Phoenix Contact COMBICON Device Connection Technology and

advertisement
COMBICON power
HC series connectors up to 2.5 mm2
16 A connector for 600 V UL
applications
Note:
In compliance with DIN EN 61984, COMBICON connectors come
without switching capacity. During designated use, they must not be
plugged in or disconnected when carrying voltage or under load.
The designation "HC" is printed in red to provide clear identification
of high current connectors.
Derating curve informations:
Derating curves, determined as per
DIN EN 61984 (VDE 0627):2002-09
Derating curve, presentation based on DIN EN 60512-5-2:2003-01
Connected conductor cross section = 2.5 mm2
Reduction factor = 0.8
No. of positions: see diagram
GMSTB 2,5 HCV/ ...-ST-7,62
Plug component with female contact and 600 V UL approval
1)
Please observe the derating curves and laboratory data sheets.
Derating curves of further combination options on request.
u
Accessories
– High-capacity within minimum space:
current carrying capacity of 16 A in
combination with an unrestricted
600 V UL approval
– Compact 7.62 mm pitch
– GMSTB 2,5 HCV plugs should be used
only with GMSTBA 2,5 HC base strips
– The double steel spring ensures
additional safety, especially in the case of
temperature and capacity fluctuations
Dimensional drawing
Type
Keying profile
CP-MSTB
Order No.
1734634
Page
38
Marker card
SK 7,62/3,8
489
a+7,4
21
17,5
For all types
3,7
Screwdriver
SZS 0,6 x 3,5
Order No.
1205053
7,62
a
Representative derating curve
Current carrying capacity [A]
Type: GMSTB 2,5 HCV/...-ST-7,62 with GMSTBA 2,5 HC/...-G-7,62
36
32
28
24
20
16
12
8
4
0
2
1 = 2-pos.
2 = 5-pos.
3 = 12-pos.
0
20
1
3
40
60
80
100
Ambient temperature [°C]
Technical data
Ordering data
Technical data in accordance with IEC / DIN VDE
Rated current / conductor cross-section
Rated insulation voltage with pollution degree 2
No. of pos.
Pitch
[mm]
Connection capacity
Solid / stranded
[mm²] / [mm²] / AWG
Stranded with ferrules without plastic sleeve
[mm2]
Stranded with ferrules with plastic sleeve
[mm2]
Multi-conductor connection capacity (2 cond. with the same cross section)
Solid / stranded
[mm2]
Stranded with ferrules without plastic sleeve
[mm2]
Stranded with TWIN ferrules with plastic sleeve
[mm2]
Insulation coordination
Surge voltage category / pollution degree
Rated insulation voltage
[V]
Rated surge voltage
[kV]
Approval data (UL/CUL)
Use Group
Nominal voltage
[V]
Nominal current
[A]
Connection capacity AWG
AWG
Approval data (CSA)
Use Group
Nominal voltage
[V]
Nominal current
[A]
Connection capacity AWG
AWG
General data
Stripping length
[mm]
Screw thread
Tightening torque
[Nm]
Type of insulation material / group of insulation material
Inflammability class acc. to UL 94
360
PHOENIX CONTACT
161) / 2.5
1000
[A] / [mm²]
[V]
7.62
0.2 - 2.5 / 0.2 - 2.5 / 24 - 12
0.25 - 2.5
0.25 - 2.5
0.2 - 1 / 0.2 - 1.5
0.25 - 1
0.5 - 1
III / 3
1000
8
B
600
16
30 - 12
B
-
III / 2
1000
8
C
600
16
30 - 12
C
-
2
3
4
5
6
7
8
9
10
11
12
Dim. a
[mm]
7.62
15.24
22.86
30.48
38.10
45.72
53.34
60.96
68.58
76.20
83.82
Type
7.62 mm pitch, color: green
Order No.
Pcs. / Pkt.
GMSTB 2,5 HCV/ 2-ST-7,62
GMSTB 2,5 HCV/ 3-ST-7,62
GMSTB 2,5 HCV/ 4-ST-7,62
GMSTB 2,5 HCV/ 5-ST-7,62
GMSTB 2,5 HCV/ 6-ST-7,62
GMSTB 2,5 HCV/ 7-ST-7,62
GMSTB 2,5 HCV/ 8-ST-7,62
GMSTB 2,5 HCV/ 9-ST-7,62
GMSTB 2,5 HCV/10-ST-7,62
GMSTB 2,5 HCV/11-ST-7,62
GMSTB 2,5 HCV/12-ST-7,62
1714278
1714281
1714294
1714304
1714317
1714320
1714333
1714346
1714359
1714362
1714375
50
50
50
50
50
50
50
50
50
50
50
II / 2
1000
8
D
D
-
8
M3
0.5 - 0.6
PA / I
V0
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Download