5/4/2009 Three Phase Transformers Three Phase Transformers Theory and Calculations Copyright 1999-2008 Dan Dudley Three Phase Transformers DELTA Transformer Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers WYE Transformer Copyright 1999-2008 Dan Dudley Three Phase Transformers Voltage and Current in a Delta Transformer Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Voltage and Current in a WYE Transformer Copyright 1999-2008 Dan Dudley Three Phase Transformers D–V W-I • D = Delta configuration • V = Volts • W = Wye configuration • I = Current Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Delta – Volts are Equal 9 Delta Configuration Transformer – Voltage is EQUAL Phase and Line ¾The Phase Voltage = Line Voltage – Current is NOT EQUAL ¾Phase Current = Line Current / 1.732 ¾Line Current = Phase Current X 1.732 – D V W I , Phase Divide, Line Multiply, by 1.732 Copyright 1999-2008 Dan Dudley Three Phase Transformers Wye – Current is Equal 9 Wye Configuration Transformer • Current is EQUAL Phase and Line ¾ The • Phase Voltage = Line Voltage Voltage is NOT EQUAL ¾ Phase Voltage = Line Voltage / 1.732 ¾ Line Voltage = Phase Voltage X 1.732 D V W I , Phase Divide, Line Multiply, by 1.732 Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers DELTA Configuration WYE (“Y”) Configuration Copyright 1999-2008 Dan Dudley Three Phase Transformers Ratio of Transformation Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers (4) (1) (2) (3) 1. Primary Line 2. Primary Phase 3. Secondary Phase Core 4. Secondary Line Copyright 1999-2008 Dan Dudley Three Phase Transformers 230 V 6.25 amps 6.25 amps X 25 amps What is the Primary Line voltage of a Delta-Wye connected transformer with a secondary line voltage of 230 volts, secondary line current of 25 amps, and primary line current of 6.25 amps Answer •1. Ratio Primary amps / Secondary amps = 25/6.25 = 4 •2. Secondary Line to Secondary Phase 230 / 1.732 = 132.8v •3. Primary Phase volts using ratio = 132.8 X 4 = 531.2 volts •4. Delta Phase Volts = Line Volts = 531.2 volts Primary Line Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers 1920 V 125 amps 15.6 amps What is the Secondary Line voltage of a Delta-Wye connected transformer with a Primary line voltage of 1920 volts, secondary line current of 125 amps, and primary line current of 15.6 amps Answer 1. Ratio Primary amps / Secondary amps = 125/15.6 = 8 2. Primary Line to Primary Phase 1920v = 1920v Primary Phase 3. Secondary phase using ratio = 1920 / 8 = 240 volts 4. Wye Line Volts = Phase Volts X 1.732 = 415.68 volts Sec Line Copyright 1999-2008 Dan Dudley Three Phase Transformers 7200v 480v 26 a X What is the Secondary Line Current of a Delta-Wye connected transformer with a Primary line voltage of 7200 volts, secondary line voltage of 480, and primary line current of 26 amps Answer 1. Ratio Primary volts / Secondary volts = 7200/480 = 15 2. Pri Line amps to Pri Phase amps = 26 / 1.732 = 15.01 amps 3. Sec phase amps using ratio = 15 X 15.01 = 225.17 amps 4. Wye Line amps = Phase amps = 225 amps Sec Line Current Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers 120 V 1440 V 140 amps What is the Primary Line current of a Delta-Wye connected transformer with a secondary line voltage of 120 volts, secondary line current of 140 amps, and primary line voltage of 1440 volts. Answer 1. Ratio Primary volts / Secondary volts = 1440/120 = 12 2. Secondary Line to Secondary Phase 140 = 140a (Wye =) 3. Primary Phase current using ratio = 140 / 12 = 11.66 amps 4. Delta Line Current = 11.66a X 1.732 = 20.20 amps Pri Line Delta Copyright 1999-2008 Dan Dudley Three Phase Transformers Making a