Fundamentals of HVAC Control Systems

advertisement
ASHRAE Hong Kong Chapter Technical Workshop
Fundamentals of HVAC
Control Systems
18, 19, 25, 26 April 2007
© 2007 ASHRAE Hong Kong Chapter
Slide 1
Chapter 3
Control Valves and Dampers
© 2007 ASHRAE Hong Kong Chapter
Slide 2
Control Valves
„
Important component of fluid distribution
systems
Š
„
Common types:
Š
Š
Š
„
Regulate the flow of fluid to the process under control
Globe valves (for modulating)
Ball valves (less expensive)
Butterfly valves (for isolation)
Valve material
Š
Bronze, cast iron, steel
© 2007 ASHRAE Hong Kong Chapter
Slide 3
Control valve components
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 4
2-Way and 3-Way Valve Circuits
2-way control valve
Mixing 3-way control valve
Diverting 3-way control valve
© 2007 ASHRAE Hong Kong Chapter
Slide 5
2-Way and 3-Way Valves
„
2-way: for variable flow
Š
More sensitive to high differential pressure
Š Harder to close off against line pressure
„
3-way: for constant flow
Š
Actuator does not need to be as powerful
© 2007 ASHRAE Hong Kong Chapter
Slide 6
Advantages of 2-Way Valves
„
„
„
„
„
Less expensive to buy and install
Result in variable flow which reduces
pumping energy
Reduced piping heat losses and pump
energy
Potentially lower costs for pumping and
distribution systems
System balancing is reduced or eliminated
© 2007 ASHRAE Hong Kong Chapter
Slide 7
Disadvantages of 2-Way Valves
„
„
Most chillers and some boilers cannot
handle widely varying flow rates
Differential pressures will increase across
control valves, reducing system
controllability
© 2007 ASHRAE Hong Kong Chapter
Slide 8
Normally Open 2-Way Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 9
Normally Closed 2-Way Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 10
Two-way globe valve application
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 11
Double-Seated 2-Way Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 12
Butterfly Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 13
Ball Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 14
Ball valve
Butterfly valve
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 15
Linear Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 16
Equal Percentage Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 17
Quick-Opening Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 18
Characteristics of Control Valves
„
Valve flow characteristics
Š
„
Relationship between the stem travel of a valve, expressed in
percent of travel, and the fluid flow through the valve,
expressed in percent of full flow
Typical flow characteristics
Š
Š
Š
Linear
Equal percentage
Quick opening
© 2007 ASHRAE Hong Kong Chapter
Slide 19
Typical Flow Characteristics
© 2007 ASHRAE Hong Kong Chapter
Slide 20
[Source: Shadpour, F., 2001. The Fundamentals of HVAC Direct Digital Control]
© 2007 ASHRAE Hong Kong Chapter
Slide 21
Flow coefficient:
AV = q
ρ
ΔP
q = volume flow (m3/s)
ρ= fluid density (kg/m3)
ΔP = static pressure loss across the valve (Pa)
For different units and locations, CV and KV are used.
For valve used in water application:
KV = Q
ρ
ΔP ⋅10
Q = volume flow (m3/h)
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 22
Control Valve Ratings
„
„
Flow coefficient
Close-off rating:
Š
„
Pressure drop:
Š
„
The maximum pressure drop that a valve can withstand
without leakage while in the full closed position
The difference in upstream and downstream pressures of the
fluid flowing through the valve
Maximum pressure and temperature:
Š
The maximum pressure and temperature limitations of fluid
flow that a valve can withstand
© 2007 ASHRAE Hong Kong Chapter
Slide 23
Location of Control Valves
„
At the outlet on the top of cooling/heating
coils
Š
Avoid coil starvation from water flow (lower pressure)
Š Flow of water from the bottom to the top (avoid air
bubble)
„
„
Flow measuring & balancing device
should be placed after the control valve
Provide a means of shut-off to allow a
proper means for servicing
© 2007 ASHRAE Hong Kong Chapter
Slide 24
[Source: Shadpour, F., 2001. The Fundamentals of HVAC Direct Digital Control]
© 2007 ASHRAE Hong Kong Chapter
Slide 25
3-Way Mixing Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 26
3-Way Diverting Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 27
Three-way valves
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 28
3-Way Mixing Valves
© 2007 ASHRAE Hong Kong Chapter
Slide 29
Flow Through 3-Way Valve
© 2007 ASHRAE Hong Kong Chapter
Slide 30
Selecting & Sizing Valves
Control valve selection depends on:
„ The fluid being controlled
„ Valve style: 2-way or 3-way
