covers MYSA-WCMSA-0305.qxd 3/24/2005 8:24 AM Page 1 West Coast Metering Circuit Breaker Enclosures and Small Load Centers Selection and Application Guide 2 – 8 CIRCUIT, 60 – 125 AMPERES (NO DOOR) Amps Max. 60 125 125 125 125 125 No. of Spaces 2 2 4 4 4 4 Max. Circuit 4 4 8 8 8 8 Indoor Enclosure NEMA Type 1 햲 Catalog Number LC002GS LC002HS 햵 LC004NF 햵햶 LC004NS 햵햶 – – Dimensions (inches) 햳 Height Width Depth 9-7/8 5-1/8 2-5/8 17-1/8 7-1/8 4-1/4 12-5/8 6-5/8 3-1/2 12-5/8 6-5/8 3-1/2 – – – – – – Outdoor Enclosure NEMA Type 3R 햴 Catalog Number LW002GR 햷 LW002HR – LW004NR 햵햶햸 LW004NRSPA50 햵햶햷햸햹 LW004NRSPA60 햵햶햷햸햹 Dimensions (inches) 햳 Height Width Depth 8-1/4 5-3/8 4-1/2 8-1/4 5-3/8 4-1/2 – – – 12-1/4 6-1/8 4-1/4 12-1/4 6-1/8 4-1/4 12-1/4 6-1/8 4-1/4 LC008DF 햵 LC008DS 햵 LC008DFG 햵햹 LC008DSG 햵햹 LC110DFCGP 햵햹햺 14-3/4 14-3/4 14-3/4 14-3/4 14-3/4 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 – LW008NR 햵 – – – – 14-3/4 – – – – 12-1/8 – – – – 4-1/8 – – – LC100CS LC200VS 17-1/8 7-1/8 19-3/4 8-1/2 4-1/4 4 LW100CR LW200VR 17-3/8 19-3/4 7-3/8 8-3/8 4-3/8 4-5/8 – – 19-3/4 8-1/2 – 4 LW002GR LW004VR 8-1/4 19-3/4 5-3/8 8-3/8 4-1/2 4-5/8 8 – 16 CIRCUIT, 125 AMPERES (WITH DOOR) 125 125 125 125 125 8 8 8 8 10 16 16 16 16 20 12-3/8 12-3/8 12-3/8 12-3/8 12-3/8 ENCLOSED BREAKERS 100 100 2 2 4 4 MAIN LUG CIRCUIT BREAKER ENCLOSURES 60 200 – 2 – 4 – LC004VS 햲 Cover type is specified by character in 7th (usually last) position, as follows: S = Surface F = Flush C = Combination Surface/Flush 햳 Dimensions shown are representative of outside box length, width and depth (⫾ 1/8”) and do not include allowance for mounting bumps, endwalls, hubs, or hardware protrusions. Allow approximately 1-1/4” additional in length and width dimensions for surface or combination overhang. 햴 Hub provision only. Closure plate included. Panels through 225 amp require HS type hub; panels over 225 amp require HV type hub. 햵 Use neutral lug kit ECLK1 or ECLK2 as required. 햶 Maximum breaker 100 amp. 햷 LW004NRSPA50 is provided with a factory installed 2-pole 50 amp GFCI breaker. LW004NRSPA60 is provided with a factory installed 2-pole 60 amp GFCI breaker. 햸 Use of 60 amp GFCI requires use of 75oC copper wire. 햹 Panel includes factory-installed ground bar. 햺 Includes (2) MP115 and (1) MP230 breakers. Murray Electrical Products Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 seainfo@sea.siemens.com www.murrayconnect.com 2005 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Murray is a trademark of Siemens Energy & Automation, Inc. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. SEA Order No. MYSA-WCMSA-0305 New 5M0305BC Printed in USA covers MYSA-WCMSA-0305.qxd 3/24/2005 8:24 AM Page 2 Rock SolidTM Load Centers Combination Meter Sockets Overhead and Underground Feed Features and Benefits Mounting keyholes for easy installation Tin-plated copper bus bars and wire forms Most wire bending space (width) in industry Sturdy, thermoplastic lug mounting bases INSTA-WIRETM neutrals Adjustable flush rails for 2” x 6” installation (flush mount devices only) install bonding strap, and use both bars for neutral and ground conductors. For non-service entrance applications, do not install bonding strap and use insulated bar for neutral conductors and bonded bar for ground conductors. MAIN LUG LOAD CENTERS – Aluminum Bus 24-40 Circuit, 125-200 Amperes, 1 Phase 3 Wire, 120/240V AC or 208Y/120V AC, Insulated and Bonded Split Neutrals 햲 Amps Max. 125 125 125 125 150 150 200 200 200 200 200 No. of Spaces 12 16 20 30 16 24 12 20 30 40 40 Max. Circuit 24 32 40 40 32 40 24 40 40 40 40 Indoor Enclosure NEMA Type 1 햳 Catalog Number LC1224L1125 LC1632L1125 LC2040L1125 LC3040L1125 LC1632L1150 LC2440L1150 – LC2040L1200 LC2440L1200 LC3040L1200 LC4040L1200 Dimensions (inches) 햴 Height Width Depth 21 14-3/8 4 21 14-3/8 4 24 14-3/8 4 30 14-3/8 4 24 14-3/8 4 30 14-3/8 4 – – – 30 14-3/8 4 30 14-3/8 4 36 14-3/8 4 39 14-3/8 4 Outdoor Enclosure NEMA Type 3R 햳햵 Catalog Number LW1224L1125 LW1632L1125 LW2040L1125 – – – LW1224L1200 LW2040L1200 – LW3040L1200 – Dimensions (inches) 햴 Height Width Depth 20 14-1/4 4-1/2 29 14-1/4 4-1/2 29 14-1/4 4-1/2 – – – – – – – – – 29 14-1/4 4-1/2 29 14-1/4 4-1/2 – – – 38 14-1/4 4-1/2 – – – MAIN LUG LOAD CENTERS – Copper Bus 40-42 Circuit, 125-400 Amperes, 1 Phase 3 Wire, 120/240V AC or 208Y/120V AC, Insulated and Bonded Split Neutrals 햲 Rigid metal basepan Removable anti-rotation lugs move to top positions for overhead feed applications Easily removable side hinge door 7” deep can for more wire room JA1224B1100SEC Catalog Number Logic Example: JA1224B1100FEC JA Load centers on this page through 225 amp feature a new split neutral with one bonded and one insulated bar. For service entrance applications, 12 24 JA = Meter Spaces Combination JC = Meter Main Circuits B B = Main Breaker L = Main Lug 1 1 = Single Phase 100 Amperage FEC F = Semi-Flush S = Surface E = EUSERC C = OH/UG Feed (side-by-side) D = UG Feed Only (over under) M = Field Added 2nd Main W = Wide Load Center (not between the studs) SS = Test Block Bypass Socket Amps Max. No. of Spaces Max. Circuit Indoor Enclosure NEMA Type 1 햳 Catalog Number Dimensions (inches) 햴 Height Width Depth Outdoor Enclosure NEMA Type 3R 햳햵 Catalog Number Dimensions (inches) 햴 Height Width Depth 125 200 200 200 225 400 20 20 30 40 42 42 40 40 40 40 42 42 LC2040L1125CU LC2040L1200CU LC3040L1200CU LC4040L1200CU LC4242L1225CU LC042SS 햷 24 30 36 39 42 47 – – – – – LW042SR – – – – – 47 햲 300 and 400 amp load centers have insulated groundable center-mounted neutrals. 햳 Standard package quantity equal to one. 햴 Dimensions shown are representative of outside box length, width and depth (⫾ 1/8”) and do not include allowance for mounting 14-3/8 14-3/8 14-3/8 14-3/8 14-3/8 20 4 4 4 4 4 6 bumps, endwalls, hubs, or hardware protrusions. Allow approximately 1-1/4” additional in length and width dimensions for surface or combination overhang. 햵 Hub provision only. Closure plate included. Panels through 225 amp require HS type hub; panels over 225 amp require HV type hub. – – – – – 20-1/2 – – – – – 6-1/2 햶 Copper bus load centers are recommended for those applications where the enviroment may be severe (i.e., farm and coastal areas). 햷 For flush installation, order accessory Cat. No. LX077SF separately. 