IMPACT OF SYNTHETIC INERTIA FROM WIND POWER ON THE PROTECTION/CONTROL SCHEMES OF FUTURE POWER SYSTEMS: SIMULATION STUDY F. Gonzalez-Longatt† † Faculty of Computering and Engineering, Coventry University AS410 Armstrong-Siddeley Building, Priory Street, CV1 5FB- Coventry, +44 779 5634298, fglongatt@ieee.org Keywords: Frequency controller, frequency stability, power system, protection scheme, wind turbine generator. Abstract Future power systems face several challenges; one of them is the use of high power converters that decouple new energy sources from the AC power grid. This decreases the total system inertia affecting its ability to overcome system frequency's disturbances. The wind power industry has created a controller to enable inertial response on wind turbines generators: Artificial, Emulated, Simulated, or Synthetic Inertial. This paper deals with issues related to the synthetic inertia of wind turbines based on full-converters and their effect on the frequency protection/control schemes during the recovery period after system frequency disturbances happen. The main contribution of this paper is to demonstrate (based on simulations) the recovery period of under-frequency transients on future power systems which integrate wind turbines with synthetic inertia capability not completely avoid worse scenarios in terms of underfrequency load shedding. The extra power delivered from a wind turbine during frequency disturbances can substantially reduce the rate of change of frequency providing time for the active governors to respond. However, synthetic inertia might not completely avoid under-frequency load shedding. 1 Introduction Future power systems face several challenges: (i) the high penetration level of renewable energy from highly variable generators connected over power converters, (ii) several technologies for energy storage with very different time constants, some of them using power converters as an interface to the grid, (iii) A pan-European transmission network facilitating the integration of large-scale renewable energy sources and the balancing and transportation of electricity based on underwater multi-terminal high voltage direct current (MTDC) transmission. All of them have an element in common, high power converters that decouple the new energy sources from the pre-existent AC power systems. During a system frequency disturbance the generation/demand power balance is lost, the system frequency will change at a rate initially determined by the total system inertia. However, future power systems will increase the installed power capacity (MVA) but the effective system inertial response will stay the same nowadays, this is because the new generation units based on power converters creates a decoupling effect of the real inertia and the ac grid. The result is deeper frequency excursions of system disturbances. A considerable reduction in the ability to overcome system frequency's disturbances is expected, the inertia response may be decreased. The inertial response of the system might be negatively affected with devastating consequences for system security and reliability. There are several good papers [1], [2], [3], and technical reports [4], [5], [6] dealing with theory [7], [8], [9], modelling [10] and simulation [2], [11] of inertial response of wind turbine generators (WTG) and some of them provide general ideas about possible impacts on power systems and there effects on transient under-frequency response [12], [13], [14]. Even some controls strategies have been proposed to mitigate the impact of reduced inertia [15]. However, there is lack of knowledge about the impact of inertial response of wind turbines on deterministic frequency protection/control schemes in future power systems. This aim of this paper is presents the real impact of synthetic inertia on wind turbines based on full-converters and there effect on the frequency protection/control schemes during the recovery period after system frequency disturbances happen. The paper is organized as follows. Section 2 describes the frequency response on power system after a frequency disturbance. Section 3 presents the concept of synthetic inertia and show two approaches used on WT controller to create inertial responses. Section 4 address aspects related to protection/control schemes on power system and some potential challenges for futures networks. Section 5 the results of simulations that define the impact of synthetic inertia on the protection/control schemes over a test system. Finally, the advantages of this novel application are discussed in Section 5. 