Self-Diagnostic/Self-Test SD/ST Series CE-17300

advertisement
general description
diagnostic operation
• NFPA 101 (life safety code) requires that a
functional test be conducted on every required
emergency lighting system at 30 day intervals for a
minimum of 30 seconds. Additionally, an annual test
must be conducted for 90 minute duration. The
Self-Diagnostics/Self-Test option assists the user in
meeting these requirements.
• Automatic Test: The unit automatically initiates a
Self-Test and Self-Diagnostic test as follows:
Verifies battery disconnection, charger failure, lamp
failure and transformer failure at every 5 seconds.
1 minute battery discharge test every month.
30 minutes battery discharge test on the 6th
month of the year.
90 minutes battery discharge test on the 12th
month of the year.
features
• Monitors battery voltage, lamp continuity, incoming
utility power and unit performance every 5
seconds without discharging battery or illuminating
lamps.
• Automatically indicates lamp, battery and charger
status by dual-color LED lamp.
• Factory preset does not need field adjustment.
• Integrated function Fire alarm (6V-24V) function is
integrated in Self-Diagnostics/Self-Test Option.
CE-17300
Self-Diagnostic/Self-Test
SD/ST Series
Circuitry & Management System
compatibility
Patron Series
Patron LED Series
VU6 Series
VC Series
VU6L
55 Line Contemporary
44R Line
VE Series
Specifier’s Reference
Project
Type
Model No.
manual test
Press test button once (within 2 seconds)
1 minute test
Press test button twice (within 2 seconds)
5 minute test
Press test button 3 times (within 2 seconds)
30 minute test
Press test button 4 times (within 2 seconds)
90 minute test
LED fault indicator code
One flash ON/pause (4 seconds)
Battery is not connected
Two flashes ON/pause (4 seconds)
Battery is shorted or Battery voltage drops below acceptable value.
Three flashes ON/pause (4 seconds) Charger board Circuit fault
Four flashes ON/pause (4 seconds)
Transformer fault.
Five flashes ON/pause (4 seconds)
Emergency lamp fault.
Six flashes ON/pause (4 seconds)
Remote head lamp fault.
Seven flashes ON/pause (4 seconds)
EXIT LED strip fault.
NOTE: Fire Alarm: Connecting extra wires to fire alarm (6V-24V), “Exit” will be blinking when fire alarm is ringing.
ordering code
• Add the SD option from the option section of select product
specification sheets
© 2013 Koninklijke Philips Electronics N.V. All rights reserved.
Specifications are subject to change without notice.
CE-17300 03/13 Comments
CE-17300 SD/ST Self-Diagnostic/Self-Testing
© 2013 Koninklijke Philips Electronics N.V. All rights reserved.
Specifications are subject to change without notice.
Philips Lighting Company
200 Franklin Square Drive
Somerset, NJ 08873
Phone: 855-486-2216
Philips Lighting Company
281 Hillmount Road
Markham ON, Canada L6C 2S3
Phone: 800-668-9008
CE-17300 03/13 www.philips.com/luminaires
www.philips.com/luminaires
Download