NXS Three Contactor Bypass Assemblies INSTALLATION INSTRUCTIONS APPLICATION WIRING The NXS Three Contactor Bypass Assemblies channel electrical power either through or around the variable frequency drive (VFD). CAUTION Equipment Damage Hazard. Can short equipment circuitry. Disconnect power supply before installation. INSTALLATION When Installing This Product… 1. 2. 3. 4. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. Installer must be a trained, experienced service technician. After installation is complete, check out product operation as provided in these instructions. WARNING Can Cause Serious Injury or Death. Installation requires work with high voltage. Disconnect power supply before installation. CAUTION Equipment Damage Hazard. Can short equipment circuitry. Disconnect power supply before installation. Location and Mounting Locate the device in a clean, dry, well-ventilated area with an ambient temperature below 125°F (52°C). ® U.S. Registered Trademark Copyright © 2003 Honeywell International Inc. All Rights Reserved IMPORTANT All wiring must agree with applicable codes, ordinances and regulations. 1. 2. Ensure that bypass box voltage corresponds with that of the power supply. To access the wiring compartment: a. Ensure handle is in the OFF position. b. Rotate latch 3/4-turn counterclockwise. c. Open the cover. IMPORTANT Use only copper wire with 167°F (75°C) minimum. 3. 4. Refer to Fig. 1 for typical wiring. If you intend to use the bypass box to manually operate the motor, set the motor overload dial to the motor full load amp (FLA) rating. OPERATION Bypass boxes have four operating positions: • VFD: Device directs power to VFD first, then to the motor. VFD controls the motor as it would without the bypass box. • OFF: Device stops power. Power reaches neither the motor nor the VFD. • TEST: Device directs power to VFD only. This allows for VFD calibration, adjustments, and diagnostics. • BYPASS: Device directs power to motor only. No power reaches the VFD. The motor operates at full speed with full power. 62-0184 NXS THREE CONTACTOR BYPASS ASSEMBLIES Operation Using the VFD VFD Bypass To set bypass box to use VFD to control the motor as it would without the bypass box: 1. Stop the motor. 2. Wait five seconds. 3. Rotate handle to DRIVE. 4. Start the VFD (see VFD instructions for details). To set bypass box to direct power only to motor: 1. Rotate handle from VFD to OFF. 2. Wait five seconds. IMPORTANT Switching the bypass box control handle to BYPASS can immediately turn the motor on. 3. 62-0184 2 Rotate handle to BYPASS. 