2 Frequency Response The frequency of a power system depends on real power balance: generation-demand. In the normal operation of a power system, the frequency is regulated within strict limits by adjusting the electrical supply to meet the demand. Responsibility of frequency control is managed in United Kingdom by National Grid PLC, thought the procurement and despatch of frequency response services, under normal operation conditions the frequency is maintained at 50Hzr0.2Hz [16]. If the balance between generation-demand is not reached, the system frequency will change at a rate which is dependent upon the initial power mismatch and the total system inertia. Large frequency disturbances, particularly trips of large generation plants, cause generation-demand unbalance that must be corrected by frequency control loops. These controllers are provided in order improve the system frequency response (SFR). The frequency controllers cover multiple time-frames: (i) inertial response also know as fast primary response, (ii) governor response also known as slow primary response, and (iii) automatic generation control (AGC). These controllers define the dynamic changes associated to System Frequency Response (SFR). During a system frequency disturbance, the inertial response dominates initial frequency changes then the combination of system inertia and governors response dictate the extreme value of frequency (maximum or minimum). Later, the governor response and load response dominate the frequency mismatch between the system frequency and statutory value until AGC takes over. Tertiary frequency control is additional and slower compared to previous two controllers. The task of tertiary control depends on the organizational structure of a given power system and the role that power plant plays in the structure [17]. Primary response is provided locally at device level, Secondary response is mainly area-wide inside an administrative area, and tertiary response is a global concept for interconnected systems. Frequency response provided by WTG's is different to traditional generation systems. Modern variable speed WTG does not naturally contribute to system inertial and does not contribute to the governor response without incurring significant operational cost penalties. 3 Synthetic Inertia The total system inertia of a traditional power system comprises of the combined inertia of most of the spinning generation and load connected to the power system. The contribution of the system inertia to a single load or generator depend on changes in the system frequency and causes change in its rotational speed hence, a change its kinetic energy. The power associated with this change in kinetic energy is fed or taken from the power system and is known as the inertial response. During a system frequency event the total system inertia response of all electrical machines connected to the system is the main factor that determines the initial rate of frequency change (ROCOF). Modern WTGs use power electronics converters to enable variable speed operation in order to capture wind energy over a wide range of speeds. However, these converters isolate the rotational speed from the system frequency so WTG based on back-to-back AC/DC/AC converters offer no natural response to system frequency [3], [10]. Author has included the adjective "natural" on the previous sentence because some manufacturers have started to integrate controllers on modern WTG’s in order to provide inertial response (and governor response on some cases) for large, short-duration frequency deviations. The Wind