MiniPurge Type Z(Y) CF Manual ML432 This manual covers Mini-Z(Y)-Purge Continuous Flow Size: 1&2 Mounting Options: bp, pm, nm, ss Output Options: IS, PO CONTENTS: 1. Specification Sheet – MiniPurge Type Z(Y) Systems 2. Application Suitability 3. Installation, Operation and Maintenance for CF Systems Section 0. Description and Principle of Operation Section 1. Installation of the System Section 2. Operation of the System Section 3. Maintenance of the System Section 4. Fault Finding - CF Systems Section 5. Annex of Options Fitted 4. Drawings 5. Certificates ML432 v14 25-Nov-14 1. Specification Sheet – MiniPurge Type Z(Y) Systems Model No. (Example): 07 1 ZCF / ss / IS Purge System Type (Note: Not all codes are applicable) Alarm (Signals) 07 = MiniPurge IS = Internal Switch “Alarm” : Dry, VFC,SPSTN/O Contact NI – Ex nA Non-Incendive Circuits Vmax < 254 Vac rms Imax < 1 A Pmax = 70 W IS – Ex i circuits Umax = 30 Vdc Imax = 350 mA Li = 0 Ci = 0 Hermetically Sealed Switch Ex m IIC T4 Gc Vmax = 254 Vac rms Imax 0.7 A PO = Pneumatic Output “Alarm” : Loss of Pressure = No signal ”Pressurized” = at supply pressure Size 1 = Sub MiniPurge Purge flow rate: 4 - 8 scfm / 10 - 225 Nl / min 2 = MiniPurge Purge flow rate: 8 - 16 scfm / 255 - 450 Nl /min Approval / Certification Z= Y= Europe EN 60079-0, EN 60079-2, EN 61241-4 Sira 01ATEX1295X II 3 (2) G D 0518 Ex [pz Gc] IIC T6 Gb Ex [p Dc] IIIC T85ºC Db Tamb -20ºC +55ºC 0518 II 2 (2) G D Ex [py] IIC T6 Gb Ex [p] IIIC T85ºC Db Tamb -20ºC +55ºC IEC IEC 60079-0, IEC 60079-2, IEC 61241-4 IECEx SIR 07.0027X Ex [pz Gc] IIC T6 Gb Ex [p Dc] IIIC T85ºC Db Tamb -20ºC +55ºC Ex [py] IIC T6 Gb Ex [p] IIIC T85ºC Db Tamb -20ºC +55ºC USA / Canada NFPA 496 FM 1X8A4AE Class I Div 2 Groups A, B, C & D bp = Back Plate (Top/Side Mount) 316L Stainless Steel (NROB finish) pm = Panel Mount (Side/Front Mount) 316L Stainless Steel (NROB finish) nm = Non Metallic (Top/Side Mount) Polystyrene c/w clear cover ss = 316L Stainless Steel (NROB finish) Neoprene “Top” Mount Gasket, loose Class I Div 1 Groups A, B, C & D UL E190061 Class I Div 2 Groups A, B, C & D Class I Div 1 Groups A, B, C & D Brazil INMETRO - TÜV 12.1462X Ex [pz Gc] IIC T6 Gb Ex [p Dc] IIIC T85ºC Db Tamb -20ºC +55ºC Supply Pressure MiniPurge Housing Purging Method CF = Continuous Flow Ex [py] IIC T6 Gb Ex [p] IIIC T85ºC Db Tamb -20ºC +55ºC 60 psi / 0.4MPa / 4 bar must be regulated at inlet. Maximum supply pressure 115 psi / 0.8MPa / 8 bar. Compressed Air / Nitrogen Flow & Pressure Sensor One sensor for both “Low Pressure and Flow” : 1 "WC / 250 Pa ( 2.5 mbarg ) Spark Arrestor Unit: Model No Purge / Dilution Flow Rate Material MiniPurge Size 1 SAU25 0.4 to 8 scfm / 10 to 225 Nl/min 8 User selectable orifice plates Stainless Steel MiniPurge Size 2 SAU40 8 to 16 scfm / 255 to 450 Nl/min 4 User selectable orifice plates Stainless Steel Model No RLV25/ss RLV36/ss Relief Valve Opening Pressure 4” WC / 1 kPa (10 mbar) Material : 316L Stainless Steel, Spark Arrestor: Stainless Steel mesh, Gasket: Neoprene Action on “Loss of Pressure”: ML432 v14 4” WC / 1 kPa (10 mbarg) ALARM ONLY 25-Nov-14 2. Application Suitability MiniPurge Systems are certified for use in Hazardous Areas, where the Hazardous Area is non-mining (i.e. above ground) and the hazard is caused by flammable gasses, vapours or dust. Mini-Z-Purge Systems may be used in IECEx, ATEX Zone 2(22) - Category 3 and NEC 500 Class I, Div 2. Mini-Y-Purge Systems may be used in IECEx, ATEX Zone 1(21) - Category 2 and NEC 500 Class I, Div 1. MiniPurge systems may be used for hazards of any gas group. However, apparatus associated with the MiniPurge system, such as Non-Incendive, Intrinsically Safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability. This system is designed for use primarily with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the Pressurized Enclosure. The following materials are used in the construction of MiniPurge systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo for further guidance. Materials of construction: Stainless Steel Mild (carbon) Steel Brass Aluminium Nylon Polyurethane Acrylic Silicone Rubber Neoprene 3. Installation, Operation and Maintenance for CF Systems This MiniPurge is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond normal industrial conditions. The MiniPurge system shall be installed and operated in accordance with relevant standards, such as IEC / EN 60079-14, NEC 500, NFPA 496 and any local codes of practice that are in force. For IEC / ATEX applications, references to the NFPA 496 within the ML383, should be replaced by the equivalent clause in IEC / EN 60079-2. For IEC / ATEX applications, the "Example calculations:" in section 1.1.4 within ML383 should read: If the PE external dimensions indicate a volume of 500 Litres then, 500 litres enclosure volume x 5 volume changes = 12 minutes purge time 225 litres/minute purge flow rate ML432 v14 25-Nov-14 Installation, Operation and Maintenance Manual for MiniPurge Continuous Flow (Model CF) conforming to NFPA 496 IMPORTANT NOTE It is essential, to ensure conformity with the standard, that the user of the system observes the following instructions: Please refer to the latest standard for detailed requirements and definitions. (N.B. These instructions apply only to the Pressurizing system. It is the responsibility of the manufacturer of the Pressurized Enclosure to provide equivalent instructions for the Enclosure.) Contents: Section 0 Section 1 Section 2 Section 3 Section 4 Section 5 Description and Principle of Operation Installation of the System Operation of the System Maintenance of the System Fault Finding Annex (if applicable) Section 0 Description and Principle of Operation All MiniPurge pressurization systems provide: a) a method of pressurizing a Pressurized Enclosure (PE) while at the same time compensating for any leakage, together with b) a method of purging the enclosure, before power is turned on, to remove any flammable gas that may have entered the enclosure while it was not pressurized. Continuous Flow Systems, Model CF, allow air to flow through the PE continuously by having a fixed outlet aperture, which does not have any means of closure. The act of pressurizing the enclosure forces air to “leak” through the outlet aperture. The Control Unit admits sufficient air at the inlet to the PE to compensate for the air leaking out of the outlet aperture as well as from any other accidental leakage paths. The flow rate is constant both during purging and thereafter. The Purging Flow rate is monitored by a separate “Purge Flow Sensor” located in the CU, which detects the differential pressure across the purge flow orifice located directly before the Outlet Orifice. The Purge Flow Sensor is set to operate when the desired differential pressure is exceeded. The output from the Flow Sensor is indicated on the CU and on “X” Pressurization systems, used to operate the automatic purge timer. Both Enclosure Pressure and Purge Flow have to be correct before the Purge Timer can start. Type CF systems comprises the following major parts: - A Control Unit (CU) containing as a minimum, for “Y” and “Z” Pressurization, a Flow Control Valve (FCV), Minimum Pressure and Purge Flow sensing devices, and a “Pressurized”/”Alarm” indicator. The CU supplies a “Pressurized” signal showing whether the PE pressure is satisfactory or not. For Type “X” Pressurization, the CU has, in addition, a fully automatic Purging controller with a purge timer and electrical power switch interlock. Expo Technologies Limited Page 1 of 6 - A Relief Valve (RLV) fitted to the PE to provide a means of limiting the maximum pressure experienced by the enclosure during operation. The RLV model number has suffixes giving the diameter of the valve aperture (in millimeters) and material, e.g. RLV **/cs (Carbon Steel) or /ss (Stainless Steel). All RLVs incorporate a Spark Arrestor to prevent sparks being ejected from the PE through the RLV aperture. The Relief Valve is fitted solely as a safety device and does not open in normal operation. - An Outlet Orifice, which has been pre-calibrated so that the pressure drop at the desired flow rate is known. The Minimum Pressure Sensor within the CU will be set to the same figure as the pressure drop. When the PE pressure exceeds the calibrated pressure the Continuous Flow must be taking place. The system is provided with one of the following types of calibrated Outlet Orifices. Please consult the system specification sheet to determine which has been supplied. The choice: - Type SAU** where the Outlet Orifice disk is removable and can be easily changed by the user to give different flow rates according to the size of the PE and the available air supply capacity. (** denotes the metric thread size of the SAU body) - SA** where the orifice size is fixed and the way to change the flow rate is either to change the setting of the Minimum Pressure Sensor or to replace the SA with one of another size. (** denotes the nominal thread size of the SA body) - For low flow rates, the Outlet Orifice may be incorporated within the Relief Valve making use of the existing Spark Arrestor. The Relief Valve will then have a suffix /CF**, where ** is the orifice size in millimeters. ML383 issue 03 – 09.01.13 Section 1 Installation of the System The installation of the MiniPurge system, the protective gas supply, any alarm device should be in accordance with the requirements of NFPA 496. The electrical installation associated with the MiniPurge system shall conform to the local codes and the relevant clauses of NFPA 496. 1.1 Installation of the Expo CF System 1.1.1 The Expo system should be installed either directly on or as close as possible to the Pressurized Enclosure (PE). It should be installed so that the system indicators may be readily observed. 1.1.2 All parts of any system carry a common serial number. If installing more than one system, ensure that this commonality is maintained on each installation. 1.1.3 Any tubing, conduit and fittings used to connect to the PE should be metallic, or, if non-metallic, conform to the local codes for flammability ratings. No valve may be fitted in any tube connecting the Expo system to the PE. 1.1.4 The user or manufacturer of the PE shall determine the volume of the PE, the necessary purging volume, and the time to be allowed for purging, using the chosen Expo system purging flow rate. It is the user’s responsibility to verify or enter this data on the PE and/or Expo system nameplate. Ask Expo if in doubt. Example calculations: a) If the PE external dimensions give a volume of 20 cubic feet, and it is NOT a motor, multiply the volume by four to get the Purging Volume i.e. 80 cubic feet. Divide the Purging Volume by the purge rate e.g. 32 cubic feet per minute, and round up to the next even minute above, i.e. purging time would be 4 minutes. b) If the PE is a motor, multiply the internal free volume by ten to get the Purging Volume. For the above example, the Purging time would be 8 minutes. 