Specification Grade GFCIs

advertisement
Specification Grade GFCIs
Specification Grade
Ground Fault Circuit
Interrupter Receptacles
1.30"
(33.0mm)
2-Pole, 3-Wire Grounding
15A, 125V/AC
20A, 125V/AC
NEMA 5-15, 5-20
4.19"
(106.4mm)
Hospital Grade GFCIs
Back Wire &
Side Wire
Description
3.28"
(83.3mm)
15A, 125V
NEMA 5-15R
426
Catalog No.
Color Suffix
Hospital GFCI
■ VGFH15___
Hospital GFCI
NAFTA Compliant
■ VGFH15F___
Tamper Resistant
Hospital GFCI
■ TRVGFH15___
Tamper Resistant
Hospital GFCI
NAFTA Compliant
■ TRVGFH15F___
20A, 125V
NEMA 5-20R
426
Catalog No.
Color Suffix
•
•
•
■ VGFH20___
B, GY, LA, RD, V, W
•
•
■ VGFH20F___
B, GY, LA, RD, V, W
•
•
■ TRVGFH20___
•
B, GY, LA, RD, V, W
•
VGFH15
•
B, GY, LA, RD, V, W
B, GY, LA, RD, V, W
•
•
■ TRVGFH20F___
B, GY, LA, RD, V, W
•
1.30"
(33.0mm)
•
•
•
•
B, GY, LA, RD, V, W
•
1.20"
(30.5mm)
•
•
4.19"
(106.4mm)
3.28"
(83.3mm)
B, GY, LA, RD, V, W
Includes standard size unbreakable wallplate
VGFH20_MOD
Depth with
ArrowLink
1.65"
(41.9mm)
1.30"
(33.0mm)
Specification Grade GFCIs
Back Wire &
Side Wire
Tamper Resistant
15A, 125V
NEMA 5-15R
Catalog No.
Color Suffix
Description
Duplex GFCI
■ VGF15___
20A, 125V
NEMA 5-20R
426
426
4.19"
(106.4mm)
Catalog No.
Color Suffix
•
•
A, B, BK, GY, LA, RD, V, W
■ VGF20___
A, B, BK, GY, LA, RD, V, W
3.28"
(83.3mm)
•
•
1.64"
(41.7mm)
Duplex GFCI
■ VGF15___-M
with Mid-Size Wallplate
A, LA, V, W
Duplex GFCI
NAFTA Compliant
■ VGF15F___
Tamper Resistant
Duplex GFCI
■ TRVGF15___
Tamper Resistant
Duplex GFCI with
Mid-Size Wallplate
■ TRVGF15___-M
Tamper Resistant
Duplex GFCI
NAFTA Compliant
■ TRVGF15F___
Weather Resistant
Duplex GFCI
■ WRVGF15___
Tamper & Weather
Resistant
Duplex GFCI
■ TWRVGF15___
TRVGFH15
•
•
•
■ VGF20F___
B, BK, GY, LA, RD, V, W
•
•
■ TRVGF20___
•
B, BK, GY, LA, RD, V, W
•
A, B, BK, GY, LA, RD, V, W
•
•
1.30"
(33.0mm)
•
A, B, BK, GY, LA, RD, V, W
4.19"
(106.4mm)
A, LA, V, W
3.28"
(83.3mm)
•
•
•
■ TRVGF20F___
B, BK, GY, LA, RD, V, W
•
•
•
B, BK, GY, LA, RD, V, W
TRVGF15_MOD
•
•
■ WRVGF20___
B, GY, V, W
•
Depth with
ArrowLink
1.65"
(41.9mm)
1.30"
(33.0mm)
•
B, GY, V, W
•
•
■ TWRVGF20___
B, GY, LA, V, W
•
•
Weather Resistant
B, GY, LA, V, W
Includes standard size unbreakable wallplate unless otherwise noted
Consult factory customer service representative for additional packaging options
4.19"
(106.4mm)
3.28"
(83.3mm)
Color Ordering Information
For ordering devices, include Cat. No. followed by the color code: A (Almond), B (Brown), BK (Black), GY (Gray),
LA (Light Almond), RD (Red), RN (Orange), V (Ivory), W (White)
Icon Key
1.20"
(30.5mm)
WRVGF15
TM
ArrowLink option available. Add "MOD" suffix to
Standard catalog number (example VGF15W,
VGF15WMOD). For ordering information on ArrowLink &
ArrowLink SPD connectors, see page G-2.
Hospital Grade
Build-To-Spec Customizable Devices - see page G-1
NAFTA Compliant - see page O-30
Tamper Resistant
Tamper Resistant
Weather Resistant
Weather Resistant
Tamper & Weather Resistant
Tamper & Weather Resistant
www.arrowhart.com
Specification Information:
Hospital Grade GFCI: G-12
Spec Grade GFCI: G-13
G-5
Specification Grade GFCIs
Specification & Performance Data
Specification Grade
Ground Fault Circuit
Interrupter Receptacles
Combined
Back & side wire
Integral wire leads, crimped & resistance welded
Backwire feed through
• cULus Listed to UL 498 and UL 943, file no. E60120
• Meets all UL 943 (GFCI), UL 498 (Receptacles) and applicable
CSA requirements
• NOM certified
• Plug & connector cULus Listed to to UL 2459, file no.