turbine industry has created several names for this control system that enable inertial responses on a WTG: Artificial, Emulated, Simulated, or Synthetic Inertial. Examples of synthetic inertia controlled commercially available for WTG are: General Electric WindINERTIA™ [18], [19], ENERCON Inertia Emulation [20]. The objective of the synthetic inertia control is extracting the stored inertial energy from the moving part on WTGs. The idea is to produce incremental energy similar to that provided by a synchronous generator with real inertia. This is a local and automatic controller at wind turbine level which has a response in the same time-frame as primary controllers (<30s). Synthetic inertia controllers are based on two different approaches: (a) Releasing "hidden" inertia and (b) Reserve capacity in pitch. 2.1 Releasing the "Hidden" Inertia Releasing the "hidden" inertia concept allows a controller to the take the kinetic energy from a wind turbine (WT) rotating mass. Significant energy is stored on a WTG, electrical generator operating at high speed has a large amount kinetic energy stored in rotor of generator, but majority of that kinetic energy is in rotor bales. A WT using permanent magnet synchronous generator (PMSG) on a direct-drive concept has less kinetic energy stored due to the lower rotational speed. Table 1 shows typical values of 3MW modern variable speed WTG. Drive train Concept Double fed 3-stage gear Low Speed Full converter (LSFC) Direct drive Medium Speed full Converter (MSFC) 2-stage gear High Speed Full Converter (HSFC) 3-stage gear Rated Speed [rpm] Generator rotor inertia [Kg/m2] 1200 250 14 40,500 Permanent magnet 14-pole 400 510 Permanent Magnet 6-pole 1600 115 Generator Type Wound rotor asynchronous 6pole Permanent magnet, multi pole Table 1: Typical data for a 3MW WTG. Releasing the "hidden" inertia control loop increases electric power output during the initial stages of a significant downward frequency event. The active power (inertial power, 'P) of the control is achieved by: df sys (1) 'P 2 H u f sys u dt where H express the synthetic inertia (sec) and fsys system frequency (p.u). Implementation of releasing hidden inertia controllers is depicted on Figure 1. The WT can quickly store and release a large amount of kinetic energy in the rotating masses because of the power electronic converter, due to a large amount of inertia and wide rotational speed. However, discharge of energy to the grid is only for a short period available (<30s) and recovery of WT power is supplied by the grid (unless the wind speed increases favorably!!!). DIgSILENT Slowing the wind turbine reduces aerodynamic lift and security limitations must be considered to avoid a stall. Inertial power must respect WTG components rating like mechanical loading as well as converter and generator electrical rating [9]. For large under-frequency events, the inertial control feature temporarily increases the power output of the wind turbine by about 5% to 10% of its rated power, for several seconds. ENERCON emulated inertia increases the power output about 4% to 10% of rated power for 10s [8]. Controller Releasing Hidden Inertia: max df/dt fs Grid Frequency [p.u] Derivator K min df/dt max df/dt Filter Kfilter,Tfilter2,Tfilter2 min filtere.. Filter D_P Delta_P K K2H 2H Additional power command df/dt Under-frequency load shedding (UFLS) is the most widely used protection against frequency collapse. Typically, load is shed based on a local frequency measurement in several steps of 5-20 % (of the total feeder load) each. Automatic load shedding is implemented using underfrequency relays. Typical threshold values are 48-48.5 Hz for a 50 Hz system. The main draw back of these schemes is their delayed response since they must wait for the frequency to decline before taking action. A great proportion of inertia is expected to be decoupled to the system frequency in future power systems. As consequence a larger frequency drop is expected in future networks, as consequence deterministic frequency protection/control schemes must be re-thought. Synthetic Inertial response from wind turbines can increase system security and aid large scale systems to overcome system frequency disturbances, however, control interactions can create disastrous situations. Figure 1: Releasing Hidden Inertia Controller. 