Intelligent Transmitter Models iT100, iT200, iT100M and iT200M Operating guide WARNING: TO PREVENT FIRE OR SHOCK HAZARD, DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR CONDENSING MOISTURE. Safety section The iT Series Intelligent Transmitter modules can be safely operated when the instructions in this manual are carefully followed. This section summarizes the safety considerations. Reminders, in the form described below, will appear in the detailed instructions to assure operator awareness of these safety considerations. Qualified personnel should operate and maintain this equipment only after becoming thoroughly familiar with this manual. WARNING:This symbol is used in the instruction manual where operator safety must be considered. The instruction manual should be consulted and read carefully. CAUTION: This symbol is used when caution is needed to prevent damage to equipment. It is used where careful attention to certain procedures described in the instruction manual is needed. This symbol is also used to emphasize procedures other than normal operating procedures. Safety summary 1. Ensure that any power connection neutral (green) wires are properly grounded to a good earth ground. 2. Disconnect the AC mains power for the DC power supply used to power the transmitter module at its source before connecting or removing any cables. 3. All cabling and wiring installation and connection should be completed prior to energizing the modules. Inspect for frayed or cut cables prior to operation. 4. Do not expose this equipment to rain or moisture. 5. Use common sense and avoid haste! 97015 rev D.1 8/08 Page 2 Contents Safety section ...................................................................................................... 2 Safety summary ................................................................................................... 2 1.0 Theory of operation ....................................................................................... 4 1.1 Root mean square (rms) ............................................................................. 4 1.2 Peak (actually “equivalent” peak)................................................................. 5 1.3 True peak..................................................................................................... 5 1.4 True peak-to-peak........................................................................................ 5 1.5 Response and decay times for true peak and peak-to-peak detection ........ 6 1.6 Application of each detection type ............................................................... 6 2.0 Product description ....................................................................................... 7 2.1 Front panel................................................................................................... 7 2.2 Side panels .................................................................................................. 8 3.0 Installation...................................................................................................... 9 3.1 Mounting and removal ................................................................................. 9 3.2 Wiring........................................................................................................... 9 4.0 Operation...................................................................................................... 10 4.1 Changing the sensor powering .................................................................. 11 4.2 Changing the filter set-points ..................................................................... 11 4.3 Changing the source of the input sensor signal ......................................... 12 4.4 Changing the buffered dynamic output coupling ........................................ 12 5.0 Maintenance.................................................................................................. 12 6.0 Technical assistance ................................................................................... 13 7.1 Technical assistance.................................................................................. 13 7.2 Customer service ....................................................................................... 13 Appendix A, iT Series model numbers ............................................................... 14 Appendix B, Circuit board component location drawing ..................................... 