63331Murray.qxd 3/24/2005 12:45 PM Page 1 EUSERC Approved Meter Main and Meter Load Centers (100-200A) Overhead and Underground Feed FEATURES 쐽 UL listed 쐽 Outdoor type 3R enclosure 쐽 Meets or exceeds EUSERC requirements 쐽 22,000 AIC rated 쐽 Surface and semi–flush units available. Semi–flush rails are depth adjustable 쐽 Side-hinged door with one screw removal 쐽 Load wiring may exit top or bottom on flush devices 쐽 Suitable for use only as service entrance equipment 쐽 RX type hub provision on top endwall (surface devices), HC type hub provision on bottom endwall 쐽 5th jaw accessory available (ECMC5J) 쐽 Ring type meter covers 쐽 Contact local utility to confirm meter socket placement prior to installation 쐽 See end of section for dimensions and wiring diagrams JC0406L1200SEC JA2442B1200SEC BETWEEN STUDS CONSTRUCTION Amps Max. 100 100 100 100 125 125 125 125 125 200 200 200 200 Main Breaker Catalog No. MP2100KH MP2100KH MP2100KH MP2100KH MP2125KH MP2125KH MP2125KH Types MP-T and MP-HT MEQ9985 MEQ9985 Types MD-T, MD-HT, MP-T and MP-HT Mounting Flush Surface Flush Surface Flush Surface Flush Flush Surface Flush Surface Flush Surface No. of Spaces 12 12 16 16 12 12 16 4 4 24 24 4 4 Max. Circuits 24 24 32 32 24 24 32 6 6 42 48 6 6 New Style Catalog Number JA1224B1100FEC JA1224B1100SEC JA1632B1100FEC JA1632B1100SEC JA1224B1125FEC JA1224B1125SEC JA1632B1125FEC JC0406L1125FEC JC0406L1125SEC JA2442B1200FEC JA2442B1200SEC JC0406L1200FEC JC0406L1200SEC Old Style Catalog Number JA112CW JA112CY – – JA412CW JA412CY JA416CW JA004CW JA004CY JA220VH JA220RK JA904CY JA904CW Dimensions (inches) Height Width Depth 26-9/16 14-1/2 7-1/2 26-9/16 14-1/2 7-1/2 30-9/16 14-1/2 7-1/2 30-9/16 14-1/2 7-1/2 26-9/16 14-1/2 7-1/2 26-9/16 14-1/2 7-1/2 30-9/16 14-1/2 7-1/2 26-9/16 14-1/2 7-1/2 26-9/16 14-1/2 7-1/2 40-9/16 14-1/2 7-1/2 40-9/16 14-1/2 7-1/2 30-9/16 14-1/2 7-1/2 30-9/16 14-1/2 7-1/2 K.O. Fig. 2 1 2 1 2 1 2 2 1 2 1 2 1 Max. Circuits 40 40 New Style Catalog Number JA3040B1200SECW JA4040B1200SECW Old Style Catalog Number JA232CY JA240CY Dimensions (inches) Height Width Depth 32-1/4 21 5-1/8 32-1/4 21 5-1/8 K.O. Fig. 3 3 WIDE LOAD CENTER CONSTRUCTION Amps Max. 200 200 Main Breaker Catalog No. MPD2200KH MPD2200KH No. of Mounting Spaces Surface 30 Surface 30 Main breaker not included. 21” width will not fit between typical 16” center stud construction. For flush mounting, use flush rail kit ECFRK1. Dimensions shown are representative of outside box dimensions and do not include allowances for protrusions. Dimensions are subject to change. Meter combo has a full width load center section with a plastic basepan. 1 63331Murray.qxd 3/24/2005 11:22 AM Page 2 Combination Meter Sockets Underground Feed Only Features and Benefits Mounting keyholes for easy installation Full width load center section for easy wiring Tin-plated copper bus bars and wire forms INSTA-WIRETM neutrals Adjustable flush rails for 2” x 6” installation (flush mount devices only) Metal basepan Sturdy, lug mounting bases Removable anti-rotation lugs JA3042B1200FED 2 63331Murray.qxd 3/24/2005 1:12 PM Page 3 EUSERC Approved Meter Main and Meter Load Centers (200-225A) Underground Feed Only FEATURES 쐽 UL listed 쐽 Meets or exceeds EUSERC requirements 쐽 22,000 AIC rated 쐽 Surface and semi–flush units available. Semi–flush rails are depth adjustable 쐽 Side-hinged door with one screw removal 쐽 Load wiring may exit top or bottom on flush mount devices 쐽 Suitable for use only as service entrance equipment 쐽 RX type hub provision on top endwall (surface devices), and HC type hub provision on bottom endwall 쐽 5th jaw accessory available (ECMC5J) 쐽 Ring type meter covers 쐽 Contact local utility to confirm meter socket placement prior to installation 쐽 See end of section for dimensions and wiring diagrams JA1212L1200SED BETWEEN THE STUDS CONSTRUCTION Main Amps 200 200 200 200 200 200 225 225 Main Breaker N/A N/A MBK200M MBK200M MBK200M MBK200M MBK225M MBK22SM No. of Spaces 12 12 20 20 30 30 30 30 No. of Circuits 12 12 40 40 42 42 42 42 Mounting Flush Surface Surface Flush Surface Flush Surface Flush JA3042B1200FED New Catalog Number JA1212L1200FED JA1212L1200SED JA2040B1200SED JA2040B1200FED JA3042B1200SED JA3042B1200FED JA3042B1225SED JA3042B1225FED Old Style Catalog Number N/A N/A N/A JA220CW N/A N/A N/A N/A Dimensions (inches) Height Width Depth 38-3/8 14-1/2 7-1/2 38-3/8 14-1/2 7-1/2 41-7/8 14-1/2 7-1/2 41-7/8 14-1/2 7-1/2 48-3/8 14-1/2 7-1/2 48-3/8 14-1/2 7-1/2 48-3/8 14-1/2 7-1/2 48-3/8 14-1/2 7-1/2 K.O. Fig. 4 3 4 3 4 3 4 3 Suitable for use as service entrance equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance branch circuit panel. Main breaker not included. Dimensions shown are representative of outside box dimensions and do not include allowances for protrusions. Dimensions are subject to change. 3 63331Murray.qxd 3/24/2005 11:22 AM Page 4 EUSERC Commercial Metering Single Sockets SINGLE COMMERCIAL SAFETY SOCKETS DESIGN / PERFORMANCE FEATURES 쐽 Outdoor/Indoor – one design for either installation. 쐽 Ring Type – meets requirements for various ring type locking provisions. 쐽 Line and load top or bottom to meet overhead or underground requirements. SYSTEMS / SPECIFICATIONS 쐽 100/200 amp maximum meter 쐽 120/240V AC, 1 phase 3 wire, 4 jaw 쐽 208Y/120V AC, 3 wire network, 5 jaw or 3 phase, 4 wire, 7 jaw 쐽 240V AC, 1 phase 3 wire, 3 phase 3 wire, or 3 phase 4 wire, 4, 5 or 7 jaw 쐽 600V AC, 1 phase 3 wire, 3 phase 3 wire, or 3 phase 4 wire, 4, 5 or 7 jaw 쐽 10,000 to 100,000 AIC 쐽 EUSERC SEC #300 UAT427-XMWR In addition to local code and National Electrical Code requirements, the serving utility may have special requirements for metering devices. Confirm meter socket acceptance prior to order placement. MS14TB RING TYPE RESIDENTIAL SOCKETS (NO DISCONNECT) 600V AC MAX. 1 PHASE 3 WIRE Amps Cont. Duty 135 135 135 200 200 200 Service OH/UG OH UG OH OH/UG UG Catalog Number SUAT121-0GWR SUAT121-BGWR SUAT121-PGWR SUAT327-0GWR SUAT427-XMWR SUAT427-PMCO Lugs #14-2/0 #14-2/0 #14-2/0 #6-350 kcmil #6-350 kcmil #6-350 kcmil No. of Jaws 4 4 4 4 4 5 5th Jaw EC659-0121 EC659-0121 EC659-0121 EC659-0121 EC659-0121 Installed Hub RX 1-1/4” Inst. RX RX. RX. RX. Dimensions (inches) Height Width Depth 11.70 8.00 3.70 11.70 8.00 3.70 11.70 8.00 3.70 14.80 8.00 4.50 14.80 11.00 4.50 14.80 11.00 4.50 K.O. Fig. 19 19 19 20 21 22 RING TYPE COMMERCIAL SAFETY SOCKETS (NO DISCONNECT) 600V AC MAX., TEST BLOCK BYPASS Amps Catalog Cont. Duty Number 1 PHASE 3 WIRE 100 MS14TB 200 MS24TB 3 PHASE 3 WIRE 100 MS15TB 200 MS25TB 3 PHASE 4 WIRE 100 MS17TB 200 MS27TB Load Lugs No. of Jaws 5th Jaw Hub Dimensions (inches) K.O. Height Width Depth Fig. Top & Bottom Exit Top & Bottom Exit #6-2/0 box lug #1/0-250 kcmil 4 4 UX001WL UX005B RX HC 24.00 30.00 12.50 14.25 4.88 6.38 5 6 Top & Bottom Exit Top & Bottom Exit #6-2/0 box lug #1/0-250 kcmil 5 5 Installed Installed RX HC 24.00 30.00 12.50 14.25 4.88 6.38 5 6 Top & Bottom Exit Top & Bottom Exit #6-2/0 box lug #1/0-250 kcmil 7 7 – – RX HC 24.00 30.00 12.50 14.25 4.88 6.38 5 6 Sockets are UL lised for OH or UG service as indicated, but do not meet EUSERC specifications. Sealing ring included. Dimensions shown are representative of outside box length, width and depth, and do not include allowances for mounting bumps, endwalls, covers hubs or hardware protusions. 5th jaw at 9 o’clock. 5th jaw at 6 o’clock. 