5 Simulation and Results 2.2 Reserve Capacity in Pitch Traditional variable speed WTs are designed to always operate at the maximum power point tracking (MPPT) so they have no power reserve to support frequency control in there steady state. Reserve capacity in pitch concept coerces a wind standby power by maintaining reserve capacity in pitch [9], [21]. A de-loading controller enable the WT to operate over de-loading curves instead of MPPT and saves the available power as reserve by using a pitch controller (pitching) or increasing the rotational speed from the MPPT value (overspeeding). Frequency support using this controller is already discussed in details in several publications [2], [9], [18], [22], even EirGrid, the transmission system operator of the Republic of Ireland, already estipulate a scheme with this controller [23]. One negative consequence of this controller is WTs have to be operated at a considerably lower power output that otherwise possible for a given wind speed, as a consequence, less power generation is achieved and the wind is not fully utilized. A monetary compensation scheme for the wind farm owners can be created to resolve this situation. An additional grid frequency control loop in the pitch angle controller is required and it must be carefully designed in order to meet mechanical loads on the pitch drive. This approach involves some well-know consequences and requirements, as consequence, it is not considered in this paper. 4 Protection/Control Schemes When a severe frequency disturbance occurs, e.g. loss of a station (all generating units), loss of a major load centre, or loss of AC or DC interconnection, emergency control measures may be required to maintain frequency stability. These control measures may include: tripping of generators, fast generation reduction, HVDC power transfer control, load shedding, controlled opening of interconnection to neighbouring systems to prevent spreading of frequency problems and controlled islanding of local system into separate areas with matching generation and load. This section presents simulations and results over a Test System representative of a future network. All models where developed by the author using information publically available and personal assumptions where they are necessary. DigSILENT PowerFactoryTM [24] is used for time-domain simulations and DIgSILENT Simulation Language (DSL) is used for dynamic modelling. All simulations are performed using a personal computer based on Intel, CoreTM i7 CPU 2.0GHz, 8 GB RAM with Windows 7 Home Edition 64-bit operating system. 5.1 Test System The test network used for simulation in this study it is given in Figure 2. This system consists of 8-generator, 8-bus, 7load, and 22-transmission lines. It is a hypothetical simplification of a large 400 kV transmission system, it has been divided in seven areas: Top-Right, Top-left, Upper-Tail, Tail-Right, Lowest-Tail, Middle and Core+Tail. The generator G4(a) represents the aggregation of a large number of generators and it is selected as a reference. The system has a total generation of 100.736 GW and a total load of 96.75GW. Figure 2 shows the load flows for case base, there is a power flow of about 15 GW from the Top to Tail, particularly from Upper-Tail and Tail-Right and Core-Tail. Tail is an area rich on generation and Core-Tail is a load-rich area. Dynamic models for governor and automatic voltage controller (AVR) are provided to this test model. Figure 3 and 4, show the general steam turbine used as governor for all synchronous power plants and a version on IEEE Type I excitation system [25] is used as AVR. For the system demand of 100 GW, equivalent system inertia of 7.2 MWs/MVA is assumed by the author for the synchronous power plants (no wind). Demand is considered 100% dynamic with a time constant of 0.1s and frequency dependence of