1.1.5 If the PE contains an internal source of release of flammable gas or vapor, the procedures for assessment of the release as given in NFPA 496 shall be observed. The user must verify that the specification of the Expo system e.g. pressures, continuous flow (dilution) rate and type of protective gas are correct for the specific application. 1.1.6 More than one PE can be protected by a single system. If PEs are connected and purged in “series” e.g. “Daisy Chained”, the Outlet Orifice must be fitted on the last enclosure with the Purge Inlet to the first enclosure. The Relief Valve may be fitted at any convenient location except when it has the option code /CF in which case it must be fitted on the last enclosure. The bore and length of the tube or conduit used to interconnect the enclosures is critical and will determine the maximum pressure experienced by the first enclosure in the series. Advice on sizing can be obtained from your Expo Technologies, sales office. The test pressure for all the enclosures Expo Technologies Limited Page 2 of 6 should be 3 times the pressure inside the first enclosure when purging is taking place. If PE’s are to be connected in parallel each enclosure must have its own Outlet Orifice/Spark Arrestor, Relief Valve, Purge Flow Sensor and Pressure Sensor. System “Models” can be mixed e.g. Model LC for one enclosure and Model CF for another. An example would be a Gas Chromatograph instrument. Expo systems with this facility have option code /TW. 1.2 Quality and Installation Pressurizing Air or Inert Gas Supply of the 1.2.1 The source of the compressed air must be in a non-classified area. Inert gas may be used as an alternative to compressed air. 1.2.2 Unless a supply shut-off valve has been specially fitted within the Expo system, a valve with the same, or larger, thread size as the Control Unit (CU) inlet fitting shall be fitted externally. In addition, for "Y" and "Z" Pressurization systems, a suitable nameplate shall be provided. 1.2.3 The tubing and fittings used must conform to 1.1.3 above. 1.3 Provision Devices and Installation of Alarm Expo Technologies systems have a Minimum Pressure Sensor set to a pressure of at least 0.1” WC (0.25 mbar). When the PE pressure is above this set point the Sensor produces a positive "Pressurized" signal. This is displayed on the Red/Green indicator. This signal can be used to operate an electrical contact for a remote “Alarm”. The pneumatic signal may be supplied either a) to a pressure operated switch (MiniPurge Option Code /IS) suitable for an Intrinsically Safe circuit, in accordance with Expo drawing EP80-2-11 (or for a Non-Incendive circuit in Division 2), or b) to a bulkhead fitting where it is available to the user (MiniPurge Option Code /PO). It can then be used to operate an external electrical switch either local e.g. explosionproof, or remote in a nonclassified area. When the enclosure pressure falls below the set point of the Sensor, the "Pressurized" signal is removed, i.e. the absence of the signal indicates an “Alarm” ("Pressure Failure") condition. If the system “Alarm” indicator is not located in a place where it can be readily observed, the user must make use of this external alarm facility in accordance with NFPA 496 requirements. Example: The "Pressurized" signal can be used to produce an "Alarm" action by means of a conventional "pressure switch" set to operate at around 15 psi (1 bar). The "Pressurized" signal from the CU at 30 psi (2 bar) or more will hold the switch in the operated position until the CU detects a low pressure in the PE and removes the "Pressurized" ML383 issue 03 – 09.01.13 signal. The Alarm switch will reset and its contacts can be used to operate a remote electrical alarm. 1.4.4 No valves are permitted between the Power Switch and the Expo system. If the switch is located in the hazardous area it must either be part of an Intrinsically Safe circuit, or be suitably protected e.g. explosionproof. The pressure switch should be IS or explosionproof even if it is fitted within the PE. 1.4.5 For "X" Pressurization, the PE door shall have fasteners that can be opened only by the use of a tool or key. Otherwise the additional requirements from NFPA 496 should apply. Expo Technologies Tip: Exception: For a “Z Purge” system fitted in a Division 2 area a non-classified switch inside the PE can be used to operate a remote Alarm provided its electrical supply comes from within the PE (i.e. NOT PROVIDING DRY CONTACTS). When the PE is in use the Alarm can operate normally in response to the pneumatic signal from the CU with option /PO. When the PE is switched off there is no need for an alarm! Ask Expo for the circuit diagram. The Alarm switch can also be located in a nearby non-classified location. To get the best response time the switch should be as close as possible to the CU and the maximum length of tubing between the CU and the Alarm switch should not exceed 150 feet (45 m) unless “Quick Exhaust Valves” are used (please ask Expo if in doubt.) Note: No valves may be fitted between the Expo system and the alarm switch. Note: The door switch provided with the Expo system (when requested) can be either pneumatic or electric. 1.5 Marking 1.5.1 The MiniPurge system carries a nameplate and a specification sheet, which give specific data such as serial and models numbers, Pressure Sensor settings, flow rates and purge time. 1.5.2 Other marking, for the PE, required by the standard includes: “WARNING - PRESSURIZED ENCLOSURE This enclosure shall not be opened unless the area is known to be free of flammable materials or unless all devices within have been deenergized" "Power shall not be restored after the enclosure has been opened until the enclosure has been purged for___minutes at a flow rate of___." 1.4.1 All power entering the PE shall be provided with a means of isolation. This requirement also applies to any external power sources that are connected to "dry contacts" or "volt-free contacts" within the PE. Expo note: It is understood that NFPA 496 requires the de-energization of all devices that are not suitable for the hazard e.g. devices that are not Explosionproof or Intrinsically Safe. For example, an explosionproof anti-condensation heater would not have to be de-energized. Exception: Power to Intrinsically Safe, or other apparatus, which is already suitable for the location need not be isolated by the Expo Technologies system. 1.5.3 If Inert Gas is used as the Protective Gas and a risk of asphyxiation exists, a suitable warning plate should be fitted to the PE. 1.4 Power Supplies and their Isolation Expo Technologies Tip: It is recommended to fit dry or volt-free contacts in the non-classified area or inside an explosionproof box rather than inside the PE. Please ask Expo about “MiniPurge Interface Units” (MIU). In the case of "X" Pressurization, the isolation of the power must be controlled by the Expo system using the "Purge Complete" pneumatic signal to operate a "Power Switch" in a similar manner to that described in 1.3 above. In the case of "Y" or "Z" Pressurization the power may be controlled manually by the operator using a local isolating switch. 1.4.2 In accordance with NFPA496 ; Expo Mini-X-Purge systems can have the "Action on Pressure Failure" (normally "Alarm and Trip") adjusted by the user to "Alarm Only". In case of an alarm, it is the responsibility of the user to de-energize the protected equipment as soon as possible. The system may require the addition of an “Alarm Only Kit” (/AO) to perform this function. Please contact Expo Sales office for further details. 1.4.3 The Power (cut-off) Switch must be approved for the location or located in a non-classified area. Expo Technologies Limited Page 3 of 6 Section 2 Operation of the System 2.1 Check that the system has been installed in accordance with Section 1 of this manual. 2.2 Disconnect the supply pipe from the inlet to the Control Unit (CU) and blow clean air through for at least 5 seconds per foot of length (15 sec/metre) to remove any debris, oil and condensation. 2.3 Connect a temporary pressure gauge or liquid manometer to the PE or CU “Pressure Test Point” (on the Low Pressure Sensor, by the removal of the Red plug - 4mm OD nylon tube). 2.4 Open the supply shutoff valve. On "X" Purge systems check that the internal gauge reads 30 psi (2 bar). If not, adjust the logic pressure regulator to suit (lift the red ring to unlock the knob first.) 2.5 Adjust the Flow Control Valve (FCV) so that the enclosure pressure rises to the point where the "Pressurized" indicator turns Green. 2.6 Continue to raise the PE pressure until the Relief Valve (RLV) opens. Verify that the RLV opens at or below the figure specified in the documentation. Repeat the test several times. ML383 issue 03 – 09.01.13 2.7 Lower the PE pressure until the "Pressurized" indicator turns Red. Verify that the indicator turns Red at or above the pressure specified in the documentation. Check the external alarm contacts (if fitted). Note: On Expo CF systems the Minimum Pressure Sensor set point may be significantly above the minimum of 0.1"WC (0.25 mbar) since it doubles as both the Pressure and the Purge Flow Sensor Set points of 1"WC (2.5 mbar) are common. Please check the documentation for the actual setting. 2.8 Open the FCV again and set the PE pressure to a level somewhere between the Minimum Pressure Sensor set point and the RLV opening pressures. This "working" pressure is not critical. Enough pressure to keep the “Pressurized” indicator Green is sufficient. 2.9 On "X" CF Purge systems the purge timer will start as soon as the “Pressurized” indicator turns Green. Check that the time delay between the indicator turning Green and the application of power to the PE is not less than the minimum time required to purge the PE. Times in excess of the minimum are permitted and a tolerance of +25% is normally acceptable. If the time is shorter than the minimum permitted, it must be adjusted accordingly. MiniPurge uses a pneumatic incremental timer which is adjusted by fully opening or closing one or more of five screwdriver-operated valves, arranged in a block on the control logic manifold – see GA Drawing. The opening of each valve incrementally provides a fixed number of minutes of purging time as in the following table Valve: 1 2 3 4 5 Minutes: 2 4 8 8 16 Section 3 Maintenance of the System The maintenance recommended for the system consists of the following, supplemented by any additional local requirements imposed by the authority having jurisdiction. 