48488D D7044M Installation Instructions.pmd

advertisement
D7044M
Installation Instructions
EN Multiplex Mini Single
Input Module
D7044M | Installation Instructions | Notices
Notices
These instructions cover the installation of the D7044M
Multiplex Mini Single Input Module in a fire system
supervised by a D7024 or DS9400M Fire Alarm
Control Panel (FACP) with firmware revision 2.0 or
greater and a D7039 or DS9431 Multiplex Expansion
Module.
Install, test, and maintain the D7044M according to
these instructions, NFPA 72, local codes, and the
Authority Having Jurisdiction (AHJ).
Follow the procedures in these instructions
to avoid personal injury and damage to the
equipment. Failure to follow these
procedures can cause the D7044M to not
operate properly. Bosch is not responsible
for improperly installed, tested, or maintained
devices.
Test the FACP according to NFPA 72.
Rotary switches (Item 3 in Figure 1) provide convenient
address setting.
An on-board Status LED, visible through the faceplate,
indicates normal operation and communication with the
control panel. The LED flash rates are:
•
Fast: Approximately 4 sec indicating an alarm
condition
•
Medium: Approximately 8 sec indicating normal
operation
•
Slow: Approximately 16 sec indicating a trouble
condition
The D7044M can be inserted in a standard single-gang
electrical box.
2.0
Setting the Address
Set the D7044M address using a single point screwdriver
to position each rotary switch located on the front
(Figure 2). Note that the switches click when turned.
Figure 2: Setting the Address
0
1.0
Description
The D7044M (Figure 1) is a general purpose module that
connects a contact device to the FACP’s multiplex bus
with a supervised input loop. All operating power for
the D7044M is drawn from the FACP.
Figure 1: D7044M Features
X
2
0 1 A
2
0
2 1 B
HUNDREDS
X X
9 0 1
8
2
3
7
6
4
5
9 0 1
8
2
3
7
6
4
5
TENS
ONES
3
1 - Status LED
2 - Wiring leads
2
A
2
0
1 B
2
1
0
1
9
2
8
3
7
6 5 4
2
0
1
9
2
8
3
7
6 5 4
3
1 - Hundreds
2 - Tens
3 - Ones
A = D7024 FACP, B = DS9400M FACP
For example:
0 hundreds, 9 tens, 5 ones = Address 095 on the
D7024 FACP
1
A = D7024
B = DS9400
1
3 - Rotary address switches
The valid D7044M address range is 9 to 255. Refer to
the D7024 Operation and Installation Guide (P/N: 31499)
or the DS9400M Reference Guide (P/N: 44578) for
additional address limitations.
The A address range works on the D7039
Multiplex Expansion Module with the D7024
FACP. The B address range works on the
DS9431 Multiplex Expansion Module with
the DS9400M FACP.
Figure 2 shows the A address range set at 095, allowing
the D7039 to work with the D7024 FACP.
Bosch | 10/04 | 48488D
D7044M | Installation Instructions | 5.0
3.0
Wiring
5.0
Remove all power before making electrical
connections. Failure to do so can result in
personal injury and damage to the
equipment.
Use normally-open (NO) contacts for
Underwriters Laboratories, Inc. (UL) Listed
fire installations.
Specifications
Table 1:
Specifications
Control Panel
Programming
Type
Control Panel
Requirements
The control panel loop and field wiring connections are
made using the flying wire leads on the D7044M
(Figure 3). All wiring is power limited and supervised.
Figure 3: Field Wiring Connections
5
1
2
6
1
7
2
3
4
1
2
3
4
5
6
7
-
Specifications
Multiplex Bus
Average
Current Draw
Operating
Temperature
Relative
Humidity
Listings and
Approvals
Single input
D7024 or DS9400M FACP with ROM
version 2.0 or greater and a D7039 or
DS9431 Multiplex Expansion Module
installed. Refer to the D7024 Operation
and Installation Guide
(P/N: 31499) or the DS9400M
Reference Guide (P/N: 44578) for
specific programming information.
Refer to the D7039 Installation Guide
(P/N: 38685) or the DS9431
Installation Guide (P/N: 41381) for
multiplex wiring information.
Alarm: 550 µA
Standby: 550 µA
Nominal: 12 V
+32°F to +120°F (0°C to +49°C)
93% non-condensing
UL864
California State Fire Marshall (CSFM)
MUX bus loop (+), red
MUX bus loop (-), black
Zone in (+) orange
Zone in (-) blue
To next device
From previous device, the D7039, or the DS9431
UL Listed 2.21 kΩ end-of-line (EOL) resistor
(P/N: 25899)
4.0
Installation
Complete all wiring connections before
inserting the D7044M into the single-gang
box.
1.
Install the D7044M into a single-gang box.
2. Place the D7044M inside the gang box and mount
the gang box according to its mounting instructions.
Bosch | 10/04 | 48488D
3
Bosch
130 Perinton Parkway
Fairport, NY 14450-9199 USA
Customer Service: (800) 289-0096
Technical Support: (888) 886-6189
© 2004 Bosch
48488D