„ Control mode: modulating or 2-position
„ Maximum fluid temperature
„ Maximum inlet pressure
„ Desired flow characteristic
„ Maximum fluid flow rate
„ Desired pressure drop when valve is full open
„ Turn-down ratio
„ Close-off pressure
© 2007 ASHRAE Hong Kong Chapter
Slide 31
Coil Subsystem
© 2007 ASHRAE Hong Kong Chapter
Slide 32
Representative Values of Cv
© 2007 ASHRAE Hong Kong Chapter
Slide 33
Flow Characteristic Selection
The desired flow characteristic is a function
of:
„ The heat transfer device being controlled
and its flow versus capacity characteristic
„ The control of fluid supply temperature
„ The control of the differential pressure
across the valve
© 2007 ASHRAE Hong Kong Chapter
Slide 34
Capacity Versus Flow Rate
© 2007 ASHRAE Hong Kong Chapter
Slide 35
Authority Distortion of
Linear Flow Characteristic
© 2007 ASHRAE Hong Kong Chapter
Slide 36
Authority Distortion of Equal
Percentage Flow Characteristic
© 2007 ASHRAE Hong Kong Chapter
Slide 37
Pump & System Curves
With Valve Control
© 2007 ASHRAE Hong Kong Chapter
Slide 38
Control Dampers
„
For controlling air distribution, such as
Š
Fire damper: A thermally actuated damper arranged to
automatically restrict the passage of fire and/or heat at a
point where an opening violates the integrity of a fire
partition or floor
Š Smoke damper: A damper arranged to control passage
of smoke through an opening or a duct
Š Volume control damper (VCD): A device used to regulate
the flow of air in an HVAC system
© 2007 ASHRAE Hong Kong Chapter
Slide 39
Control Dampers
„
Common types:
Š
Š
Š
Š
Š
Opposed blade dampers (e.g. in AHU)
Parallel blade dampers
Butterfly dampers (e.g. in VAV box)
Linear air valves (e.g. in fume hood)
Specialty dampers
© 2007 ASHRAE Hong Kong Chapter
Slide 40
[Source: Shadpour, F., 2001. The Fundamentals of HVAC Direct Digital Control]
© 2007 ASHRAE Hong Kong Chapter
Slide 41
Typical Multiblade Dampers
© 2007 ASHRAE Hong Kong Chapter
Slide 42
Parallel blade damper
Opposed blade damper
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 43
Round damper
Volume control damper
(opposed blade)
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 44
Typical (opposed blade) damper construction
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 45
Externally mounted
pneumatic actuator
Internally mounted electric actuator
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 46
Damper Sizing
„
„
Typically chosen based on duct size and
convenience of location
Proper selection and sizing provides the
following benefits:
Š
Š
Š
Š
Š
Lower installation cost (damper sizes are smaller)
Smaller actuators or a fewer number of them are required
Reduced energy costs (smaller damper, less overall leakage)
Improved control characteristics (rangeability) because the
ratio of total damper flow to minimum controllable flow is
increased
Improved operating characteristics (linearity)
© 2007 ASHRAE Hong Kong Chapter
Slide 47
Performance Data
„
„
Leakage ratings
Torque requirements
Š
Closing torque
Š Dynamic torque
„
„
„
„
Velocity ratings
Temperature ratings
Pressure ratings
UL classification (fire/smoke)
© 2007 ASHRAE Hong Kong Chapter
Slide 48
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 49
Control loop for
a damper system
Resistance to airflow
in actual system
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 50
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 51
Mixed air control system (parallel blade dampers)
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 52
Mixed air system with louvers
[Source: Honeywell, 1997. Engineering Manual of Automatic Control: for Commercial Buildings]
© 2007 ASHRAE Hong Kong Chapter
Slide 53
Selecting and Sizing Dampers
The three basic damper applications are:
„ Two-position duty
„ Capacity control duty
„ Mixing duty
© 2007 ASHRAE Hong Kong Chapter
Slide 54
Fans in Parallel
© 2007 ASHRAE Hong Kong Chapter
Slide 55
Centrifugal Fan With
Inlet Vane Damper
© 2007 ASHRAE Hong Kong Chapter
Slide 56
Characteristic Curves of Parallel
Blade Dampers
© 2007 ASHRAE Hong Kong Chapter
Slide 57
Characteristic Curves of Opposed
Blade Dampers
© 2007 ASHRAE Hong Kong Chapter
Slide 58
Flow Pattern Through Dampers
© 2007 ASHRAE Hong Kong Chapter
Slide 59
Mixing Box Arrangements
© 2007 ASHRAE Hong Kong Chapter
Slide 60
Pressure Drop Across Mixing Box
© 2007 ASHRAE Hong Kong Chapter
Slide 61
Economizer With Supply
and Return Fans
© 2007 ASHRAE Hong Kong Chapter
Slide 62
VAV System at 100% Outdoor Air and
Minimum Outdoor Air
© 2007 ASHRAE Hong Kong Chapter
Slide 63
Economizer With Relief Fan
© 2007 ASHRAE Hong Kong Chapter
Slide 64
Download