Neutral grounding Studies on the selection and optimization of transformer neutral grounding in electrical networks At a glance During the normal operation of an electrical network, the method of neutral treatment is not decisive. In the case of a ground fault, however, it is of crucial importance. More than 80 per cent of all faults in electrical networks start as ground faults. Siemens Power Technologies International (Siemens PTI), your provider of network consulting, network planning software and training on the Siemens T&D portfolio, offers explicit solutions for the review and optimization of neutral grounding, which is an essential task in sustainable network planning. Due to the topological, demographical and political conditions and historical developments different types of neutral grounding were established for public transmission and distribution networks. Also for industrial networks different methods are applied. In many regions and networks the preferred method of neutral treatment has remained unchanged for decades. Due to increasing demands on the networks and changes to the network structures in many cases the selected method is no longer the optimum solution. The Siemens PTI portfolio includes: Measurements in the network for analyzing the present situation, data collection and verification Evaluation and optimization of the present method of neutral treatment Selection and sizing of neutral grounding equipment Analysis of concepts for fault localization and protection, protection coordination Recommendations for future operation Detailed analysis of documented faults The challenge The selection of the optimum neutral grounding method for an individual network strongly Power Technologies International (Siemens PTI) Network Consulting Answers for infrastructure and cities. depends on its size and structure, shares of cables and overhead lines, and also on quality requirements regarding the energy supplied. A technical and economical optimization of the neutral treatment is particularly required in the following situations: Erection of a new (partial) network, e. g. in the industrial sector Enlargement of a network due to expansion projects or integration of neighboring networks Replacement of overhead lines by cables or other measures which increase the line-toground capacities Increasing level of network automation High investment costs for keeping the present type of neutral grounding Unsatisfactory level of supply reliability due to the number of outages, poor ground fault detection or localization Our solution In close cooperation with the client the optimum method of neutral grounding is developed for an individual network. The following describes a typical roadmap for optimizing the neutral grounding of a distribution network: Technical comparison of the pros and cons of the different types of neutral grounding Measurements in the network including zerosequence impedances, reduction factors, inductive coupling, ground potential rise and touch voltages as well as ground fault tests Review of the neutral grounding equipment and dimensioning of new equipment Calculation of the ground fault currents Analysis of the existing protection concept and requirements for new devices Evaluation of selectivity in case of ground faults (primary and backup protection) 2,0 1,8 1,6 R0 Selection of devices for ground fault localization Evaluation of the grounding systems of substations and ring main units Assessment of inductive coupling on telecommunication lines Impedance in Ohm 1,4 1,2 1,0 0,8 X0 0,6 It was found that the installed Petersen coil controller was not capable of dealing with the present conditions and thus an automatic control process was not initiated. Therefore, the installation of an appropriate new Petersen coil controller was recommended. 0,4 Resonance curve 0,2 0,0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 Measurement current in A Compilation and comparison of equipment costs for the considered variants Proposals for network conversion actions Application example 1 In this project, the network operator had to decide whether to invest in the adaptation of resonant grounding (RNG) or in the installation of low-impedance neutral grounding (LNG). The assessed 20 kV partial networks mainly were of urban character with only a small share of overhead lines (figure 1). Figure 2: Measured zero-sequence impedance of a selected cable type After a detailed assessment of both variants it was recommended to convert one partial network immediately and to temporarily operate two partial networks with short-term LNG. These were to be converted in medium term after adequate measures behead been taken (figure 3). Petersen coil + grounding transformer UW-West RNG 3 resistances, coil+ grounding transformer UW-West short term LNG earthing of pole substations with overhead lines LNG 3 resistances earthing of pole substations with overhead lines Figure 3: Recommendations for optimization Figure 1: Present status of the three partial networks (schematic view) First, the zero-sequence impedances of the decisive cable types were measured (figure 2) and the inductive coupling on telecommunication lines and the grounding conditions at typical and critical ring main units were determined. Secondly, appropriate equipment for neutral grounding was selected and network calculations were performed for both options. Published by and copyright © 2012: Siemens AG Infrastructure & Cities Sector Smart Grid Division, Services IC SG SE PTI BD Freyeslebenstr. 1 91058 Erlangen, Deutschland www.siemens.com/power-technologies www.siemens.com/smartgrid Application example 2 Figure 4: Resonance curve analysis Application example 3 For a planned offshore wind farm the suitable method for neutral grounding for the 33kV level had to be determined. Both the damping of ground fault currents and the proposed protection concept had to be considered. It was recommended to operate the 33 kV level with low-impedance neutral grounding and limit the single-phase short-circuit current to max. 500 A. For this concept location and parameters of the required grounding transformers were determined. Further, guidelines for normal operation and emergency operation were developed. Figure 5 shows the recommended approach. In this project the effectiveness of the Petersen coil controller for optimum setting of arc suppression coils had to be investigated for an industrial network operated with resonant grounding. At the beginning the phase-to-ground voltages and the neutral-to-ground voltage were measured. Then the resonance curve of the network was recorded (figure 4). Finally, the control process was verified by partial shutdown of cable sections in the network. Siemens Industry, Inc. Siemens Power Technologies International 400 State Street P.O. Box 1058 Schenectady, NY 12301-1058 USA 132 kV 33 kV Figure 5: Recommended concept. For more information, please contact our Customer Support Center. Phone: +49 180 524 84 37 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail: support.ic@siemens.com Smart Grid Division Printed in Germany Printed on elementary chlorine-free bleached paper. All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.