Delta out of a Wye Open these to make a WYE a Delta Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Three Phase example #1 Secondary Phase amps for a WYE CONNECTED TRANSFORMER, 480 V, 45 AMP, are ? Phase Amps = Line Amps (Wye) Copyright 1999-2008 Dan Dudley Three Phase Transformers Three Phase example #2 Phase volts for a 3 phase transformer are 208 v, what is the line voltage connected Wye ? Line Volts = Phase Volts X 1.732 208 X 1.732 360.256 Volts Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Three Phase example #3 Phase Current for a Delta connected transformer, 480 v, 45 kva, with 20 amps on the line are ? Phase Amps = Line amps / 1.732 20 / 1.732 11.547 amps Copyright 1999-2008 Dan Dudley Three Phase Transformers Three Phase Fault Current Calculation Transformer: 3phase, 265 kva, 208/120 volt with 2.5% impedance I = W / E (no Power Factor W = VA 3 Phase use 1.732 I - 3 phase = VA / E X 1.732 Convert K (Kilo) by dividing by 1000 Whatever your Impedance simply Divide it into 100 Do this calc first 265,000 / 208 X 1.732 265,000 / 360.256 735.58802 Multiplier = 100 / 2.5 = 40 736 amps X 40 = 29,440 amps fault current Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Service Entrance Raceway & Conductors NESC HIGH LEG PHASE “C” Meter Base NEC 230.56 & 215.8 HIGH LEG – PHASE “B” Service Equipment Feeder CB HIGH LEG Phase “B” 408.3(E) 215.8 Feeder Circuit Grounding Electrode Conductor The HIGH LEG IS ALWAYS Electrical Equipment ORANGE Copyright 1999-2008 Dan Dudley Three Phase Transformers NEC – Phase Arrangement • 408.3(E) –A – B – C • Front to Back • Top to Bottom • Left to Right –Higher Voltage to Ground • B Phase – Center Phase Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Open Delta System 1. Requires 3 transformers 2. Advantage: 3 phase power 3. Disadvantage: Reduced capacity Approx: 58% of total Copyright 1999-2008 Dan Dudley Three Phase Transformers You can derive two (2) Different voltages from this Transformer 120 volts and 208 volts Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers You can derive three (3) Different voltages from this Transformer 120, 208 and 240 volts This transformer configuration Is also called a “Center Tapped Delta” Copyright 1999-2008 Dan Dudley Three Phase Transformers Delta - Wye Transformer Connection L1 L2 L3 N L1 L2 L3 Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Delta - Delta Transformer Connection L1 L2 L3 N L1 L2 L3 Copyright 1999-2008 Dan Dudley Three Phase Transformers Wye - Wye Transformer Connection N L1 L2 L3 N L1 L2 L3 Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Wye - Delta Transformer Connection N L1 L2 L3 N L1 L2 L3 Copyright 1999-2008 Dan Dudley Three Phase Transformers Three Phase Transformer Exam 12 Questions 30 Minutes Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Three Phase Answers 1. B Equal to Line Amps = Phase Amps 2. A 51.96 Amps Ratio = 480 / 120 = 4 120 / 4 = 30 Amps 30 Amps X 1.732 = 51.96 Amps 3. C 120.09 V Line Volts / 1.732 = Phase Volts 208 / 1.732 = 120.09 V Copyright 1999-2008 Dan Dudley Three Phase Transformers Three Phase Answers 4. D Are Equal To 5. A 3.23 Amps Phase Amps = Line Amps / 1.732 Phase Amps = 5.6 amps / 1.732 Phase Amps = 3.23 Amps 6. A Wye three phase, 4 wire Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley 5/4/2009 Three Phase Transformers Three Phase Answers 7. A 108.25 I – 3phase = VA / E X 1.732 45000 / 240 X 1.732 = 108.25 8. B 5,412 Amps 100 / 2% impedance = 50 108.25 X 50 = 5,412.5 amps 9. A A,B,C left to right 408.3(a) 10. C 35000 450.23(A)(1)(a) 11. D 3 hours 450.43(A) 12. D 450.45(E) Copyright 1999-2008 Dan Dudley Copyright 2000-2007 Dan Dudley