulated using this devices, we can divide them into three categories: I. Reactive power regulation (SYC, STATCOM), 2. Real power regulation (TCSC, PST, SSSC), 3. Real and reactive power (HYDC, UPFC). from UPFC most universal transmission device for both - real and reactive power regulation and control.[3] Transmission line -------r1--l.u.J Series tTimsformer Parallel trallsfOlll1 er e omrerter1 · Converter2 -....�V, .. Fig. 3 UPFC topology[2] In next part, we will continue with description of power system used for modeling of UPFC influence. Fig. 1 STATCOM topology[7] In following we will speak mostly about UPFC and its principle. This device connects together STATCOM (Fig. I) and SSSC (Fig. 2) device, and is therefore combination of serial and parallel compensation, what on the other side corresponds to technical and economic difficulties of this device. vJ Fig. 4 Vector diagram of UPFC regulation possibilities[6] III. MODELLED POWER SYSTEM For examination of UPFC influence to power system, 39bus New England power system was selected. Mainly its complexity and installed power, has been taken into consideration, when this power system was chosen. On the same power system was previously researched influence of primary and secondary power frequency control. For this reason, power system was divided into three areas, with generation and consumption almost in balance. All devices, like exciter, exciter regulation, power system stabilizer (PSS) and turbine with governor were modeled for all generators. Fig. 2 SSSC topology[7] For purpose of power system modeling, a Positive Sequence Load Flow (PSLF) software was used, provided for authors by Slovak TSO - Slovenska elektrizacmi a prenosova sustava (SEPS) in version 17.05. UPFC consists from parallel (excitation) and serial (auxiliary) transformer. Both transformers are connected through two YSC converters which are interconnected through mutual DC intermediate circuit with condenser. Serial converter injects AC voltage Upq (voltage on serial transformer) which can be according input voltage UI (on left side) freely rotated and can have amplitude freely set in range from 0 :S Upq :S Upq max. Serial converter can therefore act in all four quadrants and independently control real and reactive power of line. Parallel converter can generate reactive current in way to keep voltage U\ on set value. In this case, converter acts in voltage control mode. Parallel reactive current can also correspond to required inductive or capacitive reactive power, and therefore converter acts in reactive power control mode. Control parameters of UPFC are therefore amplitude and phase shift of injected voltage Upq and amplitude of reactive current Iq of parallel branch. This regulation possibility makes In PSLF, UPFC is in load flow modeled by a transformer with variable tap ratio and phase shift and by a generator at the bus of line input, which supplies the reactive power for both the shunt and series converters. For dynamic simulations, UPFC is simulated using subroutine which acts as UPFC regulator, and controls series voltage injection and shunt MYAr injection into the network using current injections at input and output bus of UPFC.[9] 344 Second fault, marked as B, was modeled in the middle of the line from node 26 to node 27. This line was loaded by 316 MW and 84 MVAr, which represents about 32% of its rating. Values of CCT for lines with and without UPFC connected are in TABLE I. We can see that CCT difference for first fault is only 35ms, for second, is 158 ms. AREAl <1> TABLE I. CCT VALUES FOR AREA 1 Area C7 '" CCT (ms) I Without UPFC With UPFC Fault A (line 2-3) 277 312 Fault B (line 26-27) 207 365 <0> B. AREA2 In area 2, we have chosen also two places of fault, as in previous case. Since lines in this area are not heavily loaded, we were not able to choose any line close to overload. First fault C was modeled on line from bus 14 to 15, in the middle of the line. To be clear, when we are speaking about fault, it is always three phase solid short-circuit. This line was therefore loaded at about 32% of rating. Other fault (D) was applied to line from node 5 to node 8, also in the middle of the line. This line was loaded at about 27,7 % of rated current. CCT differences for situation with and without UPFC are more significant for this area, 95, or even 200 ms. Curves of angle of generator at bus 34 are on Fig. 7. Fig. 5 39-bus power system splited to three areas with marked places where faults were applied (from [12] , modified according description above) SIMULATIONS IV. Using previously mentioned power system model, we have chosen few faults, which have serious influence on stability, and we performed some simulations for each of three areas, on which power system was separated. UPFC was implemented in Area 3, on line, which interconnects this area with Area I. For all three areas, similar faults were chosen, and value of critical clearing time (CCT) was evaluated for each place of fault, comparing network with, and without UPFC implemented. The Critical Clearing Time is the maximum time during which a disturbance can be applied without the system losing its stability. A. TABLE II CCT VALUES FOR AREA 2 Area 2 AREA 1 In area 1, two places of fault were chosen. First was modeled in the middle of line from node 2 to node 3. This line was before fault loaded by 671 MW and 144 MVAr, which represents about 68% of its rating. This fault is marked as