active power is included. L1a ~ G Upper Top -4.62 2.95 10.54 4.75 -2.73 10.54 9.50 -5.45 36.52 ~ G 1a-2 I 400.00 1.00 18.52 Top-Left G2 400.00 1.00 15.81 11.15 2.26 -4.62 2.95 10.54 10.44 -4.14 21.62 1a-1 I 395.40 0.99 10.24 -9.88 5.08 21.62 1a-1 II 4.75 -2.73 10.54 TOP 1 10.44 -4.14 21.62 1a-2 II 1a 2 22.80 -0.13 76.00 -9.88 5.08 21.62 1-4 Top-Rigth 4.95 1.01 L1 14.80 -11.16 36.09 1-3 3-4 -14.01 12.46 36.09 4 9.94 -5.37 21.74 -9.37 6.32 21.74 3 400.00 1.00 5.61 7.20 6.77 32.94 20.20 -5.41 69.71 G ~ G ~ 14.13 2.87 G4(b) G4(a) 17.34 -8.61 37.26 400.00 1.00 0.00 8.64 4.60 32.61 Tail-Right 10.95 2.22 7.06 -3.94 15.55 G ~ L4 G3 L3 8.65 -4.74 18.98 -15.66 11.38 37.26 3-7 Upper-Tail 4-7 5-7 -8.21 5.46 18.98 Lowest-Tail 5 7 400.00 1.00 -8.90 9.51 8.76 43.08 17.34 3.52 0.38 -0.23 0.85 9.04 -4.94 19.83 L5 -0.38 0.23 0.85 Branches Active Power [GW] Reactive Power [Gvar] Loading [%] 6 400.00 1.00 -9.12 17.11 11.24 68.23 26.05 5.29 Middle G7 L7 TAIL Core+Tail yout 1 F< RelFrq* Trip_Step1 1 Logic RelLslogic 2 F< RelFrq* Trip_Step2 2 Logic RelLslogic yout 3 F< RelFrq* Trip_Step3 3 Logic RelLslogic yout 4 F< RelFrq* Trip_Step4 4 Logic RelLslogic yout 5 F< RelFrq* 5 Logic RelLslogic yout Trip_Step5 6 Logic RelLslogic yout U< Logic RelLslogic yout F 0 Measurement RelFmeas* G ~ 1 G6 L6 U Project: DPSP 2012 Graphic: Benchmark Model Francisco M. Gonzalez-Longatt 02/01/2012 fglongatt@ieee.org PowerFactory 14.0.525 16.14 3.28 G ~ -8.57 5.72 19.83 Benchmark System fglongatt.org. 11.40 9.40 49.27 6-7 5-6 G5 Under U and Under F: Under U and Under Freq Trip at 6 Steps Under Frequency Protection 400.00 1.00 -4.01 G ~ Load Flow Balanced Nodes Line-Line Voltage, Magnitude [kV] Voltage, Magnitude [p.u.] Voltage, Angle [deg] -6.76 4.43 15.55 outside statutory limits: range 49.8 Hz to 50.2Hz for more than 5 cycles, (ii) the level of normal loss of power infeed is set-up to 1.35 GW, frequency response to avoid a deviation in the system frequency by more than 0.2Hz, (iii) the system frequency could rise to 52 Hz or fall to 47 Hz in exceptional circumstances. If system frequency is over 52.0 Hz, overfrequency relays will trip generators, (iv) frequency control devices (or a speed governor) are set up to operate with an overall speed Droop of 4% (GB SQSS establishes between 3 and 5%). In this paper, UFLS is set to start at 49.8Hz and the plan consists of six load shedding steps of unequal size with the total amount of load shed of 0.25 p.u [26]. A delay for each load shedding step is 0.1 s (5 cycles). Figure 5 shows specific under-frequency relay model developed and used in this paper. DIgSILENT DIgSILENT G1 Date: 2/13/2012 Annex: 6 F< RelFrq* Trip_Step6 DIgSILENT Figure 2: Test System: Case Base. gov_GTGOV: General Turbine Governor Under_U U< RelUlim psco 0 Under Voltage Protection psetp 1 Valve Vmax Droop - w 2 Pole/Zero Gain at (1+sTb)/(1+sTa) T3,T2 {1/(1+sT)} T1 pturb K At 0 - dw wref - 1/K R 0 Vmin 3 1 Friction wlss K Dt Turb Pturb Figure 5: Under-frequency Relay Model including 6-step load shedding. pt 1 2 Power Base sgnn 4 cosn 5 5.3 Wind Turbine Model DIgSILENT Figure 3: Model of General Turbine Governor. avr_IEET1: Modified 1968 IEEE Type 1 Excitation System IEEE Std 421.5-1992 IEEE Recommended Practice for Excitation System Models for Power System Stability Studies voel 0 vuel 1 3 4 Te and and gain Ke associated with the voltage regulator Voltage Regulator Vrmax usetp 2 u upss - Verr - {K/(1+sT)} Ka,Ta Vr 1/sT Te - efd uerrs Figure 6 depict the general structure of a variable-speed wind turbine with a direct-drive permanent magnet synchronous generator (PMSG) and Figure 6 shows the model for the wind turbines created using DSL. Figure 7 show the models used for a back-to-back converter, details of each model are taken from: [27], [28], [29]. The parameters used for these models are escalated to simulate an equivalent 5 MW wind turbine. Limiter_int EFdmax,EFdmin Vf Vrmin K Ke Se sK/(1+sT) Kf,Tf Se(Efd) E1,Se1,EFdmax,Sefdmax Saturation Figure 4: Model of General AVR. Figure 6: General structure of a variable-speed wind turbine with a direct-drive synchronous generator with full-scale frequency converter. 