3.1 Initial Maintenance Expo recommends that the commissioning test be repeated at least every six months. They include checking the opening pressure of the Relief Valve, setting of the Minimum Pressure Sensor, the "Normal Working Pressure" of the enclosure and, for "X" Purge systems, the setting of the purge timer (as described in Section 2 of this manual). In addition, the following recommended at that time: checks are also - Check the RLV and any other Spark Arrestors. Remove any debris or corrosion, or replace the Spark Arrestor with a spare. - Check the condition of the air supply filter element. Clean or replace it as necessary. 3.2 Routine Maintenance At least every two years, the following additional checks are recommended: Thus for a 12 minute purge time, valves 2 and 3 would be open and the others closed. For twenty-four minutes, 4 and 5 would be open and the others closed. At least one valve must always be open and the screws must be at the appropriate limit of travel. 2.10 On “Y” and “Z” Purge systems the purge timing and power control is performed manually by the user. Never turn on the power without purging first, unless you have proved that the interior of the PE is gas free and checked that the “Pressurized” indicator is green! 2.11 On "X" CF Purge systems, once the purge time is completed the “Purge Complete” indicator turns Green. With both indicators Green, the power will be turned on by the CU. Using the FCV reduce the PE pressure to the point where both indicators turn Red and check that the power is automatically turned off. When the PE pressure is restored the system should re-purge the PE before power is once again turned on. 2.12 After initial commissioning, the system is ready for normal operation: a) “X” CF Purge systems: Turn the air supply valve On or Off to start or stop the system. After this, the Pressurizing and Purging sequence is entirely automatic. b) “Y” and “Z” Purge systems are started and stopped in the same way as “X” Purge system but the user must Expo Technologies Limited close the Power Switch only after the enclosure has been pressurized and purged sufficiently to ensure that the interior of the enclosure is gas free. The power should be shut off as soon as possible after a pressure failure. This is also the user’s responsibility. Page 4 of 6 - Apparatus is suitable for the Hazardous Location - There are no unauthorised modifications - The source of air is uncontaminated - The interlocks and alarms function correctly - Approval labels are legible and undamaged - Adequate spares are carried - The action on pressure failure is correct Section 4 4.1 Fault Finding for CF Systems General If the system does not behave in the manner described above there is a fault. Some of the more likely faults are dealt with below. If a cure cannot be effected by following the procedure shown below, please call Expo (24 hour answering) or your supplier for further assistance. The system has been designed for ease of fault finding and many of the components fitted are plugin or sub-base mounted. Check components by substitution only after establishing that such action is necessary. If the system is less than 12 months old, parts under warranty should be returned to Expo Technologies for investigation, with a full report of the fault and the system serial number. ML383 issue 03 – 09.01.13 As with any pneumatic system the greatest enemies are water, oil and debris in the air supply. For this reason a dust and water filter may be fitted. But debris can enter from other sources and it is vital therefore that the procedures described in Section 2 are carried out before using the system for the first time, or following any disconnection of the pipework. Failure to perform this work may cause damage which will not be covered under warranty. Fault Finding NOTE: Before making the following checks verify that the main supply pressure is between 60 and 115 psi (4-8 bar) at the Control Unit (CU) and, for “X” Purge systems, the regulated pressure on the logic gauge is 30 psi (2 bar) 4.3 Relief Valve Opens (Continuously or Intermittently) Possible Cause 1: The PE pressure is too high. The Flow Control Valve (FCV) is too far open. Adjust the FCV as described in Section 2 above. Possible Cause 2: Debris on the RLV disk allowing air to leak from the valve. Remove the RLV cover and clean the valve disk. The disk and spring may be removed from the RLV without affect the calibration. 4.4 System Fails to Switch Power On after the Purge Time has Elapsed? (“X” Purge Systems Only) 4.2 Minimum Pressure Alarm is ON Continuously (“Pressurized” Indicator is Red) Possible cause 1: Is power available? Is the power disconnect closed? Are the fuses or circuit breaker OK? Possible cause 1: The PE pressure is too low. Try increasing the setting of the Flow Control Valve (FCV) to raise the pressure in the PE. Possible cause 2: System fault? Timer not timed out? Possible cause 2: Enclosure fault? - Is the ACTUAL PE pressure below the setting of the Minimum Pressure Sensor? Check it with a manometer or gauge. - Is the Outlet Orifice (if separate from the RLV) fitted correctly? - Is debris stuck on the face of the Relief Valve disk, holding the valve open? - Has the PE door been closed and all conduit/cable glands sealed? Possible cause 3: Insufficient purging Flow due to inadequate air supply pressure. Check the air supply pressure at the inlet to the CU when flow is taking place. Excessive pressure drop in the supply pipe is a very common cause of this problem. The supply pipe must be at least as big as the CU inlet fitting, i.e. at least ½” NB. Possible cause 4: Excessive PE leakage. Check around the PE when flow is taking place. Any significant leakage must be cured. Has a Leakage Test been done? The total leakage should not exceed 10% of the Continuous Flow rate. Possible cause 5: PE not strong enough. Repeat the PE pressure test. FM recommend that the PE is tested to three times the Relief Valve opening pressure e.g. 12”WC (30 mbar) for standard systems. Has this test been done? Possible cause 6: System fault? Has the pressure sensing tube been damaged? If checks above reveal that the PE is correct the fault probably lies in the CU. The basic operation of the Minimum Pressure Sensor can be checked by unscrewing the 2.4” diameter diaphragm and, by using a finger, blocking the threaded hole in the top of the valve module. The valve should operate and the indicator should turn Green. If this works correctly and the enclosure pressure is above the setting of the Minimum Pressure Sensor it is likely that the Pressure Sensor diaphragm needs re-calibrating or replacing (See 4.5). Expo Technologies Limited Page 5 of 6 a) Has the “Pressurized” indicator been Green for the whole of the purge time? b) Is the logic pressure gauge at 30 psi (-0, +10%) c) Is there pressure at the Power Switch output bulkhead and at the Power Switch itself? Is the Switch set at 15 psi? d) Is the pipe to the Power Switch airtight? The signal to the Power Switch bulkhead has a restrictor that limits the permissible leakage from the pipe. e) Note the timer setting and reduce the time down to a low setting to check operation on a short purge time. If it works OK, gradually increase the time until either the time is correct, or it ceases to time out at all. In the latter case, there is an air leak in the timer circuit. If possible establish the source of the leak with soapy water and retest the system. This will involve removing the chassis from the CU –be sure this is the cause before starting the work. It is VERY unusual!! Ensure that the timer is returned to its original setting and the purge time checked before putting the system back into service. Possible cause 3: Faulty Power Switch. Check the operation of the Power Switch. It should close above 20 psi (1.4 bar). 4.5 Pressure Sensor Calibration If it is decided that the Minimum Pressure Sensor needs recalibrating it can either be returned to Expo Technologies for this service or it can be done by the user as follows: Disconnect the pressure sensing pipe from the top of the diaphragm. (It is a “push-in” quick release fitting; firmly push inwards the collar surrounding the pipe where it enters the fitting and then pull the pipe outwards while maintaining the pressure on the collar). Unscrew the 2.4” (60mm) diameter diaphragm housing from the top of the Sensor. Invert it and note the brass adjusting screw in the ML383 issue 03 – 09.01.13 centre. Turning the screw inwards (clockwise) will lower the setting. It is likely that the screw will be very stiff due to the locking sealant. If the screw cannot be moved the application of gentle heat in the area of the brass screw can often help. DO NOT OVERHEAT! 4.6 Filter Cleaning If the filter element needs cleaning the transparent bowl can be unscrewed and removed. The filter element also unscrews and can then be cleaned in soapy water. Do not use solvents on any part of the filter assembly. Expo Technologies Tip: If the bowl is very tight, it is easier to remove the filter by undoing the fitting that holds the filter into the CU. On Sub-MiniPurge systems it may be necessary to remove the Minimum Pressure Sensor diaphragm first. Section 5 Annex of Options Fitted Refer to the annexes of this manual for any options fitted as designated by the model code of the system. Expo Technologies Ltd Expo Technologies Inc, Unit 2 The Summit, 9140 Ravenna Road Unit #3, Hanworth Road, Twinsburg, Sunbury-On-Thames, OH 44087, TW16 5DB. UK. U.S.A. Expo Technologies Limited Page 6 of 6 ML383 issue 03 – 09.01.13 ML432 v14 AGE-SW0Z-017 MiniPurge System 4. Certificates SYSTEM *ZCF XBR-8TD0-012 MZ-1CF-17-CL SD7568 XBR-8TD0-010 MZ-1CF-23-GA MZ-1CF-26-GA XBR-8TD0-014 MZ-1CF-02-GA MZ-1CF-01-CL MZ-1CF-01-CT EP80-2-11 SAU25-GA SAU40-GA XSD-ATD0-003 XSD-RTD0-001 sht 1 XSD-RTD0-001 sht 2 Sira Sira INMETRO/TUV FM UL Approval Authority /bp/PO /bp/IS IECEx SIR 07.0027X 01ATEX 1295X TÜV 12.1462X 1X8A4.AE E190061 EXPO11ATEX1200X SC020 Certificate Number /pm/PO /pm/IS Consult the appropriate drawings according to the selected system. 3. Drawings /nm/IS /nm/PO /ss/IS 25-Nov-14 /ss/PO DO NOT SCALE DIMENSIONS IN mm UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH PAO PAO PAO CDM CHK'D DR'WN 1 2 3 4406 4442 DRAWN 05/01/04 08/02/08 18/3/08 MLC MLC PAO DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: * /PO option shown 5979 25/11/13 SM 4 FINISH MATERIAL SELECT ORIFICE NOTE: Spark arrestors are only used in CF systems. APP'D 1. 2. 3. 