4 63331Murray.qxd 3/24/2005 11:23 AM Page 5 EUSERC Commercial Metering 400A CT Meter Cabinets FEATURES 쐽 Rated up to 600 volts 쐽 200A and 400A services 쐽 Accepts bar-type CTs 쐽 Indoor (Type 1) and outdoor (Type 3R) rated 쐽 EUSERC approved 쐽 4-15 terminal available CT MOUNTING BASES 400A MAX. Catalog Number RT6019A Service 1 phase/ 3 phase 3 wire RT6019HA 1 phase RT6067A 3 phase/ RT6067HA 4 wire 400A TRANSFORMER RATED CT–METER CABINET (NO DISCONNECT) 600V AC MAX. Amps Cont. Catalog Duty Number Service 1 PHASE 3 WIRE 400 RTU121814 UG 400 RTU121815 UG 3 PHASE 3 WIRE 400 RTU121818 UG 3 PHASE 3 WIRE OR 3 PHASE 4 WIRE 400 RTU121413 OH/UG 400 RTU122015 UG Max. Wire AIC Range 10 (2) NEMA Studs 50 10 50 (2) NEMA Studs (2) NEMA Studs (2) NEMA Studs No. of Dimensions (inches) Jaws Hub Height Width Depth K.O. Fig. 4 5 – – 52.00 52.00 24.00 24.00 11.00 11.00 11 11 8 – 52.00 24.00 11.00 11 13 15 RX – 20.00 52.00 12.00 36.00 4.63 11.00 12 11 9387-XXXX CT mounting base not included. Order from chart below. Dimensions shown are representative of outside box length, width and depth and do not include allowances for mounting bumps, endwalls, covers hubs or hardware protusions. CT rating. Meter socket rated at 20 amps. Includes test switch provision. Transformer Rated Sockets FEATURES 쐽 Ring and ringless types available 쐽 6, 8, and 13 terminals available 쐽 Steel or aluminum construction 쐽 Split or solid cover options 쐽 Test switch provision 쐽 Prewired units available (contact local Siemens sales office) Cover Style Ring-split Ringless Ringless Ringless Ringless Ringless Ringless Ringless Ringless Ringless Service OH OH/UG OH/UG OH OH/UG OH/UG OH OH OH OH/UG Dimensions (inches) Height Width Depth 20 12 4.5 20 12 4.5 20 12 4.5 20 12 4.5 20 12 4.5 20 12 4.5 20 12 4.5 20 12 4.5 20 12 4.5 20 12 4.5 Hub Opening 1” hub installed RX opening RX closure plate 1” hub installed RX opening RX closure plate 1” hub installed 1.25” hub installed 1.50” hub installed RX opening No. of Terminals 6 6 8 8 8 13 13 13 13 13 Catalog Number Aluminum Steel – 9837-8215 – 9837-8245 – 9837-8405 – 9837-8415 – 9837-8445 9837-8540 9837-8505 9837-8514 9837-8515 – 9837-8525 – 9837-8535 – 9837-8545 5 63331Murray.qxd 3/24/2005 1:12 PM Page 6 EUSERC Commercial Metering Meter Main Combinations DESIGN / PERFORMANCE FEATURES 쐽 Outdoor/Indoor – one design for either installation. 쐽 Ring Type – meets requirements for various ring type locking provisions. 쐽 Test Block Bypass installed – easy servicing without interruption. 쐽 Main Breaker field installed – adaptable to the job. 쐽 Main T-Fuse Puller factory installed (less fuses) – adaptable to the job. SYSTEMS / SPECIFICATIONS 쐽 100/200 amp maximum meter 쐽 120/240V AC, 1 phase 3 wire, 4 jaw 쐽 208Y/120V AC, 3 wire network, 5 jaw or 3 phase 4 wire, 7 jaw 쐽 240V AC, 1 phase 3 wire, 3 phase 3 wire, or 3 phase 4 wire , 4, 5 or 7 jaw 쐽 10,000 to 100,000 AIC 쐽 EUSERC SEC #300 MM0202F3100CESS In addition to local code and National Electrical Code requirements, the serving utility may have special requirements for metering devices. Confirm meter socket acceptance prior to order placement. RING-TYPE METER MAIN COMBINATIONS (100-200A MAX.) Test Block Bypass, 240V AC Max. Amps Circuit Cont. Max. Tenant Breaker Duty AIC Main햲 Prov. 100 65,000 Circuit MP-T, Breaker MP-HT, Prov. MP-MT 100 200 200 100,000 T-Fuse Puller None 35,000 Circuit QJ2, Breaker QJH2, Prov. HQJ2, HQJH2 100,000 T-Fuse None Puller Catalog Service Jaws Number 1 phase 4 MM0202L1100ESS 3 wire 3 phase 7 MM0202L3100ESS 4 wire 1 phase 4 MM0202F1100ESS 3 wire MM0202F1100CESS 3 phase 7 MM0202F3100ESS 4 wire MM0202F3100CESS 1 phase 4 MM0202L1200ESS 3 wire MM0202L1200CESS 3 phase 7 MM0202L3200CESS 4 wire MM0202L3200CESS 1 phase 4 MM0202F1200ESS 3 wire MM0202F1200CESS 3 phase 7 MM0202F3200ESS 4 wire MM0202F3200CESS Service OH Dimensions (inches) 햳 Height Width Depth 36.00 12.50 4.88 36.00 24.00 36.00 24.00 45.00 30.00 45.00 30.00 45.00 30.00 45.00 30.00 12.50 20.13 12.50 20.13 14.25 24.25 14.25 24.25 14.25 24.25 14.25 24.25 4.88 4.88 4.88 4.88 6.38 6.38 6.38 6.38 6.38 6.38 6.38 6.38 OH OH OH/UG OH OH/UG OH OH/UG OH/UG OH/UG OH OH/UG OH OH/UG Wire Range AL/CU #6-2/0 Box Lug #6-2/0 Box Lug Hub K.O. Prov. Fig. 7 RX 7 RX #1/0-250 HC kcmil #1/0-250 HC kcmil 7 9 7 9 8 10 8 10 8 10 8 10 햲 Price does not include breaker or fuses. 햳 Dimensions shown are representative of outside box length, width and depth, and do not include allowances for mounting bumps, endwalls, covers, hubs or hardware protrusions. 6 63331Murray.qxd 3/24/2005 11:23 AM Page 7 EUSERC Commercial Metering Meter Load Center Combinations DESIGN / PERFORMANCE FEATURES 쐽 Outdoor/Indoor – one design for either installation. 쐽 Ring Type – meets requirements for various ring type locking provisions. 쐽 Test Block Bypass installed – easy servicing without interruption. 쐽 Main Breaker factory installed. 쐽 Main T-Fuse Puller factory installed (less fuses). 쐽 Compact wall-hung design reduces material and labor costs. SYSTEMS / SPECIFICATIONS 쐽 100/200 amp maximum meter 쐽 120/240V AC, 1 phase 3 wire, 4 jaw 쐽 240V AC, 3 phase 4 wire, 7 jaw 쐽 10,000 to 100,000 AIC 쐽 EUSERC SEC #300 In addition to local code and National Electrical Code requirements, the serving utility may have special requirements for metering devices. Confirm meter socket acceptance prior to order placement. MC3040MB22SS RING-TYPE COMMERCIAL METER LOAD CENTER COMBINATIONS (100-400A MAX.) Test Block Bypass, 240V AC Max. Amps Cont. Main No. of Max. Catalog Duty Breaker Spaces Circuits Service Number 1 PHASE – 3 WIRE, 4 JAWS, FACTORY INSTALLED MAIN BREAKER 100 MP2100 10 20 OH MC1020B1100ESS 12 24 OH/UG MC1224B1100CESS 200 MPD2200RH 24 40 OH/UG MC2440B1200CESS 320 MPD2200RH 30 30 UG BY1451GL 30 40 UG BY1455GL 3 PHASE – 4 WIRE, 7 JAWS, FACTORY INSTALLED T-FUSE PULLER 100 T-Fuse Prov. 18 30 OH/UG MC1830F3100CESS 200 T-Fuse Prov. 24 42 OH/UG MC2442F3200CESS Dimensions shown are representative of outside box length, width and depth, and do not include allowances for mounting bumps, endwalls, covers, hubs or hardware protrusions. UL listed to field change main breaker to higher AIC. Price does not include uses. Series rated for standard 10,000 AIC type MP-T branch circuit breakers. AIC Rating Dimensions Std. Max. (inches) (K) (K) H. W. 10 10 10 22 22 65 42 22 22 22 100 100 100 100 36.00 24.00 30.00 40.07 40.07 12.50 20.13 25.75 30.25 30.25 D. Wire Range AL/CU Hub K.O. Prov. Fig. 4.88 4.88 6.38 5.94 5.94 #6-2/0 box lug #6-2/0 box lug #1/0-250 kcmil 1 set of 2 studs per leg RX RX HC HV HV 11 12 13 18 18 #6-2/0 box lug RX #1/0-250 kcmil HC 14 15 26.00 24.25 4.88 2.00 27.25 6.38 One MPD2200RH installed. Provisions for one additional subfeed MP-T or MP-HT (100 amps max.) breaker service disconnect to feed a remote load. One MPD2200RH installed. Provisions for one additional subfeed MD-TR or MD-HTR breaker type service disconnect to feed a remote load. 7 63331Murray.qxd 3/24/2005 11:23 AM Page 8 All-In-One Pak Metering New and Improved! Murray Exclusive Smaller, more compact design! enclosures are lighter and use less wall space Floating deadfront! eliminates need for cover alignment Murray Exclusive Factory options! 5th jaw and horn bypass Deadfront knockouts! eliminates need for filler plates Murray Exclusive Double barrel connectors available for parallel feed Angled circuit breaker! for ease of installation Stud Kits for line compression lugs available Centrally located neutral minimizes neutral conductor length More secure design! greater utility acceptance Back and Bottom Exit for load conductors EUSERC designs! All ring style designs! are EUSERC approved Single piece tenant cover! easy installation Catalog Number Logic Example: MP6511RJB M M = Murray 8 P P = PAK 6 0 = No bussing 2 = 200 Amp 3 = 300 Amp 4 = 400 Amp 5 = 500 Amp 6 = 600 Amp 5 Number of Meter Sockets (2-6) 1 1 = Single Phase 1 1 = 125A Socket Rating 2 = 200A Socket Rating RJB R = Ringless J = 5th Jaw B = Horn Bypass 63331Murray.qxd 3/24/2005 11:23 AM Page 9 All-In-One Pak Metering Ring Type Units FEATURES 쐽 Individual split covers. 