5.2. Frequency Response Assumptions 5.4 Results and Discussion In this paper, the operational-control criteria used for system frequency analysis is based a specific criteria defined by the author, it is mainly a personal version of the GB Security and Quality of Supply Standards (GB SQSS). The following assumptions are used in this paper: (i) the level of infrequency loss of power infeed is set-up to 1.800 GW, and frequency response must avoid a deviation of the system frequency The impact of a synthetic inertia is being quantitatively analysed through time-domain simulations. This is a multimachine system as consequence, the author uses the concept of frequency of inertia centre (fc) to analyse changes in system frequency. A loss infeed is used as system frequency disturbance; it consists of tripping at t = 1.0s of one generating unit connected to Upper-Tail area at 1s (generator DIgSILENT Variable Speed Wind Turbine: Permanent Magnet Synchronous Generator 0 0 Rotor 0 DIgSILENT 0 PLL_R ElmPhi*1 P cosref_R sinref_R DC Voltage StaVmea* 0 Vdc_ref 1 Vac-P Controller ElmDsl* 3 4 Vdc 5 id_ref_R Inverter ElmVsc* 3 PLL_I ElmPll*,ElmPhi* DC/AC Controller 7 1 cosref_I sinref_I 300MW 500MW 700MW 1350MW 1500MW 1800MW 2300MW 2800MW 3200MW Annex: /2 0.1 50 49.5 0 10 20 Time (s) 0 I II III IV V -0.1 -0.2 -0.3 30 0 -0.06 -0.08 1 20 2 30 Time (s) 3 40 50 49.8 0 49.6 49.4 H= 0.1s 49.2 50 5 10 Time (s) 15 20 Figure 8: Under-frequency Relay Model including 6-step load shedding. The author used an exceptional loss of power infeed to trigger a substantial frequency excursion in the Test System; this system frequency disturbance activates the UFLS. This exceptional loss risk deviates system frequency more than 741 mHz and persist for more than 5 cycles (see Figure 9 and Case I Figure 10). Several UFLS schemes on demand side of Tail area are tested, loads: L4, L5, L6, L7 (see Figure 2), results of system frequency and ROCOF are shown on Figure 10 (load shedding Case I: 0 GW, II: 2.8260GW, III: 6.2940 GW, IV: 5.7520GW, V: 7.3660GW). A cluster of wind farms is connected on bus 3 at the Tail-Right area and is generating 30 GW and the control loop for releasing "hidden" inertia of 49.8 49.6 49.4 H= 1.0s 49.2 50 60 I II III IV IV -0.1 -0.2 -0.3 0.1 df/dt (Hz/s) -0.04 0.1 0 -0.1 -0.2 -0.3 49.8 df/dt (Hz/s) -0.02 50 49.6 49.4 0 -0.1 H= 5.0s 49.2 50.2 -0 2 0.05 H= 10.0s 50 df/dt (Hz/s) -0.02 df/dt (Hz) df/dt (Hz) 0 10 59.99 Date: 2/17/2012 Figure 10: System Frequency and ROCOF considering different UFLS schemes: Base Case Frequency (Hz) 0 0 [s] Response March 2012 df/dt (Hz/s) 0.02 -0.1 47.99 (c) 3 Figure 7: General structure of the model for back-to-back converter. -0.08 36.00 Francisco M. Gonzalez-Longatt, PhD 2 DC/AC Converter AC/DC Converter Vac-P -0.06 24.00 59.99 6 AC/DC Controller -0.04 12.00 (b) Exceptional Loss of Infeed 49 2 3 [s] 50.5 Frequency (Hz) fsys 1 5 0 iq_ref_R 47.99 Figure 9: System Frequency response to an exceptional loss of generation infeed (a) Frequency, Generation active power in GW (b) with and (c) without frequency response. Udc-Q 1 36.00 15.00 Frequency (Hz) AC Grid Voltage StaVmea* 1 Vdc_ref u iq_ref 0 Rectifier ElmVsc* 2 0 0 id_ref 2 4 Q Vac_Gen 1 Controller ElmDsl* 0 Q_ref Power Meas_Grid StaPqmea* AC Gen Voltage StaVmea* 0 1Vdc-Q 1 Vac_ref 24.00 20.00 Frequency (Hz) Power Meas_Gen StaPqmea* 0 12.00 59.99 25.00 fglongatt Vdc P_ref [s] 30.00 8.00 0.000 Back-to-Back Frame: Converter and Controllers MPT ElmMpt* 47.99 9.00 Figure 6: General structure of the model for a variablespeed wind turbine. speed 36.00 10.00 1 Shaft Speed Measurement 1 ElmSpe* Speed Measurement Elm* 24.00 df/dt (Hz/s) vw Wind Speed 12.00 11.00 hpi Turbine ElmTur* pt speed_gen 1Wind 2 0 Shaft 1 ElmSha* 1 speed_gen1 Wind Speed ElmFile 0 (a) 49.20 0.000 12.00 Generator ElmSym* 3 omega_tur1 Pwind 49.40 13.00 2 0 56.722 s 49.513 p.u. 14.00 ve 1 beta 16.252 s 49.560 p.u. 49.60 0.00 0.000 Mechanical System Pitch Control ElmSha* 6.602 s 49.259 p.u. 49.80 Frequency (Hz) PMG 50.00 5.00 u 1 50.20 10.00 curex 0 H = 3.75s is included. Benefits of