4. RE L VA IEF LV E JOB No: CUSTOMER: Z(Y)CF & DP /bp QUICK INSTALLATION GUIDE TITLE TW16 5DB Expo Technologies Limited SURREY UNITED KINGDOM S RE PAR ST K OR AR W FLO OL R NT LVE O C VA OL TR N O IT * C UN NTS SHEET No. 1 OF XBR-8TD0-012 DRAWING No. SCALE D IZE R SU RE ES OSU R P CL EN 1 The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. With aid of supplied mounting template cut mounting holes into the enclosure. Fix MiniPurge Control Unit to enclosure. Fix Relief Valve to enclosure. For CF systems only, select orifice for required purge flow rate and fit into Spark Arrestor with circlip. Fix Spark Arrestor to enclosure ensuring that Control Unit and Spark Arrestor Unit are diagonally opposing. 5. Connect Output option, /IS or /PO as required, refer to manual. 6. Connect isolated air supply to MiniPurge Control Unit 7. Ensure enclosure door is closed and sealed from leaks. 8. Turn on air supply 60 psig (4 barg). 9. Slowly increase Flow Control Valve until Alarm Indicator turns from RED to GREEN. 10. After Purge time has been completed power can be applied to enclosure. 11. All queries refer to manual for assistance in the first instance. Quick Installation Guide FOR CF or DP systems: 3rd ANGLE PROJECTION DR'WN CHK'D APP'D DO NOT SCALE DIMENSIONS IN mm DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: 1X DP/bp/PO 1Z DP/bp/PO 1Z DP/bp/IS 1Z(Y)CF/bp/PO 1Z(Y)CF/bp/IS FINISH MATERIAL JOB No: TITLE CUSTOMER: SURREY KT7 0RH UNITED KINGDOM IS PRESSURE SWITCH (IS OPTION) PLUG 4mm (PE TEST POINT) Expo Technologies Limited 50 26 SENSOR, MINIMUM PRESSURE INDICATOR "ALARM/PRESSURIZED" 8 14 FLOW CONTROL VALVE 17 PURGE AIR INLET 1/4"NPTF 8 26 17 14 SHEET No. DRAWING No. SCALE OF The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. 50 ENCLOSURE PRESSURE 1/8"NPTF UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH 1. APPLICABLE MODEL NUMBERS: NOTES: ALARM/PRESSURIZED OUTPUT 1/8" NPT(F) (PO OPTION) PURGE ENCLOSURE OUTLET 1/8"NPTF FLOW CONTROL VALVE ENCLOSURE LOW PRESSURE ALARM/PRESSURIZED PURGING INDICATOR 3rd ANGLE PROJECTION DO NOT SCALE DR'WN CHK'D APP'D 10 [0.39"] DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: 56 [2.19"] 4 OFF M6 SCREWS FOR MOUNTING SYSTEM 197 [7 3/4"] 132 [5.19"] ENCLOSURE PRESSURE 1/8" NPT(F) MATERIAL FINISH CERTIFICATION LABEL NOTES: 112 [4.41"] JOB No: TITLE CUSTOMER: Expo Technologies Limited 1X DP/bp/PO 1Z DP/bp/PO 1Z DP/bp/IS 1Z(Y)CF/bp/PO 1Z(Y)CF/bp/IS SURREY KT7 0RH UNITED KINGDOM 2. APPLICABLE MODEL NUMBERS: 1. APPROX WEIGHT: 2kg (4.4 lbs) 10 [0.39"] 91 [3.58"] 66 [2.60"] CUTOUT DETAIL SHEET No. DRAWING No. SCALE 4 OFF ø7 (9/32") HOLES 2 OFF ø25 (1") HOLES OF The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. ENCLOSURE PURGING INDICATOR: LOW PRESSURE ALARM (RED) PRESSURIZED(GREEN) FLOW CONTROL VALVE INDICATOR LABEL PURGE AIR INLET 1/4" NPT (F) UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH 112 [4.41"] 101 [3.98"] 76 [2.99"] 76 [2.99"] 38 [1.50"] PURGE ENCLOSURE OUTLET 1/8" NPT(F) ALARM/PRESSURIZED OUTPUT (PO OPTION) 1/8" NPT(F) [0.39"] GASKET Ex nA-NI OR I.S. ALARM PRESSURE SWITCH (IS OPTION - SEE DRAWING EP80-2-11 Fig 1a) 55 [2.17"] 10 79 [3 15/32"] 127 [5"] 31 55 [2.17"] 14 [0.54"] DIMENSIONS IN mm 34 [1.35"] 3rd ANGLE PROJECTION [1.20"] 9 [0.37"] DO NOT SCALE DIMENSIONS IN mm PAO PAO PAO CDM APP'D CHK'D DR'WN 1 2 3 4406 4442 DRAWN 23/12/03 08/02/08 18/3/08 MLC MLC SM DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: 5979 25/11/13 SM 4 FINISH MATERIAL SELECT ORIFICE NOTE: Spark arrestors are only used in CF systems. With aid of supplied mounting template cut mounting holes into the enclosure. 2. Fix MiniPurge Control Unit to enclosure [use 1/4" (6 mm) Nut and Bolt]. 3. Fix Relief Valve to enclosure. 4. For CF systems only, select orifice for required purge flow rate and fit into Spark Arrestor with circlip. Fix Spark Arrestor to enclosure ensuring that Control Unit and Spark Arrestor Unit are diagonally opposing. 5. Connect Output option, /IS or /PO as required, refer to manual. 6. Connect isolated air supply to MiniPurge Control Unit 7. Ensure enclosure door is closed and sealed from leaks. 8. Turn on air supply 60 psig (4 barg). 9. Slowly increase Flow Control Valve until Alarm Indicator turns from RED to GREEN. 10. After Purge time has been completed power can be applied to enclosure. 11. All queries refer to manual for assistance in the first instance. 1. F LIE RE LVE VA A CUSTOMER: Z(Y)CF&DP/pm QUICK INSTALLATION GUIDE JOB No: TITLE TW16 5DB Expo Technologies Limited SURREY UNITED KINGDOM PR ES EN SUR C L IZ OS ED UR E T NTS NI VE AL SHEET No. 1 OF XBR-8TD0-010 DRAWING No. SCALE N CO U OL TR W LV FLO TRO N CO 1 The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. K AR SP TOR ES RR UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH Quick Installation Guide FOR CF or DP systems: 3rd ANGLE PROJECTION DR'WN CHK'D APP'D DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: FINISH MATERIAL PURGE OUTLET 1/2" NPT (F) 5 OFF M4 MOUNTING HOLES: SCREWS AND SEALOC WASHERS SUPPLIED BY EXPO. I.S. ALARM PRESSURE SWITCH (SEE DRAWING EP80-2-11) (IS OPTION) 50 PASSIVE ALARM/PRESSURIZED OUTPUT 1/8"NPT(F) (PO OPTION) 8 26 17 ENCLOSURE PRESSURE 1/8" NPT (F) 15 JOB No: TITLE FLOW CONTROL VALVE PURGE AIR/INERT GAS SUPPLY 1/2" NPT (F) CUSTOMER: SURREY KT7 0RH UNITED KINGDOM SHEET No. DRAWING No. SCALE OF NOTES: 1. SUB MINI-Z-PURGE / SUB MINI-Y-PURGE MUST BE MOUNTED IN THE ATTITUDE SHOWN. 2. APPROX WEIGHT: 1.4 Kg (3 POUNDS) 3. EQUIVALENT IMPERIAL DIMENSIONS ARE SHOWN IN BRACKETS 4. APPLICABLE MODEL NUMBERS: 1Z(Y)CF/nm/IS 1Z DP/nm/IS 1X DP/nm/PO 1Z(Y)CF/nm/PO 1Z DP/nm/PO I.S. PRESSURE SWITCH (PO OPTION) FLOW CONTROL VALVE 17 50 FILTER, MANUAL DRAIN 15 PLUG 4mm (PE TEST POINT) SENSOR, MINIMUM PRESSURE 14 26 INDICATOR "ALARM/PRESSURIZED" SYSTEM BREATHER DO NOT OBSTRUCT 8 HINGES FITTED The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. Expo Technologies Limited = = 114 [4 31/64"] CL 165 [6 1/2"] 14 180 [7 3/32"] 240 [9 29/64"] UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH ENCLOSURE LOW PRESSURE ALARM (RED) PRESSURIZED (GREEN) PURGING INDICATOR DO NOT SCALE DIMENSIONS IN mm 37 [1 29/64"] 3rd ANGLE PROJECTION 95 [3 47/64"] 16 [5/8"] 110 [4 21/64"] DO NOT SCALE DIMENSIONS IN mm UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH PAO PAO PAO CDM CHK'D DR'WN 1 2 3 4406 4442 DRAWN 12/01/04 08/02/08 18/3/08 MLC MLC PAO DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: 5979 25/11/13 SM 4 FINISH MATERIAL SELECT ORIFICE NOTE: Spark arrestors are only used in CF systems. APP'D 1. 2. 3. 4. A PR ES EN SUR C L IZ OS ED UR E JOB No: CUSTOMER: Z(Y)CF & DP/ss QUICK INSTALLATION GUIDE TITLE TW16 5DB Expo Technologies Limited SURREY UNITED KINGDOM F LIE RE LVE VA K AR SP TOR ES RR NI T NTS SHEET No. 1 OF XBR-8TD0-014 DRAWING No. SCALE CO NT RO LU 1 The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. With aid of supplied mounting template cut mounting holes into the enclosure. Fix MiniPurge Control Unit to enclosure. Fix Relief Valve to enclosure. For CF systems only, select orifice for required purge flow rate and fit into Spark Arrestor with circlip. Fix Spark Arrestor to enclosure ensuring that Control Unit and Spark Arrestor Unit are diagonally opposing. 5. Connect Output option, /IS or /PO as required, refer to manual. 6. Connect isolated air supply to MiniPurge Control Unit 7. Ensure enclosure door is closed and sealed from leaks. 8. Turn on air supply 60 psig (4 barg). 9. Slowly increase Flow Control Valve until Alarm Indicator turns from RED to GREEN. 10. After Purge time has been completed power can be applied to enclosure. 11. All queries refer to manual for assistance in the first instance. Quick Installation Guide FOR CF or DP systems: 3rd ANGLE PROJECTION 58 [2.28"] DO NOT SCALE JTP JTP BRD CHK'D DR'WN 1 5 6 7 CERT RELATED FINISH MATERIAL 35 [1.38"] 240 [9 29/64"] 180 [7.09"] MOUNTING HOLES 85 [3.35"] MiniPurge 180 [7 7/64"] 150 [59/64"] OUTLET POINTING DOWNWARDS. JOB No: 6 [0.24"] SYSTEM BREATHERDO NOT OBSTRUCT 1Z DP/ss/IS 1Z(Y)CF/ss/PO 1ZDP/ss/PO 1Z(Y)CF/ss/IS CUSTOMER: MINIPURGE 1Z(Y)CF&DP/ss/IS & PO N.T.S SHEET No. 1 OF 1 MZ-1CF-02-GA DRAWING No. SCALE 1X DP/ss/PO APPLICABLE MODEL NUMBERS 4. WALL MOUNTING BRACKETS ARE OPTIONAL. 3. USE DIRECT MOUNTING WHEREVER POSSIBLE. TW16 5DB Expo Technologies Limited SURREY UNITED KINGDOM TITLE PURGE AIR/INERT GAS SUPPLY 1/2"NPT(F) PASSIVE ALARM "PRESURIZED" OUTPUT 1/8" NPT(F)GAS SUPPLY (PO OPTION) THE MINIPURGE MUST BE MOUNTED WITH THE PURGE 2. APPROX WEIGHT: 5 kg (11 lbs) 1. NOTES: ENCLOSURE PRESSURE 1/8"NPT(F) CERTIFICATION LABEL 77 [3.03"] 20 [0.79"] ENCLOSURE LOW PRESSURE ALARM (RED)/ PRESSURIZED (GREEN) PURGING INDICATOR The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. 210 [8.27"] MOUNTING HOLES INDICATOR LABEL 3955 4406 5952 DRAWN 03/03/1995 01/03/05 08/02/08 16/10/13 HE MLC SM JTP DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: PURGE OUTLET 1/2"NPT(F) MOUNTING BAR (SPECIAL OPTION ONLY) CABLE ENTRY SUITABLE FOR M20 GLAND (GLAND NOT SUPPLIED) (IS OPTION) APP'D 28 [1.10"] UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH 230 [9.06"] DIMENSIONS IN mm 65 [2.56"] 3rd ANGLE PROJECTION 75 [2.95"] 130 [5.12"] DR'WN CHK'D APP'D DIMENSIONS IN mm SENSOR, MINIMUM PRESSURE FILTER, MANUAL DRAIN FLOW CONTROL VALVE PLUG 4mm (PE TEST POINT) I.S. PRESSURE SWITCH (IS OPTION ONLY) 14 15 17 26 50 FINISH MATERIAL INDICATOR "ALARM/PRESSURIZED" 8 15 BLACK COLLAR (PLUGGED) 14 26 7 7 DOOR INTERNAL JOB No: CUSTOMER: Expo Technologies Limited SURREY KT7 0RH UNITED KINGDOM NOTES: 1. APPLICABLE MODEL NUMBNERS: 1Z(Y)CF/ss/IS 1Z(Y)CF/ss/PO 1Z DP/ss/IS 1Z DP/ss/PO 1X DP/ss/PO 8 SHEET No. DRAWING No. SCALE OF The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. TITLE UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH ENCLOSURE PRESSURE TEST POINT DO NOT SCALE 17 DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: 50 3rd ANGLE PROJECTION DR'WN CHK'D APP'D DRAWING STATUS: APPROVED: DATE: 26 1 3 2 50 8 FINISH MATERIAL JOB No: TITLE CUSTOMER: Expo Technologies Limited /IS OPTION IS SWITCH /PO OPTION MINIMUM PRESSURE & PURGING INDICATOR RED = ALARM GREEN = PRESSURE OK PURGE OUTLET TO PRESSURIZED ENCLOSURE ENCLOSURE PRESSURE 7 15 FILTER (OPTIONAL) SURREY KT7 0RH UNITED KINGDOM ALARM CONTACT SHEET No. DRAWING No. SCALE OF PASSIVE ALARM / PRESSURIZED" SIGNAL 60-115 PSI (4-8 barg) PURGE SUPPLY AIR OR INERT GAS 60 psig (4 barg) - MAX 115 PSI (8 barg) The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. MINIMUM 14 PRESSURE SENSOR UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH ENCLOSURE PRESSURE TEST POINT (PLUGGED) DO NOT SCALE DIMENSIONS IN mm FLOW CONTROL VALVE MOD. No: ISSUE: 17 3rd ANGLE PROJECTION Vmax = 30V Imax = 100mA Ci = 0 Li = 0 Unit Outputs e.g. to relays or power contactors. PCB Pt# S108/* (* = configuration) MOD NUMBER 4330 5076 5297 REV. 4 05 06 20/07/2011 01/11/2010 13/7/2007 APPROVED DATE AMO AMO MLC APPROVED DR'WN AMO CHK'D AMO APP'D AMO Certified 13/07/2007 DRAWING STATUS: DRAWN DATE: THIS IS A CERTIFICATION DOCUMENT. ANY UNAUTHORISED CHANGE INVALIDATES APPROVAL. Alternatively: For Gas Group A, B with Vpeak = 19.2V Imax for I.S. is 350mA. 6 For Gas Groups A, B permitted Imax for I.S., for V peak = 30V is 101 mA 5 "Simple Apparatus" is a device that will not generate or store more than 1.2V, 0.1A, 25mW or 20uJ Li plus inductance of interconnecting cabling is less than La of the associated apparatus Ci plus capacitance of interconnecting cabling is less than Ca of the associated apparatus Isc or It of associated apparatus is less than Imax 4 Voc or Vt of associated apparatus is less than Vmax SURREY KT7 0RH Simple Apparatus Connection for Manual Override Switch (dry contact) Vmax = 0V, Imax = 0A, Ci = 0, Li = 0 Vmax = 30V Imax = 100mA Ci = 0 Li = 0 JOB No: TITLE CUSTOMER: MINIPURGE OPTION 'IS' Expo Technologies Limited UNITED KINGDOM 3 For guidance on Installation see ANSI/ISA RP12.6, (Installation of IS Instrument Systems in Class I Hazardous Locations) M 0 2 1 + Hazardous Location Class I or II, Div 1 or 2 Groups A, B, C, D, E, F and G MiniPurge: Option Code /IS Fig 1b Multi-channel interface circuit e.g. "X" pressurization Alarm & Power Control Unit Interface I.S. NTS SHEET No. 1 OF 1 06 REV: EP80-2-11 DRAWING No. SCALE Outputs e.g. to relays or power contactors. Power supply (or suitably protected apparatus) Non-Hazardous Location The contents of this drawing / document are Copyright © Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. 2 Installation shall be in accordance with the manufacturer's instructions and the National Electrical Code (ANSI/NFPA 70) 1 Electrical equipment connected to associated apparatus should not use or generate more than 250 volts Notes for both Fig 1a and Fig 1b Simple apparatus device Interface I.S. Power supply (or suitably protected apparatus) Non-Hazardous Location Fig 1a Single channel interface circuit e.g. "Y" or "Z" Pressurization Alarm circuit DO NOT SCALE DIMENSIONS IN mm Hazardous Location Class I or II, Div 1 or 2 Groups A, B, C, D, E, F and G MiniPurge: Option Code /IS 3rd ANGLE PROJECTION DR'WN CHK'D DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: FINISH MATERIAL DECIDE UPON THE REQUIRED FLOW RATE. SELECT THE REQUIRED ORIFICE PLATE. INSTALL THE PLATE IN THE SPARK ARRESTOR BODY AND RETAIN WITH THE CIRCLIP. i ii iii APP'D ASSEMBLY INSTRUCTIONS: 3 THE FLOW RATE OF THE CONTINUOUS FLOW SYSTEM MAY BE CHOSEN BY THE USER BY SELECTING THE REQUIRED ORIFICE PLATE. FOR RANGE OF FLOW RATES SEE TABLE OF VALUES OPPOSITE. FLOW RATE SELECTION: EXPO PART No. SAU25 RECOMMENDED MOUNTING HOLE ø26 [1"] WEIGHT: 0.25kg [0.55lb] ø55 [2 5/32"] SELECTION OF ORIFICE PLATE 1.4 3 4.8 6.4 8.0 6 7 8 225 180 135 90 65 40 25 10 Nl/min 0.24 10.5 0.81 1.08 1.35 36 48 60 JOB No: TITLE CUSTOMER: SHEET No. DRAWING No. SCALE * VC = VOLUME CHANGES (BASED ON 30min PURGE TIME) OF Nl/min =NORMAL LITRES/MINUTE scfm = STANDARD CUBIC FEET/MINUTE SURREY KT7 0RH UNITED KINGDOM 0.54 24 0.39 0.15 8.3 17.2 0.06 m³ (5VC*) 3.0 ft³ (4VC*) ENCLOSURE VOLUME Expo Technologies Limited 3.2 5 2.3 0.9 2 4 0.4 1 scfm PURGE FLOW BASED ON A PURGE SUPPLY OF 4 barg [60 psi] & ENCLOSURE PRESSURE OF 2.5 mbarg [1" WC] ORIFICE PLATE No WASHER RETAINING NUT ORIFICE PLATE & CIRCLIP (SEE NOTE 2) GASKET PART SECTION THRU SPARK ARRESTOR BODY SPARK ARRESTOR BODY The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. TO SUIT PANEL THICKNESS 1.5 [1/16"] MINIMUM 9.5 [3/8"] MAXIMUM 2 25 [1"] 35 [1 3/8"] UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH TO ENSURE EFFECTIVE PURGING THE SPARK ARRESTOR SHOULD BE LOCATED ON THE PRESSURIZED ENCLOSURE AS FAR AWAY AS PRACTICABLE FROM THE PURGE AIR INLET. DO NOT SCALE DIMENSIONS IN mm 1 NOTES: 3rd ANGLE PROJECTION M25 x 1.5P DR'WN CHK'D APP'D DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: FINISH MATERIAL JOB No: TITLE 60.0 75.0 97.5 120.0 1.35 1.65 2.19 2.70 ENCLOSURE VOLUME ft³ (4VC*) m³ (5VC*) CUSTOMER: SHEET No. DRAWING No. SCALE FIT THE ORIFICE PLATE IN THE SPARK ARRESTOR BODY AND RETAIN WITH THE CIRCLIP. SELECT THE REQUIRED ORIFICE PLATE. USE THE TABLE ABOVE TO CHOOSE THE REQUIRED FLOW RATE. ASSEMBLY INSTRUCTIONS: TW16 5DB Expo Technologies Limited SURREY UNITED KINGDOM (c) TO ENSURE EFFECTIVE PURGING THE SPARK ARRESTOR SHOULD BE LOCATED ON THE PRESSURIZED ENCLOSURE AS FAR AWAY AS PRACTICABLE FROM THE PURGE AIR INLET. 3. RECOMMENDED MOUNTING HOLE ø41 [158" DIA] (b) EXPO PART CODE : MSK-S000-020 2. 4. (a) WEIGHT: 0.25kg [0.55lb] 225 275 365 450 PURGE FLOW Nl/min scfm 8 10 13 16 Nl/min =NORMAL LITRES/MINUTE scfm = STANDARD CUBIC FEET/MINUTE * VC = VOLUME CHANGES (BASED ON 30min PURGE TIME) 1 2 3 4 ORIFICE PLATE No BASED ON A PURGE SUPPLY OF 4 barg [60 psi] AND ENCLOSURE PRESSURE OF 2.5 mbarg [1" WC] SELECTION OF ORIFICE PLATE FOR CF SYSTEMS OF The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. ] 2" 1. M40 NUT ORIFICE PLATE AND CIRCLIP 17.5 [11/16"] 1.5 [1/16"] MINIMUM 9.5 [3/8"] MAXIMUM PANEL THICKNESS UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH /3 NOTES: GASKET SPARK ARRESTOR BODY 60 [2 3/8"] 19.5 [25/32"] DO NOT SCALE DIMENSIONS IN mm AIR/INERT GAS EXHAUST 3rd ANGLE PROJECTION 23 [1 44 DR'WN CHK'D APP'D 3rd ANGLE PROJECTION Y DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: MIN 25 [1"] X DO NOT SCALE DIMENSIONS IN mm FINISH MATERIAL Z RLV36 RLV52 SIZE 2 SIZE 3 JOB No: TITLE CUSTOMER: Expo Technologies Limited RLV25 SIZE 1 MINIPURGE HEIGHT Y SURREY KT7 0RH UNITED KINGDOM SHEET No. DRAWING No. SCALE 110 [4.33"] 185 [7.28"] 37 [1.46"] 88 [3.46"] 170 [6.69"] 33 [1.30"] 62 [2.44"] 133 [5.24"] 28 [1.10"] WIDTH X DEPTH Z OF The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. GASKET 5 [0.20"] BEFORE COMPRESSION UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH 133 [5.24"] DR'WN CHK'D APP'D DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: -0 -0 HOLE ø25 +2 [1" +0.1 ] = 62 [2.44"] = = 44 [1.73"] = DETAIL 'A' RLV25 CUTOUT 46 [1.81"] = = 44 [1.73"] 4 HOLES ø5.5 [7/32"] RLV OUTLINE 170 [6.69"] DO NOT SCALE FINISH MATERIAL 56 [2.20"] 88 [3.46"] = = = JOB No: TITLE CUSTOMER: Expo Technologies Limited -0 -0 HOLE ø36 +2 [1 1/2"+0.1 ] 64 [2.52"] = 4 HOLES ø5.5 [7/32"] RLV OUTLINE = = SHEET No. DRAWING No. SCALE -0 -0 HOLE ø52 +2 [2" +0.1 ] 109 [4.29"] 76 [3.00"] SURREY KT7 0RH UNITED KINGDOM = = DETAIL 'C' RLV52 CUTOUT 4 HOLES ø5.5 [7/32"] RLV OUTLINE The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. DETAIL 'B' RLV36 CUTOUT UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH 185 [7.28"] DIMENSIONS IN mm 65 [2.56"] 3rd ANGLE PROJECTION = 64 [2.52"] = = 76 [3.00"] OF = Address: This equipment and any acceptable variation thereto is specified in the schedule to this certificate and the documents therein referred to. Sira Certification Service, notified body number 0518 in accordance with Article 9 of Directive 94/9/EC of 23 March 1994, certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of equipment intended for use in potentially explosive atmospheres given in Annex II to the Directive. 7 8 29097 Form 9400 Issue 1 This certificate and its schedules may only be reproduced in its entirety and without change. Project Number II 2(2) GD Ex [px] ia IIC T6 Gb Ex [p] ia IIIC T95°C Db (Ta –20oC to +55oC) II 2(3) GD Ex [pz Gc ] IIC T6 Gb Ex [p Dc] IIIC T85°C Db (Ta –20°C to +55°C) Standard /ET versions II 2(2) GD Ex [px] IIC T6 Gb Ex [py] IIC T6 Gb Ex [p] IIIC T85°C Db (Ta –20°C to +55°C) Page 1 of 7 Sira 01ATEX1295X Issue 8 Metal foam Tortuous path with at least 4 x 90°or 2 x 180° bends Multi-layer stainless steel mesh Knitted mesh Threaded Orifices e.g. ¼″ NPT or 2″ BSP with a built in spark arrester. These are selected to maintain a desired back pressure within the Ex p protected apparatus when used with the Continuous Flow options. The designation of each outlet orifice indicates the nominal inlet diameter. The designations are as follows: SA3, SA6, SA9, SA12, SA19, SA25, SA32, SA38 and SA50. Plain holes in the Relief Valve disk, sized according to the flow rate required. Replaceable orifice type SAU**. • • +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Tel: Fax: Email: Web: Form 9400 Issue1 Page 2 of 7 Rake Lane, Eccleston, Chester, CH4 9JN, England +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Tel: Fax: Email: Web: Sira Certification Service Pneumatically Operated Outlet Valve - The pneumatically operated outlet valve is used to positively open or close the outlet of the purged enclosure by means of a spring return pneumatic cylinder. Systems fitted with the Pneumatically Operated Outlet Valve will carry the option OV. High Pressure Sensor for LC Systems (HP code) - If the pressure in the pressurized enclosure rises above the setting of the High Pressure sensor, the purge gas flow is isolated from the pressurised enclosure. The valve isolates both the leakage compensation and the purge streams. On detecting the overpressure, an optional facility is available for the generation of an alarm or indicator. On systems with a High Pressure sensor, the relief valve may be omitted. High Pressure Sensor for CF Systems (HP code) - If the pressure in the pressurized enclosure rises above the setting of the High Pressure sensor, the controller resets cutting the power to the enclosure. On detecting the overpressure an optional facility is available for the generation of an alarm or indicator. On systems with a High Pressure sensor, the relief valve may be omitted. • • • Outlet Orifice - Three types of orifice are used: • • The outlet of each relief valve is fitted with a spark arrestor, of which there are four optional types: RLV3, RLV6, RLV9, RLV12, RLV19, RLV25, RLV26, RLV52, RLV36, RLV75, RLV104, RLV125, RLV150 and RLV200. Relief Valve - The MiniPurge controller is supplied with an optional overpressure relief valve, which is to be fitted to the Ex p protected apparatus to prevent an internal overpressure above the maximum overpressure rating of the apparatus. There are 14 models of relief valve; the designation of each relief valve refers to its nominal bore in mm, as follows: The MiniPurge option pD is for use in combustible dust The MiniPurge control unit may be supplied within a heated enclosure to permit the use of the system within an ambient temperature down to –50oC. LC-Leakage compensation only after initial high purge CF-Continuous flow (same flow rate during and after purging) CF2-Two flow CF system with initial high purge rate only at one orifice CFHP-Continuous (lower) flow after initial high purge The Purge Controllers are pneumatically operated devices, which are intended to provide a given flow rate of purging gas for a predetermined time to unspecified Ex p protected electrical equipment. The MiniPurge Control Units provide one of the following four methods of purge operation. DESCRIPTION OF EQUIPMENT This certificate and its schedules may only be reproduced in its entirety and without change. 