쐽 UL Listed for 60/75oC conductors. See equipment markings for applications. 쐽 Outdoor surface mounted enclosures field convertible to semi-flush applications. 쐽 Top or bottom feed. 쐽 Back and bottom branch wiring exits. 쐽 Meets EUSERC specifications when NEMA stud kit is field added. 쐽 1 phase, 4 jaw sockets, 120/240V AC Max. MP2211 1 PHASE, 3 WIRE SN Amps Cont. Duty Bus Per Position Amps 125 200 125 300 125 400 125 400 125 400 125 500 125 600 125 600 200 400 200 400 200 400 200 600 200 600 200 600 Meter Positions Per Pak 2 3 4 5 6 4 5 6 2 3 4 4 5 6 Catalog Number MP2211 MP3311 MP4411 MP4511 MP4611 MP5411 MP6511 MP6611 MP4212 MP4312 MP4412 MP6412 MP6512 MP6612 Circuit Breaker Max. Provision AIC MP-T, 65,000 MP-HT, 65,000 MP-MT 65,000 65,000 65,000 65,000 65,000 65,000 MP-T, 100,000 MP-HT, 100,000 MP-MT, 100,000 MPP-T, 100,000 MPP-HT, 100,000 MPP-MT, 100,000 MPP-PT Dimensions (inches) Height Width Depth 37.50 13.50 6.00 38.40 25.20 7.50 47.40 25.20 7.50 38.40 39.20 7.50 38.40 39.20 7.50 47.40 31.50 7.50 38.40 45.20 7.50 38.40 45.20 7.50 31.50 30.75 7.50 38.44 30.75 7.50 47.44 30.75 7.50 47.44 36.75 7.50 38.44 54.44 7.50 38.44 54.44 7.50 5th Jaw Assembly GM5J GM5J GM5J GM5J GM5J GM5J GM5J GM5J GM5J GM5J GM5J GM5J GM5J GM5J Line Lugs Wire Range #6-300 kcmil #2-600 kcmil (1) 1/0-750 kcmil or (2) 1/0-250 kcmil (2) #2-600 kcmil (1) 1/0-750 kcmil or (2) 1/0-250 kcmil (2) #2-600 kcmil Semi-Flush Kit Catalog Number P221FK P331FK P441FK P4561FK P4561FK P541FK P6561FK P6561FK P422FK P432FK P442FK P642FK P6562FK P6562FK Dimensions shown are representative of outside box length, width and depth, and do not include allowances for mounting bumps, endwalls, covers, hubs, or hardware protrusions. Order Catalog No. ECMMI5J for insulated 5th jaw. All-In-One Pak Metering Accessories Catalog Number Description Grounded Insulated GM5J ECMMI5J 100 Amp 200 Amp ECMBP1U ECMBP2U ECHBK BYPASS KITS Slider Bypass Catalog Number Horn Bypass COVER PLATES Ring Style Ringless Style ECOF3 ECCP3U NEMA STUD KITS (Meets EUSERC Requirements) 400 Amp Bus 600 Amp Bus NSK400 NSK600 LUGS FOR NEMA STUD KITS ECPP ECP3 (2) #6-350 kcmil (1) #2-600 kcmil (2) #500-1000 kcmil SRSS SRSW ALTERNATE LUG KITS SEALING RINGS Snap-On Type Aluminum Screw Type Stainless Steel 1” 4” to 2” 400 Amp Bus 600 Amp Bus Description Catalog Number TYPE “HS” CONDUIT HUBS FILLER PLATES 5TH JAW KITS All Types Description SUK350TA SUK600TA SUK1000TA PLK400 PLK600 1” 1-1/4” 1-1/2” 2” 2-1/2” Closure Plate ECHS100 ECHS125 ECHS150 ECHS200 ECHS250 ECHS000 TYPE “HD” CONDUIT HUBS 2” 2-1/2” 3” 3-1/2” 4” Closure Plate EC56854 EC56855 EC56856 EC56857 EC56858 EC56933S 9 63331Murray.qxd 3/24/2005 11:23 AM Page 10 Modular Metering Service Entrance Modules – 1 Phase FEATURES 쐽 Mains available in fusible or circuit breaker style. 쐽 400-800A fusible mains and all tap boxes are invertible for top or bottom feed. 쐽 100,000A IC standard on fusible main disconnects and tap boxes. 쐽 65,000A IC standard for circuit breakers (100,000A IC versions available. Add suffix “U” to catalog number. Adder applies.) 쐽 All mains fully bussed to connect with stacks on either side. 쐽 End plates included. SELECTION GUIDE 쐽 Always check with the utility and local inspection authorities to verify all application requirements. 쐽 Select fusible or circuit breaker main after determination of amps, volts, service, and AIC. 쐽 Fusible mains and tap boxes are invertible for top or bottom feed. Breaker modules are available in dedicated top or bottom feed versions. Add suffix “BF” to circuit breaker mains for bottom feed. DB042W 1 PHASE, 3 WIRE SN, INCOMING, 120/240V AC MAX. Max. Outdoor Encl. Fuse or Line Terminal Lugs Ampere Interrupting Catalog Circuit Service No. and Size Per Rating Rating Number Breaker Type Feed Line and Neutral CIRCUIT BREAKER MODULES 400 65,000 DB042W JXD6 OH (2) #1-500 kcmil 600 65,000 DB062W LXD6 OH (2) #1-500 kcmil 800 65,000 DB082W MD6 OH (3) #1/0 400 kcmil 1000 65,000 DB102W ND6 OH (4) #2-500 kcmil 1200 65,000 DB122W ND6 OH (4) #2-500 kcmil 1600 65,000 DB162W PD6 OH (5) 300-600 kcmil FUSIBLE SWITCH MODULES 200 100,000 DPT022W T OH/UG (1) #6-250 kcmil 400 100,000 DT042W T OH/UG (2) #4-500 kcmil 600 100,000 DT062W T OH/UG (2) #4-500 kcmil 800 100,000 DT082W T OH/UG (3) #4-500 kcmil 1200 100,000 DT122W T UG (4) #250-500 kcmil TAP BOX MODULES 800 100,000 DTB082W – OH/UG (3) 1/0-400 kcmil 1200 100,000 DTB122W – OH/UG (4) 250-600 kcmil 1600 100,000 DTB162W – OH/UG (5) 300-600 kcmil COMBINATION FUSIBLE SWITCH & PULL BOX MODULES (MEETS EUSERC REQUIREMENTS) 400 100,000 DT042UW T UG 1 Set of 2 Studs 600 100,000 DT062UW T UG 1 Set of 2 Studs 800 100,000 DT082UW T UG 1 Set of 2 Studs PULL BOX MODULES (NO THRU-BUS, INCLUDES LUG LANDINGS) 400 65,000 DPB042W – OH/UG 1 Set of 2 Studs 800 65,000 DPB082W – OH/UG 1 Set of 2 Studs 1200 65,000 DPB122W – OH/UG 1 Set of 2 Studs Dimensions shown are representative of outside box length, width, and depth, and do not include allowances for mounting bumps, endwalls, covers, hubs, or hardware protrusions. Lugs may be larger than wire range given. Wire range given is according to amount of wire bend space available. 10 Main circuit breakers are top feed. Consult sales office for bottom feed applications. Lugs rated for 500 kcmil. Wire bend space limits neutral lug to 400 kcmil. Neutral on bottom feed units will only accept (2) #1-500 kcmil. Dimensions (inches) Depth Height Width Outdoor 33.00 37.00 43.00 50.00 50.00 62.00 15.09 15.09 20.09 20.09 20.09 25.03 15.00 15.00 15.00 15.00 15.00 17.50 33.00 33.50 41.50 41.50 50.00 12.00 15.00 15.00 15.00 20.00 13.00 16.00 16.00 16.00 15.00 39.00 41.00 41.75 12.00 15.00 25.00 12.00 16.00 14.00 50.06 50.06 50.06 25.50 25.50 25.50 15.00 15.00 15.00 37.50 45.50 47.50 16.69 19.44 25.94 9.34 12.72 12.72 1200 amp maximum feed per side. Fuses not included Fusible switches, except 1200 amp, are top feed, invertible for bottom feed. Fusible pull-out switch. Coupler not included. 63331Murray.qxd 3/24/2005 11:23 AM Page 11 Modular Metering Service Entrance Modules – 3 Phase FEATURES 쐽 Mains available in fusible or circuit breaker style. 쐽 400-800A fusible mains and all tap boxes are invertible for top or bottom feed. 쐽 100,000A IC standard on fusible main disconnects and tap boxes. 쐽 65,000A IC standard for circuit breakers (100,000A IC versions available. Add suffix “U” to catalog number. Adder applies.) 쐽 All mains fully bussed to connect with stacks on either side. 쐽 End plates included. SELECTION GUIDE 쐽 Always check with the utility and local inspection authorities to verify all application requirements. 쐽 Select fusible or circuit breaker main after determination of amps, volts, service, and AIC. 