general description diagnostic operation • NFPA 101 (life safety code) requires that a functional test be conducted on every required emergency lighting system at 30 day intervals for a minimum of 30 seconds. Additionally, an annual test must be conducted for 90 minute duration. The Self-Diagnostics/Self-Test option assists the user in meeting these requirements. • Automatic Test: The unit automatically initiates a Self-Test and Self-Diagnostic test as follows: Verifies battery disconnection, charger failure, lamp failure and transformer failure at every 5 seconds. 1 minute battery discharge test every month. 30 minutes battery discharge test on the 6th month of the year. 90 minutes battery discharge test on the 12th month of the year. features • Monitors battery voltage, lamp continuity, incoming utility power and unit performance every 5 seconds without discharging battery or illuminating lamps. • Automatically indicates lamp, battery and charger status by dual-color LED lamp. • Factory preset does not need field adjustment. • Integrated function Fire alarm (6V-24V) function is integrated in Self-Diagnostics/Self-Test Option. CE-17300 Self-Diagnostic/Self-Test SD/ST Series Circuitry & Management System compatibility Patron Series Patron LED Series VU6 Series VC Series VU6L 55 Line Contemporary 44R Line VE Series Specifier’s Reference Project Type Model No. manual test Press test button once (within 2 seconds) 1 minute test Press test button twice (within 2 seconds) 5 minute test Press test button 3 times (within 2 seconds) 30 minute test Press test button 4 times (within 2 seconds) 90 minute test LED fault indicator code One flash ON/pause (4 seconds) Battery is not connected Two flashes ON/pause (4 seconds) Battery is shorted or Battery voltage drops below acceptable value. Three flashes ON/pause (4 seconds) Charger board Circuit fault Four flashes ON/pause (4 seconds) Transformer fault. Five flashes ON/pause (4 seconds) Emergency lamp fault. Six flashes ON/pause (4 seconds) Remote head lamp fault. Seven flashes ON/pause (4 seconds) EXIT LED strip fault. NOTE: Fire Alarm: Connecting extra wires to fire alarm (6V-24V), “Exit” will be blinking when fire alarm is ringing. ordering code • Add the SD option from the option section of select product specification sheets © 2013 Koninklijke Philips Electronics N.V. All rights reserved. Specifications are subject to change without notice. CE-17300 03/13 Comments CE-17300 SD/ST Self-Diagnostic/Self-Testing © 2013 Koninklijke Philips Electronics N.V. All rights reserved. Specifications are subject to change without notice. Philips Lighting Company 200 Franklin Square Drive Somerset, NJ 08873 Phone: 855-486-2216 Philips Lighting Company 281 Hillmount Road Markham ON, Canada L6C 2S3 Phone: 800-668-9008 CE-17300 03/13 www.philips.com/luminaires www.philips.com/luminaires