Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives Electronic Bypass (E-Bypass) Options Description The SED2 Electronic Bypass (E-Bypass) Options are companion packages for the family of SED2 Variable Frequency Drives (VFDs). For information on the family of SED2 VFDs, see the SED2 Variable Frequency Drives Submittal Sheet (154-042). E-Bypass Features • • • • • • • • • • Enhanced visual interface for improved monitoring and diagnostics E- Bypass guarantees continuous operation even if SED2 fails Electronic touch-sensitive keypad Standard built-in networking compatibility Service mode isolates drive from the control scheme Six relay outputs for indication of operation Fourteen LEDs indicate monitoring and operation Six digital inputs Remote start via networking Contactors electrically and mechanically interlocked. 3-Contactor: Input, Output, and Bypass. • Overload protection in bypass mode • Drive test function • Complete electrical isolation of drive Input Device • Fused disconnect • Circuit breaker (optional) • All doors are interlocked and padlockable Reactor Options • Line reactor mounted in bypass option enclosure • Line reactor (in NEMA 1 enclosure) supplied separately • Load reactor (in NEMA 1 enclosure) supplied separately E-Bypass Control Features Auto Bypass • Relay logic allows user to send the motor to bypass mode based on the drive’s programmable relay. • The drive’s programmable relay, typically set to fault, can be set up for applications that run full speed for an extended period of time. Enable Input • Generally used for safety tie-ins; the motor will not operate the drive or bypass when open. Common Remote Start/Stop • Common remote start/stop can be used in both drive and bypass mode. Essential Services Mode • Also used for smoke purge; the motor goes to bypass regardless of the selected mode. • No call to stop will have an effect, including open safety or stop commands. • Only turning the power off or opening this contact will stop the motor. Input Device VF0302R2 Drive Motor 3 Contactor Bypass Siemens Industry, Inc. Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives With E-Bypass Options E-Bypass – Door Mounted Control Devices Product Numbers Your Product Number: Example Product Number: V B E 3 4 0 . F 1 3 0 X Model VFD Bypass Input On/Off Input Contactor VFD Enable Hand Start Remote Start Motor VFD0097R1 Auto Bypass Enabled INTERLOCK START LOGIC Overload Fault Enable Commanded Proofed Figure 1. SED2.6 Bypass Keypad. Typical Specifications SED2 E-Bypass Options shall send the motor to bypass mode based on an easily accessible doormounted selector or based on user's desired conditions. LED indication of operational state shall be provided. The bypass mode shall provide overload protection. Contactors shall be electrically and mechanically interlocked. An essential services mode shall send the motor to bypass regardless of the selected mode. When in safety modes it should provide indication of return state. It should indicate interlock sequence state during transition. Visually indicate faults for VFD safety/overload. Page 2 of 8 Electronic Bypass 1 208 V 230 to 240 V 380 to 480 V 500 to 600 V HP rating VFD Fault Safety Fault Essential Services E 2 3 4 Output Contactor STOP RESET VFD with Bypass Voltage Bypass Contactor Overload Relay VB Series 1.0, 1.5, 2.0, 3.0, 5.0, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125 [See Note 1 for these selections] Disconnect F B NEMA rating Fused Disconnect Circuit Breaker 1 NEMA Type 1 3 3 Contactors [See Note 2] None Input Line Reactor Contactor Reactor 0 3 Filter X Options Factory Required Designator (If no option is required, leave field blank) Notes: 1. Available only with Voltage Codes 3 and 4. 2. Only an input line reactor can be installed in a bypass enclosure. If a load reactor is required, a separate enclosed reactor is required. Example Shown: VBE340.F130X = VBE Electronic Bypass, 480V, 40 hp, fused disconnect, NEMA Type 1, 3 contactors, no reactor. Siemens Industry, Inc. Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives With E-Bypass Options Table 1. E-Bypass Approximate Weights. Dimensions Depth With Handle 10.4 (26) = Protective Shield Depth With Handle 9.6 (24) Depth With Handle 9.6 (24) 11.5 (29) 20.8 (53) Frame Size A B C D E F 2.9 (7.4) 4 (10) 1 (2.5) 2 (5) 1.5 (3.8) 13.2 (34) 53.5 (136) 10.5 TYP (27) 12.4 (31) 10.6 (27) Frame Size A and B Depth With Handle 12.2 (31) 20.8 (53) 11.5 TYP (29) 11 TYP (28) 1.5 (3.8) 19.9 (51) 2 (5) Frame Size C 3.4 (8.6) Table 2. E-Bypass Byass Frame Sizes and Power Ranges. Frame Size D HP kW 208/240V 480V 2.9 (7.4) 3 (7.6) Depth 17.4 (44) 45.5 (116) 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 57.5 (146) 58.5 (149) VFD0127R2 10 TYP (25) 19.9 (51) Exact weight will be affected by actual horsepower/voltage and selected power options. NOTE: 48 (122) 34 (86) Weight lb (kg) 45 (20) 55 (25) 75 (34) 150 (68) 180 (82) 470 (213) 5.5 (14) Frame Size E Frame Size F Figure 2. E-Bypass Dimensions in Inches (Centimeters). .75 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 575V A A B B C C C D E F N/A D D E E F F Table 3. E-Bypass Output Current Ratings (Amps) — Per NEC Motor Tables. HP NOTE: 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 208V 3.9 5.5 7.4 10.4 16.7 22 28 42 54 68 80 104 130 154 – – – 240V 3.9 5.5 6.8 9.6 15.2 22 28 42 54 68 80 104 130 154 – – – 480V 2.1 3.0 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156 575V 1.4 2.1 2.7 3.9 6.1 9 11 17 22 27 32 41 52 62 77 99 125 Drives are current rated devices. Verify that the listed ratings are ≥ the motor full load current rating. Siemens Industry, Inc. Page 3 of 8 Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives With E-Bypass Options Wiring Diagrams OPTIONAL INPUT LINE REACTOR (SUPPLIED LOOSE) POWER SUPPLY 3 PHASE 60 Hz A1 A2 B1 B2 C1 C2 GND POWER FUSES - MAIN SHORT CIRCUIT PROTECTION BY OTHERS (SEE NOTE 1) DISC1 FU1 2L1 L1 1L1 (T1) (L1) 2L2 L2 1L2 (T2) (L2) L3 1L3 2L3 (T3) (L3) DRIVE INPUT CONTACTOR GND M3 3L1 GND LUG (1) (2) 3L2 (3) (4) M1 (5) (6) (3) (4) VFD1 A2 A1 3L3 (5) (6) (1) (2) OPTIONAL INPUT LINE REACTOR B1 B2 C1 C2 R U S V T W U V W M2 (1) (2) (3) (4) (5) (6) GND OL1 1T1 (T1) 1T2 (T2) 1T3 (T3) OPTIONAL OUTPUT LOAD REACTOR (SUPPLIED LOOSE) A1 A2 B1 B2 C1 C2 M AC MOTOR (CUSTOMER SUPPLIED) GND LUG 1L1 1L2 TO STEP-DOWN CONTROL TRANSFORMER VFD1 CONTROL TERMINALS VFD0240R1 1 2 3 4 5 6 7 8 9 10 11 M2 RR (6) M2 (10) NOTES: 1. Branch circuit protection to be provided by installer, per UL508A, if not provided with drive. 2. For bypass operation, modify these drive parameters: P0702[0] and P0702[1] = 3, P0748 = Digital Out 1 Reverse ( ). 3. Control and communication wiring should be 300V UL minimum. 4. Communication wiring should be run with maximum separation possible from all other wiring. 5. Essential service mode operates the motor full speed (bypass) with no protection for the motor or system. 6. Ensure that automatic bypass will not damage the system before activating. 7. See Siemens Publication No. 125-3208 for proper fuse and wire sizes. 8. See Siemens Publication No. 125-3201 for SED2 input/output control signal wiring details. Figure 3. E-Bypass Power Circuit. Page 4 of 8 Siemens Industry, Inc. Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives With E-Bypass Options DRIVE CONTROL TERMINATIONS ANALOG INPUT EXAMPLES Control terminations located on drive I/O module 21 AO2- 3 + + 4 - RL1 NO 4.7k Ohm RL1 COM RL2 NC RL2 NO 25 N- 30 11 AIN2- 2 RL1 NC 24 P+ 29 10 AIN2+ 23 28 ISO 0VDC 9 VFD0125R2 AO2+ 22 DIN6 20 ISO 24VDC EXTERNAL 0/4 TO 20mA SPEED POTENTIOMETER 1 2 3 27 8 DIN4 - 26 7 DIN3 DIN5 EXTERNAL 0 TO 10V 2 3 17 6 DIN2 PTC B 16 5 DIN1 PTC A 15 4 AIN1- AO1- 14 3 AIN1+ AO1+ 13 2 +0VDC 12 1 +10VDC Analog input connection examples RL2 COM INTER-CONNECTIONS WITH BYPASS FACTORY WIRED VFD 24VDC POWERED 0/4-20mA DEVICE (POWER CONSUMPTION CANNOT EXCEED 100mA) 2 3 4 9 28 mA POWER Figure 4. Drive Terminations. Remote Start Input Remote Safety #1 DIGITAL INPUTS Remote Safety #2 Interlock Start Essential Services Overload Trigger VFD0114R2 DIGITAL OUTPUTS Programmable Output, NO COM NC VFD Fault, NO COM NC Drive Select, COM NO Bypass Select, COM NO Bypass Running, COM NO Overload Fault, COM NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 J2 J1 Figure 5. E-Bypass Controller Board Digital Inputs and Outputs. Siemens Industry, Inc. Page 5 of 8 Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives With E-Bypass Options Table 4. E-Bypass Specifications. Specifications Input Voltage (3-phase) Digital Inputs Description 208V, 3 AC±10%. 1 hp to 60 hp (3.9 amps to 154 amps) 240V, 3 AC±10%. 