15 97015 rev D.1 8/08 Page 3 1.0 Theory of operation The iT Series of vibration transmitter modules operate from a 24 Volt DC (nominal) power supply. They accept input signal directly from integrated electronics piezoelectric (IEPE) sensors such as accelerometers and piezovelocity transducers (PVT™). The module then processes the signal and produces an output 4-20 mA loop current proportional to the overall vibration in terms of rootmean-squared (rms) vibration level or peak (pseudo-peak) vibration levels. The input dynamic vibration signal is also buffered within the module and presented as an output at the front panel BNC and on a set of terminals. The 4-20 mA loop output signal is usually wired to a Programmable Logic Controller (PLC) or a Distributed Control System (DCS). The module has two inputs and two outputs. The two inputs are power and the dynamic vibration signal. The two outputs are the buffered dynamic vibration and the 4-20 process loop signal. Acceleration, velocity, and displacement are vibration measurements that are all related by wellknown equations. Acceleration can be integrated to produce velocity. Velocity can be integrated to produce displacement. Any one of these signals can be converted to any other. The iT Series transmitter modules can integrate the input signal once to produce another vibrational quantity. IEPE accelerometer signals can be processed to produce an acceleration 4-20 mA loop signal or can be integrated to produce a velocity 4-20 mA loop signal depending upon the particular model ordered. A vibration transducer that can interface with the plant DCS or PLC offers the possibility to trend the vibration of machinery. Simple knowledge of the trend of vibration can provide valuable clues to changes in the mechanical health of equipment. The iT Series of vibration transmitter modules allow operating personnel the ability to see the equipment vibration levels on a continuing basis. Vibration analysts can use the overall trend information to learn when vibration levels changed and whether it may be related to other equipment changes. 1.1 Root-mean-square (rms) Root-mean-square detection is a very accurate method of determining the total “power” contained in a signal. It is used in vibration detection where it is desired to know the total amount of true vibrational energy exhibited by a machine. Extracting the true rms value of a signal has always been difficult to perform as complicated analog circuitry must be employed. However, the Wilcoxon iT Series of transmitters use modern digital signal processing to extract the true rms value of vibration. Since the iT Series of transmitters can process signals as low as 0.3 Hz in acceleration, the module averages the rms signal over a period of time to produce an accurate rendition of the true rms vibration level. The averager has the effect delaying the true rms level until an adequate number of averages have been processed. This effect is observed as an exponentially rising level when a “step” input of vibration is captured. In the illustration of a captured step sine input, the effective time-constant of the averager can be observed as about 1 second, (ref fig 1.1.1) When a signal is removed from the iT Series transmitter, a similar effect is observed due to the effect of averaging. However, the decay of the output 97015 rev D.1 8/08 Page 4 Figure 1.1.1 - Response of rms averager to step signal input and cut-off signal is much slower than the rise of the output when the signal was applied. This illustrates how the averager responds faster when the signal is applied, but slower when it is removed. These two averager time-constants are different. The averager has a time-constant of about 1 second for signal onset, but is about 3 seconds when the signal is removed. The onset time is referred to as the “attack” time of the averager. While the dropping of the signal output after the input has been removed is referred to as the “decay” time of the averager. The Wilcoxon iT-series transmitters can thus be seen as having a “fast attack” and a “slow decay.” If a very short impulse for transient, like a “spike” of vibration, is applied an iTseries transmitter with rms detection, there will be no detectable change in the output because the total energy in the spike will be miniscule, (ref fig 1.1.2) The property of the rms averaging that is performed is beneficial for transmitter users. This allows for the transmitter to respond rapidly to any meaningful increases in vibration while retaining the vibration data longer when the levels decrease to allow for the DCS/PLC system to capture the vibration level. 