OVI-R2 Voltage Indicator OVI-R2 Voltage Indicator with Two Relay Outputs Features No auxiliary power is needed for voltage detection. OVI-R Capacitive Voltage Indicator is designed for to use with MV capacitive voltage divider devices. Device has two separate contact outputs for condition monitoring. This contact also can be used for interlocking the high voltage electrical equipment to prevent any dangerous operation entering into the electrified area. Bright and long-life LED to indicate. Easy for installation and maintenance. Can stand power frequency withstand voltage test together with electrical equipment in switchgears. Connection Diagram Technical Parameters 1. Rated frequency : 50Hz or 60Hz 2. Ambient temperature range : -25℃ to +55℃ 3. Protection class : IP54 4. Power frequency withstanding voltage : 2kV/1min 5. Threshold voltage : 15% to 40%Un 6. Dimension : 96*48*55mm 7. Cutting size : 91*44mm 8. Auxiliary power supply : 24VDC/AC or 110V-220VDC/AC 9. Power consumption : Less than 3W 10. Contact outputs : 2*(3.5A, 250VAC or 30VDC) Exclusive representative www.akk-energia.pl akk@akk-energia.pl OVI-R2 Voltage Indicator Function Descriptions OVI-R Terminal Position Label Marking 1 Connection Connect to earth point 2 L1 Connect with the plug of L1 wire 3 L2 Connect with the plug of L2 wire 4 L3 Connect with the plug of L3 wire 5 NO1 6 COM1 7 NC1 Normally closed first contact 5 NO2 Normally open second contact 6 COM2 7 NC2 8 P1:110V(+/~) 9 P2:0V(-/~) 10 P3:220V(+/~) Rated PhaseVoltage Input Auxiliary Power Supply Input Lock Lamp Status 3-Phase Indicator Status Yes Yes On On No No Off Off Yes No Off On No Yes Off Off Normally open first contact The common terminal of first contact Auxiliary Contact Status NC -COM (1-2) On NC-COM (1-2) On NC-COM (1-2) On NO-COM (1-2) Off NO-COM (1-2) Off NO-COM (1-2) Off NC-COM (1-2) Off NO-COM (1-2) On The common terminal of second contact Normally closed second contact Input terminal of auxiliary power supply 110V (DC/AC), null for 24V supply according to type Common terminal of auxiliary power supply 0V (DC/AC) Input terminal of auxiliary power supply 220V (DC/AC) or 24V (DC/AC) according to type Exclusive representative Required data for order Capacitance of coupling electrode C1 Cable type and length (if required) Rated voltage Un Auxiliary power supply voltage www.akk-energia.pl akk@akk-energia.pl