E325188
• cULus Listed wiring assembly, UL file no. E326691
Specification Grade Tamper Resistant & Weather Resistant
Duplex GFCI 15A & 20A; TRVGF, TRVGF__F, WRVGF, TWRVGF
Series, TRVGF___-AG
ArrowLink: MCR125_, MCR250_, MCR300_ Series
Back & side wire
Integral wire leads, crimped & resistance welded
Backwire feed through
• cULus Listed to UL 498 and UL 943, file no. E60120
• Meets all UL 943 (GFCI), UL 498 (Receptacles) and applicable
CSA requirements
• NOM certified
• Plug & connector cULus Listed to to UL 2459, file no.
E325188
• cULus Listed wiring assembly, UL file no. E326691
Flammability
Meets UL 94 requirements; V2 rated
Meets UL 94 requirements; V2 rated
Temperature Rating
-35ºC to 66ºC (-31ºF to 150.8ºF)
-35ºC to 66ºC (-31ºF to 150.8ºF)
Flammability
Meets UL 94 requirements; V2 rated
Meets UL 94 requirements; V2 rated
Temperature Rating
-35ºC to 66ºC (-31ºF to 150.8ºF)
-35ºC to 66ºC (-31ºF to 150.8ºF)
Dielectric Voltage
Current Interrupting
Withstands 2000V per UL 498
Yes, at full-rated current
Temperature Rise: max. 30ºC (86°F) after 100 cycles of overload
@ 150% of rated current (DC)
0.025 seconds (Class A)
60 Hz; Voltage: 125V; Amperage: 15A/20A 20A Feed Through
Meets and exceeds 10 kA
Voltage: withstands 2000V per UL 498
Yes, at full-rated current
Max. 30ºC (86°F) after 100 cycles of overload @ 150% of rated
current (DC)
0.025 seconds (Class A)
60 Hz; Voltage: 125V; Amperage: 15A/20A 20A Feed Through
Meets and exceeds 10 kA
20 Amps
20 Amps
300V/AC
20A
52.5A/AC for 10 cycles
Withstands 1600V per UL 2459
Limited cycles at full-rated current
Max. 50ºC (122°F) while conducting 35A after 10 cycles of
overload @ 52.5A/AC
300V/AC
20A
52.5A/AC for 10 cycles
Withstands 1600V per UL 2459
Limited cycles at full-rated current
Max. 50ºC (122°F) while conducting 35A after 10 cycles of
overload @ 52.5A/AC
#14 - #10 AWG
#14 - #10 AWG
#12 AWG
#12 AWG
Accepts #12-#14 stranded and solid wire
Accepts #12-#14 stranded and solid wire
Integral THHN #12 AWG 6" lead with ring terminal and #10
ground screw
Permanently marked on device
Integral THHN #12 AWG 6" lead with ring terminal and #10
ground screw
Permanently marked on device
ArrowLink Models Only
Material: UL recognized insulating material
Dielectric Strength: 2,000V min
HWI Rating: 4 min.
Relative temperature index, electrical: 80ºC (176ºF)
Flammability: V0 (UL 94)
Material: UL recognized insulating material
Dielectric Strength: 2,000V min
HWI Rating: 4 min.
Relative temperature index, electrical: 80ºC (176ºF)
Flammability: V0 (UL 94)
Top Housing
Bottom Housing
Strap
Line Contacts
Thermoplastic, nylon
PVC
0.047" thick steel, zinc plated
0.030" thick brass
Terminal & Ground
Screws
#8-32 steel, brass plated; neutral screw nickel plated, ground
screw green
Terminal Clamps
Housing
0.070" thick steel
Thermoplastic, nylon; except WR: nylon 6/6
PVC
0.047" thick steel, zinc plated; WR & TWR: nickel-plated
0.030" thick brass
Terminal: Brass/nickel-plated steel; WR & TWR brass/nickelplated stainless steel; Ground: ground screw green on all models,
WR and TWR stainless steel
Brass-plated steel; WR & TWR nickel-plated steel
Polycarbonate
Polycarbonate
Contacts
Copper alloy
Copper alloy
Wire Leads
Solid or stranded THHN #12 AWG
Solid or stranded THHN #12 AWG
Housing
Polycarbonate
Polycarbonate
Copper alloy
Copper alloy
Device Type
Base Device
ArrowLink
Base Device
Base
ArrowLink
Device
ArrowLink
Specifications:
Electrical
Specifications:
Environmental
Testing & Code
Compliance
Wiring
Type
Base Device
ArrowLink
ArrowLink SPD
Temperature Rise
Trip Time
Frequency
Short Circuit Testing
Maximum Interrupting
Capacity
Max. Working Voltage
Max. Continuous Current
Overload
Dielectric Voltage
Current Interrupting
Temperature Rise
Specifications:
Mechanical
Base Device Terminal
Accommodation
ArrowLink Wire Leads
ArrowLink SPD Screw
Terminals
ArrowLink SPD Ground
ArrowLink
ArrowLink
SPD
Base Device
Specifications:
Screw Terminal
Guards
Voltage Ratings
Materials:
2-Pole, 3-Wire Grounding
15A, 125V/AC; 20A, 125V/AC
NEMA 5-15, 5-20
Contacts
Specification Grade GFCI 15A & 20A
VGF and VGF__F Series, VGF___-AG*
ArrowLink: MCR125_, MCR250_, MCR300_ Series
*VGF___-AG not available with ArrowLink
www.arrowhart.com
G-13
Download