1 hp to 60 hp (3.9 amps to 154 amps) 480V, 3 AC ±10%. 1 hp to 125 hp (2.1 amps to 178 amps) 575V, 3 AC ±10%. 1 hp to 125 hp (2.3 amps to 125 amps) Six Digital Inputs as follows: • • • • • • Relay/Digital Outputs Inputs require a contact closure capable of providing a low impedance path at currents less than 20 mA. Six Relay/Digital Outputs as follows: • • • • • • Temperature Humidity Page 6 of 8 Remote start input Remote safety 1 Remote safety 2 Interlock start Essential services Overload trigger VFD fault Programmable output Drive select Bypass select Running on bypass Overload fault Each relay has a maximum rating of 2A at 120V ac. Operating: 14°F to 104°F (-10°C to 40°C) Storage: –40°F to 158°F (–40°C to 70°C) 0 to 95% rh, non-condensing Siemens Industry, Inc. Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives With E-Bypass Options Table 5. Drive Specifications. Drive Specifications Input voltage and power ranges (3-phase), amps Input frequency Output frequency Power factor VFD degree of efficiency Switch-on current Auxiliary supply 24V Overload capacity Control method PWM frequency Fixed frequencies Skip frequency bands Setpoint resolution Digital inputs (sink/source) Analog inputs Relay outputs Analog outputs Serial interface Protection level Temperature ranges Humidity Operational altitudes Protection features Standards NOTE: Description 208V and 230V to 240V, 3 ac ± 10%. 1 hp to 60 hp (3.9 amps to 154 amps) 380V to 480V, 3 ac ± 10%. 1 hp to 125 hp (2.1 amps to 178 amps) 500V to 600V, 3 ac ± 10%. 1 hp to 125 hp (2.1 amps to 125 amps) 47 Hz to 63 Hz 0 Hz to 150 Hz ≥ 0.9 96% to 97% Less than nominal input current Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA 110% for 60 seconds Linear, parabolic and programmable V/f; and flux current control low-power mode 2k Hz to 16k Hz (adjustable in 2k Hz increments) 15 programmable 4 programmable 0.01 Hz digital 0.01 Hz serial 10 bit analog 6: fully programmable and scalable isolated digital inputs, switchable 2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or Ni 1000 input 2: configurable 30 Vdc/5A (resistive), 250 Vac/2A (inductive) 2: programmable (0/4 mA to 20 mA or 0 Vdc to 10 Vdc) RS-485 transmission rate: Up to 38.4k Baud Protocols: Siemens Building Technologies, Inc., P1 and Johnson, N2 IP20: NEMA Type 1 with protective shield and gland plate installed IP54: NEMA Type 12 (400V and 500V series only) Operating: 14°F to 104°F (–10°C to 40°C) Storage: –40°F to 158°F (–40°C to 70°C) 95% rh, non-condensing Up to 3280 ft (1000 m) above sea level without derating Under-voltage, Over-voltage, Overload, Ground fault, Short circuit, Stall prevention, Locked motor, 2 Motor overtemperature l t PTC, Over-temperature, Parameter PIN protection. UL, cUL SED2 Compliance with EN61000-3-12: From September 1st, 2005 all electrical apparatus covered by the EMC directive will have to comply with EN610003-12 “Limits for harmonic currents produced by equipment connected to public low voltage systems with input currents > 16A and =< 75 A per phase”. Siemens variable speed drives of the product range SED2 (Micromaster 436) fulfill the requirements of the EN 61000-3-12 (without the need for external line reactors) regarding the THD values of Table 3 under the pre condition of Rsce > 190. The required PWHD values will not be achieved. Due to this fact it is recommended to apply for connection approval at the local electricity board. The local electricity board will evaluate among many other data the content of the 5th harmonic current and the Line Power Factor "Lambda”, which is the ratio of active power and apparent power. Siemens frequency inverters are optimized in design and operation characteristics regarding energy efficiency and less interference with line supplies. Siemens Industry, Inc. Page 7 of 8 Submittal Sheet Document No. 154-051 May 9, 2011 SED2 Variable Frequency Drives With E-Bypass Options Table 6. Order Worksheet. Item Qty. Designation Part Number Description Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2011 Siemens Industry, Inc. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 USA + 1 847-215-1000 www.buildingtechnologies.siemens.com/bt/us Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com. Document No. 154-051 Printed in the USA Page 8 of 8