1 2 3 4 5 US Army Corps of Engineers ® RATED WALL PENETRATION. 1 HOUR FIRE/SMOKE OR GREATER #6 GRN OR #2 GRN 2 HOLE LUG M. MOHAMMED HADIJI, P.E. TX LICENSE #79548. 1/4-20 HEX BOLT 1/4" FLAT WASHER D 1/4" EXT. TOOTH LOCKWASHER PRIMARY GROUND BAR/ METAL ENCLOSURE SAVANNAH 1/4-20 HEX NUT PROVIDE SUPPORTS WITHIN 12" OF WALL ON BOTH SIDES PACK WITH FIRE SAFING AFTER CABLE INSTALLATION 4" STRAP TO TRAY 06 JUNE 2014 874 Dixon Boulevard Cocoa, FL 32922 4" SLEEVE (TYPICAL FOR ALL SLEEVES) Phone: 321-636-0274 Fax: 321-639-8986 www.tlc-engineers.com © Copyr ight 2 014 TL C Engi neerin g for Architecture, Inc. TLC NO: GROUND WIRE. MINIMUM #6 COPPER TO CABLE TRAY INSTALLATION NOTES: A. SELECT BOLT LENGTH TO PROVIDE A MINIMUM OF TWO EXPOSED THREADS. B. BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG CONTACT. C. APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE CLEAN EXCESS COMPOUND. CABLE TRAY, REFER TO DRAWINGS FOR EXACT SIZE AND TYPE NOTE: CENTER HUNG CABLE TRAY IS NOT ALLOWED. 6" PROVIDE NUMBER OF SLEEVE AS REQUIRED TO MATCH CABLE TRAY CROSS SECTIONAL AREA. UL W-L 3112 D. USE SOLID COPPER WIRE AND MECHANICAL 2-HOLE LUG FOR ALL EXTERIOR GROUNDING. C JWR APPR CABLE TRAY MINIMUM CLEARANCES. 1 REVISED IN ACCORDANCE WITH RFP LETTER_R2 MARK DESCRIPTION #6 OR #2 GRN TO GROUND BAR OF FLAT SURFACE. #6 IS USED PRIMARILY AS CABINET TO BUS LINK. PROVIDE APPROPRIATE FIRE SAFING AT SLEEVE PENETRATIONS OF RATED WALLS 18 JUL 14 DATE 4" EMT CONNECTOR WITH GROUNDING BOND BUSHING 513071 BASKET TYPE CABLE TRAY. DIMENSIONS AS SHOWN ON FLOOR PLANS. 6" 12" 2" GROUND BAR 2-HOLE LUG TERMINATION NO SCALE T-504 NOTES: GROUND BUS BAR ISOMETRIC ELEVATION CPI 10622-012 OR EQUAL A1 T-504 T-504- A L H GT N E 12" CLEAR ABOVE WI DT H WALL BRACKET TGB-XXX PROVIDE WHITE CORE BAKELITE NAMEPLATE FASTENED TO A WALL/SURFACE BELOW BUSBAR AT EACH FLOOR, WITH STANDOFF DESIGNATION ENGRAVED THEREON IN 1/2" HIGH LETTERS. BRACKET CPI 10622-000 NO SCALE PLOT DATE: 7/17/2014 10:22:37 AM PLOT SCALE: NOT TO SCALE UNIVERSAL TUBULAR RUNWAY SYSTEM INSULATOR GROUND BUS BAR (TYPICAL FOR ALL TR'S) SIZE: 22" x 34" 3. INCREASE LENGTH OF BUSBAR, FOR NUMBER OF CONNECTIONS, AS REQUIRED TO MAINTAIN CORRECT SPACING BETWEEN LUGS. DESIGN BY: TLC A A3 T-504 TUBULAR RUNWAY / LADDER RACK IN TR'S NO SCALE A4 T-504 CABLE TRAY WALL MOUNTED NO SCALE TELECOMMUNICATIONS DETAILS PROVIDE # 6 COPPER CABLE 2-HOLE LUG CLAMP FOR CABLE CONNECTION. (TYP) FRONT VIEW 2-HOLE LUG (TYP) #6 COPPER TO NEXT SECTION CATEGORY CODE: 730-46-04 CKD BY: MMH B 2. BUSBAR SHALL BE 1/4" THICK (MINIMUM). CPI 10622-012 OR EQUAL WALL FILE NAME: NJMT-504.DWG CABLE RUNWAY RADIUS DROP 4222 85th Street Lubbock, Texas 79423 806.473.2200 GENERAL NOTES: 1. ALL HARDWARE (BOLTS, NUTS, WASHERS,ETC.) SHALL BE SOLID COPPER OR BRONZE. COPPER PLATING SHALL NOT BE ACCEPTABLE. ISSUE DATE: 06 June 2014 INSULATOR (TYP) 4" B THREADED ROD TO STRUCTURE "A" MEASURED FROM END OF STRINGER TO MIDDLE OF CROSS SLAT. "B" MEASURED FROM MIDDLE OF CROSS SLATS. CONTRACT NO.: ----- INSULATOR MOUNTING BRACKET (TYP.) CPI 10622-000 NO SCALE SUBMITTED BY: Parkhill, Smith & Cooper, Inc. 12" T-504 SOLICITATION NO.: W91278-14-X-CV02 PROVIDE GROUNDING CONDUCTOR TO MAIN SERVICE GROUND POINT PER TIA-607-B. 1 NO SCALE CABLE TRAY DWN BY: CVM PROVIDE GROUNDING CONDUCTOR TO BUILDINGS STEEL PER TIA-607-B. 1 C4 U.S. ARMY ENGINEER DISTRICT CORPS OF ENGINEERS SAVANNAH DISTRICT T-504 CABLE TRAY WALL PENETRATION C3 WHITE ELEMENTARY SCHOOL REPLACEMENT FORT BENNING, GEORGIA C1 PLATE REFERENCE NUMBER T-504 SHEET 603