the integration of this wind farm include the reduction of power flows between Top and Tail areas but an increase of 164 mHz in the minimum frequency during at exceptional loss of the power infeed. DIgSILENT G4(b) on Figure 2). The case base consists of just synchronous generators (no wind) which feed system demand. The author assumes four generators providing a governor frequency response and three conventional generators (G2, G5, and G7) will be operating without active governors (e.g., nuclear power stations) or at maximum power (e.g., valves wide open). Several levels of loss of power infeed from 0.3 to 3.2 GW are simulated and rate of change of frequency (ROCOF) is plotted on Figure 8. The ROCOF and the minimum frequency (nadir) increases as the level of loss of power infeed increase. 49.8 49.6 0 10 20 Time (s) 30 0 -0.05 -0.1 0 5 10 Time (s) 15 20 Figure 11: System Frequency and ROCOF considering different UFLS schemes: Wind Integration. The inertial control has a substantial impact on system performance. The short term impact is delivery of extra power from WT with substantially reduces the ROCOF, allowing time for the active governors to respond (see Figure 11). Increasing the capability of WT to release of hidden inertia helps to delay the UFLS. However, the frequency response provided by synthetic inertia might not completely avoid UFLS. Reducing the amount of synthetic inertia reduces the recovery effect but frequency support provided by wind turbines is reduced as well. Results demonstrate UFLS helps to reduce the negative recovery effect caused by synthetic inertia and increase security level during extreme loss power infeed. 4 Conclusions This paper is presents simulations results that provide ideas about the potential impact of synthetic inertia on wind turbines based on full-converter on the under-frequency protection/control schemes during the recovery period after system frequency disturbance happen. The substantial impact of synthetic inertia is on system inertial response: (a) the extra power delivered from WT can substantially reduces the ROCOF (b) it provides time for the active governors to respond, however a coordination between controllers looks desirable (c) increasing synthetic inertia helps to delay the UFLS (d) synthetic inertia might not completely avoid UFLS, (e) UFLS helps to reduce the negative recovery effect caused by synthetic inertia. The main contribution of this paper is to demonstrate (based on simulations) recovery period of underfrequency transient on future power systems that integrate synthetic inertia capability not completely avoid worse scenarios in terms of UFLS. [9] [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] References [21] [1] [2] [3] [4] [5] [6] [7] [8] J. B. Ekamayake, N. Jenkins, and G. Strbac, "Frequency Response From Wind Turbines," Wind Engineering, vol. 32, pp. 537-586, 2008. J. Ekanayake and N. Jenkins, "Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency," Energy Conversion, IEEE Transactions on, vol. 19, pp. 800-802, 2004. G. Lalor, A. Mullane, and M. O'Malley, "Frequency control and wind turbine technologies," Power Systems, IEEE Transactions on, vol. 20, pp. 1905-1913, 2005. N. Plc. (2010). National Grid, Grid Code Frequency Response Working Group: "Simulated Inertia". Available: http://www.nationalgrid.com/uk/Electricity/Codes/gridcode/workinggr oups/freqresp/ S. Seman and R. Sakki. (2011). Inertial response – generators and the power electronics. Available: http://www.nrel.gov/wind/systemsintegration/pdfs/2011/active_power _control_workshop/seman.pdf GE. (2009). WindINERTIA Control fact sheet. Available: http://www.geenergy.com/products_and_services/products/wind_turbines/index.jsp J. Morren, S. W. H. de Haan, W. L. Kling, and J. A. Ferreira, "Wind turbines emulating inertia and supporting primary frequency control," Power Systems, IEEE Transactions on, vol. 21, pp. 433-434, 2006. S. Wachtel and A. Beekmann, "Contribution of Wind Energy Converters with Inertia Emulation to frequency control and frequency stability in Power Systems," presented at the 8th International