쐽 Fusible mains and tap boxes are invertible for top or bottom feed. Breaker modules are available in dedicated top or bottom feed versions. Add suffix “BF” to circuit breaker mains for bottom feed. DT043W 3 PHASE, 4 WIRE SN, INCOMING, 120/240V AC MAX. Max. Outdoor Encl. Fuse or Line Terminal Lugs Ampere Interrupting Catalog Circuit Service No. and Size Per Rating Rating Number Breaker Type Feed Line and Neutral CIRCUIT BREAKER MODULES 400 65,000 DB043W JXD6 OH (2) #1-500 kcmil 600 65,000 DB063W LXD6 OH (2) #1-500 kcmil 800 65,000 DB083W MD6 OH (3) #1/0 400 kcmil 1000 65,000 DB103W ND6 OH (4) #2-500 kcmil 1200 65,000 DB123W ND6 OH (4) #2-500 kcmil 1600 65,000 DB163W PD6 OH (5) 300-600 kcmil FUSIBLE SWITCH MODULES 400 100,000 DT043W T OH/UG (2) #4-500 kcmil 600 100,000 DT063W T OH/UG (2) #4-500 kcmil 800 100,000 DT083W T OH/UG (3) #4-500 kcmil 1200 100,000 DT123W T UG (4) #250-500 kcmil TAP BOX MODULES 800 100,000 DTB083W – OH/UG (3) 1/0-400 kcmil 1200 100,000 DTB123W – OH/UG (4) 250-600 kcmil 1600 100,000 DTB163W – OH/UG (5) 300-600 kcmil COMBINATION FUSIBLE SWITCH & PULL BOX MODULES (MEETS EUSERC REQUIREMENTS) 400 100,000 DT043UW T UG 1 Set of 2 Studs 600 100,000 DT063UW T UG 1 Set of 2 Studs 800 100,000 DT083UW T UG 1 Set of 2 Studs PULL BOX MODULES (NO THRU-BUS, INCLUDES LUG LANDINGS) 400 65,000 DPB043W – OH/UG 1 Set of 2 Studs 800 65,000 DPB043W – OH/UG 1 Set of 2 Studs 1200 65,000 DPB043W – OH/UG 1 Set of 2 Studs Dimensions shown are representative of outside box length, width and depth, and do not include allowances for mounting bumps, endwalls, covers, hubs, or hardware protrusions. Lugs may be larger than wire range given. Wire range given is according to amount of wire bend space available. Main circuit breakers are top feed. Consult sales office for bottom feed applications. Lugs rated for 500 kcmil. Wire bend space limits neutral lug to 400 kcmil. Neutral on bottom feed units will only accept (2) #1-500 kcmil. Dimensions (inches) Depth Height Width Outdoor 33.00 37.00 43.00 50.00 50.00 62.00 15.09 15.09 20.09 20.09 20.09 25.03 15.00 15.00 15.00 15.00 15.00 17.50 33.50 41.50 41.50 50.00 15.00 15.00 15.00 20.00 16.00 16.00 16.00 15.00 39.00 41.00 41.75 12.00 15.00 25.00 12.00 16.00 14.00 50.06 50.06 50.06 25.50 25.50 25.50 15.00 15.00 15.00 37.50 45.50 47.50 16.69 19.44 25.94 9.34 12.72 12.72 1200 amp maximum feed per side. Fuses not included Fusible switches, except 1200 amp, are top feed, invertible for bottom feed. Coupler not included. 11 63331Murray.qxd 3/24/2005 11:23 AM Page 12 Modular Metering Ring Type Meter Modules FEATURES 쐽 UL Listed for 60/75o C conductors. See equipment markings for applications. 쐽 Individual split covers with barrel lock compatibility. 쐽 Interconnectable with discontinued “MM” modular metering. 쐽 Finish is ANSI #61 light gray enamel electrodeposited on zinc-coated G90 steel. 쐽 200A units UL Listed for use on systems capable of delivering up to 100,000 RMS symmetrical amperes maximum short circuit current. SERIES TESTED SYSTEMS Specify Siemens Modular Metering Equipment in conjunction with EQ약 III or Ultimate약 Load Centers DG432W DG331W DG341W 1 Phase, 3 Wire SN, Incoming and Outgoing, Ring Type Gangable Meter Stack Continuous Meter Duty Amps Positions Catalog Breaker Maximum Per Position Per Stack Number Provision AIC 1 PHASE 4-JAW SOCKETS, 1 PHASE-3 WIRE THRU-BUS 120/240V AC MAX. 125 3 DG331W MP-T, MP-HT, 65,000 4 DG431W MP-MT 65,000 5 DG531W 65,000 6 DG631W 65,000 200 2 DG232W MPP-T, MPP-HT, 100,000 3 DG332W MPP-MT, MPP-PT 100,000 4 DG432W 100,000 Dimensions (inches) Height Width Depth 5th Jaw Assembly Horn Bypass Kit 41.41 50.41 59.41 68.41 36.41 47.41 58.41 ECMM5J ECMM5J ECMM5J ECMM5J ECMM5J ECMM5J ECMM5J ECHBK ECHBK ECHBK ECHBK ECHBK ECHBK ECHBK 13.44 13.44 13.44 13.44 17.44 17.44 17.44 7.84 7.84 7.84 7.84 7.84 7.84 7.84 3 Phase, 4 Wire SN, Incoming and 1 Phase, 3 Wire SN Outgoing, Ring Type Gangable Meter Stack Continuous Meter Duty Amps Positions Catalog Breaker Maximum Per Position Per Stack Number Provision AIC 1 PHASE 5-JAW SOCKETS, 3 PHASE-4 WIRE THRU-BUS 208Y/240V AC 125 3 DG341W MP-T, 65,000 4 DG441W MP-HT, 65,000 5 DG541W MP-MT 65,000 6 DG641W 65,000 200 2 DG242W MPP-T, 100,000 3 DG342W MPP-HT, 100,000 4 DG442W MPP-MT, 100,000 Order ECMMI5J for insulated 5th jaw. Dimensions shown are representative of outside box length, width and depth, and do not include 12 Dimensions (inches) Height Width Depth 5th Jaw Assembly Horn Bypass Kit 41.41 50.41 59.41 68.41 36.41 47.41 58.41 Installed Installed Installed Installed Installed Installed Installed ECHBK ECHBK ECHBK ECHBK ECHBK ECHBK ECHBK allowances for mounting bumps, endwalls, covers, hubs or hardware protrusions. Max. AIC determined by maximum AIC of tenant breakers. Higher ratings may be 13.44 13.44 13.44 13.44 17.44 17.44 17.44 7.84 7.84 7.84 7.84 7.84 7.84 7.84 achieved thru approved series rating combinations. Order filler plate ECCP3U if using standard 2” wide circuit breaker (QP). Not for use on 3 phase, 4 wire delta systems. 63331Murray.qxd 3/24/2005 11:23 AM Page 13 Modular Metering Commercial Meter Modules 225A Maximum 1 Phase, 3 Wire SN Incoming and Outgoing 120/240 VOLT AC 225 AMPERE, 1 PHASE SOCKET Use Type MP-T, MP-HT, MP-MT, MPP-T, MPP-HT, MPP-MT, MPP-PT circuit breakers, 2-pole (plug-in) Ampere No. of Rating Meter Sckts. 1200 1 2 3 4 Catalog Number W1MM1225SS W1MM2225SS W1MM3225SS W1MM4225SS 3 Phase, 4 Wire SN, Incoming 1 Phase, 3 Wire SN, Outgoing 3 Phase, 4 Wire SN, Incoming 1 Phase, 3 Wire SN, Outgoing 120/208 VOLT AC 225 AMPERE, 1 PHASE SOCKET Use Type MP-T, MP-HT, MP-MT, MPP-T, MPP-HT, MPP-MT, MPP-PT circuit breakers, 2-pole (plug-in) 120/208 VOLT AC 200 AMPERE, 3 PHASE SOCKET Use Type QJ2, QJH2, QJ2H, HQJ2H circuit breakers, 3-pole (bolt-on) Ampere No. of Rating Meter Sckts. 1200 1 2 2 2 3 4 4 4 Catalog Number W2MM1225SS W2MM2AB225SS W2MM2BC225SS W2MM2CA225SS W2MM3225SS W2MM4AB225SS W2MM4BC225SS W2MM4CA225SS Ampere No. of Rating Meter Sckts. 1200 1 2 3 4 Catalog Number W3MM1200SS W3MM2200SS W3MM3200SS W3MM4200SS Note: All meter modules are supplied with one hanger bracket and one single bolt joint. Lag screws for hanger bracket and mounting brackets are not included. When adding modular metering modules to old installation, replace metal end closure plate with plastic end closure plate. Catalog Number WMEP. Meter socket is plug-in lever bypass clamping jaw type except where noted. 200A units UL Listed for use on systems capable of delivering up to 100,000 RMS symmetrical amperes maximum short circuit current. 200A sockets are rated continuous duty. 200A maximum breaker size. Available July 2005. 13 63331Murray.qxd 3/24/2005 11:23 AM Page 14 Plug-In Circuit Breakers Types QP, QPH, and HQP with INSTA-WIRE약, QN and QNH 1-POLE (120V AC) Continuous TYPE MP-T Current Rating 10,000A IR @40oC Catalog Number 10 MP110 15 MP115 20 MP120 25 MP125 30 MP130 35 MP135 40 MP140 45 MP145 50 MP150 60 MP160 70 MP170 2-POLE COMMON-TRIP (120/240V AC) Continuous TYPE MP-T Current Rating 10,000A IR @40oC Catalog Number 15 MP215 20 MP220 25 MP225 30 MP230 35 MP235 40 MP240 45 MP245 50 MP250 60 MP260 70 MP270 80 MP280 90 MP290 100 MP2100 110 MP2110 125 MP2125 2-POLE COMMON-TRIP (240V AC) Continuous TYPE MP-T Current Rating 10,000A IR @40oC Catalog Number 15 MPH215 20 MPH220 30 MPH230 40 MPH240 50 MPH250 60 MPH260 70 MPH270 100 MPH2100 3-POLE COMMON-TRIP (240V AC) Continuous TYPE MP-T Current Rating 10,000A IR @40oC Catalog Number 15 MP315 20 MP320 25 MP325 30 MP330 35 MP335 40 MP340 45 MP345 50 MP350 60 MP360 70 MP370 80 MP380 90 MP390 100 MP3100 14 TYPE MP-HT 22,000A IR Catalog Number – MP115KH MP120KH MP125KH MP130KH MP135KH MP140KH MP145KH MP150KH MP160KH MP170KH TYPE MP-MT 65,000A IR Catalog Number – MP115KM MP120KM MP125KM MP130KM MP135KM MP140KM MP145KM MP150KM MP160KM