ground bar 2-hole lug termination cable tray wall penetration cable

advertisement
1
2
3
4
5
US Army Corps of
Engineers ®
RATED WALL PENETRATION. 1
HOUR FIRE/SMOKE OR GREATER
#6 GRN OR #2 GRN
2 HOLE LUG
M. MOHAMMED HADIJI, P.E.
TX LICENSE #79548.
1/4-20 HEX BOLT
1/4" FLAT WASHER
D
1/4" EXT. TOOTH
LOCKWASHER
PRIMARY GROUND BAR/
METAL ENCLOSURE
SAVANNAH
1/4-20 HEX NUT
PROVIDE SUPPORTS
WITHIN 12" OF WALL
ON BOTH SIDES
PACK WITH FIRE
SAFING AFTER CABLE
INSTALLATION
4" STRAP TO TRAY
06 JUNE 2014
874 Dixon Boulevard
Cocoa, FL 32922
4" SLEEVE (TYPICAL
FOR ALL SLEEVES)
Phone: 321-636-0274
Fax: 321-639-8986
www.tlc-engineers.com
© Copyr ight 2 014 TL C Engi neerin g for
Architecture, Inc.
TLC NO:
GROUND WIRE.
MINIMUM #6 COPPER
TO CABLE TRAY
INSTALLATION NOTES:
A. SELECT BOLT LENGTH TO PROVIDE A MINIMUM OF TWO EXPOSED THREADS.
B. BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG
CONTACT.
C. APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE
CLEAN EXCESS COMPOUND.
CABLE TRAY, REFER
TO DRAWINGS FOR
EXACT SIZE AND TYPE
NOTE: CENTER HUNG CABLE
TRAY IS NOT ALLOWED.
6"
PROVIDE NUMBER OF SLEEVE AS
REQUIRED TO MATCH CABLE TRAY
CROSS SECTIONAL AREA. UL W-L 3112
D. USE SOLID COPPER WIRE AND MECHANICAL 2-HOLE LUG FOR ALL EXTERIOR
GROUNDING.
C
JWR
APPR
CABLE TRAY MINIMUM CLEARANCES.
1
REVISED IN ACCORDANCE WITH RFP LETTER_R2
MARK
DESCRIPTION
#6 OR #2 GRN TO GROUND BAR OF FLAT SURFACE.
#6 IS USED PRIMARILY AS CABINET TO BUS LINK.
PROVIDE APPROPRIATE
FIRE SAFING AT SLEEVE
PENETRATIONS OF RATED
WALLS
18 JUL 14
DATE
4" EMT CONNECTOR
WITH GROUNDING
BOND BUSHING
513071
BASKET TYPE CABLE
TRAY. DIMENSIONS AS
SHOWN ON FLOOR PLANS.
6"
12"
2"
GROUND BAR 2-HOLE LUG TERMINATION
NO SCALE
T-504
NOTES:
GROUND BUS BAR
ISOMETRIC ELEVATION
CPI 10622-012
OR EQUAL
A1
T-504
T-504-
A
L
H
GT
N
E
12" CLEAR ABOVE
WI
DT
H
WALL BRACKET
TGB-XXX
PROVIDE WHITE CORE
BAKELITE NAMEPLATE
FASTENED TO A
WALL/SURFACE BELOW
BUSBAR AT EACH FLOOR, WITH
STANDOFF DESIGNATION ENGRAVED
THEREON IN 1/2" HIGH LETTERS.
BRACKET
CPI 10622-000
NO SCALE
PLOT DATE:
7/17/2014 10:22:37 AM
PLOT SCALE:
NOT TO SCALE
UNIVERSAL TUBULAR RUNWAY SYSTEM
INSULATOR
GROUND BUS BAR (TYPICAL FOR ALL TR'S)
SIZE:
22" x 34"
3. INCREASE LENGTH OF
BUSBAR, FOR NUMBER
OF CONNECTIONS, AS
REQUIRED TO MAINTAIN
CORRECT SPACING
BETWEEN LUGS.
DESIGN BY:
TLC
A
A3
T-504
TUBULAR RUNWAY / LADDER RACK IN TR'S
NO SCALE
A4
T-504
CABLE TRAY WALL MOUNTED
NO SCALE
TELECOMMUNICATIONS DETAILS
PROVIDE # 6 COPPER CABLE 2-HOLE
LUG CLAMP FOR CABLE CONNECTION.
(TYP)
FRONT VIEW
2-HOLE LUG
(TYP)
#6 COPPER TO
NEXT SECTION
CATEGORY CODE:
730-46-04
CKD BY:
MMH
B
2. BUSBAR SHALL BE 1/4"
THICK (MINIMUM).
CPI 10622-012 OR
EQUAL
WALL
FILE NAME:
NJMT-504.DWG
CABLE RUNWAY
RADIUS DROP
4222 85th Street
Lubbock, Texas 79423
806.473.2200
GENERAL NOTES:
1. ALL HARDWARE (BOLTS,
NUTS, WASHERS,ETC.)
SHALL BE SOLID COPPER
OR BRONZE. COPPER
PLATING SHALL NOT BE
ACCEPTABLE.
ISSUE DATE:
06 June 2014
INSULATOR (TYP)
4"
B
THREADED ROD
TO STRUCTURE
"A" MEASURED FROM END OF STRINGER TO MIDDLE
OF CROSS SLAT.
"B" MEASURED FROM MIDDLE OF CROSS SLATS.
CONTRACT NO.:
-----
INSULATOR MOUNTING
BRACKET (TYP.) CPI
10622-000
NO SCALE
SUBMITTED BY:
Parkhill, Smith & Cooper, Inc.
12"
T-504
SOLICITATION NO.:
W91278-14-X-CV02
PROVIDE GROUNDING
CONDUCTOR TO MAIN
SERVICE GROUND POINT
PER TIA-607-B. 1
NO SCALE
CABLE TRAY
DWN BY:
CVM
PROVIDE GROUNDING
CONDUCTOR TO BUILDINGS
STEEL PER TIA-607-B.
1
C4
U.S. ARMY ENGINEER
DISTRICT
CORPS OF ENGINEERS
SAVANNAH DISTRICT
T-504
CABLE TRAY WALL PENETRATION
C3
WHITE ELEMENTARY SCHOOL REPLACEMENT
FORT BENNING, GEORGIA
C1
PLATE
REFERENCE
NUMBER
T-504
SHEET
603