13 EC TYPE-EXAMINATION CERTIFICATE SCHEDULE CERTIFICATION Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service C Ellaby Deputy Certification Manager Ex [px] dem ia IIC T3 or T4 Gb Ex [p] ia IIIC T200°C or T135°C Db (Ta –50°C to +55°C) Low temperature /ET versions II 2(2) GD II 2(2) GD Ex [px] dem IIC T3 or T4 Gb Ex [p] IIIC T200°C or T135°C Db (Ta –50°C to +55°C) Low temperature versions The marking of the equipment shall include the following: 12 Standard versions This EC type-examination certificate relates only to the design and construction of the specified equipment. If applicable, further requirements of this Directive apply to the manufacture and supply of this equipment. EN 61241-4: 2006 11 EN 60079-2:2007 If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to special conditions for safe use specified in the schedule to this certificate. IEC 60079-0:2011 Compliance with the Essential Health and Safety Requirements, with the exception of those listed in the schedule to this certificate, has been assured by compliance with the following documents: The examination and test results are recorded in the confidential reports listed in Section 14.2. Unit 2, The Summit, Hanworth Road, Sunbury on Thames, Surrey TW16 5DB UK EXPO Technologies Limited 10 9 Applicant: 8 6 Issue: 5 Sira 01ATEX1295X Purge Controllers: Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X Certificate Number: Equipment: 3 Equipment intended for use in Potentially Explosive Atmospheres Directive 94/9/EC 2 4 EC TYPE-EXAMINATION CERTIFICATE 1 CERTIFICATION Form 9400 Issue1 This certificate and its schedules may only be reproduced in its entirety and without change. Page 3 of 7 Tel: Fax: Email: Web: +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service Model Number Designation for ATEX approved MiniPurge systems a Size or Capacity Model Number: 1 Sub-MiniPurge 2 MiniPurge 1 X LC cs DS SS AA MO FM OA TW 3 Super-MiniPurge Key: 4 Super-MiniPurge 1800 a b cc mm Example option codes 5 Super-MiniPurge 3500 6 Super-MiniPurge 7000 7 Super-MiniPurge xxxx b Pressurization Type X X Pressurization Y Y Pressurization Z Z Pressurization cc Action after initial purging LC Leakage Compensation only after initial High Purge CF Continuous Flow (same flow rate during and after purging) CF2 Two Flow CF system with initial High Purge rate but only one orifice CFHP Continuous (lower) Flow after initial High Purge DP Dust Protection (pressurization only) mm Material of the Control Unit Enclosure al Aluminium alloy cs Mild steel, painted ss Stainless steel bp Back Plate only co Chassis only pm Panel mounting nm Non-Metallic Option codes (Added only if used) AA Active Alarm output fitted. AC Alarm cancellation circuit. AO "Alarm Only" Action on Pressure or Flow Failure. AS Alarm "Action on Pressure or Flow failure", Selector valve. CS Containment System Monitor. DS Door switch Power Interlock fitted. DT Delayed Trip after Pressure or Flow failure. DXXX Special design for specific flow rates ET Electronic Timer FM Flow Meter(s) fitted. HP System LC or CF with High Pressure Sensor IS Internal Switches suitable for Ex i circuits. MO Manual Override fitted. MT Mechanical Timer. OA On/Off switch controlling Protective gas and logic supply. OB On/Off switch controlling logic supply only. OC On/Off switch controlling Protective gas supply only. OS Outlet (Orifice) Selector valve. OV Outlet valve, pneumatically operated. PA "Ex" switch(es) built-in, with/without "Ex" junction box. PC PE Pressure Control Leakage Compensation Valve (CLAPS System.) PO Pneumatic Output signals for Power and Alarm control. SP Secondary Pressurization supply options. SS Separate Supply for Protective gas and Logic air. TW Twin (or more) outputs for two or more separate pressurized enclosures purged in parallel Old Name: Expo Telektron Safety System Limited New name: Expo Technologies Limited A change of the Applicant’s name on the certificate and the substitution of the new name for the old name on the approved label affixed to the purge controllers: Any suitably ATEX, Category 2 approved cable gland may be used, if it can be used with the ambient temperature range. An Ex e terminal box is provided within the main enclosure for connection of the heater leads. This polyester box is manufactured by Bartec and coded Ex e II T6 under BAS 98ATEX3008X. Other alternative ATEX terminal boxes may be used as a replacement if they are suitably certified, carry the same or greater ambient temperature range, occupy the same or smaller physical space, have the same certification code and have the same Temperature Class. RTDs are fitted to the air inlet pipe-work and inside the purge controller enclosure. The enclosure is made from 1.5mm or 2.5 mm thick stainless or mild steel painted and the lid is made from 1.5 mm thick stainless steel, lined with 38 mm thick insulation, or other materials with equivalent insulating properties. The purge inlet, purge outlet and pressure sensing lines are similarly insulated. The door may optionally be hinged with quick release catches, these will be fitted with a padlock. An enclosure breather tube is fitted to help prevent condensation. A plastic clear viewing window may optionally be fitted to the door. The heater (500 W maximum) is manufactured by Intertec-Hess GmbH and coded Ex d m IIC T3 (max) under PTB 02ATEX1041X. If the outer enclosure is reduced in size the power of the heater may be reduced in proportion to the reduction in surface area. Other alternative heaters may be used as a replacement if they are suitably certified, carry the same or greater ambient temperature range, occupy the same or smaller physical space, have the same certification code and have the same or more restrictive Temperature Class. Form 9400 Issue1 II 2(2) G D Page 4 of 7 The ATEX coding is modified to: [Ex pD] II T200°C 21 (Ta = -20°C to +55°C) [Ex pD] II T85°C 21 (Ta = -20°C to +55°C) - Tel: Fax: Email: Web: +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service (used with the low temperature versions) (used with the standard temperature versions) To permit the pressurisation of enclosures for the exclusion of combustible dusts in accordance with IEC61241-4:2001 and modification of the marking to include one of the following: This certificate and its schedules may only be reproduced in its entirety and without change. i. Sira 01ATEX1295X Issue 8 CERTIFICATION The purge controller to be fitted inside an additional, heated, stainless steel enclosure that allows it to be used down to -50oC. Variation 2 This variation introduced the following change: ii. i. Variation 1 This variation introduced the following changes: EC TYPE-EXAMINATION CERTIFICATE EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X Issue 8 SCHEDULE SCHEDULE CERTIFICATION Following appropriate re-assessment to demonstrate compliance with the requirements of the EN 60079 series of standards, the documents originally listed in section 9, EN 50014:1997 (amendments A1 to A2) and EN 50016:1995, were replaced by EN 60079-0:2006, EN 60079-1:2004, EN 61241-0:2006 and EN 61241-1:2006, the markings in section 12 were updated accordingly. The removal of special conditions for safe use that were not specifically associated with the equipment covered by this certificate. To permit the inclusion of the following coding for the Low Temperature MiniPurge Enclosure: Ex [p] dem IIC T4 Ex pD II 21 T135°C (Ta –50oC to +55oC) The introduction of the /ET version, an alternative to the pneumatic or mechanical timer system, this incorporates an Electronic Timer Module ETM-IS**-*** in the Mini Purge, the certification includes ‘ia’ marking when the ETM is fitted. The dust marking was changed to be consistent with the marking for gases and vapours. The introduction of a high pressure sensor for the LC option. Following appropriate re-assessment to demonstrate compliance with the requirements of the latest EN 60079 series of standards, the documents previously listed in section 9, EN 60079-0: 2006 and EN 60079-2: 2004 were replaced by those currently listed (EN 61241-0: 2006 was removed as this is incorporated into the current version of 60079-0), the markings in section 12 were updated accordingly and a new condition of certification was added. Date 3 July 2002 29 March 2004 30 September 2004 19 September 2006 Form 9400 Issue1 This certificate and its schedules may only be reproduced in its entirety and without change. Issue 0 1 2 3 Page 5 of 7 Report no. R53A7169A R53V11342A R51A11080A R51A15629A Tel: Fax: Email: Web: +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service Comment The release of prime certificate. The introduction of Variation 1. The introduction of Variation 2. The re-issue of Variation 2 to include the changes described in report number R51A15629A. Associated Sira Reports and Certificate History Refer to Certificate Annexe. Drawings 14.2 DESCRIPTIVE DOCUMENTS 14.1 The recognition of the Applicant’s address change from Summer Road, Thames Ditton, Surrey KT7 0RH to Unit 2, The Summit, Hanworth Road, Sunbury on Thames, Surrey TW16 5DB. 14 i. Variation 7 - This variation introduced the following changes: i. Variation 6 - This variation introduced the following changes: ii. iii. i. Variation 5 - This variation introduced the following changes: i. Variation 4 - This variation introduced the following changes: ii. i. Variation 3 This variation introduced the following changes: This MiniPurge Control Unit shall be incorporated into equipment and the appropriate Conformity Assessment Procedures applied to the combination as defined by Directive 94/9/EC. This certificate does not cover the combination. 15.4 Form 9400 Issue1 Page 6 of 7 Holders of Type Examination Certificates are required to comply with the production control requirements defined in Article 8 of directive 94/9/EC. 17.2 Tel: Fax: Email: Web: +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service The use of this certificate is subject to the Regulations Applicable to Holders of Sira Certificates. 