3 OL 2 2 1 1 10 SEE NOTE 5 11 AMP MAIN DISC. AMP. JUMPER GND L3 L2 L1 12 2 000X 2 0X00 X000 VFD 3 2 7 4 BYPASS X1 T114 VA AMP OFF TEST 13 CUSTOMER SUPPLIED EXTERNAL START 1A VAC 3 PH 60 HZ CUSTOMER SUPPLIED AMP M3AUX M2AUX X1 H1 X2 M2 7 8 TCR X2 X2 X2 X2 X2 TCR M3 M1 ACR VAC SECONDARY 6 M3 BYPASS RUN BYPASS CONTACTOR TEST CONTROL RELAY VFD RUN INPUT CONTACTOR OUTPUT CONTACTOR AUTO START RELAY TRANSFORMER FUSING VA PRI SEC 100 1/2A 1-1/4A 150 1/2A 2A 9 8 4 5 TCR X4 H4 AMP W2 W1 GND RELAY OUTPUT2 NXOPTA2 RELAY OUTPUT1 R01/1 R01/2 R01/3 R02/1 R02/2 R02/3 21 22 23 24 25 26 NXOPTA1 REFERECE VOLTAGE +10Vref 1 AI, 0– +10V; 0–20ma AI+ 2 AI common GND/AI1– 3 AI, 0–20ma; 0– +10V AI2+ 4 AI COMMON GND/A12– 5 24V AUXILIARY VOLTAGE 24Vout 6 I/O GROUND GND 7 DIGITAL INPUT 1 * DIN1 8 DIGITAL INPUT 2 * DIN2 9 DIGITAL INPUT 3 * DIN3 10 DI COM A FOR DIN1–DIN3 CMA 11 24V AUXILIARY VOLTAGE 24Vout 12 I/O GROUND GND 13 DIGITAL INPUT 4 DIB4 14 DIGITAL INPUT 5 DIB5 15 DIGITAL INPUT 6 DIB6 16 DI COM B FOR DIB4–DIB6 CMB 17 ANALOG SIGNAL +OUT A01+ 18 ANALOG OUTPUT COM A01– 19 OPEN COLLECTOR OUTPUT D01 20 V2 V1 GND U2 U1 HONEYWELL NXS 19 20 18 16 10 11 12 13 14 15 0L TO T114 T3 T2 T1 T1 T2 T3 SP X2 X2 1 2 3 4 5 6 7 8 9 10 11 12 13 TO MOTOR REFERECE VOLTAGE ANALOG 0– +10V; 0–20ma ANALOG common ANALOG 0–20ma; 0– +10V ANALOG COMMON 24V OUT I/O GROUND RELAY OUTPUT N.O. RELAY OUTPUT N.O. EXTERNAL FAULT EXTERNAL FAULT EXTERNAL START EXTERNAL START CUSTOMER TERMINALS M CUSTOMER MOTOR M20992 1. DEFAULT: BASE APPLICATION: DIN1 – START FORWARD, DIN2 – START REVERSE, DIN3 – RUN ENABLE 2. DASH LINES INDICATE CUSTOMER INSTALLED DEVICES AND WIRING. 3. COPPER WIRE RATED FOR 60 C INSULATION IF RATED LESS THAN 100A OR 75 C IF RATED 10A OR MORE MUST BE USED. 4. REFER TO INSTALLATION MANUAL FOR TIGHTENING TORQUE VALVES. 5. REPLACE JUMPER WITH EXTERNAL FAULT. * NOTES M2AUX ACR M1 M2 NXS THREE CONTACTOR BYPASS ASSEMBLIES Fig. 1. NXS wiring. 62-0184 NXS THREE CONTACTOR BYPASS ASSEMBLIES Table 1. NXS NEMA1 Assembly Dimension Details. Model Number UNISTRUT D A B B C M20991 Fig. 2. Dimensions of the NXS NEMA1 Assemblies. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 62-0184 B.B. 3-03 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9 Weight HP (lbs) NXS0015J 1.5 53 NXS0020J 2 NXS0030J 3 NXS0040J 4 NXS0050J 5 A B C D Motor Terminal Torque Rating Volts (inches) (lb-in.) AC 33-1/2 16 7 5 18 - 20 NXS0075J 7.5 68 NXS0100J 10 70 NXS0150J 15 70 37-1/2 16 9 NXS0200J 20 98 41-1/2 20 NXS0250J 25 98 41-1/2 20 9 5 32 -35 NXS0300J 30 98 46-1/2 NXS0400J 40 150 46-1/2 24 NXS0500J 50 150 46-1/2 24 9 6 45 - 50 NXS0600J 60 150 49-1/2 NXS0010S 1 33-1/2 16 7 5 18 - 20 NXS0015S 1.5 NXS0020S 2 NXS0030S 3 NXS0040S 4 NXS0050S 5 NXS0075S 7.5 70 53 480 230 68 70 33-1/2 37-1/2 16 9 NXS0100S 10 98 41-1/2 20 NXS0150S 15 98 41-1/2 20 9 5 32 -35 NXS0200S 20 150 46-1/2 24 NXS0250S 25 150 46-1/2 24 9 6 45 - 50 NXS0300S 30 150 49-1/2 NXS0010K 1 33-1/2 16 7 5 18 - 20 NXS0015K 1.5 NXS0020K 2 NXS0030K 3 NXS0040K 4 NXS0050K 5 NXS0075K 7.5 98 41-1/2 20 9 NXS0100K 10 98 41-1/2 20 9 5 32 -35 NXS0150K 15 150 46-1/2 24 NXS0200K 20 150 46-1/2 24 9 6 45 - 50 NXS0250K 25 150 49-1/2 NXS0300K 30 53 200 / 208 68 70 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you. Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. www.honeywell.com