Transformer Isolated Amplifier EG2-RLK Output: Relays and Transistors - Control circuit EEx ia IIC Sensor mech. Contact with LB / SC - DC 24 V supply voltage - Monitoring output for lead breakage and short circuits. - Reversible operating mode Hazardous Area Input I / Input II EEx ia IIC - 2-Channel 1 kΩ Chan. 1 Chan. 2 d2+ z2+ d4z4- d2+ z2+ 10 kΩ d4z4- - Lead breakage (LB) and short circuit (SC) monitoring may be disabled - 1 Signal output with 2 changeover contacts per channel * LB Chan. 1 Chan. 2 - 1 Active transistor output per channel d2+ z2+ Fault signal outputs b16; b18 For short circuit or lead breakage (Indicator: LED red). The fault signal outputs are combined by a circuit lead, so that only one connection is required for the fault evaluation of all channels on the card. If the evaluation of each individual channel is necessary, then the circuit lead must be breached at position 6 as shown (See side view of card). d8 z8 2.1, 2.2 + 2 Channel 3.1 1.1, 1.2 SC & =1 Notes on connection assignment Lead breakage monitoring d6, d8; z6, z8 Lead breakage monitoring can be disabled by bridging the above connections. If necessary, the unit can also be supplied with a factory installed plug-in jumper for the lead breakage monitoring setting. Mode of operation d16; z16 Logic-1: no reversal of operating mode from input to output Logic-0: reversal of operating mode from input to output (see table of operating modes on page 25) If necessary, the operating mode can also be selected by a factory installed plug-in jumper on the card. d6 z6 LB SC + The transformer isolated amplifier transmits digital signals from the hazardous area. Sensors per DIN 19234 (NAMUR) or mechanical cotacts can serve as alarms. The control circuit can be monitored through lead breakage and short circuit monitoring. d4z4- Safe Area - 1 Relay override input per channel & + - red ≥1 U yellow U 6 Chan. 1 d16 Chan. 2 z16 d20 z20 Operating Mode Output I / IV d24 d22 d26 d30 d28 d32 z24 z22 z26 z30 z28 z32 Output II / V b16 d14 b18 (L+) z14 (L-) Output Power supply III / VI Fault Signal * Bridge for disabling lead breakage monitoring Front View Type A (dimensions see page 16) LED yellow: Output Channel 2 LED yellow: Output Channel 1 LED red: Fault Signal Channel 1 Issue Date 20.02.02 LED red: Fault Signal Channel 2 Subject to reasonable modifications due to technical advances. 38 Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-22 22 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com Transformer Isolated Amplifier EG2-RLK Output: Relays and Transistors Technical data Power supply Nominal voltage Ripple Nominal current DC 20.4 V ... 27.6 V ≤ 10 % about 70 mA Inputs (intrinsically safe) Input I : Input II : Nominal values Open circuit voltage / short circuit current Switch point / switch hysteresis Input pulse length / pulse interval Lead monitoring Connections d2+, d4Connections z2+, z4per DIN 19 234 with respect to NAMUR about DC 8 V / about 8 mA 1.2 mA ... 2.1 mA / about 0.2 mA ≥ 0.5 ms / ≥ 0.5 ms Breakage J ≤ 0.1 mA Short circuit J ≥ 6 mA Connections d14 (L+), z14 (L-) Certificate of Conformity Peak Values Max. voltage U 0 Max. current I0 Max. power P 0 Allowable circuit values Ignition protection method, category Explosion group Max. external capacitance Max. external inductance PTB Nr. Ex-81/2065X other certifications see www.pepperl-fuchs.com 12.7 V 21 mA 66 mW [EEx ia] IIB 1.1 µF 5 mH Input (not intrinsically safe) Signal level Logic-1 Signal level Logic-0 Input current Input delay DC 15 V ... 30 V DC 0 V ... 5 V or B-contact input 1 mA 5 ms ... 20 ms (typically10 ms) Outputs (not intrinsically safe) Output II, I : Output IV, V : Contact load Mechanical life Energized- / De-energized delay Outpu III, VI: Nominal current Signal level Logic-1 / Logic-0 Connections d24, d22, d26; d30, d28, d32 Connections z24, z22, z26; z30, z28, z32 AC: 50 V / 2 A / cos ϕ = 1 / 1 A / cos ϕ = 0,3; DC: 40 V / 100 W Ohm load 2 x 10 5 switchings about 12 ms / about 10 ms Transistor output, active Connections d20, z20 10 mA, short circuit protected (L+) -3 V / 0.9 V or cut off output (leakage current J ≤10 µA) Transfer characteristics Output I, II, IV, V: switch frequency ≤ 25 Hz (use at high frequencies EG2-TLK) Galvanic isolation Output I ... VI from each other Output I ... VI from power supply Output I ... VI and power supply from input Safe isolation per DIN VDE 0106, design isolation voltage 50 V eff Safe isolation per DIN VDE 0106, design isolation voltage 50 V eff Safe galvanic isolation per EN 50 020, voltage peak value 375 V Conformity to standards Input Climatic conditions per DIN 19234 (NAMUR) per DIN IEC 721 Ambient temperature Connection possibilities Coding Weight -25 °C ... +70 °C (248 K ... 343 K) 32-pin plug connector per DIN 41 612, Series 2, Type F; z and d provided a3 / c3 about 200 g / IIC / 0.37 µF / 2 mH [EEx ib] IIB 3.9 µF 260 mH / IIC / 0.8 µF / 70 mH Issue Date 20.02.02 Connections d16, z16 Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-22 22 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com 39 Transformer Isolated Amplifier EG2-RLK Output: Relays and Transistors 1.1 1.2 D1.1 EExInput module V1.1 Plug Connector per DIN 41 612 3.1 EExInput module V1.2 2.1 2.2 Side View Output Relays 6 D1.2 Programming facilities on the card Jumpers Plug in design optional 1.1 (open) Reverse operating mode of channel 1 1.2 (open) Reverse operating mode of channel 2 2.1 (open) Lead breakage monitoring channel 1: active 2.2 (open) Lead breakage monitoring channel 2: active If link 3.1 is closed, short circuit and lead breakage monitoring for all channels are cut off. Delivery status Jumpers 1.1 to 3.1 Issue Date 01.08.96 open Subject to reasonable modifications due to technical advances. 40 Copyright Pepperl+Fuchs, Printed in Germany Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-22 22 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com