Counter/Frequency with detection of rotation direction Application Note English Description Application Measuring input Input cable Note Event counter as upwards/ downwards counter Frequency measurement with detection of rotation direction M-CNT2 600-858 SIM-CNT-IN Cable open (Lemo 1B 7-pin) 670-858 SIM-CNT-IN Cable open (Lemo 1B 7-pin) Sensor output signals S1/S2 are proportional to Rpm or speed with a phase shift of 90° between S1 and S2. To detect the rotating direction, a second input of M-CNT2 is required; means: S1 > Input1, S2 > Input2, respective S1 > Input3, S2 > Input4 Basic principle Wiring diagram Subject to change IPETRONIK GmbH & Co. KG ipetronik.com 2014.07 Counter/Frequency with detection of rotation direction Application Note Software settings Format CAN data format Data type 16 Bit or 8 Bit signed/unsigned Setting, e.g.: 16 Bit signed NoValue Set invalid value resp. range boundary, which is indicated as error (-FullScale, 0, +FullScale) Setting, e.g.: -FullScale Scaling Input signal scaling Mode Frequency, Frequency with direction, Duty cycle, Period duration, Pulse duration, Pause duration Event counter, Event counter with direction Setting, e.g.: Frequency with direction Sensor range Up to 200 kHz (200 s) user selectable range Setting, e.g.: Min: -100 Hz, Max: 100 Hz Physical range Scaled value Setting, e.g.: Min: -6000 rpm, Max: 6000 rpm Display Display settings (IPEmotion View area) Displaying area Physical range used in diagrams (Yt, bargraph) of visual elements Formatting Number of decimal places used for the physical range Setting, e.g.: 1 decimal place > 4500.0 rpm (Display setting! This does not affect the system accuracy!) Name Name used for the visual element. Subject to change IPETRONIK GmbH & Co. KG ipetronik.com 2014.07 Counter/Frequency with detection of rotation direction Application Note Input signal Settings for signal evaluation Signal parameters Threshold on Threshold off Edge DC compensation Start trigger to calculate frequency/period duration/events Stop trigger to calculate frequency/period duration/events Signal evaluation between rising or falling edges enables the compensation of the DC share of the input signal Zero detection threshold Gate time Minimal value Maximum time (timeout) allowed to be used for evaluation (threshold on, threshold off). Without any signal detection during this time period, the minimal value, resp. 0 is output by the system. Physical value that is indicated in case of gate time exceeding (evaluation not possible). Excitation Sensor supply voltage Sensor excitation Sensor supply voltage Setting, e.g.: 12.5 V Filter Low-pass filter at the signal input Hardware filter Up to 30 kHz user selectable antialiasing filter of the channel Averaging Block mean value calculated based on acquired data within the sample period at an internal sample rate of 5 kHz. Example: Module sampling rate (= output rate to CAN bus) = 100 Hz Averaging calculated based on 5000 Hz / 100 Hz = 50 values Subject to change IPETRONIK GmbH & Co. KG ipetronik.com 2014.07