1 6 " 30" Vented aluminum cabinet with base mounting 49" to 52" shall be Type NEMA 3R Size M-30 BASE MOUNTED TRAFFIC SIGNAL CONTROLLER CABINET Bushings required on all conduits 3" spacing between conduits (typ) Cap any unused conduit (s) Refer to contract documents for the finished concrete surface requirement for foundations. NOTE: Bolt pattern to manufacturer's specifications 24" 22" min min (2) required. (4) 3" schedule 80 PVC conduits (min) or as shown on the plans 40" MIN 1 1/2" schedule 80 PVC 42" MIN rigid metal conduit #6 insulated or larger stranded copper PLAN ground wire with 48" slack above Grade level foundation. 1 1/2" schedule 80 3/4"x 42" galvanized foundation PVC conduit bolts, nuts & washers (2 required) (Refer to Detail "A" on Handhole 3" Sheet 6 of 7 for use of 3 1/2" Drop In type bolts and anchors.) To Service Disconnect 36" 42" System Grounding NOTE: 1) Grounding system shall measure 10 ohm Use non-solder Insulated Ground wire type connection or less to ground, with a 10' (min) spacing between ground rods. ELEVATION Gravel 3/4" x 10'-0" copper clad 2) All insulated jackets are to remain ground rod(s) a variable distance from foundation as directed on cable entering controller. FOUNDATION by Engineer and in accordance with the current N.E.C. 3) Keep 1-3" conduit on left side open for ITS File: PW:RD/TR/Signals/Web/Statewide SD/Final NOT TO SCALE Rev. 02/17/15 MICHIGAN DEPARTMENT OF TRANSPORTATION BUREAU OF HIGHWAYS DELIVERY STANDARD PLAN FOR Michigan Department of Transportation ENGINEER OF DELIVERY PREPARED BY BASE MOUNTED T.S. CONTROLLER CABINET/FOUNDATIONS TRAFFIC AND SAFETY ENGINEER OF DEVELOPMENT DRAWN BY: CHECKED BY: (SPECIAL DETAIL) FHWA APPROVAL DATE SIG-045-A PLAN DATE SHEET 1 of7 1 6 " 36" Vented aluminum cabinet with base mounting 49" to 52" shall be Type NEMA 3R Size M-36 BASE MOUNTED TRAFFIC SIGNAL CONTROLLER CABINET Bushings required on all conduits 3" spacing between conduits (typ) Cap any unused conduit (s) Refer to contract documents for the finished concrete surface requirement for foundations. NOTE: Bolt pattern to manufacturer's 24" 22" min min specifications (2) required. (4) 3" schedule 80 PVC conduits (min) or as shown on the plans 40" MIN 1 1/2" schedule 80 PVC 42" MIN rigid metal conduit PLAN #6 insulated or larger stranded copper Grade level ground wire with 48" slack above foundation. 1 1/2" schedule 80 3/4"x 42" galvanized foundation PVC conduit bolts, nuts & washers (2 required) Handhole (Refer to Detail "A" on 3" Sheet 6 of 7 for use of 3 1/2" Drop In type bolts and anchors.) To Service Disconnect 36" 42" System Grounding Use non-solder type connection 3/4" x 10'-0" copper clad Insulated Ground wire ELEVATION Gravel NOTE: ground rod(s) a variable distance from foundation as directed by Engineer and in accordance FOUNDATION with the current N.E.C. 1) Grounding system shall measure 10 ohm or less to ground, with a 10' (min) spacing between ground rods. 2) All insulated jackets are to remain on cable entering controller. 