Boat Dock Exposure Voltage Mitigation Working Group on Voltages at Publicly and Privately Accessible Locations (P1695) January 2013 Frank Lambert and Shashi Patel Georgia Tech / NEETRAC Problem Statement Swimming or working in the water around docks with customer owned electrical circuits and equipment installed in accordance with current applicable standards can be unsafe because the water around a dock can be at a different potential than the dock for a variety of reasons. Proposed Solution • Create a new separately derived source that is ground isolated to feed the dock’s loads. • The secondary side ground would be bonded to dock equipment as it normally would, but this ground would have no reference to the distribution system neutral. • This would reduce or eliminate the neutral to water voltage at docks. Dock Isolation Unit Test Site 1 • • • • Permanent isolation transformer installation. Only tested with transformer secondary grounded. NEV hazard was mitigated by use of the isolation transformer Contact voltage hazard was also mitigated NEV Measurements Without Iso Tx Loc With Iso Tx Vexp-oc Vexp-cc* Vexp-oc Vexp-cc* Fr-W1 11.9 9.8 1.3 1.0 Fr-W3 16.1 13.1 1.7 1.3 Deck-W3 15.8 3.6 1.7 0.6 *Closed circuit voltage is same as exposure current Isolation Tx had ground on secondary All measurements in Volts (V) Circuit Configuration 5 Test Site 2 • • • • Test site with lowest NEV measured (under 10V). Tested with transformer secondary grounded and floating NEV hazard was mitigated by use of the isolation transformer Contact voltage hazard was also mitigated NEV Measurements Without Iso Tx With Iso Tx2 Vexp-oc Vexp-cc1 Vexp-oc Vexp-cc1 Fr-W1 3.6 3.0 0.7/0.1 0.6/0.1 Fr-W4 5.0 4.3 0.8/0.7 0.7/0.5 Light 2-W 4.7 2.5 0.8/0.1 0.4/0.3 Loc 1 Closed circuit voltage = exposure current 2 For Iso Tx readings: (with secondary grounded/with secondary floating) All measurements in Volts (V) Circuit Configuration 7 Test Site 3 • Testing was performed at an additional site where the highest NEV measured was over 50V. • NEV hazard was mitigated by use of the isolation transformer • Contact voltage hazard was also mitigated NEV Measurements Without Iso Tx Loc With Iso Tx Vexp-oc Vexp-cc* Vexp-oc Vexp-cc* Fr-W1 19.7 15.2 0.6 0.6 Fr-W2 22.5 17.6 1.0 0.6 Deck-W1 20.3 5.5 0.8 0.7 *Closed circuit voltage = exposure current All measurements in Volts (V) Neutral Exposure Voltage Magnitude at Site 3 Approximately 48 Volts NEV is related to running of a local pump storage hydro plant 9 Boat Dock Testing at Site 3 Stray Voltage Testing – Open Circuit Voltage *Configuration not tested 11 Stray Voltage Testing – Closed Circuit Voltage *Configuration not tested 12 Contact Voltage Testing – Open Circuit Voltage *Configuration not tested; results would have been similar to sites 1 and 2. 13 Contact Voltage Testing – Closed Circuit Voltage *Configuration not tested; results would have been similar to sites 1 and 2. 14 NEC Change Proposal • Submitted Changes for: – Article 555 – Marinas and Boatyards (Code Panel 19) – Article 682 – Natural and Artificial Made Bodies of Water (Code Panel 17) • Change Proposal Process (dates for NEC-2014): Change Proposal Submission (by 11/4/2011) Code Panel Report on Proposal (ROP) Meeting Panel 17: 1/19-21/2012 Panel 19: 1/9-14/2012 Code Panel (ROP) Final Ballot Results 3/9/2012 Comment Submission (by 10/17/2012) Code Panel Report on Comments (ROC) Meeting Panel 17: 12/3-5/2012 Panel 19: 12/6-8/2012 Code Panel (ROP) Final Ballot Results 3/22/2013 Change Proposal Language (555.16) 555.16 Mitigation of Neutral Related Stray Voltages and Currents To provide protection for neutral related stray voltages and currents, a suitably rated isolation transformer (a separately derived system) at the branch circuit service panel supplying the shore power shall be permitted. The following configuration is recommended for the isolated system: (1) The isolation transformer shall have overcurrent protection on the supply side as required in 450.3. (2) The isolation transformer shall be provided with a ground fault protection device on the load side. (3) Metal enclosure of the transformer shall be connected to the supply side neutral and grounding system as required by 250.4 (A). (4) The load side neutral and equipment grounding conductors shall be connected together and grounded on the secondary side of the transformer as required by 250.20(B). To provide adequate isolation, the installed grounding electrode shall be located at least 6' from the nearest grounding electrode of the supply side and shall be connected to the transformer by an insulated grounding conductor. (5) The location of the isolation transformer shall be on the load side of the service disconnecting means and shall not be below the electrical datum plane. 16 Change Proposal Language (682.16) 682.16 Mitigation of Neutral Related Stray Voltages and Currents To provide protection for neutral related stray voltages and currents, a suitably rated isolation transformer (a separately derived system) at the branch circuit service panel supplying the shore power shall be permitted. The following configuration is recommended for the isolated system: (1) The isolation transformer shall have overcurrent protection on the supply side as required in 450.3. (2) The isolation transformer shall be provided with a ground fault protection device on the load side. (3) Metal enclosure of the transformer shall be connected to the supply side neutral and grounding system as required by 250.4 (A). (4) The load side neutral and equipment grounding conductors shall be connected together and grounded on the secondary side of the transformer as required by 250.20(B). To provide adequate isolation, the installed grounding electrode shall be located at least 6' from the nearest grounding electrode of the supply side and shall be connected to the transformer by an insulated grounding conductor. (5) The location of the isolation transformer shall be on the load side of the service disconnecting means and shall not be below the electrical datum plane. 17 Comments / Contact Info Frank C. Lambert Georgia Tech / NEETRAC 404-675-1855 frank.lambert@neetrac.gatech.edu