17.1 This certificate and its schedules may only be reproduced in its entirety and without change. CONDITIONS OF CERTIFICATION 17 The relevant EHSRs that are not addressed by the standards listed in this certificate have been identified and individually assessed reports listed in Section 14.2. ESSENTIAL HEALTH AND SAFETY REQUIREMENTS (EHSRs) The values of the safety parameters shall be set in accordance with the equipment certificate that covers the combination of the pressurised enclosure(s) and MiniPurge Control Unit. 15.3 16 The installer/user shall ensure that the MiniPurge Control Unit is installed in accordance with the equipment certificate that covers the combination of the pressurised enclosure(s) and MiniPurge Control Unit. 15.2 The purge controller, low temperature version, shall be protected by a safety related system that ensures that it cannot be energised if the temperature of the air inlet or purge controller falls below 20oC. This system shall utilise the RTDs that are fitted to the purge controller to provide the appropriate level of system integrity, i.e. a level of operational safety of Cat 3 according to EN 954-1 for ATEX Category 2 (Zone 1) applications; note that these RTDs have not been assessed as a safety related device in accordance with EHSR 1.5 of Directive 94/9/EC. When using the AO, AS and DT options, the recommendations for the additional requirements of Ex p apparatus contained within EN 60079-14 shall be applied. 15.5 SPECIAL CONDITIONS FOR SAFE USE (denoted by X after the certificate number) R25983A/00 R29097A/00 Comment This Issue covers the following changes: • All previously issued certification was rationalised into a single certificate, Issue 4, Issues 0 to 3 referenced above are only intended to reflect the history of the previous certification and have not been issued as documents in this format. • The introduction of Variation 3. The introduction of Variation 4. This Issue covers the following changes: • This certificate history was modified to recognise that that Variation 2 was re-issued, subsequent Variations have therefore been re-numbered. • The introduction of Variation 5. The introduction of Variation 6. The introduction of Variation 7. 15 07 December 2011 05 October 2012 7 8 R51L19695A R23665A/00 Report no. R51L15966B Sira 01ATEX1295X Issue 8 CERTIFICATION 15.1 18 February 2009 22 December 2010 Date 7 June 2007 5 6 Issue 4 EC TYPE-EXAMINATION CERTIFICATE EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X Issue 8 SCHEDULE SCHEDULE CERTIFICATION The following routine tests shall be performed by the manufacturer: 17.4 Form 9400 Issue1 Page 7 of 7 The Purge Controllers: Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X shall not be marked as suitable for use in explosive dust atmospheres when a non-metallic or painted housing is used. 17.7 Tel: Fax: Email: Web: +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service The certification code that is appropriate to Purge Controllers low temperature version shall appear in the product marking applied to outer stainless steel enclosure. 17.6 This certificate and its schedules may only be reproduced in its entirety and without change. The products covered by this certificate incorporate previously certified devices, it is therefore the responsibility of the manufacturer to continually monitor the status of the certification associated with these devices, and the manufacturer shall inform Sira of any modifications of the devices that may impinge upon the explosion safety design of the products. 17.5 Where the HP is specified an overpressure shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Purging Overpressure protection An air supply failure shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Air Supply Failure Protection A purge failure shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Purge Failure Protection An overpressure loss shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Minimum Overpressure Cut Off The switches incorporated in the PA option shall be suitably certified for Category 2. Sira 01ATEX1295X Issue 8 17.3 EC TYPE-EXAMINATION CERTIFICATE SCHEDULE CERTIFICATION EXPO Technologies Limited Equipment: Applicant: Sheet 1 to 4 1 to 2 1 of 1 1 of 1 1 of 1 Rev. 3 2 1 1 1 Date 02 Jul 02 21 May 01 21 Sep 00 21 Sep 00 21 Sep 00 Sheet 1 of 1 Rev. 3 Date Description 22 March 04 Low Temperature Housing - General Arrangement Description Certification label Low temperature housing wiring certification drawing. Sheet 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 to 2 1 to 2 Sheet 1 to 5 Rev. 02 03 02 02 02 02 02 03 03 02 02 02 02 01 01 01 01 02 01 04 06 03 Rev. 5 Date 15 Mar 07 09 Jul 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 18 Apr 07 27 Mar 07 15 Mar 07 25 Apr 07 15 Mar 07 20 Feb 07 20 Feb 07 Date 30 Aug 06 Form 9400 Issue 1 This certificate and its schedules may only be reproduced in its entirety and without change. Number EP99-3-1 EP99-2-1 EP99-2-3 EP99-2-2 EP99-2-7 EP99-2-8 EP99-2-9 EP99-2-10 EP99-2-11 EP99-2-12 EP99-2-14 EP99-2-17 EP99-2-16 SD7533 SD7535 SD7536 SD7538 SD7449 SD7500 SD7448 SD7281 SD7282 Issue 4 Number SD7281 Page 1 of 2 Tel: Fax: Email: Web: +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service Description Minipurge Control Unit – General Assembly Schematic - Type x Leakage Compensation Sequence Diagram - Type x Leakage Compensation Schematic - Type x Continuous Flow Schematic – Separate Supply and Mechanical Timer Schematic – Delay Before Trip and On/Off Schematic – Twin Output and Manual Override Schematic – Pressure Control Leakage Compensation Internal “IS” Switches Schematic – Containment System and Secondary pressurisation Schematic – Continuous Flow with 2 Flow Rates Schematic – Continuous Flow with High Pressure Schematic – Outlet Valve Control Schematic – Dust Protection Spark Arrestor Differential Flow Monitor Continuous Flow Outlet Orifice Wiring Diagram – Low temperature Outlet Orifice Closing Device Low Temperature Housing Certification Label Details MiniPurge Data Sheet Description Certification label Issue 3 (The drawings associated with this issue were replaced by those listed in Issue 4) Number Sheet Rev. Date SD7281* 1 to 5 4 17 Dec 03 SD7449 1 of 1 1 18 Dec 03 * Modified by Sira 30 September 2004 Issue 2 (The drawings associated with this issue were replaced by those listed in Issue 4) Number SD7448 CERTIFICATION Description MiniPurge ATEX Certification Labelling MiniPurge ATEX Certification Type Numbering Scheme MiniPurge, Continuous Flow with /HP Sensor –Schematic diagram RLV, outlet orifice Outlet Valve Control Circuit Diagram Issue 1 (The drawings associated with this issue were replaced by those listed in Issue 4) Number SD7281 SD7282 EP/99-2-17 EP99-7-7 EP99-7-9 Issue 0 (The drawings associated with this issue were replaced by those listed in Issue 4) Sira 01ATEX1295X Purge Controllers Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X Certificate Number: Certificate Annexe Sheets 1 to 3 Sheets 1 of 1 1&2 1 to 3 1 of 1 Sheets 1 to 2 1 to 2 1 of 1 1 of 1 Sheets 1 to 2 1 of 1 Rev. 10 Rev. 6 5 9 2 Rev. 8 4 2 2 Rev. 7 05 Form 9400 Issue 1 CERTIFICATION Date (Sira stamp) 05 Oct 12 Date (Sira stamp) 23 Nov 11 23 Nov 11 23 Nov 11 23 Nov 11 Date (Sira stamp) 23 Dec 10 21 Dec 10 21 Dec 10 21 Dec 10 Page 2 of 2 Tel: Fax: Email: Web: +44 (0) 1244 670900 +44 (0) 1244 681330 info@siracertification.com www.siracertification.com Rake Lane, Eccleston, Chester, CH4 9JN, England Sira Certification Service Title Minipurge Certification Label Description Minipurge Low Temperature Housing Minipurge Data Sheets Minipurge ATEX/IECEx Certification Label Minipurge Dust Protection Schematic Description Minipurge ATEX/IECEx Certification Label MiniPurge Data Sheet MiniPurge electronic timer MiniPurge HP sensor Description Minipurge ATEX/IECEx Certification Label Minipurge Low temperature Housing Description Fault Evaluation Outlet Valve Circuit N/O Outlet Control Valve N/C Schematic – Type Z or Y leakage compensation Schematic Type Z or Y Continuous Flow Sequence Diagram – Type X Continuous Flow Schematic – Alarm only and Alarm Action Selector Schematic – Door Switch Active Alarm and Alarm Cancel RLV Configurations Alternative Z&Y LC System Alternative Z&Y LC System Date (Sira stamp) 12 Feb 09 12 Feb 09 Date 20 Feb 07 15 Mar 07 15 Mar 07 09 Jul 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 05 Jul 07 09 Jul 07 09 Jul 07 This certificate and its schedules may only be reproduced in its entirety and without change. Number SD7281 Issue 8 Number SD7448 SD7282 SD7281 SD7533 Issue 7 Number SD7281 SD7282 SD7913 SD7914 Issue 6 Number SD7281 SD7448 Issue 5 Rev. 01 02 01 02 01 02 02 02 01 01 01 EXPO Technologies Limited Applicant: Sheet 1 to 3 1 of 2 2 of 2 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 to 4 1 of 2 2 of 2 Purge Controllers Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X Equipment: Number SD7537 EP99-7-9 EP99-7-9 SD7531 SD7532 EP99-2-4 EP99-2-5 EP99-2-6 SD7555 SD7556 SD7556 Sira 01ATEX1295X Certificate Number: Certificate Annexe E190061 Print this page Te rm s of Use Page Top © 2012 UL LLC database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/show page.html?name=RFPW7.E190061&cc… UL pe rm its the re production of the m aterial containe d in the O nline Ce rtification Dire ctory subje ct to the following conditions: 1. The Guide Inform ation, De signs and/or Listings (file s) m ust be pre se nte d in the ir e ntire ty and in a non-m isle ading m anne r, without any m anipulation of the data (or drawings). 