Eaton Corporation Characteristics of Different Power System

advertisement
Eaton Corporation
Eaton Presentation On Power System Grounding
– Generator Grounding - Winding Pitch Factors,
Hybrid Grounding
IEEE Nashville
Date: February 3, 2015
Power System Grounding
Abstract
• Most Misunderstood Element of Power
System design
Present Practice
• Industrial / Commercial
• NEC Art. 250-1 Scope
• Grounded to Limit Voltages due to;
– Lightning
– line Surges
– Unintentional Contact with Higher Voltages
– Stabilize VLG During Normal Operation
Characteristics of Different
Power System Grounding
techniques: Fact & Fiction
By
David Shipp
Cutler-Hammer
Frank Angelini Cutler-Hammer
Introduction
• History
• Solidly Grounded
• Ungrounded
NEC Article 250-5
• (b) AC Systems
Grounded
50V-1000V - Shall be
– VLG < 150V
– 3 phase/4 wire
– 3 phase/4 wire Delta
1
NEC Article 250-5
• (b) Continued
– Exception 5 High Impedance Grounded Shall
be Permitted
– Qualified Maintenance Personnel Only
– Service Continuity Required
– VL-N Loads Not Served
Definitions (IEEE “Green Book”)
•
•
•
•
•
NEC Article 250-5
• [c] AC Systems > 1KV
– Where Such Systems Are Grounded, They
Shall Comply With Article 250
What Comprises a Ground
System? Figure 1
Ungrounded System
Grounded System
Grounded Solidly
Resistance Grounded
Effectively Grounded
Figure 2: Ground Fault on an
Ungrounded System
Figure 3: Voltages During Ground Fault
on an Ungrounded System
2
Figure 4: Ground Fault on a
Solidly Grounded System
Figure 5: Voltage Profiles for
Solidly Grounded System
a) No Ground Fault
Table I
Solid Grounded vs. Ungrounded
b) Ground Fault
To Ground the System or Not to
Ground
S y s te m
G ro u n d e d
U n g ro u n d e d
V o lta g e
P h a s e A to P h a s e C
P h a s e A to P h a s e B
480
480/
P h a s e C to P h a s e B
480/
P h a s e A to G ro u n d
P h a s e B to G ro u n d
P h a s e C to G ro u n d
480/
3
3
480
480
3
0
3
480
0
480
2 9 ,2 0 0
0
0
1 .0 4
.6
.6
480/
• VLN Loads Served?
480
• Service Continuity Importance?
F a u lt C u rr e n t - A m p e r e s
P hase B
P hase C
P hase A
Solidly-Grounded Systems
Figure 6:(Industrial/Commercial)
Ungrounded Systems
• Multiple Ground Faults
• Resonant Conditions
• Transient Overvoltages
3
Figure 7: Series Resonant Circuit
TVSS Failure Due to Arcing
Ground Fault
MOTOR STARTER FAILURE DUE TO ARCING
GROUND FAULT
Fig. 8: Transient Overvoltage
from Restriking Ground Fault
MOTOR STARTER
FAILURE DUE TO
ARCING GROUND
FAULT
SWGR TAP BOX FAILURE DUE TO ARCING
GROUND FAULT
4
ESP MOTOR FAILURE DUE TO ARCING
GROUND FAULT
ESP MOTOR WYE POINT FAILURE
DUE TO ARCING GROUND FAULT
UNGROUNDED GENERATOR
Arcing Ground Fault – 2 PH to Ground
Ground Fault on L.C. 81
Ground Fault on L.C. 81
Ground Fault on L.C. 81
5
Figure 9
Figure 10: Resistance Grounded
• Inductance
Grounded
• L.R.-200A to 1000A
• H.R.-Less than 10A
Figure 11: Grounding
Transformers
Fig. 12: The Effect of Grounding