3) Keep 1-3" conduit on left side open for ITS NOT TO SCALE MICHIGAN DEPARTMENT OF TRANSPORTATION BUREAU OF HIGHWAYS DELIVERY STANDARD PLAN File: PW:RD/TR/Signals/Web/Statewide SD/Final (SPECIAL DETAIL) FHWA APPROVAL DATE Rev.02/17/15 SIG-045-A PLAN DATE SHEET 2 of7 2 6 " Vented aluminum cabinet with base mounting shall be Type NEMA 3R Size 6 2 5 . 5 " t o 44" 58" 8" TO 27" 55" 3/4" x 2 1/2" galvanized bolts, nuts & washers (4 required) Washer A A Base Adapter (spacer if required) A 15" A Lock washer Nut SECTION A-A BASE MOUNTED TRAFFIC SIGNAL CONTROLLER CABINET Bushings required on all conduits Refer to contract documents for the finished 3" spacing between conduits (typ) Cap any unused conduit (s) concrete surface requirement for foundations. NOTE: Bolt pattern to manufactures 30" 28" min min specifications (4) required. (4) 3" schedule 80 PVC conduits 46" MIN 1 1/2" schedule 80 PVC 48" MIN rigid metal conduit PLAN Grade level #6 insulated or larger stranded copper ground wire with 48" slack above foundation. 1 1/2" schedule 80 3/4"x 42" galvanized foundation (4) bolts, PVC conduit (4) nuts & (4) washers (required) Handhole (Refer to Detail "A" on 3" Sheet 6 of 7 for use of 3 1/2" Drop In type bolts and anchors.) To Service Disconnect 36" 42" System Grounding Use non-solder type connection 3/4" x 10'-0" copper clad ground rod(s) a variable distance from foundation as directed Insulated Ground wire NOTE: ELEVATION Gravel 1) Grounding system shall measure 10 ohm or less to ground, with a 10' (min) spacing between ground rods. FOUNDATION by Engineer and in accordance 2) All insulated jackets are to remain on cable entering controller. with the current N.E.C. 3) Keep 1-3" conduit on left side open for ITS NOT TO SCALE MICHIGAN DEPARTMENT OF TRANSPORTATION BUREAU OF HIGHWAYS DELIVERY STANDARD PLAN File: PW:RD/TR/Signals/Web/Statewide SD/Final (SPECIAL DETAIL) FHWA APPROVAL DATE Rev.02/17/15 SIG-045-A PLAN DATE SHEET 3 of7 2 7 . 5 " Vented aluminum cabinet with base mounting shall be Type NEMA 3R Size 6 STRETCH 2 5 . 5 " t o 44" (USE FOR ITS APPLICATIONS) 8" TO 77" 44" 66" 3/4" x 2 1/2" galvanized bolts, nuts & washers (4 required) Washer A A Base Adapter (spacer if required) A 15" A Lock washer Nut SECTION A-A BASE MOUNTED TRAFFIC SIGNAL ITS CONTROLLER CABINET (IF USED) Bushings required on all conduits Refer to contract documents for the finished 3" spacing between conduits (typ) Cap any unused conduit (s) concrete surface requirement for foundations. NOTE: Bolt pattern to manufactures 30" 28" min min specifications (4) required. (4) 3" schedule 80 PVC conduits 46" MIN 1 1/2" schedule 80 PVC 48" MIN rigid metal conduit PLAN Grade level #6 insulated or larger stranded copper ground wire with 48" slack above foundation. 1 1/2" schedule 80 3/4"x 42" galvanized foundation (4) bolts, PVC conduit (4) nuts & (4) washers (required) Handhole (Refer to Detail "A" on 3" Sheet 6 of 7 for use of 3 1/2" Drop In type bolts and anchors.) To Service Disconnect 36" 42" System Grounding Use non-solder type connection 3/4" x 10'-0" copper clad ground rod(s) a variable distance from foundation as directed Insulated Ground wire NOTE: ELEVATION Gravel 1) Grounding system shall measure 10 ohm or less to ground, with a 10' (min) FOUNDATION by Engineer and in accordance spacing between ground rods. 2) All insulated jackets are to remain with the current N.E.C. on cable entering controller. 