Technical Datasheet

advertisement
Modular GFCIs
Project Name:
Prepared By:
Project Number:
Date:
Catalog Number:
Type:
Ground Fault Circuit
Interrupters
2-Pole, 3-Wire Grounding
15A 125V
20A 125V
1.30"
(33.0mm)
Hospital & Specification Grade GFCIs
FEATURES
• ArrowLink modular plug and connector provide
high quality circuit connections and incorporate a
first make/last break grounding design.
• Wire leads are crimped and resistance welded
to plug and connector terminals for maximum
durability.
• Audible “click” when mating plug and connector
indicates proper assembly during final device
installation.
• Pre-wired plugs provide 100% inspected and
consistent torque settings for reliable connections
to base devices.
• Connectors shipped with re-usable protective
covering that allows circuit testing while
protecting the connection from foreign matter.
• Exclusive screw terminal guards provide a
protective barrier from conductive surfaces.
• Hospital Grade models UL Listed, fully compliant
with all latest UL943 (4th edition) Class A GFCI and
UL498 Hospital Grade requirements.
• Tamper Resistant models comply with 2008
NEC® Article 406.11 requiring all dwelling
unit receptacles to be tamper resistant.
• ShockSentry™ lock-out function prevents miswired
line-load connections and GFCI circuitry damage.
• Large visual indicator light provides quick visual
reference of a tripped or “end of life” condition.
• 20A feed through rating.
• Longer, wider “bridged” strap provides 40% more
contact area with wallboard, virtually eliminating
floating installations.
• Matching standard size thermoplastic wallplate
included.
Catalog No.
NEMA
5-15R
Description
Tamper Resistant GFCI
Modular Receptacle
Tamper Resistant
AVAILABLE
Q2 2009!
GFCI Modular Receptacle
20 125
5-20R
Tamper Resistant GFCI
Modular Receptacle
Tamper Resistant
3.28"
(83.3mm)
Tamper Resistant
Hospital Specification Grade – Back Wire and Side Wire
Rating
A V
15 125
4.19"
(106.4mm)
AVAILABLE
Q2 2009!
GFCI Modular Receptacle
C
I TRVGFH15___M
Available
Colors
LA, RD, W
I VGFH15___M
LA, RD, W
R
US
Depth with
ArrowLink
1.64"
(41.7mm)
VGFH20_M
1.30"
(33.0mm)
4.19"
(106.4mm)
Tamper Resistant
3.28"
(83.3mm)
426
TRVGF15_M
I TRVGFH20___M
B, GY, LA, RD, V, W
I VGFH20___M
B, GY, LA, RD, V, W
Depth with
ArrowLink
1.64"
(41.7mm)
1.42"
(36.1mm)
Lead
Length:
6.00”
(152.4mm)
0.40"
(10.2mm)
1.08"
(27.4mm)
Specification Grade – Back Wire and Side Wire
Rating
A V
15 125
Catalog No.
NEMA
5-15R
Description
Tamper Resistant GFCI
Modular Receptacle
Tamper Resistant
GFCI Modular Receptacle
20 125
C
5-20R
Tamper Resistant GFCI
Modular Receptacle
R
US
426
I TRVGF15___M
Available
Colors
A, B, BK, GY, LA, V, W
I VGF15___M
A, B, BK, GY, LA, V, W
I TRVGF20___M
A, B, BK, GY, LA, V, W
I VGF20___M
A, B, BK, GY, LA, V, W
Tamper Resistant
GFCI Modular Receptacle
For ordering, include Cat. No. followed by the color code: A (Almond), B (Brown), BK (Black), GY (Gray), LA (Light Almond), RD
(Red), V (Ivory), W (White)
ArrowLink Receptacle Connectors
C
Description
R
US
Receptacle
Connector
1.42"
(36.1mm)
0.40"
(10.2mm)
1.08"
(27.4mm)
Receptacle
Plug
G
Catalog No.
ArrowLink Modular Receptacle 125V Building Wire Connector, Solid Wire
I MCR125SOL
ArrowLink Modular Receptacle 125V Building Wire Connector, Stranded Wire
I MCR125STR
Patent Pending
W
5-15R
G
W
5-20R
For Specification & Performance
Data, see page 20.
TESTING & CODE COMPLIANCE
MATERIAL CHARACTERISTICS
• Base Device: cULus listed to UL498 and UL943, file no. E60120;
meets all UL943 (GFCI), UL498 (Receptacles) and applicable CSA
requirements; Hospital Grade versions also meet all UL498 Hospital
Grade requirements; NOM Certified
• ArrowLink: Plug & connector cULus Listed to UL2459 file no. E325188
• Combined: cULus Listed wiring assembly, UL file no. E326691
• Nylon & PVC with adhesive terminal barrier, except Hospital Grade: nylon &
polycarbonate
• Environmental, Base Device: Flammability meets UL 94 requirements; V2 rated;
temperature rating: -35ºC to 66ºC (-31ºF to 150.8ºF)
• Environmental, ArrowLink: Flammability meets UL 94 requirements; V2 rated;
temperature rating: -20ºC to 90ºC (-4ºF to 194ºF) max.
19
Modular GFCI Receptacles
Specification & Performance Data
Project Name:
Prepared By:
Project Number:
Date:
Catalog Number:
Type:
Ground Fault Circuit
Interrupters
2-Pole, 3-Wire Grounding
15A 125V
20A 125V
Application
GFCI receptacles are designed with the safety of the user in mind. In commercial and industrial areas like public bathrooms, breakrooms
and food service areas, the NEC® requires GFCI receptacles. Arrow Hart ArrowLink GFCI receptacles are UL Listed and fully compliant with
all of the latest UL943 (4th Edition) Class A GFCI and UL498 requirements. Additionally, ArrowLink GFCIs incorporate our ShockSentry™
lock-out function to protect against mis-wired line-load connections and GFCI circuitry damage. Safety barriers provide insulation from
conductive surfaces. Patent-pending modular plug and connector provide consistent high quality circuit connections and reduce overall
installation time on the job.