1.2 Peak (actually “equivalent” peak) Figure 1.1.2 - Response of rms averager to a transient Peak detection has been used for vibration monitoring where it is desired to know the peak value of the vibration. Many vibration transmitters on the market use an rms method of detection and then covert that value to “peak” by multiplying the rms by the square-root of two (~1.414). The ratio of the peak amplitude of a sinusoidal wave to the rms of a sinusoidal wave is the square-root of two. This method of extracting a vibration value the relationship between peak and rms is only true where the signal is a sinusoidal waveform. In many instances, vibrational energy is primarily due to a single high-level vibration, so this method works well. Figure 1.2 - Relationship of rms to Many vibration transmitters develop a peak value for vibration by using this method. peak of a sine waveform The Wilcoxon iT Series transmitters have this method available for detection to provide comparable results to other vibration transmitter modules in use. It is also useful where users simply wish to have the signal output be in terms of peak vibration, rather than rms. 1.3 True peak In the true peak detection of the Wilcoxon iT Series transmitters, the power of digital signal processing is used to capture and extract the true peak value of the signal. Even very short transient signals will not escape detection. The transmitter will capture and adjust the 4-20 mA loop output current very quickly to reflect any short-duration transient increases in the vibration. 1.4 True peak-to-peak Just as in the true peak method of detection, the true peak-to-peak method relies on the powerful digital signal processing of the iT Series transmitters to capture, in near-instantaneous time, the true peak-to-peak value of the vibration signal. 97015 rev D.1 8/08 Page 5 1.5 Response and decay times for true peak and peak-to-peak detection With the true peak and the true peak-to-peak detection, the response of the transmitter module is near-instantaneous. Data is shown here to illustrate the rapid response of the transmitter to transient events that would otherwise be missed by most vibration transmitters. On the left of the illustration, (fig 1.5) is captured the response of the module output when the input is presented with a very short-duration pulse (spike). Here the pulse is less than a millisecond in duration, yet the module captures the level and, within 10 milliseconds, has computed the peak value and adjusted the loop output current to that peak level. This response can be contrasted easily to the response of rms detection presented in the explanation of the rms detection method. Rootmean-square detection will not respond to the spike while the true peak detection will respond almost instantaneously to the spike. The right side of the illustration shows the Figure 1.5 - Data showing the fast response of the true peak and true peak-to-peak module’s response after detection in all iT transmitter modules. Also shown is the decay response after the detection of the true peak signal. This allows DCS/PLC systems to capture accurate the capture of the true date even when their sampling is at one sample per second. peak level. When the signal is removed, the output loop current remains at the captured peak level for one second. This allows for the typical DCS/PLC system scanning at one sample per second to be able to accurately record the peak of the signal. If no additional peaks appear at that level, or higher, the output begins to ramp down at a rate of 25% of full-scale per second. If no further signals appear, the output will return to 4 mA four (4) seconds after the beginning of the ramp-down. 1.6 Application of each detection type The rms and peak detection output types are typically used for long-term overall vibration level trending and machinery protection applications. Their insensitivity to brief spikes of vibration is beneficial as the Wilcoxon transmitters will act to smooth the signal response. The “fast attack” of the averager serves to respond relatively quickly to sudden increases of the overall vibration level, but not so quickly as to cause monitoring system trends to appear noisy or erratic. The choice of rms versus peak detection is usually a matter of user preference. Since both work from the same basic detection method, the choice is more about the local plant personnel’s preference for one or the other. Additionally, historical vibration data may be in terms of either rms or peak vibration and, therefore, the setting of vibration limits will be more in line with the plant’s historical data. 97015 rev D.1 8/08 Page 6 The “true” peak or peak-to-peak detection will be of more use where it is desired to be able to capture transient vibration events. It can also be useful when used in concert with another transmitter module that is trending the rms levels of vibration. If a true peak vibration trend is showing a more erratic response, but the rms trend remains relatively constant, there may be problems developing where loose parts are causing transient impact events. 