Example 4.2 A balanced (a b c sequence) Y- connected source with (EAN=100∠100 V) is connected to a Δ-connected balanced load (8+j4)Ω per phase. Calculate the phase and line currents. Solution: This can be solved in two ways. Method 1: the load impedance is Z Δ = 8 + j 4 = 8.944∠26.57 0 Ω If the phase voltage EAN=100∠100, the line voltage is E AB = E AN 3∠30 0 = 100 × 3∠(10 + 30) 0 = Vab Or Vab = 173.2∠40 0 V The phase current are I ab = Vab 173.2∠40 0 = = 19.36∠13.430 A Z Δ 8.944∠26.57 0 I bc = I ab ∠ − 120 0 = 19.36∠ − 106.57 0 A I ca = I ab ∠120 0 = 19.36∠133.43 0 A The line current are I a = I ab 3∠ − 30 0 = 3 (19.36)∠(13.43 − 30) 0 = 33.53∠ − 16.57 0 A I b = I a ∠ − 120 0 = 33.53∠ − 136.57 A I c = I a ∠120 0 = 33.53∠103.43 0 A Method 2: Alternatively, using single-phase analysis Ia = E AN 100∠10 0 = = 33.54∠ − 16.57 0 A 0 ⎛ Z Δ ⎞ 2.981∠26.57 ⎟ ⎜ ⎝ 3 ⎠ As above, other line currents are obtained using the (a b c) phase sequence. 111 4.8 Balanced Delta-Wye Connection Consider the Δ-Y circuit in fig.(4.18), assuming the (a b c) sequence, the phase voltage of a Delta-connected source are. E AB = VP ∠0 0 , E BC = V P ∠ − 120 0 , E CA = V P ∠120 0 There are also the line voltages as well as the phase voltages a A ECA EAB n C EBC b B c Fig.(4.18) We can obtain the line currents in many ways. 1st method Apply KVL to loop (A a n b B A) is shown in figure, writing. E AB − Z Y I a + Z Y I b = 0 Or Z Y (I a − I b ) = E AB = V P ∠0 0 Thus VP ∠0 0 Ia − Ib = ZY But Ib lags Ia by 1200 , since we assumed the (a b c) sequence, that is I b = I a ∠ − 120 0 , hence 112 I a − I b = I a (1 − 1∠ − 120 0 ) ⎛ 1 3⎞ ⎟ = I a 3∠30 0 = ⎜⎜1 + + j ⎟ 2 2 ⎠ ⎝ Substituting we get I a 3∠30 0 = VP Ia = 3 VP ∠0 0 ZY ∠ − 30 0 ZY From this, we obtain the other line currents Ib and Ic using the positive phase sequence i.e, I b = I a ∠ − 120 0 , I c = I a ∠120 0 . The phase current are equal to line currents. 2nd method To obtain the line currents is to replace the delta-connected source with its equivalent Wye-connected source, as shown in fig.(4.19). We found that the line-to line voltages of a Wye-connected source lead their corresponding phase voltage by 300. E AB = 3E AN ∠30 0 , E AN = E AB 3 ∠ − 30 o Fig.(4.19) 113 Thus, the equivalent Wye-connected source has the phase voltages. E AN = E BN = VP ∠ − 30 0 3 VP ∠ − 150 0 3 , ECN = VP ∠90 0 3 The single phase Equivalent Therefore, we can use the equivalent single-phase circuit as shown in figure below. From which the line current for phase a is VP Ia = 3 ∠ − 30 0 ZY Or, we may transform the Wye- connected load to an equivalent deltaconnected load. This results in a delta-delta system, which can be analyzed. 114 Example 4-3 A balanced Y-connected load with a phase resistance of 40Ω and a reactance of 25Ω is supplied by a balanced, positive sequence Δ-connected source with a line voltage of 210 V, calculate the phase currents. Use EAB as reference. Solution: The load impedance is Z Y = 40 + j 25 = 47.17∠32 o Ω And the source voltage is E AB = 210∠0 o When the Δ-connected source is transformed to a Y-connected source, E AN = E AB 3 ∠ − 30 o = 121.2∠ − 30 0 V The line currents are Ia = E AN 121.2∠ − 30 o = = 2.57∠ − 62 o A o ZY 47.12∠32 I b = I a ∠ − 120 o = 2.57∠ − 182 o A I c = I a ∠120 o = 2.57∠58 o A Which are the same as the phase currents. 115 4.9 Balanced Delta- Delta Connection The source as well as the load may be delta-connected as shown in fig.(4.20). Our goal is to obtain the phase and line currents as usual. Assuming a positive sequence, the phase voltages for a delta-connected source are. E AB = VP ∠0 0 , E BC = V P ∠ − 120 0 , E CA = V P ∠120 0 The line voltages are the same as the phase voltages. And assuming there is no line impedances. E AB = Vab , E BC = Vbc , ECA = Vca Hence, the phase current are I ab = Vab E AB = , ZΔ ZΔ I bc = Vbc E BC = , ZΔ ZΔ I ca = Vca ECA = ZΔ ZΔ a A Iab ECA EAB Ica c C EBC b B Fig.(4.20) 116 Ibc The line current are obtained from the phase currents by applying KCL at nodes a, b, and c. I a = I ab − I ca , I b = I bc − I ab , I c = I ca − I bc Also, we know that, each line current lags the corresponding phase current by 300, the magnitude IL of the line current is 3 times the magnitude IP of the phase current. I L = 3I P An alternative way of analyzing the Δ-Δ circuit is to convert both the source and the load to their Y-equivalents. Example 4-4: A balanced Δ- connected load having an impedance (20-j15)Ω is connected to Δ-connected, positive-sequence generator having EAB=330∠00 V. Calculate the phase currents of the load and the line currents. Solution: The load impedance per phase is Z Δ = 20 − j15 = 25∠ − 36.87 o Ω The phase currents are I ab = Vab 330∠0 o = = 13.2∠36.87 o A Z Δ 25∠ − 36.87 o I bc = I ab ∠ − 120 o = 13.2∠ − 83.13 o A I ca = I ab ∠120 o = 13.2∠156.87 o A For a delta load, the line current always lags the corresponding phase current by 300 and has a magnitude 3 times that of the phase current. 117 I a = I ab ( ) ( 3∠ − 30 o = 13.2∠36.87 o )( 3∠ − 30 o = 22.86∠6.87 o A I b = I a ∠ − 120 o = 22.86∠ − 113.13 o A I c = I a ∠120 o = 22.86∠126.87 o A 118 )