MP170KM TYPE MP-HT 22,000A IR Catalog Number MP215KH MP220KH MP225KH MP230KH MP235KH MP240KH MP245KH MP250KH MP260KH MP270KH MP280KH MP290KH MP2100KH MP2110KH MP2125KH TYPE MP-MT 65,000A IR Catalog Number MP215KM MP220KM MP225KM MP230KM MP235KM MP240KM MP245KM MP250KM MP260KM MP270KM – MP290KM MP2100KM MP2110KM MP2125KM TYPE MP-HT 22,000A IR Catalog Number – – – – – – – – TYPE MP-MT 65,000A IR Catalog Number – – – – – – – – TYPE MP-HT 22,000A IR Catalog Number MP315KH MP320KH MP325KH MP330KH – MP340KH – MP350KH MP360KH MP370KH MP380KH MP390KH MP3100KH TYPE MP-MT 65,000A IR Catalog Number MP315KM MP320KM – MP330KM – MP340KM – MP350KM MP360KM MP370KM MP380KM MP390KM MP3100KM 2-Pole Type MP-T 1-Pole Type MP-T 3-Pole Type MP-T Type MD-T Type MD-HT Type MD-T and MD-HT Brkr. Type MD-T 2-Pole 120/ 240V AC MD-HT 2-Pole 120/ 240V AC Amp Rtg. 150 175 200 10K AIR Catalog Number MPD2150 MPD2175 MPD2200 22K AIR Catalog Number MPD2150R MPD2175R MPD2200R 150 MPD2150KH MPD2150RH 175 MPD2175KH MPD2175RH 200 MPD2200KH MPD2200RH HACR rated. UL listed for frequent switching applications (SWD). 120V AC fluorescent lighting. Built to order. Allow 2-3 weeks for delivery. 63331Murray.qxd 3/24/2005 11:23 AM Page 15 Plug-In Circuit Breakers Duplex, Triplex, Quadplex, GFCIs, AFCIs and Surge Products DUPLEX CIRCUIT BREAKERS Breaker Ampere Type Rating MH-T 15-15 1-Pole 15-20 10K AIC 20-20 120V AC 20-30 15-30 30-30 TRIPLEX CIRCUIT BREAKERS Ampere Rating Breaker Single Type Pole MH-T 15 2-Pole 15 10K AIC 15 120/240V AC 15 Center 15 Common Trip 15 15 15 20 20 20 20 20 20 20 Duplex Catalog Number MP1515 MP1520 MP2020 MP2030 MP3015 MP3030 Triplex Catalog Number MP1515N MP1520N MP2020N MP2030N MP3015N MP3030N Quadplex Common-Trip 2-Pole 15 20 25 30 35 40 45 50 20 25 30 35 40 45 50 Catalog Number MP21515 MP22015 MP22515 MP23015 MP23515 MP24015 MP24515 MP25015 MP22020 MP22520 MP23020 MP23520 MP24020 MP24520 MP25020 1 & 2-Pole GFCIs 2-Pole AFCI 1-Pole AFCI QUADPLEX CIRCUIT BREAKERS Ampere Rating Breaker Inside Type 2-Pole MH-T 15 2-Pole 15 10K AIC 20 120/240V AC 20 Common Trip 30 30 40 50 GROUND FAULT CIRCUIT INTERUPTERS (Class A - 5mA) Brkr. Type MP-GT, MP-HGT 1-Pole 120V AC MP-GT, MP-HGT 2-Pole 120/ 240V AC Amp Rtg. 15 20 25 30 10K AIR Catalog Number MP115GF MP120GF MP125GF MP130GF 22K AIR Catalog Number MP115GFH MP120GFH – MP130GFH 15 20 30 40 50 60 MP215GF MP220GF MP230GF MP240GF MP250GF MP260GF MP215GFH MP220GFH MP230GFH MP240GFH MP250GFH MP260GFH Outside 2-Pole 15 20 30 40 30 40 40 30 Catalog Number MP215215CT2 MP220220CT2 MP220230CT2 MP220240CT2 MP230230CT2 MP230240CT2 MP240240CT2 MP250230CT2 ARC FAULT CIRCUIT INTERUPTERS (Class A - 5mA) Brkr. Type MP-AT, MP-HAT 1-Pole 120V AC MP-AT, MP-HAT 2-Pole 120/ 240V AC Amp Rtg. 15 20 10K AIR Catalog Number MP115AF MP120AF 22K AIR Catalog Number MP115AFH MP120AFH 15 20 MP215AF MP220AF MP215AFH MP220AFH CB/SSA TVSS SURGE PROTECTION 10K AIR Breaker Amp. Catalog Type Rtg. Number QP (2)15 MSA1515 1-Pole 120/ (2)20 MSA2020 240V AC QP (2)20 MSA2020TVSS 1-Pole 120/ 240V AC Surge Type Surge Arrester Surge Arrester TVSS UL listed for frequent switching applications (SWD). 120V AC fluorescent lighting. Built to order. Allow 2-3 weeks for delivery. 15 HACR rated. 63331Murray.qxd 3/24/2005 11:23 AM Page 16 MISCELLANEOUS ACCESSORIES Accessories INTERCHANGEABLE HUBS Conduit Size Catalog (Ins. / lbs.) Number HS TYPE HUBS 3/4 ECHS075 1 ECHS100 1-1/4 ECHS125 1-1/2 ECHS150 2 ECHS200 2-1/2 ECHS250 RX TYPE HUBS 3/4 EC38594 1 EC38596 1-1/4 EC38597 1-1/2 EC38598 2 EC38599 2-1/2 EC38600 HC TYPE HUBS 2 ECHC200 2-1/2 ECHC250 3 ECHC300 ACCESSORIES AND CLOSURE PLATES Adapter Plate ECHCRXA Closure Plates For HC Hubs ECHC000 For HS Hubs ECHS000 For HV Hubs ECHV000 For RX Hubs EC38595 Catalog Number SX001M SX001M BYPASS KITS Catalog Description Number Manual Bypass (ring style only) MBP1U Insul. 5th Jaw (ring style only) MBP2U 200A Jumper (ring style only) JSU Horn Bypass Replacement HBPU COVER PLATE KITS Description Ring Style Ringless Style Description RT WIREWAY Termination Lugs (2) #6-350 kcmil (1) #2-600 kcmil (2) #500-1000 kcmil 16 SX087M SX088M UK350TA UK600TA UK1000TA EMC5J ECLK1 ECLK2 ECLK3 GROUND BARS (Al/Cu – except where noted) Description 5 Position, #4-14 AWG Cu/Al 10 Position, #4-14 AWG Cu/Al 10 Position, #4-14 AWG Cu/Al, 1 Position #14-1/0 Cu/Al 14 Position, #4-14 AWG Cu/Al 14 Position, #4-14 AWG Cu/Al, 1 Position #14-1/0 Cu/Al 14 Position, #4-14 AWG Cu/Al, 1 Position #6-2/0 Cu/Al 20 Position, #4-14 AWG Cu/Al 20 Position, #4-14 AWG Cu/Al, 1 Position #14-1/0 Cu/Al 20 Position, #4-14 AWG Cu/Al, 1 Position #6-2/0 Cu/Al Catalog Number ECGB5 ECGB10 ECGB101 ECGB14 ECGB141 ECGB142 ECGB20 ECGB201 ECGB202 5TH JAW KITS SEALING RINGS (Al) Description Snap-on type Screw type Description Plastic Meter Opening Cover (JA, JC) Plastic Meter Cover Ringless (JB) NEMA Stud Mechanical Lugs (2) #6-350 kcmil (1) #2-600 kcmil, Al/Cu (2) #500-1000 kcmil, Al/Cu Fifth Jaw Neutral Feeder Lugs for use on INSTA-WIRE bars #2-1/0 #4-2/0 #1-350 kcmil Catalog Number Catalog Number CPP CP3 Catalog Number UK350TA UK600TA UK1000TA Description Bonded 5th Jaw Insulated 5th Jaw For use on SP0211 only Catalog Number GM5J IGM5J WSX019P UNIVERSAL PAK/MOD. ACCESSORIES Description Sealing Rings Snap-on, stainless steel Screw-on, stainless steel Snap-on, aluminum 2-pole blank Filler Plate QP 125A max. breaker 4-pole blank Filler Plate QPP 225A max. breaker 4-pole blank Filler Plate QP (2” wide) 125A breaker installed Plastic Cover Plates Ring Type Socket Ringless Type Socket Meter Bypass Jpr. 4&5 jaw Manual Bypass Meter Skt. 125A Meter Cover Manual Bypass Meter Skt. 200A Meter Cover Catalog Number SRSS SRSW SRSTD ECP1U ECP2U ECP3U ECPP ECP3 ECJS ECMBP1U ECMBP2U MODULAR METERING ACCESSORIES Description Single Bolt Joints 1 Phase, 3 Wire, 1200A max. 3 Phase, 4 Wire, 1200A max. Indoor Bussed Elbow 1 Phase, 3 Wire, 1200A max. 3 Phase, 4 Wire, 1200A max. Outdoor Bussed Extension 1 Phase, 3 Wire, 1200A max. 3 Phase, 4 Wire, 1200A max. 5th Jaw Kit (3, 6, 9 o’clock) Ins. 5th Jaw Kit (3, 6, 9 o’clock) Pass-Thru Bushing for use with Underground Pull Box End Closure Plate HR Type Hubs for Service Entrance Module 3/4” 1” 1-1/4” 1-1/2” 2” HV Type Hubs for Service Entrance Module 2” 2-1/2” 3” 3-1/2” 4” Catalog Number SBJ1 SBJ4 BE1 BE4 WMEX1U WMEX4U ECMM5J ECMMI5J WMMBK WMEP ECHR075 ECHR100 ECHR125 ECHR150 ECHR200 ECHV200 ECHV250 ECHV300 ECHV350 ECHV400 PAK METERING ACCESSORIES Description HD Type Hubs 2” 2-1/2” 3” 3-1/2” 4” Closure Plate NEMA Stud Kit for new Uni-Pak 400A 600A Parallel Lug Kit 400A 600A 5th Jaw Kit Insulated 5th Jaw Kit NEMA Stud Kit for old Uni-Pak 400A 600A Catalog Number EC56854 EC56855 EC56856 EC56857 EC56858 EC56933S NSK400 NSK600 PLK400 PLK600 GM5J ECMMI5J LKNS4U LKNS8U For use on 125A and 200A sockets only. One pass-thru bushing supplied with each WMM8 device. When adding modular metering modules to old installation, replace metal and closure plate wtih plastic end closure plate. Item is a kit consisting of adaptor plate and Type RK hub. For use on new Pak only. Use ECMM5J for old Pak. Filler plate is not needed for new Pak. (2) required per 1 phase meter socket. Residential type ring and ringless. 200A max. Meter cannot be installed while in use. For use with ECPP cover plate. 