2.0 Product description The iT Series of vibration transmitter modules perform acquisition and processing of dynamic vibration signals. The input signal is derived from an IEPE piezoelectric accelerometer or PVT™ piezovelocity transducer. The module has two types of output signals. First, the dynamic vibration signal is buffered and presented at the front panel BNC connector as well as a set of terminals on the module. Second, the 4-20 mA loop output is a processed signal that represents either the overall rms level of vibration or the peak vibration level as described in section 1. Figure 2.0 front view The module can have high-pass and low-pass filters inserted before the rms processing occurs. These filters can be specified when the module is ordered or set in the field by placing the module filter selection into the "manual" mode. In "manual set" mode the filters are variable; the high-pass: 2 Hz to 1 kHz, the low-pass: 200 Hz to 20 kHz, (ref fig 2.0). 2.1 Front panel Dynamic signal output BNC The buffered dynamic signal is available at the BNC connector. The signal sensitivity is the same as for the sensor connected to the input and is in phase with the input signal, (ref fig 2.1.1). Green "ready" LED "On" indicates power applied "Off" indicates no power applied "Flashing" indicates sensor BOV out of range Red "status" LED "Flashing" indicates a normal operating condition "On" indicates an error condition caused by high vibration signal clipping or internal circuit failure The connection terminals are located above and below the front panel. These are 3-wire plug-in terminals. The front panel has identification for each terminal connection. The connection designation and function of each of the connection points is as follows, (ref fig 2.1.2): 97015 rev D.1 8/08 Page 7 Figure 2.1.1 Front panel Figure 2.1.2 3-wire plug for input connection Plug 1 Plug 2 Designation Description +24V Positive power input for iT module COM Common for power input GND Earth ground connection (to ground iT module) XDU+ Sensor power/signal input XDU- Sensor common input SHD Plug 3 Sensor shield wiring termination DYN OUT Dynamic signal out COM Common of dynamic signal out SHD Plug 4 see note see note 4-20 COM SHD Shield point termination for dynamic out 4-20 mA Loop return signal Common reference for 4-20 mA return see note Shield point termination for loop wiring Note: Each of the terminals designated "SHD" for shielding termination connects directly to the module ground "GND" connection. CAUTION:Use care when terminating shields at the iT Series module. Undesired ground loops may result if improper shield and ground connections are created. All wiring shields should only be connected to ground at one end. Connecting wiring shields to ground at both ends of a cable will create a ground loop condition. 2.2 Side panels Figure 2.2 Left side label Right side label The sides of the iT Series modules have no electrical or mechanical connections. The label on the right side is a guide to the connection wiring. The left side label contains information about the model number and identification data, (ref fig 2.2): 97015 rev D.1 8/08 Page 8 Model1 Serial # Tracking # -3dB low frequency1 -3dB high frequency1 Input Type1 the Input Sensitivity1 4-20 mA Output Type1 4-20 mA Full Scale Range1 Operator Base model numbers as identified on the iT Series data sheet. Defines the input type, output type, and processing detection type A Wilcoxon assigned unique identification number A Wilcoxon internal processing number This is the pre-set frequency specified when the module is ordered (High-Pass) This is the pre-set frequency specified when the module is ordered (Low-Pass) Accelerometer or PiezoVelocity transducer (PVT™) specified in original order MilliVolts/engineering unit (EU), where EU is in g's or inches per second (ips), specified when the module is ordered Acceleration, velocity, or displacement A designator of the full scale 4-20 mA output, in engineering units A Wilcoxon-assigned tracking number 3.0 Installation 3.1 Mounting and removal The iT Series of modules mount to a standard 35 mm DIN rail. The rear of the module has a clip that is spring-loaded. This clip holds the module securely in place. The clip releases by using a flat-bladed screwdriver inserted into the bottom slit of the clip to pull and release the clip attachment to the lower DIN rail. The module can be installed by placing the upper "hook" of the mount onto the DIN rail and gently "rocking" it into place until the latch "catches" on the lower rail. Removal requires a small, flat-bladed screwdriver. The blade must be less than ¼ inch (6mm) in width to fit into the slot on the latch. Insert the blade into the slot and gently "pry" the latch down until it releases from the DIN rail, then lift the module releasing it from the DIN rail, (ref fig 3.1). Figure 3.1 - Illustration of attachment clips and installation and removal method Note:The user should disconnect the plugs from the module before removing the module from the DIN rail. All plug wiring should be well marked to assure proper connections when the module is re-installed. Each module is 17.5 mm wide and therefore uses 17.5 mm of DIN rail length. 