Impedance on Transient Overvoltages
Table II
X0 / X1 and R0 / X0 for
Low Transient Overvoltages
Table II
X0 / X1 and R0 / X0 for
Low Transient Overvoltages
• Ungrounded
• Solid Grounded
• Reactance Grounded
• No Ratios Available
• Produces High
Vtransients
• X0/X1 Very Low
Unless Wye-Wye
• Low Resistance
Grounded
• R0/X0 > 2.0
• X0/X1 < 20
• High Resistance
• I0R > I0C
• X0/X1 < 3.0
6
Table III:System Characteristics
With Various Grounding Methods
Other Factors
Ungrounded
• Mechanical Stress in Generators
• Selective Relaying
• Surge Protection
Practicable System Grounding
Selections
• L. Voltage (< 1000V)
– Solid
– H. Resistance
Essentially solid grounding
Solid
Low-value reactor
Reactance
grounding
High-value reactor
Ground-fault
neutralizer
Resistance Grounding
Low
resistance
5 to 20%
High
resistance
Less than
1%
Not
excessive
No
Current for
phase-toground fault
in percent of
three-phase
fault current
Transient
over-voltages
Automatic
segregation
of faulted
zone
Lightning
arresters
Less than 1%
Varies, may be
100% or greater
Usually designed
to produce 60 to
100%
5 to 25%
Nearly zero fault
current
Very high
Not excessive
Not excessive
Very high
Not excessive
Not excessive
No
Yes
Yes
Yes
No
Yes
Ungrounded
neutral type
Grounded-neutral
type
Remarks
Not
recommended
due to over
voltages and
nonsegregation of
fault
Grounded-neutral
type if current is
60% or greater
Generally used on system (1) 600 volts
and below and (2) over 15kV
Ungrounded
neutral type
Ungrounded
neutral type
Ungrounded
neutral type
Not used due to
excessive overvoltages
Best suited for
high-voltage overhead lines where
faults may be selfhealing
Generally used on
industrial systems
of 2.4 to 15kV
Unground
ed neutral
type
Generally
used on
systems
5kV and
below
Practicable System Grounding
Selections
• M. Voltage
• Medium Voltage
• Medium Voltage
– Solid
– L. Resistance
– H. Resistance
• 3 PH / 4 W
• Aerial Lines
• Unshielded Cables
• Motors / Generators
• Shielded Cables
• No VLN Loads
• < 5 KV-No Tripping
• > 5 KV - Tripping
• No VLN Loads
• H. Voltage (>15 KV)
– Solid
Ground Fault Protection Using
Fuses
Residual Ground Fault Detection
3 Wire
52
I
A
A
B
X
H
I
1
B
A
1
I
B
C
C
C
N
P
I
N
A
B
P
P
G
G
C
7
Residual Ground Fault Detection
4 Wire
Source Neutral Ground Detection
I
I
I
I
A
A
B
A
I
B
I
A
B
C
C
B
N
C
C
P
N
I
P
P
N
G
P
I
I
P
P
G
N
G
I
Zero Sequence
I
G
H. Resistance / Pulsing Contactor
A
A
B
I
I
B
C
C
N
G
P
I
I
P
P
N
G
CURRENT IN AMPERES
1000
Zone Interlocking
1000 KVA
100
GFR
M
8
9
10
11
TIME DELAY INPUT
DS1200A 510LSG
1
GRND-A
GFR
F1
8
9
10
11
GFR
F2
8
9
10
11
GFR
B3
8
9
10
11
COMMON
1
1
1000 KVA
1
CLE-200E
0.10
1
TX Inrush
GRND-B
INPUT
ZONE 1
COMMON
10
TIME DELAY
1
TIME IN SECONDS
• NEC Art. 230-95
• L.V. Ground Fault
Protection
Coordination
ZONE 2
GFR
B1
8
9
10
11
2
GFR
B2
8
9
10
11
3
3
DS600A RMSLSG
0.01
10
APPADS.tcc
100
Ref. Voltage: 480
1K
Current Scale X 10^1
10K
ZONE 3
8
Download