63331Murray.qxd 3/24/2005 11:23 AM Page 17 Combination Meter Sockets Dimensions, Wiring, and Knockout Diagrams D (2) RX Hub Pattern A (3) B (2) B E D B (4) D F C (2) A (3) B Knockout Schedule A = 1/2” B = 1/2”, 3/4” C = 1/2”, 3/4”, 1” D = 3/4”, 1”, 1-1/4”, 1-1/2”, 2” E = 1”, 1-1/4”, 1-1/2”, 2”, 2-1/2” F = 1-1/4”, 1-1/2”, 2”, 2-1/2”, 3” G = 0.31 diameter Ground Wire K.O. B (4) D F FIGURE 1 JA1224B1100FEC JA1224B1100SEC JA1224B1125FEC JA1224B1125SEC D E C (2) A (3) FIGURE 2 JA1632B1100FEC JA1632B1100SEC JA1632B1125FEC JA2442B1200FEC JA2442B1200SEC JA2442B1225FEC JA2442B1225SEC JC0406L1125FEC JC0406L1125SEC JC0406L1200FEC JC0406L1200SEC 17 63331Murray.qxd 3/24/2005 11:23 AM Page 18 C A (10) Combination Meter Sockets Dimensions, Wiring, and Knockout Diagrams D (2) B (3) RX Hub Pattern (2) E B (2) A E B (4) D B (2) A B (4) D C (2) F A (3) Knockout Schedule A = 1/2” B = 1/2”, 3/4” C = 1/2”, 3/4”, 1” D = 3/4”, 1”, 1-1/4”, 1-1/2”, 2” E = 1”, 1-1/4”, 1-1/2”, 2”, 2-1/2” F = 1-1/4”, 1-1/2”, 2”, 2-1/2”, 3” G = 0.31 diameter Ground Wire K.O. F C (2) A (3) FIGURE 4 FIGURE 3 JA1212L1200FED JA1212L1200SED 18 JA2040B1200FED JA2040B1200SED JA3042B1200FED JA3042B1200SED JA3042B1225FED JA3042B1225SED 63331Murray.qxd 3/24/2005 11:23 AM Page 19 EUSERC Commercial Metering Wiring Diagrams MC1020B1100ESS MC1224B1100CESS MC1830F3100CESS MC2442F3200CESS MC2440B1200CESS MC3040MB21/22SS 19 63331Murray.qxd 3/24/2005 11:24 AM Page 20 EUSERC Commercial Metering Dimensions and Knockout Diagrams FIGURE 5 FIGURE 6 FIGURE 7 FIGURE 8 FIGURE 9 FIGURE 10 FIGURE 11 FIGURE 12 DIMENSIONS (inches) Catalog Number MS14TB MS15TB MS17TB MM0202B1100ESS MM0202B3100ESS MM0202F1100ESS MM0202F1100CESS MM0202F3100ESS MM0202F3100CESS MC1020B1100ESS MC1224B1100CESS MC1830F3100CESS MS24TB MS25TB 20 K.O. Fig. 5 5 5 7 7 7 9 7 9 11 12 14 6 6 Height 24 24 24 36 36 36 24 36 24 36 24 26 30 30 Width 12-1/2 12-1/2 12-1/2 12-1/2 12-1/2 12-1/2 20-1/8 12-1/2 20-1/8 12-1/2 20-1/8 24-1/4 14-1/4 14-1/4 Depth 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 4-7/8 6-3/8 6-3/8 Catalog Number MS27TB MM0202F1200ESS MM0202F1200CESS MM0202F3200ESS MM0202F3200CESS MM0202B1200ESS MM0202B1200CESS MM0202B3200ESS MM0202B3200CESS MC2440B1200CESS MC2442F3200CESS MC3040MB21SS MC3040MB22SS K.O. Fig. 6 8 10 8 10 8 10 8 10 13 15 18 18 Height 30 45 30 45 30 45 30 45 30 30 42 40 40 Width 14-1/4 14-1/4 23-1/4 14-1/4 23-1/4 14-1/4 23-1/4 14-1/4 23-1/4 25-3/4 27-1/4 30-1/4 30-1/4 Depth 6-3/8 6-3/8 6-3/8 6-3/8 6-3/8 6-3/8 6-3/8 6-3/8 6-3/8 6-3/8 6-3/8 6 6 63331Murray.qxd 3/24/2005 11:24 AM Page 21 EUSERC Commercial Metering Dimensions and Knockout Diagrams FIGURE 13 FIGURE 14 FIGURE 15 FIGURE 16 FIGURE 17 FIGURE 18 Knockout Code - Conduit Sizes (inches) 䊎 = 1/4 S = 1, 1-1/4, 1-1/2, 2, 2-1/2 A = 1/2 T = 1-1/4 B = 1/2, 3/4 U = 1-1/4, 1-1/2 C = 1/2, 3/4, 1 V = 1-1/4, 1-1/2, 2 D = 1/2, 1 W = 1-1/4, 2 E = 1/2, 3/4, 1, 1-1/4 X = 1-1/4, 1-1/2, 2, 2-1/2 F = 1/2, 1-1/4, 1-1/2 Y = 1-1/2, 2 G = 3/4 Z = 1-1/2, 2, 2-1/2 H = 3/4, 1 AA = 1-1/2, 2, 2-1/2, 3 J = 3/4, 1, 1-1/4 BB = 1-1/2, 2, 2-1/2, 3, 3-1/2 K = 3/4, 1-1/4 CC = 2, 2-1/2, 3, 3-1/2 M - 3/4, 1, 1-1/4, 1-1/2 EE = 2, 2-1/2, 3 N = 3/4, 1, 1-1/4, FF = 2-1/2, 3 1-1/2, 2 GG = 2-1/2, 3, 3-1/2 P = 1, 1-1/4 HH = 2-1/2, 3, 3-1/2, 4 Q = 1, 1-1/4, 1-1/2 JJ = 3-1/2, 4 R = 1, 1-1/4, 1-1/2, 2 LL = 3 VV=2 21 63331Murray.qxd 3/24/2005 11:24 AM Page 22 EUSERC Commercial Metering Dimensions, Wiring, and Knockout Diagrams FIGURE 19 FIGURE 20 FIGURE 21 Knockout Schedule A = 1/2” B = 1/2”, 3/4” C = 1/2”, 3/4”, 1” D = 3/4”, 1”, 1-1/4”, 1-1/2”, 2” E = 1”, 1-1/4”, 1-1/2”, 2”, 2-1/2” F = 1-1/4”, 1-1/2”, 2”, 2-1/2”, 3” G = 0.31 diameter Ground Wire K.O. FIGURE 22 Pak Metering Wiring Diagrams 2 POSITION 125 AMP 4 POSITION 125 & 200 AMP 22 2 POSITION 200 AMP 5 POSITION 125 & 200 AMP 3 POSITION 125 & 200 AMP 6 POSITION 125 & 200 AMP 63331Murray.qxd 3/24/2005 11:24 AM Page 23 Pak Metering Knockout Diagrams MP2211X MP3311X 23 63331Murray.qxd 3/24/2005 11:24 AM Page 24 Pak Metering Knockout Diagrams MP4312X MP4212X MP4411X 24 63331Murray.qxd 3/24/2005 11:24 AM Page 25 Pak Metering Knockout Diagrams MP6512X 25 63331Murray.qxd 3/24/2005 11:24 AM Page 26 Pak Metering Knockout Diagrams MP6611X 26 63331Murray.qxd 3/24/2005 11:24 AM Page 27 Pak Metering Knockout Diagrams MP6612X 27 63331Murray.qxd 3/24/2005 11:24 AM Page 28 Rock SolidTM Load Centers Load centers on this page through 225 amp feature a new split neutral with one bonded and one insulated bar. For service entrance applications, install bonding strap, and use both bars for neutral and ground conductors. For non-service entrance applications, do not install bonding strap and use insulated bar for neutral conductors and bonded bar for ground conductors. MAIN BREAKER LOAD CENTERS – Aluminum Bus 20-42 Circuit, 100-400 Amperes, 1 Phase 3 Wire, 120/240V AC, 22,000 AIC Amps Max. 100 100 100 100 100 150 150 150 150 200 200 200 200 200 200 No. of Spaces 10 12 20 24 30 16 20 24 30 12 16 20 24 30 40 Max. Circuit 20 24 40 40 40 32 40 40 40 24 32 40 40 40 40 Indoor Enclosure NEMA Type 1 Catalog Number LC110DFCGP LC1224B1100 LC2040B1100 LC2440B1100 LC3040B1100 LC1632B1150 LC2040B1150 LC2440B1150 LC3040B1150 – LC1632B1200 LC2040B1200 LC2440B1200 LC3040B1200 LC4040B1200 Dimensions (inches) Height Width Depth 14-3/4 12-3/8 3-7/8 18 14-3/8 4 24 14-3/8 4 24 14-3/8 4 30 14-3/8 4 24 14-3/8 4 30 14-3/8 4 30 14-3/8 4 36 14-3/8 4 – – – 30 14-3/8 4 30 14-3/8 4 30 14-3/8 4 36 14-3/8 4 39 14-3/8 4 MAIN LUG LOAD CENTERS – Copper Bus 40-42 Circuit, 100-400 Amperes, 1 Phase 3 Wire, 120/240V AC, 22,000 AIC Amps Max. No. of Spaces Max. Circuit Indoor Enclosure NEMA Type 1 Catalog Number Dimensions (inches) Height Width Depth 100 200 200 200 200 400 20 20 30 40 30 42 40 40 40 40 40 42 LC2040L1100CU LC2040L1200CU LC3040L1200CU LC4040L1200CU LC330SS LC442SS 24 30 36 39 47 58 14-3/8 14-3/8 14-3/8 14-3/8 20 20 4 4 4 4 6 6 LOAD CENTER SHORT CIRCUIT CURRENT RATING Murray load centes have UL recognized short circuit current ratings up to 100,000 amps when used with appropriate main or feeder (remote or internal) overcurrent devices. Load center ratings are shown below. For load center applications with residential or commercial metering equipment, refer to the appropriate section of this catalog. Single phase main breaker load centers are UL Listed for use with 60/75oC conductors and accept Murray branch circuit breakers which are also UL Listed for use with 60/75oC conductors. Type 3R load centers are furnished with a hub opening closure plate. Load Center Short Circuit Current Rating 10,000 AIC 22,000 AIC 42,000 AIC 65,000 AIC 100,000 AIC 100,000 AIC 28 Load Center Main Rating Any 100/125A 150/200/225A 100/125A 150/200/225A 100/125A 150/200/225A 100/125A 150/200/225A Internal or Remote Main or Feeder Circuit Breaker Type Any MP-HT, MQH MD-H, MQH , MPP-HT MQL MQL MP-MT, MPP-MT MPP-MT 100A, 300V AC, Class “T” Fuse 200A, 300V AC, Class “T” Fuse Outdoor Enclosure NEMA Type 3R Catalog Number – LW1224B1100 – – – LW1632B1100 LW2040B1150 – – LW1224B1200 – LW2040B1200 – LW3040B1200 LW4040B1200 Dimensions (inches) Height Width Depth – – – 20 14-1/4 4-1/2 – – – – – – – – – 20 14-1/4 4-1/2 29 14-1/4 4-1/2 – – – – – – 29 14-1/4 4-1/2 – – – 29 14-1/4 4-1/2 – – – 