3.2 Wiring The iT Series modules are designed to directly accept and power IEPE type sensors. Most industrial accelerometers and PVT™'s are IEPE type of devices. The label on the right side of the module illustrates the wiring of the iT Series modules. 1 See Appendix A of this manual for the model number designators used in ordering 97015 rev D.1 8/08 Page 9 A 24-Volt DC, nominal, supply voltage should be used to power the iT Series modules. The power supply positive (+) output connects to the “+24V” terminal. The power supply common (-) output connects to the “COM” terminal next to the “+24V” connection on the same plug. A good earth ground should connect to the “GND” terminal of the power plug. This insures the proper safety operation of the transmitter module. Note: All shield (SHD) terminations are internally connected to the ground (GND) terminal. The input sensor should be wired using one of these Wilcoxon connector types: R6, R6W, R6QI, R6QAI, or R6SLI. These are all two-pin MIL-C5015 style connectors used with the typical industrial accelerometer or PVT™. These connector types all have the shield isolated from the sensor shell at the sensor's end of the cable as illustrated here. Wiring the sensor in this manner will insure that no ground loops are created due to sensor wiring. The sensor “A” pin is normally the power/signal connection and should be wired to the “XDU+” labeled input terminal. The “B” pin is normally the sensor common connection and should be wired to the “XDU−” labeled input terminal. The “SHD” terminal of the sensor connector is for connecting the shield of the sensor wire. Do not make this connection if the sensor end of the cable has the shield grounded. Note: Verify all sensor connections with the sensor manufacturer by reference to the data sheet for any sensor used with the iT Series module. The output 4-20 mA loop wiring should use shielded, twisted pair wire. The shield for that wiring should not have the shield connected at the module end of the wire. The illustration above depicts the wiring. This is the recommended practice because most PLC or DCS system inputs have shields tied to ground at the PLC/DCS input wiring. Note: Use care when terminating shields at the iT Series module. Figure 3.2 - Illustration of the wiring connections and example wiring for an IEPE sensor and 4-20 mA loop Undesired ground loops may be created if improper shield and ground connections are created. All wiring shields should only be connected to ground at one end of the cable. Connecting wiring shields to ground at both ends of a cable will create a ground loop condition. 4.0 Operation When power is applied to the iT Series module it may require up to 120 seconds to warm up and stabilize. Once the transmitter module has achieved stable and proper operation, the green front panel LED will illuminate to indicate the transmitter is ready. If the green LED extinguishes, it indicates the module has lost power. If the green LED is “flashing” it indicates that the bias output voltage (BOV) of the attached IEPE accelerometer or PVT™ is either below 5 Volts DC or above 18 Volts DC. 4-20 mA output, may be below 4 mA or above 20 mA if the iT module senses bad sensor BOV, to activate an alarm condition. The red front panel LED will “strobe” every two (2) seconds during normal operation. If the red LED is on for an extended time (not the brief “strobe” flash), it indicates a module fault condition or sensor overload condition. A sensor overload means the sensor may be operating with 97015 rev D.1 8/08 Page 10 excessive vibration causing its internal amplifier to clip the signal yielding false vibration readings. The clip indication will keep the LED illuminated for 4 seconds after the clipping occurs. The 4-20 mA loop output current will be established 120 seconds after power has been applied to the module. There are jumpers located on the internal circuit board to allow the user to make changes to the configuration of the Intelligent