3) Keep 1-3" conduit on left side open NOT TO SCALE MICHIGAN DEPARTMENT OF TRANSPORTATION BUREAU OF HIGHWAYS DELIVERY STANDARD PLAN File: PW:RD/TR/Signals/Web/Statewide SD/Final for ITS (SPECIAL DETAIL) FHWA APPROVAL DATE Rev.02/17/15 SIG-045-A PLAN DATE SHEET 4 of 7 48" 30" 24" to 30" Controller Controller Foundation Pad 8" r Doo r Doo 30" ted oun e M r Bas lle o r t Con et n i Cab TOP VIEW 3" above Grade Level " 48 er roll Cont d a P Controller Pad Top of Pad 1" 4" Grade Level 3" 3" Expansion Joint Controller SIDE VIEW Foundation BASE MOUNTED CONTROLLER PAD NOTE: Payment for controller pad to be included in controller foundation pay item. Controller cabinet door to open toward pad. NOT TO SCALE MICHIGAN DEPARTMENT OF TRANSPORTATION BUREAU OF HIGHWAYS DELIVERY STANDARD PLAN File:PW:RD/TR/Signals/Web/Statewide SD/Final (SPECIAL DETAIL) FHWA APPROVAL DATE Rev.02/17/15 SIG-045-A PLAN DATE SHEET 5 of 7 3/4" x 3 1/8" Stainless steel Hex HD threaded bolt Top of concrete foundation Top of conduits 1" Hole diameter Mount drop in anchor flush to top of foundation 8" 3/4" x 3" Stainless steel anchor Thread length is approx. 1/2 total length of drop in anchor. 3" Embedment min. Foundation Notes: 1. Use AISI 300 Series Stainless Steel for all bolts and anchors. 2. Use Drop In foundation bolts and anchors as directed by the Engineer. ALTERNATIVE DETAIL "A": DROP IN FOUNDATION BOLTS & ANCHORS NOT TO SCALE MICHIGAN DEPARTMENT OF TRANSPORTATION BUREAU OF HIGHWAYS DELIVERY STANDARD PLAN File:PW:RD/TR/Signals/Web/Statewide SD/Final (SPECIAL DETAIL) FHWA APPROVAL DATE Rev.02/17/15 SIG-045-A PLAN DATE SHEET 6 of 7 Cabinet Interior Left Side Cabinet Interior Back Side Cabinet Interior Right Side T.S. Spare Parts T.S. Thermostat T.S. T.S. Power Radios Supply Modems T.S. Detection Rack PS 250 Preempts Reserved Shelves ITS 12" ITS 20" T.S. Controller T.S. MMU T.S. Video Monitors for Power Distribution T.S. "D" Connector (mount horizontal and slide down) & light bulb T.S. terminal facility T.S. Detector terminations (Slide this down to bottom of rail) TRAFFIC SIGNAL NEMA 3R SIZE 6 CABINET REQUIREMENTS Cabinet Interior Left Side Cabinet Interior Back Side ITS Cabinet Interior Right Side ITS ITS T.S. Thermostat T.S. Spare Parts T.S. T.S. Power Supply Radios Modems T.S. Detection Rack PS 250 Preempts Reserved Shelves 20" 12" T.S. Controller T.S. MMU for T.S. Video Monitors Power Distribution T.S. "D" Connector (mount horizontal and slide down) & light bulb T.S. terminal facility T.S. Detector terminations (Slide this down to bottom 1-2" Raceway of rail) TRAFFIC SIGNAL NEMA 3R SIZE 6 STRETCH CABINET REQUIREMENTS FOR ITS APPLICATIONS NOT TO SCALE MICHIGAN DEPARTMENT OF TRANSPORTATION (SPECIAL DETAIL) BUREAU OF HIGHWAYS DELIVERY STANDARD PLAN FHWA APPROVAL DATE File:PW:RD/TR/Signals/Web/Statewide SD/Final Rev.02/17/15 SIG-045-A PLAN DATE SHEET 7of 7