38 14-1/4 4-1/2 38 14-1/4 4-1/2 300 and 400 amp load centers have insulated groundable center-mounted neutrals. Standard package quantity equal to one. Dimensions shown are representative of outside box length, width and depth (⫾ 1/8”) and do not include allowance for mounting bumps, endwalls, hubs, or hardware protrusions. Allow approximately 1-1/4” additional in length and width dimensions for surface or combination overhang. Hub provision only. Closure plate included. Panels through 225 amp require HS type hub; panels over 225 amp require HV type hub. Copper bus load centers are recommended for those applications where the enviroment may be severe (i.e., farm and coastal areas). For flush installation, order accessory Cat. No. LX077SF separately. Dual main breaker provisions. Has factory installed 200 amp MD-TR style main breaker with provisions for second MD-TR main breaker up to 200 amps to feed subpanel or other large loads. Two MP115 and one MP230 provided. covers MYSA-WCMSA-0305.qxd 3/24/2005 8:24 AM Page 2 Rock SolidTM Load Centers Combination Meter Sockets Overhead and Underground Feed Features and Benefits Mounting keyholes for easy installation Tin-plated copper bus bars and wire forms Most wire bending space (width) in industry Sturdy, thermoplastic lug mounting bases INSTA-WIRETM neutrals Adjustable flush rails for 2” x 6” installation (flush mount devices only) install bonding strap, and use both bars for neutral and ground conductors. For non-service entrance applications, do not install bonding strap and use insulated bar for neutral conductors and bonded bar for ground conductors. MAIN LUG LOAD CENTERS – Aluminum Bus 24-40 Circuit, 125-200 Amperes, 1 Phase 3 Wire, 120/240V AC or 208Y/120V AC, Insulated and Bonded Split Neutrals 햲 Amps Max. 125 125 125 125 150 150 200 200 200 200 200 No. of Spaces 12 16 20 30 16 24 12 20 30 40 40 Max. Circuit 24 32 40 40 32 40 24 40 40 40 40 Indoor Enclosure NEMA Type 1 햳 Catalog Number LC1224L1125 LC1632L1125 LC2040L1125 LC3040L1125 LC1632L1150 LC2440L1150 – LC2040L1200 LC2440L1200 LC3040L1200 LC4040L1200 Dimensions (inches) 햴 Height Width Depth 21 14-3/8 4 21 14-3/8 4 24 14-3/8 4 30 14-3/8 4 24 14-3/8 4 30 14-3/8 4 – – – 30 14-3/8 4 30 14-3/8 4 36 14-3/8 4 39 14-3/8 4 Outdoor Enclosure NEMA Type 3R 햳햵 Catalog Number LW1224L1125 LW1632L1125 LW2040L1125 – – – LW1224L1200 LW2040L1200 – LW3040L1200 – Dimensions (inches) 햴 Height Width Depth 20 14-1/4 4-1/2 29 14-1/4 4-1/2 29 14-1/4 4-1/2 – – – – – – – – – 29 14-1/4 4-1/2 29 14-1/4 4-1/2 – – – 38 14-1/4 4-1/2 – – – MAIN LUG LOAD CENTERS – Copper Bus 40-42 Circuit, 125-400 Amperes, 1 Phase 3 Wire, 120/240V AC or 208Y/120V AC, Insulated and Bonded Split Neutrals 햲 Rigid metal basepan Removable anti-rotation lugs move to top positions for overhead feed applications Easily removable side hinge door 7” deep can for more wire room JA1224B1100SEC Catalog Number Logic Example: JA1224B1100FEC JA Load centers on this page through 225 amp feature a new split neutral with one bonded and one insulated bar. For service entrance applications, 12 24 JA = Meter Spaces Combination JC = Meter Main Circuits B B = Main Breaker L = Main Lug 1 1 = Single Phase 100 Amperage FEC F = Semi-Flush S = Surface E = EUSERC C = OH/UG Feed (side-by-side) D = UG Feed Only (over under) M = Field Added 2nd Main W = Wide Load Center (not between the studs) SS = Test Block Bypass Socket Amps Max. No. of Spaces Max. Circuit Indoor Enclosure NEMA Type 1 햳 Catalog Number Dimensions (inches) 햴 Height Width Depth Outdoor Enclosure NEMA Type 3R 햳햵 Catalog Number Dimensions (inches) 햴 Height Width Depth 125 200 200 200 225 400 20 20 30 40 42 42 40 40 40 40 42 42 LC2040L1125CU LC2040L1200CU LC3040L1200CU LC4040L1200CU LC4242L1225CU LC042SS 햷 24 30 36 39 42 47 – – – – – LW042SR – – – – – 47 햲 300 and 400 amp load centers have insulated groundable center-mounted neutrals. 햳 Standard package quantity equal to one. 햴 Dimensions shown are representative of outside box length, width and depth (⫾ 1/8”) and do not include allowance for mounting 14-3/8 14-3/8 14-3/8 14-3/8 14-3/8 20 4 4 4 4 4 6 bumps, endwalls, hubs, or hardware protrusions. Allow approximately 1-1/4” additional in length and width dimensions for surface or combination overhang. 햵 Hub provision only. Closure plate included. Panels through 225 amp require HS type hub; panels over 225 amp require HV type hub. – – – – – 20-1/2 – – – – – 6-1/2 햶 Copper bus load centers are recommended for those applications where the enviroment may be severe (i.e., farm and coastal areas). 햷 For flush installation, order accessory Cat. No. LX077SF separately. covers MYSA-WCMSA-0305.qxd 3/24/2005 8:24 AM Page 1 West Coast Metering Circuit Breaker Enclosures and Small Load Centers Selection and Application Guide 2 – 8 CIRCUIT, 60 – 125 AMPERES (NO DOOR) Amps Max. 60 125 125 125 125 125 No. of Spaces 2 2 4 4 4 4 Max. Circuit 4 4 8 8 8 8 Indoor Enclosure NEMA Type 1 햲 Catalog Number LC002GS LC002HS 햵 LC004NF 햵햶 LC004NS 햵햶 – – Dimensions (inches) 햳 Height Width Depth 9-7/8 5-1/8 2-5/8 17-1/8 7-1/8 4-1/4 12-5/8 6-5/8 3-1/2 12-5/8 6-5/8 3-1/2 – – – – – – Outdoor Enclosure NEMA Type 3R 햴 Catalog Number LW002GR 햷 LW002HR – LW004NR 햵햶햸 LW004NRSPA50 햵햶햷햸햹 LW004NRSPA60 햵햶햷햸햹 Dimensions (inches) 햳 Height Width Depth 8-1/4 5-3/8 4-1/2 8-1/4 5-3/8 4-1/2 – – – 12-1/4 6-1/8 4-1/4 12-1/4 6-1/8 4-1/4 12-1/4 6-1/8 4-1/4 LC008DF 햵 LC008DS 햵 LC008DFG 햵햹 LC008DSG 햵햹 LC110DFCGP 햵햹햺 14-3/4 14-3/4 14-3/4 14-3/4 14-3/4 3-7/8 3-7/8 3-7/8 3-7/8 3-7/8 – LW008NR 햵 – – – – 14-3/4 – – – – 12-1/8 – – – – 4-1/8 – – – LC100CS LC200VS 17-1/8 7-1/8 19-3/4 8-1/2 4-1/4 4 LW100CR LW200VR 17-3/8 19-3/4 7-3/8 8-3/8 4-3/8 4-5/8 – – 19-3/4 8-1/2 – 4 LW002GR LW004VR 8-1/4 19-3/4 5-3/8 8-3/8 4-1/2 4-5/8 8 – 16 CIRCUIT, 125 AMPERES (WITH DOOR) 125 125 125 125 125 8 8 8 8 10 16 16 16 16 20 12-3/8 12-3/8 12-3/8 12-3/8 12-3/8 ENCLOSED BREAKERS 100 100 2 2 4 4 MAIN LUG CIRCUIT BREAKER ENCLOSURES 60 200 – 2 – 4 – LC004VS 햲 Cover type is specified by character in 7th (usually last) position, as follows: S = Surface F = Flush C = Combination Surface/Flush 햳 Dimensions shown are representative of outside box length, width and depth (⫾ 1/8”) and do not include allowance for mounting bumps, endwalls, hubs, or hardware protrusions. Allow approximately 1-1/4” additional in length and width dimensions for surface or combination overhang. 햴 Hub provision only. Closure plate included. Panels through 225 amp require HS type hub; panels over 225 amp require HV type hub. 햵 Use neutral lug kit ECLK1 or ECLK2 as required. 햶 Maximum breaker 100 amp. 햷 LW004NRSPA50 is provided with a factory installed 2-pole 50 amp GFCI breaker. LW004NRSPA60 is provided with a factory installed 2-pole 60 amp GFCI breaker. 햸 Use of 60 amp GFCI requires use of 75oC copper wire. 햹 Panel includes factory-installed ground bar. 햺 Includes (2) MP115 and (1) MP230 breakers. Murray Electrical Products Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 seainfo@sea.siemens.com www.murrayconnect.com 2005 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Murray is a trademark of Siemens Energy & Automation, Inc. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. SEA Order No. MYSA-WCMSA-0305 New 5M0305BC Printed in USA