Receptacle Type
Wiring Type
Tamper Resistant Hospital Grade GFCI Duplex
Receptacle TRVGFH15_M, TRVGFH20_M Series;
Hospital Grade GFCI Duplex Receptacle VGFH15_M,
VGFH20_M Series; ArrowLink: MCR125_Series
Tamper Resistant
Base Device: Back & side wire
ArrowLink: Integral wire leads, crimped & resistance welded
Testing & Code Compliance
Base Device
• cULus listed to UL498 and UL943, file no. E60120
• Meets all UL943 (GFCI), UL498 (Receptacles), UL498 Hospital
Grade and applicable CSA requirements
• NOM Certified
Tamper Resistant
Base Device: Back & side wire
ArrowLink: Integral wire leads, crimped & resistance welded
• cULus listed to UL498 and UL943, file no. E60120
• Meets all UL943 (GFCI), UL498 (Receptacles) and applicable CSA
requirements
• NOM Certified
ArrowLink
• Plug & connector cULus Listed to UL2459 file no. E325188
• Plug & connector cULus Listed to UL2459 file no. E325188
Combined
• cULus Listed wiring assembly, UL file no. E326691
• cULus Listed wiring assembly, UL file no. E326691
Flammability meets UL 94 requirements; V2 rated
Temperature rating: -35ºC to 66ºC (-31ºF to 150.8ºF)
Flammability meets UL 94 requirements; V2 rated
Temperature rating: -35ºC to 66ºC (-31ºF to 150.8ºF)
Environmental,
ArrowLink
Flammability meets UL 94 requirements; V2 rated
Temperature rating:-20ºC to 90ºC (-4ºF to 194ºF) max.
Flammability meets UL 94 requirements; V2 rated
Temperature rating: -20ºC to 90ºC (-4ºF to 194ºF) max.
Electrical, Base Device
Dielectric Voltage: withstands 2000V per UL498
Temperature Rise: max. 30ºC (86°F) after 100 cycles of overload @
150% of rated current (DC)
Trip Time: .025 seconds (class A)
Frequency: 60 Hz; Voltage: 125 V; Amperage: 15A/20A
20A Feed Thru
Maximum Interrupting Capacity: 20 amps
Current interrupting: yes, at full-rated current
Dielectric Voltage: withstands 2000V per UL498
Temperature Rise: max. 30ºC (86°F) after 100 cycles of overload @
150% of rated current (DC)
Trip Time: .025 seconds (class A)
Frequency: 60 Hz; Voltage: 125 V; Amperage: 15A/20A
20A Feed Thru
Maximum Interrupting Capacity: 20 amps
Current interrupting: yes, at full-rated current
Electrical, ArrowLink
Maximum working voltage 300V / AC
Overload: 52.5A / AC for 10 cycles
Temperature Rise: Max. 50ºC (122°F) while conducting 35A after 10
cycles of overload @ 52.5A / AC
Dielectric Voltage: withstands 1600V per UL2459
Maximum continuous current: 20A
Current interrupting: limited cycles at full-rated current
Maximum working voltage 300V / AC
Overload: 52.5A / AC for 10 cycles
Temperature Rise: Max. 50ºC (122°F) while conducting 35A after 10
cycles of overload @ 52.5A / AC
Dielectric Voltage: withstands 1600V per UL2459
Maximum continuous current: 20A
Current interrupting: limited cycles at full-rated current
Mechanical
Base Device Terminal Accommodation: #14 - #10 AWG
ArrowLink Wire Leads: #12 AWG
Voltage ratings permanently marked on device
Base Device Terminal Accommodation: #14 - #10 AWG
ArrowLink Wire Leads: #12 AWG
Voltage ratings permanently marked on device
Screw Terminal Guards
Material: UL Recognized Insulating Material
Dielectric Strength: 2,000V Min
HWI Rating: 4 Min.
Relative Temperature Index, Electrical: 80ºC (176ºF)
Flammability: V0 (UL94)
Material: UL Recognized Insulating Material
Dielectric Strength: 2,000V Min
HWI Rating: 4 Min.
Relative Temperature Index, Electrical: 80ºC (176ºF)
Flammability: V0 (UL94)
Specifications:
Environmental,
Base Device
Materials
Top Housing
20
Tamper Resistant Specification Grade GFCI Duplex
Receptacle: TRVGF15_M, TRVGF20_M Series;
Specification Grade GFCI Duplex Receptacle:
VGF15_M, VGF20_M Series; ArrowLink: MCR125_ Series
Thermoplastic, nylon
Thermoplastic, nylon
Bottom Housing
Polycarbonate
PVC
Strap
0.047" thick steel, zinc plated
0.047" thick steel, zinc plated
Terminals
Brass
Brass
Terminal & Ground
Screws
#8-32 steel, brass plated; neutral screw nickel plated, ground screw
green
#8-32 steel, brass plated; neutral screw nickel plated, ground screw
green
ArrowLink Housing
Polycarbonate
Polycarbonate
ArrowLink Contacts
Copper alloy
Copper alloy
ArrowLink Wire Leads
Solid or stranded THHN #12 AWG
Solid or stranded THHN #12 AWG
Download