TECHNICAL BULLETIN TB-808 July 2015 (Expires 7/2017) Bottom Flange Trus Joist® TJI® Joist Attachment Connections This technical bulletin provides designers and engineers with guidelines for specifying withdrawal connections into the bottom flange of residential Trus Joist® TJI® joists with wood screws or lag screws. Examples of items commonly attached to the bottom flange include furnaces, ductwork, bike racks, garage door motors/tracks, lights, etc. The information in this bulletin is not appropriate for sprinkler attachments, which must comply with NFPA 13. For sprinkler details, refer to Weyerhaeuser’s Fire-Rated Assemblies and Sprinkler Systems, reorder 1500. Design considerations for bottom flange attachments include: • Maximum allowable bottom flange load is 500 lbs every 5 feet (250 lbs on each side of flange). • • Minimum edge and end distances shall follow 2012 NDS® guidelines. Lead holes are required as follows: o Lag screws ¼" to ½" diameter = 50% of diameter. o Wood screws larger than #8 = 70% of root diameter. • Withdrawal values shall be determined using a specific gravity, G, of 0.50 and taken as: o Lag Screws: 2012 NDS® Table 11.2A or W = 1800G (3 2 ) D (3 4 ) (lbs/in of thread penetration) Wood Screws: 2012 NDS® Table 11.2B or W = 2850G 2 D (lbs/in of thread penetration) Spacing of fasteners shall be taken as: o Lag Screws: 2012 NDS® Table 11.5.1E o Wood Screws: 2012 NDS® Table C11.1.5.7 or sufficient to prevent splitting of the flange. o • • • Penetration into the web is permitted. Loads applied or attached to the bottom flange must be accounted for in the design of the joist. Table 1: Residential TJI® Flange Sizes Joist Series TJI® 110 TJI® 210 TJI® 230 TJI® 360 TJI® 560 Minimum Flange Thickness (in) 1.25 1.25 1.25 1.375 1.375 Flange Width (in) 1.75 2.08 2.30 2.30 3.50 Note: For sprinkler attachment details, refer to 1500 (Fire-Rated Assemblies and Sprinkler Systems) Table 2: Common Screw Withdrawal Capacities Fastener Lead Hole W(1) (in/lbs) 7 gauge Wood Screw 8 gauge Wood Screw 9 gauge Wood Screw 10 gauge Wood Screw 12 gauge Wood Screw 14 gauge Wood Screw ¼" Lag Screw3 5/16" Lag Screw3 ⅜" Lag Screw3 7/16" Lag Screw3,4 ½" Lag Screw3,4 3/32" 3/32" 7/64" 7/64" 1/8" 9/64" 1/8" 5/32" 3/16" 7/32" 1/4" 107 117 126 135 154 172 225 266 305 342 378 1. 2. TJI® 110 134 146 158 169 193 215 281 - WMax(2) (lbs) TJI® 210, 230 134 146 158 169 193 215 281 333 381 428 473 TJI® 360, 560 147 161 173 186 212 237 309 366 419 470 500(5) Withdrawal capacity from 2012 NDS® Tables 11.2A and 11.2B based on the fastener diameter and a specific gravity of 0.50. Capacity shown is in pounds per inch of thread penetration into the main member, excluding the tapered tip of the fastener. Maximum withdrawal capacity is based on the threaded portion of the fastener engaging the full thickness of the flange, which may not occur with many fastener lengths and connection configurations. * 1.888.453.8358 ● www.woodbywy.com Page 1 of 2 TECHNICAL BULLETIN TB-808 3. 4. 5. July 2015 (Expires 7/2017) Clearance holes may not penetrate into the flange. Requires a 10% reduction to design moment values. Withdrawal capacity capped by the limit of 500 lbs for flange tear off. Design Example: Given: • TJI® 230 joist series. • ¼" x 1½" lag screw thru ¼" metal plate into bottom flange. Find: • What is maximum withdrawal capacity of lag screw? Solution: • From 2012 NDS® Table L2, the dimensions for a ¼" x 1½" lag screw are as follows: o H = 11/64" o L = 1 ½" o D = ¼" o Dr = 0.173" o S = ¼" o T - E = 1 3/32" o E = 5/32" Figure 1: ¼" x 1½" Lag Screw • From Table 2, the reference design withdrawal value is 225 lbs/in of thread penetration. • From Table 1, the flange thickness of a TJI® 230 joist is 1¼". • Determine the length of thread engaged in the flange: o Determine if the screw shank dimension, S, penetrates into the flange. In this example, the screw dimension "S" is the same as the metal side member, so the shank does not penetrate the main member. o Determine length of thread in the main member. Since the shank is not in the main member, the amount of thread in the main member is the dimension "T - E", 1 3/32". In this case, the flange thickness is greater than the "T - E" dimension (1¼" > 13/32"), so "T – E" is the length of thread engaged in the flange. Had the "T - E" dimension been greater than the flange thickness, the flange thickness would be used as the length of thread engaged. . • Lag screw capacity = 1 3/32" x 225 lbs/in = 245 lbs of withdrawal capacity. • Check end, edge, and spacing requirements per 2012 NDS®: o Minimum End Distance = 4D = 1" o Minimum Edge Distance = 1.5D = 3/8" o Minimum Spacing = 4D = 1" ,’Weyerhaeuser,’Forte,’Javelin,’Microllam,’Parallam,’Silent’Floor,’TimberStrand,’TJI,’TJ,’Trus’Joist,’Edge,’and’Edge’Gold’are’registered’trademarks’ and’TJ-Pro’is’a’trademark’of’Weyerhaeuser’NR.’©’2015’Weyerhaeuser’NR’Company.’All’rights’reserved. 1.888.453.8358 ● www.woodbywy.com Page 2 of 2