2. The state m e nt "R e printe d from the O nline Ce rtifications Dire ctory with pe rm ission from UL" m ust appe ar adjacent to the e x tracte d m ate rial. In addition, the re printe d m aterial m ust include a copyright notice in the following form at: "© 2012 UL LLC". The appearance of a com pany's nam e or product in this database doe s not in itse lf assure that products so ide ntifie d have be e n m anufacture d unde r UL's Follow-Up Se rvice . O nly those products bearing the UL Mark should be conside re d to be Liste d and cove re d unde r UL's Follow-Up Se rvice . Always look for the Mark on the product. W he n the UL Le af Mark is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple ase se arch the UL Environm e nt database for additional inform ation re garding this product's ce rtification. Q ue stions? Last Update d on 2012-10-14 ** - Inte rnal se rie s ide ntifie r, pre ce de s m ode l num be r, which m ay contain one or m ore characte rs. Purge control accessory: Vent unit for use in hazardous (classifie d) locations, Mode l R LV followe d by 25, 36, 52, 75, 104, 125, 150, or 200, followe d by CS or SS, m ay be followe d by FS. Type Z for use in hazardous (classifie d) locations, Mode ls** 1, 2, 3, 4, 5, 6 followe d by Z, followe d by CF, CFHP or LC, followe d by BP, CS, PM, SS, m ay be followe d by AO , DS, DT, IS, MO , NO , PO , SS. Type Y for use in hazardous (classifie d) locations, Mode l** 1, 2, 3, 4, 5, 6 or 7 followe d by Y, followe d by CF, CFHP or LC, followe d by BP, CS, NM, PM, SS, m ay be followe d by AO , DS, DT, IS, MO , NO , PO , SS. Purge control units, Type X for use in hazardous (classifie d) locations, Mode l** 1, 2, 3, 4, 5, 6 or 7 followe d by X, followe d by CF, CFHP or LC, followe d by BP, CS, PM, SS, m ay be followe d by AO , DS, DT, IS, MO , PO , SS. SUNBUR Y O N THAMES, SUR R EY TW 16 5DB UNITED KINGDO M HANW O R TH R O AD UNIT 2 THE SUMMIT EXPO TECHNOLOGIES LIMITED Se e General Inform ation for Purging and Pre ssurizing Controls and Acce ssorie s for Use in Hazardous Locations C e rtifie d for Canada Purging and Pressurizing Controls and Accessories for Use in Hazardous Locations Certified for Canada Page Bottom RFPW7.E190061 Purging and Pressurizing Controls and Accessories for Use in Hazardous Locations Certified for Canada rizing11/7/12 Controls and Accessories for Use in Hazardous Locati… 1/1 E190061 Print this page Te rm s of Use Page Top © 2012 UL LLC database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/show page.html?name=RFPW.E190061&ccn… UL pe rm its the re production of the m aterial containe d in the O nline Ce rtification Dire ctory subje ct to the following conditions: 1. The Guide Inform ation, De signs and/or Listings (file s) m ust be pre se nte d in the ir e ntire ty and in a non-m isle ading m anne r, without any m anipulation of the data (or drawings). 2. The state m e nt "R e printe d from the O nline Ce rtifications Dire ctory with pe rm ission from UL" m ust appe ar adjacent to the e x tracte d m ate rial. In addition, the re printe d m aterial m ust include a copyright notice in the following form at: "© 2012 UL LLC". The appearance of a com pany's nam e or product in this database doe s not in itse lf assure that products so ide ntifie d have be e n m anufacture d unde r UL's Follow-Up Se rvice . O nly those products bearing the UL Mark should be conside re d to be Liste d and cove re d unde r UL's Follow-Up Se rvice . Always look for the Mark on the product. W he n the UL Le af Mark is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple ase se arch the UL Environm e nt database for additional inform ation re garding this product's ce rtification. Q ue stions? Last Update d on 2012-10-14 ** - Inte rnal se rie s ide ntifie r, pre ce de s m ode l num be r, which m ay contain one or m ore characte rs. Purge control accessory: Vent unit for use in hazardous (classifie d) locations, Mode l R LV followe d by 25, 36, 52, 75, 104, 125, 150, or 200, followe d by CS or SS, m ay be followe d by FS. Type Z for use in hazardous (classifie d) locations, Mode ls** 1, 2, 3, 4, 5, 6 followe d by Z, followe d by CF, CFHP or LC, followe d by BP, CS, PM, SS, m ay be followe d by AO , DS, DT, IS, MO , NO , PO , SS. Type Y for use in hazardous (classifie d) locations, Mode l** 1, 2, 3, 4, 5, 6 or 7 followe d by Y, followe d by CF, CFHP or LC, followe d by BP, CS, NM, PM, SS, m ay be followe d by AO , DS, DT, IS, MO , NO , PO , SS. Purge control units, Type X for use in hazardous (classifie d) locations, Mode l** 1, 2, 3, 4, 5, 6 or 7 followe d by X, followe d by CF, CFHP or LC, followe d by BP, CS, PM, SS, m ay be followe d by AO , DS, DT, IS, MO , PO , SS. SUNBUR Y O N THAMES, SUR R EY TW 16 5DB UNITED KINGDO M HANW O R TH R O AD UNIT 2 THE SUMMIT EXPO TECHNOLOGIES LIMITED Se e General Inform ation for Purging and Pre ssurizing Controls and Acce ssorie s for Use in Hazardous Locations Purging and Pressurizing Controls and Accessories for Use in Hazardous Locations Page Bottom RFPW.E190061 Purging and Pressurizing Controls and Accessories for Use in Hazardous Locations zing 11/7/12 Controls and Accessories for Use in Hazardous Locations 1/1 (1) Declaration of Conformity. (2) Expo Technologies Document Number EXPO11ATEX1200X/3. (3) This declaration is issued for the electrical apparatus: AGE-SW0Z-017 non- sparking switch (4) Manufacturer: Expo Technologies Ltd Unit 2, The Summit Hanworth Road Sunbury on Thames TW16 5DB (5) This electrical apparatus and any acceptable variation thereto is specified in the Annex to this certificate and the documents therein referred to. (6) This declaration and schedule confirms compliance of each unit with the following standards: EN 60079-0: 2009 EN 60079-18: 2009 General requirements Encapsulation “m” (7) This apparatus fulfils all the requirements for Group II Category 3 equipment in accordance with European Directive 94/9/EC. (8) The design is documented in Expo Technologies Technical Construction File number 33182 (9) The apparatus marking: Ex m IIC T4 Gc II 3 G For and on behalf of Expo Technologies Ltd. Sunbury on Thames, 14th October 2013. Sarah Wickson Certification Engineer Page 1 of 2 Expo Technologies Ltd. Registered in England No2854600 David Baker Certification Engineer Expo Technologies Ltd Unit 2, The Summit, Hanworth Rd. Sunbury on Thames, Surrey. TW16 5DB T +44 (0)20 8398 8011 F +44 (0)20 8398 8014 E info@expoworldwide.com www.expoworldwide.com Annex to Declaration of Conformity EXPO11ATEX1200X/3. 10 Description: A pneumatically operated, hermetically sealed switch. The switch is contained in an aluminium alloy 6082 block encapsulated with an epoxy resin potting compound. Ambient temperature range –20 C to + 55 C. 11 Switch data: Maximum Voltage Maximum Current Humidity range Pneumatic signal: 12 254Vac rms 0.7A 0% to 100% RH at 55C, condensing. 22 to 100 p.s.i. 1.5 – 7Barg. Special conditions of safe use: The unit shall be grounded using a cable lug and appropriate grounding wire. The conductor shall be secured against loosening or twisting and that contact pressure is permanently secured. The circuit shall be protected by a suitable fuse or similar device. 13 Test Documentation Description General Arrangement Reed switch data sheet Test procedure Doc. Ref. AGE-SW0Z-017 2118502030 TP518-040-WD Rev. 3 2 2 Revision History Version 0 1 2 3 Date 12-Oct-2011 7-Jun-2012 27-Sep-2013 14-Oct-2013 Page 2 of 2 Expo Technologies Ltd. Registered in England No2854600 Comment Initial issue of DoC Maximum voltage modified from 230V to 254Vac rms Manufacturer’s address updated Rectification of anomalies in address Expo Technologies Ltd Unit 2, The Summit, Hanworth Rd. Sunbury on Thames, Surrey. TW16 5DB T +44 (0)20 8398 8011 F +44 (0)20 8398 8014 E info@expoworldwide.com www.expoworldwide.com Manufacturer’s Self Evaluation In accordance with NFPA-70 National Electric Code Clause 500.8 Expo Technologies Ltd Hanworth Road Sunbury on Thames, TW16 5DB UK The non-incendive switch AGE-SW0Z-017 Manufactured by Expo Technologies can be marked for use in Class I division 2 hazardous location. The switch contacts are formed of a reed switch which is a hermetically sealed contact. It is therefore is suitable for use in Class I Division 2 Hazardous Location in accordance with NFPA-70 clause 500.7 J Hermetically sealed. NEC 501.105 B 1 Exception 2 Allows for hermetically sealed devices to be used as an alternative to using a listed device. i.e. there is not a requirement for these to be listed . Similarly 501.1.150 .2 exception 2 also permits hermetically sealed switch for use as remote alarm. The switch is marked with the voltage and current ration of the hermetically sealed contacts and is marked as V max I max P max Non Incendive Circuit 254V AC 200V DC 1 Amp 70 W For Intinsically safe circuits or the switch contact is simple apparatus as described in NEC504.2 and used with control drawing EP-80-2.11 Similarly for non incendive circuits the switch is simple apparatus ( though also hermetically sealed.). Therefore the switch AGE-SW0Z-017 can be used as simple apparatus either in an intrinsically safe circuit or in a non incendive circuit, or it can be used as a hermetically sealed contact in a Class I Division2 Location within the ratings shown. Signed Managing Director Date 7 June 2012 Confidential Assessment file reference SC020 V3 – 10 Jun 13 S:\Files\QA\CERTS\C-OF-C\SC020 V3 Non Incendive switch.doc With European Directives EC-Declaration of Conformity Expo Technologies Ltd Unit 2, The Summit, Hanworth Road Sunbury on Thames TW16 5DB, UK This is to declare that Purge Controllers Type “MiniPurge” are manufactured in conformity with the following European Directives and standards: Electromagnetic Compatibility Directive 2004/108/EG MiniPurge Systems with a /PO suffix in the type number are non-electrical and are outside the scope of the EMC Directive. MiniPurge Systems with suffices /PA or /IS incorporate one or more volt-free (“dry”) contacts which work in circuits specified by others. In normal operation these circuits are “benign” and no CE mark is appropriate. MiniPurge Systems with Electronic Timer (Option /ET) are designed to conform to the EMC Directive, in compliance with EN 61000-6-4:2007 and EN 61000-6-2:2005 (Intertek Report EM10048000). Low Voltage Directive 2006/95/EC MiniPurge Systems are intended for use in potentially explosive atmospheres (Hazardous Areas) and are therefore excluded from the Low Voltage Directive. Pressure Equipment Directive 97/23/EC MiniPurge Systems are classified as not higher than category I under Article 9 of this Directive and intended for use in potentially explosive atmospheres (Hazardous Areas) and are therefore excluded from the Pressure Equipment Directive. ATEX Directive 94/9/EC MiniPurge Systems are designed to conform to the ATEX Directive, in compliance with: EN 60079-0 : 2012 + A11:2013 EN 60079-2 : 2007 EN 61241-4 : 2006 MiniPurge Systems are certified by SIRA Certification Service, Rake Lane, Eccleston, Chester CH4 9JN, England, under EC Type-Examination Certificate SIRA 01ATEX1295X, in compliance with: IEC 60079-0 : 2011 EN 60079-2 : 2007 EN 61241-4 : 2006 According to the model, MiniPurge Systems are rated and shall be marked as follows: MiniPurge, X & Y models MiniPurge, Z models Group II Category 2G & 2G Group II Category 3G & 3D II 2(2) GD II 2(3) GD MiniPurge systems are manufactured under Production Quality Assurance Notification SIRA 99 ATEX M043, issued by SIRA Certification Service, Notified Body No 0518. John Paul de Beer Managing Director S:\Files\QA\CERTS\C-OF-C\Minipurge CE SC004 Issue6.doc Date 02/09/2014 Confidential Assessment file reference SC004 Expo Technologies Ltd. Unit 2, The Summit Hanworth Road Sunbury on Thames TW16 5DB Tel Fax E-mail: + 44 (0) 20 8398 8011 + 44 (0) 20 8398 8014 sales@expoworldwide.com Expo Technologies Inc. 9140 Ravenna Road Unit #3 Twinsburg OH 44087 USA Tel: Tel: Fax: E-mail: +1 888-NFPA-496 +1 (440) 247 5314 +1 (330) 487 0611 sales.na@expoworldwide.com www.expoworldwide.com