fault A. Curves of angle for generator 34 and 37 are on Fig. 6. Generator3 run out of 60 synchronisn with UPFC, t--fau1t--dur-ati t�3J3ms 20 / -�/ / 5 45 -20 -4 -40 With UPFC Fault C (line 14-15) 297 392 Fault 0 (line 5-8) 247 447 Generator 34 runs out of with UPFC, II I ./ F atilt applied a simulation tim t=55 fault duration �r------ / ;A )1 \ -60 -80 Without UPFC synchronism - 80 0(") 40 CCT (ms) t �393ms Generator34 run out of synchronism without UPFC, fault duration -Fault C Without t� 278 ms UPFC 297 -Fatlit A Without time (s) 65 1\ \ '--.../ UPFC 278 UPFC 298 illS -Fatlit A With UPFC 3 12 UPFC 392 illS illS C With UPF C 393 illS Fig. 7 Curves of angle for generator 34 for fault C in area 2. -Fault illS -Fatlit A Without UPFC 227 illS -Fault C With -Fatlit A With UPFC 3 13 illS -Fault C Without illS Fig. 6 Curves of angle for generators 34 and 37 for fault A in area 1. 345 C. cheap components - two transformers and two high power converters, conclusion can be made, that other solutions will be taken into consideration, when TSO will be choosing solutions to improve power system stability and for power flow control. This statement also supports the fact, that only three UPFC were installed until present moment in whole world. Therefore other, cheaper solutions have to be subject of research for this purpose. AREA 3 [n third area, UPFC is implemented, on line from node [6 to [7 (Areal). For this area, also two faults were modeled, on line from 23 to 24 (fault E) and for line from 2 [ to 22 (fault F). First line was loaded to only [6% of rated current, other one was loaded to 34% of rated current. Observed CCT changes for this area were also significant for both faults. Differences were 165, or even 175 ms. From this point of view, control area with implemented UPFC can withstand more serious faults, than other CA without UPFC. It can be observed, that CCT for fault F was prolonged more than twice. Curves of angle of generator at bus 34 and 33 are on Fig. 8. REFERENCES [I] 100 33 / 1) (') 34 / 80 � ----II -----60 �308 --I / 40 133 / /". / 20 r------ / / V F Without 5 75 -Fault � 6,\ 65 .; UPFC -20 // F Without '\ / � -Fault -40 UPFC \'n -Fault F WithUPFC -60 \ / -80 -Fault F WithUPFC � -100 Genera or Generator runs ou of synchr run out of ism - synchronism - with Ul Fe, fault d t [2] without UPFC, ation fault duration fns [3] ms F [4] time (s) ".... Fau t applied = illS 133 illS [5] t sim ration tine t 132 307111S s [6] 308111S Fig. 8 Curves of angle for generator 34 and 33for fault F in area 3. [7] TABLE III CCT VALUES FOR AREA 3 Area 3 [8] CCT (ms) Without UPFC With UPFC Fault E (line 23-24) 242 407 Fault F (line 21-22) 132 307 [9] [10] [11] It has to be also stated, that without correct response of UPFC regulator these improvements were not so significant. Also, influence of UPFC on transient stability of more complex power system can be subject of further research. [12] [13] CONCLUSIONS From previous simulations, significant positive impact of UPFC on power system dynamic stability can be observed. Because of UPFC price, which consists from four not really 346 P. Kundur, "Power System Stability and Control", New York: McGraw­ Hill, 1998. ISBN 0-07-035958-X. Yao Shu-jun; Song Xiao-yan; Wang Van; Van Yu-xin; Van Zhi, "Research on dynamic characteristics of Unified Power Flow Controller (UPFC)," Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), Proceedings of 2011 4th International Conference, pp.490,493, 6-9 July 2011 Kolcun, M, Bena L. "Vyuzitie specializovanych zariadeni na reguliiciu tokov vykonov v elektrizacnych sustavach". Edicia vedeckych monografii, Technicka univerzita v Kosiciach, 2011. Conka, Z. "Vyskum zariadeni pre zlepsenie dynamickej stability elektrizacnej sustavy". Dissertation exam work, Technical university of Kosice, 2013. Chandrakar, V. K.; Kothari, A. G., "Comparison of RBFN based STATCOM, SSSC and UPFC Controllers for Transient Stability improvement," Power Systems Conference and Exposition, 2006. PSCE '06. 2006 IEEE PES, vol., no., pp.784,791, Oct. 29 2006-Nov. I 2006. Unified Power Flow Controller (Phasor Type), Matlab Simulink R2013b documentation, avaiable on the internet: http://www.mathworks.comlhelp/physmod/sps/powersys/ref/unifiedpow erflowcontrollerphasortype.html. Medved', D. - "Prevadzka elektrizacnej sustavy s vyuzitim FACTS zariadeni", Textbook, Technical university of Kosice, 2007.n, avaiable on the internet: http://people.tuke.skldusan.medvediMvEE/FACTS.pdf. Straka, M. "Reconfiguration in power system of Slovak republic",The 7th International Scientific Symposium ELEKTROENERGETIKA 2013, 18.-20. 9. 2013, Stara Lesna, Slovak Republic, pp. 101-104. General electric PSLF 17.05 Documentation Tesai'ova, M, "Wide Area Measurement System Applications and Experience Abroad", Proceedings of the 13lh international Scientific conference Electric Power Engineering 2012. pp 93-98 Krzeminski, Z, Guzinski, J, Jaderko, A, Abu-Rub, H, "Digital implementation of a novel controlled rectifier synchronization method" Electric Power Components and Systems, Vol 33, Iss. 10, pp 1123-1135. IEEE 39 Bus System Benchmark Model. Available at http://psdyn.ece.wisc.edulIEEE benchmarkslindex.htm Tesai'ova, M, "Phase-angle jumps of supply voltage associated with unbalanced faults in power system", In EMD'2004 (the XIV international conference on electromagnetic disturbances). Vilnius Vilnius Gediminas Technical University, 2004. s. 107-110. ISBN 998605-766-3.