Transmitter module. Opening the Intelligent Transmitter module case can access these jumpers. Each jumper location has three pins on the circuit board. The jumper is used to connect between two of the pins. The diagram illustrates how the jumper can be removed from one position and relocated to change the setting. Appendix B has a diagram showing the circuit board layout and labeling. Each jumper location is identified and the board has the designation on it for the jumper definition. Figure 4.0 - Move jumper to change setting HALF 4.1 Changing the sensor powering 3.6 mA HALF Note: Appendix B has a diagram of the component locations on the iT module circuit board discussed in this section. The sensor power is set to supply 3.6 mA to the IEPE-style sensor input using a constant-current diode (CCD). An internal jumper plug can be changed that would eliminate the CCD powering and allow for the input signal to be applied directly to the module input. Near the front of the module board is a jumper with two positions. They are marked as “3.6mA” and “HALF.” In the “3.6mA” position, the CCD is in the circuit to provide the constant-current diode powering to any IEPE-style sensor connected to the input. In the “HALF” position, the input is weakly biased by two resistors to half the power supply voltage. The “HALF” position allows AC-coupled input signals and low-impedance DC-coupled input signals. 3.6 mA 3.6 mA HALF Figure 4.1 - Jumper positions for 3.6 mA powering or “Half” voltage bias DEFAULT MAN DEFAULT MAN 4.2 Changing the filter set-points The iT Series modules are ordered with pre-programmed filter set points. Note: Appendix B has a diagram of the component locations on the iT module circuit board discussed in this section. MAN DEFAULT Figure 4.2.1 - Jumper positions for setting filters manually Users can change the filter corner frequency for both the high-pass and low-pass filter by using internal adjustable resistors. There is an internal jumper that is set to the “DEFAULT” position when the module is shipped. Moving the jumper to the “MAN” position places the iT Series module in the manual adjust mode. The resistors are marked as “HPF” for the high-pass filter and “LPF” for the low-pass filter. The resistors can be adjusted to change the filter frequencies between 2 Hz and 1000 Hz for the high-pass filter, and 200 Hz to 20,000 Hz for the low-pass filter. Figure 4.2.2 - Guide to approximate potentiometer frequency setpoints 97015 rev D.1 8/08 Page 11 An approximation of the frequency potentiometer positions for various selections is presented here in figure 4.2.2. If precise frequency control is necessary for the manually adjusted potentiometers, users will need to have an iT500 Series or iT700 Series communication module attached to the iT Series vibration transmitter module to view the exact frequency settings. Once connected to the iT501, the configuration tab can be selected in the VibeLink® software of the iT501 to view the frequency setting of the potentiometer. More details regarding this can be found in the operating guide of the iT501. The iT501 operating guide is also available on-line at www.wilcoxon.com. 4.3 Changing the source of the input sensor signal The iT Series modules have a set of jumpers labeled J11, J12, and J14. These jumpers must all be set to the same relative position. The modules are shipped from Wilcoxon with the jumpers set to the “SENSOR” position. In the “SENSOR” position, the input terminal connector at the front of the module (SHD, XDU-, XDU+) is the source for the sensor input signal connection. Note: Appendix B has a diagram of the component locations on the iT module circuit board discussed in this section. Users may change the source for the analog sensor input signal to be the T-Bus connector sensor connection by changing all three jumpers to the “TBUS” position. The T-Bus connector is located at the rear of the module and allows the interconnection of the transmitter module with other modules in the iT Series family. The T-Bus connection is useful when users desire to connect one sensor to multiple transmitter modules. This type of operation would allow the single sensor to be processed through more than one set of filters or to allow for both an acceleration 420 mA signal and a velocity 4-20 mA signal from the one sensor. SENSOR TBUS SENSOR TBUS TBUS SENSOR Figure 4.3 - Jumper positions for changing sensor signal source 4.4 Changing the Buffered Dynamic Output Coupling The iT Series modules have the input sensor signal buffered through an amplifier and presented at three output positions. The dynamic output is available at the front-panel BNC, the module lower terminal connector (DYN OUT, COM, SHD), and the T-Bus connector. The modules are shipped from Wilcoxon with the jumper set to the “AC” position. In the “AC” position, the buffered dynamic output signal is AC coupled to the output through a capacitor. The AC-coupled output signal has no DC voltage bias. Note: Appendix B has a diagram of the component locations on the iT module circuit board discussed in this section. AC DYN DC AC DC DYN DC AC Figure 4.4 - Jumper selections for output signal coupling When the jumper is moved to the “DC” position, the dynamic output signal will be an AC signal “riding” on a DC voltage level of ½ the power supply voltage. With a nominal supply voltage of 24 VDC the output bias would be 12 Volts DC. 97015 rev D.1 8/08 Page 12 5.0 Maintenance The only maintenance that can be performed on the iT Series module is the replacement of the 0.5 Ampere, fast-blow, 8AG-style fuse. It is mounted in a snap-out fuse holder on the circuit board. Additional fuses can be ordered from Wilcoxon as part number A69356, or from distributors such as DigiKey as part number F602-ND. 6.0 Technical assistance 6.1 Technical assistance For technical assistance, please contact Wilcoxon’s Product Manager at 301-330-8811, fax to 301-330-8873, or email to techasst@wilcoxon.com. 6.2 Customer service To obtain a return materials authorization (RMA) number, please contact customer service at 301330-8811, or fax to 301-330-8873. 97015 rev D.1 8/08 Page 13 Appendix A iT-series model numbers, for reference only. See Wilcoxon specification documents 98881 and 98923 for up-to-date model information. IT-F-S-L.-H ITM-F-S-L.-H IT Model designator Notes: 1 2 st 1 digit Input Signal Type 1 = Acceleration 2 = PiezoVelocity™ 2nd Digit 3rd digit Output Signal Type 1 1 = Acceleration 2 = Velocity 2 3 = Displacement Optional letter Detection Type 1 = Peak (equivalent) 2 = True R.M.S. 3 = True Peak 4 = True Peak-to-Peak Calibration Units “blank” = English M = Metric Acceleration output only valid with acceleration input Displacement output only valid with velocity input F digits Full-scale output 02 05 10 15 20 25 30 40 50 75 99 Acceleration English version Velocity Displacement 5g 10 g 0.5 in/sec 1.0 in/sec 20 g 2.0 in/sec Acceleration Metric version Velocity Displacement 0.2 mm 0.5 mm 1.0 mm 2 10 mils 20 mils 25 mils 50 m/sec 2 100 m/sec 200 m/sec 2 2.0 mm 25 mm/sec 30 g 3.0 in/sec 300 m/sec 2 50 g 5.0 in/sec 500 m/sec 2 S digits Sensitivity of Input Sensor 010 100 102 500 510 0000.3 0001.0 0002.0 0005.0 0010.0 0020.0 0030.0 0050.0 0080.0 0100.0 0200.0 0500.0 English version Metric version 100 mils English version Acceleration PiezoVelocity™ 50 mm/sec 3.0 mm 4.0 mm 5.0 mm 100 mm/sec Metric version Acceleration PiezoVelocity™ 2 10 mV/g 100 mV/g 10 mV/in/sec 100 mV/in/sec 1.02 mV/m/sec 2 10.2 mV/m/sec 500 mV/g 500 mV/in/sec 51.0 mV/m/sec 2 0.39 mV/mm/sec 3.9 mV/mm/sec 4.0 mV/mm/sec 19.7 mV/mm/sec 20.0 mV/mm/sec L. H, Low frequency and high frequency filter selections L - Low frequency (high-pass) filter H - High frequency (low-pass) filter 0.3 Hz, Acceleration output only 200 Hz 00200 300 Hz 1.0 Hz, Lowest Vel. Or Displ., ≥S500 sensitivity 00300 500 Hz 2.0 Hz, Lowest Vel. Or Displ., ≥S100 sensitivity 00500 5 Hz 800 Hz 00800 10 Hz 1,000 Hz 01000 20 Hz 2,000 Hz, maximum filter for displacement output 02000 30 Hz 3,000 Hz 03000 50 Hz 5,000 Hz, maximum filter for velocity output 05000 80 Hz 10000 10,000 Hz, maximum filter for True Peak or Pk-to-Pk 100 Hz 20000 20,000 Hz, No filtering, acceleration output only 200 Hz 500 Hz 97015 rev D.1 8/08 Page 14 0800.0 1000.0 800 Hz 1000 Hz Appendix B Internal jumper positions Use proper procedures when making any modifications that require opening the iT-series case. Avoid static-producing activities such as walking or personal radio use. Discharge any personal static charge build-up by touching a good earth ground prior to handling exposed circuit boards. The circuit board of the module can be released for removal by gently depressing the two small tabs that are located at the upper and lower side of the module case as shown in Figure B1. Use care when re-inserting the board into the case after any board changes that the TBUS tabs at the rear of the circuit board align with the rear case “cut-out” that allows connections to the circuit board. Insure that the two tabs engage and "lock" the board into place before returning the module to service. Circuit board component locations for jumpers, frequency adjustment resistors, and fuse are identified in Figure B2. Figure B2 - Location and Identification of circuit board jumpers, filter potentiometers, and fuse 97015 rev D.1 8/08 Page 15 Figure B1 - Releasing tabs to open the case