Workshop on Large Scale Integration of Wind Power into Power Systems as well as on Offshore Wind Farms, Bremen, Germany, 2009. [22] [23] [24] [25] [26] [27] [28] [29] I. Erlich and M. Wilch, "Primary frequency control by wind turbines," in Power and Energy Society General Meeting, 2010 IEEE, 2010, pp. 1-8. S. Yuan-zhang, Z. Zhao-sui, L. Guo-jie, and L. Jin, "Review on frequency control of power systems with wind power penetration," in Power System Technology (POWERCON), 2010 International Conference on, 2010, pp. 1-8. M. Singh, M. Vyas, and S. Santoso, "Using generic wind turbine models to compare inertial response of wind turbine technologies," in Power and Energy Society General Meeting, 2010 IEEE, 2010, pp. 17. R. Doherty, A. Mullane, G. Nolan, D. J. Burke, A. Bryson, and M. O'Malley, "An Assessment of the Impact of Wind Generation on System Frequency Control," Power Systems, IEEE Transactions on, vol. 25, pp. 452-460, 2010. L. Ruttledge and D. Flynn, "System-wide inertial response from fixed speed and variable speed wind turbines," in Power and Energy Society General Meeting, 2011 IEEE, 2011, pp. 1-7. I. Erlich, W. Winter, and A. Dittrich, "Advanced grid requirements for the integration of wind turbines into the German transmission system," in Power Engineering Society General Meeting, 2006. IEEE, 2006, p. 7 pp. D. Gautam, L. Goel, R. Ayyanar, V. Vittal, and T. Harbour, "Control Strategy to Mitigate the Impact of Reduced Inertia Due to Doubly Fed Induction Generators on Large Power Systems," Power Systems, IEEE Transactions on, vol. 26, pp. 214-224, 2011. GB. (2009). Security and Quality of Supply Standard (SQSS). Available: http://www.nationalgrid.com/uk/Electricity/Codes/gbsqsscode/ J. Machowski, J. W. Bialek, and J. R. Bumby, Power system dynamics : stability and control, 2nd ed. ed. Oxford: John Wiley, 2008. N. W. Miller, K. Clark, and M. Shao, "Frequency responsive wind plant controls: Impacts on grid performance," in Power and Energy Society General Meeting, 2011 IEEE, 2011, pp. 1-8. N. Miller, K. Clark, and R. Walling, "WindINERTIA: Controlled Inertial Response from GE Wind Turbine Generators," presented at the 45th Annual Minnesota Power Systems Conference, Minneapolis, Minnesota, 2009. S. Wachtel and A. Beekmann, "Contribution of Wind Energy Converters with Inertia Emulation to Frequency Control and Frequency Stability in Power Systems," presented at the 8th International Workshop on Large-Scale Integration of Wind Power into Power Systems as well as on Transmission Networks for Offshore Wind Farms, Bremen, Germany, 2009. A. Teninge, C. Jecu, D. Roye, S. Bacha, J. Duval, and R. Belhomme, "Contribution to frequency control through wind turbine inertial energy storage," Renewable Power Generation, IET, vol. 3, pp. 358370, 2009. J. R. Kristoffersen and P. Christiansen, "Horns Rev offshore windfarm: its main controller and remote control system," Wind Engineering, vol. 27, pp. 351-359, 2003. EirGrid. (2008). EirGrid Grid Code, Version 3.2. Available: http://www.eirgrid.com/operations/gridcode/ DIgSILENT, "DIgSILENT PowerFactory," 14.0.524.2 ed. Gomaringen, Germany, 2011. "IEEE Recommended Practice for Excitation System Models for Power System Stability Studies," IEEE Std 421.5-1992, p. 0_1, 1992. P. M. Anderson and M. Mirheydar, "An adaptive method for setting underfrequency load shedding relays," Power Systems, IEEE Transactions on, vol. 7, pp. 647-655, 1992. F. Gonzalez-Longatt, "Dynamical Model of Variable Speed WECS: Attend of Simplification," presented at the Proceeding of Fifth International Workshop on Large Scale Integration of Wind Power and Transmission Networks for Offshore Wind Farms, Glasgow, Scotland, 2006. S. Achilles and M. Poller. Direct drive synchronous machine models for stability assessment of wind farm. Available: http://www.digsilent.de/Consulting/Publications/DirectDrive_Modelin g.pdf F. González-Longatt, P. Wall, and V. Terzija, "A Simplified Model for Dynamic Behavior of Permanent Magnet Synchronous Generator for Direct Drive Wind Turbines," in IEEE PES Trondheim PowerTech 2011, Trondheim, Norway, 2011.